Attachment_7_Xformer_Oil_Results_2024_0002.pdf

PDF 2 MB Posted

Attached to
Transformer Supply IDIQ (Hoover Dam)
Solicitation number
140R3024R0019
Issued by

About this file

This document appears to be a laboratory test report for transformer oil samples taken from the Hoover Dam in Arizona. The report provides an analysis of the oil's chemical properties, including levels of dissolved gases, acidity, and contaminants. The results indicate the oil has experienced severe overheating, leading to high levels of carbon monoxide and carbon dioxide, as well as the presence of undesirable polar contaminants. The report references industry standards from IEEE for transformer oil specifications.

The related federal contract opportunity is a solicitation (140R3024R0019) for an Indefinite Delivery/Indefinite Quantity (IDIQ) contract for transformer materials and oil processing services for the Hoover Dam, issued by the Department of the Interior's Bureau of Reclamation. The contract is intended to provide a mechanism for the ongoing supply and maintenance of transformers and associated oils for the Hoover Dam facility.

View the file

Other files

File Type Posted
Sol_140R3024R0019_Amd_0005.pdf PDF
Attachment_11_Nameplate_Photos_-_Oil_pump___Heat_exhangers_0005.pdf PDF
Sol_140R3024R0019_Amd_0004.pdf PDF
Sol_140R3024R0019_Amd_0003.pdf PDF
Attachment_10_IDIQ_Drawing_-_Transformer_Information_0003.pdf PDF
Sol_140R3024R0019_Amd_0002.pdf PDF
Attachment_7a_Xformer_Oil_Results_2022_0002.pdf PDF
C06_Q_A_on_RFP_140R3024R0019_0002.pdf PDF
Attachment_6_Transformer_Photos_0002.pdf PDF
Attachment_8_Westinghouse_Transformer_Information_0002.pdf PDF
Attachment_9_Wage_Determination_0002.pdf PDF
Attachment_1b_IDIQ_Drawing_45-301-5216-R27_0001.pdf PDF
Attachment_5_Past_Performance_Questionnaire_0001.doc DOC document
Attachment_2b_Delivery_Order_1_SOW_Hoover_Drawing_45-D-9325_0001.pdf PDF
Sol_140R3024R0019_Amd_0001.pdf PDF
Attachment_2a_Delivery_Order_1_SOW_ABB_Operation_and_Maintenance_Manual_0001.pdf PDF
Attachment_1a_IDIQ_Drawing_45-301-4699-R24_0001.pdf PDF
Attachment_4_DI-137_Release_of_Claims.pdf PDF
Attachment_1c_IDIQ_Drawing_GBM2027-1_Westinghouse_Transformer.pdf PDF
Attachment_5_Past_Performance_Questionnaire.doc DOC document
Attachment_1_Transformer_IDIQ_Specifications.pdf PDF
Attachment_2b_Delivery_Order_1_SOW_Hoover_Drawing_45-D-9325.pdf PDF
Attachment_2a_Delivery_Order_1_SOW_ABB_Operation_and_Maintenance_Manual.pdf PDF
Attachment_1b_IDIQ_Drawing_45-301-5216-R27.pdf PDF
Attachment_3_Price_Schedule.xlsx XLSX spreadsheet
140R3024R0019_RFP.pdf PDF
Attachment_1a_IDIQ_Drawing_45-301-4699-R24.pdf PDF
Attachment_2_Delivery_Order_1_SOW_KA3A_and_KA5A_Transformer_Material.pdf PDF
Sol_140R3024R0019.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

USBR LOWER COLORADO BASIN

KA2A-A GMB20274 TRO

140R3023F0043

01-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

Hoover AZLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

WESTINGHOUSE

TRANFORMER OIL

UNKNOWN

UNKNOWN

230 kV

UNKNOWN

1734714

SAMPLE Nº: 4457-1-1-2

COMMENTS

• Carbon monoxide exceeds limits due to severe overheating.

• Carbon dioxide exceeds limits due to severe overheating.

• Low value of the interfacial tension indicates the presence of undesirable polar contaminants.

