This is an Operation & Maintenance Manual for an off-grid renewable energy project at Pine Hills Fire Station in the Cleveland National Forest, Julian, California. The project was completed by Trane U.S. in November 2018 under contracts GS-07F-0248K and AG-9A40-D-15-0007 for the USDA Forest Service Region 5 ESPC Enable AFFECT Off-Grid Renewable Project.

The manual documents two primary system components: a Mobile Solar PV system and LED lighting upgrades. The Mobile Solar PV system consists of one MS-275-R2.140 trailer unit (containing 2 Outback Power Radian GS8048A inverters, 2 FLEXmax 80 charge controllers, 9 LG 335-watt PV panels, and 2 IBE 70 kWh lead acid batteries providing 140 kWh combined capacity and two days of autonomy) and two SA-24 PV panel trailers (each containing 24 LG 335-watt panels producing 36 kWh per day). The LED lighting retrofit included replacement of T12 fluorescent fixtures with LED wraparound fixtures (Metalux WNLED series in 2-foot and 4-foot configurations), PAR30 LED lamps (GE models in various beam patterns and color temperatures), Lumark Crosstour LED wall packs (12W to 38W models), and GE LED A-line replacement lamps. The facility operates seasonally from May through October with average daily electrical loads of 63.5 kWh. The one-year construction warranty period ran from November 8, 2018 through November 8, 2019 with no equipment failures reported. For service and warranty support, Trane U.S. contact information is provided with primary contact Richard Swank at (916) 577-1126 or secondary service at 1-866-459-4155. The manual includes detailed product data sheets, wiring diagrams, maintenance procedures, and safety warnings restricting service to qualified personnel only.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OPERATION & MAINTENANCE MANUAL

Contract: GS-07F-0248K/AG-9A40-D-15-0007

USDA Forest Service, Region 5, ESPC Enable AFFECT Off-Grid Renewable Project

Pine Hills Fire Station

Cleveland National Forest

Julian, CA

Prepared by: Trane U.S., 4145 Del Mar Avenue, Rocklin, CA 95677

Phone: (916) 577-1100; Fax: (916) 577-1175

Revised December 4, 2020

PREFACE

This Operation & Maintenance Manual provides for installation instructions, operating procedures, equipment wiring diagrams, product numbers, scheduled maintenance procedures, warranty information and Trane representative contacts.

The main components of this project involved installation of new LED Lighting throughout the facilities and also a Mobile Solar PV system.

Only qualified personnel shall perform any servicing and maintenance of the equipment.

SAFETY WARNING

Only qualified personnel should install and service this equipment. The installation, starting up, shutting down and servicing of the LED Lighting and Mobile Solar PV equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in this manual, tags, stickers, and the drawings, etc.

Table of Contents

1. Contacting Trane for Service & Warranty

2. Overview of Project (White Paper)

3. Construction Drawings As-Built (Mobile Solar PV & LED Lighting)

4. LED Lighting Product Data & Installation Details

5. LED Lighting Operation & Maintenance

6. Mobile Solar PV Product Data & Installation Details

7. Mobile Solar PV System Operation & Maintenance

8. Warranty

SECTION 1

Contacting Trane for Service & Warranty

Trane Service & Warranty Contact Information:

Address: Trane U.S., 4145 Del Mar Avenue, Rocklin, CA 95677

Main Office Phone & Fax: Ph: (916) 577-1100; Fax: (916) 577-1175

Primary contact: Richard Swank, phone: (916) 577-1126; email: Richard.swank@trane.com

Secondary contact (Trane Service Department): 1-866-459-4155

Project Completion:

Trane U.S. was the installing Contractor for the Pine Hills F.S. ‘Off-Grid Mobile Solar & LED

Lighting project. The project installation was completed and commissioned on November 7 & 8, 2018. A 30-day acceptance period occurred from November 8, 2018 and completed on

December 8, 2018. Commissioning documents were produced, provided, reviewed and signed by Forest of R5 personnel on November 7, 2018.

One (1) Year Construction Warranty Period:

A one (1) year construction installation warranty period started on November 8, 2018 and ended on November 8, 2019. There were no noted equipment failures during this period requiring a warranted repair or product replacement.

Equipment Warranty:

Each product installed for this project may have a ‘product warranty’. Within this manual are listed each products information and manufacture warranty information. If you believe you may have a product that is covered under warranty please contact Trane U.S. first before attempting to replace the product with a like-in-kind replacement.

A product warranty typically covers a manufacturer product defect in manufacture (i.e.: an LED light fixture fails within the warranty period). Specific details of products covered are warranty are to be found in the ‘Warranty’ section of this manual.

mailto:Richard.swank@trane.com lbjla Text Box See SECTION 8 in this manual for Warranty information

Overview of Project (Trane ‘White Paper’)

SECTION 2

The following pages consist of the Trane ‘White Paper’ which provides for information concerning the Pine Hills Fire Station as ‘it was’ before the ENABLE project was implemented and the inventory of the existing equipment (electrical, lighting, generator, water, fuel usage, etc.).

In the white paper there is information on the recommendations for the constructed project in regards to the Mobile Solar PV system sizing and siting. Also, the existing lighting and LED

Lighting related work is inventoried. This document is a useful reference for the Pine Hills F.S.

site.

This document is important as it provides background knowledge of the site, and the inputs of information into IGA survey that Trane performed.

We also recommend that the final ‘Construction’ drawings in this manual be referenced for actual final installed products and details.

Contract # AG-94A40-D-15-0007 for

U.S. Forest Service ESPC ENABLE AFFECT Off-Grid Renewable Energy Project

Pine Hills Fire Station – Cleveland National Forest

12-1-19 Updated

On September 27th and 28th, 2015, Trane performed a site walk visit for the IGA Audit data collection at the Pine Hills Fire Station. The site was in operation during the visit. We met with several Forest Service members at the site that were knowledgeable as to facility operations. We were able to see the generator in operation and also inventory all of the lighting, appliances, etc.

We are providing Trane’s findings from the U.S. Forest site visit in the following five (5) Section elements: I. Location, II. Site Overview, III. Investment Grade Audit (IGA) Site Visit Findings, IV. Sustainable / Solar Siting Considerations and last, Appendix – Pictures.

I. Location

The Pine Hills Fire Station facility is located nearly 75 miles northeast of San Diego, CA. The site is at an elevation of 3,650 feet and experiences some snow in the winter months. The best way to reach the site is to leave from San Diego, CA travelling ‘east’ on Highway 94-E until you reach Highway 125 ‘north’ and travel until you reach I-8 ‘east’. Take I-8E for about 25 miles. Then take Exit 40 towards Descanso via Highway 79(north)/Japatul Valley Road. Continue on Highway 79 towards Julian, CA. Just before Julian take a ‘right’ onto Pine Hills Road. Travel on Pine Hills Road for about 6.5 miles, then make a right onto Eagle Peak Road and follow it until it joins Boulder Creek Road and travel about 5 miles until you reach the Pine Hills Fire Station.

II. Site Overview

Pine Hills Fire Station is open and typically used from May through the end of October (184 days). It is occasionally used in the winter months for about once-a-week with 1 or 2 personnel on-hand and typically for winter checks of the facility by the Forest Service.

Winter access may be occasionally limited with a few inches of snow conditions (i.e.: from November through March). The site has a Fire Engine Bay with an Office, one Barrack building; and a Generator building with a storage area and also several smaller out-buildings for storage and fueling supplies including a few trailer parking areas for USFS personnel in the summer periods.

Fire Engine Bay and Office Building consists of a single bay area for the fire tanker, a small front office, a Fire Captain’s office with a restroom and a storage and fire cache area on the northwest side of the building. All of the lighting is T12 fluorescent light fixtures at all inside areas. The exterior light fixtures are PAR38 lamps and MH wall packs. There is main radio operations in this building for the site. A propane hot water heater is in an indoor closet, a wall heater and a small heat pump unit (thru-the-wall) serves only the Captain’s Office area.

Barrack Building consists of four bedrooms of which one is being used as an exercise room, there is a living room area, a kitchen area, laundry room and three restroom/shower rooms.. The building has a central HVAC split system that has propane for heat. The unit is located at the end of the hallway near the bedrooms.

Generator / Storage Building has one (1) 20-kW (nominal) Cummins generator that operates from propane. This generator typically runs from 0930 until 1800 hours, 7-days/week during operating season with some evening and morning use for a couple hours due to some use of the Barracks during the operating season. During the winter (off season) there is occasional use of the site at most once-a-week or every other week. There are a couple propane tanks at the site for the generator, barracks and engine bay building for heaters, gas stoves, and other propane consuming appliances such as refrigerators.

Fuel Storage building is small structure for storing small gas cans and fuel for equipment.

There is one incandescent light in the building.

There is a submersible well pump down near a creek bed area that feeds water to a large storage water tank up on the hill past the fire station. The domestic water to the site is gravity fed from the storage tank.

III. Investment Grade Audit (IGA) Site Visit Findings Findings from this site visit is subdivided by primary Energy Conservation Measure categories, power generation and fuel. Photo documentation from the site visit are provided in the Appendix.

A. Electrical

The following electrical loads currently exist at the Pine Hills Fire Station site:

(Continued on next page)

Electrical Notes

(1) Based upon above ‘current loads’ and field observations this site has varying loads and typically has light generator loads.

A diversity of operating loads and times of use was seen. Measurements of the total watts during our visit varied from

3,500 to nearly 12,000 watts (at full load including having the submersible well pump, facility lighting and appliance loads all ‘ON’).

(2) During field site visit the generator was observed with an average daytime load of 3,500 kVA. This is a nominal use load.

The Barracks are not used much in daytime periods. Load may increase during mornings and evenings when Barracks are used.

(3) All CFL’s and incandescent lamps should be changed to LED lamps. This will help reduce overall lighting loads.

(4) The Engine Bay exterior metal halides will be changed to LED wall pack style of fixtures.

(5) T12 fixtures will be replaced with LED fluorescents. T8 fixtures will have new LED lamps.

(6) All appliances remain ‘as is’ (i.e.: no change in load wattages or replacement of appliances).

(7) We recommend a mobile solar PV system to avoid a separate building for the battery system. A mobile solar PV solution would have the battery inside the trailer. This also may eliminate a concern with the NEPA.

B. Water

The table below summarizes Trane’s inventory of water consuming devices for the site:

Water Consuming Devices:

No. Description Recommendations Hours of Use Notes

1 Engine Bay - Bathroom Sink No Change Light Use Fixture remains as is 2 Engine Bay - Bathroom Toilet No Change Light Use Fixture remains as is 3 Engine Bay - Shower No Change Light Use Low Flow Shower Head

4 Barracks – Kitchen Sink No Change Light Use Fixture remains as is 5 Barracks – Restroom #1, Sink No Change Light Use Fixture remains as is 6 Barracks – Restroom #1, Toilet No Change Light Use Fixture remains as is 7 Barracks – Restroom #2, Shower No Change Light Use Low Flow Shower Head

8 Barracks – Restroom #3, Sink No Change Light Use Fixture remains as is 9 Barracks – Restroom #3, Toilet No Change Light Use Fixture remains as is

10 Barracks – Clothes Washer No Change Light Use Appliance remains as is

NOTE: This site has minimal water usage from the fixtures listed in the above table. Most of the water consumption is from filling of the fire engine and washing fire equipment. Therefore, we do not recommend any fixture changes for this site.

C. Generator

There is one (1) Cummins model #GGMA-5936770 propane powered generator that has a nominal nameplate ‘standby’ rating of 20-kW and ‘prime’ rating of 18-kW ‘before’ being de-rated for an elevation of 3,650 feet. Cummins literature states to apply a de-rate factor of 4% per 1,000 feet of elevation gain, therefore the de-rate on the 20-kW ‘standby’ rating correlates to 17.2-kW and 15.5-kW for the ‘prime’ rating. The generator provides for 120/240- volt, 1-phase power. ‘Prime’ maximum amps would be 71.5 at 17.2-kW and 64.5 amps at 15.5-kW at full load. NOTE: This generator was replaced in November, 2018 with a new Cummins model C20 N6 (nominal 20-kW, 120/240V, 1-ph., standby generator).

The annual generator maintenance costs will vary year-to-year. The information provided by the Forest Service indicates an annual cost of $3,000. We have only stipulated an average of $3,000 per year as we do not have actual invoices from expenses incurred. We would expect on-going maintenance costs of this value or greater per year.

D. Fuel – Propane

The table below summarizes Trane’s inventory of propane consuming devices for the site:

No. Description Recommendations Future Hours of Use Notes / Recommendations

1 Cummins GGMA Propane Generator Model #GGMA-5936770 (C20 N6) 2018

Use for charging batteries & back-up power

Only when needed

Use for charging batteries & powering site, if needed

2 Engine Bay – Water Heater (40gal)

32K BTUH

Leave in-place Light Use 70% Eff., Minimum usage

3 Engine Bay –Wall Heater; 50kBTUH in Leave unit in-place.

No Change. Unit mostly left ‘off’

Light Use Leave unit ‘as is’

4 Barracks – Refrigerator #1 & #2, M#RGE-400; 1500

BTUH/each(2011)

Leave in-place In use when occupied

Leave ‘as is’

6 Barracks – Carrier Heating Unit 60K High / 39K Low input

Leave in-place Change to programmable thermostat

In use when occupied

Leave unit ‘as is’

7 Barracks – H.W. Heater (Bradford White) 50 gal.; 36K BTUH

Leave in-place Light Use Leave H.W. heater ‘as is’

8 Barracks – Lennox Heating Unit (200K input; 155.5K output) 78% eff.

Leave in-place Change to programmable thermostat

Light Use Leave unit ‘as is’

Trane received actual propane fuel bills for the previous 3-year period at this site. The U.S.

Forest Service has varying estimates for fuel costs year-to-year in the original data provided in solicitation Excel data chart. We have stipulated and used $24,186 per year of annual fuel costs (based upon previous 2013-15 fuel bill data provided) and the actual fuel bills to substantiate these costs. The estimated cost/hour to operate is $3.75/hour. Annual maintenance costs average $3,000.00/year.

