Amend1 - C3.1.Util Plan PH I.pdf

PDF 1 MB Posted

Attached to
USFS Sisters Storage Building Federal contract opportunity
Solicitation number
1240BH22R0014
Issued by
Department of Agriculture Forest Service R6-Pacific Northwest Region

About this file

This utility plan and related federal contract solicitation provide details for a US Forest Service storage building project. The utility plan outlines storm drain, sanitary sewer, and waterline installation for the project site, including pipe sizes, cleanouts, lateral connections, and manhole locations. The federal contract solicitation seeks proposals for construction of the USFS Sisters Storage Building, with a pre-proposal conference scheduled for 1 June 2022 to provide site details. The opportunity is designated for the US Department of Agriculture Forest Service Region 6 and proposals are due by 18 May 2022. Relevant project details are included to inform potential offerors on requirements for responsive proposals.

View the file

Other files for this federal contract opportunity

Other files attached to USFS Sisters Storage Building, newest first.
File Type Posted
Amendment 5.pdf PDF
Amendment 4.pdf PDF
Amend4 - Equipment Removal List for Sisters Ranger District.pdf PDF
Amendment 3.pdf PDF
Amend3 - 07 25 00-RIB-Weather Barriers-06-20-2022.pdf PDF
Amend2 - P002 - SCHEDULES - PLUMBING.pdf PDF
Amendment 2.pdf PDF
Amendment 1.pdf PDF
Amend1 - E100 - SITE PLAN - ELECTRICAL.pdf PDF
Amend1 - T100 - SITE PLAN - TECHNOLOGY.pdf PDF
Amend1 - Exhibit 01.pdf PDF
Amend1 - E501 - SINGLE LINE DIAGRAMS - ELECTRICAL.pdf PDF
Specifications.pdf PDF
Drawings.pdf PDF
CompleteSolicitation.pdf PDF
Show all 15

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

M

COMMON

WORK

SPACE

FIRE

CACHE

REC/SU

VEG MGMT

NR

TRANSPORT

ADMIN/

ARCH

STOR

A D

M

IN

/O

TH

ER

LEI

EVIDENCE

RR/SHWR

RR/SHWR

MECH

LAUNDRY

JANITOR

RR/SHWR

RR/SHWR

100A

I.T. ROOM

TV

TV

WM

TV

TV

TV

TV

TV

WM

WM

WS

WS

WS

TV

WM

TV

WS

TV

TV

WM

TV

TV

TVTVTV

WM

U G

P

CO

CO

CO

CO

C O

CO

CO

CO

COCOCO

CO

CO

EL

EL

EL

EL EL

EL

UT POLE

#102568

UT POLE

#102552

UT POLE

#102569

UT POLE

#102555

UT POLE

#102553

UT POLE

#102551

UT POLE

#102554

UT POLE

#102558

T

1-PH

5+

0+

1+

2+

3+00

4+

5+

0+00

1+00 2+00

3+

1+89

0+

1+00

0+89

0+00

0+71

0+00

0+00

1+00 1+20

1+

2+

3+

4+

5+

6+

7+

8+

9+

9+

S

IS

TE

R

S , O

R E

G O

N

SCP

01/28/2022

GMH

20145.01

0%

C D

S U

B M

IT

TA

L

- J

A N

U A

R Y

8, C3.1

U T

IL

IT

Y P

LA

N

C

IV

IL

E

N G

IN

E

E R

IN

G

S

U R

V E

Y

IN

G

P

LA

N N

IN

G

O

.B . R

IL

E

Y R

O A

D , S

TE

. 1

, B

E N

D , O

R

(5

)3

-9

W

W W

.H W

A

-IN

C .O

R G

COPYRIGHT 2022

STEELE ASSOCIATES

ARCHITECTS

All rights reserved. Reproduction or use in any form or by any means- graphic, electronic, mechanical, etc.- without written permission of STEELE ASSOCIATES ARCHITECTS is unlawful and subject to criminal prosecution.

JOB NO.

DATE

DRAWN BY CHECKED BY

SHEET NO.

5 4 3 2 1

D

C

B

A

D

C

B

A

5 4 3 2 1

OREGON

80067PE

EXPIRES: 12/31/2022

SEAN C. PASSAGE

SEPT . 11, 2018

E N G I N E ER

RE

GI

ST

E EDPROFESSIONAL

R

0 10 25 50 75 100 150

SCALE: 1" = 50'

EXISTING

FIRE HYDRANT

ASSEMBLY

EXISTING SANITARY

SEWER MAIN

EXISTING

WATER MAIN

EXISTING

ABANDONED

4" WATER LINE

EXISTING SANITARY

SEWER MAIN

EXISTING

WATER MAIN

S A N T I A M HW Y 2 0

W MAIN AVE

W ADAMS AVE

N P

IN

E

S T

PROPERTY BOUNDARY

PROPOSED SEWER LINE

(SIZE AS NOTED)

PROPOSED WATER LINE

(SIZE AS NOTED)

ALIGNMENT NAME

PROPOSED SHARED UTILITY TRENCH

(SEE ELECTRICAL (E-) AND TECHNOLOGY (T-) SHEETS FOR SIZE AND

NUMBER OF CONDUIT

PROPOSED UNDERGROUND COMMUNICATION TRENCH

(SEE TECHNOLOGY (T-) SHEETS FOR SIZE AND NUMBER OF CONDUIT)

PROPOSED UNDERGROUND POWER TRENCH

(SEE ELECTRICAL (E-) SHEETS FOR SIZE AND NUMBER OF CONDUIT)

UTILITY LEGEND

PROPERTY

BOUNDARY

PROPERTY

BOUNDARY

PROPERTY

BOUNDARY

PROPERTY

BOUNDARY

BLDG.

#1025

BLDG.

#1011

BLDG.

#1038

BLDG.

#1037

BLDG.

#1041

BLDG.

#2002

BLDG.

#2007

BLDG.

#1023

U S

F S

S

IS

T E

R S

R A

N G

E R

D

IS

T R

IC

T

S T

O R

A G

E B

U

IL

D

IN

G

1. ALL PUBLIC UTILITIES SHALL BE IN CONFORMANCE WITH CITY OF SISTERS

STANDARDS AND SPECIFICATIONS.

2. ALL PRIVATE UTILITIES SHALL BE IN CONFORMANCE WITH THESE PLANS, PROJECT

SPECIFICATIONS, AND 2021 OREGON PLUMBING SPECIALTY CODE (OPSC).

3. ALL SANITARY SEWER PIPING UNDER COVERED PORCHES, OR WITHIN 5' OF THE

BUILDING SHALL BE OF MATERIALS IN CONFORMANCE WITH THE PLUMBING CODE.

ALL OTHER SEWER PIPING SHALL BE PVC ASTM D3034.

4. ALL STORM SEWER PIPING IN COMMON TRENCHES WITH WATER, OR LOCATED UNDER

PORCHES, OR WITHIN 5' OF THE BUILDING SHALL BE SCH-40 OR ABS, PER 2021

OREGON SPECIALTY PLUMBING CODE. ALL OTHER STORM SEWER PIPING SHALL BE

PVC ASTM D3034, UNLESS NOTED OTHERWISE.

5. PER 2021 OPSC 314.4, EXCAVATIONS SHALL BE COMPLETELY BACKFILLED AS SOON

AFTER INSPECTION AS PRACTICABLE. PRECAUTION SHALL BE TAKEN TO ENSURE

COMPACTNESS OF BACKFILL AROUND PIPING WITHOUT DAMAGE TO SUCH PIPING.

TRENCHES SHALL BE BACKFILLED IN THIN LAYERS TO 12 INCHES (305 mm) ABOVE THE

TOP OF THE PIPING WITH CLEAN EARTH, WHICH SHALL NOT CONTAIN STONES,

BOULDERS, CINDERFILL, FROZEN EARTH, CONSTRUCTION DEBRIS, OR OTHER

MATERIALS THAT WILL DAMAGE OR BREAK THE PIPING OR CAUSE CORROSIVE

ACTION...FILL SHALL BE PROPERLY COMPACTED. PRECAUTIONS SHALL BE TAKEN TO

ENSURE PERMANENT STABILITY FOR PIPE LAID IN FILLED OR MADE GROUND.

6. ALL STORM DRAIN PIPING AND FITTINGS SHALL MEET THE 2021 OPSC AND BE THE

SAME AS SPECIFIED FOR SANITARY SEWERS IN SECTION 715.0 AND STORM DRAINAGE

IN SECTION 1101.4 OF THE OPSC.

7. CLEANOUTS SHALL BE INSTALLED AT INTERVALS NOT TO EXCEED 100' IN STRAIGHT

RUNS AND FOR EACH AGGREGATE HORIZONTAL CHANGE IN DIRECTION EXCEEDING

135 DEGREES PER 2021 OSPC 719.0 & 1101.13.

8. BUILDING DOWNSPOUTS SHALL DISCHARGE ROOF STORMWATER RUNOFF TO

PROPOSED DRAINAGE SWALES AS SHOWN.

9. PER OPSC 718.1, BUILDING SEWERS SHALL BE RUN IN PRACTICAL ALIGNMENT AND AT

A UNIFORM SLOPE OF NOT LESS THAN 1/4 INCH PER FOOT (20.8 mm/m) TOWARD THE

POINT OF DISPOSAL. EXCEPTION: WHERE APPROVED BY THE BUILDING OFFICIAL AND

WHERE IT IS IMPRACTICAL, DUE TO THE DEPTH OF THE STREET SEWER OR TO THE

STRUCTURAL FEATURES OR TO THE ARRANGEMENT OF A BUILDING OR STRUCTURE,

TO OBTAIN A SLOPE OF 1/4 INCH PER FOOT (20.8 mm/m), SUCH PIPE OR PIPING 4 INCHES (100 mm) THROUGH 6 INCHES (150 mm) SHALL BE PERMITTED TO HAVE A SLOPE OF NOT LESS THAN 1/8 INCH PER FOOT (10.4 mm/m) AND SUCH PIPING 8 INCHES (200 mm) AND LARGER SHALL BE PERMITTED TO HAVE A SLOPE OF NOT LESS THAN 1/16 INCH PER FOOT (5.2 mm/m) PER 2021 OPSC 718.1.

10. ALL SEWER DIMENSIONS AND SLOPES SHOWN ARE TO CENTER OF MANHOLE.

11. STATION AND OFFSETS ARE TO CENTER OF STRUCTURE UNLESS OTHERWISE NOTED.

12. SEE ELECTRICAL PLANS FOR SITE LIGHTING (POLE LOCATIONS AND ASSOCIATED

CONDUIT ROUTING).

13. SEE ELECTRICAL (E- SHEETS) AND TECHNOLOGY (T-SHEETS) PLANS FOR VAULT

DETAILS.

UTILITY NOTES

STORM DRAIN TRENCH PER DETAIL 1/C5.2

STA 0+42.05, 0.00'RT "STORM-1"

INSTALL 8" PIPE OUTFALL - 1

(SEE DETAIL 4/C5.4)

STA 0+75.75, 0.00'RT "STORM-1"

INSTALL 8" 45° ELBOW - 1

STA 1+29.53, 0.00'RT "STORM-1"

INSTALL 8"x8" WYE - 1

INSTALL 8" 45° ELBOW - 1

INSTALL 8" CLEANOUT ASSEMBLY - 1

INSTALL 8"x4" WYE - 1

(SEE DETAILS 1/C5.4 & 2/C5.4)

STA 1+76.94, 0.00'RT "STORM-1"

INSTALL 8"x4" WYE - 1

CONSTRUCT 4" SD LATERAL TO BLDG DOWNSPOUT

@ MIN. SLOPE OF 2.0%

(SEE DETAIL 2/C5.4)

STA 2+06.32, 0.00'RT "STORM-1"

INSTALL 8"x4" WYE - 1

CONSTRUCT 4" SD LATERAL TO BLDG DOWNSPOUT

@ MIN. SLOPE OF 2.0%

(SEE DETAIL 2/C5.4)

STA 2+09.97, 0.00'RT "STORM-1"

