This document contains technical drawings and specifications for electrical equipment at the Blue Mesa Powerplant. The drawings depict a single-line diagram of the station service, bus, and generator breaker layout. Protective relays, meters, switches and other devices are shown along with notes describing locations and functions. The related opportunity is a solicitation by the Bureau of Reclamation seeking a contractor to provide station service, bus, and unit breakers for the Blue Mesa Powerplant. The solicitation number is 140R4020R0006 and is for equipment to replace aging infrastructure at the facility.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
431- GM
REVISED AND REDRAWN
G.H.B.-J.J.K.
L.L.M.
W.N.P.
W.H. CLARK
J.V. BAPTIST
O.L. RICE
6-16-71
D-MEK
AS BUILT BY 431, LTR. 6-11-71
C
A
B
C
B A R
A
GENERATORS
115 KV. MAIN BUS 11.5 KV. BUS
C
A
115 KV. LINES
PHASE RELATIONSHIP-
SECONDARY POTENTIALS
SYN.
SS & 83
6A(CCA)
10A
TD
1BD
1DQ
1-12,000-120V
( A-B)
3Y-3000-5A
U1A
3Y-5000-5A
2 -12,000-120V
20A
TD
SYN.
SS & 83
U2A
2BD
1 E
KRB KRCC
A
B
C
B A
1-3 -1000KVA
12.0 KV.-480Y/277V.
± ±H.V. TAPS 2 1/2 & 5%
52A 52B
3Y-400-
5A
D1A
STATION SERVICE
ELECTRICAL INTER-
LOCK
6A(CCA)
6A
LG
I
VM
I
A3
S W
1-300G-B
L L
I
V
I
V
I
F
SYN
15 25
FROM SYN. CKTS.
S W
RUN IN
SYNCHRONIZING
EQUIPMENT
1MQ
1DNQ
A
GLQ
GL
TG
TP
71Q
LT
LOWER GUIDE BEARING
TURBINE GUIDE BEARING
TURBINE PACKING BOX
REC
T 11 STATOR
RTD'S
TO RTDS
ON KRA
GT1
GT2
GTQ
GU
QBH
QBN
QBL
UPPER GUIDE
BEARING
THRUST
BEARING
G
1 ,100 KVA
12 KV-120/240V.
K1A
GENERATOR G1
3 -48,000 KVA-11.5 KV.
0.9 PF, 200 R.P.M.
I
A
1RQ
3Y-3000-5A
1-3000-5A- A
G
RPM
RPM
BHM
(A1A)
(CCA)
(A1A)
SSG
K2A
S A M E
A S
S H O W N
F O R
U N I T
GATE LIMIT POS. (Each Unit) Selective Digital Readout
RESERVOIR LEVEL
Selective Digital Readout and Data Logging
TAILWATER LEVEL
Selective Digital Readout and Data Logging
TURBINE DISCHARGE
Selective Digital Readout (Each Unit)(C.F.S.)
and Data Logging (Total two units)(Acre Ft.)
SPILLWAY GATES No. 1 and 2
POSITION
Selective Digital Readout
1. YOU MUST LOOK AT THE 3-LINE DIAGRAMS TO FULLY UNDERSTAND THE RELAYING.
2. This plant is provided with LOCAL MANUAL, LOCAL AUTOMATIC, and REMOTE
AUTOMATIC controls for starting and stopping each unit.
3. Governor oil pumps, transformer cooling equipment and air compressor systems will be left in continuous service except for prolonged shutdown periods.
All other unit auxiliaries are taken out of service automatically when unit is shutdown.
4. May be combined by switching potentials.
GENERAL NOTES
Devices are located according to the following designations:
A1A - Governor H1 - Turbine Pit
BCA - Battery Control Board H1A - Generator Gage Board
C1A - Excitation Cubicle H1B - Butterfly Valve Cabinet
CCA - Main Control Board KRA - Main Transformer
E - Associated Equipment U1A - Unit 1 Generator Breaker (52)
G1 - Generator U2A - Unit 2 Generator Breaker (52)
CCB - Supervisory Control Board
TABLE OF PROTECTIVE RELAYS
DEVICE NO. G.E. W'HSE RATING
40F
46E
49G
51GB
51ST
51V
50/51E
59I
59G
59F
59VHZ
59T
64G
64F
87B1,2,3,4
OFFSET MHO
3-5A 7-15% ALARM, 10 SEC. TIME DELAYCOQ
CEH51A1A
C
A
B
C
B A
1-3 -1000KVA
12.0 KV.-480Y/277V.
±H.V. TAPS 2 1/2 &
±5%
STATION SERVICE SWGR.
FOR COMPLETE 1-LINE DIAGRAM
SEE DWG. 622-D-837
OTHER TELEMETERING TO PAGE
B0
DEVICE NOTES
Unless otherwise noted all symbols and device function numbers are in accordance with ASA Standard Y32.2 and C37.2. Devices not listed under
"Explanation" are located on Main Control Board unless otherwise noted.
For Unit 2, the number "1" in location designation is changed to 2.
TD
STATIC EXCITER
I
TD
WATT
TD
VAR
TD
V
TD
I
TM
(H1A)
ATLAS
W/WH
TD
PLANT
RECORDERS
SCADA TO
PAGE DISPATCH
FREQ
TD
UNIT 2 DATA
3 -11500-508
615 KVA
1-
1-300G-A
1-300G-B
40E
50/51 E
46E
CO-9
CO-9
COV-9
SVF
CO-2
CA
HU
4-16A., INST.,2-6A. V.I.
INDEPENT. OF FREQ.
55-140V., FREQ. COMP.
67V.
2-6A,V.I. 10-40A INST.
0.5-2.5A,V.I., 10-40A INST.
MAIN SINGLE LINE DIAGRAM -- SHEET 2 OF 2................622-D-836b
SWITCHYARD SINGLE LINE................................WAPA BM 0005
F
TO 115KV SWITCHYARD
(WAPA DWG. NO. BM 0005)
51GB.......CCA...Ground backup relay
51ST.......CCA...Station service overcurrent relay
51V........CCA...Overcurrent relay, voltage restrained
50/51E.....C1A...Exciter phase current (Time/Inst) 52.........U1A...Generator A.C. power circuit breaker
59I-T......CCA...Overvoltage relay, time delay, instantaneous, and frequency compensated
59F........C1A...Field undervoltage relay
59G........C1A...Generator overvoltage relay
59VHZ......C1A...Generator volts/Hz relay
REFERENCE DRAWINGS
12IJC51E2A 115-150%
12IFC53BD2A 2-50A
12IFV71BD2A 120-280V .2-2.0A
87G
87T
CV-8
CV-25
4-12A., SHORT TIME
10% SLOPE
30% SLOPE
12PJV11BK 280-580V
12STV11A5A 120V/60Hz 1.8-2.5/V/Hz
12PJG12B 120VAC
10-29-93
TO CT CKT
(WAPA DWG. NO. BM 5507)
TO FUSE FV1A
(WAPA DWG. NO. BM 0005)
64F........C1A...Generator field ground relay
64G........CCA...Generator ground relay 86G........CCA...Generator lockout relay
87.........CCA...Differential relays; B1,2,3,4- Bus; G,GX- Generator and auxiliary; T,TX,TY- Transformer and auxiliaries
71QLBL.....G1 ...Generator lower guide bearing low oil level
98CX.......G1 ...Creep Detector
71QLBN.....G1 ...Generator lower guide bearing normal oil level
46E........C1A...Exciter phase current balance relay..
49......... ...Thermal relay; A- Gen. air cooler (CCA); G- Gen. stator thermal relay (CCA); T- Transf. winding (KRA)
38.........G1 ...Thermal relays; GL- Lower guide brg. metal; GLQ- Lower guide brg. oil; GT1,2- Thrust brg. metal; GLQ- Thrust brg. oil; GU- Upper guide brg. metal
38TG.......H1 ...Turbine guide brg. temperature switch
40F,40X....C1A...Loss of field relay and auxiliary
25.........CCA...Automatic Synchronizer 26G........G1 ...Generator CO
2 thermal relay switch
26TP.......H1 ...Turbine packing box temperature switch
27......... ...Undervoltage relays; B1,B2- D.C. Battery (BCA); C-Unit Control D.C. (CCA); G-Reg. MG. set A.C. (C1A); GL- Unit protection D.C. (CCA)
DEVICE LOCATION
EXPLANATION
BASLER BE49 125VDC
G
AS BUILT AFTER REWIND/UPRATE
AB
B
C
C
A
KRA
1-3Ø-66/88/110 MVA
11.0-115 GND. Y / 66.4 KV.
H.V. TAPS ±2-1/2%
T
T
TQ
TD
3Y-600-5A
3Y-5000-5A
ADDED KRA
A
B
C
D
5 4
CADD SYSTEM
3 2
CADD FILENAME
DATE AND TIME PLOTTED
A
B
3 2
C
D
ALWAYS THINK SAFETY
AutoCAD Rel. 15.05 BM836A.DWG AUGUST 22, 2002 12:13
UNITED STATES
DEPARTMENT OF THE INTERIOR
BUREAU OF RECLAMATION
COLORADO RIVER STORAGE PROJECT
CURECANTI UNIT - GUNNISON DIVISION - COLORADO
BLUE MESA POWERPLANT
ELECTRICAL INSTALLATION
MAIN SINGLE LINE DIAGRAM
622-D-836A
622-D-836A
DENVER, COLORADO JUNE 12, 1964
SHEET 1 OF 2
DESIGNED _ _ _ _ _ _ _ _ _ _ _ _ TECH. APPR._ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
DRAWN _ _ _ _ _ _ _ _ _ _ _ _ _ _SUBMITTED _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
CHECKED _ _ _ _ _ _ _ _ _ _ _ _ _APPROVED_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
CHIEF, ELECTRICAL BRANCH
REVISED FOR NEW TRANSFORMER KRA.7-3-02
CCI-RCB
1-300G-A
64F
1-300G-B
200-5
B
SSQ
3Y-1200-5A
TBQ
1-300G-A
49G
3Y-5000-5A
T:\Acad\DWG\BM\Bm848A.dwg, 11/2/2011 6:07:42 AM, DWG To PDF.pc3
T:\Acad\DWG\BM\Bm848B.dwg, 11/2/2011 6:15:40 AM, DWG To PDF.pc3