The following Forest Service ENABLE AFFECT table is provided with older fuel data values as shown below from the fall of 2013 to the fall of 2014, which did not correlate to actual fuel bills:

Cleveland Forest Fuel Consumption

Fuel Fuel Cost Notes

Pine Hills F.S. Gallons Type $ Dollars

2012 (Oct2011-Sept2012) No Info Propane No Info The fuel use and cost does not correlate to actual bills.

2012 (Oct2012-Sept2013) No Info Propane No Info 2012 (Oct2013-Sept2014) 5,772.3 Propane $24,186.76

E. Other ECMs and Considerations

This site does experience some ‘snow’ conditions and may receive 4 to 8-inches of winter snow conditions at this elevation of 3,650 feet in a normal winter. The snow would melt relatively soon after a storm due to this lower elevation.

IV. Sustainable / Solar Siting Considerations

The Pine Hills Fire Station NEPA(National Environmental Policy Act) document suggests that the solar system be ground mounted behind the Engine Bay building and just west of Generator Building in an open area with good southern exposure.

Upon further consideration of a ground mounted system versus a mobile Solar PV system, we are recommending the mobile PV solution. This will eliminate the need for underground conduits, trenching, fencing and other job costs. A mobile solution provides similar kW production as a ground mounted system with the ease of mobility and modularity. See aerial shot on the next page showing site layout and surrounding environment.

Location is suitable for a mobile solar PV solution and would potentially avert NEPA (National Environmental Policy Act) further review. We are not aware of any special requirements for mobile PV solutions relating to the NEPA and the Forest Service would need to confirm our assumptions of a modular system. Our site visit indicates no rationale for other siting.

Pine Hills Fire Station – Google Earth

General Site Area Layout of Buildings and Generator Location Relative to PV Solar

GPS coordinates: 33°00’ 56.88” N, 116°38’ 09.36” W (PV area approx. 100’ x 80’ max.)

(Possible location of Mobile Solar PV siting location is shown in above area)

Pine Hills Fire Station – Mobile Solar System Layout (Lead Acid)

Mobile Solar Solution is depicted below for average daily load of 63.5 kWh / day

MS-275-R2.140 SA-24 (24 x 335-watt PV modules) SA-24 (24 x 335-watt PV modules)

Typical underground conduit/wire intertie between MS-275 and SA-24’s

Existing Electrical Panel Forest Service Cummins Propane Generator Notes:

1.) BASE STSTEM: Lead Acid Battery. Average daily load is 63.5 kWh/day. Proposed Mobile Solar system is 114 kWh/day.

2.) MS trailer is a heavy duty payload package, includes tandem 8,000-lb axles and heavy duty tires with spare tire.

3.) MS-275-R2.140 (16 kW AC output w/ 2 x 70 kWh lead acid battery, 14 kWh/day solar harvest from MS-275-R2.140.

Two days of battery autonomy at full charge. Physical: 19’-6”x7’ overall. MS trailer w/lead acid battery weighs 15,640-lbs.

4.) Two (2 ea.) SA-24 (24 each x 335-watt PV modules, 48 kWh/day harvest. Physical: 34’ x 10’ deployed (including tongue);

5.) Underground conduits/wire connect MS-275 trailer unit between each SA-24 trailer and also existing generator.

6.) Transport dimensions for SA-24 dimensions: 34’L x 8’-6”W x 8’-9”H Weight: ~4,200 lbs each trailer.

Engine Bay

Barracks

Generator Building Fuel Storage

Mobile Solar PV

7.) Lead Acid Pro’s:

(a) Lower upfront cost for battery.

(b) Very good operational use and life.

8.) Lead Acid Con’s:

(a) Requires some maintenance to check battery water levels at least monthly and check battery equalization.

(b) Much heavier battery which increases MS trailer weight.

9.) LITHIUM BATTERY SYSTEM OPTION (Not Used at this site – Informational only for items #9 thru #13): Lithium battery

(extra cost option). Average daily load is 63.5 kWh/day.

10.) The MS trailer is slightly downsized with the lithium 140 kWH battery option as the battery weight is greatly reduced. The

MS-225 trailer would be utilized which has three fewer PV modules, less racking and plus 3rd rail.

11.) The same other features of the SA-15 trailers and details above apply for this option.

12.) Lithium Battery Pro’s:

(a) Lithium battery is much lighter weight than lead acid battery however the cost is substantially more. MS trailer weighs 7,213-lbs. with lithium battery option.

(b) Lithium battery is not affected by cold temperatures and as long as at end of seasonal use it is fully charged it may be left over a long period with no attention.

(c) Good operational life.

13.) Lithium Battery Con’s:

(a) More expensive upfront cost.

Pine Hills Fire Station – Mobile Solar System (Lead Acid) Implemented

Pine Hills Fire Station – Mobile Solar System (Lithium Battery) Not Used

Pine Hills Fire Station – Google Earth

Location Area for Mobile Solar PV system

MS-275

SA-24

Existing Generator

Appendix - Pictures

Pictures (continued)

SECTION 3

Final Construction Drawings, Wiring Diagrams and Details

The following pages provide for the Pine Hills Fire Station installation drawings. These drawings provide for the installed equipment location(s) and information, including detailed construction plans and wiring diagrams for the Mobile Solar PV system and the LED Lighting products that have been installed.

These systems that are installed produce and consume electricity generated from the Mobile

Solar PV system.

Electrical Hazard! DO NOT attempt to change or modify the installed LED Lighting or Mobile Solar PV system as damage to the equipment may occur and warranty may be voided.

Contact Trane U.S. for any concerns or questions in regards to the equipment (see ‘Contacts’ section in this manual).

LED Lighting Product Data & Installation Details

SECTION 4

The following pages consist of the Trane ‘LED Lighting Product Data Sheets’ and also within these sheets are the manufacturer installation information for the Pine Hills Fire Station.

These product data sheets are your resource for the installed LED Lighting products.

Additional LED Lighting locations for these installed products may be found in Section 3 of the

Construction Drawings as-built along with the manufacturer model numbers (which are highlighted in these product data sheets and also on the construction drawings).

Spotlight

LED PAR30 short and long neck lamps

To learn more about saving money and energy, go to: http://products.currentbyge.com.

Featuring GE’s exclusive Visual Comfort Lens™ for the perfect blend of enhanced color quality, advanced optics and reduced glare. Exclusive Visual Comfort Lens™ Optics create halogen-like light and contrast, with the energy and cost-efficient benefits of an LED lamp.

For the perfect solution for all of your retail application needs, turn to GE’s retail PAR30 short and long neck lamps. With advanced optics and reduced glare, these lamps offer the light qualities desired by merchants.

LOW-COST OPERATION

• �For example, using only 12 watts of energy, save over $173 in energy costs over the rated life of the lamp versus a standard 75-watt halogen PAR30 lamp based on $0.11 per kWh

• �Energy efficiency and long life mean fewer lamp replacements versus standard incandescent and halogen light sources

• �Our LED PAR lamps have less heat, UV or infrared in the beam, which reduces the potential for fading of materials and décor, compared to halogen or incandescent lamps

EXCELLENT COLOR RENDERING

• Available with a CRI of 80-90

COLOR TEMPERATURE

• Halogen-like color

• Available in 2700K and 3000K

LONG LIFE

• Up to 25,000 hours rated life (L70)

DIMMABLE

• Dims from 100% to 10%

BEAM PATTERNS

• Available in 25˚ and 40˚ beam patterns

ENVIRONMENTALLY CONSCIOUS

• �These lamps are energy efficient and contain no lead or mercury

GE QUALITY AND RELIABILITY

• 3-year limited warranty

Information provided is subject to change without notice. Please verify all details with GE. All values are design or typical values when measured under laboratory conditions, and GE makes no warranty or guarantee, expressed or implied, that such performance will be obtained under end-use conditions.

Application illustation only, subject lamps not used in photo.

FIXTURE "A"

lbjla Text Box Pine Hills F.S.

G.E.

LED12DP30RW930/40

Bulb Shape

Base Type Watts

Order Code Description Volts

Case Qty**

MOL

(In)

Lumens Initial CBCP

Initial Color Temp CRI

Wattage Replacement

*Rated Life

L70 (Hrs) Dimmable

ENERGY

STAR®

Status

#Location Rating

Additional Information

Compact PAR30 - Low Glare - Visual Comfort Lens™ PAR30 MED 12 84374 LED12DP30RW93015 120 6 3.74 860 9400 3000 90 75W 25,000 Yes Damp Spot, 15° beam, White

84379 LED12DP30RW93025 120 6 3.74 900 3900 3000 90 75W 25,000 Yes Damp Narrow Flood, 25˚ beam, White 84380 LED12DP30RW93040 120 6 3.74 900 1800 3000 90 75W 25,000 Yes Damp Flood, 40˚ beam, White 84392 LED12DP30RW92725 120 6 3.74 850 3500 2700 90 75W 25,000 Yes Damp Narrow Flood, 25˚ beam, White 84395 LED12DP30RW92740 120 6 3.74 850 1700 2700 90 75W 25,000 Yes Damp Flood, 40˚ beam, White 84384 LED12DP30RW83025 120 6 3.74 1050 4800 3000 80 75W 25,000 Yes Damp Narrow Flood, 25˚ beam, White 42131 LED12DP30RW83040 120 6 3.74 1050 2400 3000 80 75W 25,000 Yes Damp Flood, 40˚ beam, White 42133 LED12DP30RW82725 120 6 3.74 1000 4700 2700 80 75W 25,000 Yes Damp Narrow Flood, 25˚ beam, White 42134 LED12DP30RW82740 120 6 3.74 1000 2200 2700 80 75W 25,000 Yes Damp Flood, 40˚ beam, White 73583 LED12DP30RB82740 120 6 3.74 1000 2200 2700 80 75W 25,000 Yes Damp Flood, 40˚ beam, White

Compact PAR30 - Long Neck - Low Glare - Visual Comfort Lens™ PAR30L MED 12 84399 LED12DP3LRW93025 120 6 4.72 900 3900 3000 90 75W 25,000 Yes Damp Narrow Flood, 25˚ beam, White

84400 LED12DP3LRW93040 120 6 4.72 900 1800 3000 90 75W 25,000 Yes Damp Flood, 40˚ beam, White 84407 LED12DP3LRW92740 120 6 4.72 850 1700 2700 90 75W 25,000 Yes Damp Flood, 40˚ beam, White 42136 LED12DP3LRW83025 120 6 4.72 1050 4800 3000 80 75W 25,000 Yes Damp Narrow Flood, 25˚ beam, White 42137 LED12DP3LRW83040 120 6 4.72 1050 2400 3000 80 75W 25,000 Yes Damp Flood, 40˚ beam, White 42141 LED12DP3LRW82725 120 6 4.72 1000 4700 2700 80 75W 25,000 Yes Damp Narrow Flood, 25° beam, White 42144 LED12DP3LRW82740 120 6 4.72 1000 2200 2700 80 75W 25,000 Yes Damp Flood, 40˚ beam, White

ENERGY STAR® is a registered U.S. mark

Product is compliant with material restriction requirements of RoHS

LED PAR30 short and long neck lamps Directional Lamps (PAR) http://products.currentbyge.com.

GE and the GE Monogram are trademarks of the General Electric Company. All other trademarks are the property of their respective owners. Information provided is subject to change without notice. All values are design or typical values when measured under laboratory conditions. GE Lighting and GE Lighting Solutions, LLC are businesses of the General Electric Company. © 2017 GE.

66635 (Rev 08/17/17)

* The life rating is based on the hours of operation the lamp will provide before reaching 70% of its original rating (L70) ** Minimum order quantity = 6

ENERGY STAR® status: ENERGY STAR® certified. Lamps without a “ ” are not ENERGY STAR® certified.

# UL 1993 Environmental Requirements for LED LAMPS
Location, damp – Exterior or interior location that is normally or periodically subject to condensation of moisture in, on, or adjacent to, electrical equipment,
and includes partially protected locations.
Location, dry– Location not normally subject to dampness, may include a location subject to temporary dampness, i.e., building under construction,
provided ventilation is adequate to prevent an accumulation of moisture.
Location, wet– Location in which water or other liquid can drip, splash, or flow on or against electrical equipment.
Notes:1) Product descriptions ending in “/TP” indicate a carded blister or clamshell package nested in a tray for shelf display. Cards also designed for hook display.

Information provided is subject to change without notice. Please verify all details with GE. All values are design or typical values when measured under laboratory conditions, and GE makes no warranty or guarantee, expressed or implied, that such performance will be obtained under end-use conditions.

Directional Lamps (PAR30 - High Output)

Bulb Shape Base Type Watts

Order Code Description Volts

Case Qty**

MOL

(In)

Lumens Initial CBCP

Initial Color Temp CRI

Wattage Replacement

*Rated Life

L70 (Hrs) Dimmable

ENERGY

STAR®

Status

#Location Rating

Additional Information

Universal 120-277V PAR30 HO MED 18 75089 LED18P30LW83015 120-277 6 4.6 1800 15500 3000 80 75W 25,000 - Damp Spot, 15°, White

75091 LED18P30LW83025 120-277 6 4.6 1800 7000 3000 80 75W 25,000 - Damp Narrow Flood, 25°, White

75065 LED18P30LW93015 120-277 6 4.6 1400 12500 3000 90 75W 25,000 - Damp Spot, 15° beam, MTO, 1000 Min. Qty, 12 Week Lead Time, White

75078 LED18P30LW93025 120-277 6 4.6 1400 5000 3000 90 75W 25,000 - Damp Narrow Flood, 25°, White lbjla Highlight

Highlight

XTOR

CROSSTOUR LED

APPLICATIONS:

WALL / SURFACE

POST / BOLLARD

LOW LEVEL

FLOODLIGHT

INVERTED

SITE LIGHTING

Lumark

SPECIFICATION FEATURES

Construction Slim, low-profile LED design with rugged one-piece, die-cast aluminum hinged removable door and back box. Matching housing styles incorporate both a small and medium design. The small housing is available in 12W, 18W and 26W. The medium housing is available in the 38W model.

Patented secure lock hinge feature allows for safe and easy tool-less electrical connections with the supplied push-in connectors. Back box includes three half-inch, NPT threaded conduit entry points. The universal back box supports both the small and medium forms and mounts to standard 3-1/2” to 4” round and octagonal, 4” square, single gang and masonry junction boxes. Key hole gasket allows for adaptation to junction box or wall. External fin design extracts heat from the fixture surface. One-piece silicone gasket seals door and back box. Minimum 5” wide pole for site lighting application.

Not recommended for car wash applications.

Optical Silicone sealed optical LED chamber incorporates a custom engineered mirrored anodized reflector providing high-efficiency illumination. Optical assembly includes impact-resistant tempered glass and meets IESNA requirements for full cutoff compliance. Available in seven lumen packages; 5000K, 4000K and

3000K CCT.

Electrical LED driver is mounted to the die-cast housing for optimal heat sinking. LED thermal management system incorporates both conduction and natural convection to transfer heat rapidly away from the LED source. 12W, 18W, 26W and 38W series operate in -40°C to 40°C [-40°F to 104°F]. High ambient 50°C models available. Crosstour luminaires maintain greater than 89% of initial light output after 72,000 hours of operation. Three half-inch NPT threaded conduit entry points allow for thru-branch wiring. Back box is an authorized electrical wiring compartment.

Integral LED electronic driver incorporates surge protection. 120- 277V 50/60Hz or 347V 60Hz models.

Finish Crosstour is protected with a Super durable TGIC carbon bronze or summit white polyester powder coat paint. Super durable TGIC powder coat paint finishes withstand extreme climate conditions while providing optimal color and gloss retention of the installed life.

Warranty Five-year warranty.

TD514013EN

2017-07-25 12:21:59

The patented Lumark Crosstour™ LED Wall Pack Series of luminaries provides an architectural style with super bright, energy efficient LEDs.

The low-profile, rugged die-cast aluminum construction, universal back box, stainless steel hardware along with a sealed and gasketed optical compartment make the Crosstour impervious to contaminants. The Crosstour wall luminaire is ideal for wall/surface, inverted mount for façade/canopy illumination, post/bollard, site lighting, floodlight and low level pathway illumination including stairs. Typical applications include building entrances, multi-use facilities, apartment buildings, institutions, schools, stairways and loading docks test.

DESCRIPTION

Catalog # Type

Date

Project

Comments

Prepared by

12W, 18W, 26W 5-3/4" [146mm]

38W 6-5/8" [168mm]

12W, 18W, 26W 6-3/4" [171mm]

38W 8" [203mm]

12W, 18W, 26W 3-5/8" [92mm]

38W 4" [102mm]

DIMENSIONS

C E R T I F I C A T I O N D A T A UL/cUL Wet Location Listed LM79 / LM80 Compliant ROHS Compliant ADA Compliant NOM Compliant Models IP66 Ingressed Protection Rated Title 24 Compliant DesignLights Consortium® Qualified*

T E C H N I C A L D A T A 40°C Maximum Ambient Temperature External Supply Wiring 90°C Minimum

E P A Effective Projected Area (Sq. Ft.):

XTOR1B, XT0R2B, XT0R3B=0.34

XTOR4B=0.45

S H I P P I N G D A T A :

Approximate Net Weight:

3.7 – 5.25 lbs. [1.7 – 2.4 kgs.]

10" [254mm]

17-1/2" [445mm]

10" [254mm]

17-1/2" [445mm]

ESCUTCHEON PLATES

*www.designlights.org lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla

FIXTURE "B"

Specifications and dimensions subject to change without notice.

Eaton 1121 Highway 74 South Peachtree City, GA 30269 P: 770-486-4800 www.eaton.com/lighting

Ambient Temperature

TM-21 Lumen Maintenance

(72,000 Hours)

Theoretical L70 (Hours)

XTOR1B Model

25°C > 90% 255,000

40°C > 89% 234,000

50°C > 88% 215,000

XTOR2B Model

25°C > 89% 240,000

40°C > 88% 212,000

50°C > 87% 196,000

XTOR3B Model

25°C > 89% 240,000

40°C > 88% 212,000

50°C > 87% 196,000

XTOR4B Model

25°C > 89% 222,000

40°C > 87% 198,000

50°C > 87% 184,000

LUMEN MAINTENANCE

LED Information XTOR1B XTOR1B-W XTOR1B-Y XTOR2B XTOR2B-W XTOR2B-Y XTOR3B XTOR3B-W XTOR3B-Y XTOR4B XTOR4B-W XTOR4B-Y

Delivered Lumens (Wall Mount)

1,418 1,396 1,327 2,135 2,103 1,997 2,751 2,710 2,575 4,269 4,205 3,995

Delivered Lumens (With Flood Accessory Kit) 1

1,005 990 940 1,495 1,472 1,399 2,099 2,068 1,965 3,168 3,121 2,965

B.U.G. Rating 2 B1-U0-G0 B1-U0-G0 B1-U0-G0 B1-U0-G0 B1-U0-G0 B1-U0-G0 B1-U0-G0 B1-U0-G0 B1-U0-G0 B2-U0-G0 B2-U0-G0 B2-U0-G0

CCT (Kelvin) 5,000 4,000 3,000 5,000 4,000 3,000 5,000 4,000 3,000 5,000 4,000 3,000

CRI (Color Rendering Index)

70 70 70 70 70 70 70 70 70 70 70 70

Power Consumption (Watts)

12W 12W 12W 18W 18W 18W 26W 26W 26W 38W 38W 38W

NOTES: 1 Includes shield and visor. 2 B.U.G. Rating does not apply to fl oodlighting.

POWER AND LUMENS BY FIXTURE MODEL

Voltage Model Series

XTOR1B XTOR2B XTOR3B XTOR4B

120V 0.103A 0.15A 0.22A 0.34A

208V 0.060A 0.09A 0.13A 0.17A

240V 0.053A 0.08A 0.11A 0.17A

277V 0.048A 0.07A 0.10A 0.15A

347V 0.039A 0.06A 0.082A 0.12A

CURRENT DRAW

XTOR CROSSTOUR LED

TD514013EN

2017-07-25 12:21:59

0 10 20 30 40 50 60 70 80 90 100

Hours (Thousands)

Lu m en M ai n te n an ce

Pe rc en t)

50°C 40°C 25°C lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight change without notice.

