B09_Attachment_11_Inspection_Report_3100-037S1107_-_Violettes_Lock_Bridge__2_0001.pdf
PDF 2 MB Posted
- Solicitation number
- 140P3026R0002
About this file
This is a Bridge Inspection Report for Violettes Lock Bridge #2, a steel multi-beam structure spanning Inlet Lock 2 at Lock 23 in C&O Canal National Historical Park, Maryland. The routine inspection was conducted on December 8, 2025, by the Federal Highway Administration's Office of Bridges and Structures. The bridge, built in 1955, is 18.5 feet long with a deck width of 18.3 feet and carries a service road over the inlet lock. The structure is rated as Priority C (Moderate) for improvement, with an overall fair condition assessment.
The primary deficiency identified is widespread paint deterioration with laminar rusting and section loss from the steel beams, particularly at the beam ends where exterior beams are completely buried and holding moisture. Additional significant issues include deterioration of mortar joints in the lock wall masonry with stone displacement and vegetation growth, deterioration of timber deck planks and bridge railings, debris accumulation on the deck and bearing seats, and a severed hold-down cable on the west side of the south abutment. The bridge's railing system does not meet current safety guidelines. Recommended corrective actions include removing soil and debris accumulation ($2,000), removing vegetation growth ($2,000), repointing masonry mortar joints ($20,000), and cleaning and painting structural steel ($20,000), with contract costs for mobilization and contingencies ($20,000). The total preliminary cost estimate is $64,000, typically needed within five years. Current load ratings are 34.0 tons inventory and 58.0 tons operating for HS truck loads.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BRIDGE INSPECTION REPORT
VIOLETTES LOCK BRIDGE #2
SERVICE ROAD OVER INLET LOCK 2
C&O CANAL NATIONAL HISTORICAL PARK
LOOKING NORTH
STRUCTURE NO. 3100-037S
INSPECTION TYPE: ROUTINE
INSPECTION DATE: 12/8/2025
EAST (DOWNSTREAM) SIDE
Report prepared by:
Federal Highway Administration FLH Office of Bridges and Structures Bridge Inspection Program 22001 Loudoun County Parkway, Building E2, Suite 200 Ashburn, VA 20147 https://bridge.flhd.fhwa.dot.gov https://bridge.flhd.fhwa.dot.gov
STRUCTURE SUMMARY STRUCTURE NO. 3100-037S
INSPECTION DATE. 12/08/2025VIOLETTES LOCK BRIDGE #2
BRIDGE IDENTIFICATION AND DESCRIPTION
MAIN SPAN MATERIAL: 3 - STEEL NO. OF MAIN SPANS: 001
MAIN SPAN TYPE: 02 - STRINGER/MULTI-BEAM OR NO. OF APPR. SPANS: 0
GIRDER
# OF BEAMS, MAIN SPAN: 6 STRUCT. TOTAL LENGTH: 18.5 FT ( 5.6 M)
DECK TYPE: 8 - WOOD OR TIMBER MAX. SPAN LENGTH: 17 FT ( 5.2 M)
WEARING SURFACE: 7 - WOOD OR TIMBER DECK WIDTH: 18.3 FT ( 5.6 M)
ABUT. FOUNDATIONS: 0 - UNKNOWN CURB TO CURB WIDTH: 17.3 FT ( 5.3 M)
PIER FOUNDATION(S): 6 - N/A YEAR BUILT: 1955
ABUTMENT / PIER MAT'L: 4 - MASONRY YEAR RECONSTRUCTED:
PROJ./PLAN REF. NO: 00000000 / NONE SKEW ANGLE: 0 °
NPS ROAD CLASS: 6 - RESTRICTED FRACTURE CRITICAL: N
STRUCTURE HISTORY:
LOCATION
C&O CANAL NATIONAL HISTORICAL PARK MILE POINT: .00 (KM PT 0 )
STATE: 243 - MARYLAND LOCATION: Adjacent to Lock 23 (Violettes Lock) - River
Road to Violettes Lock Road to end.FACILITY CARRIED: SERVICE ROAD
FEATURE INTERSECTED: INLET LOCK 2
INSPECTION TEAM: Sheila Arias-Roman, Cole Maurer
TEAM LEADER
Cole Maurer
REPORT REVIEWER
Marcus Miller
REPORT APPROVER 02/17/2026
Jorgomai Ceesay
STRUCTURE EVALUATION SUMMARY
This steel multi-beam bridge, which spans the walls of Inlet Lock 2 at Lock 23, is in fair condition overall. The main problem is widespread deterioration of the paint with laminar rusting and section loss from the steel beams. The ends of the exterior beams are also buried, holding moisture against the beams. If the beams are not cleaned and repainted, the section loss could lead to an eventual reduction in the load-carrying capacity of the structure.
Other problems include deterioration of the mortar joints in the lock walls with displacement of several stones and vegetation growing from several of the joints; deterioration of the timber deck planks and bridge rails; and debris accumulation on the deck surface and the abutment bearing seats. It should also be noted that the hold-down cable on the west side of the south abutment has been severed.
Since the previous inspection, new timber runner planks have been installed and gravel has been placed at the south approach.
STRUCTURE SUMMARY STRUCTURE NO. 3100-037S
VIOLETTES LOCK BRIDGE #2 INSPECTION DATE. 12/08/2025
Corrective action should be taken as outlined in this report to prevent the possible development of more serious or costly problems in the future.
RECOMMENDATIONS AND ESTIMATED COSTS STRUCTURE NO. 3100-037S
VIOLETTES LOCK BRIDGE #2 INSPECTION DATE : 12/08/2025
PRIORITY OF IMPROVEMENT 226
A (Critical) - Structure is closed, in immediate damage of collapse, or presents a critical safety danger.
B (Major) - Structure is seriously deficient or presents a safety hazard, but can remain open at reduced loads or with frequent inspections.
C (Moderate) - Structure is deficient, functionally obsolete, or requires substantial repairs to prevent a serious deficiency or unsafe condition.
D (Minor) - Structure is generally in good condition. Preventive maintenance may be required.
E (Special) - Structure is under construction or reconstruction.
C
Item No.
Maintenance Recommendations
(GENERALLY NOT FLHP ELIGIBLE)
QTY. UNIT UNIT
COST
PRELIM.
COST
ESTIMATE
58.7,60.3 REMOVE SOIL AND DEBRIS ACCUMULATION FROM DECK
SURFACE AND ABUTMENT BEARING SEATS. 1 LS 2000 2000
60.1,60.3,
223.1 REMOVE TREE AND VEGETATION GROWTH FROM LOCK
WALLS AND BEARING SEATS. 1 LS 2000 2000
PRELIM. MAINTENANCE TOTAL : 4000
Item No.
REHABILITATION/RECONSTRUCTION
(TYPICALLY NEEDED WITHIN 5 YEARS)
QTY. UNIT
UNIT
COST
PRELIM. COST ESTIMATES
REHAB RECONSTR
60.1,223.
REPOINT LOCK WALL MASONRY MORTAR
JOINTS AS NECESSARY. 1 LS 20000 20000
59.2,59.7 CLEAN AND PAINT STRUCTURAL STEEL.
1 LS 20000 20000
CONTRACT COSTS FOR MOBILIZATION,
TRAFFIC CONTROL, AND CONTINGENCIES. 1 LS 20000 20000
PRELIM. REHABILITATION/RECONSTRUCTION TOTAL : 60000
COST ESTIMATE SUMMARY
PRELIM. MAINTENANCE TOTAL :
PRELIM. REHABILITATION TOTAL :
PRELIM. RECONSTRUCTION TOTAL : .. 0
TOTAL ITEMIZED COSTS:
PRELIMINARY ESTIMATE TOTAL * :
(*Includes typical contract costs for mobilization, traffic control and design/construction engineering: but does not include detour bridges, work beyond the bridge limits, or work not listed above. Estimates are approximate and are for planning purposes only; they should not be used as a complete or final engineers estimate.)
Remarks : Cost estimates assume that recommended actions will be combined with similar work being performed on other structures.
FIELD INSPECTION REPORT STRUCTURE NO. 3100-037S
VIOLETTES LOCK BRIDGE #2 INSPECTION DATE: 12/08/2025
58. DECK
1. DECK SLAB
4. RIDEABILITY
5. CURBS, SIDEWALKS, AND MEDIAN
6. PARAPETS AND/OR RAILINGS
7. DRAINS AND DRAINAGE
8. UTILITIES
9. DEFLECTION AND/OR VIBRATION
10.OTHER:
59. SUPERSTRUCTURE
1. BEARING DEVICES
2. GIRDERS OR BEAMS
3. ARCH(ES) OR SLAB(S)
4. FLOOR BEAMS AND STRINGERS
5. TRUSSES
6. DIAPHRAGMS AND BRACING
7. PAINT
8. FASCIA(E)
9. DEFLECTION AND/OR VIBRATION
10.ALIGNMENT
11.OTHER
60. SUBSTRUCTURE
61. CHANNEL
1. ALIGNMENT
2. EROSION AND/OR SCOUR
3. CHANNEL PROTECTION
4. WATERWAY OBSTRUCTIONS
5. OTHER
6. ADEQUACY OF OPENING
7. NORMAL VELOCITY
8. AVERAGE CLEAR OPENING
9. STREAMBED COMPOSITION:
222. APPROACHES
1. APPROACH SLABS
2. RELIEF JOINTS
3. APPROACH GUARDRAIL
4. SURFACING
5. EROSION
6. SETTLEMENT
7. SIGNS
8. ALIGNMENT
9. OTHER
223. RETAINING WALL
1. WALL
2. WEEP HOLES
3. FOUNDATION
4. EROSION AND/OR SCOUR
5. SETTLEMENT OR DEFLECTION
6. OTHER
F
G
F
F
F
G
N
N
F
N
N
N
N
P
N
G
G
P
G
G
N
G
N
1- SUFF
3 - LOW
N
N
N
G
G
N
G
N
F
N
N
G
G
F
N
2. EXPANSION JOINTS N
3. WEARING SURFACE G
N
HOLD-DOWN CABLES
14 FT
CONDITION RATING CODE EQUIVALENTS FOR SUB-ELEMENTS
G = GOOD (CODES 7 - 9) F = FAIR (CODES 5 - 6) P = POOR (CODES 0 - 4)
CONDITION RATING CODES FOR ITEMS 58 - 62, 222, 223
NOT APPLICABLEN
EXCELLENT CONDITION9
VERY GOOD CONDITION - no problems noted.8
GOOD CONDITION - some minor problems.7
SATISFACTORY CONDITION - structural elements show some minor deterioration.6
FAIR CONDITION - all primary structural elements are sound but may have minor section loss, cracking, spalling, or scour.
POOR CONDITION - advanced section loss, deterioration, spalling, or scour.4
SERIOUS CONDITION - loss of section, deterioration, spalling, or scour have seriously affected primary structural components. Local failures are possible. Fatigue cracks in steel or shear cracks in concrete may be present.
CRITICAL CONDITION - advanced deterioration of primary structural elements. Fatigue cracks in steel or shear cracks in concrete may be present or scour may have removed substructure support. Unless closely monitored it may be necessary to close the structure until corrective action can be taken.
“IMMINENT” FAILURE CONDITION - major deterioration or section loss present in critical structural components or obvious vertical or horizontal movement affecting structure stability.
Structure is closed to
FAILED CONDITION - out of service; beyond corrective action.0
SILT
1. BREASTWALLS OR COLUMNS F
2. PILE BENTS N
3. CAPS AND/OR BEARING SEATS F
4. BACKWALLS AND/OR BULKHEADS F
5. FOUNDATIONS N
6. WINGWALLS N
7. WEEP HOLES N
8. EXPANSION JOINTS N
9. EROSION AND/OR SCOUR G
10.SETTLEMENT OR DEFLECTION G
11.SLOPE PROTECTION N
12.OTHER N
ABUTMENTS
PIER(S)
13. WALLS AND/OR COLUMNS
14.PILE BENTS
15.CAPS AND/OR BEARING SEATS
16.FOUNDATIONS
17.EROSION AND/OR SCOUR
18.SETTLEMENT OR DEFLECTION
19.OTHER
36. TRAFFIC AND SAFETY FEATURES
A. BRIDGE RAILINGS:
B. TRANSITIONS:
C. APPROACH GUARDRAILS:
D. APPROACH GUARDRAIL ENDS:
N
N
N
N
N
N
N
N
N
N
TRAFFIC SAFETY RATING CODES
0 - Does not meet standards or a safety features is required and none is provided.
