This is a technical specification document for acoustical batt insulation to be used in the AFD Visitor Center Remodel project located in Missoula, Montana. The specification outlines requirements for glass fiber acoustical insulation intended for interior walls, floors, and ceilings in residential building applications. The insulation must comply with ASTM C 665, Type 1 standards and be unfaced glass fiber batts. Performance requirements include a maximum flame spread rating of 10 and maximum smoke development of 10 under ASTM E84 testing, with the material required to pass ASTM E136 combustion characteristics testing. The insulation must demonstrate linear dimensional stability of less than 0.1% and contain zero formaldehyde content. Installation shall consist of friction-fit unfaced batts between studs in accordance with manufacturer instructions. Owens-Corning is specified as the primary manufacturer, with substitutions permitted under Section 01 6000 Product Requirements. Products must be delivered in unopened manufacturer packaging and stored protected from physical damage, moisture, and contamination. Submittals must include manufacturer data sheets covering preparation instructions, storage and handling requirements, and installation methods, along with certified test reports from independent agencies verifying compliance with specified acoustical and fire performance requirements.
View the file
Other files for this federal contract opportunity
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION 09 8311
ACOUSTICAL BATT INSULATION
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Glass fiber acoustical insulation for interior walls, floors and ceilings in residential buildings.
1.02 REFERENCED STANDARDS
A. ASTM E84 - Standard Test Method for Surface Burning Characteristics of Building Materials;
2013a.
B. E90 Laboratory Measurement of Airborne Sound Transmission Loss of Building partitions and Elements.
C. E96 Test Method for Water Vapor Transmission of Materials.
D. E196 Test Method for Sound Absorption and the Sound Absorption Coefficient by the Reverberation Room Method.
1.03 SUBMITTALS
A. See Section 01 3000 - Administrative Requirements, for submittal procedures.
B. Product Data: Manufacturer's data sheets on each product to be used, including:
1. Preparation instructions and recommendations.
2. Storage and handling requirements and recommendations.
3. Installation methods.
4. Specimen warranty.
C. Test Reports: Certified test data from an independent test agency verifying that wall systems meet specified requirements for acoustical and fire performance.
1.04 DELIVERY, STORAGE, AND HANDLING
A. Protect insulation from physical damage and from becoming wet, soiled, or covered with ice or snow. Comply with the manufacturer recommendations for handling, storage and protection during insulation.
B. Label insulation packages to include material name, production date and/or product code.
C. Store products in manufacturer's unopened packaging until ready for installation.
PART 2 PRODUCTS
2.01 MANUFACTURERS
A. Acoustical Batt Insulation:
1. Owens- Corning; www.owenscorning.com.
2. Substitutions: See Section 01 6000 - Product Requirements.
2.02 SOUND ATTENUATION BATTS
A. Type: Unfaced glass fiber acoustical insulation complying with ASTM C 665, Type 1.
B. Glass fiber insulation complying with ASTM C 665.
C. Surface Burning Characteristics:
1. Unfaced Insulation:
a. Maximum Flame Spread: 10
b. Maximum Smoke Developed: 10 D. Combustion Characteristics: Unfaced insulation passes ASTM E 136 Test.
E. Dimensional Stability: Linear stability less than 0.1%.
F. Formaldehyde Content: Zero.
USFS Kootenai SO & WC Improvements 09 8311 - 2 Acoustical Batt Insulation
PART 3 EXECUTION
3.01 EXAMINATION
A. Do not begin installation until substrates have been properly prepared.
B. If substrate preparation is the responsibility of another installer, notify Mosaic Architecture of unsatisfactory preparation before proceeding.
3.02 INSTALLATION
A. Comply with manufacturer's instruction for particular conditions of installation in each case.
B. Between Studs: Friction fit unfaced batts.