Eaton 1121 Highway 74 South Peachtree City, GA 30269 P: 770-486-4800 www.eaton.com/lighting

TD514013EN

2017-07-25 12:21:59

XTOR CROSSTOUR LED

12W Series 18W Series 26W Series 38W Series

XTOR1B=12W, 5000K, Carbon Bronze XTOR2B=18W, 5000K, Carbon Bronze XTOR3B=26W, 5000K, Carbon Bronze XTOR4B=38W, 5000K, Carbon Bronze

XTOR1B-WT=12W, 5000K, Summit White XTOR2B-W=18W, 4000K, Carbon Bronze XTOR3B-W=26W, 4000K, Carbon Bronze XTOR4B-W=38W, 4000K, Carbon Bronze

XTOR1B-PC1=12W, 5000K, 120V PC,

Carbon Bronze

XTOR2B-WT=18W, 5000K, Summit White XTOR3B-WT=26W, 5000K, Summit White XTOR4B-WT=38W, 5000K, Summit White

XTOR1B-W=12W, 4000K, Carbon Bronze XTOR2B-PC1= 18W, 5000K, 120V PC, Carbon Bronze

XTOR3B-PC1= 26W, 5000K, 120V PC,

Carbon Bronze

XTOR4B-PC1= 38W, 5000K, 120V PC, Carbon Bronze

XTOR1B-W-PC1=12W, 4000K, 120V PC,

Carbon Bronze

XTOR2B-W-PC1= 18W, 4000K, 120V PC,

Carbon Bronze

XTOR4B-W-PC1= 38W, 4000K, 120V PC,

Carbon Bronze

STOCK ORDERING INFORMATION

Sample Number: XTOR2B-W-WT-PC1

Series 1 LED Kelvin Color Housing Color Options (Add as Suffi x) Accessories (Order Separately)

XTOR1B=Small Door, 12W XTOR2B=Small Door, 18W XTOR3B=Small Door, 26W XTOR4B=Medium Door, 38W

[Blank]= Bright White (Standard), 5000K

W=Neutral White, 4000K Y=Warm White, 3000K

[Blank]= Carbon Bronze (Standard)

WT=Summit White BK=Black BZ=Bronze AP=Grey GM=Graphite Metallic DP=Dark Platinum

PC1=Photocontrol 120V 2

PC2=Photocontrol 208-277V 2, 3

347V=347V 4

HA=50ºC High Ambient 4

WG/XTOR=Wire Guard 5

XTORFLD-KNC=Knuckle Floodlight Kit 6

XTORFLD-TRN=Trunnion Floodlight Kit 6

XTORFLD-KNC-WT=Knuckle Floodlight Kit, Summit White 6

XTORFLD-TRN-WT=Trunnion Floodlight Kit, Summit White 6

EWP/XTOR= Escutcheon Wall Plate, Carbon Bronze EWP/XTOR-WT= Escutcheon Wall Plate, Summit White

NOTES:

1. DesignLights Consortium® Qualifi ed and classifi ed for both DLC Standard and DLC Premium, refer to www.designlights.org for details.

2. Photocontrols are factory installed.

3. Order PC2 for 347V models.

4. Thru-branch wiring not available with HA option or with 347V. XTOR3B not available with HA and 347V or 120V combination.

5. Wire guard for wall/surface mount. Not for use with fl oodlight kit accessory.

6. Floodlight kit accessory supplied with knuckle (KNC) or trunnion (TRN) base, small and large top visors and small and large impact shields.

ORDERING INFORMATION

lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Cross-out lbjla Inserted Text D lbjla Inserted Text F

Metalux

WNLED

LED

Uti l i ty LED Wraparound

SPECIFICATION FEATURES

Construction Housing consists of die formed cold rolled steel. Ends formed with the housing for strength and provisions for continuous row aligners. Steel end plates with 7/8” KO and light-seal embossment.

Driver cover can be removed without tools.

Controls WNLED is Powered by Fifth Light, with standard a 0-10V continuous dimming driver that works with any 0-10V control/ dimmer.

Combine with energy saving products like occupancy sensors, daylighting controls and lighting relay panels to maximize energy savings. Dimming range is 10% to 100%; varies by control device.

Electrical Long-Life LED system coupled with electrical driver to deliver optimal performance. LED’s available in 3000K, 3500K, 4000K and 5000K with a min. 80 CRI. Projected life at 70% lumen maintenance is nearly 150,000 hours with TM21 rating up to L88 > 60,000 hours. Electronic drivers are available for 120-277V applications. A 0-10V dimming driver is standard.

Emergency Battery Pack Option Optional 120V-277V integral emergency battery pack is available in 7-watts or 14-watts to meet critical life-safety lighting requirements. The 90-minute batteries provide constant power to the LED system, ensuring code compliance. The patented EZ Key prevents accidental discharge of the battery during construction.

Finish Multistage iron phosphate pretreatment ensures maximum bonding and rust inhibitor. High reflective paint after fabrication, baked white enamel finish is standard.

Channel/Wireway Cover Die formed heavy gauge steel.

Tight fit for ease of maintenance.

Shielding Acrylic, high performance, frost blend. Sides have inside linear prisms and bottom has pyramidal prisms for low brightness control.

Instal lation Fixture may be surface, pendant, or stem mounted. See accessories below for ordering information.

Compliance Indoor luminaires are cULus listed for 25ºC ambient environments, damp location listed, RoHS compliant, and LED modules comply with IESNA LM-79 and LM-80 standards. DesignLights Consortium® Qualified and classified for DLC Standard, refer to www.designlights.org for details.

Suitable for use in clothes closets when installed in accordance with the NEC 410.16 spacing requirements. Can be used for State of California Title 24 high efficacy luminaire.

Our updated WNLED series is a versatile utility based, traditionally styled LED wraparound series which can be used in a broad range of commercial, schools, institutional, retail and residential applications.

This high quality luminaire series utilizes the latest solid state LED lighting and advanced electronic driver technology which provides optimal lighting performance and maximizing energy savings. WNLED is designed to provide long service life eliminating re-lamping issues and minimizing maintenance common with traditional fluorescent.

DESCRIPTION

PS519062EN

May 21, 2018 2:35 PM

1-13/16" [46mm]

19" [483mm] 20-5/8" [523mm]

1-1/8" [29mm]

24" [610mm]

8-3/16" [208mm]

1" [25mm]1" [25mm]

6" [152mm]

7-5/8" [194mm]

2'

1-1/8" [29mm]

42-15/16" [1090mm] 44-1/2" [1131mm]1-13/16"

[46mm]

7/8" [22mm] K.O. (5)

Ground Screw Bump Ceiling Stand-Off Embossments

48" [1219mm]

42-7/16" [1078mm]

40-7/16" [1027mm]

3" [76mm]

4-1/2" [114mm]

6" [152mm]

7-5/8" [194mm]

4'

MOUNTING DATA

2-1/2" [63mm]

7-5/8" [194mm]

6" [152mm]

ENERGY AND PERFORMANCE DATA BY CATALOG NUMBER

Lumen Type Length Catalog Number

Nominal 3500K Lumens Wattage lm/W

Standard 2 ft. 2WNLED-LD4-28SL-F-UNV-L8XX-CD1-U 2786 27.5 101

Standard 4 ft. 4WNLED-LD4-32SL-F-UNV-L8XX-CD1-U 3298 28.0 118

Standard 4 ft. 4WNLED-LD4-40SL-F-UNV-L8XX-CD1-U 4062 36.0 113

Standard 4 ft. 4WNLED-LD4-50SL-F-UNV-L8XX-CD1-U 4966 46.6 107

California Title 24 Non-Residential

Compliant

Catalog #

Project

Comments

Prepared by

Type

Date lbjla Highlight lbjla Highlight lbjla

FIXTURE 'D'

change without notice.

Eaton 1121 Highway 74 South Peachtree City, GA 30269 P: 770-486-4800 www.eaton.com/lighting

WNLED

Catalog No. Wt.

2WNLED 5 lbs.

4WNLED 9 lbs.

SHIPPING DATA

Series (3)

WNLED=Utility LED Wraparound

S A M P L E N U M B E R : 4 W N L E D - L D 4 - 4 0 S L - F - U N V - L 8 4 0 - C D 1 - U

Packaging U=Unit Pack

Lamp Type

LD4=LED

LED Lumens Output

28SL=2800 (1)

32SL=3200

40SL=4000

50SL=5000

Voltage 347=347V (2)

480=480V (2)

UNV=Universal Voltage 120-277

Number of Drivers 1=1 Driver

Lens F=Frost Acrylic (standard)

Length 2=2 ft.

4=4 ft.

A C C E S S O R I E S SCF=Fixed Stem Set (Specify Length) SCS=Swivel Stem Set (Specify Length) SCA=Adjustable 48" Stem Set A1B/Spacer-U=Spacer 1-1/2" to 2-1/2" from ceiling (Use 2 per fixture) WN22AU=2' Replacement Lens WN24AU=4' Replacement Lens

NOTES: (1) 2 ft. model. (2) 4 ft. model only. (3) DesignLights Consortium® Qualified and classified for DLC Standard, refer to www.designlights.org for details. (4) With integral test switch/indicator/laser test. For approximate delivered lumens multiply the lumens per watt of the desired fixture by the wattage of the emergency battery pack (100 lm/W x 7=700 lumens). IES-format photometry for luminaire under emergency operation available.

(5) 5LTD DALI driver available for all lumen unit only. (6) Emergency options not available for 2 ft. versions. Requires larger cover which changes the appearance. (7) Emergency options use taller ballast cover that alters appearance.

Specifications & dimensions subject to change without notice. Consult your Eaton Representative for availability and ordering information.

Driver Type CD=0-10V Dimming Driver (10% - 100% Dimming)

Options Emergency (7)

CCT

L830=3000K L835=3500K L840=4000K L850=5000K

EL7W=7-watt, 120V-277V emergency battery pack installed (4), (6)

EL14W=14-watt 120V-277V emergency battery pack installed (4), (6)

ORDERING INFORMATION

4WNLED-LD4-32SL-

F-UNV-L835-CD1-U

Electronic Driver

Linear LED 3500K

Spacing criterion:

(II) 1.2 x mounting height, (⊥) 1.2 x mounting height

Lumens: 3298

Input Watts: 28.0W

Efficacy: 117.8 lm/W

Test Report:

4WNLED-LD4-32SL-F-

UNV-L835-CD1-U.IES

C a n d l e p owe r

Angle Along II 45° Across ⊥

1124 1124 1124 1124 1120 1116 1103 1102 1100 1069 1071 1071 1023 1029 1031 966 975 978 899 913 918 826 845 853 747 771 781 669 695 707 586 615 631 504 535 554 422 455 476 342 377 400 265 302 327 190 231 257 121 164 190 56 100 125 0 44 70

C o e ffi c i e n t s o f U t i l i z a t i o n

Effective floor cavity refl ectance 20% rc 80% 70% 50% 30% 10% 0% rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0

RCR

118 118 118 118 114 114 114 114 108 108 108 102 102 102 97 97 97 94 107 102 97 93 103 99 95 91 94 90 87 89 86 84 84 82 80 78 97 89 82 76 94 86 80 74 82 76 72 78 73 69 74 70 67 64 88 78 69 63 85 76 68 62 72 65 60 68 63 58 65 60 57 54 81 69 60 53 78 67 59 53 64 57 51 61 55 50 58 53 49 46 74 62 52 46 72 60 52 45 57 50 44 55 48 43 52 47 42 40 69 55 46 40 66 54 46 40 52 44 39 50 43 38 47 42 37 35 64 50 41 35 62 49 41 35 47 40 34 45 39 34 43 38 33 31 59 46 37 32 57 45 37 31 43 36 31 41 35 30 40 34 30 28 55 42 34 28 54 41 33 28 40 33 28 38 32 27 37 31 27 25 52 39 31 26 50 38 31 26 37 30 25 35 29 25 34 29 24 23

Z o n a l L u m e n S u m m a r y

Zone Lumens % Fixture 0-30

0-40

0-60

0-90

0-180

855 25.9

1381 41.9

2390 72.5

3109 94.3

3298 100.0

0˚ 15˚ 30˚

45˚

60˚

75˚

90˚

PHOTOMETRICS

4WNLED-LD4-40SL-

F-UNV-L835-CD1-U

Electronic Driver

Linear LED 3500K

Spacing criterion:

(II) 1.2 x mounting height, (⊥) 1.2 x mounting height

Lumens: 4062

Input Watts: 36.0W

Effi cacy: 112.8 lm/W

Test Report:

4WNLED-LD4-

40SL-F-UNV-L835-

CD1-U.IES

C a n d l e p owe r

Angle Along II 45° Across ⊥

1386 1386 1386 1385 1380 1375 1360 1357 1354 1318 1320 1320 1261 1266 1268 1190 1201 1203 1109 1125 1128 1018 1042 1048 922 951 964 823 857 868 721 759 773 620 660 678 521 561 584 421 464 492 326 372 403 234 285 317 148 201 233 70 123 154 1 57 89

C o e ffi c i e n t s o f U t i l i z a t i o n

Effective fl oor cavity refl ectance 20% rc 80% 70% 50% 30% 10% 0% rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0

RCR

118 118 118 118 114 114 114 114 108 108 108 102 102 102 97 97 97 94 107 102 97 93 103 99 95 91 94 90 87 89 86 84 84 82 80 78 97 89 82 76 94 86 80 74 82 76 72 78 73 69 74 70 67 64 88 78 69 63 85 76 68 62 72 65 60 68 63 58 65 61 57 54 81 69 60 53 78 67 59 53 64 57 51 61 55 50 58 53 49 46 74 62 52 46 72 60 52 45 57 50 44 55 48 43 52 47 42 40 69 55 46 40 66 54 46 40 52 44 39 50 43 38 47 42 37 35 64 50 41 35 62 49 41 35 47 40 34 45 39 34 43 38 33 31 59 46 37 32 57 45 37 31 43 36 31 41 35 30 40 34 30 28 55 42 34 28 54 41 33 28 40 33 28 38 32 27 37 31 27 25 52 39 31 26 50 38 31 26 37 30 25 35 29 25 34 29 24 23

Z o n a l L u m e n S u m m a r y

Zone Lumens % Fixture 0-30

0-40

0-60

0-90

0-180

1054 25.9

1702 41.9

2945 72.5

3832 94.3

4062 100.0

0˚ 15˚ 30˚

45˚

60˚

75˚

90˚

Approximate Color Temperature Multiplier

5000K 1.03

4000K 1.00

3000K 0.98

CCT TABLE

PS519062EN

May 21, 2018 2:35 PM lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight

Metalux

WNLED

LED

Uti l i ty LED Wraparound

SPECIFICATION FEATURES

Construction Housing consists of die formed cold rolled steel. Ends formed with the housing for strength and provisions for continuous row aligners. Steel end plates with 7/8” KO and light-seal embossment.

Driver cover can be removed without tools.

Controls WNLED is Powered by Fifth Light, with standard a 0-10V continuous dimming driver that works with any 0-10V control/ dimmer.

Combine with energy saving products like occupancy sensors, daylighting controls and lighting relay panels to maximize energy savings. Dimming range is 10% to 100%; varies by control device.

Electrical Long-Life LED system coupled with electrical driver to deliver optimal performance. LED’s available in 3000K, 3500K, 4000K and 5000K with a min. 80 CRI. Projected life at 70% lumen maintenance is nearly 150,000 hours with TM21 rating up to L88 > 60,000 hours. Electronic drivers are available for 120-277V applications. A 0-10V dimming driver is standard.

Emergency Battery Pack Option Optional 120V-277V integral emergency battery pack is available in 7-watts or 14-watts to meet critical life-safety lighting requirements. The 90-minute batteries provide constant power to the LED system, ensuring code compliance. The patented EZ Key prevents accidental discharge of the battery during construction.

Finish Multistage iron phosphate pretreatment ensures maximum bonding and rust inhibitor. High reflective paint after fabrication, baked white enamel finish is standard.

Channel/Wireway Cover Die formed heavy gauge steel.

Tight fit for ease of maintenance.

Shielding Acrylic, high performance, frost blend. Sides have inside linear prisms and bottom has pyramidal prisms for low brightness control.

Instal lation Fixture may be surface, pendant, or stem mounted. See accessories below for ordering information.

Compliance Indoor luminaires are cULus listed for 25ºC ambient environments, damp location listed, RoHS compliant, and LED modules comply with IESNA LM-79 and LM-80 standards. DesignLights Consortium® Qualified and classified for DLC Standard, refer to www.designlights.org for details.

Suitable for use in clothes closets when installed in accordance with the NEC 410.16 spacing requirements. Can be used for State of California Title 24 high efficacy luminaire.

Our updated WNLED series is a versatile utility based, traditionally styled LED wraparound series which can be used in a broad range of commercial, schools, institutional, retail and residential applications.

This high quality luminaire series utilizes the latest solid state LED lighting and advanced electronic driver technology which provides optimal lighting performance and maximizing energy savings. WNLED is designed to provide long service life eliminating re-lamping issues and minimizing maintenance common with traditional fluorescent.

DESCRIPTION

PS519062EN

May 21, 2018 2:35 PM

1-13/16" [46mm]

19" [483mm] 20-5/8" [523mm]

1-1/8" [29mm]

24" [610mm]

8-3/16" [208mm]

1" [25mm]1" [25mm]

6" [152mm]

7-5/8" [194mm]

2'

1-1/8" [29mm]

42-15/16" [1090mm] 44-1/2" [1131mm]1-13/16"

[46mm]

7/8" [22mm] K.O. (5)

Ground Screw Bump Ceiling Stand-Off Embossments

48" [1219mm]

42-7/16" [1078mm]

40-7/16" [1027mm]

3" [76mm]

4-1/2" [114mm]

6" [152mm]

7-5/8" [194mm]

4'

MOUNTING DATA

2-1/2" [63mm]

7-5/8" [194mm]

6" [152mm]

ENERGY AND PERFORMANCE DATA BY CATALOG NUMBER

Lumen Type Length Catalog Number

Nominal 3500K Lumens Wattage lm/W

Standard 2 ft. 2WNLED-LD4-28SL-F-UNV-L8XX-CD1-U 2786 27.5 101

Standard 4 ft. 4WNLED-LD4-32SL-F-UNV-L8XX-CD1-U 3298 28.0 118

Standard 4 ft. 4WNLED-LD4-40SL-F-UNV-L8XX-CD1-U 4062 36.0 113

Standard 4 ft. 4WNLED-LD4-50SL-F-UNV-L8XX-CD1-U 4966 46.6 107

California Title 24 Non-Residential

Compliant

Catalog #

Project

Comments

Prepared by

Type

Date lbjla Cross-out lbjla Highlight lbjla Highlight lbjla Highlight lbjla Highlight change without notice.

Eaton 1121 Highway 74 South Peachtree City, GA 30269 P: 770-486-4800 www.eaton.com/lighting

WNLED

Catalog No. Wt.

2WNLED 5 lbs.

4WNLED 9 lbs.

SHIPPING DATA

Series (3)

WNLED=Utility LED Wraparound

S A M P L E N U M B E R : 4 W N L E D - L D 4 - 4 0 S L - F - U N V - L 8 4 0 - C D 1 - U

Packaging U=Unit Pack

Lamp Type

LD4=LED

LED Lumens Output

28SL=2800 (1)

32SL=3200

40SL=4000

50SL=5000

Voltage 347=347V (2)

480=480V (2)

UNV=Universal Voltage 120-277

Number of Drivers 1=1 Driver

Lens F=Frost Acrylic (standard)

Length 2=2 ft.

4=4 ft.

A C C E S S O R I E S SCF=Fixed Stem Set (Specify Length) SCS=Swivel Stem Set (Specify Length) SCA=Adjustable 48" Stem Set A1B/Spacer-U=Spacer 1-1/2" to 2-1/2" from ceiling (Use 2 per fixture) WN22AU=2' Replacement Lens WN24AU=4' Replacement Lens

NOTES: (1) 2 ft. model. (2) 4 ft. model only. (3) DesignLights Consortium® Qualified and classified for DLC Standard, refer to www.designlights.org for details. (4) With integral test switch/indicator/laser test. For approximate delivered lumens multiply the lumens per watt of the desired fixture by the wattage of the emergency battery pack (100 lm/W x 7=700 lumens). IES-format photometry for luminaire under emergency operation available.

(5) 5LTD DALI driver available for all lumen unit only. (6) Emergency options not available for 2 ft. versions. Requires larger cover which changes the appearance. (7) Emergency options use taller ballast cover that alters appearance.

Specifications & dimensions subject to change without notice. Consult your Eaton Representative for availability and ordering information.

Driver Type CD=0-10V Dimming Driver (10% - 100% Dimming)

Options Emergency (7)

CCT

L830=3000K L835=3500K L840=4000K L850=5000K

EL7W=7-watt, 120V-277V emergency battery pack installed (4), (6)

EL14W=14-watt 120V-277V emergency battery pack installed (4), (6)

ORDERING INFORMATION

4WNLED-LD4-32SL-

F-UNV-L835-CD1-U

Electronic Driver

Linear LED 3500K

Spacing criterion:

(II) 1.2 x mounting height, (⊥) 1.2 x mounting height

Lumens: 3298

Input Watts: 28.0W

Efficacy: 117.8 lm/W

Test Report:

4WNLED-LD4-32SL-F-

UNV-L835-CD1-U.IES

C a n d l e p owe r

Angle Along II 45° Across ⊥

1124 1124 1124 1124 1120 1116 1103 1102 1100 1069 1071 1071 1023 1029 1031 966 975 978 899 913 918 826 845 853 747 771 781 669 695 707 586 615 631 504 535 554 422 455 476 342 377 400 265 302 327 190 231 257 121 164 190 56 100 125 0 44 70

C o e ffi c i e n t s o f U t i l i z a t i o n

Effective floor cavity refl ectance 20% rc 80% 70% 50% 30% 10% 0% rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0

RCR

118 118 118 118 114 114 114 114 108 108 108 102 102 102 97 97 97 94 107 102 97 93 103 99 95 91 94 90 87 89 86 84 84 82 80 78 97 89 82 76 94 86 80 74 82 76 72 78 73 69 74 70 67 64 88 78 69 63 85…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .