This solicitation and related project file specify requirements for replacing refrigerators and freezers at a Veterans Affairs medical center. The solicitation will be issued as a 100% Service-Disabled Veteran-Owned Small Business set-aside requesting proposals to replace NFS and pharmacy refrigerators and freezers at the Overton Brooks VA Medical Center in Shreveport, Louisiana. The project number is 667-21-101 with an estimated construction cost between $500,000 and $1,000,000. Proposals will be due around July 7, 2021 with contract award anticipated within 30 days thereafter. The contract performance period is 180 days from notice to proceed. The NAICS code is 236220 with a small business size standard of $39.5M. Offerors must represent SDVOSB status and verification in SAM and VIP databases at proposal submission.
View the file
Other files
Show 40 more
Latest 50 of 72 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION 08 90 00 LOUVERS AND VENTS
PART 1 - GENERAL
1.1 DESCRIPTION:
A. This section specifies fixed and operable wall louvers, door louvers and wall vents.
1.2 RELATED WORK:
A. Color of finish: To match existing.
1.3 SUBMITTALS:
A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B. Shop Drawings:
1. Each type, showing material, finish, size of members, operating devices, method of assembly, and installation and anchorage details.
C. Manufacturer's Literature and Data:
1. Each type of louver and vent.
D. Color samples.
1.4 APPLICABLE PUBLICATIONS:
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.
B. The Master Painters Institute (MPI): Approved Product List – Updated Monthly C. ASTM International (ASTM):
A240/A240M-14...........Chromium and Chromium-Nickel Stainless Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications A653/A653M-13...........Steel Sheet Zinc-Coated (Galvanized) or Zinc- Iron Alloy Coated (Galvannealed) by the Hot Dip Process A1008/A1008M-13.........Steel, Sheet, Carbon, Cold Rolled, Structural, and High Strength Low-Alloy with Improved Formability
PROJECT 667-21-101 REPLACE NFS & PHARMACY
REFRIGERATORS AND FREEZERS
VETERANS ADMINISTRATION, SHREVEPORT, LA
05-01-15
08 90 00 - B209-14.................Aluminum and Aluminum Alloy, Sheet and Plate B209M-14................Aluminum and Aluminum Alloy, Sheet and Plate (Metric) B221-14.................Aluminum and Aluminum Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes B221M-13................Aluminum and Aluminum Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes (Metric) D1187/D1187M-97(R2011)..Asphalt-Base Emulsions for Use as Protective Coatings for Metal D. National Association of Architectural Metal Manufacturers (NAAMM): AMP 500-06..............Metal Finishes Manual E. National Fire Protection Association (NFPA):
90A-15..................Installation of Air Conditioning and Ventilating Systems G. American Architectural Manufacturers Association (AAMA): 2605-13.................High Performance Organic Coatings on Architectural Extrusions and Panels H. Air Movement and Control Association, Inc. (AMCA): 500-L-07................Testing Louvers
PART 2 - PRODUCTS
2.1 MATERIALS:
A. Aluminum, Extruded: ASTM B221M (B221).
B. Stainless Steel: ASTM A240/A240M, Type 302B.
C. Galvanized Steel Sheet: ASTM A653/A653M; G90 min.
D. Carbon Steel and Sheet: ASTM A1008/A1008M (interior use louvers only).
E. Aluminum, Plate and Sheet: ASTM B209M (B209); alloy 3003 or 5005 with temper as required for forming.
F. Fasteners: Fasteners for securing louvers and wall vents to adjoining construction, except as otherwise specified or indicated in construction documents, to be toggle or expansion bolts of size and type as required for each specific type of installation and service condition.
1. Where type, size, or spacing of fasteners is not shown or specified, submit shop drawings showing proposed fasteners, and method of installation.
2. Fasteners for louvers, louver frames, and wire guards to be of stainless steel or aluminum with same finish as louvers.
3. Fasteners for louvers, louver frames and wire guards within mental health areas to be non-removable/tamper-proof type.
G. Inorganic Zinc Primer: MPI No. 19.
H. Bituminous Coating: ASTM D1187/D1187M; cold applied asphalt mastic emulsion.
2.2 EXTERIOR WALL LOUVERS:
A. General:
1. Provide fixed and operable type louvers of size and design shown.
2. Heads, sills and jamb sections are to have formed caulking slots or be designed to retain caulking. Head sections are to have exterior drip lip, and sill sections an integral water stop.
3. Furnish louvers with sill extension or separate sill as shown.
4. Frame is to be mechanically fastened or welded construction with welds dressed smooth and flush.
B. Performance Characteristics:
1. Weather louvers are to have a minimum of 45% percent free area and to pass 700 fpm free area velocity at a pressure drop not exceeding
0.15 inch water gage and carry not more than 0.01 ounces of water per square foot of free area for 15 minutes when tested per AMCA Standard 500-L.
2. Louvers are to bear AMCA certified rating seals for air performance and water penetration ratings.
C. Aluminum Louvers:
1. General: Frames, blades, sills and mullions (sliding interlocking type); 2 mm (0.078-inch) thick extruded 6063-T5 or –T52 aluminum. Blades to be drainable type and have reinforcing bosses.
2. Louvers, fixed: Make frame sizes 13 mm (1/2-inch) smaller than openings. Single louvers frames are not to exceed 1676 mm (66 inches) wide. When openings exceed 1676 mm (66 inches), provide twin louvers separated by mullion members.
| 3. | Louvers are to withstand the effects or gravity loads and the following wind loads and stresses within limits and under conditions indicated without permanent deformation of louver components, noise or metal fatigue caused by louver-blade rattle or flutter, or permanent damage to fasteners and anchors. |
| a. | Wind load acting inward or outward of not less than 1436 Pa (30lb. per sq. ft.). |
4. Louvers, operable: Louver frame opening sizes, single louver sizes and mullion requirements are to be as specified for fixed louvers.
a. Blades: Attach blades to frame with aluminum pivot pins through nylon bearings. Fasten each blade to stainless steel operation arms that are connected to minimum 3 mm (1/8-inch) thick stainless steel operating handle arranged for simultaneous operation of blades.
2.3 CLOSURE ANGLES AND CLOSURE PLATES:
A. Fabricate from 2 mm (0.078-inch) thick stainless steel or aluminum.
B. Provide continuous closure angles and closure plates on inside head, jambs and sill of exterior wall louvers.
C. Secure angles and plates to louver frames with screws, and to masonry or concrete with fasteners as indicated in construction documents.
2.4 WIRE GUARDS:
A. Provide wire guards on outside of all exterior louvers, except on exhaust air louvers.
B. Fabricate frames from 2 mm (0.078-inch) thick extruded or sheet aluminum designed to retain wire mesh.
C. Wire mesh to be woven from not less than 1.6 mm (0.063-inch) diameter aluminum wire in 13 mm (1/2-inch) square mesh.
D. Miter corners and join by concealed corner clips or locks extending not less than 57 mm (2-1/4 inches) into rails and stiles. Equip wire guards over 1219 mm (4 feet) in height with a mid-rail constructed as specified for frame components.
E. Fasten frames to outside of louvers with aluminum or stainless steel devices of same finish as louvers designed to allow removal and replacement without damage to the wire guard or the louver.
2.5 BLANK-OFF PANELS:
| A. | Uninsulated panels attached with clips or screws as follows: Panel finish is to be same finish applied to louvers. |
| 1. | Aluminum sheet for aluminum louvers, 1.27 mm (0.050 inch) minimum thickness. |
| 2. | Galvanized-steel sheet for galvanized-steel louvers, 1.02 mm (0.040 inch) minimum. |
3. Stainless-steel sheet for stainless-steel louvers, not less than
0.95 mm (0.038 inch) minimum.
B. Insulated laminated panels consisting of an insulating core surfaced on back and front with metal sheets and attached to back of louver with clips on screws and gasketed or sealant sealed perimeter. Panel finish is to be same finish applied to louvers.
1. Thickness: 25 mm (1 inch).
2. Aluminum sheet for aluminum louver 0.81 mm (0.032 inch) minimum.
| 3. | Galvanized-steel sheet for galvanized-steel louver 0.71 mm (0.028 inch) minimum. |
| 4. | Stainless-steel sheet for stainless-steel louvers 0.79 mm (0.031 inch) minimum. |
5. Insulating Core: Rigid, extruded-polystyrene foam.
2.6 WALL VENTS:
A. Fabricate exterior wall vents from either 4.7 mm (0.185-inch) thick aluminum plate or 6 mm (1/4-inch) thick cast iron, perforated in diamond lattice pattern, with not over 19 mm (3/4-inch) openings.
B. Vents are to have aluminum screen frame with aluminum alloy insect screening mounted on back of vent by means of 19 mm x 5 mm (3/4-inch by 3/16-inch) top and bottom bars screwed to grille.