1 - Meets currently acceptable standards.
N - Not applicable or a safety features is not required.
FIELD INSPECTION REPORT STRUCTURE NO. 3100-037S
ITEM REFERENCE AND REMARKS
58.1 MINOR TO MODERATE CHECKING AND DETERIORATION OF TIMBER DECK PLANKS WITH MINOR DECAY IN SEVERAL LOCATIONS.
WIDESPREAD MOLD GROWTH ON DECK PLANK ENDS AND DECK UNDERSIDE. MINOR DETERIORATION AND SPLITTING AT THE
WEST END OF SOUTH DECK PLANK.
58.3 TIMBER RUNNERS HAVE BEEN REPLACED SINCE PREVIOUS INSPECTION. MINOR CHECKING OF TIMBER RUNNER PLANKS.
MINOR SPLINTERING OF EAST PLANK IN EAST RUNNERS.
58.5
58.6
MODERATE TO SEVERE WEATHERING AND CHECKING OF TIMBER CURBS. SPLIT IN WEST CURB NEAR SOUTH END. MINOR TO MODERATE CHECKING OF TIMBER RAILINGS. TOP HORIZONTAL RAIL BOARD BEGINNING TO SEPARATE FROM TOP VERTICAL
RAIL BOARD. MODERATE LATERAL DEFLECTION OF RAILINGS.
58.7 MINOR DEBRIS ACCUMULATION BETWEEN DECK PLANKS, UNDER CURBS, AND ON DECK SURFACE BETWEEN RUNNERS.
59.2
59.7
ENDS OF EXTERIOR BEAMS COMPLETELY BURIED AT ABUTMENTS. BRIDGE LIKELY BUILT FROM SALVAGED STEEL; PUNCHED
HOLES IN WEBS OF BEAM ENDS AND RIVETED RAIL BRACKETS PRESENT.
WIDESPREAD MODERATE PAINT FAILURE WITH LAMINAR RUSTING OF BEAMS WITH ACTIVE SECTION LOSS FROM BEAM BOTTOM FLANGES (1/2" ORIGINAL, AS LOW AS 3/16" REMAINING) AND BOTTOM OF WEBS (5/16" ORIGINAL, AS LOW AS 1/16" REMAINING) AT ENDS FOR 2'. MODERATE RUSTING WITH SECTION LOSS FROM TOP FLANGES OF BEAMS (1/2" ORIGINAL, AS LOW
AS 7/16" REMAINING) FOR ENTIRE LENGTH.
GAP, UP TO 3/16", BETWEEN TOP FLANGE OF BEAM #1 AND TIMBER NAILER EXTENDING 8' FROM NORTH ABUTMENT.
59.11 HOLD-DOWN CABLES AT WEST CORNERS OF BRIDGE HAVE RUSTING. SOUTH CABLE COMPLETELY SEVERED.
60.1
223.1
STONE MASONRY LOCK WALLS SERVE AS ABUTMENT BREASTWALLS AND RETAINING WALLS. MINOR TO MODERATE DETERIORATION AND FRACTURING OF MASONRY STONES AT ISOLATED LOCATIONS. FRACTURED MASONRY STONE IN NORTH ABUTMENT WALL BELOW BEAM #4. WIDESPREAD MINOR DETERIORATION OF LOCK WALL MASONRY MORTAR JOINTS, PRIMARILY NEAR TOP, WITH MINOR VEGETATION GROWTH. NO MORTAR PRESENT IN JOINTS ALONG WATERLINE. WIDESPREAD
MOLD GROWTH ON LOCK WALLS BENEATH STRUCTURE.
60.3 MODERATE TO HEAVY SOIL AND DEBRIS ACCUMULATION ON ABUTMENT BEARING SEATS. TREE GROWING FROM SOUTH
ABUTMENT BEARING SEAT AT EAST END.
60.4 TIMBER BACKWALL PLANKS AT BOTH ABUTMENTS IN GOOD CONDITION.
61.4 SOME MINOR DEBRIS IN CHANNEL BELOW STRUCTURE.
222.4
222.6
STABILIZED SOIL AND GRAVEL APPROACHES; GRAVEL SURFACING ADDED TO SOUTH APPROACH SINCE PREVIOUS INSPECTION, UP TO 6-1/2" OF SETTLEMENT OF SOUTH APPROACH SURFACING AT DECK SIDES. GRAVEL SURFACING AT NORTH
APPROACH IN GOOD CONDITION.
222.5 MINOR EROSION AT CORNERS OF APPROACHES, MOST PROMINENT AT SOUTH APPROACH.
36.A BRIDGE RAILING SYSTEM DOES NOT MEET CURRENT SAFETY GUIDELINES.
STRUCTURE LOAD RATING STRUCTURE NO. 3100-037S
TRUCK TYPE
INVENTORY RATING (NORMAL TRAFFIC) OPERATING RATING (MAXIMUM LOAD)
TONS METRIC TONS TONS METRIC TONS
H 19 17 32 29
HS 34 31 58 53
TYPE 3 29 26 49 44
TYPE 3S2 46 42 78 71
TYPE 3-3 57 52 96 87
DESIGN LOADING: 0 - UNKNOWN
CAPACITY MEETS OR EXCEEDS DESIGN LOAD
CAPACITY IS LESS THAN DESIGN LOAD
ORIGINAL LOAD RATING CALCULATION APPLICABLE
X ORIGINAL LOAD RATING CALCULATION REVISED
DATE OF LOAD RATING CALCULATION: 02/01/2021
LOAD RATING CONTROLLED BY: BEAM MOMENT CAPACITY
REMARKS: SEE BRIDGE FILE FOR LOAD RATING CALCULATIONS.
Joseph Reed Line
Joseph Reed Line
Joseph Reed Line
Joseph Reed Line
Joseph Reed Line
Joseph Reed Line
Joseph Reed Line
STRUCTURE INVENTORY AND APPRAISAL STRUCTURE NO. 3100-037S
STRUCTURE IDENTIFICATION
(1) STATE:............................................ 243 - MARYLAND
(2) STATE HWY. AGENCY DIST:
(201) PARK: C&O CANAL NATIONAL HISTORICAL PARK
(202) STRUCTURE NAME:..............VIOLETTES LOCK BRIDGE #2
(203) STRUCTURE KIND:............... 1 - BRIDGE
(204) STRUCTURE NUMBER:.........3100-037 S
2 - NATIONAL CAPITAL(205) NPS REGION:
(206) ROUTE CODE NUMBER:
(207) ROAD SECTION NO:............. 037S
(208) NPS ROAD CLASS:............... 6 - RESTRICTED
(209) WITHIN NPS BNDRY?:.......... Yes
(210) OPERATING UNIT:.................PARK
(211) PROJECT NO(S):
(212) DRAWING NUMBERS:...........NONE
(21) MAINTAINED BY:......................66 - NATIONAL PARK SERVICE
(22) OWNER:................................... 66 - NATIONAL PARK SERVICE
(3) COUNTY CODE:
(4) CITY / PLACE CODE:
(5) INVENTORY ROUTE:
(6) FEATURES INTERSECTED:
(7) FACILITY CARRIED:
(8) STATE STRUCTURE NO:
(9) LOCATION:
(10) INV. RTE. - MIN. VERT. CLR:
(11) MILE POINT:
(27) YEAR BUILT:
(106) YEAR RECONSTRUCTED:
(20) TOLL:
(37) HISTORIC DESIGNATION:
24031 MONTGOMERY
00000
1 8 0 00000 0
INLET LOCK 2
SERVICE ROAD
3100037S0000000
Adjacent to Lock 23 (Violettes Lock) - River Road to Violettes Lock Road to end.
