1-Division-26 - Electrical.pdf

PDF 297 KB Posted

Attached to
West Chester Pike Sewer Extension
Solicitation number
Not on record
Issued by
Chester County, Pennsylvania

About this file

Summary

This is a specification document package for the Willistown Township Police Building HVAC System Replacement project, a public works construction project located in Pennsylvania. The specifications detail comprehensive electrical systems requirements across multiple divisions including basic electrical materials and methods, selective demolition, low-voltage power conductors and cables, control-voltage cabling, grounding and bonding systems, hangers and supports, conduit systems, boxes, identification systems, wiring devices, and enclosed switches. The project involves replacing and upgrading the existing HVAC system at the police building. Sealed bids are being received online via PennBID until April 21, 2026, at 1:00 PM local time. All bidding documents are available through the designated PennBID website at https://pennbid.net/, where addenda and other project information will be posted. No specific site visit or bidders' conference dates are identified in the specifications, though bidders should review all addenda posted to the website prior to submission.

Each bid must be accompanied by a bid bond in the amount of not less than ten percent of the total bid amount. The successful bidder will be required to provide a Performance Bond and Payment Bond equal to one hundred percent of the contract price, along with necessary insurance documentation. All bidders must complete an anti-collusion affidavit. This contract is subject to the Pennsylvania Prevailing Wage Act, requiring contractors to pay workers the minimum wage rates established by the Pennsylvania Secretary of Labor. The specifications reference NFPA 70 (National Electrical Code), NECA standards, UL listings, and various other industry standards for installation and quality assurance. No specific budget amount, incumbent vendor information, or contract term details are provided in the electrical specifications section.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Willistown Township PD Bldg.

HVAC System Replacement 260010 - 1 Basic Electrical Materials and

Methods

SECTION 260010

BASIC ELECTRICAL MATERIALS AND METHODS

PART 1 GENERAL

1.01 SUMMARY

A. Section includes the following:

1. Electrical equipment coordination and installation.

2. Common electrical installation requirements.

1.02 RELATED REQUIREMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary

Conditions and Division 01 Specification Sections, apply to this Section.

1.03 REFERENCE STANDARDS

A. NECA 1 - Standard for Good Workmanship in Electrical Construction; 2023.

B. NETA ATS - Standard for Acceptance Testing Specifications for Electrical Power Equipment

And Systems; 2025.

1.04 DEFINITIONS

A. ATS: Acceptance Testing Specifications.

1.05 SUBMITTALS

A. Coordination Drawings: The Contractor shall provide coordination drawings for each location requiring additional detail to properly plan, execute and document the work. Coordination drawings shall be drawn to scale.

1. Upon Completion of the project, a hardcopy “red-lined” sets of prints showing all work deviating from the Contract drawings or provided as part of the working drawing work shall be turned over to the ENGINEER for inspection and approval.

2. Equipment Location Plants: Working drawings shall depict all of the wiring devices, conduits, field devices, and power distribution equipment on scaled plan drawings. Detail all proposed concealed and under slab raceways.

3. Update Existing Panel Schedules

a. Provide an updated hardcopy of the panel schedule inside the existing panel.

1.06 QUALITY ASSURANCE

A. Test Equipment Suitability and Calibration: Comply with NETA ATS, "Suitability of Test

Equipment" and "Test Instrument Calibration."

1.07 FIELD CONDITIONS

A. Coordinate arrangement, mounting, and support of electrical equipment:

1. To allow maximum possible headroom unless specific mounting heights that reduce headroom are indicated.

2. To provide for ease of disconnecting the equipment with minimum interference to other installations.

3. To allow right of way for piping and conduit installed at required slope.

4. So connecting raceways, cables, wireways, cable trays, and busways will be clear of obstructions and of the working and access space of other equipment.

B. Coordinate installation of required supporting devices and set sleeves in cast-in-place concrete, masonry walls, and other structural components as they are constructed.

C. Coordinate location of access panels and doors for electrical items that are behind finished surfaces or otherwise concealed.

D. Coordinate electrical testing of electrical, mechanical, and architectural items, so equipment and systems that are functionally interdependent are tested to demonstrate successful interoperability.

HVAC System Replacement 260010 - 2 Basic Electrical Materials and

Methods

E. Interruption of Existing Electric Service: Do not interrupt electric service to facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary electric service according to requirements indicated:

1. Notify Engineer no fewer than five days in advance of proposed interruption of electric service.

2. Do not proceed with interruption of electric service without Engineer's written permission.

PART 2 PRODUCTS

2.01 MANUFACTURERS

A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection:

1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, manufacturers specified.

2. Manufacturers: Subject to compliance with requirements, provide products by one of the manufacturers specified.

PART 3 EXECUTION

3.01 COMMON REQUIREMENTS FOR ELECTRICAL INSTALLATION

A. Comply with NECA 1.

B. Measure indicated mounting heights to bottom of unit for suspended items and to center of unit for wall-mounting items.

C. Headroom Maintenance: If mounting heights or other location criteria are not indicated, arrange and install components and equipment to provide maximum possible headroom consistent with these requirements.

D. Equipment: Install to facilitate service, maintenance, and repair or replacement of components of both electrical equipment and other nearby installations. Connect in such a way as to facilitate future disconnecting with minimum interference with other items in the vicinity.

E. Right of Way: Give to raceways and piping systems installed at a required slope.

3.02 EXAMINATION

A. Examine substrates, with Installer present, for compliance with requirements for maximum moisture content, installation tolerances, and other conditions affecting performance of the Work.

B. Examine roughing-in for other trades to verify actual locations of equipment connections before equipment installation.

C. Examine walls, floors, and roofs for suitable conditions where equipment will be installed.

D. Prepare written report, endorsed by Installer, listing conditions detrimental to performance.

E. Proceed with installation only after unsatisfactory conditions have been corrected.

3.03 PROTECTION

A. Temporary Heating: Apply temporary heat to maintain temperature according to manufacturer's written instructions until equipment is ready to be energized and placed into service.

B. Replace equipment whose interiors have been exposed to a buildup of dust or debris, water or other liquids prior to Substantial Completion.

3.04 ADJUSTING

A. Adjust hardware to function smoothly, and lubricate as recommended by manufacturer.

B. Occupancy Adjustments: When requested within 12 months from date of Substantial

Completion, provide on-site assistance in adjusting system to suit actual occupied conditions.

Provide up to two visits to Project during other-than-normal occupancy hours for this purpose.

3.05 CLEANING

HVAC System Replacement 260010 - 3 Basic Electrical Materials and

Methods

A. Provide clean project area broom swept weekly.

B. Clean project area before Owner occupancy and discard all trash and debris.

END OF SECTION

HVAC System Replacement 260505 - 1 Selective Demolition for Electrical

SECTION 260505

SELECTIVE DEMOLITION FOR ELECTRICAL

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Electrical demolition.

1.02 SUBMITTALS

A. Submit temporary power plan and sequencing plan to maintain required operations as outlined on the Drawings.

PART 2 PRODUCTS

2.01 MATERIALS AND EQUIPMENT

A. Materials and equipment for patching and extending work: As specified in individual sections.

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify field measurements and circuiting arrangements are as indicated.

B. Verify that abandoned wiring and equipment serve only abandoned facilities.

C. Demolition drawings are based on casual field observation and existing record documents.

D. Report discrepancies to Engineer before disturbing existing installation.

E. Beginning of demolition means installer accepts existing conditions.

3.02 PREPARATION

A. Disconnect electrical systems in walls, floors, and ceilings to be removed.

B. Provide temporary wiring and connections to maintain existing systems in service during construction. When work must be performed on energized equipment or circuits, use personnel experienced in such operations.

C. Existing Electrical Service: Maintain existing system in service until new system is complete and ready for service. Disable system only to make switchovers and connections. Minimize outage duration.

1. Refer to 260010 - Basic Electrical Materials and Methods for additional outage information and limitations.

2. Obtain permission from Owner at least 24 hours before partially or completely disabling system.

3. Make temporary connections to maintain service in areas adjacent to work area.

3.03 DEMOLITION AND EXTENSION OF EXISTING ELECTRICAL WORK

A. Remove, relocate, and extend existing installations to accommodate new construction.

B. Remove abandoned wiring to source of supply.

C. Remove exposed abandoned conduit, including abandoned conduit above accessible ceiling finishes. Cut conduit flush with walls and floors, and patch surfaces.

D. Disconnect abandoned outlets and remove devices. Remove abandoned outlets if conduit servicing them is abandoned and removed. Provide blank cover for abandoned outlets that are not removed.

E. Disconnect and remove electrical devices and equipment serving utilization equipment that has been removed.

F. Repair adjacent construction and finishes damaged during demolition and extension work.

G. Maintain access to existing electrical installations that remain active. Modify installation or provide access panel as appropriate.

HVAC System Replacement 260505 - 2 Selective Demolition for Electrical

H. Extend existing installations using materials and methods compatible with existing electrical installations, or as specified.

3.04 CLEANING AND REPAIR

A. Maintain site clear of debris during and after demolition activities.

B. Panelboards: Clean exposed surfaces and check tightness of electrical connections. Replace damaged circuit breakers and provide closure plates for vacant positions. Provide typed circuit directory showing revised circuiting arrangement.

3.05 PROTECTION

A. Protect all existing equipment not scheduled to be demolished.

B. Remove and replace equipment that are physically damaged, wet or moisture damaged, or mold damaged as a result of demolition activity under this contract.

HVAC System Replacement 260519 - 1 Low-Voltage Electrical Power

Conductors and Cables

SECTION 260519

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Single conductor building wire.

B. Wiring connectors.

C. Electrical tape.

D. Wire pulling lubricant.

E. Cable ties.

1.02 RELATED REQUIREMENTS

A. Section 260526 - Grounding and Bonding for Electrical Systems: Additional requirements for grounding conductors and grounding connectors.

B. Section 260553 - Identification for Electrical Systems: Identification products and requirements.

1.03 REFERENCE STANDARDS

A. ASTM B3 - Standard Specification for Soft or Annealed Copper Wire; 2013 (Reapproved 2018).

B. ASTM B8 - Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft; 2023.

C. ASTM B33 - Standard Specification for Tin-Coated Soft or Annealed Copper Wire for Electrical

Purposes; 2010, with Editorial Revision (2020).

D. ASTM B787/B787M - Standard Specification for 19 Wire Combination Unilay-Stranded Copper

Conductors for Subsequent Insulation; 2004 (Reapproved 2020).

E. ASTM D3005 - Standard Specification for Low-Temperature Resistant Vinyl Chloride Plastic

Pressure-Sensitive Electrical Insulating Tape; 2017.

F. ASTM D4388 - Standard Specification for Nonmetallic Semi-Conducting and Electrically

Insulating Rubber Tapes; 2020.

G. FS A-A-59544 - Cable and Wire, Electrical (Power, Fixed Installation); 2008a (Validated 2019).

H. NECA 1 - Standard for Good Workmanship in Electrical Construction; 2023.

I. NEMA WC 70 - Power Cables Rated 2000 Volts or Less for the Distribution of Electrical

Energy; 2021.

J. NETA ATS - Standard for Acceptance Testing Specifications for Electrical Power Equipment

And Systems; 2025.

K. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having

Jurisdiction, Including All Applicable Amendments and Supplements.

L. NFPA 79 - Electrical Standard for Industrial Machinery; 2021.

M. UL 44 - Thermoset-Insulated Wires and Cables; Current Edition, Including All Revisions.

N. UL 83 - Thermoplastic-Insulated Wires and Cables; Current Edition, Including All Revisions.

O. UL 267 - Outline of Investigation for Wire-Pulling Compounds; Current Edition, Including All

Revisions.

P. UL 486A-486B - Wire Connectors; Current Edition, Including All Revisions.

Q. UL 486C - Splicing Wire Connectors; Current Edition, Including All Revisions.

R. UL 486D - Sealed Wire Connector Systems; Current Edition, Including All Revisions.

S. UL 510 - Polyvinyl Chloride, Polyethylene, and Rubber Insulating Tape; Current Edition, Including All Revisions.

HVAC System Replacement 260519 - 2 Low-Voltage Electrical Power

Conductors and Cables

T. UL 2277 - Outline of Investigation for Flexible Motor Supply Cable and Wind Turbine Tray Cable; Current Edition, Including All Revisions.

1.04 ADMINISTRATIVE REQUIREMENTS

A. Coordination:

1. Coordinate sizes of raceways, boxes, and equipment enclosures installed under other sections with the actual conductors to be installed, including adjustments for conductor sizes increased for voltage drop.

2. Coordinate the installation of direct burial cable with other trades to avoid conflicts with piping or other potential conflicts.

3. Coordinate with electrical equipment installed under other sections to provide terminations suitable for use with the conductors to be installed.

4. Notify Engineer of any conflicts with or deviations from Contract Documents. Obtain direction before proceeding with work.

1.05 SUBMITTALS

A. Product Data: Provide manufacturer's standard catalog pages and data sheets for conductors and cables, including detailed information on materials, construction, ratings, listings, and available sizes, configurations, and stranding.

B. Sustainable Design Documentation: Submit manufacturer's product data on conductor and cable showing compliance with specified lead content requirements.

C. Manufactured Wiring System Shop Drawings: Provide plan views indicating proposed system layout with components identified; indicate branch circuit connections.

D. Wire Pulling Lubricant: Certification of compatibility with conductors/cables.

E. Field Quality Control Test Reports.

F. Manufacturer's Installation Instructions: Indicate application conditions and limitations of use stipulated by product testing agency. Include instructions for storage, handling, protection, examination, preparation, and installation of product.

G. Project Record Documents: Record actual installed circuiting arrangements. Record actual routing for underground circuits.

1.06 QUALITY ASSURANCE

A. Comply with requirements of NFPA 70.

B. Maintain at the project site a copy of each referenced document that prescribes execution requirements.

C. Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum three years documented experience.

D. Product Listing Organization Qualifications: An organization recognized by OSHA as a

Nationally Recognized Testing Laboratory (NRTL) and acceptable to authorities having jurisdiction.

1.07 DELIVERY, STORAGE, AND HANDLING

A. Receive, inspect, handle, and store conductors and cables in accordance with manufacturer's instructions.

1.08 FIELD CONDITIONS

A. Do not install or otherwise handle thermoplastic-insulated conductors at temperatures lower than 14 ºF, unless otherwise permitted by manufacturer's instructions. When installation below this temperature is unavoidable, notify Engineer and obtain direction before proceeding with work.

PART 2 PRODUCTS

2.01 CONDUCTOR AND CABLE APPLICATIONS

HVAC System Replacement 260519 - 3 Low-Voltage Electrical Power

Conductors and Cables

A. Do not use conductors and cables for applications other than as permitted by NFPA 70 and product listing.

B. Provide single conductor building wire installed in suitable raceway unless otherwise indicated, permitted, or required.

C. Nonmetallic-sheathed cable is not permitted.

D. Service entrance cable is not permitted.

E. Armored cable is not permitted.

F. Metal-clad cable is not permitted.

G. Manufactured wiring systems are not permitted.

2.02 CONDUCTOR AND CABLE GENERAL REQUIREMENTS

A. Provide products that comply with requirements of NFPA 70.

B. Provide products listed, classified, and labeled as suitable for the purpose intended.

C. Provide new conductors and cables manufactured not more than one year prior to installation.

D. Unless specifically indicated to be excluded, provide all required conduit, boxes, wiring, connectors, etc. as required for a complete operating system.

E. Comply with NEMA WC 70.

F. Comply with FS A-A-59544 where applicable.

G. Thermoplastic-Insulated Conductors and Cables: Listed and labeled as complying with UL 83.

H. Thermoset-Insulated Conductors and Cables: Listed and labeled as complying with UL 44.

I. Conductors for Grounding and Bonding: Also comply with Section 260526.

J. Conductors and Cables Installed in Cable Tray: Listed and labeled as suitable for cable tray use.

K. Conductors and Cables Installed Where Exposed to Direct Rays of Sun: Listed and labeled as sunlight resistant.

L. Conductors and Cables Installed Exposed in Spaces Used for Environmental Air (only where specifically permitted): Plenum rated, listed and labeled as suitable for use in return air plenums.

M. Conductor Material:

1. Provide copper conductors only. Aluminum conductors are not acceptable for this project.

Conductor sizes indicated are based on copper.

2. Copper Conductors: Soft drawn annealed, 98 percent conductivity, uncoated copper conductors complying with ASTM B3, ASTM B8, or ASTM B787/B787M unless otherwise indicated.

3. Tinned Copper Conductors: Comply with ASTM B33.

N. Minimum Conductor Size:

1. Branch Circuits: 12 AWG.

a. Exceptions:

1) 20 A, 120 V circuits longer than 75 feet: 10 AWG, for voltage drop.

2) 20 A, 120 V circuits longer than 150 feet: 8 AWG, for voltage drop.

3) 20 A, 277 V circuits longer than 150 feet: 10 AWG, for voltage drop.

2. Control Circuits: 14 AWG.

O. Where conductor size is not indicated, size to comply with NFPA 70 but not less than applicable minimum size requirements specified.

P. Conductor Color Coding:

1. Color code conductors as indicated unless otherwise required by the authority having jurisdiction. Maintain consistent color coding throughout project.