C. Vent Frames in Masonry: Fabricate of 45 mm x 30 mm x 5 mm (1-3/4 inch by 1-1/4 inch by 3/16-inch) steel angles bolted with 6 mm (1/4-inch) diameter expansion bolts at jambs.
2.7 AIR INTAKE VENTS:
A. Fabricate exterior louvered wall ventilators for fresh air intake for air conditioning units from extruded aluminum, ASTM B221M (B221). Form with integral horizontal louvers and frame, with drip extending beyond face of wall and integral water stops.
B. Provide aluminum closures where shown for inside face of dummy vents.
C. Provide 0.8 mm (0.032-inch) thick aluminum sleeves where indicated in construction documents.
2.8 BRICK VENTS:
A. Vents are to be of size shown formed of approximately 3 mm (0.125 inch) thick cast aluminum, or 3 mm (0.118 inch) extruded aluminum.
B. Provide vents complete with aluminum screen frame with corrosion resistant insect screening mounted on back of vent.
C. Provide vents with required anchors.
2.9 FINISH:
A. In accordance with NAAMM Metal Finishes Manual: AMP 500-505 B. Aluminum Louvers Air Intake Vents, Wire Guards and Blank Off Panels:
1. Anodized finish a.AA-M10C22A44, Chemically etched medium matte, with electronically deposited metallic compound, Class I Architectural, 0.17 mm (0.7 mils) thick color anodic coating. Dyes will not be accepted.
2. Organic Finish: AAMA 2605 (Fluorocarbon coating) with total dry film thickness of not less than 0.03 mm (1.2 mil), color to match existing.
C. Aluminum Wall Vents: Sand blasted satin finish.
D. Stainless Steel: Mechanical finish No. 4 in accordance with NAAMM Metal Finishes Manual.
E. Galvanized Sheet Steel: Two-coat baked-enamel or powder-coat finish consisting of prime coat and thermosetting topcoat, with a minimum dry film thickness of 0.05 mm (2 mils).
1. Paint interior surfaces of lightproof louvers with two (2) additional finish shop coats of baked-on flat black enamel.
F. Steel: Surfaces of steel work, for which no other finish is specified, are to be cleaned free from scale, rust, oil and grease, and then given a light colored prime paint after fabrication, except ferrous metals concealed in finished work. Paint all contact surfaces of assembled work (except welded contact surfaces) with an additional shop coat of similar paint.
2.10 PROTECTION:
A. Provide protection for aluminum against galvanic action wherever dissimilar materials are in contact, by painting the contact surfaces of the dissimilar material with a heavy coat of bituminous coating (complete coverage), or by separating the contact surfaces with a performed synthetic rubber tape having pressure sensitive adhesive coating on one side.
B. Isolate the aluminum from plaster, concrete and masonry by coating aluminum with zinc-chromate primer.
C. Protect finished surfaces from damage during fabrication, erection, and after completion of the work. Strippable plastic coating on colored anodized finish is not approved.
PART 3 - EXECUTION
3.1 INSTALLATION:
A. Set work accurately, in alignment and where indicated in construction documents. Install plumb, level, free of rack and twist, and set parallel or perpendicular as required to line and plane of surface.
B. Furnish setting drawings and instructions for installation of anchors and for the positioning of items having anchors to be built into masonry construction. Provide temporary bracing for such items until masonry is set.
C. Provide anchoring devices and fasteners as shown and as necessary for securing louvers and vents to building construction as specified. Power actuated drive pins may be used, except for removal items and where members would be deformed or substrate damaged by their use.
D. Set wall louvers and vents in masonry walls during progress of the work. If wall louvers and vents are not delivered to job in time for installation in prepared openings, make provision for later installation. Set in cast-in-place concrete in prepared openings.
3.2 CLEANING AND ADJUSTING:
A. After installation, all exposed prefinished and plated items and all items fabricated from stainless steel and aluminum are to be cleaned as recommended by the manufacturer and protected from damage until completion of the project.
B. All movable parts, including hardware, are to be cleaned and adjusted to operate as designed without binding or deformation of the members, so as to be centered in the opening of frame, and where applicable, to have all contact surfaces fit tight and even without forcing or warping the components.
C. Restore louvers and vents damaged during installation and construction so no evidence remains of corrective work. If results of restoration are unsuccessful, as determined by Contracting Officer Representative (COR) damaged units and replace with new units.
- - - E N D - - -