99.99 FT ( 99.99 M)
.00 (KM PT: 0 )
3 - ON FREE ROAD
5 - NOT ELIGIBLE
STRUCTURE DESCRIPTION, FOUNDATION, AND DECK TYPE
(43A) MAIN STR. MATERIAL:..........3 - STEEL (44A) APPR. STR. MATERIAL:............ 0 - Other
(43B) MAIN STR. TYPE:.................. 02 - STRINGER/MULTI-BEAM OR (44B) APPR. STR. TYPE:.................... 00 - OTHER
GIRDER
(45) NO. OF MAIN SPANS:..............001 (46) NO OF APPROACH SPANS:
(48) MAX. SPAN LENGTH:..............17 FT ( 5.2 M)
(49) STRUCTURE LENGTH:........... 18.5 FT ( 5.6 M) (108) WEAR SURFACE/PROTECT SYSTEM:
(216A) ABUTMENT #1 FDN:........... 0 - UNKNOWN A) TYPE WEARING SURFACE:.. 7 - WOOD OR TIMBER
(216B) ABUTMENT #2 FDN:........... 0 - UNKNOWN B) TYPE MEMBRANE:................. 0 - NONE
(217A) PREDOM. PIER FDN:.......... 6 - N/A C) TYPE PROTECTION:.............. 0 - NONE
(217B) SECOND. PIER FDN:.......... 6 - N/A (218) IS SALT USED?.......................... NO
(107) DECK TYPE:.......................... 8 - WOOD OR TIMBER
LOAD RATING AND POSTING
(31) DESIGN LOAD:.........................0 - UNKNOWN (41) LOAD RESTRICTION:.................. A - OPEN
(66) INVENTORY RATING:..............34.0 METRIC TONS) (70) BRIDGE POSTING:...................... 5 - EQUAL TO OR ABOVE LEGALTONS ( 30.8
LOADS
(64) OPERATING RATING:..............58.0 TONS ( 52.6 METRIC TONS)
INSPECTION DATES
(90) INSPECTION DATE: 12/08/2025 (91) FREQ. OF INSP: 24 MONTHS (92 / 93) CRITICAL FEATURE INSPECTION (CFI):
(219) ADD. STUDIES NEEDED: N - 0 - NONE (A) FRACTURE CRITICAL:.......... N
(220) SPECIAL STUDY TYPE: 0 - NONE INSP. EVERY MONTHS - LAST INSP:
(221) SPECIAL STUDY DATE: (B) UNDERWATER:..................... N
INSP. EVERY MONTHS - LAST INSP:
(C) SPECIAL INSPECTION:........ N
INSP. EVERY MONTHS - LAST INSP:
https://RATING:
https://RATING:
STRUCTURE INVENTORY AND APPRAISAL STRUCTURE NO. 3100-037S
GEOMETRY, TRAFFIC, AND NAVIGATIONAL DATA
(16) LATITUDE:................................ 39° 04'01.00" (51) CURB TO CURB WIDTH:............ 17.3 FT ( 5.3 M)
(17) LONGITUDE:............................ 77°19 '42.90" (52) DECK WIDTH:.......................... 18.3 FT ( 5.6 M)
(19) DETOUR LENGTH:.................. 99 MI ( 159 KM) (32) APPR. ROADWAY WIDTH:...... 17.3 FT ( 5.3 M)
(28A) LANES ON STRUCT:.............01 (213) APPR. PAVEMENT WIDTH:... 17.3 FT ( 5.3 M)
(28B) LANES UNDER STRUCT:......00 LEFT SHOULDER:............... 0.0 FT ( 0 M)
(42A) SERVICE ON:.........................1 - HIGHWAY RIGHT SHOULDER:.......... 0.0 FT ( 0 M)
(42B) SERVICE UNDER:................. 5 - WATERWAY (33) BRIDGE MEDIAN:.................... 0 - NO MEDIAN
(29) AVG DAILY TRAFFIC:..............10 (34) SKEW ANGLE:......................... 0 °
(30) YEAR OF ADT:......................... 2025 (35) STRUCTURE FLARED:............ 0 - NO FLARE
(114) FUTURE ADT:.........................11 (47) TOTAL HORIZ. CLEARANCE:.. 17.3 FT ( 5.3 M)
(115) YEAR OF FUTURE ADT:........2045 (50) CURB OR SIDEWALK WIDTHS:
(101) PARALLEL STRUCTURE:......N - NO PARALLEL STRUCTURE LEFT:.................................... 0.0 FT ( 0 M)
(38) NAVIGATION CONTROL:.........0 RIGHT:.................................. 0.0 FT ( 0 M)
(39) VERTICAL CLEARANCE:.........0 FT ( 0 M) (214) BRIDGE RAIL TYPE
(40) HORIZ. CLEARANCE:..............0 FT ( 0 M) RAIL CONFIGURATION:...... 1 - FULL HEIGHT (NO PARAPET)
(111) ABUT OR PIER PROT:........... MATERIAL:........................... 7 - TIMBER
LATERAL UNDERCLEARANCE: DESIGN TYPE:..................... 1 - CONTINUOUS RAIL
(55) RIGHT:...............................00 FT ( 0 M) (215) BRIDGE RAIL HEIGHT:.......... 3.42 FT ( 1.04 M)
(56) LEFT:.................................0 FT ( 0 M) (53) MIN. VRT. CLR. OVER DECK: 99.99 FT ( 99.99 M)
(54) MIN. VRT. UNDRCLRANCE:... .00 FT ( 0 M)
CONDITION AND APPRAISAL DATA, PROPOSED IMPROVEMENTS, AND COST
(58) DECK:
(59) SUPERSTRUCTURE:
(60) SUBSTRUCTURE:
(61) CHANNEL:
(62) CULVERT:.................................N
(222) APPROACHES:
(223) RETAINING WALL:
(36) TRAFFIC SAFETY FEAT: 0 N N N
(75A) TYPE OF WORK:................... 35 - REHABILITATION - DETERIORATION
(75B) WORK DONE BY:.................. 2 - WORK TO BE DONE BY OWNER'S
FORCES
(76) IMPROVEMENT LENGTH:....... FT ( 0 M)
(67) STRUCTURAL EVALUATION:
(68) DECK GEOMETRY:
(69) UNDERCLEARANCES:................ N
(71) WATERWAY ADEQUACY:
(72) APPROACH ALIGNMENT:
(113) SCOUR CRITICAL:.................... 5 - SCOUR WITHIN LIMITS OF
FOOTING OR PILES
(225) PURPOSE OF IMPROVEMENT: 2 - REHAB/RECONSTRUCTION
(226) PRIORITY OF IMPROVEMENT: C - MODERATE
(227) MAINTENANCE COST:.............$ 4000
(228) REHAB / RECNSTR COST:..... $ 60000
(229) CONSTRUCTION COST:.......... $ 0
ADDITIONAL INFORMATION
(230) STRUCTURE HISTORY:
(231) ADDITIONAL CONSIDERATIONS:
(330) ADDITIONAL CONFIGURATION INFORMATION:
https://04'01.00
APPENDIX INSPECTION DATE. 12/08/2025
VIOLETTES LOCK BRIDGE #2 STRUCTURE NO. 3100-037S
Inspector: Cole Maurer Structure Number: 3100037S0000000
Inspection Date: 12/08/2025 Facility Carried: SERVICE ROAD
Bridge Inspection Report
Pictures
PHOTO 3
Description LOOKING SOUTH TOWARD POTOMAC RIVER (FROM 2021 REPORT)
PHOTO 4
Description WEST (UPSTREAM) SIDE (FROM 2021 REPORT)
Bridge Inspection Report
Pictures
PHOTO 5
Description GENERAL TOP SIDE VIEW LOOKING NORTH; NOTE NEW TIMBER RUNNERS
PHOTO 6
Description GENERAL UNDERSIDE VIEW LOOKING NORTH
Bridge Inspection Report
Pictures
PHOTO 7
Description TYPICAL SETTLEMENT OF APPROACH AT DECK CORNERS, SOUTHWEST CORNER
SHOWN
PHOTO 8
Description DETERIORATION OF SOUTH DECK PLANK; NOTE GRAVEL ACCUMULATION ON DECK
Bridge Inspection Report
Pictures
PHOTO 9
Description TYPICAL DETERIORATION OF TIMBER DECK PLANKS AND DEBRIS ACCUMULATION ON
DECK SURFACE
PHOTO 10
Description TYPICAL WEATHERING AND CHECKING OF TIMBER CURBS, WEST CURB AT MIDSPAN
SHOWN
Bridge Inspection Report
Pictures
PHOTO 11
Description TYPICAL CONDITION OF UNDERSIDE OF TIMBER DECK PLANKS; NOTE MOLD GROWTH
PHOTO 12
Description TYPICAL FRACTURING OF LOCK WALL MASONRY STONES, SOUTH LOCK WALL SHOWN;
NOTE VEGETATION GROWTH
Bridge Inspection Report
Pictures
PHOTO 13
Description GENERAL VIEW OF SOUTH ABUTMENT; NOTE MOLD GROWTH
PHOTO 14
Description TYPICAL CONDITION OF EXTERIOR BEAM ENDS, BEAM #1 AT SOUTH ABUTMENT SHOWN;
NOTE HOLD-DOWN CABLE COMPLETELY SEVERED
Bridge Inspection Report
Pictures
PHOTO 15
Description TYPICAL PUNCHED HOLES IN WEBS OF BEAM ENDS, BEAM #2 AT SOUTH ABUTMENT
SHOWN
PHOTO 16
Description TYPICAL SOIL AND DEBRIS ACCUMULATION ON ABUTMENT BEARING SEATS, SOUTH
ABUTMENT BETWEEN BEAMS #2 AND #3 SHOWN
Bridge Inspection Report
Pictures
PHOTO 17
Description TYPICAL PAINT FAILURE WITH RUSTING AND SECTION LOSS FROM BEAMS, WEST FACE
OF BEAM #5 AT SOUTH ABUTMENT SHOWN
PHOTO 18
Description TYPICAL SOIL ACCUMULATION ON EXTERIOR BEAM ENDS, BEAM #6 AT SOUTH
ABUTMENT SHOWN
Bridge Inspection Report
Pictures
PHOTO 19
Description TYPICAL PAINT FAILURE WITH RUSTING OF EXTERIOR BEAMS, WEST FACE OF BEAM #1
SHOWN
PHOTO 20
Description TYPICAL PAINT FAILURE WITH LAMINAR RUSTING OF BEAMS, EAST FACE OF BEAM #4
SHOWN
Bridge Inspection Report
Pictures
PHOTO 21
Description GAP BETWEEN TIMBER NAILER AND TOP FLANGE OF BEAM #1 AT NORTH ABUTMENT
PHOTO 22
Description TYPICAL PAINT FAILURE WITH RUSTING AND SECTION LOSS FROM BEAM ENDS, EAST
SIDE OF BEAM #3 AT NORTH ABUTMENT SHOWN
Bridge Inspection Report
Pictures
PHOTO 23
Description TYPICAL PAINT FAILURE WITH RUSTING AND SECTION LOSS FROM BEAM ENDS, EAST
SIDE OF BEAM #4 AT NORTH ABUTMENT SHOWN
PHOTO 24
Description TYPICAL DETERIORATION OF LOCK WALL MASONRY MORTAR JOINTS, NORTH LOCK
WALL SHOWN; NOTE VEGETATION GROWTH
Bridge Inspection Report
Pictures
PHOTO 25
Description GENERAL VIEW OF NORTH ABUTMENT; NOTE MOLD GROWTH
PHOTO 26
Description FRACTURED MASONRY STONE IN NORTH ABUTMENT BELOW BEAM #4
Bridge Inspection Report
Pictures
PHOTO 27
Description LOOKING UPSTREAM FROM DECK
PHOTO 28
Description LOOKING DOWNSTREAM FROM DECK
File details come from the government source that posted it. Updated .