2. Color Coding Method: Integrally colored insulation.

HVAC System Replacement 260519 - 4 Low-Voltage Electrical Power

Conductors and Cables

a. Conductors size 4 AWG and larger may have black insulation color coded using vinyl color coding electrical tape.

3. Color Code:

a. 208Y/120 V, 3 Phase, 4 Wire System:

1) Phase A: Black.

2) Phase B: Red.

3) Phase C: Blue.

4) Neutral/Grounded: White.

b. 240/120 V, 1 Phase, 3 Wire System:

1) Phase A: Black.

2) Phase B: Red.

3) Neutral/Grounded: White.

c. Equipment Ground, All Systems: Green.

d. Isolated Ground, All Systems: Green with yellow stripe.

e. Travelers for 3-Way and 4-Way Switching: Pink.

f. For modifications or additions to existing wiring systems, comply with existing color code when existing code complies with NFPA 70 and is approved by the authority having jurisdiction.

g. For control circuits, comply with manufacturer's recommended color code.

2.03 SINGLE CONDUCTOR BUILDING WIRE

A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

1. Copper Building Wire:

a. General Cable Technologies Corporation: www.generalcable.com/#sle.

b. Service Wire Co: www.servicewire.com/#sle.

c. Southwire Company: www.southwire.com/#sle.

d. Approved Equal.

B. Description: Single conductor insulated wire.

C. Conductor Stranding:

1. Feeders and Branch Circuits:

a. Size 10 AWG and Smaller: Solid.

b. Size 8 AWG and Larger: Stranded.

2. Control Circuits: Stranded.

D. Insulation Voltage Rating: 600 V.

E. Insulation:

1.

2. Copper Building Wire: Type THHN/THWN-2 or XHHW-2, as indicated below.

a. Size 4 AWG and Larger: Type XHHW-2.

b. Installed Underground: Type XHHW-2.

c. Installed as Service Entrance: Type XHHW-2

d. Installed as Exposed Feeders and Branch Circuits: Type XHWW-2.

e. Installed as Interior Above Grade Feeders or Branch Circuits: Type THHN/THWN-2.

2.04 WIRING CONNECTORS

A. Description: Wiring connectors appropriate for the application, suitable for use with the conductors to be connected, and listed as complying with UL 486A-486B or UL 486C as applicable.

B. Connectors for Grounding and Bonding: Comply with Section 260526.

C. Wiring Connectors for Splices and Taps:

1. Copper Conductors Size 8 AWG and Smaller: Use twist-on insulated spring connectors.

HVAC System Replacement 260519 - 5 Low-Voltage Electrical Power

Conductors and Cables

2. Copper Conductors Size 6 AWG and Larger: Use mechanical connectors or compression connectors.

D. Wiring Connectors for Terminations:

1. Provide terminal lugs for connecting conductors to equipment furnished with terminations designed for terminal lugs.

2. Provide compression adapters for connecting conductors to equipment furnished with mechanical lugs when only compression connectors are specified.

3. Where over-sized conductors are larger than the equipment terminations can accommodate, provide connectors suitable for reducing to appropriate size, but not less than required for the rating of the overcurrent protective device.

4. Provide motor pigtail connectors for connecting motor leads in order to facilitate disconnection.

5. Copper Conductors Size 8 AWG and Larger: Use mechanical connectors or compression connectors where connectors are required.

6. Stranded Conductors Size 10 AWG and Smaller: Use crimped terminals for connections to terminal screws.

7. Conductors for Control Circuits: Use crimped terminals for all connections.

E. Do not use insulation-piercing or insulation-displacement connectors designed for use with conductors without stripping insulation.

F. Do not use push-in wire connectors as a substitute for twist-on insulated spring connectors.

G. Twist-on Insulated Spring Connectors: Rated 600 V, 105 ºC for standard applications and 105

ºC for high temperature applications; pre-filled with sealant and listed as complying with UL 486D for damp and wet locations.

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. 3M: www.3m.com/#sle.

b. Ideal Industries, Inc: www.idealindustries.com/#sle.

c. NSI Industries LLC: www.nsiindustries.com/#sle.

d. Approved Equal.

H. Mechanical Connectors: Provide bolted type or set-screw type.

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. Burndy LLC: www.burndy.com/#sle.

b. nVent ILSCO: www.ilsco.com/#sle.

c. Thomas & Betts Corporation: www.tnb.com/#sle.

d. Approved Equal.

2.05 ACCESSORIES

A. Electrical Tape:

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. 3M: www.3m.com/#sle.

b. Plymouth Rubber Europa: www.plymouthrubber.com/#sle.

c. Approved Equal.

2. Vinyl Color Coding Electrical Tape: Integrally colored to match color code indicated; listed as complying with UL 510; minimum thickness of 7 mil; resistant to abrasion, corrosion, and sunlight; suitable for continuous temperature environment up to 105 ºC.

3. Vinyl Insulating Electrical Tape: Complying with ASTM D3005 and listed as complying with UL 510; minimum thickness of 7 mil; resistant to abrasion, corrosion, and sunlight;

HVAC System Replacement 260519 - 6 Low-Voltage Electrical Power

Conductors and Cables conformable for application down to 0 ºF and suitable for continuous temperature environment up to 105 ºC.

4. Rubber Splicing Electrical Tape: Ethylene Propylene Rubber (EPR) tape, complying with ASTM D4388; minimum thickness of 30 mil; suitable for continuous temperature environment up to 90 ºC and short-term 130 ºC overload service.

5. Electrical Filler Tape: Rubber-based insulating moldable putty, minimum thickness of 125 mil; suitable for continuous temperature environment up to 176 degrees F.

6. Varnished Cambric Electrical Tape: Cotton cambric fabric tape, with or without adhesive, oil-primed and coated with high-grade insulating varnish; minimum thickness of 7 mil;

suitable for continuous temperature environment up to 221 degrees F.

7. Moisture Sealing Electrical Tape: Insulating mastic compound laminated to flexible, all-weather vinyl backing; minimum thickness of 90 mil.

