Y1DA--Replacement AC Package Units at St. Albans Community Living Center 179-00 Linden Blvd, Jamaica, NY 11425
Closed Solicitation Posted
This opportunity was awarded. See the award notice from .
- Solicitation number
- 36C24226B0035
- Agency
-
Veterans Integrated Service Network 2
Veterans Health Administration, Department of Veterans Affairs
- Responses due
- Set-aside
- No set-aside
Opportunity facts
- NAICS code
- 236220 Commercial and Institutional Building Construction
- Points of contact
Notice details come from SAM.gov. Updated .
About this opportunity
The Department of Veterans Affairs Veterans Health Administration, Veterans Integrated Service Network 2 seeks qualified contractors to furnish all labor, materials, equipment, and supervision for the replacement and restoration of HVAC systems at the St. Albans Community Living Center in Jamaica, New York. The scope of work includes removing and replacing air handling units (AHUs), AC package units, an outdoor air-cooled chiller, and outdoor condensers across multiple buildings, as well as restoring and verifying the operational status of eight AC package units and one AHU. The contractor must also install new electric air curtains (MARS Model 96HV-2 or similar), provide pretesting and post-testing with balancing and deficiency reports, clean and certify all ductwork, furnish lockable local disconnect switches, and submit as-built drawings and shop drawings. The contract is awarded on a sealed bid basis to the lowest responsive and responsible bidder, with sealed bids due by April 16, 2026 at 9:45 AM Eastern Standard Time via email, public bid opening at 10:00 AM the same day, a mandatory pre-bid site visit on March 19, 2026 at 10:00 AM, and a written question submission deadline of March 26, 2026 at 4:00 PM.
This procurement is designated as a 100% Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside, requiring all offerors to be registered in the System for Award Management with verified SDVOSB status and subject to subcontracting limitations of 85% for general construction work. The estimated contract value ranges between $500,000 and $1,000,000, with a performance period of 365 calendar days from the Notice to Proceed and a one-year defect warranty from completion and acceptance. Key requirements include maintaining an English-speaking supervisor on-site with a minimum of five years' experience on similar projects, obtaining performance and payment bonds if the contract exceeds $150,000, submission of a bid bond of at least 20% of the bid price, compliance with prevailing wage determinations established by New York State wage decision NY20260003, and adherence to all applicable Federal, State, and Local codes including OSHA regulations and NFPA Life Safety Codes. The work will be performed at the St. Albans Community Living Center, located at 179-00 Linden Blvd, Jamaica, New York 11425, with all work coordinated during 8:00 AM to 4:30 PM Eastern time duty hours across multiple buildings including the Chapel, Commissary Office, Boiler Plant, and various nursing and food service facilities.
Notice text
2 versions
Update #2 · Latest ·
Replacement AC Package Units; Solicitation No. 36C24226B0035; Project No. 630A4-26-409 at St. Albans Community Living Center, 179-00 Linden Blvd, Jamaica, NY 11425.
The purpose of this amendment is to provide responses to Request for Information (RFI) and Questions, RFIs and Questions responses are hereby included. Additional changes to the Scope of Work are also included.
Scope of Work Addition and Remove
Highlighted in Red = Removed from Scope of Work
Highlighted in Green = Added to Scope of Work
Scope of Work:
Contractor to provide pretesting, post-testing, balancing and deficiency reports for all replacement / restoration work to verify all work.
Contractor to furnish and install lockable local disconnect switches for all installations.
Contractor to be responsible for any new duct connections and cleaning of existing ductwork used in HVAC renovations. Contractor to clean and certify all ductwork.
Remove and replace the following, one unit per location listed:
AHUs serving:
Building 87 Chapel
Building 88 Commissary Office
AC package units serving:
Building 89 Floor 2 Pub
Outdoor Air-cooled chiller serving:
Building 87 Sterile Processing Department (SPD)
Outdoor condensers serving:
Building 87 Chapel AHU
Building 89 Floor 2 Dining Room AC Package Unit
Building 89 Floor 2 Pub AC Package Unit
Restore and make operational the following, one unit per location listed:
AC Package Units serving:
Building 64 Boiler Plant
Building 85/86 Floors 2 and 3
Building 86 Adult Day Health Care.
Building 89 Nutrition and Food Services (NFS)
Building 89 Pharmacy
Building 89 Pharmacy Storage
Building 89 Recreation Service
Building 91 Director Conference Room
AHUs serving:
Building 88 Commissary Office
Building 88 Commissary Dom
HVAC units located in:
Building 64 Boiler Plant Ground Floor
Building 64 Boiler Plant Lower Level
Install new electric air curtains; contractor to supply power, breakers, and conduit.
Remove existing electric air curtains located at:
Building 89 Loading Dock
Building 89 Main Entrance
Install new electric air curtains, MARS Model 96HV-2 or similar, at locations:
Building 85 Main Entrance
Building 88 Outpatient Clinic Entrance
Building 89 Loading Dock
Building 89 Main Entrance
Performance Period: 365 Calendar Days
Responses to RFIs/Questions
S.O.W. ITEM 5-a-i Building 64 Boiler Plant . Please provide information. No documentation was made available nor was information available on the walk-through
VA Response: Allocation: (16) hours of diagnostics, (16) hours for deficiency report, (40) labor hours, and $10,000 in materials for repairs/restoration based on findings of diagnostics report.
S.O.W. ITEM 6-b-i and 6-b-ii Please provide distance(s) to VA electrical sources for NEW air curtains, Bldg. 85 and 88.
VA Response: The maximum distance to VA electrical sources for the new air curtains in Buildings 85 and 88 is not to exceed 150 feet.
Are the RETURN AIR FANS and EXHAUSTS (which are physically separate from the AHUs on the listed built-up systems) to be included in the replacements/restorations?
VA Response: See Question 1 response.
S.O.W. ITEM 4-a-ii and S.O.W. ITEM 5-b-i appear contradictory. 4-a-ii calls for the replacement of the COMISSARY OFFICE AHU while 5-b-i calls for restoration. Please clarify.
VA Response: There are two Commissary units: Commissary Office and Commissary Dom. Both are for restoration.
It appears that the TAG CANTEEN and NFS represent the same unit on two separate documents. Refer to the EXCELL EQUIPMENT LIST page 1, line 7 and compare to S.O.W. ITEM 5-a-iv. Please clarify.
VA Response: Disregard Canteen Condensing Unit in the Excel Equipment List. NFS in this case refers to the AHU found in the Building 89 Basement Mechanical Room A-215.
BUILDING 89 CANTEEN - Please confirm that the AHU shall be restored (S.O.W. ITEM 5-a-iv) while the DX condensing unit is to be replaced.
VA Response: The condensers to be replaced are associated with the Dining Room unit, the Pub unit, and the Chapel AHU. The NFS unit s outdoor condenser is not in scope for replacement.
Will related ancillary equipment such as STEAM GENERATORS be restored/replaced based on the specific AHU requirements?
VA Response: See Question 1 response.
Please provide any diagnostic information available for the restoration items.:
VA Response: See Question 1 response.
Please provide specifications for the new equipment as available.
VA response: Refer to the 630A4-26-409 Equipment Listing excel sheet attached on the solicitation with Manufacturer/Model# for reference only. The contractor is required to submit an Approved Equal for approval.
Please review the attached INITIAL EQUIPMENT LISTING document we have created. Please make any corrections to it and/or confirm it is a comprehensive list.
VA Response: Please see the attached VA Response SOW and VA Response Equipment Listing.
Confirm the extent of new piping and ductwork, on either the restoration or replacement units, is to be limited to the boundaries of the MER unless otherwise noted.
VA Response: Confirmed, new piping and ductwork are limited to the boundaries of the MER only unless otherwise noted.
Please provide a list of required drawings. Will there be engineered and stamped drawing required?
VA Response: Provide as-built dwgs, shop drawings, cut sheets, and certified balancing reports as typically required.
Please confirm preferred vendor for DDC control work is JCI John Mirrione.
VA Response: Confirmed. Johnson Controls
Confirm that TESTING AND BALANCING of the completed AHU work shall be of total fluid flows for equipment performance only to meet the submittal requirement. There shall not be complete distribution system balancing for ither air or water flow.
VA Response: Contractor to provide pretesting, post-testing, balancing and deficiency reports for all related new work replacement / restoration work.
Confirm that rigging for the DINING ROOM YORK ACCU-1 condensing unit located at Bldg. 89 in the lower courtyard area is approved from the grassy area at the upper level and that no underground construct would prohibit access.
VA Response: There is no prohibited access if rigging complies with OSHA requirements.
EXTENT of ductwork cleaning please provide. In all cases is it up to the MER limit or inclusive of other areas. Will biological and cleanliness sampling be required as per trade or VA requirements?
VA Response: Ductwork cleaning is required up to the MER boundaries unless otherwise specified, with biological and cleanliness sampling mandated per industry and VA standards.
630A4-26-409 Replacement AC Package Units
St. Albans VAMC 179-00 Linden Blvd, Jamaica, NY 11425
VA RFI Response Equipment Listing
BUILDING
REPLACE/REPAIR/NEW
AREA SERVED
DESCRIPTION
64
Repair
Boiler Plant
HVAC Unit Ground Level
64
Repair
Boiler Plant
HVAC Unit Lower Level
86
Repair
Intermediate Care
BASEMENT AHU-1 MCQUAY
86
Repair
Adult Day Care
ACU-3 TRANE INTELLIPAK
87
Replace
Chapel
Indoor AHU and Outdoor Condensing Unit
87
Replace
Nursing Care
Sterile Processing Department (SPD) Package Chiller
88
Repair
Commissary Office
AHU-1 MCQUAY ROOM S-203
88
Repair
Commissary Dom
AHU-2 Floor 2 Mechanical Room
89
Replace
Dining Room
York Outdoor Condenser Unit Only, No AHU Work
89
Replace
Dining Room Pub
Indoor Package Unit and Outdoor Condenser
89
Repair
Recreation Service
Carrier Vert Pkg. Floor 2 Closet
89
Repair
Pharmacy
Room A-141 Small Tonnage
89
Repair
Pharmacy Storage
Room A-146 Small Tonnage
91
Repair
Director Conference
MER ROOM E-131 FLOOR 1 SCAC-3
85
New
Bldg. 85 Main Entrance
Air Curtain
88
New
Outpatient Clinic Entrance
Air Curtain
89
Replace
Bldg. 89 Main Entrance
Air Curtain
89
Replace
Loading Dock
Air Curtain
Update #1 ·
.
Files
| File | Type | Posted |
|---|---|---|
| 36C24226B0035 0001.docx | DOCX document | |
| Wage Determination.pdf | ||
| VA NOTICE OF LIMITATIONS ON SUBCONTRACTING CERTIFICATION.pdf | ||
| 52.225-2 Buy American Certificate.pdf | ||
| NY Tax Exempt Form.pdf | ||
| 630A4-26-409 Equipment Listing.xlsx | XLSX spreadsheet | |
| 36C24226B0035_1.docx | DOCX document |
Notice history
| Notice | Type | Posted |
|---|---|---|
| Y1DA--NRM-CONST 630A4-26-409 Replacement AC Package Units | Award Notice | |
| This notice | Solicitation | |
| Y1DA--Replacement AC Package Units at St. Albans Community Living Center 179-00 Linden Blvd, Jamaica, NY 11425 | Pre-Solicitation |
Similar open opportunities
| Opportunity | Agency | Set-aside | Responses due |
|---|---|---|---|
| Z2NZ--Turn Key Chiller Equipment (Purchase and Install) | Veterans Integrated Service Network 16 | Service-Disabled Veteran-Owned Small Business | |
| Y1DZ--replace chilled water pump at the boiler plant | Veterans Integrated Service Network 2 | Service-Disabled Veteran-Owned Small Business | |
| Building 13 Stair and Roof Replacement at Castle Point VAMC | Veterans Integrated Service Network 2 | Service-Disabled Veteran-Owned Small Business | |
| Z1DA--Modernize Damen (Bldg. 1) Elevators Construction 537-24-101 | Veterans Integrated Service Network 12 | Service-Disabled Veteran-Owned Small Business | |
| Y1DA--Project620-22-110 Replace and Upgrade Fire alarm System at Montrose VAMC | Veterans Integrated Service Network 2 | Service-Disabled Veteran-Owned Small Business |
On GovTribe
Work this opportunity
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity