751/21042. ABG; Milliken Nature Ctr @ Arch Rock - Restroom
Solicitation number
RFQ - 171 - 220000000529
Issued by
Mackinac County, Mackinac Island City, Michigan

About this file

This document is the construction drawings for the Milliken Nature Center at Arch Rock project for the State of Michigan. The project includes a 1,925 square foot nature center and toilet building located on Mackinac Island in Mackinac County, Michigan. The drawings cover civil, architectural, structural, mechanical, plumbing, and electrical components of the new construction. The project is being bid as a State of Michigan contract opportunity, with a bid due date of August 12, 2022. The contract will be awarded by the Department of Technology, Management, and Budget, State Facilities Administration. The construction must comply with various state and national building codes including the 2015 Michigan Building Code and 2012 NFPA 101 Life Safety Code.

The contract opportunity includes three alternates: deduct equipment of a greywater reuse system, add a solar photovoltaic system, and remove existing asphalt and replace with concrete. Pricing terms, set asides, and funding details are not provided in the drawings. The current environment and any incumbent contractors are also not specified.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F

IL

E N

U M

B E

R

S T

A T

E I N

D E

X N

U M

B E

R S

C o ns tr uc tio n

F in a l R e co rd

Is su e d f o r

P re lim in a ry

D a te

D E

S

IG

N A

N D

C O

N S

TR

U

C

TI

O N

D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L A

C H

R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

DESIGN TEAM

ARCHITECT/ENGINEER

T O

W E

R P

IN

K

S T

E R

.C O

M

A L L R

IG

H

T S

R E

S E

R V

E D

S H

E E

T T

IT

L

E

S H

E E

T N

U M

B E

R

O W

N E

R P

R O

J E

C T

T

IT

L E

D A

T E

MILLIKEN NATURE CENTER AT ARCH

ROCK

STATE OF MICHIGAN

Mackinac Island, Michigan

CONSTRUCTION DOCUMENTS

C O

V E

R S

H E

E T

-1

.0

G

A U

G U

S T

M

IL

L

IK

E N

N A

T U

R E

C E

N T

E R

A T

A R

C H

R O

C K

M a c k in a c I s la n d

M ic h ig a n

S T

A T

E O

F M

IC

H

IG

A

N

/2

.T

A P

A U

G U

S T

CIVIL CONSULTANT

2926 WEST MAIN STREET

KALAMAZOO, MI 49006

PHONE: 269.585.2051

MACKINAC ISLAND STATE PARK

6131 ARCH ROCK ROAD

MACKINAC ISLAND, MI 49757

242 E. KALAMAZOO AVE, SUITE 100

KALAMAZOO, MICHIGAN 49007

PHONE: 269.343.6133

FAX: 269.343.6633

PROJECT AREA

TOILET BUILDING: 1,025 SQ. FT.

NATURE CENTER: 894 SQ. FT.

TOTAL FINISHED PROJECT: 1,919 SQ. FT.

MECHANICAL & PLUMBING GENERAL

MP 001 MECHANICAL & PLUMBING SYMBOLS, ABBREVIATIONS,

AND GENERAL NOTES

MECHANICAL SITE

MS 101 MECHANICAL SITE PLAN

PLUMBING

P 000 FOUNDATION PLUMBING PLAN

P 101 FIRST FLOOR PLUMBING PLAN

P 150 PLUMBING ROOF PLAN

P 501 PLUMBING SCHEDULES AND DETAILS

MECHANICAL

M 101 FIRST FLOOR MECHANICAL PLAN

M 301 ENLARGED MECHANICAL PLANS & SECTIONS

M 501 MECHANICAL SCHEDULES AND DETAILS

M 601 TEMPERATURE CONTROLS

ELECTRICAL SITE

E 001 ELECTRICAL SYMBOLS AND GENERAL NOTES

ELECTRICAL SITE

ES 101 ELECTRICAL SITE PLAN

ELECTRICAL

E 101 FIRST FLOOR POWER PLAN

E 101.A2 FIRST FLOOR POWER PLAN - ALTERNATE 2

E 150.A2 ROOF PLAN

E 201 FIRST FLOOR LIGHTING PLAN

E 401 ELECTRICAL ONE LINE

GENERAL

G 001 COVER SHEET

G 003 INTERIOR PARTITION TYPES & DEVICE ALIGNMENT

GUIDELINES, TYPICAL SYMBOLS & GENERAL NOTES

G 101 FIRST FLOOR CODE COMPLIANCE PLAN

CIVIL

C 0.0 SITE SURVEY (BY OTHERS)

C 1.0 SITE DEMOLITION PLAN

C 2.0 SITE LAYOUT PLAN

C 3.0 SITE GRADING PLAN

C 3.1 SESC PLAN

C 3.2 SESC DETAILS

C 4.0 SITE UTILITY PLAN

C 5.0 LANDSCAPE PLAN

C 6.0 SITE DETAILS

C 6.1 SITE DETAILS

STRUCTURAL

S 001 GENERAL NOTES

S 002 STATEMENT OF SPECIAL INSPECTIONS

S 003 TYPICAL DETAILS

S 004 PRECAST WALL LOADING

S 101 FOUNDATION PLAN

S 201 ROOF FRAMING PLAN

S 202 UPPER ROOF FRAMING PLAN

S 301 FOUNDATION DETAILS

S 401 FRAMING DETAILS

S 402 FRAMING DETAILS

ARCHITECTURAL

A 101 FIRST FLOOR PLAN

A 103 ROOF PLAN

A 201 FIRST FLOOR REFLECTED CEILING PLAN

A 301 EXTERIOR ELEVATIONS

A 302 EXTERIOR ELEVATIONS

A 311 BUILDING SECTIONS

A 312 BUILDING SECTIONS

A 313 BUILDING SECTIONS

A 321 WALL SECTIONS

A 322 WALL SECTIONS

A 323 WALL SECTIONS

A 324 WALL SECTIONS

A 325 WALL SECTIONS

A 326 WALL SECTIONS

A 327 WALL SECTIONS

A 341 PRECAST PANELS

A 342 PRECAST PANELS

A 343 PRECAST PANELS

A 351 ENLARGED PLAN DETAILS

A 352 CEILING DETAILS

A 353 CAST STONE & CONCRETE SINK DETAILS

A 361 EXTERIOR SIGNAGE

A 421 ENLARGED PLANS, TYPICAL MOUNTING HEIGHTS,

BARRIER-FREE MOUNTING HEIGHTS AND ACCESSORY

MATRIX

A 451 DECK & RAILING

A 501 DOOR SCHEDULES, HEADER, JAMB, & FRAME

INFORMATION

A 601 FIRST FLOOR FINISH PLAN

A 611 MATERIAL SELECTION SCHEDULE & TYPICAL DETAILS &

INTERIOR ELEVATIONS

DRAWING INDEX ALTERNATES

ALTERNATE 1: DEDUCT EQUIPMENT OF GREYWATER REUSE SYSTEM

ALTERNATE 2: ADD SOLAR PHOTOVOLTAIC SYSTEM

ALTERNATE 3: REMOVE EXISTING ASPHALT AND REPLACE WITH CONCRETE

SITE ADDRESS

ISSUED FOR DATE

BUILDING: 2015 MICHIGAN BUILDING CODE AND 2012 NFPA 101 LIFE SAFETY CODE

ENERGY: 2015 MICHIGAN ENERGY CODE

PLUMBING: 2018 MICHIGAN PLUMBING CODE

MECHANICAL: 2015 MICHIGAN MECHANICAL CODE

FUEL GAS: (IFGC) 2015 INTERNATIONAL FUEL GAS CODE

ELECTRICAL: 2017 NATIONAL ELECTRICAL CODE WITH MICHIGAN AMENDMENTS

BARRIER-FREE: 2015 MICHIGAN BUILDING CODE AND 2009 ICC & C A117.1

USE GROUP: U & A

CONSTRUCTION TYPE: IIIB

AUTOMATIC SPRINKLERS: NO

REFFERANCE CODES

GENERAL PARTITION NOTES

1. NOT ALL WALL TYPES MAY BE USED ON PROJECT.

2. REFER TO CODE COMPLIANCE PLANS FOR LOCATIONS OF SMOKE AND FIRE-RATED

PARTITIONS.

3. ALL PARTITIONS EXTEND TO BOTTOM OF STRUCTURE, UNLESS NOTED OTHERWISE.

4. LINE OF STRUCTURE/DECK AS SHOWN AT THE HEAD CONDITION OF EACH PARTITION

TYPE IS DIAGRAMMATIC ONLY AND DOES NOT INDICATE EXACT CONSTRUCTION

CONDITIONS. TERMINATE RATED PARTITIONS AT UNDERSIDE OF STRUCTURAL DECK TO

MAINTAIN RATING. PROVIDE APPROPRIATE FRAMING AND GYPSUM BOARD TO OFFSET

AROUND STRUCTURE OR OTHER OBSTRUCTIONS, SUCH AS PIPING OR DUCTWORK.

5. PARTITIONS MAY TERMINATE AT STRUCTURAL MEMBERS WITH A RATING GREATER THAN

OR EQUAL THE PARTITION, PROVIDED THAT RATING IS CONTINUOUS TO STRUCTURAL

DECK ABOVE.

6. NON-RATED PARTITIONS THAT EXTEND TO STRUCTURE SHALL TERMINATE AT

UNDERSIDE OF STRUCTURAL DECK TO MAINTAIN A CONTINUOUS PLANE OF GYPSUM

BOARD AS A NOISE, SMOKE OR OTHER TYPE OF BARRIER.

7. ALL PARTITIONS EXTENDING TO STRUCTURE ABOVE SHALL TERMINATE WITH

DEFLECTION TRACK - SEE TYPICAL DETAILS ON THIS SHEET.