• Color change due to oxidation, deterioration or contamination of the oil.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734714UNIT

SPECTROSCOPY (ASTM D5185)

ReportPb 3ppm ReportCa 1ppm ReportNa 3ppm ReportSi 1ppm

0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g

ReportSPECIFIC GRAVITY (ASTM D4052) 0.8852g/ml

35.0 MaxDISSOLVED WATER (ASTM D1533) 8ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen 10ppm

120.0 MaxMethane 16ppm

65.0 MaxEthane 14ppm

50.0 MaxEthylene 17ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 658ppm

2500.0 MaxCarbon Dioxide 2634ppm

ReportNitrogen 62871ppm ReportOxygen 3754ppm

720.0 MaxTDCG 715ppm

ReportTDG 7%

0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.074%

25.0 MinINTERFACIAL TENSION (ASTM D971) 22.6mN/m

40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 44kV

RESULTS

TEST NAME SPEC1734714UNIT

1.5 MaxCOLOR (ASTM D1500) 2.5ASTM

USBR LOWER COLORADO BASIN assumes sole responsibility for the total copy, reproduction and/or application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance.

Fixed limits programmed according to laboratory or client specifications.

KA2A-B GBM20275 TRO

140R3023F0043

16-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

Hoover AZLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

WESTINGHOUSE

TRANFORMER OIL

UNKNOWN

UNKNOWN

230 kV

UNKNOWN

1734758

SAMPLE Nº: 4457-1-2-2

COMMENTS

• Carbon monoxide exceeds limits due to severe overheating.

• Carbon dioxide exceeds limits due to severe overheating.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734758UNIT

35.0 MaxDISSOLVED WATER (ASTM D1533) 6ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen 18ppm

120.0 MaxMethane 8ppm

65.0 MaxEthane 4ppm

50.0 MaxEthylene 7ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 538ppm

2500.0 MaxCarbon Dioxide 2633ppm

ReportNitrogen 62504ppm ReportOxygen 7827ppm

720.0 MaxTDCG 575ppm

ReportTDG 7.35%

USBR LOWER COLORADO BASIN assumes sole responsibility for the total copy, reproduction and/or application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance.

KA2A-C GBM20276 TRO

140R3023F0043

01-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

Hoover AZLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

WESTINGHOUSE

TRANFORMER OIL

UNKNOWN

UNKNOWN

230 kV

UNKNOWN

1734715

SAMPLE Nº: 4457-1-3-2

COMMENTS

• Carbon monoxide exceeds limits due to severe overheating.

• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.

• Color change due to oxidation, deterioration or contamination of the oil.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734715UNIT

SPECTROSCOPY (ASTM D5185)

ReportPb 3ppm ReportFe 1ppm ReportNa 4ppm ReportSi 1ppm ReportSn 1ppm

0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g

ReportSPECIFIC GRAVITY (ASTM D4052) 0.8851g/ml

35.0 MaxDISSOLVED WATER (ASTM D1533) 6ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen 8ppm

120.0 MaxMethane 61ppm

65.0 MaxEthane 29ppm

50.0 MaxEthylene 12ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 571ppm

2500.0 MaxCarbon Dioxide 1725ppm

ReportNitrogen 63382ppm ReportOxygen <500ppm

720.0 MaxTDCG 681ppm

ReportTDG 6.58%

0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.017%

25.0 MinINTERFACIAL TENSION (ASTM D971) 27.3mN/m

40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 30kV

TEST NAME SPEC1734715UNIT

1.5 MaxCOLOR (ASTM D1500) 2.5ASTM

USBR LOWER COLORADO BASIN assumes sole responsibility for the total copy, reproduction and/or application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance.

KA3A 6311-786 TRO

140R3023F0043

01-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

Hoover AZLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

ASEA

TRANFORMER OIL

UNKNOWN

UNKNOWN

230 kV

UNKNOWN

1734716

SAMPLE Nº: 4457-1-4-2

COMMENTS

• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.

