Attachment 9 - Frenchman_Workcenter O and M_Plumas National Forest.pdf

PDF 14 MB Posted

Attached to
Off Grid PV Solar System Battery Replacements
Solicitation number
127EAT26Q0044
Issued by

About this file

This is an Operation & Maintenance Manual for an off-grid renewable energy installation at the Frenchman Work Center in Plumas National Forest. The project, completed June 6, 2019, was executed under USDA Forest Service ESPC contract GS-07F-0248K/AG-9A40-D-15-0007 by Trane U.S. and involved installation of LED lighting throughout the facility and a mobile solar photovoltaic (PV) system to reduce overall electrical consumption and extend generator life.

The facility, located at 5,760 feet elevation and operational May through October, comprises an Engine Bay building, Barracks, Generator building, and Warehouse/Storage structure. The project replaced all existing T8 fluorescent and incandescent lighting with LED fixtures (including GE A-Line lamps, LED PAR30 directional lamps, Lumark Crosstour LED wall packs, and Metalux WNLED wraparound fixtures) to reduce lighting loads. The mobile solar system consists of an MS-225 trailer with three Outback Power Radian inverters, two FLEXmax 80 charge controllers, six 335-watt LG PV panels, and a 100 kWh lithium battery system designed to provide 60 kWh daily production with two days of battery autonomy. The SA-24 solar array trailer contains 24 additional 330-watt PV modules. The existing 25-kW propane Cummins generator will serve as backup power and battery charging only, significantly reducing propane fuel consumption and operating hours. A one-year construction warranty began June 10, 2019 with no equipment failures reported. Trane service contact is Richard Swank at (916) 577-1126. The manual includes detailed product data sheets, wiring diagrams, installation specifications, and maintenance procedures for all installed equipment.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OPERATION & MAINTENANCE MANUAL

Contract: GS-07F-0248K/AG-9A40-D-15-0007

USDA Forest Service, Region 5, ESPC Enable AFFECT Off-Grid Renewable Project

Frenchman Work Center

Plumas National Forest

Located off Highway 70 & north on Highway 284 at junction of Chilcoot, CA approximately ten miles north on 284

Prepared by: Trane U.S., 4145 Del Mar Avenue, Rocklin, CA 95677

Phone: (916) 577-1100; Fax: (916) 577-1175

PREFACE

This Operation & Maintenance Manual provides for installation instructions, operating procedures, equipment wiring diagrams, product numbers, scheduled maintenance procedures, warranty information and Trane representative contacts.

The main components of this project involved installation of new LED Lighting throughout the facilities and also a Mobile Solar PV system.

Only qualified personnel shall perform any servicing and maintenance of the equipment.

SAFETY WARNING

Only qualified personnel should install and service this equipment. The installation, starting up, shutting down and servicing of the LED Lighting and Mobile Solar PV equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in this manual, tags, stickers, and the drawings, etc.

Table of Contents

1. Contacting Trane for Service & Warranty

2. Overview of Project (White Paper)

3. Construction Drawings As-Built (Mobile Solar PV & LED Lighting)

4. LED Lighting Product Data & Installation Details

5. LED Lighting Operation & Maintenance

6. Mobile Solar PV Product Data & Installation Details

7. Mobile Solar PV System Operation & Maintenance

8. Warranty

SECTION 1

Contacting Trane for Service & Warranty

Trane Service & Warranty Contact Information:

Address: Trane U.S., 4145 Del Mar Avenue, Rocklin, CA 95677

Main Office Phone & Fax: Ph: (916) 577-1100; Fax: (916) 577-1175

Primary contact: Richard Swank, phone: (916) 577-1126; email: Richard.swank@trane.com

Secondary contact (Trane Service Department): 1-866-459-4155

Project Completion:

Trane U.S. was the installing Contractor for the Frenchman Work Center ‘Off-Grid Mobile Solar &

LED Lighting project. The project installation was completed and commissioned on June 6, 2019.

A 30-day acceptance period occurred from June 6, 2019 and completed on July 30, 2019.

Commissioning documents were produced, provided, reviewed and signed by Forest of R5 personnel on June 6, 2019.

One (1) Year Construction Warranty Period:

A one (1) year construction installation warranty period started on June 10, 2019 and will have ended on June 10, 2020. There were no noted equipment failures during this period requiring a warranted repair or product replacement.

Equipment Warranty:

Each product installed for this project may have a ‘product warranty’. Within this manual are listed each products information and manufacture warranty information. If you believe you may have a product that is covered under warranty please contact Trane U.S. first before attempting to replace the product with a like-in-kind replacement.

A product warranty typically covers a manufacturer product defect in manufacture (i.e.: an LED light fixture fails within the warranty period). Specific details of products covered are warranty are to be found in the ‘Warranty’ section of this manual.

mailto:Richard.swank@trane.com

SECTION 2

Overview of Project (Trane ‘White Paper’)

The following pages consist of the Trane ‘White Paper’ which provides for information concerning the Frenchman Work Center as ‘it was’ before the ENABLE project was implemented and the inventory of the existing equipment (electrical, lighting, generator, water, fuel usage, etc.).

In the white paper there is information on the recommendations for the constructed project in regards to the Mobile Solar PV system sizing and siting. Also, the existing lighting and LED

Lighting related work is inventoried. This document is a useful reference for the Pacific Valley F.S.

site.

This document is important as it provides background knowledge of the site, and the inputs of information into IGA survey that Trane performed.

We also recommend that the final ‘Construction’ drawings in this manual be referenced for actual final installed products and details.

Contract # AG-94A40-D-15-0007 for

U.S. Forest Service ESPC ENABLE AFFECT Off-Grid Renewable Energy Project

Frenchman Work Center – Plumas National Forest

12-1-19

On August 13, 2015, Trane performed a site walk visit for the IGA Audit data collection at the Frenchman Work Center station. The site was in operation during our visit. We met with several Forest Service members at the site that were knowledgeable as to facility operations. We were able to see the generator in operation and also inventory all of the lighting, appliances, etc.

We are providing Trane’s findings from the U.S. Forest site visit in the following five (5) Section elements: I. Location, II. Site Overview, III. Investment Grade Audit (IGA) Site Visit Findings, IV. Sustainable / Solar Siting Considerations and last, Appendix – Pictures.

I. Location

The Frenchman Work Center station facility is located nearly 170 miles northeast of Sacramento, CA. The site is at an elevation of 5,760 feet and experiences snow in the winter months. The best way to reach the site is to leave from Sacramento, CA travelling ‘east’ on I-80 towards Reno, NV.

Take Highway 89 ‘north’ in Truckee, CA (about 40 minutes before Reno) and go to Sierraville, CA. In Sierraville take Highway 49 ‘east’ towards Loyalton, CA and continue on until the intersection of Highway 70. Make right (east) on Highway

70. Travel about 2 miles until Frenchman Lake Road. Make a ‘left’ on Frenchman Lake Road and travel all the way to Frenchman Work Center located on the southwest side of Frenchman Lake. Turn left into Frenchman Work Center up to the fire station.

II. Site Overview

Frenchman Work Center is open and typically used from May through the end of October (184 days). It is not used in the winter months. Winter access is limited as it usually is snowed-in (i.e.: from November through March). The site has: a Fire Engine Bay building with an office area, restroom and upstairs mezzanine area; there is one Barrack building, a Generator building, and a Fire Cache/Warehouse Storage building.

Engine Bay Building consists of multiple bays for the fire tanker and equipment, a small storage area, shop area, mezzanine area, office, break room area and a Men’s and Women’s bathroom. All of the lighting is T8 fluorescent light fixtures at most all inside areas. The exterior light fixtures are metal halide wall packs. A propane hot water heater is located on the mezzanine and a propane wall heater is located in the office area.

Barrack Building consists of: five bedrooms, a Men’s and Women’s bathroom with sinks, showers and toilets, a large Living Room area, a large Kitchen area, and a Laundry area with a clothes washer and electric clothes dryer. There is also a propane central heating system.

Generator Building has one (1) 25-kW (nominal before de-rated for elevation) Cummins generator that operates from propane. This generator typically runs approximately 12 to 14 hours per day in the operating season 7-days/week. The Barrack is occupied in the operating season. During the winter (off season) there is no use of the site and it is buttoned up for the winter months. There are a couple of propane tanks at the site for the Barracks, Office and Engine Bay building for heaters, gas stoves, and other propane consuming appliances such as refrigerators (and the generator).

Warehouse / Storage Building is an older wood structure that is used as a shop area and also storage area (Fire Cache) for equipment. There are a couple of incandescent lights in the building and PAR38’s as outside flood lights.

There is a submersible well pump down the road from the Frenchman Work Center on its own dedicated generator system. This is not part of the project scope or work. The submersible pump feeds water to a large storage water tank up on a hill above the Work Center and delivers domestic water to the site as a gravity feed from the storage tank.

III. Investment Grade Audit (IGA) Site Visit Findings

Findings from the site visit is subdivided by primary Energy Conservation Measure categories, power generation and fuel. Photo documentation from the site visit are provided in the Appendix.

A. Electrical

The following electrical loads currently exist at the Frenchman Work Center site:

Continued on next page

See next page for ‘Electrical Notes’ regarding this table

Electrical Notes

(1) Based upon the above ‘current loads’ and field observations this site has varying loads and typically has light generator loads. A diversity of operating loads and times of use was seen. Total system watts during our visit varied from 8.5-kW up to nearly 10-kW (by having most all of the lighting ‘on’ and many of the appliance loads).

(2) During field site visit the generator was observed with an average daytime load of 8.5-kW. This is a nominal use load. The

Barracks are not used too much in daytime periods. Load may increase during mornings and evenings when used more.

(3) All CFL’s and incandescent lamps would be changed to LED lamps. This will help reduce overall lighting loads.

(4) The Engine Bay exterior metal halide will be changed to LED wall pack style of fixtures.

(5) T12 fixtures will be replaced with LED fluorescents. T8 fixtures will have new LED lamps.

(6) All appliances remain ‘as is’ (i.e.: no change in load wattages).

(7) With a mobile solar PV solution a separate battery building will not be needed. The need for fencing, underground trenching, conduit and wire would also not be needed.

B. Water

The table below summarizes Trane’s inventory of water consuming devices for the site:

Water Consuming Devices:

No. Description Recommendations Hours of Use Notes

1 Engine Bay – Women’s Bathroom Sink No Change Light Use Fixture remains ‘as is’

2 Engine Bay – Women’s Bathroom Toilet No Change Light Use Fixture remains ‘as is’

3 Engine Bay – Women’s Bathroom Shower No Change Light Use Fixture remains ‘as is’

4 Engine Bay – Women’s Bathroom Sink No Change Light Use Fixture remains ‘as is’

5 Engine Bay – Women’s Bathroom Toilet No Change Light Use Fixture remains ‘as is’

6 Engine Bay – Women’s Bathroom Shower No Change Light Use Fixture remains ‘as is’

7 Engine Bay – Break Room Sink No Change Light Use Fixture remains ‘as is’

8 Barracks – Kitchen Sink No Change Normal Use Fixture remains ‘as is’

9 Barracks – Clothes Washer (1) No Change Normal Use Appliance Remains ‘as is’

10 Barracks Men’s Bathroom – Sink (1) No Change Normal Use Fixture remains ‘as is’

11 Barracks Men’s Bathroom – Toilet (1) No Change Normal Use Fixture remains ‘as is’

12 Barracks Men’s Bathroom – Shower (1) No Change Normal Use Fixture remains ‘as is’

13 Barracks Women’s Bathroom – Sink (1) No Change Normal Use Fixture remains ‘as is’

14 Barracks Women’s Bathroom – Toilet (1) No Change Normal Use Fixture remains ‘as is’

15 Barracks Women’s Bathroom – Shower (1) No Change Normal Use Fixture remains ‘as is’

16 Barracks H.W. Heaters (2) No Change Normal Use Appliance Remains ‘as is’

17 Barracks Unisex Bathroom – Sink (1) No Change Normal Use Fixture remains ‘as is’

18 Barracks Unisex Bathroom – Toilet (1) No Change Normal Use Fixture remains ‘as is’

19 Barracks Unisex Bathroom – Shower (1) No Change Normal Use Fixture remains ‘as is’

Note: The Water Consuming Devices Table above indicates ‘no change’ for existing water fixtures as this sitehas very light use of water.

A separate generator and well pump not connected to the facility generator is used to pump water to the site. Typically once a week the site staff turn the water generator on to just top the water tank. Most of the water usage consumption is due to filling of the fire truck and/or washing fire equipment and not the normal use of fixtures. Therefore, we do not recommend any fixture changes.

C. Generator

There is one (1) Cummins model #GGMB-5937588 ‘propane’ powered generator that has a nominal nameplate ‘standby’ rating of 25-kW ‘before’ being de-rated for an elevation of 5,760 feet. Cummins states to apply a de-rate factor of 4% per 1,000 feet of elevation gain, therefore the de-rate on the 25-kW ‘standby’ rating correlates to 20-kW. The generator provides for 120/240- volt, 1-phase power. ‘Standby’ maximum amps would be (104.2-amps at 120/240-V before de-rate) approximately 83-amps at full load.

The annual generator annual maintenance costs will vary year-to-year and information provided by the Forest Service indicates we have only stipulated an average of $1,250 per year as we do not have actual invoices from expenses incurred. The generator is older however is in operable condition. Maintenance may increase over time due to age. Reduced operating hours will extend useful life. Generator maintenance is by Forest Service.

Trane received one of the propane fuel bills for the 2011-2014 period. The U.S. Forest Service has varying estimates for fuel costs year-to-year in the original provided Excel data chart. We have stipulated and used $13,275 average per year of annual fuel costs (based upon 2013-14 data provided). Estimated cost/hour to operate the generator is $3.75/hour.

The following Forest Service ENABLE AFFECT table is provided with dated values as shown below from the fall of 2013 to the fall of 2014:

Plumas Forest Fuel Consumption

Fuel Fuel Cost Notes

Frenchman W.C. Gallons Type $ Dollars

2012 (Oct2011-Sept2012) No Info The fuel use in this table correlates closely to fuel bills.

2012 (Oct2012-Sept2013) No Info 2012 (Oct2013-Sept2014) 5166.4 Propane $10,826.30

Note: We used actual fuel bills provided rather than the above table values provided with the RFQ package for the IGA Audit.

D. Fuel – Propane

The table below summarizes Trane’s inventory of propane consuming devices for the site:

No

Description Recommendations Future Hours of Use

Notes / Recommendations

1 Cummins GGMB Propane Generator Model #GGMB-5937588

Use for charging batteries & back-up power

Only when needed

Use for charging batteries

2 Engine Bay (Mezzanine) – State Industries, hot water heater

(50gal) 18K BTU/Hour

Leave in-place Light Use 70% Eff., Minimum usage

3 Engine Bay (Mezzanine) Propane refrigerator: 1600 BTU/Hour

Leave in-place.

Light Use Leave unit ‘as is’

4 Engine Bay (Mezzanine) Propane instantaneous water heater: 105K

BTU

Leave in-place Light Use 70% Eff., Minimum usage

5 Engine Bay (Office) Propane Wall Heater: 25K BTU input

Leave in-place Light Use 70% Eff., Minimum usage

6 Barracks – Refrigerator #1 & #2, M#RGE-400; 1500 BTUH/each

Leave in-place In use when occupied

Leave ‘as is’

7 Barracks – Refrigerator #3 (Consul);

1600 BTUH

Leave in-place In use when occupied

Leave ‘as is’

8 Barracks – Freezer #1 (Crystal Cold); 1750 BTUH

Leave in-place In use when occupied

Leave ‘as is’

9 Barracks – Freezer #2 (Crystal Cold); 1750 BTUH

Leave in-place In use when occupied

Leave ‘as is’

10 Barracks – Payne Heating Unit

100K BTUH

Leave in-place Change to programmable statthermostat

In use when occupied

Leave unit ‘as is’

11 Barracks – H.W. Heater (Rheem) 50 gal.; 36K BTUH

Leave in-place Light Use Leave H.W. heater ‘as is’

12 Barracks – H.W. Heater (G.E.)

50 gal.; 36K BTUH

Leave in-place Light Use Leave H.W. heater ‘as is’

E. Other ECMs and Considerations

This site does experience ‘snow’ conditions and may receive 18 to 24-inches of winter snow conditions at this elevation of 5,760 feet in a normal winter.

IV. Sustainable / Solar Siting Considerations

The Frenchman Work Center station NEPA (National Environmental Policy Act) document suggests that the solar system be ground mounted to the ‘east’ of the Engine Bay building in an open rocky area. We recommend a mobile solar PV solution that will not need to be in the rocky area east of the Engine Bay building. This relocation may also avert the removal of several trees in the surrounding area for the PV field to receive adequate light levels for production with good exposure. Portable electrical cables would also be run from the mobile solar system to the existing generator building. This would avoid trenching and underground work (blue dashed line) to the generator building. Our site visit indicates no rationale for other siting.

Note: Any tree trimming or removals is by Forest Service. Final determination of trimming and removals will need to be coordinated and is dependent upon final PV location and siting.

Engine Bay/Office

Barracks

Warehouse/Storage

Generator Building

Mobile Solar PV Field ̴ (40’x60’)

Tree Removals for PV

Frenchman Work Station – Mobile Solar System Layout

Mobile Solar Solution is depicted below for average daily load of 49.3 kWh / day

MS-275-R3.100 SA-24 (24 x 330-watt PV modules)

Typical U.G. electrical conduit/wire intertie between MS-275 and SA-24

Existing Electrical Panel Existing Cummins Propane Generator Notes:

1.) BASE PV SYSTEM (Lithium): Average daily load is 49.3 kWh/day. Proposed Mobile Solar system is 60 kWh/day.

2.) ‘MS’ trailer is a heavy duty payload package, includes tandem 8,000-lb axles and heavy duty tires with spare tire.

3.) MS-275-R3.100 (24 kW AC output w/100 kWh lithium battery, ‘MS’ trailer 14 kWh/day solar harvest).

Two days of battery autonomy. Physical: 19’-6” x 7’ overall. ‘MS’ trailer weight (lead acid batteries): 8,600-lbs.

4.) One SA-24 (24 each x 330-watt PV modules); 36 kWh/day harvest. Physical: 36’ x 10’ deployed (including tongue);

Solar array dimensions would be 36’ x 10’.

5.) Underground electrical cables are to connect SA-24 to MS-275 trailer unit.

Appendix - Pictures

Pictures (continued)

Pictures (continued)

Note:

Recommend mobile solar PV system and locating PV system in non-rocky location behind fire station and near the generator building for ease of connection and use. This may also avoid tree removals if the mobile solar PV is sited in a good location.

SECTION 3

Final Construction Drawings, Wiring Diagrams and Details

The following pages provide for the Frenchman Work Center installation drawings. These drawings provide for the installed equipment location(s) and information, including detailed construction plans and wiring diagrams for the Mobile Solar PV system and the LED Lighting products that have been installed.

These systems that are installed produce and consume electricity generated from the Mobile

Solar PV system.

Electrical Hazard! DO NOT attempt to change or modify the installed LED Lighting or Mobile Solar PV system as damage to the equipment may occur and warranty may be voided.

Contact Trane U.S. for any concerns or questions in regards to the equipment (see ‘Contacts’ section in this manual).

SECTION 4

LED Lighting Product Data & Installation Details

The following pages consist of the Trane ‘LED Lighting Product Data Sheets’ and also within these sheets are the manufacturer installation information for the Frenchman Work Center.

These product data sheets are your resource for the installed LED Lighting products.

Additional LED Lighting locations for these installed products may be found in Section 3 of the

Construction Drawings as-built along with the manufacturer model numbers (which are highlighted in these product data sheets and also on the construction drawings).

GE offers dimmable LED A-Line lamps as excellent replacements for standard 25-watt, 40-watt, 60-watt, 75-watt and 100-watt incandescent lamps.

LOW-COST OPERATION

• �For example, a 100-watt incandescent replacement lamp using

13 watts of energy and producing 800 lumens can save over $129 in energy costs over the rated life of the lamp versus a standard 840 lumen, 60-watt incandescent A19 based on $0.11 per kWh

• �Energy efficiency and long life mean fewer lamp replacements versus standard incandescent or halogen light sources

EXCELLENT COLOR RENDERING

• Available with a CRI of 78 - 80

COLOR TEMPERATURE

• Halogen-like color

• Available in 2400K, 2700K, 3000K, 4000K and 5000K

LONG LIFE

• Up to 25,000 hours rated life (L70)

DIMMABLE

• Dims from 100% to as low as 10%

ENVIRONMENTALLY CONSCIOUS

• �These lamps are energy efficient, contain no lead or mercury, and are compliant with material restriction requirements of RoHS

GE QUALITY AND RELIABILITY

• 3-year limited warranty

Illuminate

LED A-Line general purpose lamps

To learn more about saving money and energy, go to: http://products.currentbyge.com.

Information provided is subject to change without notice. Please verify all details with GE. All values are design or typical values when measured under laboratory conditions, and GE makes no warranty or guarantee, expressed or implied, that such performance will be obtained under end-use conditions.

Application illustation only, subject lamps not used in photo.

lbjla Typewritten Text Frenchman Work Center F.S.

GE LED10DA19/840 lamps lbjla Highlight lbjla Text Box

FIXTURE "A"

ENERGY STAR® is a registered U.S. mark

Product is compliant with material restriction requirements of RoHS

A-Line Lamps LED A-Line general purpose lamps http://products.currentbyge.com.

GE and the GE Monogram are trademarks of the General Electric Company. All other trademarks are the property of their respective owners. Information provided is subject to change without notice. All values are design or typical values when measured under laboratory conditions. GE Lighting and GE Lighting Solutions, LLC are businesses of the General Electric Company. © 2017 GE.

63563 (Rev 08/18/17)

* The life rating is based on the hours of operation the lamp will provide before reaching 70% of its original rating (L70) ** Minimum order quantity = 6

ENERGY STAR® status: ENERGY STAR® certified. Lamps without a “ ” are not ENERGY STAR® certified.

# UL 1993 Environmental Requirements for LED LAMPS
Location, damp – Exterior or interior location that is normally or periodically subject to condensation of moisture in, on, or adjacent to, electrical equipment,
and includes partially protected locations.
Location, dry– Location not normally subject to dampness, may include a location subject to temporary dampness, i.e., building under construction,
provided ventilation is adequate to prevent an accumulation of moisture.
Location, wet– Location in which water or other liquid can drip, splash, or flow on or against electrical equipment.
Notes:1) Product descriptions ending in “/TP” indicate a carded blister or clamshell package nested in a tray for shelf display. Cards also designed for hook display.

Information provided is subject to change without notice. Please verify all details with GE. All values are design or typical values when measured under laboratory conditions, and GE makes no warranty or guarantee, expressed or implied, that such performance will be obtained under end-use conditions.

Bulb Shape

Base Type Watts

Order Code Description Volts

Case Qty**

MOL

(In) Lumens Initial CBCP

Initial Color Temp CRI

Wattage Replacement

*Rated Life

L70 (Hrs) Dimmable

ENERGY

STAR®

Status

#Location Rating

Additional Information

A-15

MED 4 34038 LED4DA15-W3/827 120 6 3.5 300 2700 80 40W 15,000 Yes Damp White

34051 LED4DA15-C3/827 120 6 3.5 300 2700 80 40W 15,000 Yes Damp Clear A-19

MED 6 69115 LED6DA19/827 120 6 4.4 480 2700 80 40W 15,000 Yes Damp White, Omnidirectional 69118 LED6DA19/830 120 6 4.4 480 3000 80 40W 15,000 Yes Damp White, Omnidirectional

69132 LED6DA19/840 120 6 4.4 480 4000 80 40W 15,000 Yes Damp White, Omnidirectional

69144 LED6DA19/850 120 6 4.4 480 5000 80 40W 15,000 Yes Damp White, Omnidirectional 7 95928 LED7DAV3/5K 120 6 4.6 500 5000 80 40W 25,000 Yes Damp White, Semi-Omni

34238 LED7DA19/824 120 6 4.44 450 2400 80 40W 25000 Yes Damp White 10 69117 LED10DA19/827 120 6 4.4 800 2700 80 60W 15,000 Yes Damp White, Omnidirectional

69119 LED10DA19/830 120 6 4.4 800 3000 80 60W 15,000 Yes Damp White, Omnidirectional 69133 LED10DA19/840 120 6 4.4 800 4000 80 60W 15,000 Yes Damp White, Omnidirectional 69146 LED10DA19/850 120 6 4.4 800 5000 80 60W 15,000 Yes Damp White, Omnidirectional

11 29268 LED11DA19/824 120 6 4.44 800 2400 80 60W 25,000 Yes Damp White, Omnidirectional GU24 11 74357 LED11DA19827GU24 120 6 4.4 800 2700 80 60W 25,000 Yes Damp White, Omnidirectional

A-21 MED 12 76037 LED12DA19/827 120 6 5.16 1100 2700 80 75W 15,000 Yes Damp White, Omni, ES 2.0

76041 LED12DA21/830 120 6 5.16 1100 3000 80 75W 15,000 Yes Damp White, Omni, ES 2.0 76045 LED12DA21/840 120 6 5.16 1100 4000 80 75W 15,000 Yes Damp White, Omni, ES 2.0 76102 LED12DA21/850 120 6 5.16 1100 5000 80 75W 15,000 Yes Damp White, Omni, ES 2.0 73404 LED12DA21/850FE 120 6 5.31 1100 5000 80 75W 25,000 Yes Enclosed White, Enclosed, Omni 73384 LED12DA21/830FE 120 6 5.31 1100 3000 80 75W 25,000 Yes Enclosed White, Enclosed, Omni

15 76038 LED15DA21/827 120 6 5.16 1600 2700 80 100W 15,000 Yes Damp White, Omni, ES 2.0 76043 LED15DA21/830 120 6 5.16 1600 3000 80 100W 15,000 Yes Damp White, Omni, ES 2.0 76060 LED15DA21/840 120 6 5.16 1600 4000 80 100W 15,000 Yes Damp White, Omni, ES 2.0 76117 LED15DA21/850 120 6 5.16 1600 5000 80 100W 15,000 Yes Damp White, Omni, ES 2.0

GU24 16 92498 LED16DA21827GU24 120 6 5.43 1600 2700 80 100W 25,000 Yes Damp White, Omnidirectional MED 16 73376 LED16A30/100/827 120 6 5.31 360/1400/900 2700 80 30/70/100 25,000 - Damp White, 3-Way

92118 LED16A30/100/5KB 120 3 5.31 360/1400/900 5000 80 30/70/100 25,000 - Damp White, 3-Way 22 73378 LED22A50/150/827 120 6 5.31 700/2155/1600 2700 80 50/100/150 25,000 - Damp White, 3-Way

92120 LED22A50/150/5KB 120 3 5.31 700/2155/1600 5000 80 50/100/150 25,000 - Damp White, 3-Way lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight

Spotlight

LED PAR30 short and long neck lamps

To learn more about saving money and energy, go to: http://products.currentbyge.com.

Featuring GE’s exclusive Visual Comfort Lens™ for the perfect blend of enhanced color quality, advanced optics and reduced glare. Exclusive Visual Comfort Lens™ Optics create halogen-like light and contrast, with the energy and cost-efficient benefits of an LED lamp.

For the perfect solution for all of your retail application needs, turn to GE’s retail PAR30 short and long neck lamps. With advanced optics and reduced glare, these lamps offer the light qualities desired by merchants.

LOW-COST OPERATION

• �For example, using only 12 watts of energy, save over $173 in energy costs over the rated life of the lamp versus a standard 75-watt halogen PAR30 lamp based on $0.11 per kWh

• �Energy efficiency and long life mean fewer lamp replacements versus standard incandescent and halogen light sources

• �Our LED PAR lamps have less heat, UV or infrared in the beam, which reduces the potential for fading of materials and décor, compared to halogen or incandescent lamps

EXCELLENT COLOR RENDERING

• Available with a CRI of 80-90

COLOR TEMPERATURE

• Halogen-like color

• Available in 2700K and 3000K

LONG LIFE

• Up to 25,000 hours rated life (L70)

DIMMABLE

• Dims from 100% to 10%

BEAM PATTERNS

• Available in 25˚ and 40˚ beam patterns

ENVIRONMENTALLY CONSCIOUS

• �These lamps are energy efficient and contain no lead or mercury

GE QUALITY AND RELIABILITY

• 3-year limited warranty

Information provided is subject to change without notice. Please verify all details with GE. All values are design or typical values when measured under laboratory conditions, and GE makes no warranty or guarantee, expressed or implied, that such performance will be obtained under end-use conditions.

Application illustation only, subject lamps not used in photo.

lbjla Text Box Frenchman W.C. (Plumas N.F.)

Fixture Type: 'B'

Make/Model: GE LED12DP30R

Bulb Shape

Base Type Watts

Order Code Description Volts

Case Qty**

MOL

(In)

Lumens Initial CBCP

Initial Color Temp CRI

Wattage Replacement

*Rated Life

L70 (Hrs) Dimmable

ENERGY

STAR®

Status

#Location Rating

Additional Information

Compact PAR30 - Low Glare - Visual Comfort Lens™ PAR30 MED 12 84374 LED12DP30RW93015 120 6 3.74 860 9400 3000 90 75W 25,000 Yes Damp Spot, 15° beam, White

84379 LED12DP30RW93025 120 6 3.74 900 3900 3000 90 75W 25,000 Yes Damp Narrow Flood, 25˚ beam, White 84380 LED12DP30RW93040 120 6 3.74 900 1800 3000 90 75W 25,000 Yes Damp Flood, 40˚ beam, White 84392 LED12DP30RW92725 120 6 3.74 850 3500 2700 90 75W 25,000 Yes Damp Narrow Flood, 25˚ beam, White 84395 LED12DP30RW92740 120 6 3.74 850 1700 2700 90 75W 25,000 Yes Damp Flood, 40˚ beam, White 84384 LED12DP30RW83025 120 6 3.74 1050 4800 3000 80 75W 25,000 Yes Damp Narrow Flood, 25˚ beam, White 42131 LED12DP30RW83040 120 6 3.74 1050 2400 3000 80 75W 25,000 Yes Damp Flood, 40˚ beam, White 42133 LED12DP30RW82725 120 6 3.74 1000 4700 2700 80 75W 25,000 Yes Damp Narrow Flood, 25˚ beam, White 42134 LED12DP30RW82740 120 6 3.74 1000 2200 2700 80 75W 25,000 Yes Damp Flood, 40˚ beam, White 73583 LED12DP30RB82740 120 6 3.74 1000 2200 2700 80 75W 25,000 Yes Damp Flood, 40˚ beam, White

Compact PAR30 - Long Neck - Low Glare - Visual Comfort Lens™ PAR30L MED 12 84399 LED12DP3LRW93025 120 6 4.72 900 3900 3000 90 75W 25,000 Yes Damp Narrow Flood, 25˚ beam, White

84400 LED12DP3LRW93040 120 6 4.72 900 1800 3000 90 75W 25,000 Yes Damp Flood, 40˚ beam, White 84407 LED12DP3LRW92740 120 6 4.72 850 1700 2700 90 75W 25,000 Yes Damp Flood, 40˚ beam, White 42136 LED12DP3LRW83025 120 6 4.72 1050 4800 3000 80 75W 25,000 Yes Damp Narrow Flood, 25˚ beam, White 42137 LED12DP3LRW83040 120 6 4.72 1050 2400 3000 80 75W 25,000 Yes Damp Flood, 40˚ beam, White 42141 LED12DP3LRW82725 120 6 4.72 1000 4700 2700 80 75W 25,000 Yes Damp Narrow Flood, 25° beam, White 42144 LED12DP3LRW82740 120 6 4.72 1000 2200 2700 80 75W 25,000 Yes Damp Flood, 40˚ beam, White

ENERGY STAR® is a registered U.S. mark

Product is compliant with material restriction requirements of RoHS

LED PAR30 short and long neck lamps Directional Lamps (PAR) http://products.currentbyge.com.

GE and the GE Monogram are trademarks of the General Electric Company. All other trademarks are the property of their respective owners. Information provided is subject to change without notice. All values are design or typical values when measured under laboratory conditions. GE Lighting and GE Lighting Solutions, LLC are businesses of the General Electric Company. © 2017 GE.

66635 (Rev 08/17/17)

* The life rating is based on the hours of operation the lamp will provide before reaching 70% of its original rating (L70) ** Minimum order quantity = 6

ENERGY STAR® status: ENERGY STAR® certified. Lamps without a “ ” are not ENERGY STAR® certified.

# UL 1993 Environmental Requirements for LED LAMPS
Location, damp – Exterior or interior location that is normally or periodically subject to condensation of moisture in, on, or adjacent to, electrical equipment,
and includes partially protected locations.
Location, dry– Location not normally subject to dampness, may include a location subject to temporary dampness, i.e., building under construction,
provided ventilation is adequate to prevent an accumulation of moisture.
Location, wet– Location in which water or other liquid can drip, splash, or flow on or against electrical equipment.
Notes:1) Product descriptions ending in “/TP” indicate a carded blister or clamshell package nested in a tray for shelf display. Cards also designed for hook display.

Information provided is subject to change without notice. Please verify all details with GE. All values are design or typical values when measured under laboratory conditions, and GE makes no warranty or guarantee, expressed or implied, that such performance will be obtained under end-use conditions.

Directional Lamps (PAR30 - High Output)

Bulb Shape Base Type Watts

Order Code Description Volts

Case Qty**

MOL

(In)

Lumens Initial CBCP

Initial Color Temp CRI

Wattage Replacement

*Rated Life

L70 (Hrs) Dimmable

ENERGY

STAR®

Status

#Location Rating

Additional Information

Universal 120-277V PAR30 HO MED 18 75089 LED18P30LW83015 120-277 6 4.6 1800 15500 3000 80 75W 25,000 - Damp Spot, 15°, White

75091 LED18P30LW83025 120-277 6 4.6 1800 7000 3000 80 75W 25,000 - Damp Narrow Flood, 25°, White

75065 LED18P30LW93015 120-277 6 4.6 1400 12500 3000 90 75W 25,000 - Damp Spot, 15° beam, MTO, 1000 Min. Qty, 12 Week Lead Time, White

75078 LED18P30LW93025 120-277 6 4.6 1400 5000 3000 90 75W 25,000 - Damp Narrow Flood, 25°, White lbjla Highlight lbjla Highlight lbjla Highlight

XTOR

CROSSTOUR LED

APPLICATIONS:

WALL / SURFACE

POST / BOLLARD

LOW LEVEL

FLOODLIGHT

INVERTED

SITE LIGHTING

Lumark

SPECIFICATION FEATURES

Construction Slim, low-profile LED design with rugged one-piece, die-cast aluminum hinged removable door and back box. Matching housing styles incorporate both a small and medium design. The small housing is available in 12W, 18W and 26W. The medium housing is available in the 38W model.

Patented secure lock hinge feature allows for safe and easy tool-less electrical connections with the supplied push-in connectors. Back box includes three half-inch, NPT threaded conduit entry points. The universal back box supports both the small and medium forms and mounts to standard 3-1/2” to 4” round and octagonal, 4” square, single gang and masonry junction boxes. Key hole gasket allows for adaptation to junction box or wall. External fin design extracts heat from the fixture surface. One-piece silicone gasket seals door and back box. Minimum 5” wide pole for site lighting application.

Not recommended for car wash applications.

Optical Silicone sealed optical LED chamber incorporates a custom engineered mirrored anodized reflector providing high-efficiency illumination. Optical assembly includes impact-resistant tempered glass and meets IESNA requirements for full cutoff compliance. Available in seven lumen packages; 5000K, 4000K and

3000K CCT.

Electrical LED driver is mounted to the die-cast housing for optimal heat sinking. LED thermal management system incorporates both conduction and natural convection to transfer heat rapidly away from the LED source. 12W, 18W, 26W and 38W series operate in -40°C to 40°C [-40°F to 104°F]. High ambient 50°C models available. Crosstour luminaires maintain greater than 89% of initial light output after 72,000 hours of operation. Three half-inch NPT threaded conduit entry points allow for thru-branch wiring. Back box is an authorized electrical wiring compartment.

Integral LED electronic driver incorporates surge protection. 120- 277V 50/60Hz or 347V 60Hz models.

Finish Crosstour is protected with a Super durable TGIC carbon bronze or summit white polyester powder coat paint. Super durable TGIC powder coat paint finishes withstand extreme climate conditions while providing optimal color and gloss retention of the installed life.

Warranty Five-year warranty.

TD514013EN

2017-07-25 12:21:59

The patented Lumark Crosstour™ LED Wall Pack Series of luminaries provides an architectural style with super bright, energy efficient LEDs.

The low-profile, rugged die-cast aluminum construction, universal back box, stainless steel hardware along with a sealed and gasketed optical compartment make the Crosstour impervious to contaminants. The Crosstour wall luminaire is ideal for wall/surface, inverted mount for façade/canopy illumination, post/bollard, site lighting, floodlight and low level pathway illumination including stairs. Typical applications include building entrances, multi-use facilities, apartment buildings, institutions, schools, stairways and loading docks test.

DESCRIPTION

Catalog # Type

Date

Project

Comments

Prepared by

12W, 18W, 26W 5-3/4" [146mm]

38W 6-5/8" [168mm]

12W, 18W, 26W 6-3/4" [171mm]

38W 8" [203mm]

12W, 18W, 26W 3-5/8" [92mm]

38W 4" [102mm]

DIMENSIONS

C E R T I F I C A T I O N D A T A UL/cUL Wet Location Listed LM79 / LM80 Compliant ROHS Compliant ADA Compliant NOM Compliant Models IP66 Ingressed Protection Rated Title 24 Compliant DesignLights Consortium® Qualified*

T E C H N I C A L D A T A 40°C Maximum Ambient Temperature External Supply Wiring 90°C Minimum

E P A Effective Projected Area (Sq. Ft.):

XTOR1B, XT0R2B, XT0R3B=0.34

XTOR4B=0.45

S H I P P I N G D A T A :

Approximate Net Weight:

3.7 – 5.25 lbs. [1.7 – 2.4 kgs.]

10" [254mm]

17-1/2" [445mm]

10" [254mm]

17-1/2" [445mm]

ESCUTCHEON PLATES

*www.designlights.org

Specifications and dimensions subject to change without notice.

Eaton 1121 Highway 74 South Peachtree City, GA 30269 P: 770-486-4800 www.eaton.com/lighting

Ambient Temperature

TM-21 Lumen Maintenance

(72,000 Hours)

Theoretical L70 (Hours)

XTOR1B Model

25°C > 90% 255,000

40°C > 89% 234,000

50°C > 88% 215,000

XTOR2B Model

25°C > 89% 240,000

40°C > 88% 212,000

50°C > 87% 196,000

XTOR3B Model

25°C > 89% 240,000

40°C > 88% 212,000

50°C > 87% 196,000

XTOR4B Model

25°C > 89% 222,000

40°C > 87% 198,000

50°C > 87% 184,000

LUMEN MAINTENANCE

LED Information XTOR1B XTOR1B-W XTOR1B-Y XTOR2B XTOR2B-W XTOR2B-Y XTOR3B XTOR3B-W XTOR3B-Y XTOR4B XTOR4B-W XTOR4B-Y

Delivered Lumens (Wall Mount)

1,418 1,396 1,327 2,135 2,103 1,997 2,751 2,710 2,575 4,269 4,205 3,995

Delivered Lumens (With Flood Accessory Kit) 1

1,005 990 940 1,495 1,472 1,399 2,099 2,068 1,965 3,168 3,121 2,965

B.U.G. Rating 2 B1-U0-G0 B1-U0-G0 B1-U0-G0 B1-U0-G0 B1-U0-G0 B1-U0-G0 B1-U0-G0 B1-U0-G0 B1-U0-G0 B2-U0-G0 B2-U0-G0 B2-U0-G0

CCT (Kelvin) 5,000 4,000 3,000 5,000 4,000 3,000 5,000 4,000 3,000 5,000 4,000 3,000

CRI (Color Rendering Index)

70 70 70 70 70 70 70 70 70 70 70 70

Power Consumption (Watts)

12W 12W 12W 18W 18W 18W 26W 26W 26W 38W 38W 38W

NOTES: 1 Includes shield and visor. 2 B.U.G. Rating does not apply to fl oodlighting.

POWER AND LUMENS BY FIXTURE MODEL

Voltage Model Series

XTOR1B XTOR2B XTOR3B XTOR4B

120V 0.103A 0.15A 0.22A 0.34A

208V 0.060A 0.09A 0.13A 0.17A

240V 0.053A 0.08A 0.11A 0.17A

277V 0.048A 0.07A 0.10A 0.15A

347V 0.039A 0.06A 0.082A 0.12A

CURRENT DRAW

XTOR CROSSTOUR LED

TD514013EN

2017-07-25 12:21:59

0 10 20 30 40 50 60 70 80 90 100

Hours (Thousands)

Lu m en M ai n te n an ce

Pe rc en t)

50°C 40°C 25°C lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight change without notice.

Eaton 1121 Highway 74 South Peachtree City, GA 30269 P: 770-486-4800 www.eaton.com/lighting

TD514013EN

2017-07-25 12:21:59

XTOR CROSSTOUR LED

12W Series 18W Series 26W Series 38W Series

XTOR1B=12W, 5000K, Carbon Bronze XTOR2B=18W, 5000K, Carbon Bronze XTOR3B=26W, 5000K, Carbon Bronze XTOR4B=38W, 5000K, Carbon Bronze

XTOR1B-WT=12W, 5000K, Summit White XTOR2B-W=18W, 4000K, Carbon Bronze XTOR3B-W=26W, 4000K, Carbon Bronze XTOR4B-W=38W, 4000K, Carbon Bronze

XTOR1B-PC1=12W, 5000K, 120V PC,

Carbon Bronze

XTOR2B-WT=18W, 5000K, Summit White XTOR3B-WT=26W, 5000K, Summit White XTOR4B-WT=38W, 5000K, Summit White

XTOR1B-W=12W, 4000K, Carbon Bronze XTOR2B-PC1= 18W, 5000K, 120V PC, Carbon Bronze

XTOR3B-PC1= 26W, 5000K, 120V PC,

Carbon Bronze

XTOR4B-PC1= 38W, 5000K, 120V PC, Carbon Bronze

XTOR1B-W-PC1=12W, 4000K, 120V PC,

Carbon Bronze

XTOR2B-W-PC1= 18W, 4000K, 120V PC,

Carbon Bronze

XTOR4B-W-PC1= 38W, 4000K, 120V PC,

Carbon Bronze

STOCK ORDERING INFORMATION

Sample Number: XTOR2B-W-WT-PC1

Series 1 LED Kelvin Color Housing Color Options (Add as Suffi x) Accessories (Order Separately)

XTOR1B=Small Door, 12W XTOR2B=Small Door, 18W XTOR3B=Small Door, 26W XTOR4B=Medium Door, 38W

[Blank]= Bright White (Standard), 5000K

W=Neutral White, 4000K Y=Warm White, 3000K

[Blank]= Carbon Bronze (Standard)

WT=Summit White BK=Black BZ=Bronze AP=Grey GM=Graphite Metallic DP=Dark Platinum

PC1=Photocontrol 120V 2

PC2=Photocontrol 208-277V 2, 3

347V=347V 4

HA=50ºC High Ambient 4

WG/XTOR=Wire Guard 5

XTORFLD-KNC=Knuckle Floodlight Kit 6

XTORFLD-TRN=Trunnion Floodlight Kit 6

XTORFLD-KNC-WT=Knuckle Floodlight Kit, Summit White 6

XTORFLD-TRN-WT=Trunnion Floodlight Kit, Summit White 6

EWP/XTOR= Escutcheon Wall Plate, Carbon Bronze EWP/XTOR-WT= Escutcheon Wall Plate, Summit White

NOTES:

1. DesignLights Consortium® Qualifi ed and classifi ed for both DLC Standard and DLC Premium, refer to www.designlights.org for details.

2. Photocontrols are factory installed.

3. Order PC2 for 347V models.

4. Thru-branch wiring not available with HA option or with 347V. XTOR3B not available with HA and 347V or 120V combination.

5. Wire guard for wall/surface mount. Not for use with fl oodlight kit accessory.

6. Floodlight kit accessory supplied with knuckle (KNC) or trunnion (TRN) base, small and large top visors and small and large impact shields.

ORDERING INFORMATION

lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight

Metalux

WNLED

LED

Uti l i ty LED Wraparound

SPECIFICATION FEATURES

Construction Housing consists of die formed cold rolled steel. Ends formed with the housing for strength and provisions for continuous row aligners. Steel end plates with 7/8” KO and light-seal embossment.

Driver cover can be removed without tools.

Controls WNLED is Powered by Fifth Light, with standard a 0-10V continuous dimming driver that works with any 0-10V control/ dimmer.

Combine with energy saving products like occupancy sensors, daylighting controls and lighting relay panels to maximize energy savings. Dimming range is 10% to 100%; varies by control device.

Electrical Long-Life LED system coupled with electrical driver to deliver optimal performance. LED’s available in 3000K, 3500K, 4000K and 5000K with a min. 80 CRI. Projected life at 70% lumen maintenance is nearly 150,000 hours with TM21 rating up to L88 > 60,000 hours. Electronic drivers are available for 120-277V applications. A 0-10V dimming driver is standard.

Emergency Battery Pack Option Optional 120V-277V integral emergency battery pack is available in 7-watts or 14-watts to meet critical life-safety lighting requirements. The 90-minute batteries provide constant power to the LED system, ensuring code compliance. The patented EZ Key prevents accidental discharge of the battery during construction.

Finish Multistage iron phosphate pretreatment ensures maximum bonding and rust inhibitor. High reflective paint after fabrication, baked white enamel finish is standard.

Channel/Wireway Cover Die formed heavy gauge steel.

Tight fit for ease of maintenance.

Shielding Acrylic, high performance, frost blend. Sides have inside linear prisms and bottom has pyramidal prisms for low brightness control.

Instal lation Fixture may be surface, pendant, or stem mounted. See accessories below for ordering information.

Compliance Indoor luminaires are cULus listed for 25ºC ambient environments, damp location listed, RoHS compliant, and LED modules comply with IESNA LM-79 and LM-80 standards. DesignLights Consortium® Qualified and classified for DLC Standard, refer to www.designlights.org for details.

Suitable for use in clothes closets when installed in accordance with the NEC 410.16 spacing requirements. Can be used for State of California Title 24 high efficacy luminaire.

Our updated WNLED series is a versatile utility based, traditionally styled LED wraparound series which can be used in a broad range of commercial, schools, institutional, retail and residential applications.

This high quality luminaire series utilizes the latest solid state LED lighting and advanced electronic driver technology which provides optimal lighting performance and maximizing energy savings. WNLED is designed to provide long service life eliminating re-lamping issues and minimizing maintenance common with traditional fluorescent.

DESCRIPTION

PS519062EN

May 21, 2018 2:35 PM

1-13/16" [46mm]

19" [483mm] 20-5/8" [523mm]

1-1/8" [29mm]

24" [610mm]

8-3/16" [208mm]

1" [25mm]1" [25mm]

6" [152mm]

7-5/8" [194mm]

2'

1-1/8" [29mm]

42-15/16" [1090mm] 44-1/2" [1131mm]1-13/16"

[46mm]

7/8" [22mm] K.O. (5)

Ground Screw Bump Ceiling Stand-Off Embossments

48" [1219mm]

42-7/16" [1078mm]

40-7/16" [1027mm]

3" [76mm]

4-1/2" [114mm]

6" [152mm]

7-5/8" [194mm]

4'

MOUNTING DATA

2-1/2" [63mm]

7-5/8" [194mm]

6" [152mm]

ENERGY AND PERFORMANCE DATA BY CATALOG NUMBER

Lumen Type Length Catalog Number

Nominal 3500K Lumens Wattage lm/W

Standard 2 ft. 2WNLED-LD4-28SL-F-UNV-L8XX-CD1-U 2786 27.5 101

Standard 4 ft. 4WNLED-LD4-32SL-F-UNV-L8XX-CD1-U 3298 28.0 118

Standard 4 ft. 4WNLED-LD4-40SL-F-UNV-L8XX-CD1-U 4062 36.0 113

Standard 4 ft. 4WNLED-LD4-50SL-F-UNV-L8XX-CD1-U 4966 46.6 107

California Title 24 Non-Residential

Compliant

Catalog #

Project

Comments

Prepared by

Type

Date lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight change without notice.

Eaton 1121 Highway 74 South Peachtree City, GA 30269 P: 770-486-4800 www.eaton.com/lighting

WNLED

Catalog No. Wt.

2WNLED 5 lbs.

4WNLED 9 lbs.

SHIPPING DATA

Series (3)

WNLED=Utility LED Wraparound

S A M P L E N U M B E R : 4 W N L E D - L D 4 - 4 0 S L - F - U N V - L 8 4 0 - C D 1 - U

Packaging U=Unit Pack

Lamp Type

LD4=LED

LED Lumens Output

28SL=2800 (1)

32SL=3200

40SL=4000

50SL=5000

Voltage 347=347V (2)

480=480V (2)

UNV=Universal Voltage 120-277

Number of Drivers 1=1 Driver

Lens F=Frost Acrylic (standard)

Length 2=2 ft.

4=4 ft.

A C C E S S O R I E S SCF=Fixed Stem Set (Specify Length) SCS=Swivel Stem Set (Specify Length) SCA=Adjustable 48" Stem Set A1B/Spacer-U=Spacer 1-1/2" to 2-1/2" from ceiling (Use 2 per fixture) WN22AU=2' Replacement Lens WN24AU=4' Replacement Lens

NOTES: (1) 2 ft. model. (2) 4 ft. model only. (3) DesignLights Consortium® Qualified and classified for DLC Standard, refer to www.designlights.org for details. (4) With integral test switch/indicator/laser test. For approximate delivered lumens multiply the lumens per watt of the desired fixture by the wattage of the emergency battery pack (100 lm/W x 7=700 lumens). IES-format photometry for luminaire under emergency operation available.

(5) 5LTD DALI driver available for all lumen unit only. (6) Emergency options not available for 2 ft. versions. Requires larger cover which changes the appearance. (7) Emergency options use taller ballast cover that alters appearance.

Specifications & dimensions subject to change without notice. Consult your Eaton Representative for availability and ordering information.

Driver Type CD=0-10V Dimming Driver (10% - 100% Dimming)

Options Emergency (7)

CCT

L830=3000K L835=3500K L840=4000K L850=5000K

EL7W=7-watt, 120V-277V emergency battery pack installed (4), (6)

EL14W=14-watt 120V-277V emergency battery pack installed (4), (6)

ORDERING INFORMATION

4WNLED-LD4-32SL-

F-UNV-L835-CD1-U

Electronic Driver

Linear LED 3500K

Spacing criterion:

(II) 1.2 x mounting height, (⊥) 1.2 x mounting height

Lumens: 3298

Input Watts: 28.0W

Efficacy: 117.8 lm/W

Test Report:

4WNLED-LD4-32SL-F-

UNV-L835-CD1-U.IES

C a n d l e p owe r

Angle Along II 45° Across ⊥

1124 1124 1124 1124 1120 1116 1103 1102 1100 1069 1071 1071 1023 1029 1031 966 975 978 899 913 918 826 845 853 747 771 781 669 695 707 586 615 631 504 535 554 422 455 476 342 377 400 265 302 327 190 231 257 121 164 190 56 100 125 0 44 70

C o e ffi c i e n t s o f U t i l i z a t i o n

Effective floor cavity refl ectance 20% rc 80% 70% 50% 30% 10% 0% rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0

RCR

118 118 118 118 114 114 114 114 108 108 108 102 102 102 97 97 97 94 107 102 97 93 103 99 95 91 94 90 87 89 86 84 84 82 80 78 97 89 82 76 94 86 80 74 82 76 72 78 73 69 74 70 67 64 88 78 69 63 85 76 68 62 72 65 60 68 63 58 65 60 57 54 81 69 60 53 78 67 59 53 64 57 51 61 55 50 58 53 49 46 74 62 52 46 72 60 52 45 57 50 44 55 48 43 52 47 42 40 69 55 46 40 66 54 46 40 52 44 39 50 43 38 47 42 37 35 64 50 41 35 62 49 41 35 47 40 34 45 39 34 43 38 33 31 59 46 37 32 57 45 37 31 43 36 31 41 35 30 40 34 30 28 55 42 34 28 54 41 33 28 40 33 28 38 32 27 37 31 27 25 52 39 31 26 50 38 31 26 37 30 25 35 29 25 34 29 24 23

Z o n a l L u m e n S u m m a r y

Zone Lumens % Fixture 0-30

0-40

0-60

0-90

0-180

855 25.9

1381 41.9

2390 72.5

3109 94.3

3298 100.0

0˚ 15˚ 30˚

45˚

60˚

75˚

90˚

PHOTOMETRICS

4WNLED-LD4-40SL-

F-UNV-L835-CD1-U

Electronic Driver

Linear LED 3500K

Spacing criterion:

(II) 1.2 x mounting height, (⊥) 1.2 x mounting height

Lumens: 4062

Input Watts: 36.0W

Effi cacy: 112.8 lm/W

Test Report:

4WNLED-LD4-

40SL-F-UNV-L835-

CD1-U.IES

C a n d l e p owe r

Angle Along II 45° Across ⊥

1386 1386 1386 1385 1380 1375 1360 1357 1354 1318 1320 1320 1261 1266 1268 1190 1201 1203 1109 1125 1128 1018 1042 1048 922 951 964 823 857 868 721 759 773 620 660 678 521 561 584 421 464 492 326 372 403 234 285 317 148 201 233 70 123 154 1 57 89

C o e ffi c i e n t s o f U t i l i z a t i o n

Effective fl oor cavity refl ectance 20% rc 80% 70% 50% 30% 10% 0% rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0

RCR

118 118 118 118 114 114 114 114 108 108 108 102 102 102 97 97 97 94 107 102 97 93 103 99 95 91 94 90 87 89 86 84 84 82 80 78 97 89 82 76 94 86 80 74 82 76 72 78 73 69 74 70 67 64 88 78 69 63 85 76 68 62 72 65 60 68 63 58 65 61 57 54 81 69 60 53 78 67 59 53 64 57 51 61 55 50 58 53 49 46 74 62 52 46 72 60 52 45 57 50 44 55 48 43 52 47 42 40 69 55 46 40 66 54 46 40 52 44 39 50 43 38 47 42 37 35 64 50 41 35 62 49 41 35 47 40 34 45 39 34 43 38 33 31 59 46 37 32 57 45 37 31 43 36 31 41 35 30 40 34 30 28 55 42 34 28 54 41 33 28 40 33 28 38 32 27 37 31 27 25 52 39 31 26 50 38 31 26 37 30 25 35 29 25 34 29 24 23

Z o n a l L u m e n S u m m a r y

Zone Lumens % Fixture 0-30

0-40

0-60

0-90

0-180

1054 25.9

1702 41.9

2945 72.5

3832 94.3

4062 100.0

0˚ 15˚ 30˚

45˚

60˚

75˚

90˚

Approximate Color Temperature Multiplier

5000K 1.03

4000K 1.00

3000K 0.98

CCT TABLE

PS519062EN

May 21, 2018 2:35 PM lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight

Metalux

WNLED

LED

Uti l i ty LED Wraparound

SPECIFICATION FEATURES

Construction Housing consists of die formed cold rolled steel. Ends formed with the housing for strength and provisions for continuous row aligners. Steel end plates with 7/8” KO and light-seal embossment.

Driver cover can be removed without tools.

Controls WNLED is Powered by Fifth Light, with standard a 0-10V continuous dimming driver that works with any 0-10V control/ dimmer.

Combine with energy saving products like occupancy sensors, daylighting controls and lighting relay panels to maximize energy savings. Dimming range is 10% to 100%; varies by control device.

Electrical Long-Life LED system coupled with electrical driver to deliver optimal performance. LED’s available in 3000K, 3500K, 4000K and 5000K with a min. 80 CRI. Projected life at 70% lumen maintenance is nearly 150,000 hours with TM21 rating up to L88 > 60,000 hours. Electronic drivers are available for 120-277V applications. A 0-10V dimming driver is standard.

Emergency Battery Pack Option Optional 120V-277V integral emergency battery pack is available in 7-watts or 14-watts to meet critical life-safety lighting requirements.