This document contains technical drawings and specifications for electrical equipment at the Blue Mesa Powerplant. The drawings depict a single-line diagram of the station service, bus, and generator breaker layout. Protective relays, meters, switches and other devices are shown along with notes describing locations and functions. The related opportunity is a solicitation by the Bureau of Reclamation seeking a contractor to provide station service, bus, and unit breakers for the Blue Mesa Powerplant. The solicitation number is 140R4020R0006 and is for equipment to replace aging infrastructure at the facility.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

431- GM

REVISED AND REDRAWN

G.H.B.-J.J.K.

L.L.M.

W.N.P.

W.H. CLARK

J.V. BAPTIST

O.L. RICE

6-16-71

D-MEK

AS BUILT BY 431, LTR. 6-11-71

C

A

B

C

B A R

A

GENERATORS

115 KV. MAIN BUS 11.5 KV. BUS

C

A

115 KV. LINES

PHASE RELATIONSHIP-

SECONDARY POTENTIALS

SYN.

SS & 83

6A(CCA)

10A

TD

1BD

1DQ

1-12,000-120V

( A-B)

3Y-3000-5A

U1A

3Y-5000-5A

2 -12,000-120V

20A

TD

SYN.

SS & 83

U2A

2BD

1 E

KRB KRCC

A

B

C

B A

1-3 -1000KVA

12.0 KV.-480Y/277V.

± ±H.V. TAPS 2 1/2 & 5%

52A 52B

3Y-400-

5A

D1A

STATION SERVICE

ELECTRICAL INTER-

LOCK

6A(CCA)

6A

LG

I

VM

I

A3

S W

1-300G-B

L L

I

V

I

V

I

F

SYN

15 25

FROM SYN. CKTS.

S W

RUN IN

SYNCHRONIZING

EQUIPMENT

1MQ

1DNQ

A

GLQ

GL

TG

TP

71Q

LT

LOWER GUIDE BEARING

TURBINE GUIDE BEARING

TURBINE PACKING BOX

REC

T 11 STATOR

RTD'S

TO RTDS

ON KRA

GT1

GT2

GTQ

GU

QBH

QBN

QBL

UPPER GUIDE

BEARING

THRUST

BEARING

G

1 ,100 KVA

12 KV-120/240V.

K1A

GENERATOR G1

3 -48,000 KVA-11.5 KV.

0.9 PF, 200 R.P.M.

I

A

1RQ

3Y-3000-5A

1-3000-5A- A

G

RPM

RPM

BHM

(A1A)

(CCA)

(A1A)

SSG

K2A

S A M E

A S

S H O W N

F O R

U N I T

GATE LIMIT POS. (Each Unit) Selective Digital Readout

RESERVOIR LEVEL

Selective Digital Readout and Data Logging

TAILWATER LEVEL

Selective Digital Readout and Data Logging

TURBINE DISCHARGE

Selective Digital Readout (Each Unit)(C.F.S.)

and Data Logging (Total two units)(Acre Ft.)

SPILLWAY GATES No. 1 and 2

POSITION

Selective Digital Readout

1. YOU MUST LOOK AT THE 3-LINE DIAGRAMS TO FULLY UNDERSTAND THE RELAYING.

2. This plant is provided with LOCAL MANUAL, LOCAL AUTOMATIC, and REMOTE

AUTOMATIC controls for starting and stopping each unit.

3. Governor oil pumps, transformer cooling equipment and air compressor systems will be left in continuous service except for prolonged shutdown periods.

All other unit auxiliaries are taken out of service automatically when unit is shutdown.

4. May be combined by switching potentials.

GENERAL NOTES

Devices are located according to the following designations:

A1A - Governor H1 - Turbine Pit

BCA - Battery Control Board H1A - Generator Gage Board

C1A - Excitation Cubicle H1B - Butterfly Valve Cabinet

CCA - Main Control Board KRA - Main Transformer

E - Associated Equipment U1A - Unit 1 Generator Breaker (52)

G1 - Generator U2A - Unit 2 Generator Breaker (52)

CCB - Supervisory Control Board

TABLE OF PROTECTIVE RELAYS

DEVICE NO. G.E. W'HSE RATING

40F

46E

49G

51GB

51ST

51V

50/51E

59I

59G

59F

59VHZ

59T

64G

64F

87B1,2,3,4

OFFSET MHO

3-5A 7-15% ALARM, 10 SEC. TIME DELAYCOQ

CEH51A1A

C

A

B

C

B A

1-3 -1000KVA

12.0 KV.-480Y/277V.

±H.V. TAPS 2 1/2 &

±5%

STATION SERVICE SWGR.

FOR COMPLETE 1-LINE DIAGRAM

SEE DWG. 622-D-837

OTHER TELEMETERING TO PAGE

B0

DEVICE NOTES

Unless otherwise noted all symbols and device function numbers are in accordance with ASA Standard Y32.2 and C37.2. Devices not listed under

"Explanation" are located on Main Control Board unless otherwise noted.

For Unit 2, the number "1" in location designation is changed to 2.

TD

STATIC EXCITER

I

TD

WATT

TD

VAR

TD

V

TD

I

TM

(H1A)

ATLAS

W/WH

TD

PLANT

RECORDERS

SCADA TO

PAGE DISPATCH

FREQ

TD

UNIT 2 DATA

3 -11500-508

615 KVA

1-

1-300G-A

1-300G-B

40E

50/51 E

46E

CO-9

CO-9

COV-9

SVF

CO-2

CA

HU

4-16A., INST.,2-6A. V.I.

INDEPENT. OF FREQ.

55-140V., FREQ. COMP.

67V.

2-6A,V.I. 10-40A INST.

0.5-2.5A,V.I., 10-40A INST.

MAIN SINGLE LINE DIAGRAM -- SHEET 2 OF 2................622-D-836b

SWITCHYARD SINGLE LINE................................WAPA BM 0005

F

TO 115KV SWITCHYARD

(WAPA DWG. NO. BM 0005)

51GB.......CCA...Ground backup relay

51ST.......CCA...Station service overcurrent relay

51V........CCA...Overcurrent relay, voltage restrained

50/51E.....C1A...Exciter phase current (Time/Inst) 52.........U1A...Generator A.C. power circuit breaker

59I-T......CCA...Overvoltage relay, time delay, instantaneous, and frequency compensated

59F........C1A...Field undervoltage relay

59G........C1A...Generator overvoltage relay

59VHZ......C1A...Generator volts/Hz relay

REFERENCE DRAWINGS

12IJC51E2A 115-150%

12IFC53BD2A 2-50A

12IFV71BD2A 120-280V .2-2.0A

87G

87T

CV-8

CV-25

4-12A., SHORT TIME

10% SLOPE

30% SLOPE

12PJV11BK 280-580V

12STV11A5A 120V/60Hz 1.8-2.5/V/Hz

12PJG12B 120VAC

10-29-93

TO CT CKT

(WAPA DWG. NO. BM 5507)

TO FUSE FV1A

(WAPA DWG. NO. BM 0005)

64F........C1A...Generator field ground relay

64G........CCA...Generator ground relay 86G........CCA...Generator lockout relay

87.........CCA...Differential relays; B1,2,3,4- Bus; G,GX- Generator and auxiliary; T,TX,TY- Transformer and auxiliaries

71QLBL.....G1 ...Generator lower guide bearing low oil level

98CX.......G1 ...Creep Detector

71QLBN.....G1 ...Generator lower guide bearing normal oil level

46E........C1A...Exciter phase current balance relay..

49......... ...Thermal relay; A- Gen. air cooler (CCA); G- Gen. stator thermal relay (CCA); T- Transf. winding (KRA)

38.........G1 ...Thermal relays; GL- Lower guide brg. metal; GLQ- Lower guide brg. oil; GT1,2- Thrust brg. metal; GLQ- Thrust brg. oil; GU- Upper guide brg. metal

38TG.......H1 ...Turbine guide brg. temperature switch

40F,40X....C1A...Loss of field relay and auxiliary

25.........CCA...Automatic Synchronizer 26G........G1 ...Generator CO

2 thermal relay switch

26TP.......H1 ...Turbine packing box temperature switch

27......... ...Undervoltage relays; B1,B2- D.C. Battery (BCA); C-Unit Control D.C. (CCA); G-Reg. MG. set A.C. (C1A); GL- Unit protection D.C. (CCA)

DEVICE LOCATION

EXPLANATION

BASLER BE49 125VDC

G

AS BUILT AFTER REWIND/UPRATE

AB

B

C

C

A

KRA

1-3Ø-66/88/110 MVA

11.0-115 GND. Y / 66.4 KV.

H.V. TAPS ±2-1/2%

T

T

TQ

TD

3Y-600-5A

3Y-5000-5A

ADDED KRA

A

B

C

D

5 4

CADD SYSTEM

3 2

CADD FILENAME

DATE AND TIME PLOTTED

A

B

3 2

C

D

ALWAYS THINK SAFETY

AutoCAD Rel. 15.05 BM836A.DWG AUGUST 22, 2002 12:13

UNITED STATES

DEPARTMENT OF THE INTERIOR

BUREAU OF RECLAMATION

COLORADO RIVER STORAGE PROJECT

CURECANTI UNIT - GUNNISON DIVISION - COLORADO

BLUE MESA POWERPLANT

ELECTRICAL INSTALLATION

MAIN SINGLE LINE DIAGRAM

622-D-836A

622-D-836A

DENVER, COLORADO JUNE 12, 1964

SHEET 1 OF 2

DESIGNED _ _ _ _ _ _ _ _ _ _ _ _ TECH. APPR._ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

DRAWN _ _ _ _ _ _ _ _ _ _ _ _ _ _SUBMITTED _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

CHECKED _ _ _ _ _ _ _ _ _ _ _ _ _APPROVED_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

CHIEF, ELECTRICAL BRANCH

REVISED FOR NEW TRANSFORMER KRA.7-3-02

CCI-RCB

1-300G-A

64F

1-300G-B

200-5

B

SSQ

3Y-1200-5A

TBQ

1-300G-A

49G

3Y-5000-5A

T:\Acad\DWG\BM\Bm848A.dwg, 11/2/2011 6:07:42 AM, DWG To PDF.pc3

T:\Acad\DWG\BM\Bm848B.dwg, 11/2/2011 6:15:40 AM, DWG To PDF.pc3

Model