INSTALL 8"x8" ELBOWS - 2

INSTALL 8" CLEANOUT ASSEMBLY - 1

(SEE DETAIL 1/C5.4)

STA 2+18.47, 0.00'RT "STORM-1"

INSTALL 8"x4" WYE - 1

INSTALL 4" 45° ELBOW - 1

CONSTRUCT 4" SD LATERAL TO BLDG DOWNSPOUT

@ MIN. SLOPE OF 2.0%

(SEE DETAIL 2/C5.4)

STA 2+23.21, 0.00'RT "STORM-1"

INSTALL 8"x8" ELBOWS - 2

INSTALL 8" CLEANOUT ASSEMBLY - 1

(SEE DETAIL 1/C5.4)

STA 2+53.58, 0.00'RT "STORM-1"

INSTALL 8"x4" WYE - 1

CONSTRUCT 4" SD LATERAL TO BLDG DOWNSPOUT

@ MIN. SLOPE OF 2.0%

(SEE DETAIL 2/C5.4)

STA 2+61.33, 0.00'RT "STORM-1"

INSTALL 8" ELBOWS - 2

STA 2+82.09, 0.00'RT "STORM-1"

INSTALL 8"x4" WYE - 1

CONSTRUCT 4" SD LATERAL TO BLDG DOWNSPOUT

@ MIN. SLOPE OF 2.0%

(SEE DETAIL 2/C5.4)

STA 3+08.35, 0.00'RT "STORM-1"

INSTALL 8"x4" WYE - 1

INSTALL 8" CLEANOUT ASSEMBLY - 1

CONSTRUCT 4" SD LATERAL TO BLDG DOWNSPOUT

@ MIN. SLOPE OF 2.0%

(SEE DETAILS 1/C5.4 & 2/C5.4)

STA 0+69.89, 0.00'RT "STORM-2"

INSTALL 8" ELBOWS - 2

STA 0+79.22, 0.00'RT "STORM-2"

INSTALL 8"x4" WYE - 1

INSTALL 8" CLEANOUT ASSEMBLY - 1

CONSTRUCT 4" SD LATERAL TO BLDG DOWNSPOUT

@ MIN. SLOPE OF 2.0%

(SEE DETAILS 1/C5.4 & 2/C5.4)

STA 1+10.56, 0.00'RT "STORM-2"

INSTALL 8"x4" WYE - 1

CONSTRUCT 4" SD LATERAL TO BLDG DOWNSPOUT

@ MIN. SLOPE OF 2.0%

(SEE DETAIL 2/C5.4)

STA 1+37.18, 0.00'RT "STORM-2"

INSTALL 8"x8" WYE - 1 INSTALL 8"x4" WYE - 1

INSTALL 8" CLEANOUT ASSEMBLY - 1

INSTALL 8" 45° ELBOW - 1

CONSTRUCT 4" SD LATERAL TO BLDG DOWNSPOUT

@ MIN. SLOPE OF 2.0%

(SEE DETAILS 1/C5.4 & 2/C5.4)

STA 1+52.23, 0.00'RT "STORM-2"

INSTALL 8"x4" WYE - 1

CONSTRUCT 4" SD LATERAL TO BLDG DOWNSPOUT

@ MIN. SLOPE OF 2.0%

(SEE DETAIL 2/C5.4)

STA 1+56.90, 0.00'RT "STORM-2"

INSTALL 8" ELBOWS - 2

STA 1+81.45, 0.00'RT "STORM-2"

INSTALL 8"x4" WYE - 1

CONSTRUCT 4" SD LATERAL TO BLDG DOWNSPOUT

@ MIN. SLOPE OF 2.0%

(SEE DETAIL 2/C5.4)

STORM DRAIN KEY NOTES

NOTE:

SANITARY SEWER TRENCH PER DETAIL 1/C5.2

STA 2+39.52, 0.00'RT "SEWER-1"

INSTALL 6" 45° ELBOW - 1

CONNECT 6" PIPE TO EXISTING 6" SEWER

STA 2+99.28, 0.00'RT "SEWER-1"

INSTALL 6"x4" WYE - 1

INSTALL 4" 45° ELBOW - 1

(SEE DETAIL 2/C5.4)

CONNECT 4" SEWER LATERAL TO BLDG

(COORDINATE WITH PLUMBING SHEET P100)

STA 3+11.47, 0.00'RT "SEWER-1"

INSTALL 6"x6" WYE - 1

INSTALL 6" 45° ELBOW - 1

INSTALL CLEANOUT ASSEMBLY

(SEE DETAIL 1/C5.4)

STA 4+17.27, 0.00'RT "SEWER-1"

INSTALL 6" 45° ELBOW - 1

CONNECT 6" PIPE TO EXISTING 6" SEWER

STA 0+09.97, 1.94'LT "SEWER-2"

INSTALL 6"x4" WYE - 1

INSTALL 4" 45° ELBOW - 1

(SEE DETAIL 2/C5.4)

STA 0+52.54, 0.00'RT "SEWER-2"

INSTALL 4" 45° ELBOW - 1

STA 0+84.22, 0.00'RT "SEWER-2"

INSTALL 4" 45° ELBOW - 1

CONNECT 4" PIPE TO EXISTING 4" SEWER

STA 2+50.55, 0.00'RT "SEWER-1"

INSTALL 6"x4" WYE - 1

INSTALL 4" OIL/WATER SEPARATOR LINE TO

SAND/OIL INTERCEPTOR AS SHOWN.

(SEE PLUMBING SHEET P100 FOR CONTINUATION)

SANITARY SEWER KEY NOTES

NOTE:

"WATER-2"

"W

ATER-1"

WATERLINE TRENCH PER DETAIL 2/C5.2

STA 0+23.94, 0.00'RT "WATER-1"

INSTALL 2"x2" TEE - 1

INSTALL 2" GATE VALVE - 1

STA 0+77.44, 0.00'RT "WATER-1"

INSTALL 2" 22.5° ELBOW - 1

INSTALL 2" 45° ELBOW - 1

STA 0+89.44, 0.00'RT "WATER-1"

CONNECT 2" DOMESTIC WATER TO BUILDING

(COORDINATE WITH PLUMBING SHEET P100)

STA 0+49.15, 0.00'RT "WATER-2"

INSTALL WATER FILL STATION - 1

(SEE DETAIL 3/C5.4)

STA 0+08.79, 0.00'RT "WATER-2"

INSTALL 2"x2" TEE - 1

INSTALL 2" GATE VALVE - 1

INSTALL 3"x2" REDUCER - 1

WATER KEY NOTES

NOTE:

2 3

"STORM-1"

"STORM-2"

4 13

14 15

6 7

"S

EW

ER

-1

"SEWER-2"

CONTRACTOR SHALL POTHOLE AND VERIFY

EXISTING SEWER LATERAL LINE SIZE AND

DEPTHS AT PROPOSED POINTS OF

CONNECTION. CONTRACTOR SHALL NOTIFY

CONTRACTING OFFICER OF FINDINGS PRIOR

TO ANY SEWER LINE CONSTRUCTION, TYP.

(ASSUMED 6-INCH SS LATERAL PER

MANHOLE DIP INFORMATION)

CONTRACTOR SHALL POTHOLE AND VERIFY

EXISTING SEWER LATERAL LINE SIZE AND

DEPTHS AT PROPOSED POINTS OF

CONNECTION. CONTRACTOR SHALL NOTIFY

CONTRACTING OFFICER OF FINDINGS PRIOR

TO ANY SEWER LINE CONSTRUCTION, TYP.

CONTRACTOR SHALL POTHOLE AND VERIFY

EXISTING SEWER LATERAL LINE SIZE AND

DEPTHS AT PROPOSED POINTS OF

CONNECTION. CONTRACTOR SHALL NOTIFY

CONTRACTING OFFICER OF FINDINGS PRIOR

TO ANY SEWER LINE CONSTRUCTION, TYP.

SEE ELECTRICAL

SHEETS FOR VAULT

DETAILS

SEE ELECTRICAL

SHEETS FOR JUNCTION

DETAILS

SEE ELECTRICAL

SHEETS FOR JUNCTION

DETAILS

2" WM & DCVA