• Color change due to oxidation, deterioration or contamination of the oil.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734716UNIT

SPECTROSCOPY (ASTM D5185)

ReportP 1ppm ReportPb 2ppm ReportCu 1ppm ReportNa 3ppm ReportMo 1ppm ReportSn 1ppm

0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g

ReportSPECIFIC GRAVITY (ASTM D4052) 0.8855g/ml

35.0 MaxDISSOLVED WATER (ASTM D1533) 6ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen 7ppm

120.0 MaxMethane 17ppm

65.0 MaxEthane 3ppm

50.0 MaxEthylene 5ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 267ppm

2500.0 MaxCarbon Dioxide 906ppm

ReportNitrogen 32847ppm ReportOxygen <500ppm

720.0 MaxTDCG 299ppm

ReportTDG 3.41%

0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.061%

25.0 MinINTERFACIAL TENSION (ASTM D971) 28.9mN/m

40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 35kV

TEST NAME SPEC1734716UNIT

1.5 MaxCOLOR (ASTM D1500) 2.0ASTM

USBR LOWER COLORADO BASIN assumes sole responsibility for the total copy, reproduction and/or application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance.

KA4A 6311-788 TRO

140R3023F0043

16-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

Hoover AZLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

ASEA

TRANFORMER OIL

UNKNOWN

UNKNOWN

230 kV

UNKNOWN

1734759

SAMPLE Nº: 4457-1-5-2

COMMENTS

• Carbon monoxide exceeds limits due to severe overheating.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734759UNIT

35.0 MaxDISSOLVED WATER (ASTM D1533) 6ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen 7ppm

120.0 MaxMethane 18ppm

65.0 MaxEthane 6ppm

50.0 MaxEthylene 27ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 579ppm

2500.0 MaxCarbon Dioxide 1751ppm

ReportNitrogen 63171ppm ReportOxygen <500ppm

720.0 MaxTDCG 637ppm

ReportTDG 6.56%

USBR LOWER COLORADO BASIN assumes sole responsibility for the total copy, reproduction and/or application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance.

KA5A 6311-789 TRO

140R3023F0043

01-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

Hoover AZLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

ASEA

TRANFORMER OIL

UNKNOWN

UNKNOWN

230 kV

UNKNOWN

1734717

SAMPLE Nº: 4457-1-6-2

COMMENTS

• Carbon monoxide exceeds limits due to severe overheating.

• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.

• Color change due to oxidation, deterioration or contamination of the oil.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734717UNIT

SPECTROSCOPY (ASTM D5185)

ReportPb 1ppm ReportCu 1ppm ReportNa 4ppm

0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g

ReportSPECIFIC GRAVITY (ASTM D4052) 0.8856g/ml

35.0 MaxDISSOLVED WATER (ASTM D1533) 5ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen 8ppm

120.0 MaxMethane 88ppm

65.0 MaxEthane 31ppm

50.0 MaxEthylene 12ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 522ppm

2500.0 MaxCarbon Dioxide 1424ppm

ReportNitrogen 58112ppm ReportOxygen <500ppm

720.0 MaxTDCG 661ppm

ReportTDG 6.02%

0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.099%

25.0 MinINTERFACIAL TENSION (ASTM D971) 29.2mN/m

40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 35kV

1.5 MaxCOLOR (ASTM D1500) 2.0ASTM

USBR LOWER COLORADO BASIN assumes sole responsibility for the total copy, reproduction and/or application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance.

KA6A 6311-787 TRO

140R3023F0043

01-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

Hoover AZLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

ASEA

TRANFORMER OIL

UNKNOWN

UNKNOWN

230 kV

UNKNOWN

1734718

SAMPLE Nº: 4457-1-7-2

COMMENTS

• Carbon monoxide exceeds limits due to severe overheating.

• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734718UNIT

SPECTROSCOPY (ASTM D5185)

ReportP 1ppm ReportNa 4ppm ReportSn 1ppm

0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g

ReportSPECIFIC GRAVITY (ASTM D4052) 0.8884g/ml

35.0 MaxDISSOLVED WATER (ASTM D1533) 5ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen 6ppm

120.0 MaxMethane 8ppm

65.0 MaxEthane 1ppm

50.0 MaxEthylene 28ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 890ppm

2500.0 MaxCarbon Dioxide 2158ppm

ReportNitrogen 60271ppm ReportOxygen 4223ppm

720.0 MaxTDCG 933ppm

ReportTDG 6.76%

0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.037%

25.0 MinINTERFACIAL TENSION (ASTM D971) 29.4mN/m

40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 28kV

1.5 MaxCOLOR (ASTM D1500) 1.5ASTM

whose obligation is limited to good faith performance.

KA7A 6311-784 TRO

140R3023F0043

01-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

Hoover AZLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

ASEA

TRANFORMER OIL

UNKNOWN

UNKNOWN

230 kV

UNKNOWN

1734721

SAMPLE Nº: 4457-1-8-2

COMMENTS

• Carbon monoxide exceeds limits due to severe overheating.

• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.

• Color change due to oxidation, deterioration or contamination of the oil.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734721UNIT

SPECTROSCOPY (ASTM D5185)

ReportP 1ppm ReportCu 1ppm ReportNa 4ppm

0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g

ReportSPECIFIC GRAVITY (ASTM D4052) 0.8718g/ml

35.0 MaxDISSOLVED WATER (ASTM D1533) 6ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen 5ppm

120.0 MaxMethane 23ppm

65.0 MaxEthane 5ppm

50.0 MaxEthylene 33ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 589ppm

2500.0 MaxCarbon Dioxide 2284ppm

ReportNitrogen 57347ppm ReportOxygen <500ppm

720.0 MaxTDCG 655ppm

ReportTDG 6.03%

0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.042%

25.0 MinINTERFACIAL TENSION (ASTM D971) 29mN/m

40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 27kV

whose obligation is limited to good faith performance.

KA8A 6311-785 TRO

140R3023F0043

01-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

Hoover AZLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

ASEA

TRANFORMER OIL

UNKNOWN

UNKNOWN

230 kV

UNKNOWN

1734724

SAMPLE Nº: 4457-1-9-2

COMMENTS

• Carbon monoxide exceeds limits due to severe overheating.

• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.

• Color change due to oxidation, deterioration or contamination of the oil.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734724UNIT

SPECTROSCOPY (ASTM D5185)

ReportCu 1ppm ReportNa 2ppm

0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g

ReportSPECIFIC GRAVITY (ASTM D4052) 0.8855g/ml

35.0 MaxDISSOLVED WATER (ASTM D1533) 4ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen 2ppm

120.0 MaxMethane 45ppm

65.0 MaxEthane 10ppm

50.0 MaxEthylene 9ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 513ppm

2500.0 MaxCarbon Dioxide 1288ppm

ReportNitrogen 49923ppm ReportOxygen <500ppm

720.0 MaxTDCG 579ppm

ReportTDG 5.18%

0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.062%

25.0 MinINTERFACIAL TENSION (ASTM D971) 29.4mN/m

40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 26kV

whose obligation is limited to good faith performance.

KN2A-A GMB20277 TRO

140R3023F0043

01-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

Hoover NVLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

WESTINGHOUSE

TRANFORMER OIL

168 hrs/week

UNKNOWN

230 kV

UNKNOWN

1734727

SAMPLE Nº: 4457-1-10-2

COMMENTS

• Carbon monoxide exceeds limits due to severe overheating.

• Carbon dioxide exceeds limits due to severe overheating.

• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.

• Color change due to oxidation, deterioration or contamination of the oil.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734727UNIT

SPECTROSCOPY (ASTM D5185)

ReportPb 5ppm ReportNa 4ppm ReportSi 1ppm

0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g

ReportSPECIFIC GRAVITY (ASTM D4052) 0.8855g/ml

35.0 MaxDISSOLVED WATER (ASTM D1533) 7ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen 16ppm

120.0 MaxMethane 15ppm

65.0 MaxEthane 15ppm

50.0 MaxEthylene 17ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 476ppm

2500.0 MaxCarbon Dioxide 2514ppm

ReportNitrogen 61455ppm ReportOxygen 7684ppm

720.0 MaxTDCG 539ppm

ReportTDG 7.22%

0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.099%

25.0 MinINTERFACIAL TENSION (ASTM D971) 29.2mN/m

40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 25kV

1.5 MaxCOLOR (ASTM D1500) 2.5ASTM

whose obligation is limited to good faith performance.

