This solicitation is for the construction of a new Sequoia National Forest Supervisor's office located at 480 North Henrahan Street in Porterville, California. The contractor will furnish all labor, materials, equipment, project management, supervision, and transportation to complete general construction, sitework, site improvements, site utilities, concrete foundations, wood framing, exterior finishes including aluminum windows, manufactured stone, plaster, fiber cement siding, single ply and composition shingle roofing, civil, mechanical, plumbing, electrical, fire protection, and telecommunication work as shown in the drawings and specifications. A pre-bid conference will be held on August 25, 2020 and sealed bids are due by September 1, 2020. This is a 100% total small business set-aside procurement. The selected contractor must meet bonding and wage rate requirements and have a current SAM registration. The Forest Service Pacific Southwest Region is the contracting agency for this project.
View the file
Other files for this federal contract opportunity
Show all 25
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
(a) By completing items 8 and 15, and returning or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
E. IMPORTANT: Contractor is not is required to sign this document and return copies to the issuing office.
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE
2. AMENDMENT/MODIFICATION NUMBER 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)
7. ADMINISTERED BY (If other than Item 6) CODE
STANDARD FORM 30 (REV. 11/2016)
Prescribed by GSA FAR (48 CFR) 53.243
FACILITY CODE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED (SEE ITEM 11)
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended. is not extended.
12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER
NUMBER IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15C. DATE SIGNED
15A. NAME AND TITLE OF SIGNER (Type or print)
16C. DATE SIGNED
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
PAGE OF PAGES
6. ISSUED BY CODE
8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X)
CODE
15B. CONTRACTOR/OFFEROR
(Signature of person authorized to sign)
16B. UNITED STATES OF AMERICA
(Signature of Contracting Officer)
Previous edition unusable
A00002
GREGORY L. CUNNINGHAM
129JGP20B0001 - Sequoia NF SO Construction - Amendment A00002. The purpose of this solicitation amendment is to post the following documents;
Official RFI Responses Round 1 - All RFI’s submitted on or before 8/25/2020 25 Aug 20 Site Visit Meeting Notes & Site Visit Sign-In Roster Division 1, Section 01 06 00 - Addendum 2 City of Porterville Permit Requirements
USDA FOREST SERVICE
NEVADA CITY CA 95959
631 COYOTE STREET
ATTN: GREGORY CUNNINGHAM
R5 CENT-CAL ACQ SERV AREA CCASA
ALL INTERESTED VENDORS 129JGP20B0001
1 16
08/31/2020
08/05/2020
FOR OFFICIAL USE ONLY
REQUEST FOR INFORMATION (RFI) OFFICIAL RESPONSES
(All RFI’s submitted on or before 8/25/2020)
129JGP20B0001 - Sequoia NF SO Construction
RFI responses will be responded to as necessary in amendment format which will be posted to the solicitation via beta.SAM.gov
Telephone requests for information will not be accepted or returned.
RFI #1 – I see the tower specs in the specs and I see several details of the tower in the plans, specifically relating to the grounding and cable tray, however, I don’t see any plans for the tower itself. There is one or two references to “Refer to civil drawings” for the tower – do we have those civil drawings?
USFS Response – The drawings and specifications provide the performance parameters for the communications tower. Per Section 33 81 16, para. 1.02.A, Contractor is responsible for the design, manufacture, factory testing, on site construction and site testing of a complete and operable communications tower. Para. 1.06.A further obligates Contractor to provide complete shop drawings and design calculations stamped and signed by a registered structural engineer.
See Drawings 6/A1.5 and E6.2 and Section 33 81 16.
RFI #2 – Per FAR 52.236-1 - Performance of Work by the Contractor;
The Contractor shall perform on the site, and with its own organization, work equivalent to at least twenty-five (25) percent of the total amount of work to be performed under the contract.
My interpretation of the above indicates the general contractor, as the proposing small business, if teaming with another contractor, is required to have under contract (subcontracted) at least 25% of the total prime contract value. Is this correct?
USFS Response – The certified small business awardee shall self-perform 25% of the total contract value within their own organization.
RFI #3 – My interpretation of FAR 52.236-1 indicates it does not require the proposing general contractor to perform or self-perform 25% of the total prime contract value. Is this correct?
USFS Response – The certified small business awardee shall self-perform 25% of the total contract value within their own organization.
RFI #4 – My interpretation of FAR 52.236-1 indicates it is not a requirement that every subcontractor be a certified small business. Is this correct?
USFS Response – Negative, subcontractors, while preferred small business, is not a contractual requirement.
RFI #5 – On plan A4.2 shows frame types #8 interior, #10 interior, #11 interior, #13 interior and #14 interior show aluminum framing but with a door type "A" which is a flush wood stained door traditionally we see timely frames used in this application unless you would like us to use our interior storefront and prep for the wood doors to be installed into it by others, we would not supply any hardware for these doors. Please clarify if these will be timely frames and if we are providing glass for them or if they will be aluminum interior storefront & we will provide the glass for them also just no doors or hardware supplied or installed.
USFS Response – Drawing A4.2, frame types 8, 10, 11, 12, 13 and 14 shall be glazed interior aluminum storefront types as shown and as specified in Section 08 41 13, para. 2.03.D. Doors shall be Type A solid core, stain finish, as indicated on Drawing A4.1 Door Schedule. Door hardware shall be as specified in Section 08 71 00.
RFI #6 – On plan A4.2 I show frame type #12 interior frame to be used on Alternate #1 but I don't show it labeled on the floor plan or marked anywhere. Please clarify if this will used or not and if used what kind of framing it will be.
USFS Response – For plan location of Drawing A4.2, interior aluminum storefront type 12, see Drawing A2.2 (Conference 133). See also response to RFI #5.
RFI #7 – On plan A4.2 I show window types to be Kawneer 8400TL thermal window but I believe #1A, #1 B, #2A AND #2B to be these type of windows and #3 and #4 not to be. I believe #3 To be old castle 3,000 thermal and #4 to be interior storefront old castle 2,000 series but please clarify what is to be used on each frame.
USFS Response – Drawing A4.2, Window Types 1A, 1B, 2A, 2B and 3 are “Window” Types as specified in Section 08 51 13. Refer to Addendum for clarification that Window 3 detail callouts are intended to be Details 1, 2 and 3, in lieu of Details 10, 11 and 12.
Refer to Addendum for clarification that Window Type 4 is intended to be an interior aluminum storefront type per Section 08 41 13, consistent with the Detail callouts 10, 11 and 12/A4.5, as currently shown.
RFI #8 – On spec sheet for glazing it calls out for several make-ups for the insulated units, could you please clarify what make-up will be used for this project?
USFS Response – Provide four distinct exterior [insulated] glazing types as specified in Section 08 80 00, para. 2.03.C. Refer to Addendum for slight modification of Para. 2.03.C.
RFI #9 – PLEASE HAVE AOR CONFIRM INSULATED GLASS COMPOSITION. PER
ARCHITECTURAL DOCUMENTS A4.2, GLAZING TYPES MAKE REFERENCE TO
“TINTED INSULATED GLASS” YET NO GLASS CURRENTLY AS DEFINED IN
DIVISION 8 GLASS SPECIFICATION ARE “TINTED”. FURTHERMORE, GLASS AS
DEFINED IN SPECIFICATION IS UNIQUE AND SHOULD BE REVIEWED BY AOR AS IT
DOES NOT EXIST AS DEFINED.
PPG® STARPHIRE™ IS LOW-IRON ULTRA CLEAR GLASS. PPG® SB70XL™ IS NOT OFFERED ON STARPHIRE™, ALSO, NO POINT IN PUTTTING ANOTHER LOW-E ON THE INBOARD LITE, AS WELL AS IT BEING ON “CLEAR” GLASS RATHER
THAN STARPHIRE™ IF OUTBOARD REMAINS STARPHIRE™
IF THE INTENT IS TRULY TO USE PPG® STARPHIRE™ YOU WILL NEED TO USE SOLARBAN 72.
HOWEVER, WE RECCOMEND TO CHANGE GLASS SPECIFICATION TOO:
¼” PPG® SOLARBAN 70XL™ #2 ON CLEAR
½” AIRSPACE
¼” PPG® CLEAR
THIS MAKEUP WILL PROVIDE THE FOLLOWING PERFORMANCE SPECIFICATION(S):
USFS Response – Refer to Addendum for slightly modified text of Section 08 80 00, para. 2.03.C.
RFI #10 – PLEASE ADVISE IF IT IS OKAY TO UTILIZE ARCADIA® ARCHITECTURAL
PRODUCTS AS A STOREFRONT, ENTRANCE, AND WINDOW VENDOR. PRODUCTS ARE
LOCAL AND COMPARABLE.
FOR EXTERIOR STOREFRONTS: ARCADIA® AG451T™ A 2” X 4-1/2” STOREFRONT,
THERMALLY BROKEN FOR 1” CENTER GLAZING
CSI SPECIFICATION: https://arcadiainc.com/media/2019/11/Framing-AG451T-Series.pdf REFERENCE: https://arcadiainc.com/media/2020/04/Framing-Arcadia-Thermal-AG451T-ALL- Series.pdf
FOR INTERIOR STOREFRONTS:
ARCADIA® A450™ A 1-3/4” X 4-1/2” STOREFRONT, NON-THERMAL FOR ¼” CENTER
GLAZING
CSI SPECIFICATION: https://arcadiainc.com/media/2019/11/Framing-A450-Series.pdf REFERENCE: https://arcadiainc.com/media/2020/04/Framing-Arcadia-NonThermal-A450-ALL- Series.pdf
FOR THERMAL STOREFRONT ENTRANCES:
ARCADIA® WS512T™ THERMAL STOREFRONT ENTRANCES FOR 1” GLAZING
CSI SPECIFICATION: https://arcadiainc.com/media/2019/11/Entrance-Arcadia-WS512T-ALL- Series.pdf REFERENCE: https://arcadiainc.com/media/2019/11/Entrance-Arcadia-WS512T-ALL-Series.pdf
FOR THERMAL OPERABLE SLIDING & FIXED WINDOWS:
ARCADIA® 500 SERIES™ THERMAL SLIDING WINDOWS FOR 1” GLAZING
CSI SPECIFICATION: https://arcadiainc.com/media/2019/11/Window-ULT500-Series.pdf REFERENCE: https://arcadiainc.com/media/2019/11/Window-Arcadia-Thermal-ULT-500-ALL- Series.pdf BROCHURE: https://arcadiainc.com/media/2019/11/Arcadia-Window-500-Series-Brochure.pdf
USFS Response – This is a substitution request by Bidder. Per the Solicitation, the Contractor is responsible for ensuring that any substituted “equal” has the salient characteristics of the brand name. See page 9 of solicitation “BRAND NAME OR EQUAL:” and FAR 52.211-6
RFI #11 – PLEASE UPDATE DOOR SPECIFICATION TO READ AS “WIDE” STILE VERSUS
“MEDIUM” STILE. THE DEFINED VON DUPRIN HARDWARE REQUIRES THE USE OF A
WIDE-STILE DOOR.
USFS Response – Refer to Addendum for change in spec Section 08 41 13, para. 2.03.B.1 from medium stile to wide stile.
RFI #12 – PLEASE BE ADVISED THAT IT IS NOT TYPICAL TO OBTAIN A 20-YEAR
FINISH WARRANTY FOR “ANODIZED” FINISHES. IT IS HOWEVER TYPICAL TO
OBTAIN FOR “PAINTED” FINISHING. SHOULD ASSEMBLIES BE CHANGED TO
PAINTED TO MAINTAIN 20-YEAR FINISH, OR CAN 20-YEAR FINISH WARRANTY
DEGRADE TO 10-YEAR AND MAINTAIN ANODIZING?
USFS Response – Refer to Addendum for change in spec Section 08 41 13, para. 1.06.B from 20-year anodized aluminum finish warranty to 10-year finish warranty.
RFI #13 – Please clarify the pricing scenarios:
1) Base Bid
2) Base Bid + Alt 1
3) Base Bid + Alt 1 + Alt 2
Should we;
Provide a base bid number...
Provide an Alternate Add for Alt-1….
Provide an Alternate Add for Alt-2 (…and assume they’ll add in the Alt-1 price to the Alt-2)??
USFS Response – Please carefully review the bid schedule. It is very clear that there are to be values input for:
Total Base Bid
Total Bid Add Alternative 1:
Sub Total - Base + Alternative 1:
Total Bid Add Alternative 2:
Sub Total - Base + Alternative 1 & 2:
Total Bid Add Alternative 3:
Sub Total - Base + Alternative 1, 2, & 3:
Total Bid Add Alternative 4 A, B, & C:
Total Bid - Base + Alternative 1, 2, 3, & 4:
Agriculture
United States Department of
Forest Service
Sequoia National Forest
FAX (559) 781-4744
Sequoia National Forest 1839 South Newcomb Porterville, CA 93257
(559) 784-1500
Caring for the Land and Serving People Printed on Recycled Paper
File Code: 7720 Date: August 25, 2020 Subject: New S.O. Building Project Pre-Bid Tour Notes Solicitation: 129JGP20B0001
To: Contracting Officer – Gregory Cunningham
An On-Site Pre-Bid Tour for the Current Solicitation of the Advertised New S.O. Building Project, was conducted Tuesday August 25, 2020, from 1000 to 1130 hours. Two Sign-In Lists were provided prior to the start of the meeting for the approximately 45 participants to write their Names, Phone Numbers and E-mail Addresses onto for the project file and future reference.
Meeting with the four and half groups was held at parking area in front of the Fire Shop Office on the existing compound north of the New Building Construction Site. Steven Ray started by thanking all who showed interest in the project by their attendance, also introducing himself and me and discussing our roles in the project. We would go over key project elements during this time, told participants to feel free to ask any questions they may have during these discussions.
We informed the groups, we would also tour the new building site afterwards, if they wanted to do so and answer any questions they may have later there. None of the groups chose to tour the new building site later after the meeting.
Following Government Personnel attended, spoke & answered questions at the Pre-Bid Tour:
Steven Ray – Forest Engineer Rich Mora – Construction COR Level 3
Following listed Solicitation Items & Questions were discussed and answered, also will check with references & Contracting Officer later for any items not resolved at meeting:
Steven briefly discussed the Base Bid & Different Alternative Bid Items. Grouping of some work & separation of other work, which led to their development. Current Funding Limits is main reason for Alternative Items. Whether Options/Alternatives are awarded, will be determined by the Successful Bid Award Amount. Talked about the Schedule of Items & the Divisional Breakdown Sheets, what is required/needed information for both Base Bid & each Bid Alternative on these sheets, basically what needs to be submitted for consideration during this bidding process. Following Questions were asked & the Answers that were provided.
1) What is the Current Funding Available for the Project? Provided Answer: The Government Estimate is between 5 to 10 Million Dollars for all items, any other information is confidential and cannot be provided. We are currently seeking other funds for this project, but cannot guarantee extra funding will be available for all Alternatives. They just need to submit their best bids, to do all the work and see what happens after award of Contract.
2) Does the Original Number of Contract Days cover both the Base Bid and all the Bid Alternative Items? Provided Answer: The 325 Days of Contract Time is for the Base Bid Items. There will be Additional Contract Time Days for each Awarded Bid Alternative, as stated within the Solicitation (see section 2.2 Statement of Work para C.3).
Next Items discussed were Building Materials, such as the different Classes of Concrete for the different areas of the construction for everyone’s information. Discussed that both the Class II Aggregate Base and the Asphalt are not controlled only by Federal Specifications, but may be in Compliance to State (Cal-Trans) Specifications instead. State (Cal-Trans) requires the use of Currently Certified Asphalt Mix Designs from Annually Inspected and Currently Certified Asphalt Plants. Site Earthwork Phases were also covered, such as Excavation, Waste Removal of Unsuitable Excavation, Imported Replacement Embankment and the Required Quality Control for Placement Operations. Everyone was made aware that only the quality control for the Earthwork is provided by the Geo-Tech Services of the A&E Firm that did the Site Design, due to the special requirements of the Soils Report for the building site. Clarified to everyone, quality control for the rest of the Project is the responsibility of the Contractor awarded the project. Following Questions were asked & the Answers that were provided.
1) Is the Required Compaction of these materials more than Visual Displacement?
Provided Answer: Yes, it will be Controlled Compaction, based on proctor tests from approved materials for the work.
2) What is the availability of the Geo-Tech Services for Testing Soil Materials during placement operations and when should their services be scheduled for testing on the site? Provided Answer: Need to make good use of their availability for these services and schedule these services, when you plan to do large quantities of earthwork. They need to schedule travel in advance, so prior coordination efforts are important for best use of time. Any additional expenses, due to poor planning or workmanship by the Contractor, shall be paid for by the Contractor.
3) Is the Geotechnical Soils Report available for review, so we have a better idea of Current Soil Conditions On-Site and the Recommended Corrections for the site?
Provided Answer: Yes, it is part of the Solicitation Package.
Discussed the Requirement for a Project Quality Control Manager and how important this position is for the overall success of the project. Referred everyone to the Specification Subsection under Quality Control, which shows the requirements for this position. Both a Fully Competent Quality Control Manager and Site Superintendent are required positions.
Quality Control Manager has many responsibilities and this is a huge project, so the Site Superintendent cannot also be the QCM. Following Questions were asked & the Answers that were provided.
1) What are the Correct Procedures for All Submittals and RFIs? Provided Answer: All Submittals and RFIs need to be sent to the Contracting Officer, who will take the appropriate action, needed for these items.
2) Is a Safety Manager also a Required Position? Provided Answer: No, this is Not a Required Position, but project safety and accident prevention are important and required project elements. This could be done as part of the assigned duties of either the Site Superintendent or the Quality Control Manager, also it could be assigned to someone else on the Prime Contractor’s Staff. Designations of Contractor’s Site Personnel and their Authorities are required submittals, to be provided to the Contracting Officer prior to start of operations.
3) Who is responsible for getting Permits, such as a Surface Water Run-Off Treatment Permit, also doing any coordination with the City Public Utilities for services, or has this already been taken care of by the Government? Provided Answer: It is the Contractor’s Responsibility to get any necessary permits, also to take care of any needed coordination with the City Public Utilities for all service hook-ups. Should the Government need to be present or involved in any of these efforts, they need to contact the Contracting Officer and work through him, or he will provide direction on how to proceed. We will contact the Design Firm and get any information they may have gathered on these topics during the Design Process.
4) Noticed there are some Specified Manufacturer Products on a few of the Drawings, so are these required or will any substitutions be considered? Provided Answer:
Contractor can submit an Equivalent or Better Product, which Meets or Exceeds Project Quality Requirements for Review and Approval, provided there is No Additional Cost to the Government.
5) Will the Contractor be allowed to use the Existing Compound on the other side of the fence north of the New Building Site for any activities, such as Existing Facilities, Temporary Power, Water, Storage, or Staging of some operations? Provided Answer:
No, this area is not available for the Contractor’s use for any operations. They need to provide their own temporary power, water, sanitation facilities or other project needs.
6) Several People asked if they could get copies or take photos of the Sign-In Lists from today’s meeting? Provided Answer: We will check with the Contracting Officer and he will decide whether or not it will be provided to the meeting participants.
Richard Mora
SQF NEW SUPERVISOR’S OFFICE
480 NORTH HENRAHAN STREET, PORTERVILLE, CA 93257
ADDENDUM NUMBER 2
[date]
SPECIFICATIONS
1. DIVISION 1, Section 01 06 00: Add new Para. 1.04 to read:
1.04 Permit Requirements
A. Encroachment Permit: Contractor shall comply with all City permit requirements and secure and pay for the City of Porterville encroachment permit and bond required for work in the public right of way. Permit information may be obtained from the City Public Works Department, 559-782- 7462. [A Permit Requirements hand-out is attached for reference.]
B. Utility Connection Permits and Fees: Contractor shall secure and pay for all City of Porterville utility connection and inspection permits and fees for the project, including water, sewer and storm. Utility connection fee information may be obtained from the City Engineering Division, 559-782-7462.
2. DIVISION 8, Section 08 41 13: Amend Para. 1.06.B to read:
A. Furnish written warranty covering aluminum finish against cracking, checking, blistering, peeling, flaking, chipping, chalking and fading, as defined, for 10-years following date of Substantial Completion.
3. DIVISION 8, Section 08 41 13: Amend Para. 2.03.B.1 and 2.03.B.7 to read:
1. Basis of Design: Oldcastle Thermal Clad, wide stile.
7. Stiles:
a. 5” x 0.0125” thick.
4. DIVISION 8, Section 08 51 13: Add new Para. 1.05.C to read:
C. Provide manufacturer’s 10-year warranty for the anodized window finish.
5. DIVISION 8, Section 08 80 00: Amend Para. 2.03.C to read:
C. Exterior Glazing: Vitro Solarban 70, or equal, Solar Control Low-E Insulating
Glass
2. Color clear
3. Type 1: South and West facing windows and storefronts.
a. Outdoor Lite: 6mm Solarban 70XL (2) on clear
b. ½” Airspace
c. Indoor Lite: 6mm Pilkington Energy Advantage, or equal (4) on Clear
d. VLT = 60%; SHGC = 0.26; Winter U-Value = 0.23
4. Type 2: East & North facing walls
a. Outdoor Light: 6mm Solarban 70XL (2) on clear
b. ½” Airspace
c. Indoor Lite: 6mm Clear
d. VLT – 64%; SHGC = 0.27; Winter U-Value = 0.28
5. Tempered units
a. Outdoor Lite: 6mm Solarban 70XL (2) on clear
b. ½” Airspace
c. Indoor Lite: 6mm Pilkington Energy advantage or 6mm Clear
d. VLT, SHGC, & U-Value to match exposures listed above.
6. Obscure
a. Outdoor Lite: 6mm Solarban 70XL (2) on clear
b. ½” Airspace
c. Indoor Lite: 6mm Standard Obscure (submit samples for COR approval).
DRAWINGS
1. Drawing A4.2: Replace with amended Drawing A4.2, with delta 2 edits, dated 8/31/2020, enclosed.
END OF ADDENDUM NUMBER 2
| A00002 - Time Extension & RFIs (Round 1) |
| 129JGP20B0001 - RFI Official Responses - RFIs prior to 8-25 |