B. Wire Pulling Lubricant:

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. 3M: www.3m.com/#sle.

b. American Polywater Corporation: www.polywater.com/#sle.

c. Ideal Industries, Inc: www.idealindustries.com/#sle.

d. Approved Equal.

2. Listed and labeled as complying with UL 267.

3. Suitable for use with conductors/cables and associated insulation/jackets to be installed.

4. Suitable for use at installation temperature.

C. Cable Ties: Material and tensile strength rating suitable for application.

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. Burndy LLC: www.burndy.com/#sle.

b. Approved Equal.

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify that interior of building has been protected from weather.

B. Verify that work likely to damage wire and cable has been completed.

C. Verify that raceways, boxes, and equipment enclosures are installed and are properly sized to accommodate conductors and cables in accordance with NFPA 70.

D. Verify that field measurements are as indicated.

E. Verify that conditions are satisfactory for installation prior to starting work.

3.02 PREPARATION

A. Clean raceways thoroughly to remove foreign materials before installing conductors and cables.

3.03 INSTALLATION

A. Circuiting Requirements:

1. Unless dimensioned, circuit routing indicated is diagrammatic.

2. When circuit destination is indicated without specific routing, determine exact routing required.

3. Arrange circuiting to minimize splices.

4. Include circuit lengths required to install connected devices within10 feet of location indicated.

5. Maintain separation of Class 1, Class 2, and Class 3 remote-control, signaling, and power-limited circuits in accordance with NFPA 70.

HVAC System Replacement 260519 - 7 Low-Voltage Electrical Power

Conductors and Cables

6. Maintain separation of wiring for emergency systems in accordance with NFPA 70.

7. Circuiting Adjustments: Unless otherwise indicated or required by code, when branch circuits are indicated as separate, combining them together in a single raceway is permitted, under the following conditions:

a. Provide no more than six current-carrying conductors in a single raceway. Dedicated neutral conductors are considered current-carrying conductors.

b. Increase size of conductors as required to account for ampacity derating.

c. Size raceways, boxes, etc. to accommodate conductors.

8. Common Neutrals: Unless otherwise indicated, sharing of neutral/grounded conductors among up to three single phase branch circuits of different phases installed in the same raceway is not permitted. Provide dedicated neutral/grounded conductor for each individual branch circuit.

B. Install products in accordance with manufacturer's instructions.

C. Perform work in accordance with NECA 1 (general workmanship).

D. Installation in Raceway:

1. Tape ends of conductors and cables to prevent infiltration of moisture and other contaminants.

2. Pull all conductors and cables together into raceway at same time.

3. Do not damage conductors and cables or exceed manufacturer's recommended maximum pulling tension and sidewall pressure.

4. Use suitable wire pulling lubricant where necessary, except when lubricant is not recommended by the manufacturer.

E. Paralleled Conductors: Install conductors of the same length and terminate in the same manner.

F. Secure and support conductors and cables in accordance with NFPA 70 using suitable supports and methods approved by the authority having jurisdiction. Provide independent support from building structure. Do not provide support from raceways, piping, ductwork, or other systems.

1. Installation Above Suspended Ceilings: Do not provide support from ceiling support system. Do not provide support from ceiling grid or allow conductors and cables to lay on ceiling tiles.

2. Installation in Vertical Raceways: Provide supports where vertical rise exceeds permissible limits.

G. Terminate cables using suitable fittings.

H. Install conductors with a minimum of 12 inches of slack at each outlet.

I. Where conductors are installed in enclosures for future termination by others, provide a minimum of 5 feet of slack.

J. Neatly train and bundle conductors inside boxes, wireways, panelboards and other equipment enclosures.

K. Group or otherwise identify neutral/grounded conductors with associated ungrounded conductors inside enclosures in accordance with NFPA 70.

L. Make wiring connections using specified wiring connectors.

1. Make splices and taps only in accessible boxes. Do not pull splices into raceways or make splices in conduit bodies or wiring gutters.

2. Remove appropriate amount of conductor insulation for making connections without cutting, nicking or damaging conductors.

3. Do not remove conductor strands to facilitate insertion into connector.

4. Clean contact surfaces on conductors and connectors to suitable remove corrosion, oxides, and other contaminates. Do not use wire brush on plated connector surfaces.

5. Mechanical Connectors: Secure connections according to manufacturer's recommended torque settings.

HVAC System Replacement 260519 - 8 Low-Voltage Electrical Power

Conductors and Cables

6. Compression Connectors: Secure connections using manufacturer's recommended tools and dies.

M. Insulate splices and taps that are made with uninsulated connectors using methods suitable for the application, with insulation and mechanical strength at least equivalent to unspliced conductors.

1. Dry Locations: Use insulating covers specifically designed for the connectors, electrical tape, or heat shrink tubing.

a. For taped connections, first apply adequate amount of rubber splicing electrical tape or electrical filler tape, followed by outer covering of vinyl insulating electrical tape.

b. For taped connections likely to require re-entering, including motor leads, first apply varnished cambric electrical tape, followed by adequate amount of rubber splicing electrical tape, followed by outer covering of vinyl insulating electrical tape.

2. Damp Locations: Use insulating covers specifically designed for the connectors, electrical tape, or heat shrink tubing.

a. For connections with insulating covers, apply outer covering of moisture sealing electrical tape.

b. For taped connections, follow same procedure as for dry locations but apply outer covering of moisture sealing electrical tape.

3. Wet Locations: Use heat shrink tubing.

N. Insulate ends of spare conductors using vinyl insulating electrical tape.

O. Field-Applied Color Coding: Where vinyl color coding electrical tape is used in lieu of integrally colored insulation as permitted in Part 2 under "Color Coding", apply half overlapping turns of tape at each termination and at each location conductors are accessible.

P. Identify conductors and cables in accordance with Section 260553.

Q. Install firestopping to preserve fire resistance rating of partitions and other elements, using materials and methods specified in Section 078400.

R. Unless specifically indicated to be excluded, provide final connections to all equipment and devices, including those furnished by others, as required for a complete operating system.

3.04 FIELD QUALITY CONTROL

A. Inspect and test in accordance with NETA ATS, except Section 4.

B. Perform inspections and tests listed in NETA ATS, Section 7.3.2. The insulation resistance test is required for all conductors. The resistance test for parallel conductors listed as optional is not required.

1. Disconnect surge protective devices (SPDs) prior to performing any high potential testing.

Replace SPDs damaged by performing high potential testing with SPDs connected.

C. Correct deficiencies and replace damaged or defective conductors and cables.

HVAC System Replacement 260523 - 1 Control-Voltage Electrical Power

Cables

SECTION 260523

CONTROL-VOLTAGE ELECTRICAL POWER CABLES

PART 1 GENERAL

1.01 REFERENCE STANDARDS

A. BICSI ITSIMM - Information Technology Systems Installation Methods Manual (ITSIMM), 8th Edition; 2022.

B. BICSI TDMM - Telecommunications Distribution Methods Manual, 15th Edition; 2024.

C. ICEA S-90-661 - Category 3 and 5E Individually Unshielded Twisted Pairs, Indoor Cables (With or Without an Overall Shield) for Use in General Purpose and LAN Communication Wiring Systems; 2021.

D. IEC 60603-7 - Connectors for Electronic Equipment - Part 7: Detail Specification for 8-Way, Unshielded, Free and Fixed Connectors; 2020.

E. IEEE C2 - National Electrical Safety Code(R) (NESC(R)); 2023.

F. NECA 1 - Standard for Good Workmanship in Electrical Construction; 2023.

G. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having

Jurisdiction, Including All Applicable Amendments and Supplements.

H. TIA-232 - Interface Between Data Terminal Equipment and Data Circuit-Terminating Equipment

Employing Serial Binary Data Interchange; 1997f (Reaffirmed 2012).

I. TIA-569 - Telecommunications Pathways and Spaces; 2019e, with Addendum (2022).

J. TIA-606 - Administration Standard for Telecommunications Infrastructure; 2021d.

K. TIA-607 - Telecommunications Bonding and Grounding (Earthing) for Customer Premises;

2024e.

L. UL 44 - Thermoset-Insulated Wires and Cables; Current Edition, Including All Revisions.

M. UL 83 - Thermoplastic-Insulated Wires and Cables; Current Edition, Including All Revisions.

N. UL 969 - Marking and Labeling Systems; Current Edition, Including All Revisions.

O. UL 1277 - Electrical Power and Control Tray Cables with Optional Optical-Fiber Members;

Current Edition, Including All Revisions.

P. UL 1569 - Metal-Clad Cables; Current Edition, Including All Revisions.

Q. UL 1581 - Reference Standard for Electrical Wires, Cables, and Flexible Cords; Current Edition, Including All Revisions.

R. UL 1685 - Standard for Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for

Electrical and Optical-Fiber Cables; Current Edition, Including All Revisions.

1.02 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.03 SUMMARY

A. Section Includes:

1. Low-voltage control cabling.

2. Control-circuit conductors.

3. Identification products.

1.04 DEFINITIONS

A. EMI: Electromagnetic interference.

B. Low Voltage: As defined in NFPA 70 for circuits and equipment operating at less than 50 V or for remote-control and signaling power-limited circuits.

HVAC System Replacement 260523 - 2 Control-Voltage Electrical Power

Cables

C. Plenum: A space forming part of the air distribution system to which one or more air ducts are connected. An air duct is a passageway, other than a plenum, for transporting air to or from heating, ventilating, or air-conditioning equipment.

1.05 ACTION SUBMITTALS

A. Product Data: For each type of product.

1.06 INFORMATIONAL SUBMITTALS

A. Source quality-control reports.

B. Field quality-control reports.

PART 2 PRODUCTS

2.01 PERFORMANCE REQUIREMENTS

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. RoHS compliant.

2.02 SHIELDED TWISTED PAIR CONTROL CABLE

A. Description: Shielded Twisted Pair (STP) cables shall be used for all analog signal wiring installed under this contract.

B. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

C. Belden Electronic Wire and Cable Company.

1. General Cable; Prysmian Group North America.

2. Okonite Company.

3. Approved Equal.

D. Paired Cable: NFPA 70, Type CMG.

1. One pair, twisted, No. 16 AWG , stranded (19x29) tinned-copper conductors.

2. PVC insulation, 600 V .

3. Cable shield shall be aluminum-polyester tape overlapped to provide 100% coverage, and a 7 strand tinned copper drain wire, size 18 AWG.

4. PVC jacket, 80 C temperature rating.

5. Flame Resistance: Comply with UL 1685.

6. Suitable for both indoor dry and outdoor wet locations.

2.03 CONTROL-CIRCUIT CONDUCTORS

A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

1. General Cable; Prysmian Group North America.

2. Service Wire Co.

3. Southwire Company.

4. Approved Equal.

B. Class 1 Control Circuits: Stranded copper, Type THHN/THWN-2, complying with UL 83 in raceway.

C. Class 2 Control Circuits: Stranded copper, Type THHN/THWN-2, complying with UL 83 in raceway.

D. Class 3 Remote-Control and Signal Circuits: Stranded copper, Type THHN/THWN-2, complying with UL 83 in raceway.

2.04 SOURCE QUALITY CONTROL

A. Factory test twisted pair cables according to TIA-568-C.2.

B. Cable will be considered defective if it does not pass tests and inspections.

HVAC System Replacement 260523 - 3 Control-Voltage Electrical Power

Cables

C. Prepare test and inspection reports.

PART 3 EXECUTION

3.01 EXAMINATION

A. Test cables on receipt at Project site.

1. Test each pair of twisted pair cable for open and short circuits.

2. Reject failed cables.

B. Comply with requirements in Sections 260533.16 "Boxes for Electrical Systems" and

260533.23 "Surface Raceways for Electrical Systems" for raceway selection and installation requirements for boxes, conduits, and wireways as supplemented or modified in this Section.

1. Outlet boxes shall be no smaller than 2 inches wide, 3 inches high, and 2-1/2 inches deep.

2. Outlet boxes for cables shall be no smaller than 4 inches square by 1-1/2 inches deep with extension ring sized to bring edge of ring to within 1/8 inch of the finished wall surface.

3. Flexible metal conduit shall not be used.

C. Comply with TIA-569-D for pull-box sizing and length of conduit and number of bends between pull points.

D. Install manufactured conduit sweeps and long-radius elbows if possible.

3.02 RACEWAY INSTALLATION IN EQUIPMENT ROOMS:

A. Position conduit ends adjacent to a corner on backboard if a single piece of plywood is installed, or in the corner of the room if multiple sheets of plywood are installed around perimeter walls of the room.

B. Install cable trays to route cables if conduits cannot be located in these positions.

C. Secure conduits to backboard if entering the room from overhead.

D. Extend conduits 3 inches ???Insert dimension??? above finished floor.

E. Install metal conduits with grounding bushings and connect with grounding conductor to grounding system.

3.03 INSTALLATION OF CONDUCTORS AND CABLES

A. Comply with NECA 1.

B. General Requirements for Cabling:

1. Comply with TIA-568-C Series of standards.

2. Comply with BICSI ITSIMM, Ch. 5, "Copper Structured Cabling Systems."

3. Terminate all conductors; no cable shall contain unterminated elements. Make terminations only at indicated outlets, terminals, and cross-connect and patch panels.

4. Cables may not be spliced and shall be continuous from terminal to terminal. Do not splice cable between termination, tap, or junction points. Make taps, and terminations only at indicated outlets, terminals, and cross-connect and patch panels.

5. Cables serving a common system may be grouped in a common raceway. Install network cabling and control wiring and cable in separate raceway from power wiring. Do not group conductors from different systems or different voltages.

6. Furnish a separate raceway system for shielded signal cable. Do not run in the same conduit with power cable.

7. Where telemetry cables are run in the same duct bank with power cables, use galvanized steel conduit. Use junction boxes and "LB" fittings in manholes to maintain a continuous steel raceway system for signal cables.

8. Secure and support cables at intervals not exceeding 30 inches and not more than 6 inches from cabinets, boxes, fittings, outlets, racks, frames, and terminals.

9. Bundle, lace, and train conductors to terminal points without exceeding manufacturer's limitations on bending radii, but not less than radii specified in BICSI ITSIMM, Ch. 5, "Copper Structured Cabling Systems." Install lacing bars and distribution spools.

HVAC System Replacement 260523 - 4 Control-Voltage Electrical Power

Cables

10. Install exposed cables parallel and perpendicular to surfaces or exposed structural members and follow surface contours where possible.

11. Do not install bruised, kinked, scored, deformed, or abraded cable. Remove and discard cable if damaged during installation and replace it with new cable.

12. Cold-Weather Installation: Bring cable to room temperature before dereeling. Do not use heat lamps for heating.

13. Pulling Cable: Comply with BICSI ITSIMM, Ch. 5, "Copper Structured Cabling Systems."

Monitor cable pull tensions.

14. Support cables at intervals not exceeding 30 inches and not more than 6 inches from cabinets, boxes, fittings, outlets, racks, frames, and terminals. Do not allow cables to lie on removable ceiling tiles.

15. Secure: Fasten securely in place with hardware specifically designed and installed so as to not damage cables.

16. Provide strain relief.

17. Keep runs short. Allow extra length for connecting to terminals. Do not bend cables in a radius less than 10 times the cable OD. Use sleeves or grommets to protect cables from vibration at points where they pass around sharp corners and through penetrations.

18. Ground wire shall be copper, and grounding methods shall comply with IEEE C2.

Demonstrate ground resistance.

C. Installation of Control-Circuit Conductors:

1. Install wiring in raceways.

2. Use insulated spade lugs for wire and cable connection to screw terminals.

3. Comply with requirements specified in Sections 260533.16 "Boxes for Electrical Systems" and 260533.23 "Surface Raceways for Electrical Systems"

4. Control wiring may be pulled in the power conduits and wireways providing the highest voltage of the adjacent wires is not more than 120 volts.

5. All terminators required to interface the new cables to the various devices shall be furnished, installed, connected and tested as part of this contract.

D. Power Control Systems

1. The wiring of this category (single conductor, or multiple conductor) is to be installed in accordance with the NEC.

E. Telemetry and Instrumentation Signal Systems

1. Separate conduit and wireway runs are required for this category. All wiring is to be isolated from all power systems.

F. Separation from EMI Sources:

1. Comply with BICSI TDMM and TIA-569-D recommendations for separating unshielded copper voice and data communications cable from potential EMI sources including electrical power lines and equipment.

2. Separation between open communications cables or cables in nonmetallic raceways and unshielded power conductors and electrical equipment shall be as follows:

a. Electrical Equipment or Circuit Rating Less Than 2 kVA: A minimum of 5 inches.

b. Electrical Equipment or Circuit Rating between 2 and 5 kVA: A minimum of 12 inches.

c. Electrical Equipment or Circuit Rating More Than 5 kVA: A minimum of 24 inches.

3. Separation between communications cables in grounded metallic raceways and unshielded power lines or electrical equipment shall be as follows:

a. Electrical Equipment or Circuit Rating Less Than 2 kVA: A minimum of 2-1/2 inches.

b. Electrical Equipment or Circuit Rating between 2 and 5 kVA: A minimum of 6 inches.

c. Electrical Equipment or Circuit Rating More Than 5 kVA: A minimum of 12 inches.

4. Separation between communications cables in grounded metallic raceways and power lines and electrical equipment located in grounded metallic conduits or enclosures shall be as follows:

a. Electrical Equipment or Circuit Rating Less Than 2 kVA: No requirement.

b. Electrical Equipment or Circuit Rating between 2 and 5 kVA: A minimum of 3 inches.

HVAC System Replacement 260523 - 5 Control-Voltage Electrical Power

Cables

c. Electrical Equipment or Circuit Rating More Than 5 kVA: A minimum of 6 inches.

5. Separation between Communications Cables and Electrical Motors and Transformers, 5 kVA or 5 HP and Larger: A minimum of 48 inches.

6. Separation between Communications Cables and Fluorescent Fixtures: A minimum of 5 inches.

3.04 REMOVAL OF CONDUCTORS AND CABLES

A. Remove abandoned conductors and cables. Abandoned conductors and cables are those installed that are not terminated at equipment and are not identified with a tag for future use.

3.05 CONTROL-CIRCUIT CONDUCTORS

A. Minimum Conductor Sizes:

1. Class 1 remote-control and signal circuits; No 14 AWG.

2. Class 2 low-energy, remote-control, and signal circuits; No. 16 AWG.

3. Class 3 low-energy, remote-control, alarm, and signal circuits; No 12 AWG.

3.06 GROUNDING

A. For data communication wiring, comply with TIA-607-B and with BICSI TDMM, "Bonding and

Grounding (Earthing)" Chapter.

1. Ground cable shield at termination of instrumentation cabinet only. Ground connection should be visible.

B. For low-voltage control wiring and cabling, comply with requirements in Section 260526

"Grounding and Bonding for Electrical Systems."

3.07 IDENTIFICATION

A. Comply with requirements for identification specified in Section 260553 "Identification for Electrical Systems."

B. Identify data and communications system components, wiring, and cabling according to TIA- 606-B; label printers shall use label stocks, laminating adhesives, and inks complying with UL 969.

C. Identify each wire on each end and at each terminal with a number-coded identification tag.

Each wire shall have a unique tag.

3.08 FIELD QUALITY CONTROL

A. Perform tests and inspections.

B. General Tests and Inspections:

1. Visually inspect cable jacket materials for UL or third-party certification markings. Inspect cabling terminations to confirm color-coding for pin assignments, and inspect cabling connections to confirm compliance with TIA-568-C.1.

2. Visually inspect cable placement, cable termination, grounding and bonding, equipment and patch cords, and labeling of all components.

3. Test cabling for direct-current loop resistance, shorts, opens, intermittent faults, and polarity between conductors. Test operation of shorting bars in connection blocks. Test cables after termination, but not after cross-connection.

a. Test instruments shall meet or exceed applicable requirements in TIA-568-C.2.

Perform tests with a tester that complies with performance requirements in its "Test Instruments (Normative)" Annex, complying with measurement accuracy specified in its "Measurement Accuracy (Informative)" Annex. Use only test cords and adapters that are qualified by test equipment manufacturer for channel or link test configuration.

C. Balanced Twisted Pair Cable Testing

1. Wire-map test that reports open circuits, short circuits, crossed pairs, reversed pairs, split pairs, and improper terminations.

HVAC System Replacement 260523 - 6 Control-Voltage Electrical Power

Cables

2. Channel and permanent link tests for cable length, insertion loss, near-end crosstalk loss, power sum near-end crosstalk loss, equal-level far-end crosstalk loss, power sum equal-level far-end crosstalk, return loss, propagation delay, and delay skew. Performance shall comply with minimum criteria in TIA/EIA-568-B.2.

D. Retest and inspect cabling to determine compliance of replaced or additional work with specified requirements.

E. Document data for each measurement. Print data for submittals in a summary report that is formatted using Table 10.1 in BICSI TDMM as a guide, or transfer the data from the instrument to the computer, save as text files, print, and submit.

F. End-to-end cabling will be considered defective if it does not pass tests and inspections.

1. Remove and replace cabling where test results indicate that they do not comply with specified requirements. Retest until satisfactory.

G. Prepare test and inspection reports.

HVAC System Replacement 260526 - 1 Grounding and Bonding for

Electrical Systems

SECTION 260526

GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Grounding and bonding requirements.

B. Conductors for grounding and bonding.

C. Connectors for grounding and bonding.

1.02 RELATED REQUIREMENTS

A. Section 260519 - Low-Voltage Electrical Power Conductors and Cables: Additional requirements for conductors for grounding and bonding, including conductor color coding.

1. Includes oxide inhibiting compound.

B. Section 260553 - Identification for Electrical Systems: Identification products and requirements.

1.03 REFERENCE STANDARDS

A. IEEE 81 - IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Grounding System; 2012.

B. NECA 1 - Standard for Good Workmanship in Electrical Construction; 2023.

C. NEMA GR 1 - Grounding Rod Electrodes and Grounding Rod Electrode Couplings; 2022.

D. NETA ATS - Standard for Acceptance Testing Specifications for Electrical Power Equipment

And Systems; 2025.

E. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having

Jurisdiction, Including All Applicable Amendments and Supplements.

F. NFPA 780 - Standard for the Installation of Lightning Protection Systems; 2023.

G. UL 467 - Grounding and Bonding Equipment; Current Edition, Including All Revisions.

1.04 SUBMITTALS

A. Product Data: Provide manufacturer's standard catalog pages and data sheets for grounding and bonding system components.

B. Shop Drawings:

1. Indicate proposed arrangement for signal reference grids. Include locations of items to be bonded and methods of connection.

C. Manufacturer's Instructions: Indicate application conditions and limitations of use stipulated by product testing agency. Include instructions for storage, handling, protection, examination, preparation, and installation of product.

D. Field quality control test reports.

1.05 QUALITY ASSURANCE

A. Comply with requirements of NFPA 70.

B. Maintain at the project site a copy of each referenced document that prescribes execution requirements.

C. Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum…