Attachment_7_Xformer_Oil_Results_2024_0002.pdf
PDF 2 MB Posted
- Attached to
- Transformer Supply IDIQ (Hoover Dam)
- Solicitation number
- 140R3024R0019
About this file
This document appears to be a laboratory test report for transformer oil samples taken from the Hoover Dam in Arizona. The report provides an analysis of the oil's chemical properties, including levels of dissolved gases, acidity, and contaminants. The results indicate the oil has experienced severe overheating, leading to high levels of carbon monoxide and carbon dioxide, as well as the presence of undesirable polar contaminants. The report references industry standards from IEEE for transformer oil specifications.
The related federal contract opportunity is a solicitation (140R3024R0019) for an Indefinite Delivery/Indefinite Quantity (IDIQ) contract for transformer materials and oil processing services for the Hoover Dam, issued by the Department of the Interior's Bureau of Reclamation. The contract is intended to provide a mechanism for the ongoing supply and maintenance of transformers and associated oils for the Hoover Dam facility.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USBR LOWER COLORADO BASIN
KA2A-A GMB20274 TRO
140R3023F0043
01-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
Hoover AZLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
WESTINGHOUSE
TRANFORMER OIL
UNKNOWN
UNKNOWN
230 kV
UNKNOWN
1734714
SAMPLE Nº: 4457-1-1-2
COMMENTS
• Carbon monoxide exceeds limits due to severe overheating.
• Carbon dioxide exceeds limits due to severe overheating.
• Low value of the interfacial tension indicates the presence of undesirable polar contaminants.
• Color change due to oxidation, deterioration or contamination of the oil.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734714UNIT
SPECTROSCOPY (ASTM D5185)
ReportPb 3ppm ReportCa 1ppm ReportNa 3ppm ReportSi 1ppm
0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g
ReportSPECIFIC GRAVITY (ASTM D4052) 0.8852g/ml
35.0 MaxDISSOLVED WATER (ASTM D1533) 8ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen 10ppm
120.0 MaxMethane 16ppm
65.0 MaxEthane 14ppm
50.0 MaxEthylene 17ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 658ppm
2500.0 MaxCarbon Dioxide 2634ppm
ReportNitrogen 62871ppm ReportOxygen 3754ppm
720.0 MaxTDCG 715ppm
ReportTDG 7%
0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.074%
25.0 MinINTERFACIAL TENSION (ASTM D971) 22.6mN/m
40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 44kV
RESULTS
TEST NAME SPEC1734714UNIT
1.5 MaxCOLOR (ASTM D1500) 2.5ASTM
USBR LOWER COLORADO BASIN assumes sole responsibility for the total copy, reproduction and/or application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance.
Fixed limits programmed according to laboratory or client specifications.
KA2A-B GBM20275 TRO
140R3023F0043
16-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
Hoover AZLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
WESTINGHOUSE
TRANFORMER OIL
UNKNOWN
UNKNOWN
230 kV
UNKNOWN
1734758
SAMPLE Nº: 4457-1-2-2
COMMENTS
• Carbon monoxide exceeds limits due to severe overheating.
• Carbon dioxide exceeds limits due to severe overheating.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734758UNIT
35.0 MaxDISSOLVED WATER (ASTM D1533) 6ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen 18ppm
120.0 MaxMethane 8ppm
65.0 MaxEthane 4ppm
50.0 MaxEthylene 7ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 538ppm
2500.0 MaxCarbon Dioxide 2633ppm
ReportNitrogen 62504ppm ReportOxygen 7827ppm
720.0 MaxTDCG 575ppm
ReportTDG 7.35%
USBR LOWER COLORADO BASIN assumes sole responsibility for the total copy, reproduction and/or application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance.
KA2A-C GBM20276 TRO
140R3023F0043
01-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
Hoover AZLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
WESTINGHOUSE
TRANFORMER OIL
UNKNOWN
UNKNOWN
230 kV
UNKNOWN
1734715
SAMPLE Nº: 4457-1-3-2
COMMENTS
• Carbon monoxide exceeds limits due to severe overheating.
• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.
