11-334100 - Storm Utility Drainage Piping.pdf

PDF 268 KB Posted

Attached to
IFB - Highland Park Elementary - Plaza Remodel
Solicitation number
TB2673-HPA
Issued by
Salt Lake County, Salt Lake City, Utah

About this file

This is a specification section for storm utility drainage piping work for the Salt Lake School District's Highland Park Elementary Plaza Remodel project located in Salt Lake City, Utah. The scope of work encompasses gravity-flow, nonpressure storm drainage systems outside the building, including special fittings for expansion and deflection, cleanouts, drains, precast concrete and cast-in-place manholes, inlet boxes, and catch basins. The specification details comprehensive requirements for piping materials, including PVC, HDPE, nonreinforced concrete pipe (CP), and reinforced concrete pipe (RCP) in various configurations. A mandatory pre-bid site visit is scheduled for Tuesday, May 26, 2026 at 10:00 A.M. at Highland Park Elementary School (1738 East 2700 South, Salt Lake City, Utah 84106), and contractors who do not attend on time will be prohibited from bidding. All questions must be submitted in writing through the Bonfire/U3P system or asked at the pre-bid meeting, with official answers provided only through the same platform or authorized addenda.

The specification establishes detailed performance requirements including a gravity-flow, nonpressure drainage-piping pressure rating of 10-foot head of water with joints that must be at least silt-tight. Bidders must provide product data, shop drawings with design calculations and concrete design-mix reports, coordination drawings showing pipe sizes and locations, and profile drawings at specified scales. Contractors are required to submit field quality-control test reports and must conduct video inspections of the storm drain system showing all lineal footage on DVD format, with monthly submissions to the owner and a final submission with as-built drawings. The specification includes approved manufacturers for various components such as cleanouts, drains, manholes, and couplings, with options for local precast manufacturers subject to engineer and architect approval. Installation requirements mandate compliance with multiple ASTM and AWWA standards, with specific protocols for gravity-flow and pressure piping installation, joint construction, and system testing to ensure proper alignment, deflection tolerances, and leak-free operation before final approval.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Salt Lake School District – High-land Park Elementary - Plaza

334100 - 1 Storm Utility Drainage Piping

SECTION 334100 - STORM UTILITY DRAINAGE PIPING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes gravity-flow, nonpressure storm drainage outside the building, with the following components:

1. Special fittings for expansion and deflection.

2. Cleanouts.

3. Drains.

4. Precast concrete manholes, inlet boxes, catch basins.

5. Cast in place inlet boxes and catch basins and manhole bases over existing pipes.

1.3 DEFINITIONS

A. PVC: Polyvinyl chloride plastic.

B. HDPE: High density polyethylene.

C. CP: Non-reinforced concrete pipe.

D. RCP: Reinforced concrete pipe.

1.4 PERFORMANCE REQUIREMENTS

A. Gravity-Flow, Nonpressure, Drainage-Piping Pressure Rating: 10-foot head of water. Pipe joints shall be at least silttight, unless otherwise indicated.

1.5 SUBMITTALS

A. Product Data: For the following:

1. Special pipe fittings.

2. Drains.

3. Storage.

4. Pipes.

B. Shop Drawings: For the following:

334100 - 2 Storm Utility Drainage Piping

1. design calculations, and concrete design-mix report for cast-in-place manholes.

2. Catch Basins and Stormwater Inlets. Include plans, elevations, sections, details, and frames, covers, and grates.

3. Stormwater Detention Structures: Include plans, elevations, sections, details, frames and covers, design calculations, and concrete design-mix report.

C. Coordination Drawings: Show pipe sizes, locations, and elevations. Show other piping in same trench and clearances from storm drainage system piping. Indicate interface and spatial relationship between manholes, piping, and proximate structures.

D. Profile Drawings: Show system piping in elevation. Draw profiles at horizontal scale of not less than 1 inch equals 50 feet and vertical scale of not less than 1 inch equals 5 feet. Indicate manholes and piping. Show types, sizes, materials, and elevations of other utilities crossing system piping.

E. Field quality-control test reports.

1.6 DELIVERY, STORAGE, AND HANDLING

A. Do not store plastic manholes, pipe, and fittings in direct sunlight.

B. Protect pipe, pipe fittings, and seals from dirt and damage.

C. Handle manholes according to manufacturer's written rigging instructions.

D. Handle catch basins and stormwater inlets according to manufacturer's written rigging instructions.

1.7 PROJECT CONDITIONS

A. Interruption of Existing Storm Drainage Service: Do not interrupt service to facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary service according to requirements indicated:

1. Notify Architect, Construction Manager, and Owner no fewer than two days in advance of proposed interruption of service. Coordinate interruptions during weekly meetings and at pre-construction meeting.

2. Do not proceed with interruption of service without Architect's, Construction Manager's, and Owner's written permission.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection:

334100 - 3 Storm Utility Drainage Piping

1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include local pre-cast manufacturers but are subject to approval of the engineer and architect.

2.2 PIPING MATERIALS

A. Refer to Part 3 "Piping Applications" Article for applications of pipe, fitting, and joining materials.

2.3 PVC & HDPE PIPE AND FITTINGS

A. HDPE Pressure Pipe: AWWA C906, ASTM D3350, only to be used where specifically noted in plans.

B. PVC Pressure Pipe: AWWA C900, Class 150 for gasketed joints and using ASTM F 477, elastomeric seals.

1. Fittings NPS 4 to NPS 8: PVC pressure fittings complying with AWWA C907, for gasketed joints and using ASTM F 477, elastomeric seals.

2. Fittings NPS 10 and Larger: Ductile-iron, compact fittings complying with AWWA C153, for push-on joints and using AWWA C111, rubber gaskets.

C. PVC Water-Service Pipe and Fittings: ASTM D 1785, Schedule 80 pipe, with plain ends for solvent-cemented joints with ASTM D 2467, Schedule 80, socket-type fittings.

D. PVC Cellular-Core Pipe and Fittings: ASTM F 891, Sewer and Drain Series, PS 50 minimum stiffness pipe with ASTM D 3034, SDR 35, socket-type fittings for solvent-cemented joints.

E. PVC Sewer Pipe and Fittings, NPS 15 and Smaller: ASTM D 3034, SDR 35, with bell-and-spigot ends for gasketed joints with ASTM F 477, elastomeric seals.

F. PVC Sewer Pipe and Fittings, NPS 18 and Larger: ASTM F 679, T 2 wall thickness, with bell-and-spigot ends for gasketed joints with ASTM F 477, elastomeric seals.

G. PVC Profile Gravity Sewer Pipe and Fittings: ASTM F 794 pipe, with bell-and-spigot ends;

ASTM D 3034 fittings, with bell ends; and ASTM F 477, elastomeric seals.

2.4 CONCRETE PIPE AND FITTINGS

A. Nonreinforced-Concrete Sewer Pipe and Fittings: ASTM C 14, Class I, II or III, with bell-and-spigot ends and gasketed joints with ASTM C 443, rubber gaskets.

B. Piping in paragraph below is available in 5 classes and 3 wall thicknesses, and in NPS 12 to NPS 144. Not all classes and wall thicknesses are available. Joints are gasket type.

Contractor, at his option, may use non-reinforced pipe for sizes up to 21-inches if structural requirements based on load on pipe are not exceeded for that pipe. If reinforced pipe is selected, choose the pipe class and wall thickness to suit availability and structural requirements based on loads and cover.

C. Reinforced-Concrete Sewer Pipe and Fittings: ASTM C 76, with bell-and-spigot ends and gasketed joints with ASTM C 443, rubber gaskets.

334100 - 4 Storm Utility Drainage Piping

1. Class I

2. Class II

3. Class III

2.5 NONPRESSURE-TYPE PIPE COUPLINGS

A. Comply with ASTM C 1173, elastomeric, sleeve-type, reducing or transition coupling, for joining underground nonpressure piping. Include ends of same sizes as piping to be joined, and corrosion-resistant-metal tension band and tightening mechanism on each end.

B. Sleeve Materials:

1. For Concrete Pipes: ASTM C 443, rubber.

2. For Cast-Iron Soil Pipes: ASTM C 564, rubber.

3. For Plastic Pipes: ASTM F 477, elastomeric seal or ASTM D 5926, PVC.

4. For Dissimilar Pipes: ASTM D 5926, PVC or other material compatible with pipe materials being joined.

C. Unshielded Flexible Couplings: Elastomeric sleeve with stainless-steel shear ring and corrosion-resistant-metal tension band and tightening mechanism on each end.

1. Manufacturers:

a. Dallas Specialty & Mfg. Co.

b. Fernco Inc.

c. Logan Clay Products Company (The).

d. Mission Rubber Company; a division of MCP Industries, Inc.

e. NDS Inc.

f. Plastic Oddities, Inc.

D. Shielded Flexible Couplings: ASTM C 1460, elastomeric or rubber sleeve with full-length, corrosion-resistant outer shield and corrosion-resistant-metal tension band and tightening mechanism on each end.

1. Manufacturers:

a. Cascade Waterworks Mfg.

b. Dallas Specialty & Mfg. Co.

c. Mission Rubber Company; a division of MCP Industries, Inc.

E. Ring-Type Flexible Couplings: Elastomeric compression seal with dimensions to fit inside bell of larger pipe and for spigot of smaller pipe to fit inside ring.

1. Manufacturers:

a. Fernco Inc.

b. Logan Clay Products Company (The).

c. Mission Rubber Company; a division of MCP Industries, Inc.

334100 - 5 Storm Utility Drainage Piping

A. Reducing or transition, metal, bolted, sleeve-type, reducing or transition coupling, for joining underground pressure piping. Include 150-psig minimum pressure rating and ends of same sizes as piping to be joined.

2.6 PRESSURE-TYPE PIPE COUPLINGS

B. Tubular-Sleeve Couplings: AWWA C219, with center sleeve, gaskets, end rings, and bolt fasteners.

1. Manufacturers:

a. Cascade Waterworks Mfg.

b. Dresser, Inc.; DMD Div.

c. Ford Meter Box Company, Inc. (The); Pipe Products Div.

d. JCM Industries.

e. Romac Industries, Inc.

f. Smith-Blair, Inc.

g. Viking Johnson.

2. Center-Sleeve Material: Manufacturer's standard.

3. Gasket Material: Natural or synthetic rubber.

4. Metal Component Finish: Corrosion-resistant coating or material.

C. Split-Sleeve Couplings: With split sleeve with sealing pad and closure plates, O-ring gaskets, and bolt fasteners.

1. Manufacturers:

a. Brico Industries.

2. Sleeve Material: Manufacturer's standard.

3. Sleeve Dimensions: Of thickness and width required to provide pressure rating.

4. Gasket Material: O-rings made of EPDM rubber, unless otherwise indicated.

5. Metal Component Finish: Corrosion-resistant coating or material.

2.7 SPECIAL PIPE FITTINGS

A. Ductile-Iron Flexible Expansion Joints: Compound fitting with combination of flanged and mechanical-joint ends complying with AWWA C110 or AWWA C153. Include 2 gasketed ball-joint sections and 1 or more gasketed sleeve sections, rated for 250-psig minimum working pressure and for offset and expansion indicated.

1. Manufacturers:

a. EBAA Iron Sales, Inc.

b. Romac Industries, Inc.

c. Star Pipe Products.

B. Ductile-Iron Deflection Fittings: Compound coupling fitting with ball joint, flexing section, gaskets, and restrained-joint ends complying with AWWA C110 or AWWA C153. Include rating for 250-psig minimum working pressure and for up to 15 degrees of deflection.

1. Manufacturers:

334100 - 6 Storm Utility Drainage Piping

a. EBAA Iron Sales, Inc.

C. Ductile-Iron Expansion Joints: Three-piece assembly of telescoping sleeve with gaskets and restrained-type, ductile-iron, bell-and-spigot end sections complying with AWWA C110 or AWWA C153. Include rating for 250-psig minimum working pressure and for expansion indicated.

1. Manufacturers:

a. Dresser, Inc.; DMD Div.

b. EBAA Iron Sales, Inc.

c. JCM Industries.

d. Smith-Blair, Inc.

2.8 CLEANOUTS

A. Gray-Iron Cleanouts: ASME A112.36.2M, round, gray-iron housing with clamping device and round, secured, scoriated, gray-iron cover. Include gray-iron ferrule with inside calk or spigot connection and countersunk, tapered-thread, brass closure plug.

1. Manufacturers:

a. Josam Company.

b. MIFAB Manufacturing, Inc.

c. Smith, Jay R. Mfg. Co.

d. Wade Div.; Tyler Pipe.

e. Watts Industries, Inc.

f. Watts Industries, Inc.; Enpoco, Inc. Div.

g. Zurn Industries, Inc.; Zurn Specification Drainage Operation.

2. Top-Loading Classification(s): Light, Medium, Heavy, and Extra-heavy duty depending on location and expected driving load on cleanout.

3. Sewer Pipe Fitting and Riser to Cleanout: ASTM A 74, Service class, cast-iron soil pipe and fittings.

B. PVC Cleanouts: PVC body with PVC threaded plug. Include PVC sewer pipe fitting and riser to cleanout of same material as sewer piping. Place in grey iron housing with clamping device and round, secured, scoriated, gray-iron cover.

1. Manufacturers:

a. Canplas Inc.

b. IPS Corporation.

c. NDS Inc.

d. Plastic Oddities, Inc.

e. Sioux Chief Manufacturing Company, Inc.

f. Zurn Industries, Inc.; Zurn Light Commercial Specialty Plumbing Products.

334100 - 7 Storm Utility Drainage Piping

2.9 DRAINS

A. Gray-Iron Area Drains: ASME A112.21.1M, round body with anchor flange and round secured grate. Include bottom outlet with inside calk or spigot connection, of sizes indicated.

1. Manufacturers:

a. Josam Company.

b. MIFAB Manufacturing, Inc.

c. Smith, Jay R. Mfg. Co.

d. Wade Div.; Tyler Pipe.

e. Watts Industries, Inc.

f. Watts Industries, Inc.; Enpoco, Inc. Div.

g. Zurn Industries, Inc.; Zurn Specification Drainage Operation.

2. Top-Loading Classification(s): Medium and heavy duty depending on location and expected driving load.

B. Gray-Iron Trench Drains: ASME A112.21.1M, 6-inch to 12-inch-wide top surface, rectangular body with anchor flange or other anchoring device, and rectangular secured grate. Include units of total length indicated and number of bottom outlets with inside calk or spigot connections, of sizes indicated.

1. Manufacturers:

a. Josam Company.

b. Smith, Jay R. Mfg. Co.

c. Wade Div.; Tyler Pipe.

d. Watts Industries, Inc.

e. Watts Industries, Inc.; Enpoco, Inc. Div.

f. Zurn Industries, Inc.; Zurn Specification Drainage Operation.

g. Poly Drain, ABT

2. Top-Loading Classification(s): Medium, heavy, and extra-heavy duty.

2.10 MANHOLES

A. Standard Precast Concrete Manholes: ASTM C 478, precast, reinforced concrete, of depth indicated, with provision for sealant joints.

1. Diameter: 48 inches minimum, unless otherwise indicated and as needed for pipe sizes.

2. Ballast: Increase thickness of precast concrete sections or add concrete to base section, as required to prevent flotation.

3. Base Section: 9-inch minimum thickness for floor slab and 4-inch minimum thickness for walls and base riser section, and having separate base slab or base section with integral floor.

4. Riser Sections: 4-inch minimum thickness, and lengths to provide depth indicated.

5. Top Section: Eccentric-cone type unless concentric-cone or flat-slab-top type is indicated. Top of cone of size that matches grade rings.

6. Joint Sealant: ASTM C 990, bitumen or butyl rubber.

334100 - 8 Storm Utility Drainage Piping

7. Resilient Pipe Connectors: ASTM C 923, cast or fitted into manhole walls, for each pipe connection.

8. Steps: Not used.

9. Adjusting Rings: Interlocking rings with level or sloped edge in thickness and diameter matching manhole frame and cover. Include sealant recommended by ring manufacturer.

10. Grade Rings: Reinforced-concrete rings, 6- to 9-inch total thickness, to match diameter of manhole frame and cover.

11. Manhole Frames and Covers: Ferrous; 24-inch ID by 7- to 9-inch riser with 4-inch-minimum width flange and 26-inch- diameter cover. Include indented top design with lettering cast into cover, using wording equivalent to "STORM SEWER."

a. Material: ASTM A 536, Grade 60-40-18 ductile or ASTM A 48, Class 35 gray iron, unless otherwise indicated and to match existing manhole frames and covers.

b. Protective Coating: Foundry-applied, SSPC-Paint 16, coal-tar, epoxy-polyamide paint; 15-mil minimum thickness applied to all surfaces, unless otherwise indicated.

B. Cast-in-Place Concrete Manholes: Construct of reinforced-concrete bottom, walls, and top;

designed according to ASTM C 890 for A-16 (ASSHTO HS20-44), heavy-traffic, structural loading; of depth, shape, dimensions, and appurtenances indicated.

1. Ballast: Increase thickness of concrete, as required to prevent flotation.

2. Resilient Pipe Connectors: ASTM C 923, cast or fitted into manhole walls, for each pipe connection.

3. Steps: Not used.

4. Adjusting Rings: Interlocking rings with level or sloped edge in thickness and diameter matching manhole frame and cover. Include sealant recommended by ring manufacturer.

5. Grade Rings: Reinforced-concrete rings, 6- to 9-inch total thickness, to match diameter of manhole frame and cover.

6. Manhole Frames and Covers: Ferrous; 24-inch ID by 7- to 9-inch riser with 4-inch-minimum width flange and 26-inch- diameter cover. Include indented top design with lettering cast into cover, using wording equivalent to "STORM SEWER."

a. Material: ASTM A 536, Grade 60-40-18 ductile or ASTM A 48, Class 35 gray iron, unless otherwise indicated and to match existing frames and covers.

b. Protective Coating: Foundry-applied, SSPC-Paint 16, coal-tar, epoxy-polyamide paint 15-mil minimum thickness applied to all surfaces, unless otherwise indicated.

2.11 CONCRETE

A. General: Cast-in-place concrete according to ACI 318/318R, ACI 350R, and the following:

334100 - 9 Storm Utility Drainage Piping

1. Cement: ASTM C 150, Type II.

2. Fine Aggregate: ASTM C 33, sand.

3. Coarse Aggregate: ASTM C 33, crushed gravel.

4. Water: Potable.

B. Portland Cement Design Mix: 4000 psi minimum, with 0.45 maximum water-cementitious materials ratio.

1. Reinforcement Fabric: ASTM A 185, steel, welded wire fabric, plain.

2. Reinforcement Bars: ASTM A 615/A 615M, Grade 60, deformed steel.

C. Ballast and Pipe Supports: Portland cement design mix, 3000 psi minimum, with 0.58 maximum water-cementitious materials ratio.

1. Reinforcement Fabric: ASTM A 185, steel, welded wire fabric, plain.

2. Reinforcement Bars: ASTM A 615/A 615M, Grade 60, deformed steel.

2.12 POLYMER-CONCRETE, CHANNEL DRAINAGE SYSTEMS

A. Description, General: Modular system of precast, polymer-concrete channel sections, grates, and appurtenances; designed so grates fit into channel recesses without rocking or rattling.

Include number of units required to form total lengths indicated.

B. Manufacturers:

1. ABT, Inc.

2. ACO Polymer Products, Inc.

3. Innovative Plastics Products. Inc.

4. Mea-Josam Div.; Josam Company.

5. Strongwell; Lenoir City Div.

C. Sloped-Invert, Polymer-Concrete Systems: Include the following components:

1. Channel Sections: Interlocking-joint, precast, modular units with end caps. Include inside width and depth as indicated with rounded bottom, with built-in invert slope of 0.6 percent and with outlets in number, sizes, and locations indicated. Include extension sections necessary for required depth.

a. Frame: Include gray-iron or steel frame for grate.

2. Grates with manufacturer's designation "Heavy Duty," with slots or perforations that fit recesses in channels.

a. Material: Gray iron.

3. Covers: Solid gray iron, if indicated.

4. Locking Mechanism: Manufacturer's standard device for securing grates to channel sections.

D. Narrow-Width, Level-Invert, Polymer-Concrete Systems: Include the following components:

334100 - 10 Storm Utility Drainage Piping

1. Channel Sections: Interlocking-joint, precast, modular units with end caps. Include 5-inch inside width and 9-3/4-inch deep, rounded bottom, with level invert and with NPS 4 outlets in number and locations indicated.

2. Grates with slots or perforations that fit recesses in channels.

a. Material: Gray iron.

3. Covers: Solid gray iron, if indicated.

4. Locking Mechanism: Manufacturer's standard device for securing grates to channel sections.

E. Wide-Width, Level-Invert, Polymer-Concrete Systems: Include the following components:

1. Channel Sections: Interlocking-joint, precast, modular units with end caps. Include 8-inch inside width and 13-3/4-inch-deep, rounded bottom, with level invert and with outlets in number, sizes, and locations indicated.

2. Grates with slots or other openings that fit recesses in channels.

a. Material: Gray iron.

3. Covers: Solid gray iron, if indicated.

4. Locking Mechanism: Manufacturer's standard device for securing grates to channel sections.

F. Supports, Anchors, and Setting Devices: Manufacturer's standard, unless otherwise indicated.

G. Channel-Section Joining and Fastening Materials: As recommended by system manufacturer.

2.13 CATCH BASINS

A. Standard Precast Concrete Catch Basins: ASTM C 478, precast, reinforced concrete, of depth indicated, with provision for sealant joints.

1. Base Section: 6-inch minimum thickness for floor slab and 4-inch minimum thickness for walls and base riser section, and having separate base slab or base section with integral floor.

2. Riser Sections: 4-inch minimum thickness, and lengths to provide depth indicated.

3. Top Section: Flat-slab-top type with hole for frame and grate is indicated.

4. Joint Sealant: ASTM C 990, bitumen or butyl rubber.

5. Adjusting Rings: Interlocking rings with level or sloped edge in thickness and shape matching catch basin frame and grate. Include sealant recommended by ring manufacturer.

6. Grade Rings: Include 2 or 3 reinforced-concrete rings, of 6- to 9-inch total thickness, that match frame and grate.

7. Steps: Not Used.

8. Pipe Connectors: ASTM C 923, resilient, of size required, for each pipe connecting to base section. Size sections and box or manhole to fit pipes without necessary.

9. Catch basins shall be provided by the contractor in an appropriate size to accommodate the pipe size, material, flow lines and arrangement as shown on the plans.

334100 - 11 Storm Utility Drainage Piping

B. Cast-in-Place Concrete, Catch Basins: Construct of reinforced concrete; designed according to ASTM C 890 for structural loading; of depth, shape, dimensions, and appurtenances indicated.

1. Bottom, Walls, and Top: Reinforced concrete.

2. Channels and Benches: Concrete.

3. Steps: Not used.

C. Frames and Grates: ASTM A 536, Grade 60-40-18, ductile iron designed for H-20, structural loading. Include flat grate with small square or short-slotted drainage openings. All grates shall be bicycle proof. Grates installed in pedestrian areas shall be heel proof as determined by the manufacturer.

1. Size: 24 by 24 inches minimum, unless otherwise indicated.

2. Grate Free Area: Approximately 50 percent, unless otherwise indicated.

2.14 STORMWATER INLETS

A. Gutter Inlets: Horizontal gutter opening, of materials and dimensions indicated. Include heavy-duty frames and grates. All grates to be bicycle safe.

B. Combination Inlets: Vertical curb and horizontal gutter openings, of materials and dimensions indicated. Include heavy-duty frames and grates.

2.15 PIPE OUTLETS

A. Head Walls: Cast-in-place reinforced concrete, with apron and tapered sides.

B. Riprap Basins: Broken, irregular size and shape, graded stone according to NSSGA's "Quarried Stone for Erosion and Sediment Control."

C. Filter Stone: According to NSSGA's "Quarried Stone for Erosion and Sediment Control," No. FS-2, No. 4 screen opening, average-size, graded stone.

D. Energy Dissipaters: According to NSSGA's "Quarried Stone for Erosion and Sediment Control," No. A-1, 3-ton average weight armor stone, unless otherwise indicated.

2.16 DRY WELLS

A. Description: ASTM C 913, precast, reinforced, perforated concrete manholes with ring and cover, frame and grate, or lid as indicated and include the following:

1. Floor: Cast-in-place concrete support ring.

2. Cover: Liftoff-type concrete cover with cast-in lift rings.

3. Wall Thickness: 4 inches minimum with 1-inch diameter or 1-by-3-inch maximum slotted perforations arranged in rows parallel to axis of ring.

a. Total Free Area of Perforations: Approximately 15 percent of ring interior surface.

b. Ring Construction: Designed to be self-aligning.

4. Filtering Material: ASTM D 448, Size No. 24, 3/4- to 2-1/2-inch washed, crushed stone or gravel. The % of material passing the # 200 sieve shall not exceed 5%.

334100 - 12 Storm Utility Drainage Piping

PART 3 - EXECUTION

3.1 EARTHWORK

A. Excavation, trenching, and backfilling are specified in Division 31 Section "Earth Moving."

3.2 PIPING APPLICATIONS

A. Pipe couplings and special pipe fittings with pressure ratings at least equal to piping rating may be used in applications below, unless otherwise indicated.

1. Use nonpressure-type flexible couplings where required to join gravity-flow, nonpressure sewer piping, unless otherwise indicated.

a. Flexible or rigid couplings for same or minor difference OD pipes.

b. Unshielded, increaser/reducer-pattern, flexible or rigid couplings for pipes with different OD.

c. Ring-type flexible couplings for piping of different sizes where annular space between smaller piping's OD and larger piping's ID permits installation.

2. Use pressure-type pipe couplings for force-main joints.

B. Special Pipe Fittings: Use for pipe expansion and deflection. Pipe couplings and special pipe fittings with pressure ratings at least equal to piping rating may be used in applications below, unless otherwise indicated.

C. Gravity-Flow, Nonpressure Sewer Piping: Use any of the following pipe materials for each size range:

1. PVC water-service pipe; PVC Schedule 40, water-service-pipe fittings; and solvent-cemented joints.

2. PVC sewer pipe and fittings; gaskets; and gasketed joints.

3. Class [1] [2] [3], nonreinforced-concrete sewer pipe and fittings, gaskets, and gasketed joints.

4. Ductile-iron culvert pipe, ductile-iron standard or compact fittings, gaskets, and gasketed joints.

5. Reinforced-concrete sewer pipe and fittings, gaskets, and gasketed joints.

6. Corrugated steel pipe and fittings, standard and special-joint bands, and banded joints.

7. Corrugated aluminum pipe and fittings, standard and special-joint bands, and banded joints.

8. Corrugated PE pipe and fittings, silttight couplings, and coupled joints.

3.3 PIPING INSTALLATION

A. General Locations and Arrangements: Drawing plans and details indicate general location and arrangement of underground storm drainage piping. Location and arrangement of piping layout take design considerations into account. Install piping as indicated, to extent practical. Where specific installation is not indicated, follow piping manufacturer's written instructions.

334100 - 13 Storm Utility Drainage Piping

B. Install piping beginning at low point, true to grades and alignment indicated with unbroken continuity of invert. Place bell ends of piping facing upstream. Install gaskets, seals, sleeves, and couplings according to manufacturer's written instructions for use of lubricants, cements, and other installation requirements.

C. Install manholes for changes in direction unless fittings are indicated. Use fittings for branch connections unless direct tap into existing sewer is indicated.

D. Install proper size increasers, reducers, and couplings where different sizes or materials of pipes and fittings are connected. Reducing size of piping in direction of flow is prohibited.

E. Tunneling: Install pipe under streets or other obstructions that cannot be disturbed by tunneling, jacking, or a combination of both.

F. Install gravity-flow, nonpressure drainage piping according to the following:

1. Install piping pitched down in direction of flow, at slope indicated.

2. Install piping with restrained joints at tee fittings and at changes in direction for pressure pipe. Use corrosion-resistant rods, pipe or fitting manufacturer's proprietary restraint system, or cast-in-place concrete supports or anchors.

3. Install piping with cover indicated.

4. Notify engineer of clearance problems that would result in changes to grade and alignment.

5. Install PVC cellular-core piping according to ASTM D 2321 and ASTM F 1668.

6. Install PVC sewer piping according to ASTM D 2321 and ASTM F 1668.

7. Install PVC profile gravity sewer piping according to ASTM D 2321 and ASTM F 1668.

8. Install nonreinforced-concrete sewer piping according to ASTM C 1479 and ACPA's

"Concrete Pipe Installation Manual."

9. Install reinforced-concrete sewer piping according to ASTM C 1479 and ACPA's

"Concrete Pipe Installation Manual."

G. Install force-main pressure piping according to the following:

1. Install piping with restrained joints at tee fittings and at horizontal and vertical changes in direction. Use corrosion-resistant rods, pipe or fitting manufacturer's proprietary restraint system, or cast-in-place concrete supports or anchors.

2. Install piping with line and grade as indicated or below frost line if not inidcated.

3. Install PVC pressure piping according to AWWA M23 or ASTM D 2774 and

ASTM F 1668.

4. Install PVC water-service piping according to ASTM D 2774 and ASTM F 1668.

3.4 PIPE JOINT CONSTRUCTION

A. Basic pipe joint construction is specified in Division 33 Section "Common Work Results for Utilities." Where specific joint construction is not indicated, follow piping manufacturer's written instructions.

B. Join gravity-flow, nonpressure drainage piping according to the following:

1. Join PVC cellular-core piping according to ASTM D 2321 and ASTM F 891 for solvent-cement joints.

334100 - 14 Storm Utility Drainage Piping

2. Join PVC sewer piping according to ASTM D 2321 and ASTM D 3034 for elastomeric-seal joints or ASTM D 3034 for elastomeric gasket joints.

3. Join PVC profile gravity sewer piping according to ASTM D 2321 for elastomeric-seal joints or ASTM F 794 for gasketed joints.

4. Join nonreinforced-concrete sewer piping according to ASTM C 14and ACPA's "Concrete Pipe Installation Manual" for rubber-gasket joints.

5. Join reinforced-concrete sewer piping according to ACPA's "Concrete Pipe Installation Manual" for rubber-gasket joints.

6. Join dissimilar pipe materials with nonpressure-type flexible or rigid couplings.

C. Join dissimilar pipe materials with pressure-type couplings.

3.5 CLEANOUT INSTALLATION

A. Install cleanouts and riser extension from sewer pipe to cleanout at grade. Use same pipe type as sewer line that the cleanout is connected to. Install piping so cleanouts open in direction of flow in sewer pipe.

1. Use light-duty, top-loading classification cleanouts in earth or unpaved foot-traffic areas.

2. Use medium-duty, top-loading classification cleanouts in paved foot-traffic areas.

3. Use heavy-duty, top-loading classification cleanouts in vehicle-traffic service areas.

4. Use extra-heavy-duty, top-loading classification cleanouts in roads areas.

B. Set cleanout frames and covers in earth in cast-in-place concrete block, 12 inches around outside of cover. At contractors option, a square block can be used that is at least 12-inches wider that the cover. Set with tops 1 inch above surrounding earth grade.

C. Set cleanout frames and covers in concrete pavement with tops flush with pavement surface.

3.6 DRAIN INSTALLATION

A. Install type of drains in locations indicated.

1. Use heavy-duty, top-loading classification drains in vehicle-traffic service areas, earth or unpaved foot-traffic areas and paved foot-traffic areas.

2. Use extra-heavy-duty, top-loading classification drains in roads areas.

B. Embed drains in 4-inch minimum depth of concrete around bottom and sides.

C. Fasten grates to drains if indicated.

D. Set drain frames and covers with tops flush with pavement surface.

E. Assemble trench sections with flanged joints.

F. Embed trench sections in 4-inch minimum concrete around bottom and sides.

3.7 MANHOLE INSTALLATION

A. General: Install manholes, complete with appurtenances and accessories indicated.

334100 - 15 Storm Utility Drainage Piping

B. Install precast concrete manhole sections according to ASTM C 891.

C. Construct cast-in-place manholes as indicated.

D. Install PE sheeting on earth where cast-in-place-concrete manholes are to be built.

E. Set tops of frames and covers flush with finished surface of manholes that occur in pavements.

Set tops 3 inches above finished surface elsewhere, unless otherwise indicated.

3.8 CATCH BASIN INSTALLATION

A. Construct catch basins in an appropriate size to accommodate the pipe size, material, flow lines and arrangement as shown on the plans.