8. ALL GYPSUM BOARD PARTITIONS NOT EXTENDING TO THE STRUCTURE MUST BE

BRACED.

9. UL DESIGN NUMBERS REFER TO THE FIRE RESISTANCE DIRECTORY; UNDERWRITERS

LABORATORY, LATEST EDITION.

10. MISCELLANEOUS NON-RATED CHASES TO BE 5/8" GYPSUM BOARD ON 3 5/8" METAL

STUD FRAMING AT 16" O.C., UNLESS NOTED OTHERWISE.

11. MISCELLANEOUS FURRING AROUND COLUMNS TO BE 5/8" GYPSUM BOARD ON 11/2"

STUDS, UNLESS NOTED OTHERWISE.

12. FIRE-RATED PARTITIONS TO HAVE FIRE-STOPPING SEALANTS AT HEAD, SILL JUNCTURE

WITH DISSIMILAR MATERIALS, ETC. AND AROUND ALL PENETRATIONS AND OPENINGS.

13. CONSTRUCT ALL PARTITIONS WITH SOUND ATTENUATION BATTS WITH THE FOLLOWING

SOUND BATT THICKNESS: 2 1/2" OR LESS METAL STUD - 1 1/2" THICKNESS, 3 5/8"

OR LARGER METAL STUD - 3" THICKNESS. UNLESS NOTED OTHERWISE.

1X

METAL STUD/FURRING, CH STUD AND WOOD STUD KEY

METAL STUD/FURRING

DESIGNATION SIZE

A GYPSUM BOARD DIRECT APPLIED TO CMU

B 7/8"

C 1 1/2"

D 1-5/8"

E 2 1/2"

F 3 1/2"

G 3 5/8"

H 4"

J 5 1/2"

K 6"

L 8"

M 10"

N 12"

P (OPEN)

Q (OPEN)

CH STUD

DESIGNATION SIZE

R 2 1/2"

S 4"

T 6"

PARTITION TYPE TAG (REFER TO FLOOR PLANS)

PARTITION TYPE

NUMBER

METAL STUD, FURRING OR

CH STUD FRAMING LETTER

FIRE-RATING, IF REQUIRED

1X

WOOD STUD

DESIGNATION SIZE

U 2"x4"

V 2"x6"

W 2"x8"

INTERSECTION OF NON-RATED AT

1 HOUR RATED PARTITION

INTERSECTION OF NON-RATED AT 2 HOUR

RATED PARTITION - U.L. ASSEMBLY U425

1 HOUR RATED

PARTITION - REFER

TO PLAN

METAL STUD FRAMING

NON-RATED PARTITION - REFER TO PLAN

2 HOUR RATED

PARTITION -

REFER TO PLAN

METAL STUD FRAMING

NON-RATED PARTITION - REFER TO PLAN

INTERSECTION OF NON-RATED AT 2 HOUR

RATED PARTITION - U.L. ASSEMBLY U438

2 HOUR RATED

PARTITION -

REFER TO PLAN

CH STUD FRAMING

NON-RATED PARTITION - REFER TO PLAN

INTERSECTION OF

CONCRETE/MASONRY AT 1 HOUR

RATED PARTITION

CONCRETE OR MASONRY

WALL - REFER TO PLAN

1 HOUR RATED PARTITION -

REFER TO PLAN

METAL FURRING

GYPSUM BOARD CONTROL

JOINT NON-RATED PARTITION

• 1/2" MAXIMUM GAP FOR CONTROL JOINT

• 30'-0" MAX. BETWEEN CONTROL JOINTS

• REFER TO PARTITION TYPES FOR COMPLETE

DESCRIPTION OF COMPONENT PARTS

GYPSUM BOARD

METAL STUD FRAMING

BACKER

ROD AND

SEALANT

CONTROL JOINT

GYPSUM BOARD CONTROL

JOINT 1 HOUR RATED

PARTITION

• 1/2" MAXIMUM GAP FOR CONTROL JOINT

• 30'-0" MAX. BETWEEN CONTROL JOINTS

• REFER TO PARTITION TYPES FOR COMPLETE

DESCRIPTION OF COMPONENT PARTS

GYPSUM BOARD

METAL STUD FRAMING

(2) LAYERS TYPE

"X" GYPSUM

BOARD

CONTROL JOINT

GYPSUM BOARD CONTROL

JOINT 2 HOUR RATED

PARTITION

• 1/2" MAXIMUM GAP FOR CONTROL JOINT

• 30'-0" MAX. BETWEEN CONTROL JOINTS

• REFER TO PARTITION TYPES FOR COMPLETE

DESCRIPTION OF COMPONENT PARTS

METAL STUD FRAMING

(2) LAYERS TYPE "X"

