This document is a set of electrical construction plans for the North Water Treatment Plant Valve Removal and Replacement project in Fort Worth, Texas, prepared by Freese and Associates engineering firm. The project involves the removal and replacement of motor-operated valves at a terminal storage reservoir, with comprehensive electrical infrastructure modifications including PLC (programmable logic controller) cabinet installation, motor control center (MCC) upgrades, disconnected switch installations, and associated control systems. The plans specify detailed electrical equipment requirements including NEMA 4X stainless steel enclosures for outdoor installations, control schematic designs for butterfly valve operations, equipment racks constructed of 316 stainless steel, and conduit routing systems. The project encompasses site work including concrete pad preparation, ground rod installation, equipment anchoring, and conduit encasement, with specifications for three motor-operated valves (TSR-VALVE 6-01P, 6-02P, and 6-03P) each requiring 30-amp, 3-pole disconnecting switches and associated wiring.

The plans include extensive technical specifications and installation details for electrical components, structural supports, grounding systems, and conduit penetration treatments designed to meet National Electrical Code requirements and withstand corrosive wet environments. All contractor work must comply with Texas811 utility location procedures, requiring notification a minimum of two full working days prior to commencing ground disturbance activities. The document establishes that all equipment removed shall remain the property of the City of Lubbock, with the contractor responsible for proper disposal of materials the city chooses not to retain. Specifications require field verification of existing cable, conduit, and equipment locations prior to demolition, and mandate that replacement MCC buckets match the ampere interrupting capacity rating of existing equipment. Equipment installation must include proper bonding, sealing, and grounding per National Electrical Code standards, with particular attention to moisture protection and corrosion resistance in the water treatment plant environment.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TEXAS811 NOTE:

CONTRACTOR SHALL

CONTACT TEXAS811 BY

DIALING 811 FOR

UTILITY LOCATES NO

LATER THAN TWO FULL

WORKING DAYS PRIOR TO

COMMENCING GRADING/

PAVING/CONSTRUCTION.

REVISIONS

NORTH WATER TREATMENT

PLANT VALVE REMOVAL

AND REPLACEMENT

801 Cherry Street, Suite 2800 Fort Worth, Texas 76102 Phone - (817) 735-7300 Web - www.freese.com

3-B-1751

PREWIRED

HORN

COMBINATION STROBE/HORN

CEILING MOUNTED STROBE

PW

M UTILITY METER

MANHOLEMH

WALL MOUNTED STROBE

SMOKE DETECTOR

HEAT DETECTOR

MOTORIZED LOUVERM

LIGHTING FIXTURE

"A" - FIXTURE TYPE

"b" - SWITCH NUMBER

CONDUIT STUBBED OUT AND CAPPED

3-4"C.

2-2/C#16

JUNCTION BOX

CEILING MOUNTED EXIT SIGN

"X" - FIXTURE TYPE

TIME SWITCH

3 WAY SWITCH

DIMMER LIGHTING CONTROL SWITCH

MULTI POLE SWITCH

"x" - INDICATES NUMBER OF POLE "c" - INDICATES SWITCH SHALL CONTROL LIGHT FIXTURES WITH "c" DESIGNATION

CONDUIT, EXPOSED/SURFACE MOUNTED

CONDUIT, EXPOSED/SURFACE MOUNTED, TURNING UP

CONDUIT, EXPOSED/SURFACE MOUNTED, TURNING DOWN

MANUAL MOTOR STARTER /DISCONNECT

SINGLE POLE SWITCH

"b" - INDICATES SWITCH LEG SHALL CONTROL LIGHT FIXTURES WITH "b" - DESIGNATION

NORMALLY CLOSED

NON-FUSED

NORMALLY OPEN OR NUMBER

NUMBER

OUTSIDE DIAMETER

OVERHEAD ELECTRIC

OVERLOAD

OVERLOAD CONTROL RELAY

POLE

PULL BOX OR PUSH BUTTON

PHOTOCELL

PUMP CONTROL CONSOLE

POWER FACTOR CORRECTION CAPACITOR

PHASE FAILURE RELAY

PHASE

PLATE

PROGRAMMABLE LOGIC CONTROLLER

POWER OVER ETHERNET

PHASE PROTECTIVE RELAY

POWER QUALITY METER

PAIR OR PAIR CABLE

POTENTIAL TRANSFORMER

PUSH TO TEST TYPE

POLYVINYL CHLORIDE

QUANTITY

REMOTE CONTROL

RELAY CONTROL PANEL

CIRCUIT RECLOSURE

RECEPTACLES

REQUIRED

RESISTANCE TEMPERATURE DETECTOR

REMOTE TERMINAL UNIT

SURGE CAPACITOR

SCHEMATIC

SHORT CIRCUIT TERMINAL BLOCK

SECONDS OR SECONDARY

SHIELD OR SHIELDED

SHEET

SOLID NEUTRAL

SURGE PROTECTION DEVICES

SOLID-STATE REDUCED VOLTAGE STARTER

STAINLESS STEEL

STARTER

STATION

SIGNAL TERMINATION CABINET

SOLENOID VALVE

SWITCH

SWITCHGEAR

MOTOR STARTER WITH SIZE

TERMINATION CABINET OR TRAY CABLE

TELEPHONE

TIME DELAY ON OPENING

TRIAD

TEMPERATURE SWITCH

TWISTED

TYPICAL

UNDERGROUND

UNINTERRUPTIBLE POWER SUPPLY

UNSHIELDED TWISTED PAIR CABLE

VOLTS

VARIABLE

VARIABLE FREQUENCY DRIVE

VACUUM FAULT INTERUPTER

VALVE OPERATOR

WITH, WIRE OR WATT

WEATHERPROOF

WEATHER RESISTANT

TRANSFORMER

TRANSMITTER

EXPLOSION PROOF

ALTERNATING CURRENT

AMP FRAME

ADJUSTABLE FREQUENCY DRIVE

ABOVE FINISHED FLOOR OR GRADE

ABOVE GRADE

ABOVE GROUND SPLICE BOX

AMPERES INTERRUPTING CAPACITY

ALUMINUM

AMPERE

AMP TRIP

AUTOMATIC TRANSFER SWITCH

AUTOMATIC

AUXILIARY

AMERICAN WIRE GAUGE

CONDUIT

CIRCUIT BREAKER

CENTER TO CENTER

COMMUNICATION MANHOLE/HANDHOLE

CIRCUIT

CURRENT LIMITING FUSE

CONTINUATION

CONTROL PANEL

CONTROL POWER TRANSFORMER

CONTROL RELAY

CONTROL SWITCH OR COMBINATION STARTER

CURRENT TRANSFORMER

COPPER

DIRECT CURRENT

DOOR INTERLOCK

DIAMETER

DOWN

DIFFERENTIAL PRESSURE

DRAWING

EMPTY CONDUIT

ELECTRICAL MANHOLE

ELECTRICAL

ELEVATION

EMERGENCY

ELECTRICAL MANHOLE/HANDHOLE

ELECTRICALLY OPERATED

ELAPSED TIME METER

ELECTRIC UTILITY CO.

EXISTING

FURNISHED BY OTHERS

FIBER OPTIC

FIBERGLASS REINFORCED POLYESTER

FEET

FUSE

GROUND

GAUGE

GENERATOR CONTROL PANEL

GENERATOR

GROUND FAULT INTERRUPTER

GROUND FAULT SENSING

GATE OPERATOR

GALVANIZED RIGID STEEL

HANDHOLE

HORSEPOWER

HEIGHT

HEAT TRACE PANEL

HEATER

HERTZ

INTERNAL DIAMETER

INSTRUMENT MANHOLE

INSTRUMENT

INTERPOSING RELAY PANEL

JUNCTION BOX

KILO AMPERE INTERRUPTING CAPACITY

KILOVOLT-AMPERE

KILOWATT

LIGHTNING ARRESTER

LIGHTNING CONTACTOR

LIGHT EMITTING DIODE

LIGHTING PANEL

LONG, SHORT, INSTANTANEOUS

LONG, SHORT, INSTANTANEOUS, GROUND

LIGHTS/LIGHTING

MOTOR OPERATED BUTTERFLY VALVE

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MOTOR CIRCUIT PROTECTOR

MANUFACTURER

MANUFACTURER'S

MANHOLE

MULTILIN

MAIN LUGS ONLY

MOTOR OPERATED VALVE

MOTOR PROTECTION RELAY

MULTIRATIO

MOUNTED

MOUNTING

MANUAL TRANSFER SWITCH

AC

AF

AFD

AFF

AG

AGSB

AIC

AL OR ALUM

AMP OR A

AT

ATS

AUTO

AUX

AWG

C.

CB

C/C

CHH

CKT

CLF

CONT.

CP

CPT

CR

CS

CT

CU

DC

DI

DIA

DN

DP

DWG

EC

EHH

ELEC

ELEV

EM

EMH

EO

ETM

EUC

EXIST.

FBO

FO

FRP

FT

FU

G. OR GRND

GA.

GCP

GEN

GFI

GFS

GO

GRS

HH

HP

HT

HTP

HTR

HZ

ID

IMH

INST

IRP

JB

kAIC kVA kW

LA

LC

LED

LP

LSI

LSIG

LTG/LTNG

MBFV

MCB

MCC

MCP

MFR

MFR'S

MH

ML

MLO

MOV

MPR

MR

MTD

MTG

MTS

EMERGENCY BATTERY PACK LIGHT FIXTURE

"A" - FIXTURE TYPE

WALL MOUNTED EXIT SIGN

ARROW INDICATES DIRECTION OF EGRESS

"X" - FIXTURE TYPE

CONDUIT OR DUCT BANK, CONCEALED

FLEXIBLE METAL CONDUIT

LA-1,3

4 WAY SWITCH

DUPLEX RECEPTACLE, 20A, 120V, 2P, 3W

"C" - MOUNTED ABOVE COUNTERTOP

"GFI" OR "GF" - GROUND FAULT INTERRUPTER TYPE

"WP" - WEATHERPROOF

FLOOR MOUNTED RECEPTACLE

SIMPLEX RECEPTACLE, GROUNDED TYPE

QUADPLEX RECEPTACLE

PULL BOX

TERMINAL CABINET

OCCUPANCY SENSOR

PHOTOCELL

OS

PC

TC

PB

INDICATES THAT ALL ELECTRICAL EQUIPMENT AND MATERIALS

INSTALLED WITHIN THE ROOM OR AREA IN WHICH THIS

NOTATION APPEARS SHALL BE OF NEMA 4 CONSTRUCTION

UNLESS OTHERWISE NOTED

CLASS I, DIV.1,

GROUP D

THREE (3) 4" CONDUITS

DENOTES A QUANTITY OF TWO (2) 3" CONDUITS

EACH CONTAINING THREE (3) NO. 3/0 AWG CONDUCTORS

AND ONE (1) NO.2 AWG GROUND CONDUCTOR

INDICATES THAT ALL ELECTRICAL EQUIPMENT AND

MATERIALS INSTALLED WITHIN THE ROOM OR AREA

IN WHICH THIS NOTATION APPEARS SHALL BE OF

NEMA 12 CONSTRUCTION UNLESS OTHERWISE NOTED

INDICATES THAT ALL ELECTRICAL EQUIPMENT AND

MATERIALS INSTALLED WITHIN THE ROOM OR AREA

IN WHICH THIS NOTATION APPEARS SHALL BE OF

NEMA 4X CONSTRUCTION UNLESS OTHERWISE NOTED

DENOTES A QUANTITY OF TWO (2) INSTRUMENT CABLES.

EACH CONSISTS OF TWO (2) NO.16 AWG CONDUCTORS

CABLE TAG FOUR (4) #14 CONTROL OR POWER

CONDUCTORS, ONE (1) #14 GROUND CONDUCTOR. ALL

CONDUCTORS IN A 3/4" CONDUIT. TWO (2) OF THE FOUR (4)

#14 CONTROL OR POWER CONDUCTORS ARE SPARE

2 (3 #3/0, #2G., 3"C.)

INDICATES THAT ALL ELECTRICAL EQUIPMENT AND MATERIALS

INSTALLED WITHIN THE ROOM OR AREA IN WHICH THIS

NOTATION APPEARS SHALL CONFORM TO N.E.C REQUIREMENTS

FOR THE HAZARDOUS AREA CLASSIFICATION SHOWN

NC or N.C.

NF

NO or N.O.

NO.

OD

OHE

OL

OLX

P

PB

PC

PCC

PFCC

PFR

PH

PL.

PLC

PoE

PPR

PQM

PR.

PT

PTT

PVC

QTY

RC

RCP

REC.

RECP

REQ'D

RTD

RTU

SC

SCH

SCTB

SEC

SHLD. OR SH

SHT

SN OR S/N

SPD

SSRVS

SS

ST

STA.

STC

SV

SW

SWGR

Sz#

TC

TEL

TO

TR.

TS

TW

TYP

UG

UPS

UTP

V

VAR.

VFD

VFI

VO

W

WP

WR

XFMR

XMTR

XP

HEAT TRACE

HOMERUN, CIRCUITS 1 AND 3 RUN TO PANEL "LA"

2 #12, #12G., 3/4"C. UNLESS NOTED OTHERWISE

VOLTMETER (WITH SWITCH IF 3-PHASE)

PANEL

AMMETER (WITH SWITCH IF 3-PHASE)

METER

WM - WATTMETER

WHM - WATTHOUR METER

WHDM - WATTHOUR DEMAND METER

WHDR - WATTHOUR DEMAND RECORDER

PF - POWER FACTOR METER

ETM - ELAPSED TIME METER

TRANSDUCER

AX - CURRENT TRANSDUCER

WX - WATT TRANSDUCER

MOTOR, NUMBER DESIGNATES HORSEPOWER

RELAY, NO. AS INDICATED

25 - SYNCHRONISM CHECK RELAY

27 - UNDER VOLTAGE RELAY

38 - BEARING PROTECTIVE DEVICE

40 - LOSS OF EXCITATION RELAY

42 - RUNNING CONTACTOR/PILOT RELAY

46 - REVERSE PHASE/PHASE BALANCE/CURRENT RELAY

47 - PHASE SEQUENCE VOLTAGE RELAY

48 - MACHINE OR TRANSFORMER THERMAL RELAY

50 - INSTANTANEOUS OVERCURRENT RELAY

50G - INSTANTANEOUS GROUND

51 - TIME OVER CURRENT RELAY, GROUNDING RESISTOR TYPE

51N - TIME OVERCURRENT RELAY, RESIDUAL TYPE

51V - TIME OVERCURRENT RELAY WITH VOLTAGE RESTRAINT

59 - OVER VOLTAGE RELAY

60 - NEGATIVE SEQUENCE VOLTAGE RELAY

62 - TIME DELAY RELAY

63 - OVER PRESSURE RELAY

67 - AC DIRECTIONAL OVERCURRENT RELAY

83 - AUTOMATIC SELECTIVE CONTROL OR TRANSFER RELAY

86 - LOCKING-OUT RELAY

87 - DIFFERENTIAL PROTECTIVE RELAY

B - SUFFIX INDICATES "BUS"

G - SUFFIX INDICATES "GENERATOR"

GF - GROUND FAULT

IR - INTERPOSING RELAY

PFR - PHASE FAILURE, PHASE REVERSAL, UNDERVOLTAGE,

OVERVOLTAGE RELAY

ST - SHUNT TRIP

T - SUFFIX INDICATES "TRANSFORMER"

TRP CAP - CAPACITOR TRIP

X - SUFFIX INDICATES "AUXILIARY"

M

X

JJ

OVERHEAD SECONDARY LINE

UNDERGROUND PRIMARY LINE

OVERHEAD PRIMARY LINE

UNDERGROUND ELECTRIC LINE

OVERHEAD ELECTRIC LINEOHE

UGE

UGP

OHP

OHS

UGS UNDERGROUND SECONDARY LINE

UNDERGROUND COMMUNICATION LINEUGC

OHC OVERHEAD COMMUNICATION LINE

OVERHEAD FIBER OPTIC LINEOHFO

UNDERGROUND FIBER OPTIC LINEUGFO

SHEET

RE: X/X-XX

NUMBER

IDENTIFIER

REFERENCE

NUMBER

X

A

NOTE:

THIS IS A STANDARD LEGEND. THEREFORE,

NOT ALL OF THIS INFORMATION MAY BE

USED ON THIS PROJECT.

OR

MANUAL PULL STATION

FIRE ALARM CONTROL PANELFACP

ABBREVIATIONSABBREVIATIONS PLAN SYMBOL DESCRIPTION PLAN SYMBOL DESCRIPTION

ONE-LINE OR

CONTROL DIAGRAM PLAN DESCRIPTION

WET

DAMP

CORROSIVE

SPECIAL RECEPTACLE

MC1-XXX

4 #14, #14G., 3/4"C.

(2 #14 SPARE)

F

X b A

VM

AM

TM

D

TM

D

M

Xc b

F

LOCAL CONTROL STATIONLCS

E-101

LEGEND I

J.O. 125012 C.I.P. #92804.9241.30000

DESIGNED BY: BAM

DRAWN BY: JTR

CHECKED BY: JNH

DATE: 4/4/25

6/26/2025

3 POSITION SELECTOR SWITCH, MAINTAINED CONTACT

O-OPEN X-CLOSED

OFF/ON SELECTOR SWITCH

EMERGENCY STOP PUSH BUTTON WITH RED MUSHROOM

HEAD OPERATOR (MAINTAINED CONTACT)

PUSH BUTTON, MOMENTARY CONTACT, SPRING RETURN,

NORMALLY CLOSED

SPECIAL CAPACITOR

SC - SURGE CAPACITOR

PF - POWER FACTOR CORRECTION CAPACITOR

TERMINAL OR TEST BLOCK

FUSE, AMPERE RATING AS NOTED

CONTACT, NORMALLY OPEN (NO)

CONTACT, NORMALLY CLOSED (NC)

LIGHTNING ARRESTER

FIELD INSTRUMENT, TAG NO. OR LOOP NO. AS INDICATED

- INDICATES INSTRUMENT TYPE DEFINED ON LOOP SHEETS

## - INDICATES LOOP NO.

AC INDUSTRIAL

CONTROL RELAY COIL, # - NUMBER AS INDICATED

MOTOR STARTER COIL, # - NUMBER AS INDICATED

INDICATING LAMP, COLOR INDICATED

R - RED

G - GREEN

B - BLUE

W - WHITE

A - AMBER

O - ORANGE

PTT - PUSH TO TEST

PUSH BUTTON STATION, REFER TO ELECTRICAL SCHEMATIC

FOR NUMBER OF DEVICES.

INDICATES LIMITS OF EQUIPMENT OR WIRING ENCLOSURE

HEATER

TERMINAL

NODE

MECHANICAL INTERLOCK

LOCATED REMOTE

LOCATED AT MOTOR

LOCATED AT SCADA RTU

(A/B/C)

HOA - HAND/OFF/AUTO

HOR - HAND/OFF/REMOTE

LOR - LOCAL/OFF/REMOTE

OCS - OPEN/CLOSE/STOP

OOA - ON/OFF/AUTO

NOTE:

2 POSITION MULTI-CONTACT SWITCH

FOLLOWS SAME CONVENTION

TIMING RELAY

RANGE AS NOTED, SET POINT AS NOTED

#-NUMBER AS INDICATED

TDD-TIME DELAY AFTER DE-ENERGIZATION-OFF DELAY

TDE-TIME DELAY AFTER ENERGIZATION-ON DELAY

NOTC-NORMALLY OPEN, TIMED CLOSING WHEN ENERGIZED

NCTO-NORMALLY CLOSED, TIMED OPENING WHEN ENERGIZED

NOTO-NORMALLY OPEN, TIMED OPENING WHEN DE-ENERGIZED

NCTC-NORMALLY CLOSED, TIMED CLOSING WHEN DE-ENERGIZED

LIQUID LEVEL (FLOAT) SWITCH

NORMALLY CLOSED, OPENS ON FALLING LEVEL

NORMALLY OPEN, CLOSES ON FALLING LEVEL

NORMALLY CLOSED, OPENS ON RISING LEVEL

NORMALLY OPEN, CLOSES ON RISING LEVEL

TEMPERATURE SWITCH OR THERMOSTAT

NORMALLY OPEN, CLOSES ON RISING TEMPERATURE

NORMALLY OPEN, CLOSES ON DROPPING TEMPERATURE

NORMALLY CLOSED, OPENS ON RISING TEMPERATURE

NORMALLY CLOSED, OPENS ON DROPPING TEMPERATURE

CONDUCTORS ELECTRICALLY CONNECTED

GROUND ROD

GROUND ROD TEST WELL

INDUCTOR

OVERLOAD CONTACT

KIRK KEY INTERLOCK

CONDUCTORS OR CONDUITS CROSSING PATHS BUT NOT

CONNECTED

PRESSURE OR VACUUM SWITCH

NORMALLY OPEN, CLOSES ON RISING PRESSURE

NORMALLY CLOSED, OPENS ON RISING PRESSURE

NORMALLY OPEN, CLOSES ON DROPPING PRESSURE

NORMALLY CLOSED, OPENS ON DROPPING PRESSURE

FLOW SWITCH (AIR, WATER, ETC.)

NORMALLY OPEN, CLOSES ON INCREASED FLOW

NORMALLY CLOSED, OPENS ON INCREASED FLOW

POSITION (LIMIT) SWITCH

NORMALLY OPEN

NORMALLY OPEN - HELD CLOSED

NORMALLY CLOSED

NORMALLY CLOSED - HELD OPEN

TORQUE SWITCH NORMALLY CLOSED, OPENS ON HIGH TORQUE

MEDIUM VOLTAGE FUSED MOTOR CONTROLLER

FUSED CONTACTOR DRAWOUT TYPE

FUSIBLE DISCONNECT SWITCH, 600 VOLT, 3 POLE,

AMPERE RATING AND FUSE SIZE AS NOTED

AMPERE RATING NOTED

FUSE RATING

NON-FUSIBLE DISCONNECT SWITCH, 600 VOLT, 3 POLE

AMPERE RATING NOTED

LOW VOLTAGE CIRCUIT BREAKER, 3 POLE

UNLESS OTHERWISE NOTED

A - AMP TRIP, P - POLES

VACUUM CONTACTOR

SPEED POTENTIOMETER

MOTOR CIRCUIT PROTECTOR

MEDIUM VOLTAGE DRAWOUT TYPE

POWER CIRCUIT BREAKER

COMBINATION MOTOR CIRCUIT PROTECTOR AND MAGNETIC MOTOR

STARTER, FULL VOLTAGE NON-REVERSING UNLESS OTHERWISE NOTED:

FVR - FULL VOLTAGE REVERSING

FVNR - FULL VOLTAGE, NON REVERSING

RVNR - REDUCED VOLTAGE NON-REVERSING

2S1W - TWO SPEED, ONE WINDING

2S2W - TWO SPEED, TWO WINDING

Sz# - NEMA SIZE OF STARTER

GENERATOR, RATINGS AND CONNECTIONS AS NOTED

TRANSFORMER, RATINGS AND CONNECTIONS AS NOTED

CURRENT TRANSFORMER

# - QUANTITY

A - RATIO

POTENTIAL TRANSFORMER

# - QUANTITY

TRANSFER SWITCH

ATS - AUTOMATIC TRANSFER SWITCH

MTS - MANUAL TRANSFER SWITCH

"N" - INDICATES NORMAL SOURCE

"S" - INDICATES STANDBY SOURCE

#A - INDICATES CONTINUOUS CURRENT RATING

CONTROL POWER TRANSFORMER

GROUND CURRENT SENSOR TRANSFORMER

# - QUANTITY

A - RATIO

CONTROL TRANSFORMER

MOTOR OVERLOAD

OVERLOAD RELAY HEATER

OR

FUSED SWITCH/FUSED CUTOUT

NOTE:

THIS IS A STANDARD LEGEND. THEREFORE,

NOT ALL OF THIS INFORMATION MAY BE

USED ON THIS PROJECT.

COMBINATION TELEPHONE/DATA

TELEPHONE

DATA

FLOOR MOUNTED DATA OUTLET

FLOOR MOUNTED TELEPHONE OUTLET

CATV

FLOOR COMBINATION POWER/DATA/VOICE OUTLET

SECURITY DEVICE

SEC - SECURITY PANEL

MAG - MAGNETIC LOCK

CR - CARD READERS

DR - REMOTE DOOR RELEASE

MD - MOTION DETECTOR

SK - SECURITY KEYPAD

ES - ELECTRIC STRIKE

DS - DOOR SWITCH

IC - INTERCOM STATION

SB - SECURITY PANIC BUTTON

UTILITY METER

PUSH BUTTON, MOMENTARY CONTACT, SPRING RETURN,

NORMALLY OPEN

POSITION CONTACT

TOP MIDDLE

CONTACT

BOTTOM

CONTACT

XO0C

OO0B

OOXA

DRAWOUT TYPE EQUIPMENT OR DEVICE

MEDIUM VOLTAGE CABLE TERMINATION

MEDIUM VOLTAGE AIR INTERRUPTER SWITCH

MEDIUM VOLTAGE FUSED AIR INTERRUPTER SWITCH

#A

ATS-1

N S

OR

OR

OR

OR

OR

OR

T

SECURITY CAMERA

F - FIXED

Z - PAN/TILT/ZOOM

POKE-THRU DEVICE

COMBINATION POWER/DATA/VOICE OUTLET

ONE-LINE OR

CONTROL DIAGRAM PLAN DESCRIPTION ONE-LINE OR

CONTROL DIAGRAM PLAN DESCRIPTION SYMBOL DESCRIPTION

ONE-LINE OR

CONTROL DIAGRAM PLAN DESCRIPTION

CB

OR

30A

OR K

TR#

Sz#

MCP

MCP

A P

AF

AT

PTT

A B

C

X00

00X

OFF ON

M#

CR#

VAC

G

A

#CT'S

#PT'S

#CT'S

A

TQ

ZS

FS

TS

T

PS

M M

TB

OL

LA

G

TEXAS811 NOTE:

CONTRACTOR SHALL

CONTACT TEXAS811 BY

DIALING 811 FOR

UTILITY LOCATES NO

LATER THAN TWO FULL

WORKING DAYS PRIOR TO

COMMENCING GRADING/

PAVING/CONSTRUCTION.

REVISIONS

NORTH WATER TREATMENT

PLANT VALVE REMOVAL

AND REPLACEMENT

801 Cherry Street, Suite 2800 Fort Worth, Texas 76102 Phone - (817) 735-7300 Web - www.freese.com

3-B-1751

E-102

LEGEND

II

J.O. 125012 C.I.P. #92804.9241.30000

DESIGNED BY: BAM

DRAWN BY: JTR

CHECKED BY: JNH

TSR-LSH-01C

NEW MOTOR

ACTUATOR VALVE

RE: 8/E-107

ELECTRICAL

BUILDING

TSR-VALVE 6-01P

TSR-VALVE 6-02P

MCC2 PROPOSED PLC

CABINET

TSR-VALVE-6-01C

EQUIPMENT RACK

RE: 2/E-106

SITE PLAN

1" = 20'

SCALE IN FEET

0 40'20'

NORTH

TEXAS811 NOTE:

CONTRACTOR SHALL

CONTACT TEXAS811 BY

DIALING 811 FOR

UTILITY LOCATES NO

LATER THAN TWO FULL

WORKING DAYS PRIOR TO

COMMENCING GRADING/

PAVING/CONSTRUCTION.

REVISIONS

NORTH WATER TREATMENT

PLANT VALVE REMOVAL

AND REPLACEMENT

801 Cherry Street, Suite 2800 Fort Worth, Texas 76102 Phone - (817) 735-7300 Web - www.freese.com

3-B-1751

J.O. 125012 C.I.P. #92804.9241.30000

DESIGNED BY: BAM

DRAWN BY: JTR

CHECKED BY: JNH

DATE: 4/4/25

E-103

GENERAL NOTES:

1. THIS SHEET IS TO BE USED FOR REFERENCE ONLY. CONTRACTOR TO FIELD

VERIFY EQUIPMENT'S CURRENT AND FINAL LOCATIONS.

2. EQUIPMENT AND BOXES INSTALLED OUTDOORS SHALL BE NEMA 4X STAINLESS

STEEL.

SITE PLAN

MCC DEMOLITION PHOTO

NOT TO SCALE

PLC DEMOLITION PHOTO

NOT TO SCALE

PARTIAL DEMOLITION

ONE-LINE DIAGRAM

NOT TO SCALE

"MCC2 480V, 600A, 25KAIC"

20A 3P

LIGHTING

CONTACTOR

TEXAS811 NOTE:

CONTRACTOR SHALL

CONTACT TEXAS811 BY

DIALING 811 FOR

UTILITY LOCATES NO

LATER THAN TWO FULL

WORKING DAYS PRIOR TO

COMMENCING GRADING/

PAVING/CONSTRUCTION.

REVISIONS

NORTH WATER TREATMENT

PLANT VALVE REMOVAL

AND REPLACEMENT

801 Cherry Street, Suite 2800 Fort Worth, Texas 76102 Phone - (817) 735-7300 Web - www.freese.com

3-B-1751

E-104

GENERAL NOTES:

1. EXISTING IS SHOWN AS LIGHT. DEMOLITION ASSOCIATED WITH THIS

CONTRACT IS SHOWN AS HATCHED.

2. THE CONTRACTOR SHALL USE CARE AS TO NOT DAMAGE EXISTING

EQUIPMENT TO REMAIN WHILE REMOVING OTHER PIECES OF EQUIPMENT.

ALL EQUIPMENT TO BE REMOVED SHALL REMAIN THE PROPERTY OF THE CITY

OF LUBBOCK. ALL MATERIALS AND EQUIPMENT THAT THE CITY OF LUBBOCK

CHOOSES NOT TO KEEP SHALL BECOME THE PROPERTY OF THE CONTRACTOR

AND SHALL BE REMOVED FROM SITE. THE CONTRACTOR SHALL PROPERLY

DISPOSE OF ALL EQUIPMENT OFF SITE AND IN ACCORDANCE WITH ALL

APPLICABLE CODES. REFER TO SECTION 26 05 10, "ELECTRICAL DEMOLITION"

FOR ADDITIONAL INFORMATION.

3. CONTRACTOR SHALL FIELD VERIFY LOCATION AND FUNCTIONALITY OF ALL

CABLES, CONDUITS, AND EQUIPMENT TO BE DEMOLISHED PRIOR TO

BEGINNING DEMOLITION.

4. FOR ALL ITEMS BEING DEMOLISHED, REMOVE AND DISPOSE OF ALL

ASSOCIATED CONDUCTORS AND EXPOSED CONDUITS TO SOURCE UNLESS

OTHERWISE STATED.

NOTES BY SYMBOL " "

1. CONTRACTOR TO EXTEND CABLE AND CONDUIT AS NEEDED FOR INSTALLATION

OF PROPOSED PLC CABINET.

DEMOLITION PHOTOS

& ONE- LINE DIAGRAM

J.O. 125012 C.I.P. #92804.9241.30000

DESIGNED BY: BAM

DRAWN BY: JTR

CHECKED BY: JNH

PARTIAL

ONE-LINE DIAGRAM

NOT TO SCALE

"MCC2 480V, 600A, 25KAIC"

20A 3P

SPARE

30A 3P

TS

R-

VA

LV

E 6-

P

3#

G.

, 2

"C

30A 3P

NF

TS

R-

VA

LV

E 6-

P

#1

0, G.

, 1 "C

1 1

MOTOR

OPERATOR

TS

R-

VA

LV

E 6-

P

3#

G.

, 2

"C

30A 3P

30AF

LOOP EQUIPMENT DESCRIPTION FIELD DEVICE/FIELD WIRING

INTERCONNECTION DIAGRAM

PL

C

TSR-VALVE 6

TSR-VALVE 6-01C

24 #14, #14G., 3/4"C.

(4 #14 SPARE)

MOV 6

VALVE VAULT FLOAT TSR-LSH MANUFACTURER

SUPPLIED CABLE

JUNCTION

BOX

J TSR-LSH-01C

4 #14, #14G., 2"C.

TSR-LSH-01C

28 #14, #14G., 2"C.

(4 #14 SPARE)

TSR-VALVE 6-01C 6

TEXAS811 NOTE:

CONTRACTOR SHALL

CONTACT TEXAS811 BY

DIALING 811 FOR

UTILITY LOCATES NO

LATER THAN TWO FULL

WORKING DAYS PRIOR TO

COMMENCING GRADING/

PAVING/CONSTRUCTION.

REVISIONS

NORTH WATER TREATMENT

PLANT VALVE REMOVAL

AND REPLACEMENT

801 Cherry Street, Suite 2800 Fort Worth, Texas 76102 Phone - (817) 735-7300 Web - www.freese.com

3-B-1751

E-105

INTERIOR PHOTO

NOT TO SCALE

INTERIOR PHOTO

NOT TO SCALE

INTERIOR PHOTO

NOT TO SCALE

EXTERIOR PHOTO

NOT TO SCALE

PROPOSED

NEW PLC

CABINET

RE: 4/E-105

FOR

CONTINUATION

RE: 3/E-105

FOR

CONTINUATION

RE: E-103 FOR

CONTINUATION

NOTES BY SYMBOL " "

1. CONTRACTOR SHALL PROVIDE REPLACEMENT MCC BUCKET THAT CONSISTS OF

2 SIDE BY SIDE BREAKERS. THE AIC RATING OF THE NEW MCC BREAKERS SHALL

MATCH THAT OF THE EXISTING.

2. CONDUIT CORRESPONDS TO CABLE TAG TSR-VALVE 6-01C AND TSR-VALVE

6-02C. CONDUIT PATH MOVES THROUGH E-105/2 TO E-105/5 IN SEQUENTIAL

ORDER.

3. CONDUIT CORRESPONDS TO CABLE TAG TSR-VALVE 6-01P. CONDUIT PATH

MOVES THROUGH E-105/2 TO E-105/5 IN SEQUENTIAL ORDER.

4. EQUIPMENT TO BE RACK MOUNTED AT MOV.

5. CONTRACTOR TO SAW CUT, REPLACE, AND MATCH EXISTING SIDE WALK AS

NEEDED.

6. UTILIZE THE SAME 2"C. FOR CONTROLS RUN FROM JUNCTION BOX TO PLC.

7. EQUIPMENT TO BE LOCATED WITHIN VALVE VAULT.

ONE-LINE DIAGRAM,

INTERCONNECTION

DIAGRAM, & PHOTOS

J.O. 125012 C.I.P. #92804.9241.30000

DESIGNED BY: BAM

DRAWN BY: JTR

CHECKED BY: JNH

BUTTERFLY VALVE

CONTROL SCHEMATIC

NOT TO SCALE

- (FOR TSR-VALVE 6)

MOTOR OPERATED

C

O

3OL'S

O

C

G

CLOSED

R

OPEN

LSO

TSCLSC

C

O

INST.

LSO

LSC

TSO

THERMAL

SWITCH

MOTOR

REMOTE

CLOSE

REMOTE

OPEN

CVLS4

VALVE

100%

OPEN

OVLS5

VALVE

OPEN

STATUS

LS2

LS1

VALVE CLOSED

VALVE 5% OPEN

VALVE CLOSED

VALVE 100% OPEN

LIMIT SWITCH POSITIONS

VALVE POSITION

SWITCH

NUMBERS

LIMIT

OPEN

LIMIT

CLOSE INTERMEDIATE FUNCTION

CVLS-1

PERCENT OPEN0% 95% 100%50%

NOTES:

1. INDICATES OPEN CONTACTS.

2. INDICATES CLOSED CONTACTS.

480VAC

120VAC

PROPOSED PLC CABINET

REMOTE

MODE

INDICATION

00X

CVLS1

VALVE

CLOSED

VALVE OPEN

25%

SPACE HEATER

CLOSESTOP

OPEN

FROM PROPOSED

PLC CABINET

NO.1 GENERAL NOTES:

1. THE CONTROLS SCHEMATIC SHOWING SHALL BE INCORPORATED INTO MBFV

CONTROLS MBFV SUPPLIER.

2. EQUIPMENT SHOWN WITH A DASHED BOX IS NOT PROVIDED BY MBFV SUPPLIER.

OVLS-2

CVLS-3

CVLS-4

OVLS-5

6" SLAB W/#4 @ 1'-0"C/C EW.

EXTEND 1'-0" BEHIND & 4'-0"

IN FRONT OF SUPPORT POSTS

NO.2 GENERAL NOTES:

1. ALL MEMBERS SHOWN AND REQUIRED CONNECTING HARDWARE SHALL BE 316

STAINLESS STEEL.

2. MEMBERS ARE INDICATED BY UNISTRUT PART NUMBERS. PROVIDE ALL MEMBERS

AND CONNECTING HARDWARE BY UNISTRUT OR APPROVED EQUAL.

3. SLOPE SLAB-ON-GRADE TO DRAIN.

4. RACKS SHALL BE GROUNDED PER THE NATIONAL ELECTRICAL CODE. PROVIDE AS A

MINIMUM ONE 3/4"x10'-0" COPPER CLAD GROUND ROD ON EACH SIDE OF THE

ELECTRICAL EQUIPMENT RACK.

5. ALL NUTS, BOLTS, WASHERS, OTHER FASTENERS AND HARDWARE ON ELECTRICAL

EQUIPMENT RACK SHALL BE 316 STAINLESS STEEL.

6. PROVIDE TWO (2) 9/16"DIA BOLT HOLES IN OUTSTANDING LEG OF L3x3 CLIP ANGLE

OF ATTACHMENT OF UNISTRUT P1359 BRACKET.

7. PROVIDE AN ADDITIONAL 316 STAINLESS STEEL JUNCTION BOX WHERE NECESSARY

TO DISTRIBUTE POWER CONDUCTORS TO MULTIPLE DISCONNECT SWITCHES.

CONTROL AND POWER CONDUCTORS SHALL BE ROUTED IN SEPARATE BOXES.

P1359 BRACKET

MOUNTED TO

L3x3x1/4"x0'-4" CLIP

P1001C CHANNEL

3"x3"x1/4" POST

1' -6

"M

AX

1/4" CAP PLATE

5' -0

6"

3' -6

6"

1' -6

" M

AX

1'-0" 5'-0"MAX 1'-0"

CONCRETE PIER

DISCONNECT

SWITCH

15"MIN

PVC COATED CONDUIT (TYP)

RIGID CONDUIT (TYP)

#8 AWG GROUND

EXOTHERMIC WELD

3/4"DIA x 10'-0" COPPER

CLAD STEEL GROUND ROD

NO.2 NOTES BY SYMBOL " "

1. PROVIDE A 30A/3P/FUSED DISCONNECT SWITCH IN A NEMA 4X 316 STAINLESS STEEL

ENCLOSURE FOR EACH MOTOR OPERATED VALVE.

2. PROVIDE LIGHT SWITCH WITH WP COVER FOR FIXTURE LOCATED WITHIN VALVE VAULT.

PROVIDE 2#12, #12G., 1"C. FROM PANELBOARD ELECTRICAL BUILDING. ROUTE CONDUIT TO

LIGHT FIXTURE IN VALVE VAULT. RE: 8/E-107.

3. PROVIDE A NEMA 4X, 316 STAINLESS STEEL JUNCTION BOX FOR CONTROL WIRING.

ELECTRICAL EQUIPMENT RACK DETAIL

NOT TO SCALE

TO

V

AL

VE

TO

R

TU

TO

V

AL

VE

TO

M

CC

TO

P

AN

EL

BO

AR

D

TO

L

EV

EL

S W

IT

CH

TEXAS811 NOTE:

CONTRACTOR SHALL

CONTACT TEXAS811 BY

DIALING 811 FOR

UTILITY LOCATES NO

LATER THAN TWO FULL

WORKING DAYS PRIOR TO

COMMENCING GRADING/

PAVING/CONSTRUCTION.

REVISIONS

NORTH WATER TREATMENT

PLANT VALVE REMOVAL

AND REPLACEMENT

801 Cherry Street, Suite 2800 Fort Worth, Texas 76102 Phone - (817) 735-7300 Web - www.freese.com

3-B-1751

E-106

CONTROL SCHEMATIC,

DETAIL, & LIGHT

FIXTURE SCHEDULE

J.O. 125012 C.I.P. #92804.9241.30000

DESIGNED BY: BAM

DRAWN BY: JTR

CHECKED BY: JNH

NO.7 NOTES BY SYMBOL " "

1. SEAL ALL CONDUITS ENTERING ENCLOSURES WITH

REMOVABLE SILICON CAULK.

BOND ALL CONDUITS TO

EQUIPMENT GROUND BUS WITH

ALUMINUM #4 AWG BONDING

JUMPER (SIZE PER NEC)

REMOVE NUT, CUT BOLT FLUSH

AND PLUG WELD TO STEEL PRIOR

TO SETTING EQUIPMENT (TYP)

FULL LENGTH 4" SS CHANNELS LAIN

LEVEL ALONG ENTIRE LENGTH AND

WITH EACH OTHER, DRILL AND TAP

FOR EQUIPMENT ANCHOR BOLTS

STRUCTURAL FLOOR

FINISH FLOOR

1/2" HILTI EPOXY ANCHOR BOLTS AT

2'-0" O/C WITH LEVELING NUTS (TYP)

TYPICAL FREE STANDING

EQUIPMENT, PROVIDE

MID-SUPPORT WHERE

REQUIRED BY MANUFACTURE

INSULATED BUSHING

WITH GROUND LUG (TYP)

EQUIPMENT CHANNEL

4" HIGH CONCRETE PAD WITH

1" CHAMFER ALL AROUND

BOX OUT CONCRETE AS

REQ'D. FILL VOIDS WITH

FIRE RETARDANT FILLER

AFTER CONDUIT

INSTALLATION IS COMPLETE

EQUIPMENT PAD DETAIL

NOT TO SCALE

CAULK ALL AROUND

W/SEALANT PRIOR TO

INSTALLING BUSHING

FILL VOID WITH

"CHASE FOAM" AFTER

INSTALLATION

CORE DRILLED HOLEFLANGED TYPE

SEALING BUSHING

CONDUIT

CONCRETE WALL

OR FOUNDATION

STRUCTURES ABOVE OR BELOW GRADE

WATERTIGHT CONDUIT PENETRATION

NOT TO SCALE

3" 6"

JUNCTION BOX MOUNTED

AS HIGH AS POSSIBLE 3

NO.1 NOTES BY SYMBOL " "

1. SEAL ALL CONDUITS ENTERING ENCLOSURES WITH REMOVABLE

SILICON CAULK.

2. APPLY RUBBER ELECTRICAL TAPE TO ALL EXPOSED METAL CONDUIT

OR CONDUIT THREADS. EXTEND TAPE A MINIMUM 2" IN BOTH

DIRECTIONS BEYOND EXPOSED CONDUIT.

3. ALLOW MINIMUM OF 12" OF WIRES SLACK IN JUNCTION BOX TO

ACCOMMODATE EXPANSION JOINT.

ABOVE GRADE CONDUIT TERMINATION

NOT TO SCALE

REFER TO APPLICABLE

WALL PENETRATION

DETAILS, THIS SHEET

CONCRETE SLOPED AWAY

FROM BUILDING, 1"

CHAMFER ALL AROUND

CONCRETE ENCASEMENT AS

INDICATED ON PLANS

ALUM CONDUIT

ALUM EXPANSION FITTING

PVC COATED CONDUIT

COUPLING. TAPE

TRANSITION AT EACH END

WITH 1/2 LAPPED TO 3"

BEYOND TRANSITION (TYP)

SCHEDULE

40 PVC

COMPRESSIBLE

JOINT FILLER

EXISTING/NEW

FOOTING OR

FOUNDATION

PVC COATED

ALUMINUM CONDUIT

PVC COATED ALUM

LONG SWEEP ELBOW

PVC COATED

ALUMINUM CONDUIT

SCHEDULE 40 PVC CONDUIT

(TYP)

#4 CONTINUOUS REBAR @

EACH REBAR HOLE IN SPACER

(MIN OF FOUR (4), TYP)

#4 STIRRUP @ 1'-6"C/C MAX

SPACERS @ 8'-0"O/C (TYP)

BACKFILL & COMPACT

W/SELECT MATERIAL

3000 PSI CONCRETE

ENCASEMENT

FINISHED GRADE

LOCATION TAPE

(1'-0" BELOW GRADE)

4"

4" M

IN

1'

-6 "M

IN

NO.2 NOTES BY SYMBOL " "

1. SELECT BACKFILL TO BE CLASS 4 EARTH FILL. FILL SHALL CONSIST OF

MATERIALS WHICH ARE CLASSIFIED AS SP, SM, SC, CL OR DUAL

CLASSIFICATIONS THEREOF, WHICH HAVE A LIQUID LIMIT LESS THAN

OR EQUAL TO 35 AND A PLASTICITY INDEX OF A MINIMUM OF 4 AND

A MAXIMUM OF 15, WHICH ARE FREE OF ORGANIC MATERIALS.

NO.2 GENERAL NOTES:

1. CONTRACTOR SHALL PROVIDE CHAIRS FOR REBAR ROUTED ALONG

BOTTOM OF DUCT BANK TO VERIFY THAT REBAR IS FULLY ENCASED

WITH 4" OF CONCRETE.

2. CONTRACTOR TO BOND GROUNDING CONDUCTOR AT EQUIPMENT

RACK AND MAIN GROUNDING SYSTEM AT ELECTRICAL BUILDING

CONCRETE ENCASED

DUCT BANK DETAIL

NOT TO SCALE

8" M

IN

#4 REBAR DRIVEN INTO SOLID

EARTH FOR ANCHOR (TYP)

#4/0 BARE TINNED COPPER

GROUND

WALL PENETRATION

NOT TO SCALE

PVC COATED CONDUIT

316 SS

CONDUIT CLAMP

316 SS

CHANNEL STRUT

FILL SPACE BETWEEN

CONDUIT & HOLE

W/NON-SHRINK GROUT

1' -0

"M

IN

2' -0

"M

AX

FLOOR

LB FITTING (TYP)

TO EQUIPMENT

RIGID CONDUIT

6" M

IN

PVC COATED CONDUIT

COUPLING. TAPE

TRANSITION AT EACH END

WITH 1/2 LAPPED TO 3"

BEYOND TRANSITION (TYP)

EXPANSION FITTING

PVC COATED CONDUIT

SCHEDULE 40 PVC

2 1/2" 100MILS NEOPRENE

BUSHING (TYP)

316 SS UNISTRUT CHANNEL

CONDUIT

(TYP)1

NO.6 NOTES BY SYMBOL " "

1. ANCHORS SHALL BE 1/2"DIA ADHESIVE STAINLESS STEEL.

316 SS CLAMP

(SIZE AS REQUIRED)

CEILING OR WALL EXPOSED

CONDUIT INSTALLATION

NOT TO SCALE

AASHTO HS-20

TRAFFIC RATED

BROOKS OR EQUAL

AASHTO HS-20

TRAFFIC RATED COVER

LOW VOLTAGE

PULL BOX

NOT TO SCALE

NO.5 GENERAL NOTES:

1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR

SIZING AND PROVIDING ALL PULL BOXES AS

REQUIRED BY THE NATIONAL ELECTRICAL CODE.

NO.8 NOTES BY SYMBOL " "

1. PROVIDE CONTEGRA FS-202 LEVEL FLOAT SWITCH. MOUNT TO

ACTIVATE SWITCH AT 6" AFF. ROUTE MANUFACTURE SUPPLIED

CABLE TO JUNCTION BOX IN VAULT. MOUNT JUNCTION BOX AT

LEAST 4'-0 AFF.

2. PROVIDE NEMA 4X 316 SS JUNCTION BOX FOR CONTROL

WIRING.

3. PROVIDE 30A/3P/NF NEMA 4X 316 SS DISCONNECT SWITCH TO

BE MOUNTED AT LEAST 4'-0 AFF AS TO NOT INTERFERE WITH

PERSONNEL CLIMBING ACCESS LADDER.

4. PROVIDE LIGHT FIXTURE A FROM LIGHTING FIXTURE SCHEDLE.

MOUNT FIXTURE AT 9'-0" AFF. PROVIDE 2#12, #12G., 1"C. ROUTE

CONDUIT TO SWITCH ON DISCONNECT RACK ABOVE GRADE. RE:

2/E-106

LIGHT

FIXTURE4

DISCONNECT

SWITCH

TSR-LSH

VAULT DETAIL

NOT TO SCALE

J2

TEXAS811 NOTE:

CONTRACTOR SHALL

CONTACT TEXAS811 BY

DIALING 811 FOR

UTILITY LOCATES NO

LATER THAN TWO FULL

WORKING DAYS PRIOR TO

COMMENCING GRADING/

PAVING/CONSTRUCTION.

REVISIONS

NORTH WATER TREATMENT

PLANT VALVE REMOVAL

AND REPLACEMENT

801 Cherry Street, Suite 2800 Fort Worth, Texas 76102 Phone - (817) 735-7300 Web - www.freese.com

3-B-1751

E-107

DETAILS

J.O. 125012 C.I.P. #92804.9241.30000

DESIGNED BY: BAM

DRAWN BY: JTR

CHECKED BY: JNH

3-B-1751 COL
FNI 6-26-2025