03_12_2026_Douglas County DOT Storage Buildin.pdf
PDF 9 MB Posted
- Solicitation number
- PE-64800-NONST-2026-000000077
- Issued by
- Douglas County, Georgia
About this file
Summary
This construction document set consists of architectural, structural, mechanical, plumbing, and electrical drawings for the interior and exterior alteration and rehabilitation of the Douglas County Department of Transportation (DOT) Storage Building located at 8251 Chicago Avenue, Douglasville, Georgia 30134. The project involves renovation of an existing two-story building totaling approximately 18,075 gross square feet with no change in occupancy use. Level 1 will be used for DOT equipment storage (approximately 14,650 square feet), and Level 2 will house sign shop staff offices and workspace (approximately 2,171 square feet for business use and 117 square feet for storage). The building is classified as non-separated Group B (Business) and S-1 (Storage) occupancies under Type II-B construction with sprinkler protection. Major scope items include installation of a new NFPA 13 sprinkler system throughout, a new fire alarm system, roof replacement, exterior metal wall panel replacement, interior demolition and reconstruction of select walls, new mechanical and electrical systems, plumbing fixture upgrades, and accessibility improvements. The drawings were issued for construction on September 19, 2025, with a revision dated March 4, 2026 for county-requested updates. The project is being designed by CSC Design, Inc. with structural engineering by Keystone Structural Engineering, mechanical and plumbing design by Savant Engineering, LLC, and the general contractor is RA-Lin Construction.
The project must comply with the 2018 International Building Code with Georgia amendments, the 2024 NFPA 101 Life Safety Code, the 2023 National Electrical Code, and the 2010 Americans with Disabilities Act standards. The building maintains a design occupant load of 78 persons with seven emergency exits provided. Construction is anticipated to proceed in phases while maintaining access to the existing facility and coordination with daily operations. The contractor is responsible for obtaining all permits, inspections, and governmental approvals, with special inspections required per IBC Chapter 17. The project includes comprehensive demolition of existing non-structural elements, roof, mechanical/electrical systems, and interior finishes, while preserving the concrete floor slab, structural frame components where feasible, and the existing roll-up door. Final certification of occupancy will require approval from both the Fire Marshal and Building Official prior to any building occupancy or storage use.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SITE ADDRESS: 8251 CHICAGO AVENUE, DOUGLASVILLE
GA 30134
PARCEL ID: 02240250004
JURISDICTION: DOUGLAS COUNTY, GEORGIA
PROJECT DESCRIPTION: RENOVATION & REHABILITATION OF EXISTING DOUGLAS COUNTY DOT STORAGE BUILDING AND SIGN SHOP.
NO CHANGE OF USE FROM PREVIOUS OCCUPANCY CLASSIFICATION AND NO INCREASE OF BUILDING AREA.
BUILDING WILL BE USED FOR STORAGE OF DOT EQUIPMENT ON LEVEL 1 AND FOR SIGN SHOP STAFF ON 2ND FLOOR (2ND FLOOR EXITS ON GRADE). BUILDING WILL BE PROVIDED WITH NEW NFPA 13 SPRINKLER
SYSTEM THROUGHOUT ALONG WITH NEW FIRE ALARM SYSTEM THROUGHOUT.
CLASSIFICATIONS: NON-SEPARATED BUSINESS (GROUP B) AND STORAGE (S-1) OCCUPANCIES.
CONSTRUCTION TYPES: II-B
SPRINKLERED: YES (NFPA 13)
NO. OF STORIES: 2
HIGH-RISE: NO
FIRE ALARM SYSTEM: YES
GROUP CLASSIFICATION
(B) & (S-1) BUSINESS (B) AND STORAGE (S-1)
GROUP
(B) & (S-1)
C. TYPE OF CONSTRUCTION (IBC TABLE 601)
TYPE
IIB
SPRINKLERED
YES
GROUP
B
D. HEIGHT AND AREA LIMITS (IBC TABLE 504.3, 504.4, 506.2, & 406.5.4)
SPRINKLERED
YES
ALLOWABLE BUILDING HEIGHT AND AREA:
MAX HEIGHT*
75'
MAX STORIES*
MAX AREA/LEVEL**
69,000 SF
* PER IBC TABLE 504.3 & 504.4
** PER IBC TABLE 506.2
GROUP
(B) & (S-1)
SPRINKLERED
ACTUAL BUILDING HEIGHT AND AREA:
HEIGHT STORIES
FIRST FLOOR
AREA/LEVEL
2,723 SF
E. FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (IBC TABLE 601)
PRIMARY STRUCTURAL FRAME
BUILDING ELEMENT
EXTERIOR BEARING WALLS
INTERIOR BEARING WALLS
EXTERIOR NONBEARING WALLS AND PARTITIONS
INTERIOR NONBEARING WALLS AND PARTITIONS
FLOOR CONSTRUCTION
ROOF CONSTRUCTION
TYPE II-B
SEE F
PRIMARY STRUCTURAL FRAME
BUILDING ELEMENT
EXTERIOR BEARING WALLS
INTERIOR BEARING WALLS
EXTERIOR NONBEARING WALLS AND PARTITIONS
INTERIOR NONBEARING WALLS AND PARTITIONS
FLOOR CONSTRUCTION
ROOF CONSTRUCTION
SEE F
PROVIDED BUILDING FIRE-RESISTANCE ASSEMBLIES:
F. FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE SEPARATION DISTANCE (IBC TABLE 602)
X < 5
FIRE SEPARATION
5 ≤ X < 10
10 ≤ X < 30
X ≥ 30
TYPE OF CONSTRUCTION
OCCUPANCY GROUP
H F-1, M, S-1 A, B, E, F-2, I, R, S-2, U
ALL
I-A, IV-A
I-A, I-B, IV-A, IV-B
ALL 0
OTHERS
II-B, V-B
OTHERS
1*
1*
* OPEN PARKING GARAGES COMPLYING WITH SECTION 406 SHALL NOT BE REQUIRED TO HAVE A FIRE-RESISTANCE RATING
B. OCCUPANCY CLASSIFICATION (IBC CHAPTER 3, LSC CHAPTER 6.1) NON-SEPARATED
TYPE II-B
BUILDING INFORMATION
8251 CHICAGO AVENUE, DOUGLASVILLE, GA, 30134
DOUGLAS COUNTY, GEORGIA
DOUGLAS COUNTY DOT STORAGE BUILDING
VICINITY LOCATION
SITE LOCATION
BUILDING CODE ANALYSIS SHEET INDEXPROJECT DIRECTORY
OWNER
ARCHITECT
CSC DESIGN, INC
135 P. RICKMAN INDUSTRIAL DR. SUITE 100
CANTON, GA 30115
CONTACT:
KEVIN WHIPPLE, RA
770-345-2579
KWHIPPLE@CSCDE.COM
STRUCTURAL ENGINEER
MEP ENGINEER
CONSULTANTS NOT IN CSC DESIGN'S SCOPE OF SERVICES. DRAWINGS ARE NOT BY ARCHITECT AND ARE INCLUDED HEREIN FOR
CONVENIENCE ONLY.
TN
TN
PROJECT LOCATION
PROJECT LOCATION
KEYSTONE STRUCTURAL ENGINEERING
531 ROSELANE STREET, SUITE 150
MARIETTA, GA 30060
CONTACT:
BRENDAN F. CROWLEY, P.E.
404-483-6921
BCROWLEY@KEYSTONEPC.COM
DOUGLAS COUNTY BOARD OF COMMISSIONERS
8700 HOSPITAL DR.
DOUGLASVILLE, GA 30134
CONTACT:
JAMES L. KING
JLKING@DOUGLASCOUNTYGA.GOV
SAVANT ENGINEERING, LLC
5064 ROSWELL ROAD, SUITE D-301
SANDY SPRINGS, GA 30342
CONTACT:
JOSHUA D. ANDERSON
770-319-7400
JANDERSON@SAVANTENG.COM
A. GENERAL
1. GOVERNING CODES
2018 INTERNATIONAL BUILDING CODE (IBC) W/ GA AMENDMENTS (2020)(2022)(2024)(2025)
2018 INTERNATIONAL PLUMBING CODE (IPC) W/ GA AMENDMENTS (2020)(2022)(2023)(2024)
2018 INTERNATIONAL MECHANICAL CODE (IMC) W/ GA AMENDMENTS (2020)(2024)
2018 INTERNATIONAL FUEL GAS CODE W/ GA AMENDMENTS (2020)(2022)
2023 NATIONAL ELECTRICAL CODE (NEC)
2015 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) W/ GA SUPPLEMENTS AND AMENDMENTS (2020)(2022)(2023)
ACCESSIBILITY
GEORGIA STATE HANDICAPPED ACCESSIBILITY LAW 120-3-20 (EFFECTIVE JANUARY 1, 2015)
2010 EDITION OF THE AMERICANS WITH DISABILITIES ACT (ADA)
2017 ANSI A-117.1 ACCESSIBLE & USABLE BUILDINGS & FACILITIES
LIFE SAFETY
2024 NFPA 101, LIFE SAFETY CODE (LSC) W/ GA AMENDMENTS
2018 INTERNATIONAL FIRE CODE (IFC) W/ GA AMENDMENTS
CHAPTER 120-3-3 RULES & REGULATIONS OF THE STATE MIN. & FIRE SAFETY STANDARDS (EFFECTIVE JANUARY 1, 2020)
2019 NFPA 13 W/ GA AMENDMENTS
2020 NFPA 70 NATIONAL ELECTRICAL CODE (NEC) W/ GA AMENDMENTS
2019 NFPA 72 W/ GA AMENDMENTSCONTRACTOR
RA-LIN CONSTRUCTION
110 DIXIE ST. SUITE 200
CARROLLTON, GA 30117
CONTACT:
TYLER STOGNER
470-214-3508
TYLER.STOGNER@RALINCONSTRUCTION.COM
S-1 YES 75' 3 52,500 SF
YES 33' - 8"
SECOND FLOOR
15,352 SF
INTERIOR AND EXTERIOR ALTERATION AND REHABILITATION FOR:
18, 075 SFGROSS SQ.FT
FOR CONSTRUCTION
CIVIL ENGINEER
CSC DESIGN, INC
135 P. RICKMAN INDUSTRIAL DR., SUITE 100
CANTON, GA 30115
CONTACT:
MATTHEW ZIEG, P.E.
770-345-2579
MZIEG@CSCDE.COM
Phone: (770) 345-2579
135 P RICKMAN INDUSTRIAL DR.
SUITE 100 CANTON, GA 30115
© 2025, CSC Design. These drawings are protected by the copyright laws of the United States. These drawings or any part thereof may not be used for any purpose or reproduced in any form or by any means without the written consent of CSC Design.
CSC
DESIGN,
INC.
ARCHITECTS ENGINEERS&
PROJECT NUMBER:
R E
V
IS
IO
N
S
/1
/2
:2
:0
A
M Y
P ro je c ts
\2 -0
D o u g la s C o u n ty
D O
T S to ra g e B u ild in g
D o u g la s C o u n ty
G
A \A rc h \0
R
E V
IT
\2
-0
D o u g la s C o u n ty
D O
T S to ra g e B u ild in g
R e v
.r v t
G-000
FOR CONSTRUCTION
COVER SHEET
C S
C .2
4.
1.
25-026
D O
U G
L A
S C
O U
N T
Y D
O T
S T
O R
A G
E B
U
IL
D
IN
G
C
H
IC
A G
O A
V E
N U
E
D O
U G
LA
S
V
IL
LE
, G
A , 3
IN
T
E R
IO
R
A N
D E
X T
E R
IO
R
A L T
E R
A T
IO
N
A N
D R
E H
A B
IL
IT
A T
IO
N
F O
R
SHEET NUMBER SHEET NAME 09
.1
9.
IS
S U
E D
F O
R C
O N
S T
R U
C T
IO
N
.0
4.
R
E V
IS
IO
N
(C
O U
N T
Y R
E Q
U E
S T
E D
U P
D A
T E
S
REVISIONS
# DATE
GENERAL
G-000 COVER SHEET ■ ■ 1 03/04/2026
G-005 SYMBOLS & LEGENDS ■
G-006 GENERAL NOTES ■ ■ 1 03/04/2026
G-050 ACCESSIBLITY DETAILS ■
LS101 LIFE SAFETY PLANS ■ ■ 1 03/04/2026
DEMOLITION
AD100 DEMOLITION FLOOR PLANS - LEVELS 1 & 2 ■ ■ 1 03/04/2026
AD101 ENLARGED DEMOLITION FLOOR PLANS - LEVEL 1 ■ ■ 1 03/04/2026
AD102 ENLARGED DEMOLITION FLOOR PLAN - LEVEL 2 ■ ■ 1 03/04/2026
AD201 DEMOLITION RCP - LEVELS 1 & 2 ■ ■ 1 03/04/2026
AD202 ENLARGED DEMOLITION RCP - LEVELS 1 & 2 ■ ■ 1 03/04/2026
AD301 DEMOLITION ELEVATIONS ■ ■ 1 03/04/2026
AD401 DEMOLITION BUILDING SECTIONS ■ ■ 1 03/04/2026
AD402 DEMOLITION BUILDING SECTIONS ■ ■ 1 03/04/2026
ARCHITECTURE
A-001 ARCHITECTURAL SITE PLAN ■ 1 03/04/2026
A-101 CONSTRUCTION FLOOR PLANS - LEVELS 1 & 2 ■ ■ 1 03/04/2026
A-101-A ENLARGED CONSTRUCTION FLOOR PLANS - LEVEL 1 ■ ■ 1 03/04/2026
A-102 ENLARGED CONSTRUCTION FLOOR PLAN - LEVEL 2 ■ ■ 1 03/04/2026
A-103 CONSTRUCTION ROOF PLAN ■ ■ 1 03/04/2026
A-121 FINISHES PLANS ■ ■ 1 03/04/2026
A-201 CONSTRUCTION RCP PLANS - LEVELS 1 & 2 ■ ■ 1 03/04/2026
A-202 ENLARGED CONSTRUCTION RCP PLANS - LEVELS 1 & 2 ■ ■ 1 03/04/2026
A-301 CONSTRUCTION EXTERIOR ELEVATIONS ■ ■ 1 03/04/2026
A-401 CONSTRUCTION BUILDING SECTIONS ■
A-402 CONSTRUCTION BUILDING SECTIONS ■ ■ 1 03/04/2026
A-411 WALL SECTIONS ■
A-412 WALL SECTIONS ■
A-505 ENLARGED RESTROOM & KITCHENETTE DETAILS ■
A-601 VERTICAL CIRCULATION - EXISTING STAIR & DETAILS ■
A-602 VERTICAL CIRCULATION - EXISTING STAIR & DETAILS ■ 1 03/04/2026
A-701 BUILDING DETAILS ■
A-702 ENLARGED DETAILS - METAL, HORIZONTAL MWP ■
A-703 ENLARGED DETAILS - ZEE, VERTICAL MWP ■
A-800 DOOR AND FRAME ELEVATIONS & LEGEND ■ ■ 1 03/04/2026
A-805 DOOR HEAD & JAMB DETAILS - HM, METAL ■
STRUCTURAL
S0.1 STRUCTURAL GENERAL NOTES & SCHEDULES ■
S2.1 ROOF FRAMING PLAN ■
S4.1 FRAMING DETAILS ■
S5.1 SCHEDULE OF SPECIAL INSPECTIONS ■
MECHANICAL
M-001 SCHEDULES, DETAILS, AND NOTES - HVAC ■ ■ 1 03/04/2026
M-101 FLOOR PLAN - LEVEL 1 - HVAC ■ ■ 1 03/04/2026
M-102 FLOOR PLAN - LEVEL 2 - HVAC ■ ■ 1 03/04/2026
M-201 PART PLAN - LEVEL 1 - HVAC ■ ■ 1 03/04/2026
M-202 PART PLAN - LEVEL 2 - HVAC ■ ■ 1 03/04/2026
PLUMBING
P-001 SCHEDULES, DETAILS, AND NOTES - PLUMBING ■
P-101 OVERALL FLOOR PLAN - PLUMBING ■ ■ 1 03/04/2026
P-102 OVERALL FLOOR PLAN - PLUMBING ■ ■ 1 03/04/2026
P-201 PART PLANS - PLUMBING ■ ■ 1 03/04/2026
ELECTRICAL
E-001 LEGENDS AND SPECIFICATIONS ELECTRICAL ■ ■ 1 03/04/2026
E-101 POWER PLAN LEVEL 1 ELECTRICAL ■ ■ 1 03/04/2026
E-102 ENLARGED POWER PLAN LEVEL 2 ELECTRICAL ■ ■ 1 03/04/2026
E-103 SITE PLAN ELECTRICAL ■ 1 03/04/2026
E-201 LIGHTING PLAN LEVEL 1 ELECTRICAL ■ ■ 1 03/04/2026
E-202 LIGHTING PLAN LEVEL 2 ELECTRICAL ■ ■ 1 03/04/2026
E-301 RISER AND DETAILS ELECTRICAL ■ ■ 1 03/04/2026
E-302 PANEL SCHEDULES ELECTRICAL ■ ■ 1 03/04/2026
N O
D
A T
E
IS
S
U E
/0
/2
R
E V
IS
IO
N
C
O U
N T
Y R
E Q
U E
S T
E D
U P
D A
T E
S
03/13/2026
ALIGN
A
LI
G N
SYMBOLS LEGENDSECTION/PLAN LEGENDABBREVIATION LEGEND
A-NNN-UU SHEET NUMBER
OPTIONAL: SUPPLIMENTAL / REVISION
SHEET SEQUENCE DESIGNATOR
SHEET TYPE DESIGNATOR
DISCIPLINE DESIGNATOR
NORTH ARROW
DRAWING TITLE
VIEW NAME
VIEW SCALE
VIEW NUMBER
GRID LINE
VERTICAL ELEVATION
DIMENSIONS
1'-0"
FROM FACE OF STUD TO FACE OF STUD
1'-0"
FROM CENTER TO CENTER
BUILDING SECTION CALLOUT
VIEW NUMBER
SHEET NUMBER
WALL SECTION CALLOUT
DETAIL SECTION CALLOUT
ELEVATION CALLOUT
VIEW NUMBER
SHEET NUMBER
PLAN DETAIL CALLOUT
PARTITION TYPE TAG
SEE G-200'S FOR MORE INFORMATION
ROOM TAG
DOOR TAG
WINDOW TAG
STOREFRONT TAG
CENTERLINE
BREAK LINE
MATCHLINE
SHEET NUMBER
VIEW NUMBER
ROOF PITCH
DRAWING REVISION
REVISION NUMBER
REVISION DELTA
ALUMINUM
BATT INSULATION
BRICK
CONCRETE
CONCRETE MASONRY
EARTH
GRAVEL / DGA
PLASTER,
GYPSUM WALL BOARD
PLYWOOD
TRUE NORTH
TN
CEILING HEIGHT
9'-0"
CL
A-101
A-101
A-101
A-101
VIEW NUMBER
SHEET NUMBER
VIEW NUMBER
SHEET NUMBER
A101
VIEW NUMBER
SHEET NUMBER
A-101
A-BC1-D
ROOM NAME
101A
ALIGN
SF1
1'-0"
FROM FINISH FACE TO FINISH FACE
RIGID INSULATION
SAND
SPRAY FOAM INSULATION
STEEL, IRON
STONE
WOOD BLOCKING / SHIM
WOOD DIMENSIONAL
WOOD FINISH
1 FLOOR PLAN - LEVEL 01
G-001 | 1/8" = 1'-0"
SHEET NUMBER
/1 A101
Phone: (770) 345-2579
135 P RICKMAN INDUSTRIAL DR.
SUITE 100 CANTON, GA 30115
© 2025, CSC Design. These drawings are protected by the copyright laws of the United States. These drawings or any part thereof may not be used for any purpose or reproduced in any form or by any means without the written consent of CSC Design.
CSC
DESIGN,
INC.
ARCHITECTS ENGINEERS&
PROJECT NUMBER:
R E
V
IS
IO
N
S
/6
/2
:0 :3
P
M Y
P ro je c ts
\2 -0
D o u g la s C o u n ty
D O
T S to ra g e B u ild in g
D o u g la s C o u n ty
G
A \A rc h \0
R
E V
IT
\2
-0
D o u g la s C o u n ty
D O
T S to ra g e B u ild in g
R e v
.r v t
G-005
FOR CONSTRUCTION
SYMBOLS &
LEGENDS
C S
C .2
4.
1.
25-026
D O
U G
L A
S C
O U
N T
Y D
O T
S T
O R
A G
E B
U
IL
D
IN
G
C
H
IC
A G
O A
V E
N U
E
D O
U G
LA
S
V
IL
LE
, G
A , 3
IN
T
E R
IO
R
A N
D E
X T
E R
IO
R
A L T
E R
A T
IO
N
A N
D R
E H
A B
IL
IT
A T
IO
N
F O
R
% PERCENT
§ SECTION
A
A/C AIR CONDITIONER
A/E ARCHITECT / ENGINEER
A/V AUDIO VISUAL
AB ANCHOR BOLT
ACC ACCESSIBLE
ACI AMERICAL CONCRETE INSTITUTE
ACT ACOUSTICAL CEILING TILE
ADA AMERICANS WITH DISSABILITIES
ACT
ADJ ADJACENT;
ADJUSTABLE
ADMIN ADMINISTRATION
AFF ABOVE FLOOR FINISH
AFG ABOVE FINISH GRADE
AHJ AUTHORITY HAVING
JURISTICTION
AHU AIR HANDLING UNIT
AIA AMERICAN INSTITUTE OF
ARCHITECTS
AISC AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
ALT ALTERNATE;
ALTERNATING
ALUM ALUMINUM
ANOD ANODIZED
ANSI AMERICAN NATIONAL
STANDARDS INSTITUTE
APPROX APPROXIMATE
ARCH ARCHITECT
AUTO AUTOMATIC
AVG AVERAGE
AWI ARCHITECTURAL WOODWORKING
INSTITUTE
B
B.O. BOTTOM OF
B.O.D. BASIS OF DESIGN
BD BOARD
BETW BETWEEN
BEV BEVELED
BIT BITUMINOUS
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BR BEDROOM;
BRICK
BSMT BASEMENT
BTM BOTTOM
BTU BRITISH THERMAL UNIT
BUR BUILT UP ROOFING
BW BOTH WAYS
C
CCD CONTRACT CHANGE DIRECTIVE
CD CONSTRUCTION DOCUMENTS
CER CERAMIC
CF CONTRACTOR FURNISHED
CFC CHLOROFLOUROCARBONS
CFM CUBIC FEET PER MINUTE
CFS CUBIC FEET PER SECOND
CI CONTRACTOR INSTALLED
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTER LINE;
CLASS
CLG CEILING
CLO CLOSET
CLR CLEAR
CM CONSTRUCTION MANAGEMENT
CMU CONCRETE MASONRY UNIT
CO CERTIFICATE OF OCCUPANCY;
CLEANOUT
COL COLUMN
CONC CONCRETE
CONSTR CONSTRUCTION
CONTR CONTRACTOR
CORR CORRIDOR
CPT CARPET
CSI CONSTRUCTION SPECIFICATION
INSTITUTE
CT CERAMIC TILE;
COUNT
CTR CENTER
CU CUBIC
D
D DEEP;
DEPTH
d PENNY (NAIL)
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION;
DEMOLISH
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DH DOUBLE HUNG
DIA DIAMETER
DIAG DIAGONAL
DIFF DIFFERENCE;
DIFFUSER
DIM DIMENSION
DISP DISPENSER
DIST DISTANCE
DL DEAD LOAD
DN DOWN
DR DOOR;
DOORS;
DRAIN
DS DOWNSPOUT
DTL DETAIL
DW DISHWASHER
DWG DRAWING
DWR DRAWER
E
E EAST
EA EACH
EF EACH FACE;
EXHAUST FAN
EIFS EXTERIOR INSULATION AND
FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC;
ELECTRICAL
ELEV ELEVATOR
EMERG EMERGENCY
ENCL ENCLOSURE
ENGR ENGINEER
ENTR ENTRANCE
EPA ENVIRONMENTAL PROTECTION
AGENCY
EQ EQUAL
EST ESTIMATE
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXP EXPANSION;
EXPOSED
EXT EXTERIOR;
EXTERNAL
F
F.O. FACE OF
FAR FLOOR AREA RATING
FC FOOT CANDLES
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FF&E FURNITURE, FIXTURES &
EQUIPMENT
FFC FIRE EXTINGUISHER CABINET
FHC FIRE HOSE CABINET
FIG FIGURE
FIN FINISH
FIXT FIXTURE
FLEX FLEXIBLE
FLG FLOORING
FLOUR FLOURESCENT
FLR FLOOR
FOM FACE OF MASONRY
FOS FACE OF STUD
FP FIRE PROTECTIONS
FPL FABRIC PANEL
FR FIRE RATING;
FIRE RESISTANT;
FRAME
FRTWD FIRE RETARDENT TREATED
WOOD
FT FEET (FOOT)
FTG FOOTING
FURR FURRING
FWC FABRIC WALL COVERTING
G
GA GAGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERAL
GENR GENERATOR
GFI GROUND FAULT INTERRUPTER
GL GLASS
GLZ GLAZING
GRD GROUND
GSB GYPSUM SHEATHING BOARD
GWB GYPSUM WALL BOARD
GYP GYPSUM
H
H HIGH
HB HOSE BIBB
HC HANDICAP;
HOLLOW CORE
HDR HEADER
HDW HARDWARE
HEX HEXAGONAL
HID HIGH INTENSITY DISCHARGE
HM HOLLOW METAL
HR HOUR
HT HEIGHT
HTG HEATING
HTR HEATER
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
HW HOT WATER
HW HOT WATER
HWY HIGHWAY
I
IAQ INDOOR AIR QUALITY
IBC INTERNATIONAL BUILDING CODE
IC IN CONTRACT
ID IDENTIFICATION;
INTERIOR DESIGN;
INSIDE DIAMETER
IN INCHES
INCAND INCANDESCENT
INCL INCLUSIVE
INCLDG INCLUDING
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
INV INVERT
J
JAN JANITOR
JB JUNCTION BOX
JST JOIST
JT JOINT
K
KD KNOCK DOWN
KIP THOUSAND POUNDS
KIT KITCHEN
KWY KEYWAY
L
L ANGLE;
LENGTH;
LOW
LAB LABORATORY
LAM LAMINATE;
LAMINATED
LAV LAVATORY
LB POUND
LBS POUNDS
LDG LANDING
LED LIGHT EMITTING DIODE
LF LINEAR FOOT;
LINEAR FEET
LH LEFT HAND
LHR LEFT HAND REVERSE
LIB LIBRARY
LIN LINEAR
LL LIVE LOAD
LONG LONGITUDINAL
LR LIVING ROOM
LT LIGHT
LTG LIGHTING
LVL LAMINATED VENEER LUMBER;
LEVEL
M m METER
M HAL METAL HALIDE
MAINT MAINTENANCE
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MBR MEMBER
MECH MECHANICAL
MED MEDIUM
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM;
MINUTE
MISC MISCELANIOUS
MO MASONRY OPENING
MT MOUNT
MTG MOUNTING
MTL METAL
MW MICROWAVE
MWP METAL WALL PANEL
N
N NORTH
N/A NOT APPLICABLE
NE NORTH EAST
NEC NATIONAL ELECTRIC CODE
NEG NEGATIVE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NRC NOISE REDUCTION COEFFICIENT
NSF NET SQUARE FOOT;
NET SQUARE FOOT
NTS NOT TO SCALE
NW NORTHWEST
O
OC ON CENTER
OCC OCCUPANCY;
OCCUPIED
OD OUTSIDE DIAMETER
OFF OFFICE
OH OVERHEAD
OPG OPENING
OPP OPPOSITE
OZ OUNCE;
OUNCES
P
PART PARTIAL
PASS PASSAGE
PC PRECAST
PCC PRECAST CONCRETE
PD PEDISTAL
PERF PERFORATED
PERP PERPENDICULAR
PL PLATE;
PROPERTY LINE
PLAM PLASTIC LAMINATE
PLAS PLASTIC
PLB PLUMB
PLBG PLUMBING
PLF POUNDS PER LINEAR FOOT
PLYWD PLYWOOD
PNL PANEL
POS POSITIVE
PR PAIR
PREFAB PREFABRICATED
PROJ PROJECT;
PROJECTED
PROP PROPERTY;
PROPOSAL
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT;
PRESSURE TREATED
PTD PAINTED
PTN PARTITION
Q
QT QUARRY TILE
QTY QUANTITY
R
R MEASURE OF THERMAL
RESISTANCE;
RADIUS;
RISER
RB RESILIENT BASE;
RUBBER BASE
RBR RUBBER
RC REINFORCED CONCRETE
RCP REFLECTED CEILING PLAN
RD ROAD;
ROOF DRAIN
REBAR REINFORCING STEEL BARS
REC RECESSED
RECEPT RECEPTICAL
RECT RECTANGLE
REF REFERENCE;
REFRIGERATOR
REINF REINFORCE;
REINFORCING;
REINFORCEMENT
REQ REQUIRE;
REQUIRED
RET RETURN
REV REVISE;
REVISED;
REVISION
RFG ROOFING
RFI REQUEST FOR INFORMATION
RH RIGHT HAND
RHR RIGHT HAND REVERSE
RM ROOM
RO ROUGH OPENING
ROW RIGHT OF WAY
RPM ROTATIONS PER MINUTE
RSF RENTABLE SQUARE FEET
RT RUBBER TILE
RTG RATING
RTU ROOFTOP UNIT
RWC RAIN WATER CONDUCTOR
S
S SOUTH
SAN SANITARY
SB STONE BASE
SC SOLID CORE
SCH SCHEDULE;
SCHEDULED
SCHEM SCHEMATIC
SD SMOKE DETECTOR;
STORM DRAIN
SDG SIDING
SE SOUTH EAST
SECT SECTION
SF SQARE FOOT;
SQUARE FEET
SGL SINGLE
SHT SHEET
SHWR SHOWER
SIM SIMILAR
SPEC SPECIFICATION
SPKR SPEAKER
SQ SQUARE
SST STAINLESS STEEL
ST STAIRS;
STREET;
STAIN
STC SOUND TRANSMISSION
COEFFICIENT
STD STANDARD
STL STEEL
STN STONE
STO STORAGE
STR STRUCTURE;
STRUCTURAL
SUSP SUSPENDED
SW SOUTH WEST
SWR SEWER
SYMB SYMBOL
SYS SYSTEM
T
T TILE;
TREAD;
TREADS
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
T.O. TOP OF
TB TILE BASE
TBD TO BE DETERMINED
TEL TELEPHONE
TEMP TEMPERATURE;
TEMPORARY
TERR TERRAZZO
THK THICK;
THICKENED;
THICKNESS
THRES THRESHOLD
THRU THROUGH
TMPD TEMPERED
TOC TOP OF CONCRETE;
TOP OF CURB
TOPO TOPOGRAPH;
TOPOGRAPHY;
TOPOGRAPHIC
TOS TOP OF STEEL
TOW TOP OF WALL
TRANSF TRANSFORMER
TSTAT THERMOSTAT
TV TELEVISION
TYP TYPICAL
U
U HEAT TRANSFER COEFFICIENT
UC UNDERCUT
UH UNIT HEATER
UL UNDERWRITERS LABORATORIES
INC.
UNEXCAV UNEXCAVATED
UNO UNLESS NOTED OTHERWISE
UPS UNITERRUPTABLE POWER
SUPPLY
UR URINAL
USF USABLE SQUARE FOOTAGE
USG UNITED STATES GYPSUM
CORPORATION
UTIL UTILITY
V
V VENT;
VOLT
V.I.F. VERIFY IN FIELD
VAR VARIES
VAV VARIABLE AIR VOLUME
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VENT VENTILATION
VERT VERTICAL
VEST VESTIBULE
VOC VOLATILE ORGANIC COMPOUND
VOL VOLUME
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W
W WATT;
WEST;
WIDE;
WIDTH
W/ WITH
W/D WASHER / DRYER
W/O WITHOUT
WB WOOD BASE
WC WATER CLOSET;
TOILET
WCO WALL CLEANOUT
WD WOOD
WDW WINDOW
WF WIDE FLANGE
WH WATER HEATER
WL WIND LOAD
WLD WELDED
WP WATERPROOF;
WATERPROOFING;
WEATHERPROOF
WPT WORKING POINT
WT WEIGHT
WWF WELDED WIRE FABRIC
X
XPS EXTRUDED POLYSYRENE BOARD
(INSULATION)
Y
YD YARD;
YARD DRAIN
N O
D
A T
E
IS
S
U E
03/06/2026
GENERAL NOTES
1. DO NOT SCALE DRAWINGS - USE DIMENSIONS ONLY. FOR DIMENSIONS NOT SHOWN OR IN QUESTION, CONTRACTOR SHALL REQUEST CLARIFICATION FROM ARCHITECT
BEFORE PROCEEDING. THE CONTRACTOR SHALL VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS AND CONDITIONS ON THE JOB AND MUST NOTIFY THE ARCHITECT IMMEDIATELY IN WRITING OF ANY DISCREPANCIES OR VARIATIONS FROM THE DIMENSIONS OR CONDITIONS SHOWN BY THESE DRAWINGS PRIOR TO ORDERING MATERIALS
OR OTHERWISE PROCEEDING WITH THE WORK.
2. UNLESS NOTED OTHERWISE, WALL AND PARTITION DIMENSIONS ARE GIVEN FROM FACE OF STUD/CMU TO FACE OF STUD/CMU OR TO COLUMN CENTERLINE. EXCEPTION:
MILLWORK DETAILS WHERE DIMENSIONS ARE GIVEN FROM FACE OF FINISH SURFACES (GWB, PLASTER, ETC.). LOCATE EDGE OF DOOR OPENINGS 6" FROM FACE OF
ADJACENT PARTITION UNLESS NOTED OTHERWISE.
3. ELEVATIONS AND LEVELS ARE SHOWN FROM TOP OF SLAB BASED ON A "REFERENCE BENCHMARK ELEVATION" - THE CONTRACTOR SHALL COORDINATE THE ELEVATIONS PROVIDED WITH THE CIVIL DRAWINGS AND EXISTING ELEVATIONS WHEN APPLICABLE. COORDINATE WITH ARCHITECT AND CIVIL ENGINEER WHERE SITE REQUIRES
MODIFICATIONS TO DESIGN ELEMENTS.
4. ALL CENTERLINE OF FOOTINGS, WALLS, GRADE BEAMS, COLUMNS AND BEAMS SHALL COINCIDE, UNLESS NOTED OTHERWISE.
5. ALL DETAILS, SECTIONS AND NOTES SHOWN ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND SHALL APPLY TO SIMILAR SITUATIONS ELSEWHERE, UNLESS
SPECIFICALLY SHOWN OTHERWISE.
6. THIS SET OF CONSTRUCTION DOCUMENTS IS INTENDED TO BE READ AS A COMPREHENSIVE SET OF DRAWINGS AND SPECIFICATIONS. NOTE THAT THE SPECIFICATIONS FORM AN INTEGRAL PART OF THIS CONSTRUCTION DOCUMENTATION. THE CONTRACTOR SHALL CAREFULLY STUDY & COMPARE THE CONTRACT DOCUMENTS WITH EACH OTHER (EACH DISCIPLINE) AND THE INFORMATION FURNISHED BY THE DEVELOPER AND NOTIFY THE ARCHITECT OF ANY ERRORS, INCONSISTENCIES OR OMISSIONS.
INFORMATION GIVEN BY ONE DISCIPLINE SHALL BE APPLICABLE FOR ALL PORTIONS OF THE CONSTRUCTION DOCUMENTS IN ORDER TO MEET THE DESIGN INTENT. IF THE CONTRACTOR PERFORMS ANY CONSTRUCTION ACTIVITY WHERE AN ERROR, INCONSISTENCY OR OMISSION IN THE CONTRACT DOCUMENTS IS EVIDENT WITHOUT SUCH NOTICE TO THE ARCHITECT. THE CONTRACTOR SHALL ASSUME THE APPROPRIATE RESPONSIBILITY AT NO ADDITIONAL COST TO THE OWNER.
7. ALL DRAWINGS, SPECIFICATIONS, & OTHER DOCUMENTS PREPARED BY THE ARCHITECT & ARCHITECT'S CONSULTANTS ARE INSTRUMENTS OF SERVICE SOLELY FOR THIS
PROJECT.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING, COORDINATING AND PAYING FOR THE COST OF ALL INSPECTIONS, TESTS, PERMITS, LICENSES AND OTHER GOVERNMENTAL FEES, AS NECESSARY FOR PROPER EXECUTION TO COMPLETE THE WORK AND AS INDICATED ON THE PLANS AND SPECIFICATIONS, RECOMMENDED BY THE GEOTECHNICAL REPORT AND/OR AS REQUIRED BY ANY GOVERNMENTAL AGENCY. REVISIONS MADE AFTER INITIAL PERMIT PULL REQUIRING RESUBMISSION OF REVISED DOCUMENTS AND/OR ADDITIONAL FEES SHALL BE THE CONTRACTOR'S RESPONSIBILITY.
9. THE CONTRACTOR SHALL COMPLY WITH AND GIVE NOTICES REQUIRED BY LAWS, ORDINANCES, RULES, REGULATIONS, AND LAWFUL ORDERS OF THE PUBLIC AUTHORITIES BEARING ON THE PERFORMANCE OF THE WORK. ALL WORK SHALL BE PREPARED IN ACCORDANCE WITH ALL APPLICABLE NATIONAL, STATE, & LOCAL CODES &
REGULATIONS.
10. THE CONTRACTOR SHALL VISIT THE SITE AND SURROUNDING AREAS TO BECOME FAMILIAR WITH THE WORK REQUIRED PRIOR TO ANY ON-SITE CONSTRUCTION OR MOBILIZATION. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO CONSTRUCTION. THE CONTRACTOR SHALL ASSUME RESPONSIBILITY TO ACCOUNT FOR NON-TYPICAL SOILS CONDITIONS, INCLUDING BY NOT LIMITED TO THE PRESENCE OF CLAY OR GROUND WATER.
11. THE CONTRACTOR SHALL PROVIDE LABOR, MATERIAL, EQUIPMENT, AND SERVICES REQUIRED TO EXECUTE AND COMPLETE ALL ITEMS OF WORK AS SHOWN, OR INDICATED ON THE DRAWINGS AND AS SPECIFIED INCLUDING INCIDENTAL ITEMS TO EFFECT A FINISHED AND COMPLETE JOB. THE ARCHITECT SHALL NOT BE RESPONSIBLE FOR THE CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES, OR PROCEDURES OR SAFETY REGULATIONS IN CONNECTION WITH WORK.
12. THE CONTRACTOR SHALL PROVIDE ALL REGULATORY AGENCY REQUIRED SIGNAGE NECESSARY FOR CERTIFICATE OF OCCUPANCY.
13. ANY AND ALL REVISIONS FROM THESE PLANS MUST BE APPROVED BY THE ARCHITECT PRIOR TO INSTALLATION. ONCE CONSTRUCTION HAS COMMENCED, ANY REVISIONS IN THE FIELD MUST BE APPROVED BY THE OWNER'S CONSTRUCTION REPRESENTATIVE AND THE ARCHITECT. THE ARCHITECT MAY AUTHORIZE AT ANY POINT MINOR CHANGES IN WORK INVOLVING ADJUSTMENTS IN CONTRACT SUM VIA ARCHITECT'S SUPPLEMENTAL INSTRUCTIONS (ASI) WHICH ARE CONSISTENT WITH THE INTENT OF THE CONTRACT
DOCUMENTS.
14. THE CONTRACTOR SHALL BE COMPLETELY RESPONSIBLE FOR BRACING AND SHORING OF THE STRUCTURE DURING CONSTRUCTION TO ENSURE STABILITY.
15. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING INSPECTIONS WITH THE AUTHORITIES HAVING JURISDICTION ON THE PROJECT.
16. THE CONTRACTOR SHALL MAINTAIN ON SITE AND MAKE AVAILABLE IN THE JOB TRAILER A LIST OF SPECIAL INSPECTORS CONDUCTING INSPECTIONS ON THE PROJECT. THE LIST SHALL INDICATE THE NAMES OF INSPECTOR, DATES, AND TIMES PRESENT ON JOB SITE AND TYPES OF INSPECTIONS BEING CONDUCTED. INSPECTION REPORTS SHALL
ALSO BE MADE AVAILABLE UPON REQUEST.
17. THE CONSTRUCTION SCHEDULE SHALL BE RELATED TO THE ENTIRE PROJECT AND BE CONDUCTED IN STRICT ACCORDANCE WITH THE SEQUENCE OF OPERATIONS IN WHICH THE CONTRACTOR HAS COORDINATED WITH THE OWNER'S APPROVAL ON ALL SCHEDULE SEQUENCING TO AVOID CONFLICTS WITH DAILY OPERATIONS AND SPECIAL
EVENTS INCLUDING ANY EXISTING FACILITIES AND ACCESS AS MAY BE APPLICABLE.
18. THE USE OF THE SITE SHALL BE CONFINED TO THOSE AREAS APPROVED BY THE OWNER AND CODE IN ORDER TO MINIMIZE PUBLIC EXPOSURE TO UNSAFE CONDITIONS AND
TO CONTINUE THE OPERATION OF THE SURROUNDING DEVELOPMENT.
19. NO STRUCTURE OF ANY KIND IS TO BE CONSTRUCTED ON OR PLACED WITHIN PUBLIC UTILITY EASEMENTS EXCEPT WOOD, WIRE OR REMOVABLE SECTION TYPE FENCING, REQUIRE PAVING FOR ACCESS AND GROUND COVER INCLUDING GRASS. THE CONTRACTOR SHALL REPLACE ANY OBSTRUCTIONS OR PLANTING THAT MUST BE REMOVED DURING THE COURSE OF MAINTENANCE, CONSTRUCTION OR RECONSTRUCTION OF THE PUBLIC UTILITIES AT NO COST TO THE OWNER.
20. NO BUILDING OR PORTION OF A BUILDING SHALL BE OCCUPIED OR USED INCLUDING STORAGE PRIOR TO ISSUANCE OF CERTIFICATE OF OCCUPANCY. APPROVAL FOR OCCUPANCY IS ONLY GRANTED AFTER ACCEPTANCE BY THE FIRE MARSHAL AND BUILDING OFFICIAL.
21. MATERIAL AND EQUIPMENT STORAGE SHALL BE ON SITE AND COORDINATED WITH OWNER'S DIRECTIVES.
22. SIGNS, LOCATION, NUMBER, AND SIZE ARE NOT APPROVED UNDER THIS BUILDING PERMIT. A SEPARATE PERMIT IS REQUIRED FOR EACH SIGN. ALL IDENTIFICATION SIGNAGE SHALL BE PROVIDED BY OWNER AND INSTALLED BY CONTRACTOR (UNLESS NOTED OTHERWISE) SIGNAGE ON RESTROOM DOORS SHALL BE RAISED AND BRAILLE CHARACTERS AND PICTORIAL SYMBOL SIGNS. IDENTIFICATION SIGNAGE SHALL BE INSTALLED ON THE WALL ADJACENT TO THE LATCH SIDE OF THE DOOR. WHERE THERE IS NO WALL SPACE TO THE LATCH SIDE OF THE DOOR, INCLUDING AT DOUBLE LEAF DOORS, SIGNS SHALL BE PLACED ON THE NEAREST ADJACENT WALL. MOUNTING HEIGHT SHALL COMPLY WITH THE GEORGIA ACCESSIBILITY CODE AND THE ADA STANDARDS FOR ACCESSIBLE DESIGN.
23. EXIT DOORS SHALL NOT BE SUBJECTED TO USE OF A KEY OR REQUIRE SPECIAL KNOWLEDGE TO OPERATE PER THE NFPA 101 LIFE SAFETY CODE 2018 EDITION, CHAPTER 5-2.15.2. PANIC HARDWARE SHALL BE PROVIDED FOR ALL EXIT DOORS PER THE REQUIREMENTS OF THE NFPA LIFE SAFETY CODE. EXIT DOORS SHALL OPERATE PER NFPA
101 LIFE SAFETY CODE.
24. (DOOR/HARDWARE) HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERATING DEVICES ON ACCESSIBLE DOORS SHALL HAVE A SHAPE THAT IS EASY TO GRASP WITH ONE HAND AND DOES NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING, OR TWISTING OF THE WRIST TO OPERATE. LEVER-OPERATED MECHANISMS, PUSH-TYPE MECHANISMS, AND U-SHAPED HANDLES SHALL BE PROVIDED THAT COMPLY WITH GEORGIA ACCESSIBILITY CODE AND THE ADA STANDARDS FOR ACCESSIBLE DESIGN. OPERABLE PARTS SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N) MAX.
25. PROTRUDING OBJECTS SHALL NOT REDUCE THE CLEAR WIDTH OF AN ACCESSIBLE ROUTE AND SHALL BE INSTALLED WITH THE GEORGIA ACCESSIBILITY CODE AND THE ADA
STANDARDS FOR ACCESSIBLE DESIGN.
26. DETECTIBLE WARNINGS ON WALKING SURFACES SHALL COMPLY WITH THE GEORGIA ACCESSIBILITY CODE AND THE ADA STANDARDS FOR ACCESSIBLE DESIGN.
27. ALL MATERIALS EXPOSED WITHIN PLENUMS ARE REQUIRED TO BE NONCOMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX AND A SMOKE-DEVELOPED INDEX OF NOT
MORE THAN 50 AS DETERMINED IN ACCORDANCE WITH ASTM E84.
28. THE CONTRACTOR SHALL DOCUMENT THAT INSULATION MATERIALS IN CONCEALED OR EXPOSED SPACES SHALL HAVE A FLAME SPREAD INDEX AND A SMOKE-DEVELOPED
INDEX THAT MEETS CODE.
29. ALL INTERIOR FINISH PRODUCTS SHALL BE PROVIDED IN COMPLIANCE WITH THE REQUIREMENTS OF THE RESPECTIVE OCCUPANCY CHAPTER OF THE NFPA 101 LIFE SAFETY CODE FOR WHICH THE PROJECT IS BEING PERMITTED UNDER. THE CONTRACTOR SHALL PROVIDE DOCUMENTATION VERIFYING AT THE TIME OF FINAL INSPECTION THAT
PRODUCTS ARE COMPLIANT WITH THE CODE REQUIREMENTS.
30. ALL WOOD LUMBER AND PLYWOOD OR O.S.B. USED IN EXTERIOR CONSTRUCTION SHALL BE PRESSURE TREATED THAT COMES IN CONTACT WITH CONCRETE OR WITHIN 12"
OF GRADING/SOIL.
31. EMERGENCY LIGHTING COMPLYING WITH NFPA 101 LIFE SAFETY CODE SHALL BE INSTALLED. ADDITIONAL EMERGENCY LIGHTING MAY BE REQUIRED UPON FIELD
INSPECTION.
32. THE CONTRACTOR SHALL PERMANENTLY IDENTIFY ALL FIRE-RATED WALLS AND SMOKE BARRIERS WITH SIGNS OR STENCILING ABOVE CEILING OR IN CONCEALED SPACES WITH LETTERS A MINIMUM OF 2" HIGH ON A CONTRASTING BACKGROUND SPACED AT A MAXIMUM OF 12'-0" ON CENTER WITH A MINIMUM OF ONE PER WALL OR BARRIER IN
ACCORDANCE WITH CODE.
33. PRIOR TO INSTALLATION, THE CONTRACTOR SHALL SUBMIT DETAILS FOR REVIEW AND APPROVAL WHICH CLEARLY INDICATE LATERAL BRACING TO BUILDING STRUCTURE FOR ALL PARTITIONS OF LIGHT GAUGE METAL FRAMING WHICH EXCEED 9'-0" IN HEIGHT TO ADEQUATELY RESIST THE APPLICABLE LATERAL SEISMIC DESIGN FORCES PER
CODE.
34. ALL COLD FORM METAL FRAMING SHOWN ON THE DRAWINGS IS FOR DIAGRAMMATIC USE ONLY. MEMBER SIZE, CONFIGURATION, DETAILS AND CONNECTIONS ARE THE RESPONSIBILITY OF THE CONTRACTOR'S COLD FORM METAL FRAMING ENGINEER. COLD FORM METAL FRAMING SHOP DRAWINGS, COMPLETE WITH CALCULATIONS, SHALL BE SIGNED AND SEALED BY THE COLD FORM METAL FRAMING ENGINEER IN THE STATE HAVING JURISDICTION OVER THE PROJECT AND SHALL BE SUBMITTED FOR REVIEW
AND APPROVAL.
35. PROVIDE FIRE RETARDANT TREATED BLOCKING IN PARTITIONS AS REQUIRED FOR SUPPORTING WALL MOUNTED EQUIPMENT, ETC.
36. ELECTRICAL PANELS, ALARM BOXES, FIRE EQUIPMENT CABINETS AND OTHER SIMILARLY RECESSED BOXES GREATER THAN 16" THAT ARE LOCATED IN A RATED ASSEMBLY SHALL BE BACKED BY GYPSUM WALLBOARD LAYERS SUFFICIENT TO MAINTAIN THE DESIGNATED FIRE RATING. FIRE EQUIPMENT CABINETS MAY BE PROVIDED WITH A RATED
CABINET TO MATCH THE MINIMUM DESIGNED ASSEMBLY RATING THEY ARE LOCATED WITHIN.
37. ATTIC ACCESS FROM AN ADJACENT SPACE SHALL BE PROVIDED WHERE THE BELOW ITEMS OCCUR OVER GYPSUM BOARD CEILINGS:
A. VALVES
B. FLOW MEASURING DEVICES
C. MIXING BOXES
D. POWER OPERATED DAMPERS
E. ACCESS PANELS IN DUCTWORK
F. VOLUME AND BALANCING DEVICES
G. WATERFLOW SWITCHES
H. SPRINKLER SYSTEM DRAINS AND TEST CONNECTIONS
I. PRESSURE SWITCHES
J. ANY OTHER SIMILAR RELATED ITEMS/DEVICES REQUIRING ACCESS FOR SERVICING OR MAINTENANCE
38. PATCH AND REPAIR ALL ITEMS DAMAGED OR ALTERED DURING CONSTRUCTION. ALL PATCHES SHALL BLEND WITH ADJACENT MATERIAL, COLOR, FINISH, AND TEXTURE. ALL EXISTING WORK FURNISHINGS, EQUIPMENT OR MATERIAL TO REMAIN THAT ARE DAMAGED BY THE CONTRACTOR'S OPERATION SHALL BE REPAIRED AT NO ADDITIONAL
COST TO THE OWNER.
39. SLOPE ALL SLABS AT EXTERIOR BUILDING ENTRANCES 1/8" FT AWAY FROM BUILDING IN ALL LOCATIONS.
40. ISOLATE DISSIMILAR METALS BY MEANS OF HEAVY BITUMINOUS COATING, APPROVED PAINT, ADHERED POLYETHYLENE SHEET, OR OTHER MEANS APPROVED OF BY THE
ARCHITECT.
41. PRIME AND PAINT ALL STEEL LINTELS, HANDRAILS, AND ANY AND ALL OTHER INTERIOR OR EXTERIOR EXPOSED FERROUS METAL SURFACES NOT OTHERWISE INDICATED AS
COATED OR PAINTED.
42. STRUCTURAL WORK, INCLUDING MATERIAL STRESSES AND METHODS OF CONSTRUCTION SHALL BE IN COMPLIANCE WITH THE LATEST ADOPTED BUILDING CODE, OSHA AND
GOVERNING AGENCIES HAVING JURISDICTION.
43. THE CONTRACTOR SHALL USE CONSTRUCTION METHODS THAT ARE IN STRICT ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS.
44. THE CONTRACTOR SHALL MAINTAIN THE PREMISES FREE FROM ACCUMULATIONS OF WASTE MATERIALS, DEBRIS AND RUBBISH CAUSED BY OPERATIONS.
45. AFTER COMPLETION OF WORK ALL ADDITIONAL MATERIALS REMAINING DUE TO CONSTRUCTION SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE DISPOSED OF/REMOVED FROM THE SITE IN ACCORDANCE WITH ALL APPLICABLE LAWS, ORDINANCES, RULES, AND REGULATIONS U.N.O. THE CONTRACTOR SHALL ALSO REMOVE ALL WASTE DEBRIS, RUBBISH, TOOLS, EQUIPMENT, AND SURPLUS MATERIALS UPON COMPLETION OF WORK. THROUGHOUT CONSTRUCTION THE SITE SHALL BE
ORGANIZED AND CLEANED BY THE CONTRACTOR ON A DAILY BASIS.
46. THE CONTRACTOR SHALL RESTORE TO ITS ORIGINAL CONDITION ALL SITE APPURTENANCES DAMAGED UNDER THIS CONTRACT AT NO ADDITIONAL COST TO THE OWNER.
47. ANY MATERIAL SCHEDULED FOR DEMOLITION SHALL BECOME THE PROPERTY OF THE CONTRACTOR UNLESS NOTED OTHERWISE AND SHALL BE DISPOSED OF LEGALLY BY
THE CONTRACTOR.
48. THE CONTRACTOR SHALL REVIEW FLOOR FINISHES. ALL FINISHED FLOORS SHALL BE FLUSH TO ADJACENT FLOOR SYSTEMS WHETHER OF SIMILAR OR DISSIMILAR
MATERIALS.
49. THE FLOOR LEVEL SHALL BE THE SAME ON BOTH SIDES OF ALL INTERIOR DOORS.
50. PROVIDE FLASHING AT ALL WINDOWS AND DOORS IN EXTERIOR WALLS THROUGHOUT. PROVIDE ALL WALL, BASE, CAP, THRU-WALL, AND COUNTER FLASHING AS REQUIRED
TO PREVENT ENTRANCE OF MOISTURE AND WATER INTO THE BUILDING.
51. ALL PENETRATIONS INTO OR THROUGHOUT EITHER A VERTICAL AND/OR HORIZONTAL FIRE RATED ASSEMBLY SHALL BE PROTECTED BY A FIRE-STOPPING ASSEMBLY LISTED
BY A RECOGNIZED TESTING AGENCY.
52. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY PRODUCT DATA, SAMPLES, AND SHOP DRAWINGS FOR SPECIFIED ITEMS. THESE ITEMS MUST BE SUBMITTED TO THE
ARCHITECT FOR REVIEW PRIOR TO FABRICATION.
53. COMPLETE SHOP DRAWINGS FOR ALL SPECIALITY ITEMS INCLUDED BUT NOT LIMITED TO ORNAMENTAL GUARDRAILS SHALL BE PROVIDED BY THE CONTRACTOR WITH SIGNATURE AND SEAL SIGNIFYING REVIEW AND APPROVAL BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE OF GEORGIA AND SHALL BE MADE AVAILABLE AT THE
JOB SITE DURING TIMES OF CONSTRUCTION.
54. THE CONTRACTOR SHALL PROVIDE TEMPORARY FIRE EXTINGUISHERS DURING CONSTRUCTION AND PERMANENT FIRE EXTINGUISHERS INCLUDING AT ALL FIRE EXTINGUISHER CABINET LOCATIONS MARKED ON PLAN IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS AND IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 10.
55. ALL FINAL MATERIAL FINISH SELECTIONS TO BE APPROVED BY OWNER PRIOR TO ORDERING.
56. INDICATED TELEVISION LOCATIONS ON PLAN SHALL BE PROVIDED WITH BLOCKING AS REQUIRED IN WALLS WITH OWNER'S FINAL FURNITURE, FIXTURES, AND EQUIPMENT PACKAGE. T.V.'S AND WALL BRACKETS ARE BY OWNER'S F.F.E. AND/OR RESIDENTS. CONTRACTOR SHALL CONFIRM FINAL BLOCKING REQUIREMENTS WITH OWNER PRIOR TO
WALL COVER-UP.
57. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL SPECIAL INSPECTIONS AS REQUIRED BY IBC CHAPTER 17. SPECIAL INSPECTION REPORTS AND FINAL REPORT IN ACCORDANCE WITH SECTION 1704.2.4 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL PRIOR TO THE TIME THAT PHASE OF WORK IS APPROVED FOR OCCUPANCY.
58. UNLESS DETERMINED BY THE "FIRE CODE OFFICIAL" THAT A RADIO COVERAGE SYSTEM IS NOT NEEDED FOR NEW BUILDINGS, THE GENERAL CONTRACTOR SHALL PROVIDE FOR IFC 510 TESTING AND PROVIDE SYSTEM AS REQUIRED BASED ON TEST DATA AND FIRE MARSHAL REQUIREMENTS.
59. COORDINATE LOCATION OF UTILITY METERS WITH SITE PLAN. MINIMIZE VISUAL IMPACT OF METERS BY KEEPING THEM AS LOW AS POSSIBLE.
60. THE CONTRACTOR SHALL SUBMIT CERTIFIED FIRE SUPRESSION AND FIRE ALARM DOCUMENTS TO FIRE MARSHAL FOR APPROVAL PRIOR TO PROCEEDING WITH ANY WORK.
Phone: (770) 345-2579
135 P RICKMAN INDUSTRIAL DR.
SUITE 100 CANTON, GA 30115
© 2025, CSC Design. These drawings are protected by the copyright laws of the United States. These drawings or any part thereof may not be used for any purpose or reproduced in any form or by any means without the written consent of CSC Design.
CSC
DESIGN,
INC.
ARCHITECTS ENGINEERS&
PROJECT NUMBER:
R E
V
IS
IO
N
S
/6
/2
:0 :3
P
M Y
P ro je c ts
\2 -0
D o u g la s C o u n ty
D O
T S to ra g e B u ild in g
D o u g la s C o u n ty
G
A \A rc h \0
R
E V
IT
\2
-0
D o u g la s C o u n ty
D O
T S to ra g e B u ild in g
R e v
.r v t
G-006
FOR CONSTRUCTION
GENERAL NOTES
C S
C .2
4.
1.
25-026
D O
U G
L A
S C
O U
N T
Y D
O T
S T
O R
A G
E B
U
IL
D
IN
G
C
H
IC
A G
O A
V E
N U
E
D O
U G
LA
S
V
IL
LE
, G
A , 3
IN
T
E R
IO
R
A N
D E
X T
E R
IO
R
A L T
E R
A T
IO
N
A N
D R
E H
A B
IL
IT
A T
IO
N
F O
R
N O
D
A T
E
IS
S
U E
/0
/2
R
E V
IS
IO
N
C
O U
N T
Y R
E Q
U E
S T
E D
U P
D A
T E
S
1:6
M
IN
18" MIN.
A. FRONT APPROACH, PULL SIDE
M
IN
36" MIN.
B. HINGE APPROACH, PULL SIDE
M
IN
24" MIN.
D. LATCH APPROACH, PULL SIDE
M
IN
24" MIN.
E. LATCH APPROACH W/ CLOSER, PULL SIDE
M
IN
42" MIN.
C. HINGE APPROACH, PULL SIDE
F. FRONT APPROACH, PUSH SIDE
8"
G. FRONT APPROACH W/ CLOSER, PUSH SIDE
8"
MIN.
12"
H. HINGE APPROACH, PUSH SIDE
2"
MIN.
22"
I. HINGE APPROACH W/ CLOSER, PUSH SIDE
8"
MIN.
22"
J. LATCH APPROACH, PUSH SIDE
2"
MIN.
24"
K. LATCH APPROACH W/ CLOSER, PUSH SIDE
8"
MIN.
24"
ANSI 117.1-2010 §404.2.4 - MANEUVERING CLARANCE AT SWING DOORS
ADA 2010 §304.3 - TURNING CLEARANCE
ø60" MIN.
MIN.
12" 36" MIN.
MIN.
12"
M
IN
M
IN
M
IN
TOE
OVERLAP
"T" SHAPED TURNING CLEARANCECIRCULAR TURNING CLEARANCE
ADA 2010 §306.3 - KNEE CLEARANCE ADA 2010 §306.2 - TOE CLEARANCE
M
IN
11" MIN.
8" MIN.
PLANELEVATION
M
IN
30" MIN.
M
A X
PLANELEVATION
M
IN
30" MIN.
MAX.
6"
M
IN
" C
LE
A
R U
N D
E R
E
LE
M E
N T
C
LE
A R
U N
D E
R E
LE
M
E N
T
M
IN
ACCESSIBLE TOILET COMPARTMENT
ADA 2010 §604.8.1
M
IN
. C
L E
A R
59" MIN. CLEAR - FLOOR MOUNT
56" MIN. CLEAR - WALL HUNG
M
IN
2"
MAX.
12"
36" GRAB BAR **
FLUSH CONTROLS ARE TO
BE LOCATED ON THE OPEN
SIDE OF THE WATER CLOSET
42" GRAB BAR **
LARGE ACCESSIBLE TOILET COMPARTMENT
ADA 2010 §604.8.1
M
IN
. C
L E
A R
M
IN
2"
MAX.
12"
36" GRAB BAR **
FLUSH CONTROLS ARE TO
BE LOCATED ON THE OPEN
SIDE OF THE WATER CLOSET
42" GRAB BAR **
M
IN
M
IN
STANDARD TOILET COMPARTMENT
2018 IPC §405.3.1
M A
X
SELF CLOSING
32" MIN. CLEAR 4"
59" MIN. CLEAR - FLOOR MOUNT
56" MIN. CLEAR - WALL HUNG 3'-0" MIN.
42" MIN. CLEAR
STANDARD CLEARANCES
* SIZES SHOWN ASSUME TOE CLEARANCE IS
PROVIDED ON ONE SIDE AND AT THE FRONT OF THE
STALL. IF STALLS DO NOT HAVE TOE CLEARANCES,
THE MIN. WIDTH MUST BE INCREASED TO 66" CLEAR.
8"
30"
LAVATORY
ADA 2010 §606.2
8"
30"
URINAL
ADA 2010 §605.3
8"
LOW FOUNTAIN
30" CENTER ON
HI-LOW DRINKING FOUNTAIN
ADA 2010 §602.2 & 602.5
M A
X
M
IN
60" MIN. CLEAR
AMBULATORY TOILET COMPARTMENT
ADA 2010 §604.8.2
42" MIN. CLEAR
42" GRAB BAR **
MAX.
12"
S E
L F
C L
O S
IN
G
M
IN
. C
L E
A R
W / A
C C
. L A
T C
H
W/ ACC. LATCH
SELF CLOSING
32" MIN. CLEAR
W/ ACC. LATCH
** ALL GRAB BARS TO BE CAPABLE OF SUPPORTING
250 LB. LOAD. REINFORCE PARTITION WALLS AS REQ.
WATER CLOSET SEAT HEIGHT
ADA 2010 §604.4
T .O
B
A R
0"
T .O
B
L O
C K
IN
G
8"
3"42" BLOCKING
12" MIN.24" MIN.
0"
48" BLOCKING 9"
42" 12"MAX
T .O
B
A R
16"-18"
WATER CLOSET REAR WALL VIEW
ADA 2010 §604.5.2
WATER CLOSET SIDE WALL VIEW
ADA 2010 §604.5.1
T .O
B
L O
C K
IN
G
8"
36" 6"
RECESSED DISPENSER
ANSI 117.1-2017 604.7.1
PROTRUDING DISPENSER
ABOVE GRAB BAR
ANSI 117.1-2017 604.7.1
"M
IN
"M A
X
24"MIN
36"MAX
"M
IN
"M A
X
42"MAX
24"MIN
36"MAX
"M
IN
42"MAX
24"MIN
PROTRUDING DISPENSER
BELOW GRAB BAR
ANSI 117.1-2017 604.7.1
MOUNTING HEIGHTS
LAVATORY AND MIRROR
2018 IPC §405.3.1
ADA 2010 §603.3
T O
M
IR
R O
E R
E D
S U
R F
A C
E
M
A X
M
A X
M
A X
M
IN
11" MIN.
8" MIN.
17" MIN.
INSULATE / PROTECT
EXPOSED PIPES AND
SURFACES
LAVATORY
ADA 2010 §606.3 & 606.5
/2
M
IN
TOILET SEAT
COVERS
ADA 2010 §308.3.2
T O
H
IG
H E
S T
C O
N T
R O
L S
SANITARY
NAPKIN DISPOSAL
ADA 2010 §308.3.1
T O
O P
E N
IN
G
RECESSED WASTE
DISPENSER
ADA 2010 §308.3.2
T O
O P
E N
IN
G
SANITARY
NAPKIN DISPENSER
ADA 2010 §308.3.2
T O
O P
E N
IN
G
M
A X
T O
H
IG
H E
S T
C O
N T
R O
L S
M
A X
SOAP DISPENSER
ADA 2010
§307.2 & 308.2.2
T O
H
IG
H E
S T
C O
N T
R O
L S
M
IN
"11" MIN.
MIN.
8"
M
IN
T .O
. S P
O U
T
M
A X
5" MAX. 15" MIN.
LOW DRINKING FOUNTAIN
ADA 2010 §306.3 & 602.5
HI-LOW DRINKING FOUNTAIN
ADA 2010 §306.3 & 602.4
M
IN
M
IN
T .O
. S P
O U
T
M
A X
M
A X
M
IN
BABY CHANGING STATION
ADA 2010 §306.3 & 902.3
T O
H
IG
H E
S T
C O
N T
R O
L S
AIR HAND DRYER
ADA 2010
§307.2 & 308.2.2
FIRE EXTINGUISHER
WALL MOUNT
NFPA 10 §6.1.3.8.1
M
A X
L B
S
M
A X
L B
S
FIRE EXTINGUISHER
CABINET
ADA 2010 §307.2 & 308.2.1
NFPA 10 §6.1.3.10.5
M
A X
URINAL
2018 IPC §405.3.1
ADA 2010 §605.2
SIGNAGE
SEE SHEET G-060
B .O
. L O
W E
S T
C H
A R
A C
T E
R
M
IN
T .O
H
IG
H
E S
T C
H A
R A
C T
E R
"M A
X
FIRE ALARM
PULL
ADA 2010 §308.2.1
T .O
. P U
L L
M
A X
VISUAL STROBE
ADA 2010 §702.1
NFPA 72 §18.5.5
B O
T T
O M
O F
L E
N S
M
A X
T .O
. L E
N S
M
A X
M
A X
15"MIN.
M
A X
T .O
. O P
E N
IN
G
15" 15"
M
A X
M
A X
COAT/ROBE HOOK
ADA 2010 §308.3.1
T .O
H
O O
K
Phone: (770) 345-2579
135 P RICKMAN INDUSTRIAL DR.
SUITE 100 CANTON, GA 30115
© 2025, CSC Design. These drawings are protected by the copyright laws of the United States. These drawings or any part thereof may not be used for any purpose or reproduced in any form or by any means without the written consent of CSC Design.
CSC
DESIGN,
INC.
ARCHITECTS ENGINEERS&
PROJECT NUMBER:
R E
V
IS
IO
N
S
/6
/2
:0 :3
P
M Y
P ro je c ts
\2 -0
D o u g la s C o u n ty
D O
T S to ra g e B u ild in g
D o u g la s C o u n ty
G
A \A rc h \0
R
E V
IT
\2
-0
D o u g la s C o u n ty
D O
T S to ra g e B u ild in g
R e v
.r v t
G-050
FOR CONSTRUCTION
ACCESSIBLITY
DETAILS
C S
C .2
4.
1.
25-026
D O
U G
L A
S C
O U
N T
Y D
O T
S T
O R
A G
E B
U
IL
D
IN
G
C
H
IC
A G
O A
V E
N U
E
D O
U G
LA
S
V
IL
LE
, G
A , 3
IN
T
E R
IO
R
A N
D E
X T
E R
IO
R
A L T
E R
A T
IO
N
A N
D R
E H
A B
IL
IT
A T
IO
N
F O
R
N O
D
A T
E
IS
S
U E
UP
LIFE SAFETY LEGEND
EXIT TRAVEL DISTANCE
TOTAL TRAVEL DISTANCE
EXIT DATA
EXIT NUMBER
E X
IT
LIFE SAFETY GENERAL NOTES
1. REFER TO PARTITION TYPES SCHEDULE FOR PARTITION TYPE DETAILS AND TESTED RATED
ASSEMBLY DETAILS.
STAIR EGRESS CAPACITY
DOOR EGRESS CAPACITY
DOOR EGRESS WIDTH
EXIT / EMERGENCY LIGHT
COMBINATION WITH EMERGENCY
BATTERY - SEE ELECTRICAL
DRAWINGS
34"
FIRE EXTINGUISHERFE
EXIT
EMERGENCY LIGHT FIXTURE -
SEE ELECTRICAL DRAWINGS
TD1: 100'-0"
TRAVEL DISTANCE
EXISTING BUSINESS OCCUPANCY [SPRINKLERED] STORAGE OCCUPANCY [SPRINKLERED]
LSC CHAPTER 39, IBC CHAPTER 3
GROUP B (BUSINESS) OCCUPANCY
TRAVEL DISTANCE = 300' MAX; LSC 39.2.6.3
COMMON PATH = 100'; LSC 39.2.5.3.1
DEAD END LIMIT = 50'; LSC 39.2.5.2
LSC CHAPTER 42, IBC CHAPTER 3
GROUP S-1 (STORAGE) OCCUPANCY
TRAVEL DISTANCE = 400' MAX; LSC TABLE 42.2.6
COMMON PATH = 100' MAX; LSC 42.2.5
DEAD END LIMIT = 100' MAX; LSC 42.2.5
LIFE SAFETY KEYNOTES LS
OCCUPANCY LEGEND
STORAGE 1
123456789
STRUCTURE NOT
IN SCOPE
STRUCTURE NOT IN
SCOPE
11,157.99 SF 500 GROSS
22 OCC
STORAGE 1
STORAGE
1,021.53 SF 500 GROSS
2 OCC
STORAGE 1
STORAGE
874.07 SF 500 GROSS
2 OCC
STORAGE 1
STORAGE
137.04 SF 500 GROSS
0 OCC
STORAGE 1
STORAGE
630.45 SF 500 GROSS
1 OCC
STORAGE 1
STORAGE
509.62 SF 500 GROSS
1 OCC
STORAGE 1
STORAGE
319.20 SF 500 GROSS
1 OCC
STORAGE 1
STORAGE
EXIT
EXIT EXIT EXIT
E X
IT
EXIT
E X
IT
EXIT
170E X
IT
170E X
IT
170E X
IT
170E X
IT
170E X
IT
34"
FE
FE
FE
FE
TRAVEL DISTANCE = 106' - 8"
T R
A V
E L D
IS
T
A N
C E
TRAVEL DISTANCE = 87' - 0"
A
B
C
PROSPOSED FIRE RISER LOCATION
VERIFY WITH FIRE MARSHAL FOR
EXTERIOR FIRE RISER SIGNAGE
LOCATION AND KNOX BOX
123456789
STRUCTURE NOT
IN SCOPE
STRUCTURE NOT IN
SCOPE
2,171.48 SF 50 GROSS
43 OCC
BUSINESS
BUSINESS - CONCEN.
117.32 SF 500 GROSS
0 OCC
STORAGE 1
STORAGE
287.76 SF 50 GROSS
6 OCC
BUSINESS
UNCONCENTRATED
OCCUPANCY LEGEND
BUSINESS
STORAGE 1
STORAGE AREA BELOW
OPEN TO BELOW
OPEN TO BELOW
EXIT
EXIT
170E X
IT
170E X
IT
" 34
FE FE
T R
A V
E L D
IS
T
A N
C E
A
B
C
Phone: (770) 345-2579
135 P RICKMAN INDUSTRIAL DR.
SUITE 100 CANTON, GA 30115
© 2025, CSC Design. These drawings are protected by the copyright laws of the United States. These drawings or any part thereof may not be used for any purpose or reproduced in any form or by any means without the written consent of CSC Design.
CSC
DESIGN,
INC.
ARCHITECTS ENGINEERS&
PROJECT NUMBER:
R E
V
IS
IO
N
S
/6
/2
:0 :4
P
M Y
P ro je c ts
\2 -0
D o u g la s C o u n ty
D O
T S to ra g e B u ild in g
D o u g la s C o u n ty
G
A \A rc h \0
R
E V
IT
\2
-0
D o u g la s C o u n ty
D O
T S to ra g e B u ild in g
R e v
.r v t
LS101
FOR CONSTRUCTION
LIFE SAFETY
PLANS
C S
C .2
4.
1.
25-026
D O
U G
L A
S C
O U
N T
Y D
O T
S T
O R
A G
E B
U
IL
D
IN
G
C
H
IC
A G
O A
V E
N U
E
D O
U G
LA
S
V
IL
LE
, G
A , 3
IN
T
E R
IO
R
A N
D E
X T
E R
IO
R
A L T
E R
A T
IO
N
A N
D R
E H
A B
IL
IT
A T
IO
N
F O
R
OCCUPANCY USE SCHEDULE
FUNCTION/USE AREA FACTOR
CALCULATED
OCCUPANT
LOAD
ACTUAL
OCCUPANT
OVERRIDE
DESIGN
OCCUPANT
LOAD
LEVEL 01
STORAGE 1
STORAGE 14,649.91 SF 500 GROSS 29 0 29
LEVEL 02
BUSINESS
BUSINESS - CONCEN. 2,171.48 SF 50 GROSS 43 0 43
UNCONCENTRATED 287.76 SF 50 GROSS 6 0 6
STORAGE 1
STORAGE 117.32 SF 500 GROSS 0 0 0
TOTAL OCCUPANT LOAD 17,226.47 SF 78 0 78
OCCUPANT TOTAL NUMBER OF EXITS
MIN. REQ. PROVIDED
N/A N/A
MIN. REQ. PROVIDEDMIN. REQ. PROVIDED
HORIZONTAL: 0.2/OCC STAIRWAY: 0.3/OCC
16"
EGRESS CAPACITY:
2 7 238"
N O
D
A T
E
IS
S
U E
/0
/2
R
E V
IS
IO
N
C
O U
N T
Y R
E Q
U E
S T
E D
U P
D A
T E
S
LS101 | 1/16" = 1'-0"1 LIFE SAFETY PLAN - LEVEL 1
LS101 | 1/16" = 1'-0"2 LIFE SAFETY PLAN - LEVEL 2
PLUMBING FIXTURE REQUIREMENTS SCHEDULE
PLUMBING FIXTURE COUNT AREA
CALCULATED
OCCUPANT
LOAD
WATER CLOSETS LAVATORIES
DRINKING
FOUNTAIN
MALE FEMALE MALE FEMALE
COUNTCOUNT URINAL COUNT COUNT COUNT COUNT
LEVEL 01
27 - STORAGE 14,649.91 SF 29 0.15 0.07 0.15 0.15 0.15 0.03
LEVEL 02
10 - BUSINESS 2,459.24 SF 49 0.98 0.49 0.98 0.61 0.61 0.49
27 - STORAGE 117.32 SF 0 0.00 0.00 0.00 0.00 0.00 0.00
17,226.47 SF 78 1.13 0.56 1.13 0.76 0.76 0.52
WATER CLOSETS
MALE
MIN.
REQ. PROVIDED
FEMALE
LAVATORIES
MALE FEMALE
BATH / SHOWER DRINKING
FOUNTAINS
MIN.
REQ. PROVIDED
MIN.
REQ. PROVIDED
MIN.
REQ. PROVIDED
MIN.
REQ. PROVIDED
MIN.
REQ.
URINALS
PROVIDED
W.C.
PROVIDED
PLUMBING FIXTURE COUNT SCHEDULE: LEVEL 01 & LEVEL 02
1 1 1 1 1 1 1 1 1 N/A N/A 1 1
TN
TN
ADDITIONAL ADA AND REGULAR RESTROOMS ARE AVAILABLE AT THE NEW DOT OFFICE FACILITY WITHIN 500' OF THIS BUILDING.
DN
DN
AD402
AD402
AD402
AD402
AD401
AD401AD301
AD401
AD401
AD301 4
14'-5 1/2" 25'-0" 25'-0" 25'-0 3/4" 22'-0" 25'-0" 25'-0" 24'-5" 30'-9"
AD402
AD402
STORAGE AREA
OVHD OVHD OVHD OVHD OVHD OVHD OVHD OVHD
OVHD OVHD
RR RR
WC
SH
STORAGE
STORAGE
STORAGE
RETAINING WALL
STRUCTURE NOT
IN SCOPE
STRUCTURE NOT IN
SCOPE
STORAGE
A D
A D
A D
A D
STORAGE
STO.
185'-11 1/4" 61'-2"
A A
BB
CC
AD3013
AD301
AD402
AD402
AD402
AD402
AD401
AD401
AD301 4
STORAGE AREA BELOW
OPEN TO BELOW
OPEN TO BELOW
AD402
AD402
RR RR
M E
C H
STORAGE
STO
EXISTING AIR COMPRESSOR
WORKSHOP 3 WORKSHOP 4
OFFICE/ENTRY
UPPER ENTRY
W.SHOP 2W.SHOP 1
STRUCTURE NOT
IN SCOPE
STRUCTURE NOT IN
SCOPE
14'-5 1/2" 25'-0" 25'-0" 25'-0 3/4" 22'-0" 25'-0" 25'-0" 24'-5" 30'-9"
OPEN TO BELOW
OPEN TO BELOW
A D
A D
185'-11 1/4"
STAIR
A A
BB
CC
61'-2"
AD3013
AD301
AD301
DEMOLITION LEGEND
DEMOLITION GENERAL NOTES
1. CONTRACTOR SHALL PROTECT ALL PORTIONS SCHEDULED TO REMAIN / NOT SCHEDULED
FOR DEMOLITION. CONTRACTOR SHALL RESTORE ANY AND ALL DAMAGED AREAS
SCHEDULED TO REMAIN THROUGH DEMOLITION AND CONSTRUCTION PHASES TO ORIGINAL
LIKE NEW CONDITION AT NO COST TO THE OWNER, TYP.
2. REMOVED AND SALVAGED MATERIAL AND EQUIPMENT SHALL BE STORED ON SITE AND AS
DIRECTED BY THE OWNER.
3. CONTRACTOR SHALL MAINTAIN SAFE ACCESS TO AND FROM ALL BUILDING EXITS AT ALL
TIMES. CONTRACTOR SHALL COORDINATE WITH OWNER SCHEDULING OF WORK TIMES,
PRIOR TO COMMENCEMENT OF ANY AND ALL WORK.
4. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND CONDITIONS SHOWN ON THE
DRAWINGS AND IMMEDIATELY NOTIFY ARCHITECT OF ANY DISCREPANCIES PRIOR TO
ORDERING OR FABRICATING MATERIALS OR OTHERWISE PROCEEDING WITH THE WORK.
5. PROVIDE LABOR, MATERIAL, EQUIPMENT AND SERVICES REQUIRED TO EXECUTE AND
COMPLETE ALL ITEMS OF WORK AS SHOWN OR INDICATED ON THE DRAWINGS AND AS
SPECIFIED, INCLUDING INCIDENTAL ITEMS TO AFFECT A FINISHED AND COMPLETE JOB, EVEN
THOUGH SUCH ITEMS ARE NOT SHOWN OR SPECIFICALLY MENTIONED.
6. MAINTAIN PREMISES AND PUBLIC PROPERTIES FREE FROM ACCUMULATIONS OF WASTE
MATERIALS, DEBRIS AND RUBBISH CAUSED BY OPERATIONS.
7. CONTRACTOR SHALL BE COMPLETELY RESPONSIBLE FOR BRACING AND SHORING OF THE
STRUCTURE DURING DEMOLITION AND CONSTRUCTION TO ENSURE STABILITY.
8. THE CONTRACTOR SHALL RESTORE TO IT'S ORIGINAL CONDITION AND QUALITY (AS
APPROVED BY THE ARCHITECT, ENGINEER, UTILITY REPRESENTATIVE AND/OR APPLICABLE
OWNER REPRESENTATIVE) ALL SITE APPURTENANCES DAMAGED AT NO ADDITIONAL COST
TO THE OWNER.
9. DEMOLISH ALL FLOORING, CEILINGS AND WALL FINISHES.
10. PATCH AND REPAIR ANY AND ALL DAMAGED AREAS SCHEDULED TO REMAIN TO LIKE NEW
CONDITION.
11. REMOVE EXISTING ELECTRICAL LIGHT FIXTURES. REMOVE ANY AND ALL EXISTING CONDUIT, JUNCTION BOXES, WIRING AND RELATED LIGHTING ACCESSORIES IN THEIR ENTIRETY - CAP
OFF IN A CODE COMPLIANT MANNER AT INACCESSIBLE/CONCEALED LOCATIONS AS
REQUIRED, TYP.
12. CONTRACTOR TO SAW CUT WALLS AND FLOORS AT TRANSITIONS OF SCHEDULED
DEMOLITION TO PROVIDE A CLEAN EDGE FOR FUTURE WORK.
13. NOTIFY ARCHITECT IMMEDIATELY UPON DISCOVERING ANY UNFORESEEN "UNKNOWNS," FOR
FURTHER DIRECTION PRIOR TO PROCEEDING WITH FURTHER WORK.
14. AFTER COMPLETION OF WORK, DEMOLITION AND NEW, ALL REMAINING CONSTRUCTION
MATERIALS (EXCEPT SPECIFIED ATTIC STOCK) SHALL BECOME THE PROPERTY OF THE
GENERAL CONTRACTOR AND SHALL BE DISPOSED OR/REMOVED FROM THE SITE IN
ACCORDANCE WITH ALL APPLICABLE LAWS, ORDINANCES, RULES AND REGULATIONS UNLESS
NOTIFIED OTHERWISE (INCLUDING BUT NOT LIMITED TO SURPLUS STOCK MATERIAL SUCH AS
PAINT, TILES, ETC.). CONTRACTOR SHALL ALSO REMOVE ALL WASTE DEBRIS, RUBBISH,
TOOLS AND EQUIPMENT UPON COMPLETION OF WORK. THROUGHOUT CONSTRUCTION, SITE
SHALL BE ORGANIZED AND CLEANED BY CONTRACTOR ON A DAILY BASIS.
15. RELOCATE ANY AND ALL EXISTING UTILITIES IN AFFECTED DEMOLITION SCHEDULED TO BE
REUSED TO AREAS SCHEDULED AS NEW OR REMAINING ADJACENT AREAS.
EXISTING WALL TO BE REMOVED
EXISTING WALL TO REMAIN
EXISTING DOOR TO BE REMOVED
EXISTING WINDOW TO BE REMOVED
Phone: (770) 345-2579
135 P RICKMAN INDUSTRIAL DR.
SUITE 100 CANTON, GA 30115
© 2025, CSC Design. These drawings are protected by the copyright laws of the United States. These drawings or any part thereof may not be used for any purpose or reproduced in any form or by any means without the written consent of CSC Design.
CSC
DESIGN,
INC.
ARCHITECTS ENGINEERS&
PROJECT NUMBER:
R E
V
IS
IO
N
S
/6
/2
:0 :4
P
M Y
P ro je c ts
\2 -0
D o u g la s C o u n ty
D O
T S to ra g e B u ild in g
D o u g la s C o u n ty
G
A \A rc h \0
R
E V
IT
\2
-0
D o u g la s C o u n ty
D O
T S to ra g e B u ild in g
R e v
.r v t
AD100
FOR CONSTRUCTION
DEMOLITION
FLOOR PLANS -
LEVELS 1 & 2
C S
C .2
4.
1.
25-026
D O
U G
L A
S C
O U
N T
Y D
O T
S T
O R
A G
E B
U
IL
D
IN
G
C
H
IC
A G
O A
V E
N U
E
D O
U G
LA
S
V
IL
LE
, G
A , 3
IN
T
E R
IO
R
A N
D E
X T
E R
IO
R
A L T
E R
A T
IO
N
A N
D R
E H
A B
IL
IT
A T
IO
N
F O
R
AD100 | 1/16" = 1'-0"1 DEMOLITION FLOOR PLAN - LEVEL 1
AD100 | 1/16" = 1'-0"2 DEMOLITION FLOOR PLAN - LEVEL 2
TN
TN
N O
D
A T
E
IS
S
U E
/0
/2
R
E V
IS
IO
N
C
O U
N T
Y R
E Q
U E
S T
E D
U P
D A
T E
S
23456789
AD402
AD402
AD402
AD402
AD301 4
AD402
AD402
OVHD
STORAGE AREA
OVHDOVHDOVHDOVHDOVHD
OVHD OVHD
EDGE OF ORIGINAL
STORAGE BUILDING
STRUCTURE
NOT IN SCOPE
STRUCTURE NOT
IN SCOPE
'-9
/4
A D
A D
M A
T C
H
LI
N E
A
B
C
1111111111
11 11
44 42 42 7 7 73
30614
14 30
32 25
37 7 7 7
AD301
AD301
12 2
AD401
AD401
AD401
AD401
AD402
AD402
RR
RR
W.C.
SHOWER
STORAGE AREA
OVHD OVHD
STORAGE STORAGE
STORAGE
STORAGE
A D
A D
M A
T C
H
LI
N E
M A
T C
H
LI
N E
STORAGE
STORAGE
A
B
C
OVHD
OVHD
11 117 7 7 47 14
43 25
48 48
21 25
33 38
33 38
20 5858
AD3013
AD301
DEMOLITION LEGEND
EXISTING WALL TO BE REMOVED
EXISTING WALL TO REMAIN
EXISTING DOOR TO BE REMOVED
EXISTING WINDOW TO BE REMOVED
DEMOLITION PLAN KEY NOTES
1 - DEMOLISH EXISTING ROOF THROUGHOUT INCLUDING ANY ROOF INSULATION AND CORRUGATED
METAL DECK
2 - DEMOLISH EXISTING ROOF VENT
3 - DEMOLISH AND REPLACE EXISTING STRUCTURAL MAINFRAME AS INDICATED IN DASHED RED
4 - DEMOLISH AND REPLACE EXISTING PURLINS AS INDICATED IN DASHED RED
5 - DEMOLISH AND REPLACE PURLINS AS REQUIRED BASED ON CONDITION. SEE STRUCTURAL FOR
MORE INFORMATION
6 - DEMOLISH EXISTING EXTERIOR METAL WALL PANEL AND ANY EXISTING WALL INSULATION.
DEMOLISH ANY UNUSED WALL MOUNTED CONDUITS, WIRING, PLUMBING LINES, SIGNAGE, ETC.
7 - EXISTING REINFORCED CONCRETE WALL TO REMAIN. REMOVE ANY UNUSED SURFACE MOUNTED
CONDUITS, WIRING, PLUMBING LINES, ETC.
8 - EXISTING METAL BRACING TO REMAIN
9 - DEMOLISH EXISTING VINYL WALLS. PREPARE FOR NEW WALL INFILL
10- DEMOLISH EXISTING CANOPY
11- DEMOLISH EXISTING OVERHEAD DOOR, DOOR JAMBS, TRACKS, AND/OR HOUSING
12- DEMOLISH EXISTING GARAGE DOOR AND DOOR GUIDES
13- EXISTING ROLL-UP DOOR TO REMAIN. GC TO CLEAN, ADJUST, AND GREASE DOOR AS REQUIRED
14- DEMOLISH EXISTING DOOR, FRAME, AND HARDWARE
15- DEMOLISH EXISTING DOUBLE DOOR, FRAME, AND HARDWARE
16- DEMOLISH EXISTING WINDOW AND FRAME, PREPARE FOR OPENING INFILL
17- REMOVE AND SALVAGE EXISTING WINDOW FOR RE-INSTALLATION
18- DEMOLISH AND REPLACE EXISTING WINDOW, FRAME, AND/OR TRIMS
19- EXISTING INTERIOR WINDOW TO REMAIN. REMOVE PAINT FROM GLASS PANELS, MULLIONS, AND
FRAME. PREPARE FOR NEW PAINT
20- DEMOLISH EXISTING AC CONDENSER UNIT
21- EXISTING EXTERIOR CONCRETE STAIR TO REMAIN. CLEAN/ PRESSURE WASH AS REQUIRED
22- EXISTING STAIR CONCRETE CURB TO REMAIN
23- EXISTING CONCRETE FLOOR SLAB TO REMAIN
24- DEMOLISH EXISTING GYP. BOARD AND / OR WOOD PANELING AT INTERIOR SIDE OF WALL. PREPARE
WALL FOR NEW GYP. BOARD.
25- REMOVE VEGETATION AND/OR WEEDS AROUND BUILDING PERIMETER
26- DEMOLISH EXISTING INTERIOR WALLS AS DEPICTED WITH DASHED LINES
27- EXISTING METAL WALL FRAMING TO REMAIN, DEMOLISH EXISTING T1-11 PANEL AND PREPARE FOR
NEW SHEATHING INSTALLATION, BOTH SIDES
28- EXISTING INTERIOR WALL TO REMAIN, REPLACE EXISTING WALL BASE AND TRIMS. PATCH AND
REPAIR ANY DAMAGED T1-11 PANELS AND PREPARE FOR NEW PAINT
29- EXISTING CORRUGATED WALL TO REMAIN. REMOVE ANY UNUSED SURFACE MOUNTED CONDUITS AND/OR DEVICES, REMOVE EXISTING PAINT. PATCH, REPAIR, AND CLEAN CORRUGATED WALL AS
REQUIRED AND PREPARE FOR NEW PAINT
30- DEMOLISH EXISTING GUTTERS AND DOWNSPOUTS, TYPICAL THROUGHOUT
31- DEMOLISH EXISTING METAL RAILING
32-…