Amendment_0006_Valve_Replacement.pdf

PDF 804 KB Posted

Attached to
Replace Primary Potable Water Pumps 1&2 Which Provides Water to the South Rim - Indian Garden
Solicitation number
140P2018R0105
Issued by

About this file

Amendment 0006_Valve Replacement

View the file

Other files

File Type Posted
SF30_Amendment_0008.pdf PDF
Q_and_A_Amendment_0008.pdf PDF
SF30_Amendment_0007.pdf PDF
Q_and_A_Amendment_0007.pdf PDF
SF30_Amendment_0006.pdf PDF
Q_and_A_Amendment_0006.pdf PDF
SF30_Amendment_0005.pdf PDF
Amendment_0005_Attachment_1.pdf PDF
SF30_Amendment_0004.pdf PDF
Pre-Proposal_Conference_Sign_In_Sheet_08.07.2018.pdf PDF
Q_and_A_Amendment_0004.pdf PDF
Amendment_0003_Revised_Section_J_08.02.18.pdf PDF
Attachment_7_Scope_of_Work_Sediment_Removal_and_Condition_Assessment.pdf PDF
SF30_Amendment_0003.pdf PDF
Amendment_0003_Revised_Contract_Price_Schedule.pdf PDF
SF30_Amendment_0002.pdf PDF
Amendment_0002_Section_J_of_RFP_08.02.18.pdf PDF
Attachment_1A_Specifications_Part_2_GRCA_182403_Div_02-49.pdf PDF
Amendment_0002_Technical_Specification_Section_01_11_00_1.9D_REVISED.pdf PDF
Attachment_5_IG_Pumphouses_Asbestos_and_LBP_Report_092816.pdf PDF
Attachment_6_Statement_of_Structural_Tests_and_Special_Inspections.pdf PDF
SF30_Amendment_0001_140P2018R0105_GRCA_182403.pdf PDF
02_80_00_Facility_Remediation_ACM_and_LBP_-_FINAL.pdf PDF
Attachment_1_Specifications_GRCA_182403.pdf PDF
Attachment_3_Construction_Wage_Determination.pdf PDF
Attachment_4_South_Rim_Map_with_Heli-base_location.pdf PDF
B08_Proposal_Submission_Package.zip ZIP file
Attachment_2_Drawings_GRCA_182403.pdf PDF
FINAL_RFP_GRCA_182403_Indian_Gardens_Phase_II.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Valve Replacement

This addendum includes replacing two existing valves in the South Pump House to facilitate construction. These valves are the North Pump House Isolation Valve and the 8” TCWL Borehole Isolation Valve. Locations of these valves are shown on the attached, edited Sheet D2 from the final CD package. In addition, attached is an installation detail.

Furnish, and install in the manner depicted in Figure A, two (2) gate valves specified within the Contract Documents and as supplemented below. The valves shall be class 900 valves with single valve by-pass, Class 900# RF, WCB Body, API Trim 5 Full Stellite, Bolted Bonnet, OS&Y, Hand Wheel Operated Gate Valve.

Gate Valves

Acceptable Manufacturers

1. Cameron/Newco.

2. Bonney Forge.

3. Or approved equal.

Materials

1. Body and Wedge: Cast Steel, ASTM A216-WCB

2. Coating/Lining: Epoxy, NSF 61 certified.

Design Requirements

1. Style: ASME B16.34/API 600 and ASME B16.10

2. Connections: ASME B16.5, Raised Face Flanges

3. Pressure Class: ANSI 900

4. Testing: API 598

5. Mounting Orientation: Vertical.

Accessories

1. Actuator: Handwheel, OS&Y, rising stem, stuffing box stem seal.

2. Bypass: Welded, factory installed.

a. Minimum size: 3/4-IN

b. Install bypass such that the stem of the main valve and bypass valve are parallel.

c. Bypass components and materials shall be rated for the same service as the main valve.