09 65 16-06R2 SRE Transitions.pdf

PDF 15 MB Posted

Attached to
Z2DA--554-22-137 Renovate K1 SCI Residential Apartment (VA-22-00041954)
Solicitation number
36C25922R0040
Issued by

About this file

This solicitation is for renovation services at the Rocky Mountain Regional Veterans Affairs Medical Center in Denver, Colorado. The scope of work involves converting an existing residential apartment into a storage and repair area for powered wheelchairs along with computer workstations. An existing nursing office will be renovated into two flexible private treatment spaces. The contractor must comply with all applicable codes and regulations including NFPA, OSHA, and VA standards. The period of performance is ninety calendar days from notice to proceed. The selected contractor will be responsible for project management documentation, site safety plans, permits, schedules, and quality control to ensure all work meets specifications and acceptance standards of the VA.

View the file

Other files

File Type Posted
Pre-Bid Site Visit Attendance Renovate K1 SCI Residential Apt.docx DOCX document
36C25922R0040 0010.docx DOCX document
S04 -Site Visit Meeting Doc 6.9.22.docx DOCX document
36C25922R0040 0009.docx DOCX document
36C25922R0040 0008.docx DOCX document
08 71 00-07R1 - IBN Interior Door Hardware Resubmittal.pdf PDF
08 14 00-03R1 - IBN - Wood Door Resubmittal.pdf PDF
08 14 00-03 - IBN - Wood Door Submittal.pdf PDF
36C25922R0040 0007.docx DOCX document
08 71 00-07 - IBN Hardware.pdf PDF
Questions Amend 7.docx DOCX document
36C25922R0040 0006.docx DOCX document
36C25922R0040 0005.docx DOCX document
36C25922R0040 0004.docx DOCX document
K1 Apartment Door Product Literature.pdf PDF
K1 Apartment Level 1 Arch Plan.pdf PDF
K1 Apartment Door Hardware Schedule.pdf PDF
K1 Apartment Door Hardware Data.pdf PDF
K1 Apartment Level 1S Arch Plan.pdf PDF
K1 Apartment Door Submittals.pdf PDF
36C25922R0040 0003.docx DOCX document
36C25922R0040 0002.docx DOCX document
S04 -Site Visit Meeting Doc.docx DOCX document
Pre-Bid Sign In Sheet.pdf PDF
36C25922R0040 0001.docx DOCX document
Past Performance Questionnaire.docx DOCX document
Combined Spec.pdf PDF
Pages from 09 68 00-02 Carpet.pdf PDF
36C25922R0040_1.docx DOCX document
Pages from 09 65 16-06R1 Sheet Flooring.pdf PDF
Combined Drawings.pdf PDF
ICRA MASTER-RMR.docx DOCX document
Show all 32

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

na ç ir. - nn - p9

RETURN OF SUBMITTAL

title Ur Description Date: Spec. Section:

lBS - IBN - Floorz Resilient Floorina Submittal Plans SD's0965 16
Contractor's Name and AddressStation Location:

Chris Bantner 13611 East Colfax Ave.

Aurora, CO 80045

Kiewit-Turner. a Joint Venture Contract No: Project No:

13611 East Colfax AvenueVAI01F-15-C-0005 554-501
Aurora, CO 80045Transmittal Date:VA File No:

8/28/2015 0965 16- 006- R2

Submittal Scone 09 65 16 - IBS-IBN - Floorz Resilient Flooring WSF 01-10

Submittal Items Acted Upon

Submittal Item Status

001 - IBS - IBN - Floorz Resilient Flooring Submittal APP- Approved Plans SD's WSF 01-10

Supplier or Manufacturer Submittal Type

Floorz Shop Drawings Notes/Comments

APPROVED. Questions or comments can be directed to John Calzada 720-857-5188

Signature of Authorizing Official

I

Date

Fax: 303.930.9001

303.930.9000Tel:

Kiewit - Turner a Joint Venture

Suite A-300 7200 S. Alton Way

Englewood, CO 80112

Job: 15387 - Replacement Medical Center Facility

Product Data

Sample

Other

Shop Drawing

Resubmittal

First Submittal X

VA Proj #:

To: H+L Architecture 1755 Blake Street

Suite 400

Denver, CO 80202

DESCRIPTIONSpecificationSUBMITTAL

ItemQuantity Section Sub./SupplierNo. Mfgr.

ACTION

DCBA E

Kiewit Submittal No. 22 13 00-01 Architect's Submittal No. 00008

Review Cycle: 001

Attn: Chuck Adkisson

1 SWPPP - CBS & RFP #3 OnlyKiewit - Turner a

Joint Venture

01 573

ACTION TAKEN

CONTRACTOR'S SIGNATURE:

CONTRACTOR'S NOTES:

DATE: 7/12/2011

Reviewed Only for Revisions to

Reviewed: Incorporate Changes

Reviewed=

A

B

C

Previous Submittal

Revise and Resubmit=D

Rejected =E

ARCHITECT/ENGINEER RESPONSE:

REMARKS:

BY: DATE:

Expedition f_sb_pks_01a

VA101CFM-C-0100

Cc: Tim Pogany, U.S. Dept. of Veterans Affairs

Received By ___________________

Date _______________

09 65 16

X

IBS IBN Floorz Resilient Flooring Submittal Plans SD's

X

Floorz, LLLP

09 65 1606R2

08/28/2015

09/11/2015

Kiewit-Turner Submittal No.

VA 1

JVT 2

REQUESTED RETURN DATE:

Kevin Lindsey, U.S. Dept. of Veterans Affairs

VA101F-15-C-0005

13611 E. Colfax Avenue 2nd Floor Aurora, CO 80045

VHAECHBoltoT Received

These shop drawings/submittals have been reviewed in accordance with the provisions of the Contract Documents. Kiewit-Turner's review shall not serve to relieve Subcontractors or Suppliers of contractual responsibilities for any error or deviation from contract and subcontract requirements.

KIEWIT-TURNER

a Joint Venture

REVIEWED - NO COMMENTS MADE

REVIEWED WITH COMMENTS

RESUBMITTAL REQUIRED

DATE SIGNED

SUBMITTAL #:

Brett Dickerson

8/28/15

09 65 16-06R2 x

Kiewit-Turner a Joint Venture

7200 S. Alton Way, Suite A-300, Englewood, CO 80112

Phone: 303-930-9000 FAX: 303-930-9001

Project Name:

Subcontractor Name: Submittal Date: 07/29/2015 Contact Name: E-mail: Return By Date:

Contact Phone(s): Review Days: 21

Number: Name:

1.4.C.3 n/a Y N N YX

M e e ts

A ll

S p e c

R e q u ir e m e n ts

E x c e p ti o n s o r

V a ri a n c e s f ro m S p e c

A p p ro v e r

In fo rm a ti o n

N e e d e d

I n

T h is P a c k a g e

Submittal Type

Submittal Item Description Manufacturer

(303) 574-0777

Specification Section: 09 65 16 IBN & IBS - Resilient Sheet Flooring

S p e c

S u b m it ta l

P a ra g ra p h

S p e c

P ro d u c t

P a ra g ra p h

S p e c if ie d o r L is te d

M a n u fa c tu re r?

SUBMITTAL INDEX & COVER SHEET

Department of Veteran's Affairs

Replacement Medical Center

FloorZ, LLLP07/

Nicole Kammerer nkammerer@osfloorz.com 08/14/2015

Reviewed By Date 8/13/2014

Submittal is in Compliance

Submittal is in Compliance with Variances from Specifications

Signature Brett Dickerson

Floorz, LLLPShop Drawing - WSF 01 - 10

SubmittalIndexForm_041009 Page 1 of 1

X Brett Dickerson

8/28/15 9/10/15

Y

-05R2 mailto:nkammerer@osfloorz.com

6" FC outside corner

Transition resilient flooring to conc Johnsonite EG-49-J Beige

Transition carpet to resilent Johnsonite CTA-49-D Beige

WSF02 Armstrong

WSF07 Lonseal Lonwood Natural Heiko Gentle Wind 7462

WSF01 Armstrong Medintone Powder Chocolate H8316

0 (99% of Scale); Bldg 04 IBS Inpatient Building South; Projects 10 v1.0; 7/27/2015 03:42 PM

04.AI.100

Transition - Resilient to Resinous Flooring (Transition Strip Provided by Resinous Contractor)

Transition - Resilient to Ceramic Tile Flooring (Transition Strip Provided by Ceramic Contractor)

Transition - Resilient to Resilient Flooring (Transition Strip not needed per Detail 8/XX.AI.771)

Transition carpet to resilent Johnsonite CTA-49-D Beige

WSF07 Lonseal Lonwood Natural Heiko Gentle Wind 7462

WSF02 Armstrong

WSF08 Lonseal Lonwood Natural Heiko Thunderstorm 7463

2 Transition - WSF to SVT

Transition - WSF Heat Weld

1 Transition - WSF to Epoxy

4 Transition - WSF to VCT

04.AI.101

- APP in Submittal # 09 67 23.20/60)

- APP in Submittal # 09 30 00-05)

- (Attachment D)

- (Attachment A)

- (Attachment B)

- (Attachment C)

- (Attachment E)

8-9/

* Note - On some drawings, please disregard material overlap; does not affect quantities.

Transition carpet to resilent Johnsonite CTA-49-D Beige

WSF07 Lonseal Lonwood Natural Heiko Gentle Wind 7462

WSF02 Armstrong

WSF08 Lonseal Lonwood Natural Heiko Thunderstorm 7463

04.AI.102

WSF02 Armstrong Medintech Sand Light H8319

Transition carpet to resilent Johnsonite CTA-49-D Beige

Transition resilient flooring to conc Johnsonite EG-49-J Beige

WSF07 Lonseal Lonwood Natural Heiko Gentle Wind 7462

04.AI.103

WSF07 Lonseal Lonwood Natural Heiko Gentle Wind 7462

Transitions

WSF01 Armstrong Medintone Powder Chocolate H8316

05.AI.100

8' 3"

WSF07 Lonseal Lonwood Natural Heiko Gentle Wind 7462

WSF08 Lonseal Lonwood Natural Heiko Thunderstorm 7463

WSF08 Lonseal Lonwood Natural Heiko Thunderstorm 7463

WSF08 Lonseal Lonwood Natural Heiko Thunderstorm 7463

WSF02 Armstrong Medintech Sand Light H8319

Transitions

Transition carpet to resilent Johnsonite CTA-49-D Beige

Transition resilient flooring to conc Johnsonite EG-49-J Beige

05.AI.101_JSI058.pdf (99% of Scale); Bldg 05 IBN Inpatient Building North; Projects 10 v1.0; 7/29/2015 11:12 AM

2 Transition - WSF to SVT

Transition - WSF01 Heat Weld

1 Transition - WSF to Epoxy

4 Transition - WSF to VCT

05.AI.101

WSF02 Armstrong Medintech Sand Light H8319

WSF08 Lonseal Lonwood Natural Heiko Thunderstorm 7463

WSF08 Lonseal Lonwood Natural Heiko Thunderstorm 7463

Transition carpet to resilent Johnsonite CTA-49-D Beige

Transition resilient flooring to conc Johnsonite EG-49-J Beige

05.AI.102_JSI058.pdf (99% of Scale); Bldg 05 IBN Inpatient Building North; Projects 10 v1.0; 7/29/2015 11:09 AM

05.AI.102

WSF02 Armstrong Medintech Sand Light H8319

WSF08 Lonseal Lonwood Natural Heiko Thunderstorm 7463

WSF08 Lonseal Lonwood Natural Heiko Thunderstorm 7463

Transitions

WSF06 Armstrong Medintone Tea Green Mid H8332

Transition carpet to resilent Johnsonite CTA-49-D Beige

Transition resilient flooring to conc Johnsonite EG-49-J Beige

05.AI.103_JSI058.pdf (99% of Scale); Bldg 05 IBN Inpatient Building North; Projects 10 v1.0; 7/29/2015 11:06 AM

05.AI.103

Johnsonite carpet to resilient transition, color #49 Beige

ATTACHMENT A

Carpet

Resilient

Johnsonite resilient to concrete, color #49 Beige

ATTACHMENT B

Resilient

DOOR (CLOSED) AND TRANSITION

DOOR FRAME BEYOND

CERAMIC TILE AS

SCHEDULED W/ CRACK-

SUPPRESSION

MEMBRANE

DOOR WHERE OCCURS.

FLOAT CONCRETE FLOOR SLAB

FOR GRADUAL SLOPE TO ALIGN

FLOOR FINISH MATERIALS

TOP OF CARPET PILE

TOP OF TILE

STAINLESS STEEL EDGE TRIM

CARPET AS SCHEDULED

SLOPE

1:20

1/

SANITARY STOP BEYOND

SEE DOOR SCHEDULE FOR DOOR

TYPE (WHERE DOOR OCCURS)

CARPET

CONCRETE AS SCHEDULED

RESILIENT TRANSITION STRIP

DOOR (CLOSED) AND TRANSITION

FLOAT CONCRETE FLOOR SLAB FOR

GRADUAL SLOPE TO ALIGN FINISH

FLOORING MATERIALS

SILICONE SEALANT AT JOINT

(1/8" MAXIMUM)

TOP OF CARPET PILE

TOP OF FINISHED FLOOR

DOOR WHERE OCCURS

RESILIENT TRANSITION STRIP

CARPET OR ENTRANCE

FLOOR MAT AS SCHEDULED

RESILIENT FLOORING AS SCHEDULED

SLOPE 1:20 MAX.

1/

FLOOR FINISH

SEE SCHEDULE THINSET OVER

CRACK SUPPRESSION MEMBRANE

TILE

SOLID SURFACE

THRESHOLD

1/ 4"

M A

X

SILICONE SEALANT TO MATCH GROUT

1/ 2"

M A

X

DOOR (CLOSED) AND TRANSITION

DOOR FRAME BEYOND

DOOR WHERE OCCURS.

4"

FLOOR FINISH

SEE SCHEDULE

WALL BEYOND WHERE OCCURS

THINSET OVER

CRACK SUPPRESSION MEMBRANE

TILE

SOLID SURFACE

THRESHOLD

1/ 4"

M A

X

SILICONE SEALANT TO MATCH GROUT

1/ 2"

M A

X

4"

RESILIENT TRANSITION STRIPCONCRETE AS

SCHEDULED

SEE DOOR SCHEDULE

FOR DOOR TYPE

WHERE DOOR OCCURS

RESILIENT FLOORING AS SCHEDULED

DOOR (CLOSED) AND TRANSITION STRIP

RESILIENT FLOORING AS

SCHEDULED

RESILIENT FLOORING

AS SCHEDULED

SEE DOOR SCHEDULE

FOR DOOR TYPE

WHERE DOOR OCCURS

HEAT WELD MATERIALS

AS SPECIFIED

DOOR (CLOSED) AND TRANSITION STRIP

THICKER RESILIENT

FLOORING AS SCHEDULED

THINNER RESILIENT FLOORING

AS SCHEDULED

SEE DOOR SCHEDULE

FOR DOOR TYPE

WHERE DOOR OCCURS

HEAT WELD MATERIALS

AS SPECIFIED

DOOR (CLOSED) AND TRANSITION

FLOAT CONCRETE FLOOR SLAB FOR

GRADUAL SLOPE TO ALIGN FINISH

FLOORING MATERIALS, SLOPE 1:20 MAX

STAINLESS STEEL EDGE

PROTECTION,CONTINUOUS

DOOR AS SCHEDULED

RESILIENT FLOORING AS

SCHEDULED - SEALED

CONC AT SIM LOCATION

DOOR (CLOSED) AND TRANSITION STRIP

EPOXY FLOORING AS

SCHEDULED

SILICONE SEALANT

@ JOIN 1/8" MAX

CONC TOPPING

SLAB AT WHERE

RECESSED CONC

SLAB OCCURS

FILLET STRIP

SHEET VINYL AS SCHEDULED

ZERO EDGE COVE CAP

CONTINUOUS SEALANT

BETWEEN COVE CAP

AND FINISHED WALL

PARTITION AS SCHEDULED

SCHEDULED

PARTITION

SETTING MATERIALS,

AS SPECIFIED

FLOOR TILE, AS SCHEDULED

SEALANT TO MATCH GROUT

SEALANT

WALL TILE, AS

SCHEDULED

NOTE:

ALIGN VERTICAL JOINTS ON WALL W/ JOINTS ON FLOOR

PROVIDE MANUFACTURER'S FINISHED TRIM UNITS AS REQUIRED

CONCRETE SLAB

CRACK-SUPPRESSION

MEMBRANE OVER CONCRETE

GROUT

1/ 4"

M

IN

FLEXIBLE EPOXY BASE

COAT AT WET LOCATIONS

ROUGHEN CONC. SURFACE

6"-12" IN DIAMETER AROUND

DRAIN TO INCREASE

BONDING DRAIN WITHOUT

SECONDARY WEEPS

RESINOUS EPOXY

TOP COAT

ADJUSTABLE

HEIGHT STRAINER

BACKER ROD

AND SEALANT

1/4"/FT SLOPE

MAX

1/4"/FT SLOPE

MAX

FLOOR DRAIN

CERAMIC TILE. THIN SET

ON WATERPROOF

MEMBRANE ON SLOPED

MORTAR BED OVER

SLAB DEPRESSION

CLAMP WATER PROOF

MEMBRANE INSIDE

DRAIN BODY

SLOPED MORTAR BED

BOUNDED WATER

PROOF MEMBRANE

1/4"/FT SLOPE

MAX

1/4"/FT SLOPE

MAX

STANDARD METAL

COVE STRIP

TOP COAT

MORTAR

3/16" PLASTIC FLOOR STRIP

CONTINUOUS SEALANT

BETWEEN COVE CAP AND

FINISHED WALL

R E

: R O

O M

F

IN

IS

H

S C

H E

D

4" U

.N .O

FLOORING AS SCHEDULED

SCHEDULED PARTITION

CONTINUOUS CLEAR SEALANT

AT TOP AND BOTTOM OF

BASE WHERE OCCURS

COVE BASE AS

SCHEDULED

SEALANT

GROUT COAT

MORTAR

3/16" PLASTIC FLOOR STRIP

GLAZED CMU

UN-GLAZED CMU

INTEGRAL COVED

EPOXY BASE

UNTOOLED, FLAT

MORTAR JOINT

U N

G

LA

Z E

D C

M U

G

LA

Z E

D C

M U

GROUT COAT

MORTAR

3/16" PLASTIC FLOOR STRIP

CONTINUOUS SEALANT

BETWEEN COVE CAP AND

FINISHED WALL

R E

: R O

O M

F

IN

IS

H

S C

H E

D

4" U

.N .O

EPOXY WALL PANEL ON

SUBSTRATE W/ BEVELED

EDGE AT BASE

EPOXY FLOORING;

RE: FINISH SCHEDULE

SSTL PIT LINER

SSTL GRATING

TREAD AND

SUPPORT RODS

SELF-LEVELING

CEMENTITIOUS

UNDERLAYMENT - FILL AS

NECESSARY TO OBTAIN

MANUFACTURERS

RECOMMENDED PIT

DEPTH AND TO ALIGN TOP

OF GRATING W/

ADJACENT FINISH FLOOR

3/4"x3/4"x1/8"

SSTL ANGLE

5/ 8"

ALIGN

RESILIENT FLOORING

AS SCHEDULED

M A

X 1/

2"

SLOPING TILE @

SHOWER FLOOR

SEALANT TO

MATCH GROUT

FLOOR TILE @ ROOM

BULLNOSE GROUND EDGE

WATERPROOFING

MEMBRANE

REINFORCING

SLOPED MOTAR BED

SCHEDULED

PARTITION

FLOOR TILE -

RE: FINISH SCHED

SEALANT TO

MATCH GROUT

WALL TILE, AS

SCHEDULED

NOTE: ALIGN VERTICAL JOINTS ON WALL W/ JOINTS ON FLOOR

PROVIDE MANUFACTURER'S FINISHED TRIM UNITS AS REQUIRED

SLOPED CONC BACKFILL

CRACK-SUPPRESSION

MEMBRANE OVER

CONCRETE

GROUT

TRENCH DRAIN

ASSEMBLY

WATERPROOF MEMBRANE

DRAIN PIPE

BEYOND

CONC FLR SLAB -

RE: STRUCT DWGS

8" M

IN

1/4"/FT SLOPE

MAX

TILE EDGING (BOTH SIDES)

FLOOR TILE -

RE: FINISH SCHEDULE

SLOPED CONC

BACKFILL

CRACK-SUPPRESSION

MEMBRANE OVER

CONCRETE

GROUT

TRENCH DRAIN

ASSEMBLY

WATERPROOF

MEMBRANE

DRAIN PIPE BEYOND

CONC FLR SLAB -

RE: STRUCT DWGS

1/4"/FT SLOPE

MAX

1/4"/FT SLOPE

MAX

TILE EDGING

(BOTH SIDES)

FIREPROOFING AS

REQUIRED AT

FLOOR - RE: FLS

PLANS FOR RATING

FLOOR SINK W/

GRATE - RE: PLUMB

EPOXY FLOORING -

RE: ROOM FIN SCHED

8"

ALIGN

GROUT TO FINE

ADJUST HEIGHT

AS REQUIRED

CONT ALUM

TRANSISTION STRIP

SET IN SEALANT

SEALED CONCRETE

AS SCHEDULED

SEE DOOR SCHEDULE

FOR DOOR TYPE

WHERE DOOR OCCURS

EPOXY FLOORING -

RE: FINISH SCHEDULE

DOOR (CLOSED) AND TRANSITION STRIP

11 12 08 09 13

03040506

Drawing Number

Building Number

Project NumberProject Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

Key Plan

CONSULTANTS:

DateRevisions

1 2 3 4 5 6 7 8 9 10 11 12

D

C

B

A

554-501REPLACEMENT MEDICAL CENTER

FACILITY, EASTERN COLORADO

HEALTH CARE SYSTEM

AURORA, COLORADO

N

C O

N

R

E S

D A

T

IB

S

IB

N

E

N C

C

LC

C B

N

C

B C

C B

S

P

S N

P V

N

P

V S

13 14

1 2 3 4 5 6 7 8 9 10 11 12 13 14

E

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

ARCHITECT/ENGINEERS:

H+L Architecture 1755 Blake Street, Suite 400 Denver, CO 80202

Skidmore, Owings & Merrill LLP 224 South Michigan Avenue Suite 1000 Chicago, IL 60604

Cator, Ruma & Associates 896 Tabor Street Lakewood, CO 80401

S. A. Miro, Inc.

4582 South Ulster Street Pkwy.

Suite 300 Denver, CO 80237

Professional Seal

8/

/2

9:

:2

A

M C

:\U se rs \b br ab ec \D es kt op \A

I- T

Y P

IC

A

L D

E T

A

IL

S .r vt

XX.AI.771

FINISH DETAILS

08/31/2012

3" = 1'-0"1

TYP. TRANSITION CARPET

TO CERAMIC TILE

3" = 1'-0"2

TYP. TRANSITION CARPET

TO CONCRETE

3" = 1'-0"3

TYP TRANSITION CARPET

TO RESILIENT FLOORING

3" = 1'-0"5

TYP. TRANSITION FROM

CERAMIC TILE

3" = 1'-0"6

TYP. TRANSITION TO

CERAMIC TILE W/O DOOR

3" = 1'-0"7

TYP. TRANSITION CONC. TO

RESILIENT FLOORING

3" = 1'-0"8

TYP. TRANSITION @ SAME

THICKNESS RESILIENT

3" = 1'-0"9

TYP. TRANSITION @

DIFFERENT THICKNESS

RESILIENT

3" = 1'-0"10

TYP. TRANSITION

RESILIENT TO EPOXY

3" = 1'-0"11

TYP INTEGRAL COVED

WELDED SHEET FLOORING

3" = 1'-0"14 TYP. BASE @ CERAMIC TILE

3" = 1'-0"16

TYPICAL SHOWER DRAIN @

RESINOUS FLOORING

3" = 1'-0"17

TYPICAL FLOOR DRAIN @

CERAMIC TILE

6" = 1'-0"12

TYP. COVE @ EPOXY

FLOORING

3" = 1'-0"13 TYP. RUBBER BASE - COVE

3" = 1'-0"19

TYP. COVE DETAIL @ EPOXY

FLOORING & GLAZED CMU

6" = 1'-0"20

COVE @ EPOXY FLOORING -

PROJECTING WALL FINISH

6" = 1'-0"21

TYPICAL FLOOR GRATING

TRANISTION DETAIL

6" = 1'-0"18

TYPICAL SHOWER

THRESHOLD

3" = 1'-0"22

TYPICAL SHOWER TRENCH

DRAIN @ CERAMIC TILE

3" = 1'-0"23

TYPICAL SHOWER TRENCH

DRAIN @ SHOWER CENTER

3" = 1'-0"24 TYPICAL FLOOR SINK

3" = 1'-0"4

TYP. TRANSITION CONC. TO

EPOXY FLOORING

CDI No.12 08/31/2012

See RFI 1511

KT RFI 2364 (VA RFI

2068) Provide a manufacturer standard, silicone sealant joint transition detail similar to base detail 20/XX.AI771, between the epoxy wall panel (RESWC-1) and scheduled ceiling.

KT RFI #5954/VA #5223:

Acceptable to float the subfloor to the solid surface thresholds, up to 2% per ADA requirement.

The top of finished floor needs to maintain the 1/2" MAX dim from top of finish floor to top of threshold.

KT RFI #3165 / VA RFI #2939

The "waterproof membrane" shown is not a "vapor barrier".

The waterproof membranes are required as shown.

ATTACHMENT C & D

ATTACHMENT E

ATTACHMENT C

ATTACHMENT D

Float included w/sub