05 751.21042.TAP_Milliken Nature Center at Park Arch_CD Drawings - 01 General.pdf
PDF 1 MB Posted
- Solicitation number
- RFQ - 171 - 220000000529
- Issued by
- Mackinac County, Mackinac Island City, Michigan
About this file
This document is the construction drawings for the Milliken Nature Center at Arch Rock project for the State of Michigan. The project includes a 1,925 square foot nature center and toilet building located on Mackinac Island in Mackinac County, Michigan. The drawings cover civil, architectural, structural, mechanical, plumbing, and electrical components of the new construction. The project is being bid as a State of Michigan contract opportunity, with a bid due date of August 12, 2022. The contract will be awarded by the Department of Technology, Management, and Budget, State Facilities Administration. The construction must comply with various state and national building codes including the 2015 Michigan Building Code and 2012 NFPA 101 Life Safety Code.
The contract opportunity includes three alternates: deduct equipment of a greywater reuse system, add a solar photovoltaic system, and remove existing asphalt and replace with concrete. Pricing terms, set asides, and funding details are not provided in the drawings. The current environment and any incumbent contractors are also not specified.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
F
IL
E N
U M
B E
R
S T
A T
E I N
D E
X N
U M
B E
R S
C o ns tr uc tio n
F in a l R e co rd
Is su e d f o r
P re lim in a ry
D a te
D E
S
IG
N A
N D
C O
N S
TR
U
C
TI
O N
D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L A
C H
R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
DESIGN TEAM
ARCHITECT/ENGINEER
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
MILLIKEN NATURE CENTER AT ARCH
ROCK
STATE OF MICHIGAN
Mackinac Island, Michigan
CONSTRUCTION DOCUMENTS
C O
V E
R S
H E
E T
-1
.0
G
A U
G U
S T
M
IL
L
IK
E N
N A
T U
R E
C E
N T
E R
A T
A R
C H
R O
C K
M a c k in a c I s la n d
M ic h ig a n
S T
A T
E O
F M
IC
H
IG
A
N
/2
.T
A P
A U
G U
S T
CIVIL CONSULTANT
2926 WEST MAIN STREET
KALAMAZOO, MI 49006
PHONE: 269.585.2051
MACKINAC ISLAND STATE PARK
6131 ARCH ROCK ROAD
MACKINAC ISLAND, MI 49757
242 E. KALAMAZOO AVE, SUITE 100
KALAMAZOO, MICHIGAN 49007
PHONE: 269.343.6133
FAX: 269.343.6633
PROJECT AREA
TOILET BUILDING: 1,025 SQ. FT.
NATURE CENTER: 894 SQ. FT.
TOTAL FINISHED PROJECT: 1,919 SQ. FT.
MECHANICAL & PLUMBING GENERAL
MP 001 MECHANICAL & PLUMBING SYMBOLS, ABBREVIATIONS,
AND GENERAL NOTES
MECHANICAL SITE
MS 101 MECHANICAL SITE PLAN
PLUMBING
P 000 FOUNDATION PLUMBING PLAN
P 101 FIRST FLOOR PLUMBING PLAN
P 150 PLUMBING ROOF PLAN
P 501 PLUMBING SCHEDULES AND DETAILS
MECHANICAL
M 101 FIRST FLOOR MECHANICAL PLAN
M 301 ENLARGED MECHANICAL PLANS & SECTIONS
M 501 MECHANICAL SCHEDULES AND DETAILS
M 601 TEMPERATURE CONTROLS
ELECTRICAL SITE
E 001 ELECTRICAL SYMBOLS AND GENERAL NOTES
ELECTRICAL SITE
ES 101 ELECTRICAL SITE PLAN
ELECTRICAL
E 101 FIRST FLOOR POWER PLAN
E 101.A2 FIRST FLOOR POWER PLAN - ALTERNATE 2
E 150.A2 ROOF PLAN
E 201 FIRST FLOOR LIGHTING PLAN
E 401 ELECTRICAL ONE LINE
GENERAL
G 001 COVER SHEET
G 003 INTERIOR PARTITION TYPES & DEVICE ALIGNMENT
GUIDELINES, TYPICAL SYMBOLS & GENERAL NOTES
G 101 FIRST FLOOR CODE COMPLIANCE PLAN
CIVIL
C 0.0 SITE SURVEY (BY OTHERS)
C 1.0 SITE DEMOLITION PLAN
C 2.0 SITE LAYOUT PLAN
C 3.0 SITE GRADING PLAN
C 3.1 SESC PLAN
C 3.2 SESC DETAILS
C 4.0 SITE UTILITY PLAN
C 5.0 LANDSCAPE PLAN
C 6.0 SITE DETAILS
C 6.1 SITE DETAILS
STRUCTURAL
S 001 GENERAL NOTES
S 002 STATEMENT OF SPECIAL INSPECTIONS
S 003 TYPICAL DETAILS
S 004 PRECAST WALL LOADING
S 101 FOUNDATION PLAN
S 201 ROOF FRAMING PLAN
S 202 UPPER ROOF FRAMING PLAN
S 301 FOUNDATION DETAILS
S 401 FRAMING DETAILS
S 402 FRAMING DETAILS
ARCHITECTURAL
A 101 FIRST FLOOR PLAN
A 103 ROOF PLAN
A 201 FIRST FLOOR REFLECTED CEILING PLAN
A 301 EXTERIOR ELEVATIONS
A 302 EXTERIOR ELEVATIONS
A 311 BUILDING SECTIONS
A 312 BUILDING SECTIONS
A 313 BUILDING SECTIONS
A 321 WALL SECTIONS
A 322 WALL SECTIONS
A 323 WALL SECTIONS
A 324 WALL SECTIONS
A 325 WALL SECTIONS
A 326 WALL SECTIONS
A 327 WALL SECTIONS
A 341 PRECAST PANELS
A 342 PRECAST PANELS
A 343 PRECAST PANELS
A 351 ENLARGED PLAN DETAILS
A 352 CEILING DETAILS
A 353 CAST STONE & CONCRETE SINK DETAILS
A 361 EXTERIOR SIGNAGE
A 421 ENLARGED PLANS, TYPICAL MOUNTING HEIGHTS,
BARRIER-FREE MOUNTING HEIGHTS AND ACCESSORY
MATRIX
A 451 DECK & RAILING
A 501 DOOR SCHEDULES, HEADER, JAMB, & FRAME
INFORMATION
A 601 FIRST FLOOR FINISH PLAN
A 611 MATERIAL SELECTION SCHEDULE & TYPICAL DETAILS &
INTERIOR ELEVATIONS
DRAWING INDEX ALTERNATES
ALTERNATE 1: DEDUCT EQUIPMENT OF GREYWATER REUSE SYSTEM
ALTERNATE 2: ADD SOLAR PHOTOVOLTAIC SYSTEM
ALTERNATE 3: REMOVE EXISTING ASPHALT AND REPLACE WITH CONCRETE
SITE ADDRESS
ISSUED FOR DATE
BUILDING: 2015 MICHIGAN BUILDING CODE AND 2012 NFPA 101 LIFE SAFETY CODE
ENERGY: 2015 MICHIGAN ENERGY CODE
PLUMBING: 2018 MICHIGAN PLUMBING CODE
MECHANICAL: 2015 MICHIGAN MECHANICAL CODE
FUEL GAS: (IFGC) 2015 INTERNATIONAL FUEL GAS CODE
ELECTRICAL: 2017 NATIONAL ELECTRICAL CODE WITH MICHIGAN AMENDMENTS
BARRIER-FREE: 2015 MICHIGAN BUILDING CODE AND 2009 ICC & C A117.1
USE GROUP: U & A
CONSTRUCTION TYPE: IIIB
AUTOMATIC SPRINKLERS: NO
REFFERANCE CODES
GENERAL PARTITION NOTES
1. NOT ALL WALL TYPES MAY BE USED ON PROJECT.
2. REFER TO CODE COMPLIANCE PLANS FOR LOCATIONS OF SMOKE AND FIRE-RATED
PARTITIONS.
3. ALL PARTITIONS EXTEND TO BOTTOM OF STRUCTURE, UNLESS NOTED OTHERWISE.
4. LINE OF STRUCTURE/DECK AS SHOWN AT THE HEAD CONDITION OF EACH PARTITION
TYPE IS DIAGRAMMATIC ONLY AND DOES NOT INDICATE EXACT CONSTRUCTION
CONDITIONS. TERMINATE RATED PARTITIONS AT UNDERSIDE OF STRUCTURAL DECK TO
MAINTAIN RATING. PROVIDE APPROPRIATE FRAMING AND GYPSUM BOARD TO OFFSET
AROUND STRUCTURE OR OTHER OBSTRUCTIONS, SUCH AS PIPING OR DUCTWORK.
5. PARTITIONS MAY TERMINATE AT STRUCTURAL MEMBERS WITH A RATING GREATER THAN
OR EQUAL THE PARTITION, PROVIDED THAT RATING IS CONTINUOUS TO STRUCTURAL
DECK ABOVE.
6. NON-RATED PARTITIONS THAT EXTEND TO STRUCTURE SHALL TERMINATE AT
UNDERSIDE OF STRUCTURAL DECK TO MAINTAIN A CONTINUOUS PLANE OF GYPSUM
BOARD AS A NOISE, SMOKE OR OTHER TYPE OF BARRIER.
7. ALL PARTITIONS EXTENDING TO STRUCTURE ABOVE SHALL TERMINATE WITH
DEFLECTION TRACK - SEE TYPICAL DETAILS ON THIS SHEET.
8. ALL GYPSUM BOARD PARTITIONS NOT EXTENDING TO THE STRUCTURE MUST BE
BRACED.
9. UL DESIGN NUMBERS REFER TO THE FIRE RESISTANCE DIRECTORY; UNDERWRITERS
LABORATORY, LATEST EDITION.
10. MISCELLANEOUS NON-RATED CHASES TO BE 5/8" GYPSUM BOARD ON 3 5/8" METAL
STUD FRAMING AT 16" O.C., UNLESS NOTED OTHERWISE.
11. MISCELLANEOUS FURRING AROUND COLUMNS TO BE 5/8" GYPSUM BOARD ON 11/2"
STUDS, UNLESS NOTED OTHERWISE.
12. FIRE-RATED PARTITIONS TO HAVE FIRE-STOPPING SEALANTS AT HEAD, SILL JUNCTURE
WITH DISSIMILAR MATERIALS, ETC. AND AROUND ALL PENETRATIONS AND OPENINGS.
13. CONSTRUCT ALL PARTITIONS WITH SOUND ATTENUATION BATTS WITH THE FOLLOWING
SOUND BATT THICKNESS: 2 1/2" OR LESS METAL STUD - 1 1/2" THICKNESS, 3 5/8"
OR LARGER METAL STUD - 3" THICKNESS. UNLESS NOTED OTHERWISE.
1X
METAL STUD/FURRING, CH STUD AND WOOD STUD KEY
METAL STUD/FURRING
DESIGNATION SIZE
A GYPSUM BOARD DIRECT APPLIED TO CMU
B 7/8"
C 1 1/2"
D 1-5/8"
E 2 1/2"
F 3 1/2"
G 3 5/8"
H 4"
J 5 1/2"
K 6"
L 8"
M 10"
N 12"
P (OPEN)
Q (OPEN)
CH STUD
DESIGNATION SIZE
R 2 1/2"
S 4"
T 6"
PARTITION TYPE TAG (REFER TO FLOOR PLANS)
PARTITION TYPE
NUMBER
METAL STUD, FURRING OR
CH STUD FRAMING LETTER
FIRE-RATING, IF REQUIRED
1X
WOOD STUD
DESIGNATION SIZE
U 2"x4"
V 2"x6"
W 2"x8"
INTERSECTION OF NON-RATED AT
1 HOUR RATED PARTITION
INTERSECTION OF NON-RATED AT 2 HOUR
RATED PARTITION - U.L. ASSEMBLY U425
1 HOUR RATED
PARTITION - REFER
TO PLAN
METAL STUD FRAMING
NON-RATED PARTITION - REFER TO PLAN
2 HOUR RATED
PARTITION -
REFER TO PLAN
METAL STUD FRAMING
NON-RATED PARTITION - REFER TO PLAN
INTERSECTION OF NON-RATED AT 2 HOUR
RATED PARTITION - U.L. ASSEMBLY U438
2 HOUR RATED
PARTITION -
REFER TO PLAN
CH STUD FRAMING
NON-RATED PARTITION - REFER TO PLAN
INTERSECTION OF
CONCRETE/MASONRY AT 1 HOUR
RATED PARTITION
CONCRETE OR MASONRY
WALL - REFER TO PLAN
1 HOUR RATED PARTITION -
REFER TO PLAN
METAL FURRING
GYPSUM BOARD CONTROL
JOINT NON-RATED PARTITION
• 1/2" MAXIMUM GAP FOR CONTROL JOINT
• 30'-0" MAX. BETWEEN CONTROL JOINTS
• REFER TO PARTITION TYPES FOR COMPLETE
DESCRIPTION OF COMPONENT PARTS
GYPSUM BOARD
METAL STUD FRAMING
BACKER
ROD AND
SEALANT
CONTROL JOINT
GYPSUM BOARD CONTROL
JOINT 1 HOUR RATED
PARTITION
• 1/2" MAXIMUM GAP FOR CONTROL JOINT
• 30'-0" MAX. BETWEEN CONTROL JOINTS
• REFER TO PARTITION TYPES FOR COMPLETE
DESCRIPTION OF COMPONENT PARTS
GYPSUM BOARD
METAL STUD FRAMING
(2) LAYERS TYPE
"X" GYPSUM
BOARD
CONTROL JOINT
GYPSUM BOARD CONTROL
JOINT 2 HOUR RATED
PARTITION
• 1/2" MAXIMUM GAP FOR CONTROL JOINT
• 30'-0" MAX. BETWEEN CONTROL JOINTS
• REFER TO PARTITION TYPES FOR COMPLETE
DESCRIPTION OF COMPONENT PARTS
METAL STUD FRAMING
(2) LAYERS TYPE "X"
GYPSUM BOARD
CONTROL JOINT
(2) LAYERS TYPE
"X" GYPSUM
BOARD
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
FLOOR CONSTRUCTION
METAL STUDS @ 16" O.C. WITH 5/8"
GYPSUM BOARD BACK SIDE, 5/8"
CEMENT BOARD AT ROOM SIDE;
(1 HOUR FIRE) U.L. ASSEMBLY U465
WHERE NOTED ON PLANS
METAL STUD WALL
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
SOUND BATTS (AT CHASE
WALLS ONLY) - UNLESS
NOTED OTHERWISE
FLOOR CONSTRUCTION
METAL STUDS @ 16" O.C. WITH 5/8"
CEMENT BOARD ON ROOM SIDE - BRACE
WALL @ 4'-0" O.C. MAXIMUM.
METAL STUD CHASE WALL OR
FURRING
C H A S E S
ID
E
R O
O M
S
ID
E
1X 2X
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
DEFLECTION TRACK
SEALANT
SOUND BATTS IN
ALL WALLS -
UNLESS NOTED
OTHERWISE
FLOOR CONSTRUCTION
METAL STUDS @ 16" O.C. WITH 3/4"
CEDAR PLYWOOD BOTH SIDES
METAL STUD WALL
3X
HEAD
PLAN
SILL
STRUCTURE /
DECK ABOVE
SEALANT
FLOOR CONSTRUCTION
PRECAST PANEL
PRECAST WALL
4X
NOTE:
MOUNT EQUIPMENT AS SHOWN UNLESS SPECIFIED OTHERWISE.
MAX TWO DEVICES IN ONE HIGHER MOUNT
LOCATION AT LATCH SIDE OF DOOR, PROVIDE RFI
IF MORE DEVICES ARE NECESSARY. WHERE THERE
IS ONE DEVICE, CENTER OVER LOWER DEVICE. (TO
BE WITHIN ADA HEIGHT). (IF SWITCH CANNOT BE
LOCATED ON LATCH SIDE, LOCATE ONE DOOR
LEAF AWAY ON HINGE SIDE.)
DOOR
LOW DEVICES
RECEPTACLEVOICE/DATA
MASONRY COURSING
(WHERE APPLICABLE)
LIGHT SWITCH
F.A. AUDIO/VISUAL
ALIGNMENT NOTES
• ALIGN AND LOCATE CLOSE TOGETHER ANY DEVICES INSTALLED WITHIN 6' HORIZONTALLY.
• CENTER ALL DEVICES WHERE INDICATED ON COLUMN WRAP OR BUMP OUT; STACK AND ALIGN VERTICALLY.
• INSTALL DEVICES AT HEIGHTS INDICATED IN SYMBOL LEGEND UNLESS STACKING PER THIS DETAIL.
• WHERE HEIGHT IS SPECIFICALLY NOTED ON FLOOR PLANS, USE THAT MOUNTING HEIGHT
• CENTER ON DOORFRAME OR WHITEBOARDS ANY DEVICES INDICATED ABOVE.
O R L
A N D
IN
G
F R O
M F
LO
O
R
F R O
M F
LO
O
R O
R L
A N D
IN
G
6' - 0" MIN.
4" MAX
CAMERAS, CLOCKS, WALL
OCCUPANCY SENSORS
WHITE BOARD (WHERE APPLICABLE -
VERIFY WITH DETAILS/PLANS PROPER
INSTALL HEIGHT) CENTER ANY SINGLE
DEVICE WITH CENTER OF WHITE BOARD
ANY DEVICES
SHOWN OVER DOOR
TO BE CENTERED.
EQ EQ
EQ EQ
F R O
M F
LO
O
R O
R L
A N D
IN
G
SHORT THROW PROJECTOR
WHERE APPLICABLE
~12"
FA PULL STATION - HINGE SIDE
OF DOOR 1-LEAF AWAY WITHIN
5'-0" OF EXTERIOR OR STAIR
DOORS, WHEN WALL MOUNT
STROBES ARE ON PROJECT,
ALIGN ABOVE.
WHEN DEVICES ARE WITHIN DIMENSION, STACK
HIGH/LOW VERTICALLY AND GROUP DEVICES AT
SAME HEIGHT. UNLESS DEVICES IS PART OF
TECHNOLOGY DETAIL GROUPING OR SERVING A
FURNITURE GROUP.
CASEWORK, COORDINATE DEVICE BOTTOM
TO BE 2" OVER BACKSPLASH OR OVER
COUNTERTOP (IF NO BACKSPLASH). FOR
LARGE FORMAT TILE, ALIGN EDGE OF DEVICE
WITH HORIZONTAL GROUT LINE CLOSEST TO
COUNTERTOP.
COORDINATE OUTLET LOCATIONS WITH
GROUT LINES, EDGE OF DEVICE ON GROUT
LINE IF POSSIBLE. COORDINATE WITH
INTERIOR DESIGN DRAWINGS.
TYPICAL COLUMN
ENCLOSURE, CHASE OR
BUMP-OUT WITH DEVICES
INDICATED IN PLANS.
EQ EQ
EQEQEQEQ
THERMOSTAT,
SENSORS OR AV
CONTROLLER, CARD
READER, ETC.
GENERAL DEMOLITION NOTES
1. CONTRACTORS ARE REQUIRED TO INSPECT/REVIEW THE EXISTING BUILDING PRIOR TO
RELATED DEMOLITION WORK. UNLESS NOTED OTHERWISE, REMOVAL OF ANY WALL,
FLOOR OR CEILING INCLUDES ALL GENERAL MECHANICAL AND ELECTRICAL ITEMS
WHICH ARE A PART OF, OR ATTACHED TO IT.
2. CONTRACTOR SHALL VERIFY ALL EXISTING JOB SITE CONDITIONS AND DIMENSIONS
AND BE RESPONSIBLE FOR THE SAME. ADVISE CONSTRUCTION MANAGER OF ANY
AND ALL DISCREPANCIES.
3. PATCH FLOORS, WALLS AND CEILINGS DAMAGED DURING CONSTRUCTION AND
DEMOLITION AS REQUIRED. FINISH TO MATCH EXISTING.
4. ACCOMMODATE NEW CONSTRUCTION IF NOT INDICATED.
5. PROTECT ALL EXISTING FINISHES THROUGHOUT PROJECT.
6. REFER TO DEMOLITION ELEVATIONS, SECTIONS AND DETAILS FOR ADDITIONAL
INFORMATION.
7. REFER TO STRUCTURAL, MECHANICAL, PLUMBING AND ELECTRICAL PLANS FOR
ADDITIONAL DEMOLITION NOTES.
8. SALVAGE ALL UNISTRUT AND PROTECT FOR RE-USE IN NEW CONSTRUCTION, IF
REQUIRED.
9. AT LOCATIONS OF REMOVED WALLS, ALL ASSOCIATED ITEMS ATTACHED TO THE WALL
ARE TO BE REMOVED. SUCH AS: DOORS, WINDOWS, FRAMES, MARKERBOARDS,
TACKBOARDS, TACK STRIPS, ETC.
GENERAL NOTES - ARCHITECTURAL
1. THE OWNER RESERVES THE RIGHT TO REMOVE ANY ITEM FROM THE PROJECT PRIOR
TO COMMENCEMENT OF CONTRACTED DEMOLITION WORK.
2. ALL EXISTING CONDITIONS SHOULD BE FIELD VERIFIED BEFORE WORK BEGINS.
3. DIMENSIONS GIVEN ARE ACTUAL AND ARE TO THE FACE OF MASONRY UNITS OR TO
THE FACE OF STUD FRAMING, UNLESS NOTED OTHERWISE.
4. DETAILS SHOWN ILLUSTRATE DESIGN INTENT, NOT ALL POSSIBLE CONDITIONS. FOR
CONDITIONS NOT SHOWN, USE DETAILS CLOSEST TO CONDITION IN QUESTION.
5. EXTEND ALL INTERIOR WALL PARTITIONS FROM FLOOR TO STRUCTURE/DECK ABOVE
UNLESS NOTED OR DETAILED OTHERWISE.
6. WITHIN BUILDING INTERIOR PROVIDE BULLNOSE BLOCK IN CMU WALL ASSEMBLIES AT
ALL EXPOSED OUTSIDE CORNERS, INCLUDING WINDOW AND DOOR JAMBS, UNLESS
NOTED OR DETAILED OTHERWISE. PROVIDE SQUARE OUTSIDE CORNERS AT ALL
LOCATIONS FINISHED WITH WALL TILE, REFER TO FINISH PLANS (A600 SHEETS)
FOR LOCATIONS.
7. TOOTH-IN MASONRY AT NEW OPENINGS IN EXISTING WALLS.
8. TOOTH-IN NEW MASONRY INFILL INTO EXISTING OPENINGS AT ALL BULLNOSE BLOCK
LOCATIONS.
9. STUD WALLS SPANNING OVER 12'-0" IN HEIGHT SHALL BE A MINIMUM OF 20 GAGE.
10. STUD WALL SUPPORTING WALL CABINETS SHALL BE A MINIMUM OF 20 GAGE.
11. DOORS ARE TO BE 4" FROM CORNER OF ROOM, UNLESS NOTED OR DIMENSIONED
OTHERWISE.
12. FIRESTOP ALL INTERCONNECTIONS BETWEEN VERTICAL AND HORIZONTAL SPACES AND
CONCEALED WALL SPACES AT CEILING, FLOOR AND ROOF LEVELS.
13. FIRESEAL ALL PENETRATIONS, SUCH AS, PIPES, DUCTS, CONDUITS, ETC. THROUGH
FIRE AND/OR SMOKE RATED ASSEMBLIES.
14. FOR CONTROL JOINT (C.J.) LOCATIONS REFER TO EXTERIOR ELEVATIONS AND/OR
FLOOR PLANS.
15. PAINT ALL ELECTRICAL PANEL COVERS AND ACCESS PANELS TO MATCH ADJACENT
FINISHES. USING OIL-BASED PAINT, NOT LATEX WALL PAINT.
16. PROVIDE WOOD BLOCKING IN WALLS THAT REQUIRE WALL MOUNTED EQUIPMENT OR
ACCESSORIES. COORDINATE WITH EQUIPMENT OR ACCESSORY MANUFACTURER.
17. PROVIDE ALL ASSOCIATED CURBS FOR ROOF TOP EQUIPMENT AND MECHANICAL
ROOF TOP UNITS. LARGE VOIDS BELOW THE AIR HANDLING UNITS SHALL BE FILLED
WITH INSULATION AS SPECIFIED FOR NOISE CONTROL.
18. ALL EXISTING ROOF TOP PENETRATIONS BEING REMOVED REQUIRE ROOF PATCHING
TO MATCH EXISTING ADJACENT.
A101A
TYPICAL SYMBOLS & REFERENCES
NOTE:
ROOM NAMES AND NUMBERS ON PLANS ARE
FOR CONSTRUCTION PURPOSES ONLY.
COORDINATE WITH OWNER REGARDING
PROPOSED NUMBERS FOR ALL SIGNAGE,
SCHEDULE AND PANEL DESIGNATIONS.
ROOM IDENTIFICATION TAG
ROOM NAME
ROOM NUMBER
DETAIL TITLE
1 DETAIL TITLE
1" = 0'-1"A101
DETAIL NUMBER
SHEET NUMBER
UNIT MATCHLINES
U N
IT
A
U N
IT
B
TYPICAL NOTATION SYMBOLS
CALLOUT REFERENCE BUBBLE
A351
DETAIL NUMBER
SHEET NUMBER
EXTERIOR ELEVATION REFERENCE BUBBLE
A301
A
ELEVATION LETTER
SHEET NUMBER
INTERIOR ELEVATION REFERENCE BUBBLE
4 A 652
ELEVATION NUMBER
SHEET NUMBER
DETAIL REFERENCE BUBBLE
A351
DETAIL NUMBER
SHEET NUMBER
BUILDING SECTION REFERENCE BUBBLE
A 311
DETAIL NUMBER
SHEET NUMBER
ELEVATION AND SECTION REFERENCE TOOLS
ELEVATION TAG - EXISTING
FINISH FLOOR
ELEVATION 100'-0"
ELEVATION TAG FOR EXTERIOR ELEVATIONS
AND BUILDING SECTIONS
100'-0" ELEVATION TAG FOR FLOOR PLANS AND
REFLECTED CEILING PLANS
ELEVATION TAG - NEW
FINISH FLOOR
ELEVATION 100'-0"
100'-0"
ELEVATION TAG FOR EXTERIOR ELEVATIONS
AND BUILDING SECTIONS
ELEVATION TAG FOR FLOOR PLANS AND
REFLECTED CEILING PLANS
WORKING POINT LAYOUT TAG
100'-0" : 100'-0"
DISTANCE IN THE "Y" DIRECTION FROM THE
"X" BASE LINE
DISTANCE IN THE "X" DIRECTION FROM THE
"Y" BASE LINE
BORROWED LIGHT AND DOOR IDENTIFICATION
A 502
SHEET NUMBER
ELEVATION NUMBER
DOOR NUMBER - CORRESPONDS TO THE ROOM NUMBER
LETTER DESIGNATES MORE THAN ONE IN ROOM
SYMBOLS
BARRIER-FREE
B1 REVISION IDENTIFIER (ADDENDUM AND BULLETIN)
COLUMN BUBBLE AND LINE
CLASSROOM
A000A
F
IL
E N
U M
B E
R
S T
A T
E I N
D E
X N
U M
B E
R S
C o ns tr uc tio n
F in a l R e co rd
Is su e d f o r
P re lim in a ry
D a te
D E
S
IG
N A
N D
C O
N S
TR
U
C
TI
O N
D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L A
C H
R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
IN
T
E R
IO
R
P A
R T
IT
IO
N T
Y P
E S
D
E V
IC
E
A L
IG
N M
E N
T G
U
ID
E L
IN
E S
T
Y P
IC
A
L S
Y M
B O
L S
G
E N
E R
A L N
O T
E S
-1
.0
G
A U
G U
S T
M
IL
L
IK
E N
N A
T U
R E
C E
N T
E R
A T
A R
C H
R O
C K
M a c k in a c I s la n d
M ic h ig a n
S T
A T
E O
F M
IC
H
IG
A
N
/2
.T
A P
A U
G U
S T
NOT TO SCALE
DEVICE ALIGNMENT GUIDELINES
ISSUED FOR DATE
T S
T S
F
F
EQ
C S
EQ
FS
FS
FS
C S
C S
CS CS CS CS CS
EQ
EQ
EQ
JB JB JB JB JB
JB JB JB JB JB
C S
1. ALL PENETRATIONS THROUGH A FIRE OR SMOKE RATED PARTITION SHOULD BE
SEALED WITH AN APPROVED U.L. RATED PRODUCT.
2. THE TOPS OF ALL FIRE RATED PARTITIONS SHALL BE SEALED TO THE
CONTINUOUS STRUCTURE ABOVE WITH A U.L. RATED SYSTEM OR ASSEMBLY.
3. WOOD BLOCKING IN FIRE-RATED PARTITIONS SHALL BE NON-COMBUSTIBLE
TREATED WOOD.
4. REFER TO SPECIFICATION U.L. RATING INFORMATION.
5. FIRE-RATED WALLS ENDING INTO AN ACOUSTICAL DECK MUST HAVE THE FLUTES
FILLED, REFER TO 'TOP OF WALL DETAIL AT ACOUSTIC DECK' SHOWN ON THIS
SHEET.
• FOR MASONRY WALLS THE MASON SHALL FILL VOIDS AND FIRE SPRAY WITH UL LISTED
MATERIAL.
• FOR STUD WALLS USE FIRE SAFING AND FIRE CAULK.
CODE COMPLIANCE KEY
EGRESS SYMBOLS
EGRESS EXIT NUMBER FROM ROOM OR SPACE
MAXIMUM NUMBER OF OCCUPANTS PERMITTED
BY EGRESS WIDTH
ROOM OR SPACE EGRESS IS FROM
TRAVEL DISTANCE : 100'-0"
PERMITTED TRAVEL DISTANCE - 200'-0"
EXISTING TRAVEL DISTANCE
TO EGRESS DOOR
PERMITTED MAXIMUM TRAVEL
DISTANCE PER CONDITION
DIRECTION OF EGRESS
FIRE SAFETY SYMBOLS
FIRE-RATING KEY
DESIGNATION PARTITION RATING PRIORITY
EGRESS
Door #
EGRESS ROOM
XFE
XFEC
FE
FEC
EXISTING FIRE EXTINGUISHER
EXISTING FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
AED
AUTOMATED EXTERNAL DEFIBRILLATIOR (AED)
RECESSED CABINET
3 HOUR 1
2 HOUR FIRE/SMOKE 2
2 HOUR 3
1 HOUR FIRE/SMOKE 4
1 HOUR 5
SMOKE RESISTANT 6
FE
FE
TRAVEL DISTANCE : 54' - 8"
PERMITTED TRAVEL DISTANCE - 75' - 0"
TRAVEL DISTANCE : 54' - 9"
PERMITTED TRAVEL DISTANCE - 75' - 0"
TRAVEL DISTANCE : 29' - 4"
PERM
ITTED TRAVEL DISTANCE - 75' - 0"
TR
A V E L D
IS
T A N C E : 32' -
9"
P E R M
IT
TE
D
TR
A V E L D
IS
T A N C E
75' - 0"
F
IL
E N
U M
B E
R
S T
A T
E I N
D E
X N
U M
B E
R S
C o ns tr uc tio n
F in a l R e co rd
Is su e d f o r
P re lim in a ry
D a te
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L A
C H
R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R
O W
N E
R P
R O
J E
C T
T
IT
L E
D A
T E
F
IR
S T
F L O
O R
C O
D E
C O
M P
L
IA
N C
E P
L A
N
-1
.0
G
A U
G U
S T
M
IL
L
IK
E N
N A
T U
R E
C E
N T
E R
A T
A R
C H
R O
C K
M a c k in a c I s la n d
M ic h ig a n
S T
A T
E O
F M
IC
H
IG
A
N
/2
.T
A P
A U
G U
S T
1/4" = 1'-0"
FIRST FLOOR CODE COMPLIANCE PLAN
THIS DRAWING SHEET IS INTENDED TO BE PLOTTED IN
COLOR. IF THIS TEXT APPEARS IN BLACK AND WHITE,
IT IS PLOTTED INCORRECTLY. DISCARD AND OBTAIN
AN ACCURATE DRAWING
INTERNATIONAL ENERGY CONSERVATION CODE:
C301: CLIMATE ZONE: 7
C303.1.3(1): DOUBLE GLAZED DOOR AND WINDOW METAL W/ THERMO BREAK
U-VALUE: .65 -- use .25 SHGC .23
C303.1.3(2): WOOD DOOR
U-VALUE: .5
C402.1.3
ROOF INSULATION ABOVE: R-35
PRECAST WALL PANEL ABOVE GRADE (MASS WALL): 15.2 CUBIC INCH
PRECAST WALL BELOW GRADE (MASS WALL): 15 CUBIC INCH
UNHEATED SLAB ON GRADE: R-15 TO 24" BELOW
R-VALUE
ROOF
2.5" RIGID INSULATION = 14.4 R-VALUE
3" RIGID INSULATION = 17.4 R-VALUE
1/2" COVER BOARD = .56 R-VALUE
WALL
1" CONCRETE = 0.063 R-VALUE
3" RIGID INSULATION = 17.4 R-VALUE
PRECAST 3, 3, 4 = (10") 17.78 R-VALUE
PRECAST 3, 3, 6 = (12") 17.90 R-VALUE
PLUMBING CODE:
419: URINALS
419.2: IN EACH BATHROOM OR TOILET
ROOM, URINALS SHALL NOT BE SUBSATUTED
FOR MORE THAN 67 PERCENT OF THE
REQUIRED WATER CLOSETS IN ASSEMBLY AND
EDUCATIONAL OCCUPANCIES. URINALS SHALL
NOT BE SUBSETUTED FOR MORE THAN 50
PERCENT OF THE REQUIRED WATER CLOSETS IN
ALL OTHER OCCUPANTIES.
GRAPHIC SCALE
0' 3' 6' 12' 18' 24'
BUILDING CODE:
303.4 ASSEMBLY GROUP A-3
504.3 ALLOWABLE BULIDING HEIGHT IN FEET ABOVE GRADE PLANE
OCCUPANCY CLASSIFICATION: A-3 - NON SPRINKLERED - 55 FEET
504.4 NUMBER OF STORIES ABOVE GRADE PLANE
OCCUPANCY CLASSIFICATION: F-1 - SPRINKLERED - 2 STORIES
1004.5 MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT
1. ASSEMBLY WITHOUT FIXED SEATS: 7 NET
1006.2.1 SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY
OCCUPANCY: A-3 - 49 MAXIMUM OCCUPANT LOAD OF SPACE
WITH SPRINKLER: 75 FEET
1006.3.1 MINIMUM NUMBER OF EXITS OR ACCESS TO EXITS PER STORY
OCCUPANT LOAD PER STORY: 1-500 PERSONS
MINIMUM NUMBER OF EXITS: 2
1006.3.3.2 STORIES WITH ONE EXIT OR ACCESS TO ONE EXIT FOR OTHER OCCUPANCIES
FIRST SOTRY ABOVE OR BELOW GRADE PLANE: OCCUPANCY A-3
MAXIMUM OCCUPANT LOAD PER STORY: 49 PERSON
MAXIMUM COMMON PATH OF EGRESS TRAVEL DISTANCE: 75 FEET
1017.2 EXIT ACCESS TRAVEL DISTANCE
OCCUPANCY: A-3
NON SPRINKLER SYSTEM: 200 FEET
2902.1 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES
FACTORY AND INDUSTRIAL:
WATER CLOSET
MALE: 1 PER 100
FEMALE: 1 PER 100
LAVATORIES
MALE: 1 PER 100
FEMALE: 1 PER 100
DRINKING FOUNTAINS: 1 PER 400
SERVICE SINK: 1
2902.1.2 SINGLE USER TOILET FACILITY AND BAYHTING ROOM FIXTURES
THE PLUMBING FIXTURES LOCATED IN SINGLE-USER TOILET FACITLITES AND BATHING
ROOMS, INCLUDING FAMILY OR ASSISTED-USE TOILET AND BATHRING ROOMS THAT ARE
REQUIRED BY SECTION 1109.2, SHALL CONTRIBUE TOWARD THE TOTAL NUMBER OF
REUQIRED PLUMBING FIXTURES FOR A BUILDING OR TENANT SPACE.
ISSUED FOR DATE
| 01.1 - GENEARL |
| G 001 - COVER SHEET |
| G 003 - INTERIOR PARTITION TYPES & DEVICE ALIGNMENT GUIDELINES, TYPICAL SYMBOLS & GENERAL NOTES |
01.2 - GENEARL COLOR