KN2A-B GMB20278 TRO

140R3023F0043

01-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

Hoover NVLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

WESTINGHOUSE

TRANFORMER OIL

UNKNOWN

UNKNOWN

230 kV

UNKNOWN

1734729

SAMPLE Nº: 4457-1-11-2

COMMENTS

• Carbon monoxide exceeds limits due to severe overheating.

• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.

• Color change due to oxidation, deterioration or contamination of the oil.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734729UNIT

SPECTROSCOPY (ASTM D5185)

ReportPb 4ppm ReportNa 4ppm

0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g

ReportSPECIFIC GRAVITY (ASTM D4052) 0.8854g/ml

35.0 MaxDISSOLVED WATER (ASTM D1533) 7ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen 6ppm

120.0 MaxMethane 31ppm

65.0 MaxEthane 30ppm

50.0 MaxEthylene 16ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 553ppm

2500.0 MaxCarbon Dioxide 1886ppm

ReportNitrogen 63810ppm ReportOxygen 3282ppm

720.0 MaxTDCG 636ppm

ReportTDG 6.96%

0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.072%

25.0 MinINTERFACIAL TENSION (ASTM D971) 29.3mN/m

40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 31kV

whose obligation is limited to good faith performance.

KN2A-C GMB20279 TRO

140R3023F0043

01-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

Hoover NVLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

WESTINGHOUSE

TRANFORMER OIL

UNKNOWN

UNKNOWN

230 kV

UNKNOWN

1734732

SAMPLE Nº: 4457-1-12-2

COMMENTS

• Carbon monoxide exceeds limits due to severe overheating.

• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.

• Color change due to oxidation, deterioration or contamination of the oil.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734732UNIT

SPECTROSCOPY (ASTM D5185)

ReportPb 1ppm ReportNa 3ppm

0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g

ReportSPECIFIC GRAVITY (ASTM D4052) 0.8854g/ml

35.0 MaxDISSOLVED WATER (ASTM D1533) 8ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen 6ppm

120.0 MaxMethane 14ppm

65.0 MaxEthane 15ppm

50.0 MaxEthylene 21ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 481ppm

2500.0 MaxCarbon Dioxide 2267ppm

ReportNitrogen 65807ppm ReportOxygen 7747ppm

720.0 MaxTDCG 537ppm

ReportTDG 7.64%

0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.045%

25.0 MinINTERFACIAL TENSION (ASTM D971) 29mN/m

40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 15kV

whose obligation is limited to good faith performance.

KN4A-A GMB20271 TRO

140R3023F0043

01-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

Hoover NVLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

WESTINGHOUSE

TRANFORMER OIL

UNKNOWN

UNKNOWN

230 kV

UNKNOWN

1734734

SAMPLE Nº: 4457-1-13-2

COMMENTS

• Carbon monoxide exceeds limits due to severe overheating.

• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.

• Color change due to oxidation, deterioration or contamination of the oil.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734734UNIT

SPECTROSCOPY (ASTM D5185)

ReportP 1ppm ReportPb 2ppm ReportNa 3ppm ReportMo 1ppm ReportSi 1ppm

0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g

ReportSPECIFIC GRAVITY (ASTM D4052) 0.885g/ml

35.0 MaxDISSOLVED WATER (ASTM D1533) 7ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen 8ppm

120.0 MaxMethane 20ppm

65.0 MaxEthane 6ppm

50.0 MaxEthylene 17ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 821ppm

2500.0 MaxCarbon Dioxide 2282ppm

ReportNitrogen 65699ppm ReportOxygen 897ppm

720.0 MaxTDCG 872ppm

ReportTDG 6.98%

0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.054%

25.0 MinINTERFACIAL TENSION (ASTM D971) 29.1mN/m

40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 28kV

TEST NAME SPEC1734734UNIT

1.5 MaxCOLOR (ASTM D1500) 3.0ASTM

USBR LOWER COLORADO BASIN assumes sole responsibility for the total copy, reproduction and/or application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance.

KN4A-B GMB20272 TRO

140R3023F0043

16-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

Hoover NVLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

WESTINGHOUSE

TRANFORMER OIL

UNKNOWN

UNKNOWN

230 kV

UNKNOWN

1734761

SAMPLE Nº: 4457-1-14-2

COMMENTS

• Carbon monoxide exceeds limits due to severe overheating.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734761UNIT

35.0 MaxDISSOLVED WATER (ASTM D1533) 7ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen 10ppm

120.0 MaxMethane 6ppm

65.0 MaxEthane 5ppm

50.0 MaxEthylene 14ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 507ppm

2500.0 MaxCarbon Dioxide 1884ppm

ReportNitrogen 57708ppm ReportOxygen 6763ppm

720.0 MaxTDCG 542ppm

ReportTDG 6.69%

USBR LOWER COLORADO BASIN assumes sole responsibility for the total copy, reproduction and/or application of and reliance upon results and recommendations reported by Tribologik Corporation, whose obligation is limited to good faith performance.

KN4A-C GMB20273 TRO

140R3023F0043

01-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

Hoover NVLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

WESTINGHOUSE

TRANFORMER OIL

UNKNOWN

UNKNOWN

230 kV

UNKNOWN

1734737

SAMPLE Nº: 4457-1-15-2

COMMENTS

• Carbon monoxide exceeds limits due to severe overheating.

• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.

• Color change due to oxidation, deterioration or contamination of the oil.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734737UNIT

SPECTROSCOPY (ASTM D5185)

ReportNa 3ppm ReportMo 1ppm

0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g

ReportSPECIFIC GRAVITY (ASTM D4052) 0.885g/ml

35.0 MaxDISSOLVED WATER (ASTM D1533) 6ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen 10ppm

120.0 MaxMethane 21ppm

65.0 MaxEthane 20ppm

50.0 MaxEthylene 19ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 643ppm

2500.0 MaxCarbon Dioxide 2012ppm

ReportNitrogen 64250ppm ReportOxygen 3874ppm

720.0 MaxTDCG 713ppm

ReportTDG 7.08%

0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.033%

25.0 MinINTERFACIAL TENSION (ASTM D971) 29.3mN/m

40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 24kV

1.5 MaxCOLOR (ASTM D1500) 3.0ASTM

whose obligation is limited to good faith performance.

KN6A-A 219801 TRO

140R3023F0043

01-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

Hoover NVLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

SMITH & LOVELESS INC

TRANFORMER OIL

UNKNOWN

UNKNOWN

230 kV

UNKNOWN

1734740

SAMPLE Nº: 4457-1-16-2

COMMENTS

• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.

• Color change due to oxidation, deterioration or contamination of the oil.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734740UNIT

SPECTROSCOPY (ASTM D5185)

ReportNa 2ppm ReportSn 1ppm

0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g

ReportSPECIFIC GRAVITY (ASTM D4052) 0.8847g/ml

35.0 MaxDISSOLVED WATER (ASTM D1533) 6ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen 7ppm

120.0 MaxMethane 5ppm

65.0 MaxEthane 1ppm

50.0 MaxEthylene 1ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 90ppm

2500.0 MaxCarbon Dioxide 695ppm

ReportNitrogen 10235ppm ReportOxygen <500ppm

720.0 MaxTDCG 104ppm

ReportTDG 1.1%

0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.032%

25.0 MinINTERFACIAL TENSION (ASTM D971) 29mN/m

40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 27kV

whose obligation is limited to good faith performance.

KN6A-B 219800 TRO

140R3023F0043

01-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

Hoover NVLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

SMITH & LOVELESS INC

TRANFORMER OIL

UNKNOWN

UNKNOWN

230 kV

UNKNOWN

1734742

SAMPLE Nº: 4457-1-17-2

COMMENTS

• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.

• Color change due to oxidation, deterioration or contamination of the oil.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734742UNIT

SPECTROSCOPY (ASTM D5185)

ReportP 1ppm ReportNa 4ppm

0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g

ReportSPECIFIC GRAVITY (ASTM D4052) 0.8847g/ml

35.0 MaxDISSOLVED WATER (ASTM D1533) 6ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen 12ppm

120.0 MaxMethane 6ppm

65.0 MaxEthane 2ppm

50.0 MaxEthylene 1ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 110ppm

2500.0 MaxCarbon Dioxide 864ppm

ReportNitrogen 14682ppm ReportOxygen <500ppm

720.0 MaxTDCG 131ppm

ReportTDG 1.57%

0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.035%

25.0 MinINTERFACIAL TENSION (ASTM D971) 29.1mN/m

40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 26kV

whose obligation is limited to good faith performance.

KN6A-C 219799 TRO

140R3023F0043

01-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

Hoover NVLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

SMITH & LOVELESS INC

TRANFORMER OIL

UNKNOWN

UNKNOWN

230 kV

UNKNOWN

1734743

SAMPLE Nº: 4457-1-18-2

COMMENTS

• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.

• Color change due to oxidation, deterioration or contamination of the oil.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734743UNIT

SPECTROSCOPY (ASTM D5185)

ReportP 1ppm ReportPb 1ppm ReportNa 3ppm

0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g

ReportSPECIFIC GRAVITY (ASTM D4052) 0.8848g/ml

35.0 MaxDISSOLVED WATER (ASTM D1533) 5ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen 7ppm

120.0 MaxMethane 5ppm

65.0 MaxEthane 1ppm

50.0 MaxEthylene 1ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 105ppm

2500.0 MaxCarbon Dioxide 1240ppm

ReportNitrogen 16813ppm ReportOxygen 938ppm

720.0 MaxTDCG 119ppm

ReportTDG 1.91%

0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.039%

25.0 MinINTERFACIAL TENSION (ASTM D971) 29.2mN/m

40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 28kV

whose obligation is limited to good faith performance.

KN8A-A 219802 TRO

140R3023F0043

01-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

Hoover NVLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

SMITH & LOVELESS INC

TRANFORMER OIL

UNKNOWN

UNKNOWN

230 kV

UNKNOWN

1734744

SAMPLE Nº: 4457-1-19-2

COMMENTS

• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.

• Color change due to oxidation, deterioration or contamination of the oil.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734744UNIT

SPECTROSCOPY (ASTM D5185)

ReportP 1ppm ReportNa 3ppm ReportMo 1ppm

0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g

ReportSPECIFIC GRAVITY (ASTM D4052) 0.8856g/ml

35.0 MaxDISSOLVED WATER (ASTM D1533) 6ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen 6ppm

120.0 MaxMethane 8ppm

65.0 MaxEthane 4ppm

50.0 MaxEthylene 1ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 80ppm

2500.0 MaxCarbon Dioxide 603ppm

ReportNitrogen 14456ppm ReportOxygen <500ppm

720.0 MaxTDCG 99ppm

ReportTDG 1.52%

0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.051%

25.0 MinINTERFACIAL TENSION (ASTM D971) 29.5mN/m

40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 18kV

whose obligation is limited to good faith performance.

KN8A-B 219803 TRO

140R3023F0043

01-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

Hoover NVLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

SMITH & LOVELESS INC

TRANFORMER OIL

UNKNOWN

UNKNOWN

230 kV

UNKNOWN

1734745

SAMPLE Nº: 4457-1-20-2

COMMENTS

• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.

• Color change due to oxidation, deterioration or contamination of the oil.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734745UNIT

SPECTROSCOPY (ASTM D5185)

ReportP 1ppm ReportNa 4ppm

0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g

ReportSPECIFIC GRAVITY (ASTM D4052) 0.8856g/ml

35.0 MaxDISSOLVED WATER (ASTM D1533) 6ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen 10ppm

120.0 MaxMethane 4ppm

65.0 MaxEthane 2ppm

50.0 MaxEthylene 1ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 63ppm

2500.0 MaxCarbon Dioxide 564ppm

ReportNitrogen 64934ppm ReportOxygen 11760ppm

720.0 MaxTDCG 80ppm

ReportTDG 7.73%

0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.032%

25.0 MinINTERFACIAL TENSION (ASTM D971) 29.3mN/m

40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 29kV

whose obligation is limited to good faith performance.

KN8A-C 219804 TRO

140R3023F0043

01-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

HOOVER NVLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

SMITH & LOVELESS INC

TRANFORMER OIL

UNKNOWN

UNKNOWN

230 kV

UNKNOWN

1734746

SAMPLE Nº: 4457-1-21-2

COMMENTS

• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.

• Color change due to oxidation, deterioration or contamination of the oil.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734746UNIT

SPECTROSCOPY (ASTM D5185)

ReportP 1ppm ReportNa 3ppm

0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g

ReportSPECIFIC GRAVITY (ASTM D4052) 0.8853g/ml

35.0 MaxDISSOLVED WATER (ASTM D1533) 5ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen <2ppm

120.0 MaxMethane 4ppm

65.0 MaxEthane 1ppm

50.0 MaxEthylene 1ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 64ppm

2500.0 MaxCarbon Dioxide 496ppm

ReportNitrogen 10302ppm ReportOxygen <500ppm

720.0 MaxTDCG 70ppm

ReportTDG 1.09%

0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.021%

25.0 MinINTERFACIAL TENSION (ASTM D971) 29.5mN/m

40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 34kV

whose obligation is limited to good faith performance.

NV Spare 10 GMB202710 TRO 140R3023F0043

01-Jul-2024

JASON FYFFE 22-Jul-2024

16-Jul-2024HOOVER DAM

TRIBOLOGIK

Sample InformationCustomer Information

CUSTOMER:

PLANT:

PO #:

CONTACT:

LABNO:

REPORT DATE:

MACHINE:

OIL TYPE:

SAMPLE DATE:

RECEIVED DATE:

SPEC LIMITS:

MINERAL

Machine Information

MACHINE:

Oil Type:

Hoover NVLocation:

Model:

Manufacturer: Age/Years:

Operating Hours:

Oil Manufacturer:

Oil Capacity:

Voltage:

Power:

WESTINGHOUSE

TRANFORMER OIL

UNKNOWN

UNKNOWN

230 kV

UNKNOWN

1734747

SAMPLE Nº: 4457-1-22-2

COMMENTS

• Please check and eliminate the source of the contamination (water, dirt) which affects the dielectric breakdown.

• All limits derived from IEEE C57.104 & IEEE C57.106 specifications.

RESULTS

TEST NAME SPEC1734747UNIT

SPECTROSCOPY (ASTM D5185)

ReportPb 1ppm ReportNa 3ppm ReportMo 1ppm

0.2 MaxACID N° (ASTM D974) 0.03mg KOH/g

ReportSPECIFIC GRAVITY (ASTM D4052) 0.8852g/ml

35.0 MaxDISSOLVED WATER (ASTM D1533) 5ppm

DISSOLVED GAS ANALYSIS (ASTM D3612)

100.0 MaxHydrogen 3ppm

120.0 MaxMethane 3ppm

65.0 MaxEthane 1ppm

50.0 MaxEthylene 1ppm

1.0 MaxAcethylene <1ppm

350.0 MaxCarbon Monoxide 23ppm

2500.0 MaxCarbon Dioxide 137ppm

ReportNitrogen 42445ppm ReportOxygen <500ppm

720.0 MaxTDCG 31ppm

ReportTDG 4.26%

0.5 MaxPOWER FACTOR 25 °C (ASTM D924) 0.027%

25.0 MinINTERFACIAL TENSION (ASTM D971) 26.5mN/m

40.0 MinDIELECTRIC BREAKDOWN 2MM (ASTM D1816) 28kV

1.5 MaxCOLOR (ASTM D1500) 1.5ASTM