GYPSUM BOARD

CONTROL JOINT

(2) LAYERS TYPE

"X" GYPSUM

BOARD

HEAD

PLAN

SILL

STRUCTURE /

DECK ABOVE

DEFLECTION TRACK

SEALANT

SOUND BATTS IN

ALL WALLS -

UNLESS NOTED

OTHERWISE

FLOOR CONSTRUCTION

METAL STUDS @ 16" O.C. WITH 5/8"

GYPSUM BOARD BACK SIDE, 5/8"

CEMENT BOARD AT ROOM SIDE;

(1 HOUR FIRE) U.L. ASSEMBLY U465

WHERE NOTED ON PLANS

METAL STUD WALL

HEAD

PLAN

SILL

STRUCTURE /

DECK ABOVE

DEFLECTION TRACK

SEALANT

SOUND BATTS (AT CHASE

WALLS ONLY) - UNLESS

NOTED OTHERWISE

FLOOR CONSTRUCTION

METAL STUDS @ 16" O.C. WITH 5/8"

CEMENT BOARD ON ROOM SIDE - BRACE

WALL @ 4'-0" O.C. MAXIMUM.

METAL STUD CHASE WALL OR

FURRING

C H A S E S

ID

E

R O

O M

S

ID

E

1X 2X

HEAD

PLAN

SILL

STRUCTURE /

DECK ABOVE

DEFLECTION TRACK

SEALANT

SOUND BATTS IN

ALL WALLS -

UNLESS NOTED

OTHERWISE

FLOOR CONSTRUCTION

METAL STUDS @ 16" O.C. WITH 3/4"

CEDAR PLYWOOD BOTH SIDES

METAL STUD WALL

3X

HEAD

PLAN

SILL

STRUCTURE /

DECK ABOVE

SEALANT

FLOOR CONSTRUCTION

PRECAST PANEL

PRECAST WALL

4X

NOTE:

MOUNT EQUIPMENT AS SHOWN UNLESS SPECIFIED OTHERWISE.

MAX TWO DEVICES IN ONE HIGHER MOUNT

LOCATION AT LATCH SIDE OF DOOR, PROVIDE RFI

IF MORE DEVICES ARE NECESSARY. WHERE THERE

IS ONE DEVICE, CENTER OVER LOWER DEVICE. (TO

BE WITHIN ADA HEIGHT). (IF SWITCH CANNOT BE

LOCATED ON LATCH SIDE, LOCATE ONE DOOR

LEAF AWAY ON HINGE SIDE.)

DOOR

LOW DEVICES

RECEPTACLEVOICE/DATA

MASONRY COURSING

(WHERE APPLICABLE)

LIGHT SWITCH

F.A. AUDIO/VISUAL

ALIGNMENT NOTES

• ALIGN AND LOCATE CLOSE TOGETHER ANY DEVICES INSTALLED WITHIN 6' HORIZONTALLY.

• CENTER ALL DEVICES WHERE INDICATED ON COLUMN WRAP OR BUMP OUT; STACK AND ALIGN VERTICALLY.

• INSTALL DEVICES AT HEIGHTS INDICATED IN SYMBOL LEGEND UNLESS STACKING PER THIS DETAIL.

• WHERE HEIGHT IS SPECIFICALLY NOTED ON FLOOR PLANS, USE THAT MOUNTING HEIGHT

• CENTER ON DOORFRAME OR WHITEBOARDS ANY DEVICES INDICATED ABOVE.

O R L

A N D

IN

G

F R O

M F

LO

O

R

F R O

M F

LO

O

R O

R L

A N D

IN

G

6' - 0" MIN.

4" MAX

CAMERAS, CLOCKS, WALL

OCCUPANCY SENSORS

WHITE BOARD (WHERE APPLICABLE -

VERIFY WITH DETAILS/PLANS PROPER

INSTALL HEIGHT) CENTER ANY SINGLE

DEVICE WITH CENTER OF WHITE BOARD

ANY DEVICES

SHOWN OVER DOOR

TO BE CENTERED.

EQ EQ

EQ EQ

F R O

M F

LO

O

R O

R L

A N D

IN

G

SHORT THROW PROJECTOR

WHERE APPLICABLE

~12"

FA PULL STATION - HINGE SIDE

OF DOOR 1-LEAF AWAY WITHIN

5'-0" OF EXTERIOR OR STAIR

DOORS, WHEN WALL MOUNT

STROBES ARE ON PROJECT,

ALIGN ABOVE.

WHEN DEVICES ARE WITHIN DIMENSION, STACK

HIGH/LOW VERTICALLY AND GROUP DEVICES AT

SAME HEIGHT. UNLESS DEVICES IS PART OF

TECHNOLOGY DETAIL GROUPING OR SERVING A

FURNITURE GROUP.

CASEWORK, COORDINATE DEVICE BOTTOM

TO BE 2" OVER BACKSPLASH OR OVER

COUNTERTOP (IF NO BACKSPLASH). FOR

LARGE FORMAT TILE, ALIGN EDGE OF DEVICE

WITH HORIZONTAL GROUT LINE CLOSEST TO

COUNTERTOP.

COORDINATE OUTLET LOCATIONS WITH

GROUT LINES, EDGE OF DEVICE ON GROUT

LINE IF POSSIBLE. COORDINATE WITH

INTERIOR DESIGN DRAWINGS.

TYPICAL COLUMN

ENCLOSURE, CHASE OR

BUMP-OUT WITH DEVICES

INDICATED IN PLANS.

EQ EQ

EQEQEQEQ

THERMOSTAT,

SENSORS OR AV

CONTROLLER, CARD

READER, ETC.

GENERAL DEMOLITION NOTES

1. CONTRACTORS ARE REQUIRED TO INSPECT/REVIEW THE EXISTING BUILDING PRIOR TO

RELATED DEMOLITION WORK. UNLESS NOTED OTHERWISE, REMOVAL OF ANY WALL,

FLOOR OR CEILING INCLUDES ALL GENERAL MECHANICAL AND ELECTRICAL ITEMS

WHICH ARE A PART OF, OR ATTACHED TO IT.

2. CONTRACTOR SHALL VERIFY ALL EXISTING JOB SITE CONDITIONS AND DIMENSIONS

AND BE RESPONSIBLE FOR THE SAME. ADVISE CONSTRUCTION MANAGER OF ANY

AND ALL DISCREPANCIES.

3. PATCH FLOORS, WALLS AND CEILINGS DAMAGED DURING CONSTRUCTION AND

DEMOLITION AS REQUIRED. FINISH TO MATCH EXISTING.

4. ACCOMMODATE NEW CONSTRUCTION IF NOT INDICATED.

5. PROTECT ALL EXISTING FINISHES THROUGHOUT PROJECT.

6. REFER TO DEMOLITION ELEVATIONS, SECTIONS AND DETAILS FOR ADDITIONAL

INFORMATION.

7. REFER TO STRUCTURAL, MECHANICAL, PLUMBING AND ELECTRICAL PLANS FOR

ADDITIONAL DEMOLITION NOTES.

8. SALVAGE ALL UNISTRUT AND PROTECT FOR RE-USE IN NEW CONSTRUCTION, IF

REQUIRED.

9. AT LOCATIONS OF REMOVED WALLS, ALL ASSOCIATED ITEMS ATTACHED TO THE WALL

ARE TO BE REMOVED. SUCH AS: DOORS, WINDOWS, FRAMES, MARKERBOARDS,

TACKBOARDS, TACK STRIPS, ETC.

GENERAL NOTES - ARCHITECTURAL

1. THE OWNER RESERVES THE RIGHT TO REMOVE ANY ITEM FROM THE PROJECT PRIOR

TO COMMENCEMENT OF CONTRACTED DEMOLITION WORK.

2. ALL EXISTING CONDITIONS SHOULD BE FIELD VERIFIED BEFORE WORK BEGINS.

3. DIMENSIONS GIVEN ARE ACTUAL AND ARE TO THE FACE OF MASONRY UNITS OR TO

THE FACE OF STUD FRAMING, UNLESS NOTED OTHERWISE.

4. DETAILS SHOWN ILLUSTRATE DESIGN INTENT, NOT ALL POSSIBLE CONDITIONS. FOR

CONDITIONS NOT SHOWN, USE DETAILS CLOSEST TO CONDITION IN QUESTION.

5. EXTEND ALL INTERIOR WALL PARTITIONS FROM FLOOR TO STRUCTURE/DECK ABOVE

UNLESS NOTED OR DETAILED OTHERWISE.

6. WITHIN BUILDING INTERIOR PROVIDE BULLNOSE BLOCK IN CMU WALL ASSEMBLIES AT

ALL EXPOSED OUTSIDE CORNERS, INCLUDING WINDOW AND DOOR JAMBS, UNLESS

NOTED OR DETAILED OTHERWISE. PROVIDE SQUARE OUTSIDE CORNERS AT ALL

LOCATIONS FINISHED WITH WALL TILE, REFER TO FINISH PLANS (A600 SHEETS)

FOR LOCATIONS.

7. TOOTH-IN MASONRY AT NEW OPENINGS IN EXISTING WALLS.

8. TOOTH-IN NEW MASONRY INFILL INTO EXISTING OPENINGS AT ALL BULLNOSE BLOCK

LOCATIONS.

9. STUD WALLS SPANNING OVER 12'-0" IN HEIGHT SHALL BE A MINIMUM OF 20 GAGE.

10. STUD WALL SUPPORTING WALL CABINETS SHALL BE A MINIMUM OF 20 GAGE.

11. DOORS ARE TO BE 4" FROM CORNER OF ROOM, UNLESS NOTED OR DIMENSIONED

OTHERWISE.

12. FIRESTOP ALL INTERCONNECTIONS BETWEEN VERTICAL AND HORIZONTAL SPACES AND

CONCEALED WALL SPACES AT CEILING, FLOOR AND ROOF LEVELS.

13. FIRESEAL ALL PENETRATIONS, SUCH AS, PIPES, DUCTS, CONDUITS, ETC. THROUGH

FIRE AND/OR SMOKE RATED ASSEMBLIES.

14. FOR CONTROL JOINT (C.J.) LOCATIONS REFER TO EXTERIOR ELEVATIONS AND/OR

FLOOR PLANS.

15. PAINT ALL ELECTRICAL PANEL COVERS AND ACCESS PANELS TO MATCH ADJACENT

FINISHES. USING OIL-BASED PAINT, NOT LATEX WALL PAINT.

16. PROVIDE WOOD BLOCKING IN WALLS THAT REQUIRE WALL MOUNTED EQUIPMENT OR

ACCESSORIES. COORDINATE WITH EQUIPMENT OR ACCESSORY MANUFACTURER.

17. PROVIDE ALL ASSOCIATED CURBS FOR ROOF TOP EQUIPMENT AND MECHANICAL

ROOF TOP UNITS. LARGE VOIDS BELOW THE AIR HANDLING UNITS SHALL BE FILLED

WITH INSULATION AS SPECIFIED FOR NOISE CONTROL.

18. ALL EXISTING ROOF TOP PENETRATIONS BEING REMOVED REQUIRE ROOF PATCHING

TO MATCH EXISTING ADJACENT.

A101A

TYPICAL SYMBOLS & REFERENCES

NOTE:

ROOM NAMES AND NUMBERS ON PLANS ARE

FOR CONSTRUCTION PURPOSES ONLY.

COORDINATE WITH OWNER REGARDING

PROPOSED NUMBERS FOR ALL SIGNAGE,

SCHEDULE AND PANEL DESIGNATIONS.

ROOM IDENTIFICATION TAG

ROOM NAME

ROOM NUMBER

DETAIL TITLE

1 DETAIL TITLE

1" = 0'-1"A101

DETAIL NUMBER

SHEET NUMBER

UNIT MATCHLINES

U N

IT

A

U N

IT

B

TYPICAL NOTATION SYMBOLS

CALLOUT REFERENCE BUBBLE

A351

DETAIL NUMBER

SHEET NUMBER

EXTERIOR ELEVATION REFERENCE BUBBLE

A301

A

ELEVATION LETTER

SHEET NUMBER

INTERIOR ELEVATION REFERENCE BUBBLE

4 A 652

ELEVATION NUMBER

SHEET NUMBER

DETAIL REFERENCE BUBBLE

A351

DETAIL NUMBER

SHEET NUMBER

BUILDING SECTION REFERENCE BUBBLE

A 311

DETAIL NUMBER

SHEET NUMBER

ELEVATION AND SECTION REFERENCE TOOLS

ELEVATION TAG - EXISTING

FINISH FLOOR

ELEVATION 100'-0"

ELEVATION TAG FOR EXTERIOR ELEVATIONS

AND BUILDING SECTIONS

100'-0" ELEVATION TAG FOR FLOOR PLANS AND

REFLECTED CEILING PLANS

ELEVATION TAG - NEW

FINISH FLOOR

ELEVATION 100'-0"

100'-0"

ELEVATION TAG FOR EXTERIOR ELEVATIONS

AND BUILDING SECTIONS

ELEVATION TAG FOR FLOOR PLANS AND

REFLECTED CEILING PLANS

WORKING POINT LAYOUT TAG

100'-0" : 100'-0"

DISTANCE IN THE "Y" DIRECTION FROM THE

"X" BASE LINE

DISTANCE IN THE "X" DIRECTION FROM THE

"Y" BASE LINE

BORROWED LIGHT AND DOOR IDENTIFICATION

A 502

SHEET NUMBER

ELEVATION NUMBER

DOOR NUMBER - CORRESPONDS TO THE ROOM NUMBER

LETTER DESIGNATES MORE THAN ONE IN ROOM

SYMBOLS

BARRIER-FREE

B1 REVISION IDENTIFIER (ADDENDUM AND BULLETIN)

COLUMN BUBBLE AND LINE

CLASSROOM

A000A

F

IL

E N

U M

B E

R

S T

A T

E I N

D E

X N

U M

B E

R S

C o ns tr uc tio n

F in a l R e co rd

Is su e d f o r

P re lim in a ry

D a te

D E

S

IG

N A

N D

C O

N S

TR

U

C

TI

O N

D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L A

C H

R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

T O

W E

R P

IN

K

S T

E R

.C O

M

A L L R

IG

H

T S

R E

S E

R V

E D

S H

E E

T T

IT

L

E

S H

E E

T N

U M

B E

R

O W

N E

R P

R O

J E

C T

T

IT

L E

D A

T E

IN

T

E R

IO

R

P A

R T

IT

IO

N T

Y P

E S

D

E V

IC

E

A L

IG

N M

E N

T G

U

ID

E L

IN

E S

T

Y P

IC

A

L S

Y M

B O

L S

G

E N

E R

A L N

O T

E S

-1

.0

G

A U

G U

S T

M

IL

L

IK

E N

N A

T U

R E

C E

N T

E R

A T

A R

C H

R O

C K

M a c k in a c I s la n d

M ic h ig a n

S T

A T

E O

F M

IC

H

IG

A

N

/2

.T

A P

A U

G U

S T

NOT TO SCALE

DEVICE ALIGNMENT GUIDELINES

ISSUED FOR DATE

T S

T S

F

F

EQ

C S

EQ

FS

FS

FS

C S

C S

CS CS CS CS CS

EQ

EQ

EQ

JB JB JB JB JB

JB JB JB JB JB

C S

1. ALL PENETRATIONS THROUGH A FIRE OR SMOKE RATED PARTITION SHOULD BE

SEALED WITH AN APPROVED U.L. RATED PRODUCT.

2. THE TOPS OF ALL FIRE RATED PARTITIONS SHALL BE SEALED TO THE

CONTINUOUS STRUCTURE ABOVE WITH A U.L. RATED SYSTEM OR ASSEMBLY.

3. WOOD BLOCKING IN FIRE-RATED PARTITIONS SHALL BE NON-COMBUSTIBLE

TREATED WOOD.

4. REFER TO SPECIFICATION U.L. RATING INFORMATION.

5. FIRE-RATED WALLS ENDING INTO AN ACOUSTICAL DECK MUST HAVE THE FLUTES

FILLED, REFER TO 'TOP OF WALL DETAIL AT ACOUSTIC DECK' SHOWN ON THIS

SHEET.

• FOR MASONRY WALLS THE MASON SHALL FILL VOIDS AND FIRE SPRAY WITH UL LISTED

MATERIAL.

• FOR STUD WALLS USE FIRE SAFING AND FIRE CAULK.

CODE COMPLIANCE KEY

EGRESS SYMBOLS

EGRESS EXIT NUMBER FROM ROOM OR SPACE

MAXIMUM NUMBER OF OCCUPANTS PERMITTED

BY EGRESS WIDTH

ROOM OR SPACE EGRESS IS FROM

TRAVEL DISTANCE : 100'-0"

PERMITTED TRAVEL DISTANCE - 200'-0"

EXISTING TRAVEL DISTANCE

TO EGRESS DOOR

PERMITTED MAXIMUM TRAVEL

DISTANCE PER CONDITION

DIRECTION OF EGRESS

FIRE SAFETY SYMBOLS

FIRE-RATING KEY

DESIGNATION PARTITION RATING PRIORITY

EGRESS

Door #

EGRESS ROOM

XFE

XFEC

FE

FEC

EXISTING FIRE EXTINGUISHER

EXISTING FIRE EXTINGUISHER CABINET

FIRE EXTINGUISHER

FIRE EXTINGUISHER CABINET

AED

AUTOMATED EXTERNAL DEFIBRILLATIOR (AED)

RECESSED CABINET

3 HOUR 1

2 HOUR FIRE/SMOKE 2

2 HOUR 3

1 HOUR FIRE/SMOKE 4

1 HOUR 5

SMOKE RESISTANT 6

FE

FE

TRAVEL DISTANCE : 54' - 8"

PERMITTED TRAVEL DISTANCE - 75' - 0"

TRAVEL DISTANCE : 54' - 9"

PERMITTED TRAVEL DISTANCE - 75' - 0"

TRAVEL DISTANCE : 29' - 4"

PERM

ITTED TRAVEL DISTANCE - 75' - 0"

TR

A V E L D

IS

T A N C E : 32' -

9"

P E R M

IT

TE

D

TR

A V E L D

IS

T A N C E

75' - 0"

F

IL

E N

U M

B E

R

S T

A T

E I N

D E

X N

U M

B E

R S

C o ns tr uc tio n

F in a l R e co rd

Is su e d f o r

P re lim in a ry

D a te

D E

S

IG

N A

N D

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

D E

P A

R T

M E

N T

O F

T E

C H

N O

L O

G Y

M

A N

A G

E M

E N

T A

N D

B U

D G

E T

S T

A T

E O

F M

IC

H

IG

A

N

A D

A M

P L A

C H

R

A D

IR

E

C T

O R

S T

A T

E F

A C

IL

IT

IE

S

A D

M

IN

IS

T

R A

T

IO

N

T O

W E

R P

IN

K

S T

E R

.C O

M

A L L R

IG

H

T S

R E

S E

R V

E D

S H

E E

T T

IT

L

E

S H

E E

T N

U M

B E

R

O W

N E

R P

R O

J E

C T

T

IT

L E

D A

T E

F

IR

S T

F L O

O R

C O

D E

C O

M P

L

IA

N C

E P

L A

N

-1

.0

G

A U

G U

S T

M

IL

L

IK

E N

N A

T U

R E

C E

N T

E R

A T

A R

C H

R O

C K

M a c k in a c I s la n d

M ic h ig a n

S T

A T

E O

F M

IC

H

IG

A

N

/2

.T

A P

A U

G U

S T

1/4" = 1'-0"

FIRST FLOOR CODE COMPLIANCE PLAN

THIS DRAWING SHEET IS INTENDED TO BE PLOTTED IN

COLOR. IF THIS TEXT APPEARS IN BLACK AND WHITE,

IT IS PLOTTED INCORRECTLY. DISCARD AND OBTAIN

AN ACCURATE DRAWING

INTERNATIONAL ENERGY CONSERVATION CODE:

C301: CLIMATE ZONE: 7

C303.1.3(1): DOUBLE GLAZED DOOR AND WINDOW METAL W/ THERMO BREAK

U-VALUE: .65 -- use .25 SHGC .23

C303.1.3(2): WOOD DOOR

U-VALUE: .5

C402.1.3

ROOF INSULATION ABOVE: R-35

PRECAST WALL PANEL ABOVE GRADE (MASS WALL): 15.2 CUBIC INCH

PRECAST WALL BELOW GRADE (MASS WALL): 15 CUBIC INCH

UNHEATED SLAB ON GRADE: R-15 TO 24" BELOW

R-VALUE

ROOF

2.5" RIGID INSULATION = 14.4 R-VALUE

3" RIGID INSULATION = 17.4 R-VALUE

1/2" COVER BOARD = .56 R-VALUE

WALL

1" CONCRETE = 0.063 R-VALUE

3" RIGID INSULATION = 17.4 R-VALUE

PRECAST 3, 3, 4 = (10") 17.78 R-VALUE

PRECAST 3, 3, 6 = (12") 17.90 R-VALUE

PLUMBING CODE:

419: URINALS

419.2: IN EACH BATHROOM OR TOILET

ROOM, URINALS SHALL NOT BE SUBSATUTED

FOR MORE THAN 67 PERCENT OF THE

REQUIRED WATER CLOSETS IN ASSEMBLY AND

EDUCATIONAL OCCUPANCIES. URINALS SHALL

NOT BE SUBSETUTED FOR MORE THAN 50

PERCENT OF THE REQUIRED WATER CLOSETS IN

ALL OTHER OCCUPANTIES.

GRAPHIC SCALE

0' 3' 6' 12' 18' 24'

BUILDING CODE:

303.4 ASSEMBLY GROUP A-3

504.3 ALLOWABLE BULIDING HEIGHT IN FEET ABOVE GRADE PLANE

OCCUPANCY CLASSIFICATION: A-3 - NON SPRINKLERED - 55 FEET

504.4 NUMBER OF STORIES ABOVE GRADE PLANE

OCCUPANCY CLASSIFICATION: F-1 - SPRINKLERED - 2 STORIES

1004.5 MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT

1. ASSEMBLY WITHOUT FIXED SEATS: 7 NET

1006.2.1 SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY

OCCUPANCY: A-3 - 49 MAXIMUM OCCUPANT LOAD OF SPACE

WITH SPRINKLER: 75 FEET

1006.3.1 MINIMUM NUMBER OF EXITS OR ACCESS TO EXITS PER STORY

OCCUPANT LOAD PER STORY: 1-500 PERSONS

MINIMUM NUMBER OF EXITS: 2

1006.3.3.2 STORIES WITH ONE EXIT OR ACCESS TO ONE EXIT FOR OTHER OCCUPANCIES

FIRST SOTRY ABOVE OR BELOW GRADE PLANE: OCCUPANCY A-3

MAXIMUM OCCUPANT LOAD PER STORY: 49 PERSON

MAXIMUM COMMON PATH OF EGRESS TRAVEL DISTANCE: 75 FEET

1017.2 EXIT ACCESS TRAVEL DISTANCE

OCCUPANCY: A-3

NON SPRINKLER SYSTEM: 200 FEET

2902.1 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES

FACTORY AND INDUSTRIAL:

WATER CLOSET

MALE: 1 PER 100

FEMALE: 1 PER 100

LAVATORIES

MALE: 1 PER 100

FEMALE: 1 PER 100

DRINKING FOUNTAINS: 1 PER 400

SERVICE SINK: 1

2902.1.2 SINGLE USER TOILET FACILITY AND BAYHTING ROOM FIXTURES

THE PLUMBING FIXTURES LOCATED IN SINGLE-USER TOILET FACITLITES AND BATHING

ROOMS, INCLUDING FAMILY OR ASSISTED-USE TOILET AND BATHRING ROOMS THAT ARE

REQUIRED BY SECTION 1109.2, SHALL CONTRIBUE TOWARD THE TOTAL NUMBER OF

REUQIRED PLUMBING FIXTURES FOR A BUILDING OR TENANT SPACE.

ISSUED FOR DATE

01.1 - GENEARL
G 001 - COVER SHEET
G 003 - INTERIOR PARTITION TYPES & DEVICE ALIGNMENT GUIDELINES, TYPICAL SYMBOLS & GENERAL NOTES

01.2 - GENEARL COLOR