B. Set frames and grates to elevations indicated.

C. Align boxes so that frame and grates are square to adjacent sidewalks, curbs or roadways.

3.9 STORMWATER INLET AND OUTLET INSTALLATION

A. Construct inlet head walls, aprons, and sides of reinforced concrete, as indicated.

B. Construct riprap of broken stone, as indicated.

C. Install outlets that spill onto grade, anchored with concrete, where indicated.

D. Install outlets that spill onto grade, with flared end sections that match pipe, where indicated.

E. Construct energy dissipaters at outlets, as indicated.

F. Place cast-in-place concrete according to ACI 318/318R.

3.10 DRAINAGE SYSTEM INSTALLATION

A. Assemble and install components according to manufacturer's written instructions.

B. Install with top surfaces of components, except piping, flush with finished surface.

C. Assemble channel sections to form slope down toward drain outlets. Use sealants, adhesives, fasteners, and other materials recommended by system manufacturer.

D. Embed channel sections and drainage specialties in 4-inch minimum concrete around bottom and sides.

E. Fasten grates to channel sections if indicated.

F. Assemble channel sections with flanged or interlocking joints.

G. Embed channel sections in 4-inch minimum concrete around bottom and sides.

334100 - 16 Storm Utility Drainage Piping

3.11 CONNECTIONS

A. Connect nonpressure, gravity-flow drainage piping in building's storm building drains specified in Division 22 Section "Facility Storm Drainage Piping."

B. Connect force-main pressure piping to building's storm drainage force mains specified in Division 22 Section "Facility Storm Drainage Piping." Terminate piping where indicated.

1. Use commercially manufactured wye fittings for piping branch connections. Remove section of existing pipe; install wye fitting into existing piping; and encase entire wye fitting, plus 6-inch overlap, with not less than 6 inches of concrete with 28-day compressive strength of 3000 psi.

2. Protect existing piping, manholes, and structures to prevent concrete or debris from entering while making tap connections. Remove debris or other extraneous material that may accumulate.

C. Connect to sediment interceptors specified in Division 22 Section "Sanitary Waste Interceptors."

3.12 CLOSING ABANDONED STORM DRAINAGE SYSTEMS

A. Abandoned Piping: Close open ends of abandoned underground piping indicated to remain in place. Include closures strong enough to withstand hydrostatic and earth pressures that may result after ends of abandoned piping have been closed. Use either procedure below:

1. Close open ends of piping with at least 8-inch-thick, brick masonry bulkheads.

2. Close open ends of piping with threaded metal caps, plastic plugs, or other acceptable methods suitable for size and type of material being closed. Do not use wood plugs.

B. Abandoned Manholes and Structures: Excavate around manholes and structures as required and use one procedure below:

1. Remove manhole or structure and close open ends of remaining piping.

2. Remove top of manhole or structure down to at least 36 inches below final grade. Fill to within 12 inches of top with stone, rubble, gravel, or compacted dirt. Fill to top with concrete.

C. Backfill to grade according to Division 31 Section "Earth Moving."

3.13 IDENTIFICATION

A. Materials and their installation are specified in Division 31 Section "Earth Moving." Arrange for installation of green warning tape directly over piping and at outside edge of underground structures.

1. Use warning tape or detectable warning tape over ferrous piping.

2. Use detectable warning tape over nonferrous piping and over edges of underground structures.

334100 - 17 Storm Utility Drainage Piping

3.14 FIELD QUALITY CONTROL

A. Inspect interior of piping to determine whether line displacement or other damage has occurred.

Inspect after approximately 24 inches of backfill is in place, and again at completion of Project.

1. Submit separate reports for each system inspection.

a. Reports shall include a video log of storm drain showing all lineal footage of the system in DVD format. Log shall be submitted to the owner once a month. A final log shall be submitted with the as built drawing for the use of the owner and Architect.

2. Defects requiring correction include the following:

a. Alignment: Less than full diameter of inside of pipe is visible between structures.

b. Deflection: Flexible piping with deflection that prevents passage of ball or cylinder of size not less than 92.5 percent of piping diameter.

c. Crushed, broken, cracked, or otherwise damaged piping.

d. Infiltration: Water leakage into piping.

e. Exfiltration: Water leakage from or around piping.

3. Replace defective piping using new materials, and repeat inspections until defects are within allowances specified.

4. Reinspect and repeat procedure until results are satisfactory.

B. Test new piping systems, and parts of existing systems that have been altered, extended, or repaired, for leaks and defects.

1. Do not enclose, cover, or put into service before inspection and approval.

2. Test completed piping systems according to authorities having jurisdiction.

3. Schedule tests and inspections by authorities having jurisdiction with at least 24 hours' advance notice.

4. Submit separate report for each test.

5. Gravity-Flow Storm Drainage Piping: Test according to requirements of authorities having jurisdiction, UNI-B-6, and the following:

a. Exception: Piping with soiltight joints unless required by authorities having jurisdiction.

b. Option: Test plastic piping according to ASTM F 1417.

c. Option: Test concrete piping according to ASTM C 924.

C. Leaks and loss in test pressure constitute defects that must be repaired.

D. Replace leaking piping using new materials, and repeat testing until leakage is within allowances specified.

3.15 CLEANING

A. Clean interior of piping of dirt and superfluous materials.

END OF SECTION 334100

334100 - 18 Storm Utility Drainage Piping

PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes gravity-flow, nonpressure storm drainage outside the building, with the following components:
1. Special fittings for expansion and deflection.
2. Cleanouts.
3. Drains.
4. Precast concrete manholes, inlet boxes, catch basins.
5. Cast in place inlet boxes and catch basins and manhole bases over existing pipes.
1.3 DEFINITIONS
A. PVC: Polyvinyl chloride plastic.
B. HDPE: High density polyethylene.
C. CP: Non-reinforced concrete pipe.
D. RCP: Reinforced concrete pipe.
1.4 PERFORMANCE REQUIREMENTS
A. Gravity-Flow, Nonpressure, Drainage-Piping Pressure Rating: 10-foot head of water. Pipe joints shall be at least silttight, unless otherwise indicated.
1.5 SUBMITTALS
A. Product Data: For the following:
1. Special pipe fittings.
2. Drains.
3. Storage.
4. Pipes.
B. Shop Drawings: For the following:
1. design calculations, and concrete design-mix report for cast-in-place manholes.
2. Catch Basins and Stormwater Inlets. Include plans, elevations, sections, details, and frames, covers, and grates.
3. Stormwater Detention Structures: Include plans, elevations, sections, details, frames and covers, design calculations, and concrete design-mix report.
C. Coordination Drawings: Show pipe sizes, locations, and elevations. Show other piping in same trench and clearances from storm drainage system piping. Indicate interface and spatial relationship between manholes, piping, and proximate structures.
D. Profile Drawings: Show system piping in elevation. Draw profiles at horizontal scale of not less than 1 inch equals 50 feet and vertical scale of not less than 1 inch equals 5 feet. Indicate manholes and piping. Show types, sizes, materials, an...
E. Field quality-control test reports.
1.6 DELIVERY, STORAGE, AND HANDLING
A. Do not store plastic manholes, pipe, and fittings in direct sunlight.
B. Protect pipe, pipe fittings, and seals from dirt and damage.
C. Handle manholes according to manufacturer's written rigging instructions.
D. Handle catch basins and stormwater inlets according to manufacturer's written rigging instructions.
1.7 PROJECT CONDITIONS
A. Interruption of Existing Storm Drainage Service: Do not interrupt service to facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary service according to requirement...
1. Notify Architect, Construction Manager, and Owner no fewer than two days in advance of proposed interruption of service. Coordinate interruptions during weekly meetings and at pre-construction meeting.
2. Do not proceed with interruption of service without Architect's, Construction Manager's, and Owner's written permission.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection:
1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include local pre-cast manufacturers but are subject to approval of the engineer and architect.
2.2 PIPING MATERIALS
A. Refer to Part 3 "Piping Applications" Article for applications of pipe, fitting, and joining materials.
2.3 PVC & HDPE PIPE AND FITTINGS
A. HDPE Pressure Pipe: AWWA C906, ASTM D3350, only to be used where specifically noted in plans.
B. PVC Pressure Pipe: AWWA C900, Class 150 for gasketed joints and using ASTM F 477, elastomeric seals.
1. Fittings NPS 4 to NPS 8: PVC pressure fittings complying with AWWA C907, for gasketed joints and using ASTM F 477, elastomeric seals.
2. Fittings NPS 10 and Larger: Ductile-iron, compact fittings complying with AWWA C153, for push-on joints and using AWWA C111, rubber gaskets.
C. PVC Water-Service Pipe and Fittings: ASTM D 1785, Schedule 80 pipe, with plain ends for solvent-cemented joints with ASTM D 2467, Schedule 80, socket-type fittings.
D. PVC Cellular-Core Pipe and Fittings: ASTM F 891, Sewer and Drain Series, PS 50 minimum stiffness pipe with ASTM D 3034, SDR 35, socket-type fittings for solvent-cemented joints.
E. PVC Sewer Pipe and Fittings, NPS 15 and Smaller: ASTM D 3034, SDR 35, with bell-and-spigot ends for gasketed joints with ASTM F 477, elastomeric seals.
F. PVC Sewer Pipe and Fittings, NPS 18 and Larger: ASTM F 679, T 2 wall thickness, with bell-and-spigot ends for gasketed joints with ASTM F 477, elastomeric seals.
G. PVC Profile Gravity Sewer Pipe and Fittings: ASTM F 794 pipe, with bell-and-spigot ends; ASTM D 3034 fittings, with bell ends; and ASTM F 477, elastomeric seals.
2.4 CONCRETE PIPE AND FITTINGS
A. Nonreinforced-Concrete Sewer Pipe and Fittings: ASTM C 14, Class I, II or III, with bell-and-spigot ends and gasketed joints with ASTM C 443, rubber gaskets.
B. Piping in paragraph below is available in 5 classes and 3 wall thicknesses, and in NPS 12 to NPS 144. Not all classes and wall thicknesses are available. Joints are gasket type. Contractor, at his option, may use non-reinforced pipe for sizes up...
C. Reinforced-Concrete Sewer Pipe and Fittings: ASTM C 76, with bell-and-spigot ends and gasketed joints with ASTM C 443, rubber gaskets.
1. Class I
2. Class II
3. Class III
2.5 NONPRESSURE-TYPE PIPE COUPLINGS
A. Comply with ASTM C 1173, elastomeric, sleeve-type, reducing or transition coupling, for joining underground nonpressure piping. Include ends of same sizes as piping to be joined, and corrosion-resistant-metal tension band and tightening mechanism ...
B. Sleeve Materials:
1. For Concrete Pipes: ASTM C 443, rubber.
2. For Cast-Iron Soil Pipes: ASTM C 564, rubber.
3. For Plastic Pipes: ASTM F 477, elastomeric seal or ASTM D 5926, PVC.
4. For Dissimilar Pipes: ASTM D 5926, PVC or other material compatible with pipe materials being joined.
C. Unshielded Flexible Couplings: Elastomeric sleeve with stainless-steel shear ring and corrosion-resistant-metal tension band and tightening mechanism on each end.
1. Manufacturers:
a. Dallas Specialty & Mfg. Co.
b. Fernco Inc.
c. Logan Clay Products Company (The).
d. Mission Rubber Company; a division of MCP Industries, Inc.
e. NDS Inc.
f. Plastic Oddities, Inc.
D. Shielded Flexible Couplings: ASTM C 1460, elastomeric or rubber sleeve with full-length, corrosion-resistant outer shield and corrosion-resistant-metal tension band and tightening mechanism on each end.
1. Manufacturers:
a. Cascade Waterworks Mfg.
b. Dallas Specialty & Mfg. Co.
c. Mission Rubber Company; a division of MCP Industries, Inc.
E. Ring-Type Flexible Couplings: Elastomeric compression seal with dimensions to fit inside bell of larger pipe and for spigot of smaller pipe to fit inside ring.
1. Manufacturers:
a. Fernco Inc.
b. Logan Clay Products Company (The).
c. Mission Rubber Company; a division of MCP Industries, Inc.
2.6 PRESSURE-TYPE PIPE COUPLINGS
A. Reducing or transition, metal, bolted, sleeve-type, reducing or transition coupling, for joining underground pressure piping. Include 150-psig minimum pressure rating and ends of same sizes as piping to be joined.
B. Tubular-Sleeve Couplings: AWWA C219, with center sleeve, gaskets, end rings, and bolt fasteners.
1. Manufacturers:
a. Cascade Waterworks Mfg.
b. Dresser, Inc.; DMD Div.
c. Ford Meter Box Company, Inc. (The); Pipe Products Div.
d. JCM Industries.
e. Romac Industries, Inc.
f. Smith-Blair, Inc.
g. Viking Johnson.
2. Center-Sleeve Material: Manufacturer's standard.
3. Gasket Material: Natural or synthetic rubber.
4. Metal Component Finish: Corrosion-resistant coating or material.
C. Split-Sleeve Couplings: With split sleeve with sealing pad and closure plates, O-ring gaskets, and bolt fasteners.
1. Manufacturers:
a. Brico Industries.
2. Sleeve Material: Manufacturer's standard.
3. Sleeve Dimensions: Of thickness and width required to provide pressure rating.
4. Gasket Material: O-rings made of EPDM rubber, unless otherwise indicated.
5. Metal Component Finish: Corrosion-resistant coating or material.
2.7 SPECIAL PIPE FITTINGS
A. Ductile-Iron Flexible Expansion Joints: Compound fitting with combination of flanged and mechanical-joint ends complying with AWWA C110 or AWWA C153. Include 2 gasketed ball-joint sections and 1 or more gasketed sleeve sections, rated for 250-psi...
1. Manufacturers:
a. EBAA Iron Sales, Inc.
b. Romac Industries, Inc.
c. Star Pipe Products.
B. Ductile-Iron Deflection Fittings: Compound coupling fitting with ball joint, flexing section, gaskets, and restrained-joint ends complying with AWWA C110 or AWWA C153. Include rating for 250-psig minimum working pressure and for up to 15 degrees ...
1. Manufacturers:
a. EBAA Iron Sales, Inc.
C. Ductile-Iron Expansion Joints: Three-piece assembly of telescoping sleeve with gaskets and restrained-type, ductile-iron, bell-and-spigot end sections complying with AWWA C110 or AWWA C153. Include rating for 250-psig minimum working pressure and...
1. Manufacturers:
a. Dresser, Inc.; DMD Div.
b. EBAA Iron Sales, Inc.
c. JCM Industries.
d. Smith-Blair, Inc.
2.8 CLEANOUTS
A. Gray-Iron Cleanouts: ASME A112.36.2M, round, gray-iron housing with clamping device and round, secured, scoriated, gray-iron cover. Include gray-iron ferrule with inside calk or spigot connection and countersunk, tapered-thread, brass closure plug.
1. Manufacturers:
a. Josam Company.
b. MIFAB Manufacturing, Inc.
c. Smith, Jay R. Mfg. Co.
d. Wade Div.; Tyler Pipe.
e. Watts Industries, Inc.
f. Watts Industries, Inc.; Enpoco, Inc. Div.
g. Zurn Industries, Inc.; Zurn Specification Drainage Operation.
2. Top-Loading Classification(s): Light, Medium, Heavy, and Extra-heavy duty depending on location and expected driving load on cleanout.
3. Sewer Pipe Fitting and Riser to Cleanout: ASTM A 74, Service class, cast-iron soil pipe and fittings.
B. PVC Cleanouts: PVC body with PVC threaded plug. Include PVC sewer pipe fitting and riser to cleanout of same material as sewer piping. Place in grey iron housing with clamping device and round, secured, scoriated, gray-iron cover.
1. Manufacturers:
a. Canplas Inc.
b. IPS Corporation.
c. NDS Inc.
d. Plastic Oddities, Inc.
e. Sioux Chief Manufacturing Company, Inc.
f. Zurn Industries, Inc.; Zurn Light Commercial Specialty Plumbing Products.
2.9 DRAINS
A. Gray-Iron Area Drains: ASME A112.21.1M, round body with anchor flange and round secured grate. Include bottom outlet with inside calk or spigot connection, of sizes indicated.
1. Manufacturers:
a. Josam Company.
b. MIFAB Manufacturing, Inc.
c. Smith, Jay R. Mfg. Co.
d. Wade Div.; Tyler Pipe.
e. Watts Industries, Inc.
f. Watts Industries, Inc.; Enpoco, Inc. Div.
g. Zurn Industries, Inc.; Zurn Specification Drainage Operation.

2. Top-Loading Classification(s): Medium and heavy duty depending on location and expected driving load.

B. Gray-Iron Trench Drains: ASME A112.21.1M, 6-inch to 12-inch-wide top surface, rectangular body with anchor flange or other anchoring device, and rectangular secured grate. Include units of total length indicated and number of bottom outlets with ...
1. Manufacturers:
a. Josam Company.
b. Smith, Jay R. Mfg. Co.
c. Wade Div.; Tyler Pipe.
d. Watts Industries, Inc.
e. Watts Industries, Inc.; Enpoco, Inc. Div.
f. Zurn Industries, Inc.; Zurn Specification Drainage Operation.
g. Poly Drain, ABT

2. Top-Loading Classification(s): Medium, heavy, and extra-heavy duty.

2.10 MANHOLES
A. Standard Precast Concrete Manholes: ASTM C 478, precast, reinforced concrete, of depth indicated, with provision for sealant joints.
1. Diameter: 48 inches minimum, unless otherwise indicated and as needed for pipe sizes.
2. Ballast: Increase thickness of precast concrete sections or add concrete to base section, as required to prevent flotation.
3. Base Section: 9-inch minimum thickness for floor slab and 4-inch minimum thickness for walls and base riser section, and having separate base slab or base section with integral floor.
4. Riser Sections: 4-inch minimum thickness, and lengths to provide depth indicated.
5. Top Section: Eccentric-cone type unless concentric-cone or flat-slab-top type is indicated. Top of cone of size that matches grade rings.
6. Joint Sealant: ASTM C 990, bitumen or butyl rubber.
7. Resilient Pipe Connectors: ASTM C 923, cast or fitted into manhole walls, for each pipe connection.
8. Steps: Not used.
9. Adjusting Rings: Interlocking rings with level or sloped edge in thickness and diameter matching manhole frame and cover. Include sealant recommended by ring manufacturer.
10. Grade Rings: Reinforced-concrete rings, 6- to 9-inch total thickness, to match diameter of manhole frame and cover.
11. Manhole Frames and Covers: Ferrous; 24-inch ID by 7- to 9-inch riser with 4-inch- minimum width flange and 26-inch- diameter cover. Include indented top design with lettering cast into cover, using wording equivalent to "STORM SEWER."
a. Material: ASTM A 536, Grade 60-40-18 ductile or ASTM A 48, Class 35 gray iron, unless otherwise indicated and to match existing manhole frames and covers.
b. Protective Coating: Foundry-applied, SSPC-Paint 16, coal-tar, epoxy-polyamide paint; 15-mil minimum thickness applied to all surfaces, unless otherwise indicated.
B. Cast-in-Place Concrete Manholes: Construct of reinforced-concrete bottom, walls, and top; designed according to ASTM C 890 for A-16 (ASSHTO HS20-44), heavy-traffic, structural loading; of depth, shape, dimensions, and appurtenances indicated.
1. Ballast: Increase thickness of concrete, as required to prevent flotation.
2. Resilient Pipe Connectors: ASTM C 923, cast or fitted into manhole walls, for each pipe connection.
3. Steps: Not used.
4. Adjusting Rings: Interlocking rings with level or sloped edge in thickness and diameter matching manhole frame and cover. Include sealant recommended by ring manufacturer.
5. Grade Rings: Reinforced-concrete rings, 6- to 9-inch total thickness, to match diameter of manhole frame and cover.

This is the start of the file's text. The full file is on GovTribe.