13 - Hazmat Report.pdf

PDF 2 MB Posted

Attached to
Y1LZ--TIERED SET-ASIDE - Parking Ramp Expansion Minor Construction - Buffalo VAMC 528-375
Solicitation number
36C77626R0046
Issued by

About this file

Summary: Pre-Renovation Hazardous Materials Inspection Report

This is a Pre-Renovation Asbestos-Containing Materials, Lead-Based Paint, and Exterior PCB-Containing Materials Inspection Report prepared by Encorus Group Engineering, P.C. for the Buffalo Veterans Affairs Medical Center Parking Garage Expansion project located at 3495 Bailey Avenue, Buffalo, NY 14215. The inspection was conducted on January 22 and February 7, 2024, to identify hazardous materials prior to renovation work. The report was prepared for Bancroft Architects + Engineers and documents conditions as of February 7, 2024.

The inspection covered three primary areas: asbestos-containing materials (ACM) identified using Polarized Light Microscopy and Transmission Electron Microscopy analysis; lead-based paint tested using X-Ray Fluorescence (XRF) with a Heuresis Corp. Pb200i analyzer at a 1.0 mg/cm² action level; and exterior PCB-containing caulks and sealants analyzed per EPA Method 8082. All sampled materials tested negative for asbestos contamination exceeding one percent. No lead-based painted or coated components meeting HUD/EPA standards (≥1.0 mg/cm² via XRF or ≥0.5% by weight) were detected within the scope of work. No suspect exterior PCB-containing materials were found. Eight asbestos samples and multiple lead-paint XRF readings were collected from functional spaces including the first, second, and third-floor garages, stair towers, roof, and upper roof areas. Laboratory analysis reports, chains of custody, certifications for Encorus Group's asbestos handling and lead-based paint activities licenses, and detailed XRF spectrum data are included in the appendices.

View the file

Other files

File Type Posted
36C77626R0046 0006.pdf PDF
0005 - Responses to Tech Questions - 5-21-26.pdf PDF
36C77626R0046 0005.pdf PDF
0005 - DBA Wages - Erie County - 05-18-2026.pdf PDF
0004 - SCA Wages - Erie County - 05-13-2026.pdf PDF
36C77626R0046 0004.pdf PDF
0004 - Responses to Tech Questions - 5-19-26.pdf PDF
36C77626R0046 0003.pdf PDF
0002 - Responses to Tech Questions - 5-14-26.pdf PDF
36C77626R0046 0002.pdf PDF
0001 - Electrical Redesign - Questions 11 and 70.pdf PDF
0001 - Site Visit Sign-in Sheet 4-22-26.pdf PDF
0001 - 36C77625R0023 Technical Questions - FINAL - Buffalo - 3-13-25 - UPDATED 5-1-26.pdf PDF
0001 - 1947 Soil Borings - Question 58.pdf PDF
0001 - 15A - SCA Wages - Erie County - 04-29-2026.pdf PDF
0001 - Subsurface Exploration Report - Question 58.pdf PDF
36C77626R0046 0001.pdf PDF
03 - Summary of Qualification Requirements.pdf PDF
06 - Drawings - Structural.pdf PDF
09 - Drawings - Plumbing.pdf PDF
14 - PCRA.pdf PDF
17 - Division Cost Breakdown.xlsx XLSX spreadsheet
18 - Site Visit Instructions.pdf PDF
01 - Specs Vol 1 of 2.pdf PDF
10 - Drawings - Mechanical.pdf PDF
12 - Drawings - Technology.pdf PDF
16 - Limitations on Subcontracting.pdf PDF
19 - Subcontracting Plan Template.docx DOCX document
02 - Specs Vol 2 of 2.pdf PDF
04 - Drawings - General.pdf PDF
05 - Drawings - Civil.pdf PDF
08 - Drawings - Fire Protection.pdf PDF
15 - DBA Wages - Erie County - 01-02-2026.pdf PDF
RFP 36C77626R0046 - 4-7-26.pdf PDF
07 - Drawings - Architectural.pdf PDF
11 - Drawings - Electrical.pdf PDF
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

23 Mechanic Street Springville, NY 14141

295 Main Street West Seneca, NY 14224 encorus.com 716.592.3980

Encorus Group is a Service-Disabled Veteran-Owned Small Business.

February 20, 2024

John Robbins Bancroft Architects + Engineers 3300 Dundee Road, Northbrook, IL 60062

Re: Pre-Renovation Asbestos-Containing Materials, Lead-Based Paint, Exterior PCB-

Containing Materials and Inspection Report Buffalo VAMC – Parking Ramp Expansion Project No. 528-375 BAE Project No. 21-113 3495 Bailey Avenue Buffalo, NY 14215 Encorus #24033

Dear John Robbins:

Enclosed please find a copy of the Asbestos-Containing Materials, Lead-Based Paint and Exterior PCB-Containing Materials Inspection Report for the Buffalo VAMC – Parking Ramp Expansion located at 3495 Bailey Avenue in Buffalo, New York. Should you have any questions please do not hesitate to contact our office at 716.592.3980. Thank you for the opportunity to be of service to Bancroft Architects + Engineers.

Sincerely, Sean Fitzgerald RBM Lead

Enclosures

Pre-Renovation Asbestos-Containing Materials, Lead-Based Paint and Exterior PCB-Containing Materials

Inspection Report

OF THE:

Buffalo VAMC – Parking Ramp Expansion 3495 Bailey Avenue Buffalo, NY 14215

Project No. 528-375 BAE Project No. 21-113

Encorus#24033

PREPARED BY:

PREPARED FOR:

3300 Dundee Road, Northbrook, IL 60062

CONDITIONS AS OF:

February 7, 2024

295 Main Street West Seneca, NY 14224 encorus.com

Table of Contents

1 Introduction

2 Asbestos-Containing Materials Inspection

2.1 Methodology

2.2 Executive Summary

2.3 Confirmed Asbestos-Containing Materials

2.4 Assumed Asbestos-Containing Suspect Materials

2.5 Confirmed Non-Asbestos Containing Materials

2.6 Summary Table of Asbestos-Containing Materials

3 Lead-Based Paint Inspection

3.1 Methodology

3.2 HUD/ EPA Standards

3.3 Summary Table of Lead-Based Painted/Coated Materials

3.4 OSHA Regulations

3.5 Disclosure Requirements

4 PCB Inspection

4.1 Methodology

4.2 Suspect PCB-Containing Materials

Appendices A. General Conditions of Inspection B. Certifications and Licenses C. Chains of Custody and Laboratory Reports D. XRF Spectrum Analyzer Report and Instrument Information E. Sample Floor Plans F. Summary of Inspected Functional Spaces

295 Main Street West Seneca, NY 14224 encorus.com

1 Introduction

Encorus Group Engineering, P.C. (Encorus Group) was retained by Bancroft Architects + Engineers to perform an inspection of the Buffalo Veterans Affairs Medical Center Parking Garage located at 3495 Bailey Avenue in Buffalo, New York, to determine the presence of asbestos-containing materials, lead-based painted/coated materials and exterior PCB-containing caulks, glazing and sealants prior to work associated with the Buffalo VAMC – Parking Ramp Expansion project.

The inspection was conducted on January 22 and February 7, 2024.

The scope of inspection work provided is as indicated in the proposal for Inspection Services dated October 16, 2023 and includes the following:

The project scope of work is to correct parking system deficiencies at the Buffalo VAMC and increase parking capacity as much as possible. Sienna’s scope of work is to perform hazardous materials inspection and abatement design services (if necessary) as part of the investigation of existing conditions and systems related to the existing Parking Ramp Building 29. Investigation is required to determine where the parking ramp connects to the Main Hospital Building 1, and Support Buildings 2 and 3.

Encorus Group was charged with conducting the following tasks for this project:

1. Conducting an asbestos inspection in accordance with all applicable regulations,

2. Performing an inspection via X-Ray Florescence (XRF) for lead in accordance with all applicable regulations and guidelines,

3. Sampling exterior caulks, glazing and sealants for PCB-containing materials in accordance with all applicable regulations and guidelines, and

4. Providing a summary report of findings.

This report is generated for the exclusive use of the client and is not designed to serve as a specification for abatement. The owner is strongly encouraged to contract with a consultant having a current Asbestos Project Designer Certificate as issued by New York State Department of Labor for the preparation of contract specifications, work plans, and/or drawings prior to requesting bids for the abatement or removal of the materials identified in this report.

295 Main Street West Seneca, NY 14224

2 Asbestos-Containing Materials Inspection

2.1 Methodology

All asbestos inspection work performed by Encorus Group was conducted in accordance with applicable regulations including New York State Department of Labor standards 12 NYCRR Part 56, National Emission Standards for Hazardous Air Pollutants (NESHAPS), the Asbestos Hazard Emergency Response Act, and Occupational Safety and Health Administration regulations. All Encorus Group’s personnel assigned to conduct inspections have completed the Environmental Protection Agency (EPA) required training and New York State Department of Labor Division of Safety and Health certification program.

Based on the functional spaces and homogeneous areas (materials uniform in color or texture) identified by Encorus Group, samples of suspect materials were collected. Techniques used for sample collection were designed to minimize damage to suspected areas, reduce any potential for fiber release, and ensure the safety of the inspector and building occupants.

Samples were analyzed using Polarized Light Microscopy (PLM) in accordance with NYS DOH ELAP Item #198.1 or #198.6. For materials classified as non-friable organically bound materials (NOBs) that were analyzed as equal to or less than 1% asbestos by PLM, additional analysis was performed under Transmission Electron Microscopy (TEM) in accordance with NYS DOH ELAP Item #198.4. The results of this analysis confirmed whether or not a suspect material actually contained asbestos. The confirmed materials and all assumed materials are listed in Section 2.3 Confirmed Asbestos-Containing Materials and Section 2.4 Assumed Asbestos-Containing Suspect Materials.

Although the report is a comprehensive analysis of the asbestos inspection work performed, it would be helpful to review all applicable federal, state and local rules, laws and regulations regarding the handling and treatment of asbestos-containing materials (ACM). The following is a list of suggested reading and information sources relating to asbestos:

New York State Department of Labor Industrial Code Rule 56 Occupational Safety and Health Administration Environmental Protection Agency Rule CFR 763.86 Asbestos Hazard Emergency Response Act Environmental Protection Agency Rule 40 CFR, Chapter 61, Subpart M of the National Emission

Standards for Hazardous Air Pollutants (NESHAPS)

2.2 Executive Summary

The asbestos inspection included identification, sampling, analysis, and quantification of suspect materials that may be disturbed by the project. By definition an Asbestos-Containing Material (ACM) is any material which contains greater than one percent (>1%) asbestos. Materials which contain asbestos in measurable concentrations less than or equal to one percent (≤1%) are reported as containing “trace” amounts.

Copies of all laboratory analysis reports and chains of custody listing locations of sample collection are located in Appendix C. Refer to floor plans located in Appendix E for specific sample location points.

Refer to Appendix F for a summary of all functional spaces which were included as part of this inspection service.

295 Main Street West Seneca, NY 14224 encorus.com 716.592.3980

2.3 Confirmed Asbestos-Containing Materials

All sampled materials have been analyzed by current EPA AHERA and ELAP protocols. No identified suspect materials have been confirmed to be Asbestos-Containing Materials.

Refer to Section 2.4 and 2.5.

2.4 Assumed Asbestos-Containing Suspect Materials

No suspect Asbestos-Containing Materials have been assumed to be Asbestos-Containing Materials.

Refer to Sections 2.3 and 2.5.

2.5 Confirmed Non-Asbestos Containing Materials

These materials were sampled and analyzed by current EPA AHERA and ELAP protocols and were proven to contain one percent asbestos or less (≤1%).

HAN Number Material Description Comments

MISCELLANEOUS (600s)

600 Expansion Joint Compound – Tan --- 601 Door Caulk – Grey ---

ROOFING (700s)

700.1 Denz Deck ---

700.2 Iso Paper ---

2.6 Summary Table of Asbestos-Containing Materials

All sampled materials have been analyzed by current EPA AHERA and ELAP protocols. No identified suspect materials have been confirmed to be Asbestos-Containing Materials, and none were assumed to be ACM.

Refer to Section 2.3, 2.4 and 2.5.

295 Main Street West Seneca, NY 14224 encorus.com 716.592.3980

3 Lead-Based Paint Inspection

3.1 Methodology

Encorus Group used a spectrum analyzer (Refer to Appendix D for additional information) to test painted or coated surfaces included in the scope of work. The analyzer measures the amount of lead in painted surfaces using X-Ray Fluorescence technology (XRF). The analyzer uses a radioactive source which locates lead atoms in painted surfaces and measures the concentration in milligrams per square centimeter. If necessary, paint chip samples were also collected as part of this inspection.

Representative surfaces/components were tested in a manner designed to adequately represent the different components, substrates, types of paint, construction and paint history. Various federal, state and local laws, rules, regulations and guidelines may be applicable to this project as it relates to Lead- Based Paint/coatings (LBP) including but not limited to:

1. Lead-Based Paint Renovation, Repair and Painting Regulation Rule (40 CFR Part 745.8 Subpart E (EPA))

2. Lead Safe Housing Rule (HUD 24 CFR Part 35)

3. Guidelines for the Evaluation and Control of Lead-Based Paint Hazards in Housing (US

Department of Housing and Urban Development (HUD))

4. Occupational Safety and Health Administration (OSHA 29 CFR 1910 and 1926)

5. New York State Education Department (NYSED)

6. State of New York codes and laws

7. All local codes

8. All federal codes

9. US-DOT 49 CFR

The most recent edition of any relevant regulation, standard, document, or code shall be applicable to the work. Where conflict among the requirements exists, the most stringent requirements are generally applicable.

295 Main Street West Seneca, NY 14224

3.2 HUD/ EPA Standards

Certain HUD and EPA standards apply to “Lead-Based Paint” which is any paint or coating which contains lead at or above 1.0 mg/cm2 (via XRF), or 0.5 percent by weight (paint chip). Analysis indicated that components, listed in Section 3.3, have a lead content equal to or greater than the HUD/EPA standard for Lead-Based Paint.

3.3 Summary Table of Lead-Based Painted/Coated Materials

Functional Space ID/ Description

Material Description Approximate Quantity

Condition Positive or Homogeneous with Shot #

100 – First Floor Garage

No Lead-Based Painted/Coated components were detected within the scope of work.

101 – Stair Tower 1 102 – Stair Tower 2 200 – Second Floor Garage 300 – Third Floor Garage 400 – Roof 401 – Upper Roof

The presence of lead in surfaces that were analyzed as less than 0.5 percent lead by weight or in measurable amounts but less than 1.0 mg/cm2 is a consideration for the purposes of complying with OSHA regulations. Refer to Section 3.4 for details.

3.4 OSHA Regulations

On May 4, 1993, OSHA promulgated the Lead Exposure in Construction Rule (29 CFR Part 1926.62).

This regulation applies to all construction activities involving potential lead exposures. This regulation applies when lead is present in any detectible amount and is not limited to HUD’s definition of Lead- Based Paint. Surface abrading and demolition activities may release lead from unpainted materials which contain lead such as glazed ceramic tile and porcelain, or enameled wall panels. Although these items do not meet HUD’s definition of Lead-Based Paint and need not be included in disclosure under the Lead Disclosure Rule (Refer to Section 3.5), they have been included for reference in Section 3.3 above.

295 Main Street West Seneca, NY 14224

3.5 Disclosure Requirements

If the subject property of this report is target housing, the owner has certain responsibilities under the Lead Disclosure Rule when the property is being sold or leased, or when a lease is being renewed with revisions. In general, lead disclosure is required in these circumstances, except that disclosure does not have to be made when the target housing is being leased if the inspection has found that it is Lead-Based Paint free.

Per 40 CFR Part 745 “Target Housing” is defined as: any housing constructed prior to 1978, except housing for the elderly or persons with disabilities (unless any child who is less than 6 years of age resides or is expected to reside in such housing); or any 0-bedroom dwelling.

Results of this inspection must be provided to new lessees (tenants) and prospective buyers of this property under Federal law (24 CFR part 35 and 40 CFR part 745) before they become obligated under a lease or sales contract. The complete report must be provided by the owner to prospective buyers and it must be made available to prospective tenants and to renewing tenants if they have not been provided the information previously. The Inspector’s plain language summary of the report must be provided to the client (e.g., property owner or manager) when the complete report is provided. The landlord (lessor) or seller is also required to distribute an educational pamphlet approved by the U.S.

Environmental Protection Agency and include the Lead Warning Statement in the lease or sale contracts to ensure that parents have the information they need to protect their children from Lead- Based Paint hazards. Complete disclosure requires the landlord/sellers and renters/buyers (and their agents) to sign and date an acknowledgement that the required information and materials were provided and received. Also, prospective buyers must be provided the opportunity to have their own Lead-Based Paint inspection, lead hazard screen or risk assessment performed before the purchase agreement is signed; the standard period is 10 days, but this period may be changed or waived by agreement between the seller and prospective buyer. EPA regulations require the inspector to keep the inspection report for at least 3 years. (See Section IV of Chapter 7 of the HUD Guidelines for the Evaluation and Control of Lead-Based Paint Hazards in Housing for further details; see www.hud.gov/lead.)

295 Main Street West Seneca, NY 14224

4 PCB Inspection

4.1 Methodology

Encorus Group identified suspect exterior PCB-containing caulk, glazing, or other sealant on building components that are included in the scope of work.

The inspection was performed in conformance with all applicable federal, state and local rules, laws, regulations and/or guidelines. The US EPA’s specified limit for PCB content/concentration is 50 ppm (parts per million) or 50 mg/kg (milligrams per kilogram) by weight.

The laboratory used for bulk sample analysis was approved by NYS ELAP and AIHA or NVLAP and performed laboratory analysis by EPA Method 8082.The laboratory results are reported in mg/Kg (milligrams per kilogram) which equates to ppm (parts per million). Copies of all laboratory analysis reports and chains of custody listing locations of sample collection are located in Appendix C.

4.2 Suspect PCB-Containing Materials

No Suspect exterior PCB-containing caulking, glazing, or sealant materials were detected within the scope of work.

295 Main Street West Seneca, NY 14224

Appendix A

General Conditions of Inspection

1. Encorus Group Engineering, P.C. LLC neither accepts nor implies any liability for the implementation of the recommendations found within this report.

2. This inspection was limited to areas accessible to the inspector. Encorus Group Engineering, P.C.

neither accepts nor implies any liability for hazardous materials that may be present in other areas of the building.

3. The results of the laboratory analytical reports that may be contained herein are the product of the knowledge, experience and expertise of the laboratory retained to perform such services. Encorus Group neither accepts nor implies any liability for sample analysis reports compiled by others.

4. This report is based on the condition and contents present at the site on the day of the inspection.

Encorus Group Engineering, P.C.is not liable for materials, chemicals or other substances of concern that may have been removed from the site, cleaned or disposed of prior to the inspection date or subsequent to that date.

5. An inspection for Asbestos-Containing Materials, Lead-Based Paint or PCB-Containing Materials relies heavily upon identification of homogeneous areas, with subsequent sampling and laboratory analysis determined by: the quantity of surfaces identified, generally accepted inspection protocols, regulatory requirements, and the inspector’s judgment. Specific sample locations are determined with the objective of selecting representative samples. As with any type of sampling, the possibility of obtaining a false positive or false negative does exist, is inherent in the sampling process, and can at times result from the uneven distribution of target analytes within the suspect material. The comprehensive inspection protocol developed and utilized by Encorus Group Engineering, P.C.

attempts to minimize the risk of a false positive or false negative result. However, the client is advised that the risk of false positives or false negatives cannot be completely eliminated.

295 Main Street West Seneca, NY 14224

Appendix B

Certifications and Licenses

Encorus Group Engineering, P.C.

has fulfilled the requirements of the Toxic Substances Control Act (TSCA) Section 402, and has received certification to conduct lead-based paint activities pursuant to 40 CFR Part 745.226

All EPA Administered Lead-based Paint Activities Program States, Tribes and Territories

This certification is valid from the date of issuance and expires November 30, 2026

Certification #

LBP-F256665-1

Issued On

November 16, 2023

Michelle Price, Chief

Lead, Heavy Metals, and Inorganics Branch is hereby APPROVED as an Environmental Laboratory for the category

ENVIRONMENTAL ANALYSES SOLID AND HAZARDOUS WASTE

All approved subcategories and/or analytes are listed below:

CERTIFICATE OF APPROVAL FOR LABORATORY SERVICE

Issued in accordance with and pursuant to section 502 Public Health Law of New York State

MR. CORY M. PARNELL

AMERISCI RICHMOND

13635 GENITO RD

MIDLOTHIAN, VA 23112

NY Lab Id No: 10984

NEW YORK STATE DEPARTMENT OF HEALTH

WADSWORTH CENTER

Expires Issued

Revised

12:01 AM April 01, 2024 April 01, 2022 March 30, 2023

Miscellaneous Asbestos in Friable Material Item 198.1 of Manual

EPA 600/M4/82/020

Asbestos in Non-Friable Material-PLM Item 198.6 of Manual (NOB by PLM)

Asbestos in Non-Friable Material-TEM Item 198.4 of Manual

Asbestos-Vermiculite-Containing MaterialItem 198.8 of Manual

Serial No.: 66278 Property of the New York State Department of Health. Certificates are valid only at the address shown and must be conspicuously posted by the laboratory. Continued accreditation depends on the laboratory's successful ongoing participation in the Program. Consumers may verify a laboratory's accreditation status online at https://apps.health.ny.gov/pubdoh/applinks/wc/elappublicweb/, by phone (518) 485-5570 or by email to elap@health.ny.gov.

295 Main Street West Seneca, NY 14224

Appendix C

Chains of Custody and Laboratory Reports

January 27, 2024

Dear Sean Fitzgerald:

Encorus Group Engineering P.C.

Attn: Sean Fitzgerald 350 Elmwood Ave Springville, NY 14141

RE: Encorus Group Engineering P.C.

Job Number 124011883 P.O. #4237 4237; Bancroft Architects & Engineers / John Robbins; Buffalo VAMC - Parking Ramp Expansion / 3495 Bailey Avenue Buffalo, NY 14215

AmeriSci Richmond

13635 GENITO ROAD

MIDLOTHIAN, VIRGINIA 23112

TEL: 8047631200 FAX: 8047631800

Enclosed are the results of Asbestos Analysis - Bulk Protocol of the following Encorus Group Engineering P.C. samples, received at AmeriSci on Wednesday, January 24, 2024, for a 3 day turnaround:

20240122-4237-600-1, 20240122-4237-600-2, 20240122-4237-601-1, 20240122-4237-601-2, 20240122-4237-700.1-1, 20240122-4237-700.1-2, 20240122-4237-700.2-1, 20240122-4237-700.2-2

The 8 samples, placed in zip lock bag, were shipped to AmeriSci via Fed Ex 7222 8092 7718 B 1035. Encorus Group Engineering P.C. requested ELAP PLM/TEM analysis of these samples.

The results of the analyses which were performed under NYSDOH ELAP Lab Certification # 10984 following ELAP 198.4 TEM guidelines are presented within the Summary Table of this report. The presence of matrix reduction data in the Summary Table normally indicates an NOB sample. For NOB samples the individual matrix reduction and TEM analysis results are listed in Table I. Complete PLM results for individual samples analyzed by ELAP 198.1 (friable) and ELAP 198.6 (NOB) are presented in the PLM Bulk Asbestos Report. This combined report relates ONLY to sample analysis expressed as percent composition by weight and percent asbestos. This report must not be used to claim product endorsement or approval by these laboratories, NVLAP, ELAP or any other associated agency. The National Institute of Standards and Technology accreditation requirements, mandate that this report must not be reproduced, except in full without the written approval of the laboratory. This report may contain specific data not covered by NVLAP or ELAP accreditations respectively, if so identified in relevant footnotes.

Glenn F. Massey

Sincerely, QA Manager | Authorized Signatory

AmeriSci appreciates this opportunity to serve your organization. Please contact us for any further assistance or with any questions.

Boston - Los Angeles - New York - Richmond

AmeriSci Richmond

13635 GENITO ROAD

MIDLOTHIAN, VIRGINIA 23112

TEL: (804) 763-1200 • FAX: (804) 763-1800

01/24/24 AmeriSci Job # 124011883 01/27/24

ELAP # 10984 1 2

4237; Bancroft Architects & Engineers / John Robbins; Buffalo VAMC - Parking Ramp Expansion / 3495 Bailey Avenue Buffalo, NY 14215

PLM Bulk Asbestos Report Date Received Date Examined

RE:

ofPage

P.O. # Encorus Group Engineering P.C.

350 Elmwood Ave

Springville, NY 14141

Attn: Sean Fitzgerald

Asbestos Present Total % AsbestosClient No. / HGA Lab No.

Location:

Analyst Description:

Asbestos Types:

Other Material:

No20240122-4237-600-1 124011883-01 NAD Expansion Joint Compound - Tan; 300600

Gray, Heterogeneous, Non-Fibrous, Bulk Material

Non-Asbestos 39%

(NOB by NYS ELAP 198.6) by Eric H. Ahles on 01/27/24

Comment: Heat Sensitive (organic): 28.0%; Acid Soluble (inorganic): 32.5%; Inert (Non-asbestos): 39.5%

Location:

Analyst Description:

Asbestos Types:

Other Material:

No20240122-4237-600-2 124011883-02 NAD Expansion Joint Compound - Tan; 102600

Gray, Heterogeneous, Non-Fibrous, Bulk Material

Non-Asbestos 3.1%

(NOB by NYS ELAP 198.6) by Eric H. Ahles on 01/27/24

Comment: Heat Sensitive (organic): 67.0%; Acid Soluble (inorganic): 29.9%; Inert (Non-asbestos): 3.1%

Location:

Analyst Description:

Asbestos Types:

Other Material:

No20240122-4237-601-1 124011883-03 NAD Door Caulk - Grey; 102601

Gray, Heterogeneous, Non-Fibrous, Bulk Material

Non-Asbestos 22%

(NOB by NYS ELAP 198.6) by Eric H. Ahles on 01/27/24

Comment: Heat Sensitive (organic): 21.1%; Acid Soluble (inorganic): 56.7%; Inert (Non-asbestos): 22.2%

Location:

Analyst Description:

Asbestos Types:

Other Material:

No20240122-4237-601-2 124011883-04 NAD Door Caulk - Grey; 102601

Gray, Heterogeneous, Non-Fibrous, Bulk Material

Non-Asbestos 43%

(NOB by NYS ELAP 198.6) by Eric H. Ahles on 01/27/24

Comment: Heat Sensitive (organic): 37.6%; Acid Soluble (inorganic): 19.4%; Inert (Non-asbestos): 43.1%

See Reporting notes on last page

AmeriSci Job #: 124011883 Page 2 of 2

4237; Bancroft Architects & Engineers / John Robbins; Buffalo VAMC - Parking Ramp Expansion / 3495 Bailey Avenue Buffalo, NY 14215

PLM Bulk Asbestos Report Client Name: Encorus Group Engineering P.C.

Asbestos Present Total % AsbestosClient No. / HGA Lab No.

Location:

Analyst Description:

Asbestos Types:

Other Material:

No20240122-4237-700.1-1 124011883-05 NAD Denz Deck; 400700.1

White, Heterogeneous, Non-Fibrous, Bulk Material

Fibrous glass 5.0%, Non-fibrous 95%

(by NYS ELAP 198.1) by Eric H. Ahles on 01/27/24

Location:

Analyst Description:

Asbestos Types:

Other Material:

No20240122-4237-700.1-2 124011883-06 NAD Denz Deck; 400700.1

White, Heterogeneous, Non-Fibrous, Bulk Material

Fibrous glass 5.0%, Non-fibrous 95%

(by NYS ELAP 198.1) by Eric H. Ahles on 01/27/24

Location:

Analyst Description:

Asbestos Types:

Other Material:

No20240122-4237-700.2-1 124011883-07 NAD Iso Paper; 400700.2

Brown/White, Heterogeneous, Non-Fibrous, Bulk Material

Cellulose 30%, Non-fibrous 70%

(by NYS ELAP 198.1) by Eric H. Ahles on 01/27/24

Location:

Analyst Description:

Asbestos Types:

Other Material:

No20240122-4237-700.2-2 124011883-08 NAD Iso Paper; 400700.2

Brown/White, Heterogeneous, Non-Fibrous, Bulk Material

Cellulose 30%, Non-fibrous 70%

(by NYS ELAP 198.1) by Eric H. Ahles on 01/27/24

Reporting Notes:

*NAD = no asbestos detected, Detection Limit <1%, Reporting Limits: CVES = 1%, 400 Pt Ct = 0.25%, 1000 Pt Ct = 0.1%; "Present" or NVA = "No Visible Asbestos" are observations made during a qualitative analysis; NA = not analyzed; NA/PS = not analyzed / positive stop; PLM Bulk Asbestos Analysis using Meiji, Model MT 6130 microscope, Serial #1410298, by EPA 600/R-93/116 per 40 CFR 763 (NVLAP Lab Code 101904-0) and ELAP PLM Analysis Protocol 198.1 for New York friable samples which includes quantitation of any vermiculite observed (198.6 for NOB samples) or EPA 400 pt ct by EPA 600/M4-82-020 (NYSDOH ELAP Lab # 10984); CA ELAP Lab # 2508; Note: PLM is not consistently reliable in detecting asbestos in floor coverings and similar NOB materials. NAD or Trace results by PLM are inconclusive, TEM is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos-containing in New York State (also see EPA Advisory for floor tile, FR 59, 146, 38970, 8/1/94). NIST Accreditation requirements mandate that this report must not be reproduced except in full without the approval of the laboratory. This PLM report relates ONLY to the items tested.

Analyzed by: Eric H. Ahles Date: 1/27/2024

Reviewed by: Glenn F. Massey

Client Name:

124011883

Encorus Group Engineering P.C.

4237; Bancroft Architects & Engineers / John Robbins; Buffalo VAMC - Parking Ramp Expansion / 3495 Bailey Avenue Buffalo, NY 14215

AmeriSci Job #: Page 1 of 1

Table I Summary of Bulk Asbestos Analysis Results by NYS ELAP 198.4

Client Sample#

NOB Sample Weight (gram)

NOB Heat Sensitive

Organic %

NOB Acid Soluble

Inorganic %

NOB Insoluble Non-Asbestos

Inorganic %

HG

Area ** Asbestos % by

PLM/DS

** Asbestos % by

TEM

AmeriSci Sample #

01 20240122-4237-600-1 600 0.640 28.0 32.5 39.5 NAD NAD

Expansion Joint Compound - Tan; 300Location:

02 20240122-4237-600-2 600 0.447 67.0 29.9 3.1 NAD NAD

Expansion Joint Compound - Tan; 102Location:

03 20240122-4237-601-1 601 0.420 21.1 56.7 22.2 NAD NAD

Door Caulk - Grey; 102Location:

04 20240122-4237-601-2 601 0.852 37.6 19.4 43.1 NAD NAD

Door Caulk - Grey; 102Location:

05 20240122-4237-700.1-1 700.1 ---- ---- ---- ---- NAD NA

Denz Deck; 400Location:

06 20240122-4237-700.1-2 700.1 ---- ---- ---- ---- NAD NA

Denz Deck; 400Location:

07 20240122-4237-700.2-1 700.2 ---- ---- ---- ---- NAD NA

Iso Paper; 400Location:

08 20240122-4237-700.2-2 700.2 ---- ---- ---- ---- NAD NA

Iso Paper; 400Location:

Semi-Quantitative Analysis: NAD = no asbestos detected; NA = not analyzed; NA/PS = not analyzed due to positive stop; Trace = <1%; PLM analysis by EPA 600/R-93/116 per 40 CFR 763 (NVLAP Lab Code 101904-0) or NY ELAP 198.1 for New York friable samples which includes quantitation of any vermiculite observed (198.6 for NOB samples) or EPA 400 pt ct by EPA 600/M4-82-020 (NY ELAP Lab # 10984);

TEM prep by EPA 600/R-93/116 Section 2.3 (analysis by Section 2.5, not covered by NVLAP Bulk accreditation); or NY ELAP 198.4 for New York NOB samples (NY ELAP Lab # 10984). Analysis using Jeol, Model JEM-100CX II microscope, Serial #156147-247. ** Warning Notes: Consider PLM fiber diameter limitation, only TEM will resolve fibers <0.25 micrometers in diameter. TEM bulk analysis is representative of the fine grained matrix material and may not be representative of non-uniformly dispersed debris, soils or other heterogeneous materials for which a combination PLM/TEM evaluation is recommended;

Quantitation for beginning weights of <0.1 grams should be considered as qualitative only.

Analyzed by: Glenn F. Massey Date: 1/27/2024

Reviewed by: Glenn F. Massey

295 Main Street West Seneca, NY 14224

Appendix D

XRF Spectrum Analyzer Report and Instrument Information

295 Main Street West Seneca, NY 14224

LEAD PAINT INSPECTION REPORT

CLIENT

Buffalo Veterans Affairs Medical Center Parking Garage

INSPECTION LOCATION

January 22 and February 7, 2024 INSPECTION DATE(s)

Heuresis Corp. Pb200i

XRF INSTRUMENT TYPE

XRF INSTRUMENT SERIAL NUMBER

1.0 mg/cm2

ACTION LEVEL

SIGNED: Daniel G. Korff DATE: 02/14/2024

Company Heuresis Corp.

Model Pb200i

Type XRF Lead Paint Analyzer

Serial Num. 1633

App Version Pb200i-4.1-11

Reading # Concentration Units Color Substrate Component Orientation Side Condition Space ID Floor

496 1.1 mg/cm2 Calibration Wood

497 1 mg/cm2 Calibration Wood

498 1 mg/cm2 Calibration Wood

502 0 mg/cm2 Black Metal Roof flashing B Intact 400 Roof

535 1 mg/cm2 Green Wood CALIBRATION

536 1 mg/cm2 Green Wood CALIBRATION

537 0.9 mg/cm2 Green Wood CALIBRATION

538 0.2 mg/cm2 Green Concrete Wall B Intact 100 First Floor

539 0.2 mg/cm2 Grey Metal Railing C Intact 100 First Floor

540 0.2 mg/cm2 Black Metal Louver D Intact 100 First Floor

541 0.1 mg/cm2 Grey Metal Railing D Intact 102

542 0.1 mg/cm2 Black Metal Window Frame D Intact 102

543 0.4 mg/cm2 Red Concrete Wall B Intact 102

544 0.1 mg/cm2 Yellow Concrete Wall B Intact 102

545 0.2 mg/cm2 Black Concrete Louver D Intact 200 Second Floor

546 0.1 mg/cm2 Grey Metal Railing D Intact 200 Second Floor

547 0.1 mg/cm2 Grey Metal Railing D Intact 101

548 0.2 mg/cm2 Grey Metal Structural Steel Vertical B Intact 101

549 0.4 mg/cm2 Grey Concrete Floor - Intact 101

550 0.2 mg/cm2 Grey Metal Light Fixture - Intact 300 Third Floor

551 0.2 mg/cm2 Grey Metal Railing - Intact 300 Third Floor

552 0.2 mg/cm2 Black Metal Louver - Intact 300 Third Floor

553 0.5 mg/cm2 White Metal Ceiling - Intact 300 Third Floor

554 -0.1 mg/cm2 Black Metal Gutter - Intact 300 Third Floor

555 1 mg/cm2 Green Wood CALIBRATION

556 1 mg/cm2 Green Wood CALIBRATION

557 1 mg/cm2 Green Wood CALIBRATION

295 Main Street West Seneca, NY 14224

Appendix E

Sample Floor Plans

295 Main Street West Seneca, NY 14224

Appendix F

Summary of Inspected Functional Spaces

295 Main Street West Seneca, NY 14224

100 – First Floor Garage 101 – Stair Tower 1 102 – Stair Tower 2 200 – Second Floor Garage 300 – Third Floor Garage 400 – Roof 401 – Upper Roof

File details come from the government source that posted it. Updated .