• Color change due to oxidation, deterioration or contamination of the oil.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734715UNIT
SPECTROSCOPY (ASTM D5185)
ReportPb 3ppm ReportFe 1ppm ReportNa 4ppm ReportSi 1ppm ReportSn 1ppm
0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g
ReportSPECIFIC GRAVITY (ASTM D4052) 0.8851g/ml
35.0 MaxDISSOLVED WATER (ASTM D1533) 6ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen 8ppm
120.0 MaxMethane 61ppm
65.0 MaxEthane 29ppm
50.0 MaxEthylene 12ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 571ppm
2500.0 MaxCarbon Dioxide 1725ppm
ReportNitrogen 63382ppm ReportOxygen <500ppm
720.0 MaxTDCG 681ppm
ReportTDG 6.58%
0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.017%
25.0 MinINTERFACIAL TENSION (ASTM D971) 27.3mN/m
40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 30kV
TEST NAME SPEC1734715UNIT
1.5 MaxCOLOR (ASTM D1500) 2.5ASTM
USBR LOWER COLORADO BASIN assumes sole responsibility for the total copy, reproduction and/or application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance.
KA3A 6311-786 TRO
140R3023F0043
01-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
Hoover AZLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
ASEA
TRANFORMER OIL
UNKNOWN
UNKNOWN
230 kV
UNKNOWN
1734716
SAMPLE Nº: 4457-1-4-2
COMMENTS
• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.
• Color change due to oxidation, deterioration or contamination of the oil.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734716UNIT
SPECTROSCOPY (ASTM D5185)
ReportP 1ppm ReportPb 2ppm ReportCu 1ppm ReportNa 3ppm ReportMo 1ppm ReportSn 1ppm
0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g
ReportSPECIFIC GRAVITY (ASTM D4052) 0.8855g/ml
35.0 MaxDISSOLVED WATER (ASTM D1533) 6ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen 7ppm
120.0 MaxMethane 17ppm
65.0 MaxEthane 3ppm
50.0 MaxEthylene 5ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 267ppm
2500.0 MaxCarbon Dioxide 906ppm
ReportNitrogen 32847ppm ReportOxygen <500ppm
720.0 MaxTDCG 299ppm
ReportTDG 3.41%
0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.061%
25.0 MinINTERFACIAL TENSION (ASTM D971) 28.9mN/m
40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 35kV
TEST NAME SPEC1734716UNIT
1.5 MaxCOLOR (ASTM D1500) 2.0ASTM
USBR LOWER COLORADO BASIN assumes sole responsibility for the total copy, reproduction and/or application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance.
KA4A 6311-788 TRO
140R3023F0043
16-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
Hoover AZLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
ASEA
TRANFORMER OIL
UNKNOWN
UNKNOWN
230 kV
UNKNOWN
1734759
SAMPLE Nº: 4457-1-5-2
COMMENTS
• Carbon monoxide exceeds limits due to severe overheating.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734759UNIT
35.0 MaxDISSOLVED WATER (ASTM D1533) 6ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen 7ppm
120.0 MaxMethane 18ppm
65.0 MaxEthane 6ppm
50.0 MaxEthylene 27ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 579ppm
2500.0 MaxCarbon Dioxide 1751ppm
ReportNitrogen 63171ppm ReportOxygen <500ppm
720.0 MaxTDCG 637ppm
ReportTDG 6.56%
USBR LOWER COLORADO BASIN assumes sole responsibility for the total copy, reproduction and/or application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance.
KA5A 6311-789 TRO
140R3023F0043
01-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
Hoover AZLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
ASEA
TRANFORMER OIL
UNKNOWN
UNKNOWN
230 kV
UNKNOWN
1734717
SAMPLE Nº: 4457-1-6-2
COMMENTS
• Carbon monoxide exceeds limits due to severe overheating.
• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.
• Color change due to oxidation, deterioration or contamination of the oil.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734717UNIT
SPECTROSCOPY (ASTM D5185)
ReportPb 1ppm ReportCu 1ppm ReportNa 4ppm
0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g
ReportSPECIFIC GRAVITY (ASTM D4052) 0.8856g/ml
35.0 MaxDISSOLVED WATER (ASTM D1533) 5ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen 8ppm
120.0 MaxMethane 88ppm
65.0 MaxEthane 31ppm
50.0 MaxEthylene 12ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 522ppm
2500.0 MaxCarbon Dioxide 1424ppm
ReportNitrogen 58112ppm ReportOxygen <500ppm
720.0 MaxTDCG 661ppm
ReportTDG 6.02%
0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.099%
25.0 MinINTERFACIAL TENSION (ASTM D971) 29.2mN/m
40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 35kV
1.5 MaxCOLOR (ASTM D1500) 2.0ASTM
USBR LOWER COLORADO BASIN assumes sole responsibility for the total copy, reproduction and/or application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance.
KA6A 6311-787 TRO
140R3023F0043
01-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
Hoover AZLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
ASEA
TRANFORMER OIL
UNKNOWN
UNKNOWN
230 kV
UNKNOWN
1734718
SAMPLE Nº: 4457-1-7-2
COMMENTS
• Carbon monoxide exceeds limits due to severe overheating.
• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734718UNIT
SPECTROSCOPY (ASTM D5185)
ReportP 1ppm ReportNa 4ppm ReportSn 1ppm
0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g
ReportSPECIFIC GRAVITY (ASTM D4052) 0.8884g/ml
35.0 MaxDISSOLVED WATER (ASTM D1533) 5ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen 6ppm
120.0 MaxMethane 8ppm
65.0 MaxEthane 1ppm
50.0 MaxEthylene 28ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 890ppm
2500.0 MaxCarbon Dioxide 2158ppm
ReportNitrogen 60271ppm ReportOxygen 4223ppm
720.0 MaxTDCG 933ppm
ReportTDG 6.76%
0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.037%
25.0 MinINTERFACIAL TENSION (ASTM D971) 29.4mN/m
40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 28kV
1.5 MaxCOLOR (ASTM D1500) 1.5ASTM
whose obligation is limited to good faith performance.
KA7A 6311-784 TRO
140R3023F0043
01-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
Hoover AZLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
ASEA
TRANFORMER OIL
UNKNOWN
UNKNOWN
230 kV
UNKNOWN
1734721
SAMPLE Nº: 4457-1-8-2
COMMENTS
• Carbon monoxide exceeds limits due to severe overheating.
• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.
• Color change due to oxidation, deterioration or contamination of the oil.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734721UNIT
SPECTROSCOPY (ASTM D5185)
ReportP 1ppm ReportCu 1ppm ReportNa 4ppm
0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g
ReportSPECIFIC GRAVITY (ASTM D4052) 0.8718g/ml
35.0 MaxDISSOLVED WATER (ASTM D1533) 6ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen 5ppm
120.0 MaxMethane 23ppm
65.0 MaxEthane 5ppm
50.0 MaxEthylene 33ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 589ppm
2500.0 MaxCarbon Dioxide 2284ppm
ReportNitrogen 57347ppm ReportOxygen <500ppm
720.0 MaxTDCG 655ppm
ReportTDG 6.03%
0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.042%
25.0 MinINTERFACIAL TENSION (ASTM D971) 29mN/m
40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 27kV
whose obligation is limited to good faith performance.
KA8A 6311-785 TRO
140R3023F0043
01-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
Hoover AZLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
ASEA
TRANFORMER OIL
UNKNOWN
UNKNOWN
230 kV
UNKNOWN
1734724
SAMPLE Nº: 4457-1-9-2
COMMENTS
• Carbon monoxide exceeds limits due to severe overheating.
• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.
• Color change due to oxidation, deterioration or contamination of the oil.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734724UNIT
SPECTROSCOPY (ASTM D5185)
ReportCu 1ppm ReportNa 2ppm
0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g
ReportSPECIFIC GRAVITY (ASTM D4052) 0.8855g/ml
35.0 MaxDISSOLVED WATER (ASTM D1533) 4ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen 2ppm
120.0 MaxMethane 45ppm
65.0 MaxEthane 10ppm
50.0 MaxEthylene 9ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 513ppm
2500.0 MaxCarbon Dioxide 1288ppm
ReportNitrogen 49923ppm ReportOxygen <500ppm
720.0 MaxTDCG 579ppm
ReportTDG 5.18%
0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.062%
25.0 MinINTERFACIAL TENSION (ASTM D971) 29.4mN/m
40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 26kV
whose obligation is limited to good faith performance.
KN2A-A GMB20277 TRO
140R3023F0043
01-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
Hoover NVLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
WESTINGHOUSE
TRANFORMER OIL
168 hrs/week
UNKNOWN
230 kV
UNKNOWN
1734727
SAMPLE Nº: 4457-1-10-2
COMMENTS
• Carbon monoxide exceeds limits due to severe overheating.
• Carbon dioxide exceeds limits due to severe overheating.
• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.
• Color change due to oxidation, deterioration or contamination of the oil.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734727UNIT
SPECTROSCOPY (ASTM D5185)
ReportPb 5ppm ReportNa 4ppm ReportSi 1ppm
0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g
ReportSPECIFIC GRAVITY (ASTM D4052) 0.8855g/ml
35.0 MaxDISSOLVED WATER (ASTM D1533) 7ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen 16ppm
120.0 MaxMethane 15ppm
65.0 MaxEthane 15ppm
50.0 MaxEthylene 17ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 476ppm
2500.0 MaxCarbon Dioxide 2514ppm
ReportNitrogen 61455ppm ReportOxygen 7684ppm
720.0 MaxTDCG 539ppm
ReportTDG 7.22%
0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.099%
25.0 MinINTERFACIAL TENSION (ASTM D971) 29.2mN/m
40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 25kV
1.5 MaxCOLOR (ASTM D1500) 2.5ASTM
whose obligation is limited to good faith performance.
KN2A-B GMB20278 TRO
140R3023F0043
01-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
Hoover NVLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
WESTINGHOUSE
TRANFORMER OIL
UNKNOWN
UNKNOWN
230 kV
UNKNOWN
1734729
SAMPLE Nº: 4457-1-11-2
COMMENTS
• Carbon monoxide exceeds limits due to severe overheating.
• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.
• Color change due to oxidation, deterioration or contamination of the oil.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734729UNIT
SPECTROSCOPY (ASTM D5185)
ReportPb 4ppm ReportNa 4ppm
0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g
ReportSPECIFIC GRAVITY (ASTM D4052) 0.8854g/ml
35.0 MaxDISSOLVED WATER (ASTM D1533) 7ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen 6ppm
120.0 MaxMethane 31ppm
65.0 MaxEthane 30ppm
50.0 MaxEthylene 16ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 553ppm
2500.0 MaxCarbon Dioxide 1886ppm
ReportNitrogen 63810ppm ReportOxygen 3282ppm
720.0 MaxTDCG 636ppm
ReportTDG 6.96%
0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.072%
25.0 MinINTERFACIAL TENSION (ASTM D971) 29.3mN/m
40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 31kV
whose obligation is limited to good faith performance.
KN2A-C GMB20279 TRO
140R3023F0043
01-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
Hoover NVLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
WESTINGHOUSE
TRANFORMER OIL
UNKNOWN
UNKNOWN
230 kV
UNKNOWN
1734732
SAMPLE Nº: 4457-1-12-2
COMMENTS
• Carbon monoxide exceeds limits due to severe overheating.
• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.
• Color change due to oxidation, deterioration or contamination of the oil.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734732UNIT
SPECTROSCOPY (ASTM D5185)
ReportPb 1ppm ReportNa 3ppm
0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g
ReportSPECIFIC GRAVITY (ASTM D4052) 0.8854g/ml
35.0 MaxDISSOLVED WATER (ASTM D1533) 8ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen 6ppm
120.0 MaxMethane 14ppm
65.0 MaxEthane 15ppm
50.0 MaxEthylene 21ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 481ppm
2500.0 MaxCarbon Dioxide 2267ppm
ReportNitrogen 65807ppm ReportOxygen 7747ppm
720.0 MaxTDCG 537ppm
ReportTDG 7.64%
0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.045%
25.0 MinINTERFACIAL TENSION (ASTM D971) 29mN/m
40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 15kV
whose obligation is limited to good faith performance.
KN4A-A GMB20271 TRO
140R3023F0043
01-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
Hoover NVLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
WESTINGHOUSE
TRANFORMER OIL
UNKNOWN
UNKNOWN
230 kV
UNKNOWN
1734734
SAMPLE Nº: 4457-1-13-2
COMMENTS
• Carbon monoxide exceeds limits due to severe overheating.
• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.
• Color change due to oxidation, deterioration or contamination of the oil.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734734UNIT
SPECTROSCOPY (ASTM D5185)
ReportP 1ppm ReportPb 2ppm ReportNa 3ppm ReportMo 1ppm ReportSi 1ppm
0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g
ReportSPECIFIC GRAVITY (ASTM D4052) 0.885g/ml
35.0 MaxDISSOLVED WATER (ASTM D1533) 7ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen 8ppm
120.0 MaxMethane 20ppm
65.0 MaxEthane 6ppm
50.0 MaxEthylene 17ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 821ppm
2500.0 MaxCarbon Dioxide 2282ppm
ReportNitrogen 65699ppm ReportOxygen 897ppm
720.0 MaxTDCG 872ppm
ReportTDG 6.98%
0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.054%
25.0 MinINTERFACIAL TENSION (ASTM D971) 29.1mN/m
40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 28kV
TEST NAME SPEC1734734UNIT
1.5 MaxCOLOR (ASTM D1500) 3.0ASTM
USBR LOWER COLORADO BASIN assumes sole responsibility for the total copy, reproduction and/or application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance.
KN4A-B GMB20272 TRO
140R3023F0043
16-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
Hoover NVLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
WESTINGHOUSE
TRANFORMER OIL
UNKNOWN
UNKNOWN
230 kV
UNKNOWN
1734761
SAMPLE Nº: 4457-1-14-2
COMMENTS
• Carbon monoxide exceeds limits due to severe overheating.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734761UNIT
35.0 MaxDISSOLVED WATER (ASTM D1533) 7ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen 10ppm
120.0 MaxMethane 6ppm
65.0 MaxEthane 5ppm
50.0 MaxEthylene 14ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 507ppm
2500.0 MaxCarbon Dioxide 1884ppm
ReportNitrogen 57708ppm ReportOxygen 6763ppm
720.0 MaxTDCG 542ppm
ReportTDG 6.69%
USBR LOWER COLORADO BASIN assumes sole responsibility for the total copy, reproduction and/or application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance.
KN4A-C GMB20273 TRO
140R3023F0043
01-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
Hoover NVLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
WESTINGHOUSE
TRANFORMER OIL
UNKNOWN
UNKNOWN
230 kV
UNKNOWN
1734737
SAMPLE Nº: 4457-1-15-2
COMMENTS
• Carbon monoxide exceeds limits due to severe overheating.
• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.
• Color change due to oxidation, deterioration or contamination of the oil.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734737UNIT
SPECTROSCOPY (ASTM D5185)
ReportNa 3ppm ReportMo 1ppm
0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g
ReportSPECIFIC GRAVITY (ASTM D4052) 0.885g/ml
35.0 MaxDISSOLVED WATER (ASTM D1533) 6ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen 10ppm
120.0 MaxMethane 21ppm
65.0 MaxEthane 20ppm
50.0 MaxEthylene 19ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 643ppm
2500.0 MaxCarbon Dioxide 2012ppm
ReportNitrogen 64250ppm ReportOxygen 3874ppm
720.0 MaxTDCG 713ppm
ReportTDG 7.08%
0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.033%
25.0 MinINTERFACIAL TENSION (ASTM D971) 29.3mN/m
40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 24kV
1.5 MaxCOLOR (ASTM D1500) 3.0ASTM
whose obligation is limited to good faith performance.
KN6A-A 219801 TRO
140R3023F0043
01-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
Hoover NVLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
SMITH & LOVELESS INC
TRANFORMER OIL
UNKNOWN
UNKNOWN
230 kV
UNKNOWN
1734740
SAMPLE Nº: 4457-1-16-2
COMMENTS
• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.
• Color change due to oxidation, deterioration or contamination of the oil.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734740UNIT
SPECTROSCOPY (ASTM D5185)
ReportNa 2ppm ReportSn 1ppm
0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g
ReportSPECIFIC GRAVITY (ASTM D4052) 0.8847g/ml
35.0 MaxDISSOLVED WATER (ASTM D1533) 6ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen 7ppm
120.0 MaxMethane 5ppm
65.0 MaxEthane 1ppm
50.0 MaxEthylene 1ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 90ppm
2500.0 MaxCarbon Dioxide 695ppm
ReportNitrogen 10235ppm ReportOxygen <500ppm
720.0 MaxTDCG 104ppm
ReportTDG 1.1%
0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.032%
25.0 MinINTERFACIAL TENSION (ASTM D971) 29mN/m
40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 27kV
whose obligation is limited to good faith performance.
KN6A-B 219800 TRO
140R3023F0043
01-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
Hoover NVLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
SMITH & LOVELESS INC
TRANFORMER OIL
UNKNOWN
UNKNOWN
230 kV
UNKNOWN
1734742
SAMPLE Nº: 4457-1-17-2
COMMENTS
• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.
• Color change due to oxidation, deterioration or contamination of the oil.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734742UNIT
SPECTROSCOPY (ASTM D5185)
ReportP 1ppm ReportNa 4ppm
0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g
ReportSPECIFIC GRAVITY (ASTM D4052) 0.8847g/ml
35.0 MaxDISSOLVED WATER (ASTM D1533) 6ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen 12ppm
120.0 MaxMethane 6ppm
65.0 MaxEthane 2ppm
50.0 MaxEthylene 1ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 110ppm
2500.0 MaxCarbon Dioxide 864ppm
ReportNitrogen 14682ppm ReportOxygen <500ppm
720.0 MaxTDCG 131ppm
ReportTDG 1.57%
0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.035%
25.0 MinINTERFACIAL TENSION (ASTM D971) 29.1mN/m
40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 26kV
whose obligation is limited to good faith performance.
KN6A-C 219799 TRO
140R3023F0043
01-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
Hoover NVLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
SMITH & LOVELESS INC
TRANFORMER OIL
UNKNOWN
UNKNOWN
230 kV
UNKNOWN
1734743
SAMPLE Nº: 4457-1-18-2
COMMENTS
• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.
• Color change due to oxidation, deterioration or contamination of the oil.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734743UNIT
SPECTROSCOPY (ASTM D5185)
ReportP 1ppm ReportPb 1ppm ReportNa 3ppm
0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g
ReportSPECIFIC GRAVITY (ASTM D4052) 0.8848g/ml
35.0 MaxDISSOLVED WATER (ASTM D1533) 5ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen 7ppm
120.0 MaxMethane 5ppm
65.0 MaxEthane 1ppm
50.0 MaxEthylene 1ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 105ppm
2500.0 MaxCarbon Dioxide 1240ppm
ReportNitrogen 16813ppm ReportOxygen 938ppm
720.0 MaxTDCG 119ppm
ReportTDG 1.91%
0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.039%
25.0 MinINTERFACIAL TENSION (ASTM D971) 29.2mN/m
40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 28kV
whose obligation is limited to good faith performance.
KN8A-A 219802 TRO
140R3023F0043
01-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
Hoover NVLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
SMITH & LOVELESS INC
TRANFORMER OIL
UNKNOWN
UNKNOWN
230 kV
UNKNOWN
1734744
SAMPLE Nº: 4457-1-19-2
COMMENTS
• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.
• Color change due to oxidation, deterioration or contamination of the oil.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734744UNIT
SPECTROSCOPY (ASTM D5185)
ReportP 1ppm ReportNa 3ppm ReportMo 1ppm
0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g
ReportSPECIFIC GRAVITY (ASTM D4052) 0.8856g/ml
35.0 MaxDISSOLVED WATER (ASTM D1533) 6ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen 6ppm
120.0 MaxMethane 8ppm
65.0 MaxEthane 4ppm
50.0 MaxEthylene 1ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 80ppm
2500.0 MaxCarbon Dioxide 603ppm
ReportNitrogen 14456ppm ReportOxygen <500ppm
720.0 MaxTDCG 99ppm
ReportTDG 1.52%
0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.051%
25.0 MinINTERFACIAL TENSION (ASTM D971) 29.5mN/m
40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 18kV
whose obligation is limited to good faith performance.
KN8A-B 219803 TRO
140R3023F0043
01-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
Hoover NVLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
SMITH & LOVELESS INC
TRANFORMER OIL
UNKNOWN
UNKNOWN
230 kV
UNKNOWN
1734745
SAMPLE Nº: 4457-1-20-2
COMMENTS
• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.
• Color change due to oxidation, deterioration or contamination of the oil.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734745UNIT
SPECTROSCOPY (ASTM D5185)
ReportP 1ppm ReportNa 4ppm
0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g
ReportSPECIFIC GRAVITY (ASTM D4052) 0.8856g/ml
35.0 MaxDISSOLVED WATER (ASTM D1533) 6ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen 10ppm
120.0 MaxMethane 4ppm
65.0 MaxEthane 2ppm
50.0 MaxEthylene 1ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 63ppm
2500.0 MaxCarbon Dioxide 564ppm
ReportNitrogen 64934ppm ReportOxygen 11760ppm
720.0 MaxTDCG 80ppm
ReportTDG 7.73%
0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.032%
25.0 MinINTERFACIAL TENSION (ASTM D971) 29.3mN/m
40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 29kV
whose obligation is limited to good faith performance.
KN8A-C 219804 TRO
140R3023F0043
01-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
HOOVER NVLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
SMITH & LOVELESS INC
TRANFORMER OIL
UNKNOWN
UNKNOWN
230 kV
UNKNOWN
1734746
SAMPLE Nº: 4457-1-21-2
COMMENTS
• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.
• Color change due to oxidation, deterioration or contamination of the oil.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734746UNIT
SPECTROSCOPY (ASTM D5185)
ReportP 1ppm ReportNa 3ppm
0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g
ReportSPECIFIC GRAVITY (ASTM D4052) 0.8853g/ml
35.0 MaxDISSOLVED WATER (ASTM D1533) 5ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen <2ppm
120.0 MaxMethane 4ppm
65.0 MaxEthane 1ppm
50.0 MaxEthylene 1ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 64ppm
2500.0 MaxCarbon Dioxide 496ppm
ReportNitrogen 10302ppm ReportOxygen <500ppm
720.0 MaxTDCG 70ppm
ReportTDG 1.09%
0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.021%
25.0 MinINTERFACIAL TENSION (ASTM D971) 29.5mN/m
40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 34kV
whose obligation is limited to good faith performance.
NV Spare 10 GMB202710 TRO 140R3023F0043
01-Jul-2024
JASON FYFFE 22-Jul-2024
16-Jul-2024HOOVER DAM
TRIBOLOGIK
Sample InformationCustomer Information
CUSTOMER:
PLANT:
PO #:
CONTACT:
LABNO:
REPORT DATE:
MACHINE:
OIL TYPE:
SAMPLE DATE:
RECEIVED DATE:
SPEC LIMITS:
MINERAL
Machine Information
MACHINE:
Oil Type:
Hoover NVLocation:
Model:
Manufacturer: Age/Years:
Operating Hours:
Oil Manufacturer:
Oil Capacity:
Voltage:
Power:
WESTINGHOUSE
TRANFORMER OIL
UNKNOWN
UNKNOWN
230 kV
UNKNOWN
1734747
SAMPLE Nº: 4457-1-22-2
COMMENTS
• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.
• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.
RESULTS
TEST NAME SPEC1734747UNIT
SPECTROSCOPY (ASTM D5185)
ReportPb 1ppm ReportNa 3ppm ReportMo 1ppm
0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g
ReportSPECIFIC GRAVITY (ASTM D4052) 0.8852g/ml
35.0 MaxDISSOLVED WATER (ASTM D1533) 5ppm
DISSOLVED GAS ANALYSIS (ASTM D3612)
100.0 MaxHydrogen 3ppm
120.0 MaxMethane 3ppm
65.0 MaxEthane 1ppm
50.0 MaxEthylene 1ppm
1.0 MaxAcethylene <1ppm
350.0 MaxCarbon Monoxide 23ppm
2500.0 MaxCarbon Dioxide 137ppm
ReportNitrogen 42445ppm ReportOxygen <500ppm
720.0 MaxTDCG 31ppm
ReportTDG 4.26%
0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.027%
25.0 MinINTERFACIAL TENSION (ASTM D971) 26.5mN/m
40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 28kV
1.5 MaxCOLOR (ASTM D1500) 1.5ASTM
whose obligation is limited to good faith performance.