J061--Emergency Switchgear Repairs PWS 539
Open Pre-Solicitation Posted
- Solicitation number
- 36C25027Q0125
- Agency
-
Veterans Integrated Service Network 10
Veterans Health Administration, Department of Veterans Affairs
- Responses due
- Set-aside
- No set-aside
Opportunity facts
- NAICS code
- 811310 Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance
- Place of performance
- Cincinnati Vamc 3200 Vine Street, United States
- Points of contact
Notice details come from SAM.gov. Updated .
About this opportunity
The Department of Veterans Affairs, through the Cincinnati VA Medical Center in VISN 10, is conducting market research by sources sought notice for emergency repairs to failed emergency generators and associated paralleling switchgear, with responses due December 7, 2026. The set-aside line reads No Set-Aside Used, and the notice is for information only: firms must not submit proposals or questions. Place of performance is Cincinnati VA Medical Center, 3200 Vine Street, Cincinnati, Ohio 45220-2637, Building 1, Room B013.
The attached Performance Work Statement (dated November 23, 2026) describes a firm-fixed-price contract with a 120-day period of performance covering two Kohler 1500REOZDC generators (1,560 kW each, 277/480V, MTU Detroit Diesel T1238A36 engines). Scope includes replacing damaged MFR13 and reverse power protective relays, modifying switchgear doors and wiring, programming and testing replacement relays, load-bank testing, and an operational test of the full emergency power system. Load-bank testing requires a minimum of 4 hours per generator at 30%, 50%, and 75% of nameplate kW rating. Generator work occurs on separate weekends, one generator per weekend, on Saturdays and Sundays unless the Contracting Officer approves otherwise in writing.
Contractor requirements include obtaining "proper security clearance" (level not stated), VAMC/VAACC identification badges, general liability insurance of at least $1,000,000 per occurrence, and a licensed Professional Engineer for design-build oversight. Deliverables include relay settings, updated ABB system drawings, individual load-bank test reports, and a final paralleling and functional test report.
Respond by email to ronald.heidemann@va.gov with firm name, socio-economic status, whether the firm holds a contract vehicle available for ordering, and any alternative NAICS code. Product Service Code is J061 and NAICS is 811310. Attachments include 2023 ABB service and test records for the switchgear and a July 27, 2026 ABB email describing relay-upgrade work beyond the original plan.
Notice text
The Cincinnati Veterans Administration Medical Center (VAMC) has a requirement to provide repairs to generator operation to address failed generators & associated paralleling switchgear.
The intention of this Sources Sought is to obtain information only. Please do not send a proposal or questions.
Requested information:
To aid acquisition planning, we re seeking capable and interested firms for the information requested. If your firm meets the criteria please send the point of contact (ronald.heidemann@va.gov) the following, via email:
Firm s Name
Socio-Economic Status
Whether or not your company has a contract vehicle we can order against
If your company believes there is an alternative NAICS code please provide this
Please attachments for more information.
Files
Show all 12
Notice history
| Notice | Type | Posted |
|---|---|---|
| This notice | Pre-Solicitation | |
| J061--Emergency Switchgear Repairs PWS 539 | Pre-Solicitation |
Similar open opportunities
| Opportunity | Agency | Set-aside | Responses due |
|---|---|---|---|
| APT Generator Switchgear Testing – Alvin C. York VA Medical Center | Veterans Integrated Service Network 9 | No set-aside | |
| Z1DA--Project No. 583-22-106- Replace Electrical Panels & Expand Distribution. | Veterans Integrated Service Network 10 | No set-aside | |
| Increase Emergency Power | Veterans Integrated Service Network 1 | Service-Disabled Veteran-Owned Small Business | |
| J061--TVHS Generator PM/Bank Testing Base+4 | Veterans Integrated Service Network 9 | Service-Disabled Veteran-Owned Small Business | |
| V301--539 - Fifth Floor Pharmacy Move Service Contract | Veterans Integrated Service Network 10 | No set-aside |
On GovTribe
Work this opportunity
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity