WMA Midland HVAC Drawings #1021 - Pages 9-15 (Structural).pdf
PDF 843 KB Posted
- Attached to
- WMA Midland Campus HVAC - RFP 1021
- Solicitation number
- RFP WMA 210000002377 3
- Issued by
- Macomb County, Whitehall City, Michigan
About this file
This document comprises structural design drawings and general notes for HVAC improvements at Waterford Montessori Academy's Midland Campus, prepared under Project No. 1021 for bidding and permitting as of July 12, 2021. The project involves the installation of heating, ventilation, and air conditioning equipment requiring structural modifications to the existing building, including roof framing alterations, equipment support systems, and opening preparations. The structural work encompasses steel beam installation, wood deck modifications, concrete pad construction, and equipment mounting curbs to support multiple DOAS (Dedicated Outdoor Air System) units and RTU (Rooftop Unit) equipment with weights ranging from 2,850 to 3,900 pounds. All work must comply with Title 24 of the California Code and the Michigan Building Code (IBC 2015), with design criteria including seismic design category B classification, 120 mph basic wind speed, and occupancy risk category III. The project site is located at the existing academy facility where bidders are required to visit and verify existing conditions before submitting proposals.
The structural design establishes comprehensive requirements for materials, fabrication, and construction methodology across structural steel, cast-in-place concrete, masonry, and wood components. All structural steel must conform to ASTM standards with specified grades and yield strengths, including hot-dip galvanizing for weather-exposed elements. Concrete work requires 4,000 psi compressive strength with specific mix designs and curing requirements, while wood framing must utilize pressure-treated lumber and comply with ANSI/AWC National Design Specification standards. The contractor bears sole responsibility for jobsite safety, shop drawing coordination and review, field verification of all dimensions and existing conditions, and protection of adjacent surfaces. Special inspection agencies must submit testing and inspection programs for approval at least two weeks prior to work commencement, with inspection reports due within 48 hours of completed work. No core drilling or field cutting of structural elements is permitted without written structural engineer approval, and any discrepancies between contract documents and site conditions must be reported to the architect before construction proceeds.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. ALL WORK SHALL COMPLY WITH TITLE 24 OF THE CALIFORNIA CODE OF CALIFORNIA
BUILDING CODE, LATEST EDITION, AND ALL OTHER LOCAL OR STATE AGENCIES HAVING
JURISDICTION ON THIS PROJECT.
2. NEITHER THE PROFESSIONAL ACTIVITIES OF THE ENGINEER, NOR THE PRESENCE OF THE
ENGINEER OR THEIR EMPLOYEES AND SUBCONSULTANTS AT THE CONSTRUCTION SITE,
SHALL RELIEVE THE CONTRACTOR AND ANY OTHER ENTITY OF THEIR OBLIGATIONS,
DUTIES AND RESPONSIBILITIES INCLUDING BUT NOT LIMITED TO, CONSTRUCTION MEANS,
METHODS, SEQUENCE, TECHNIQUES OR PROCEDURES NECESSARY FOR PERFORMING,
SUPERINTENDING OR COORDINATING ALL PORTIONS OF THE CONSTRUCTION WORK IN
ACCORDANCE WITH THE CONTRACT DOCUMENTS AND ANY HEALTH OR SAFETY
PRECAUTIONS REQUIRED BY ANY REGULATORY AGENCIES. THE ENGINEER AND THEIR
PERSONNEL HAVE NO AUTHORITY TO EXERCISE ANY CONTROL OVER ANY
CONSTRUCTION CONTRACTOR OR OTHER ENTITY OR THEIR EMPLOYEES IN CONNECTION
WITH THEIR WORK OR ANY HEALTH OR SAFETY PRECAUTIONS. THE CONTRACTOR IS
SOLELY RESPONSIBLE FOR THE JOBSITE SAFETY. THE ENGINEER AND THE ENGINEER’S
CONSULTANTS SHALL BE MADE ADDITIONAL INSUREDS UNDER THE CONTRACTOR’S
GENERAL LIABILITY INSURANCE POLICY.
3. ALL DRAWINGS ARE CONSIDERED TO BE A PART OF THE CONTRACT DOCUMENTS. THE
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE REVIEW AND COORDINATION
OF ALL DRAWINGS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL
BE BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO THE START OF
CONSTRUCTION SO A CLARIFICATION CAN BE ISSUED. ANY WORK PERFORMED IN
CONFLICT WITH THE CONTRACT DOCUMENTS OR ANY CODE REQUIREMENTS SHALL BE
CORRECTED BY THE CONTRACTOR AT THEIR OWN EXPENSE AND AT NO EXPENSE TO THE
OWNER OR ARCHITECT.
4. ALL DIMENSIONS AND SITE CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR AT THE
JOBSITE PRIOR TO CONSTRUCTION, START OF SHOP DRAWINGS, START OF
CONSTRUCTION, AND/OR FABRICATION OF MATERIALS. IF DISCREPANCIES ARE
ENCOUNTERED, OR CONDITIONS DEVELOP THAT ARE NOT COVERED BY THE CONTRACT
DOCUMENTS, THE ARCHITECT SHALL BE NOTIFIED FOR CLARIFICATION.
5. CONTRACTOR SHALL PROVIDE AND BE RESPONSIBLE FOR THE PROTECTION AND REPAIR
OF ADJACENT EXISTING SURFACES AND AREAS WHICH MAY BE DAMAGED AS A RESULT
OF NEW WORK.
6. STRUCTURAL DRAWINGS INCLUDE DESIGN REQUIREMENTS AND DIMENSIONS FOR
STRUCTURAL INTEGRITY BUT DO NOT SHOW ALL DETAIL DIMENSIONS TO FIT INTRICATE
ARCHITECTURAL AND MECHANICAL DETAILS. CONTRACTOR SHALL SO CONSTRUCT THE
WORK SO IT WILL CONFORM TO THE CLEARANCES REQUIRED BY ARCHITECTURAL,
MECHANICAL AND ELECTRICAL DESIGN.
7. ALL SYMBOLS AND ABBREVIATIONS USED ON THE DRAWINGS ARE CONSIDERED TO BE
CONSTRUCTION STANDARDS. IF CLARIFICATION IS REQUIRED, THE CONTRACTOR SHALL
NOTIFY THE ARCHITECT PRIOR TO PROCEEDING WITH THE WORK.
8. DO NOT SCALE DRAWINGS. PRINTED DIMENSIONS HAVE PRECEDENCE OVER SCALED
DRAWINGS AND LARGE-SCALE OVER SMALL-SCALE DRAWINGS. CONTRACTOR TO
DETERMINE FINAL DIMENSION WITH ARCHITECT.
9. TYPICAL DETAILS SHALL APPLY TO SITUATIONS OCCURRING ON THE PROJECT THAT ARE
THE SAME OR SIMILAR TO THOSE SPECIFICALLY REFERENCED. WHERE NO DETAILS ARE
GIVEN, CONSTRUCTION SHALL BE AS SHOWN FOR SIMILAR WORK.
10. THE CONTRACT DOCUMENTS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT
INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL
MEASURES NECESSARY TO PROTECT THE STRUCTURE AND SAFETY OF WORKMEN
DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO,
BRACING AND SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC.
OBSERVATION VISITS TO THE SITE BY THE ARCHITECT OR STRUCTURAL ENGINEER SHALL
NOT INCLUDE INSPECTION OR APPROVAL OF THE ABOVE ITEMS AND DOES NOT IN ANY
WAY RELIEVE THE CONTRACTOR OF THEIR RESPONSIBILITIES FOR THE ABOVE.
11. SEE ARCHITECTURAL, ELECTRICAL AND MECHANICAL DRAWINGS FOR DETAILS,
CONDITIONS, PITS, TRENCHES, PADS, DEPRESSIONS, ROOF/FLOOR OPENINGS, STAIRS,
SLEEVES, ITEMS TO BE EMBEDDED OR ATTACHED TO STRUCTURAL ELEMENTS, ETC., NOT
SHOWN ON THE STRUCTURAL DRAWINGS.
12. ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR MECHANICAL, ELECTRICAL AND
PLUMBING WITH APPROPRIATE TRADE CONTRACTORS. OPENING SIZES AND LOCATIONS
SHOWN FOR DUCTS, PIPE, INSERTS AND OTHER PENETRATIONS WHEN SHOWN ARE FOR
GENERAL INFORMATION ONLY AND SHALL BE VERIFIED PRIOR TO FORMING.
13. NO HOLES, NOTCHES, BLOCKOUTS, ETC. ARE ALLOWED IN STRUCTURAL ELEMENTS
UNLESS SPECIFICALLY DETAILED ON THE STRUCTURAL DRAWINGS OR APPROVED BY THE
STRUCTURAL ENGINEER.
14. BEFORE SUBMITTING A PROPOSAL FOR THIS WORK, EACH BIDDER SHALL VISIT THE
PREMISES AND BECOME FULLY ACQUAINTED WITH THE EXISTING CONDITIONS,
TEMPORARY CONSTRUCTION REQUIRED, QUANTITIES AND TYPE OF EQUIPMENT, ETC. THE
BID SHALL INCLUDE ALL SUMS REQUIRED TO DO THE WORK WITHIN THE EXISTING
CONDITIONS.
15. SHOP DRAWINGS SHALL BE REVIEWED AND COORDINATED PRIOR TO SUBMITTING TO THE
ARCHITECT. EACH SHOP DRAWING SUBMITTED SHALL BE STAMPED INDICATING REVIEW
BY THE CONSTRUCTION MANAGER/GENERAL CONTRACTOR AND REVIEW BY THE
ARCHITECT SHALL NOT BEGIN UNTIL THIS IS COMPLETE. WORK SHALL NOT BEGIN
WITHOUT REVIEW BY THE ARCHITECT/STRUCTURAL ENGINEER.
16. SHOP DRAWINGS SHALL BE REVIEWED BY THE ARCHITECT/STRUCTURAL ENGINEER FOR
GENERAL CONFORMANCE WITH DESIGN CONCEPT ONLY. NOTATIONS MADE BY THE
ARCHITECT/STRUCTURAL ENGINEER ON THE SHOP DRAWINGS DO NOT RELIEVE THE
CONTRACTOR FROM COMPLYING WITH THE REQUIREMENTS OF THE DRAWINGS.
17. ELEVATIONS ARE BASED ON THE FIRST FLOOR ELEVATION OF (+0'-0").
18. EXISTING CONDITIONS:
A. EXISTING STRUCTURAL INFORMATION SHOWN WAS OBTAINED FROM EXISTING
DRAWINGS DATED __________ BY __________________.
B. EXISTING STRUCTURAL INFORMATION SHOWN WAS OBTAINED FROM FIELD TAKE-OFF
BY IMEG AS PERMITTED BY ACCESS RESTRICTIONS DURING DESIGN.
C. ALL INFORMATION SHOWN ON THE DRAWINGS RELATIVE TO EXISTING CONDITIONS IS
GIVEN AS THE BEST PRESENT KNOWLEDGE. CONTRACTOR TO VERIFY EXISTING
INFORMATION, DIMENSIONS AND SIZES AS REQUIRED TO COMPLETE THEIR WORK.
WHERE ACTUAL CONDITIONS CONFLICT WITH THE DRAWINGS, THEY SHALL BE
REPORTED TO THE ARCHITECT OR STRUCTURAL ENGINEER SO PROPER
CLARIFICATION MAY BE MADE. MODIFICATION OF CONSTRUCTION DETAILS SHALL NOT
BE MADE WITHOUT WRITTEN APPROVAL OF THE ARCHITECT OR STRUCTURAL
ENGINEER.
19. EXISTING BUILDING MATERIAL PROPERTIES:
A. _____
GENERAL
1. STRUCTURE HAS BEEN DESIGNED TO COMPLY WITH:
IBC 2015
MICHIGAN BUILDING CODE
ASCE/SEI 7-10
ACI 318-11
ACI 530-11
AISC 360-10
AISC 341-10, INCLUDING SUPPLEMENTS
AWS D1.1
AISI S100
NDS-12 AND SDPWS-08
TMS 402/602-16
2. OCCUPANCY RISK CATEGORY III
3. SEISMIC:
SEISMIC DESIGN CATEGORY B
IMPORTANCE FACTOR 1.25
SOIL CLASSIFICATION PER
GEOTECHNICAL REPORT D
SS 0.09 g S1 0.04 g Sds 0.09 g Sd1 0.07 g
SEISMIC FORCE RESISTING SYSTEM ORDINARY MASONRY SHEAR WALLS
R 1.5
4. WIND:
BASIC WIND SPEED 120 MPH
IMPORTANCE FACTOR 1.0
EXPOSURE CLASS C
C&C DESIGN PRESSURE PER APPLICABLE BUILDING CODE SEE ___
5. LIVE LOADS:
TYPICAL ROOF 20 PSF (REDUCIBLE)
TYPICAL FLOOR 100 PSF (REDUCIBLE)
MECHANICAL 10 PSF (UNREDUCIBLE)
CORRIDORS, STAIR & PUBLIC AREAS 100 PSF (UNREDUCIBLE)
PARTITION LOAD 15 PSF (UNREDUCIBLE)
ELEVATOR MACHINE FLOOR 125 PSF (UNREDUCIBLE)
HANDRAILS MAX OF SIMULTANEOUS VERT AND HORIZ
THRUST 50 PLF APPLIED AT THE TOP OF THE
RAILING OR 200 LBS IN ANY DIRECTION
6. SNOW:
GROUND SNOW 25 PSF
SNOW EXPOSURE FACTOR 1.0
THERMAL FACTOR 1.0
IMPORTANCE FACTOR 1.1
FLAT-ROOF SNOW 22 PSF
DESIGN SNOW 22 PSF
RAIN-ON-SNOW SURCHARGE 5 PSF
DESIGN CRITERIA AND LOADS
1. WHERE THERE IS NOT SUFFICIENT SPACE FOR SLOPED EMBANKMENTS, SHORING
WILL BE REQUIRED. REFER TO CONTRACT DOCUMENTS.
2. REFER TO THE GEOTECHNICAL REPORT FOR INFORMATION REGARDING THE
DESIGN AND INSTALLATION OF THE SHORING. SHORING THAT IS NOT PART OF
THE PERMANENT BUILDING SUPPORT IS THE CONTRACTOR’S RESPONSIBILITY
AND OUTSIDE THIS PERMIT.
SHORING
LINTELS
1. PROVIDE LINTELS OVER ALL OPENINGS AND RECESSES IN MASONRY
CONSTRUCTION.
2. PENETRATIONS NOT IDENTIFIED ON THE DOCUMENTS ARE TO BE TREATED IN A
MANNER SIMILAR TO THE IDENTIFIED LOCATIONS. LINTELS OCCURRING IN
EXISTING BEARING WALLS ARE TO BE SIZED ACCORDING TO SIMILAR CONDITIONS
AND SPANS IN THE NEW CONSTRUCTION. LINTELS ARE NOT REQUIRED OVER
OPENINGS 12” WIDE OR LESS AND AT LEAST 1 COURSE BELOW THE TOP OF WALL.
3. LINTELS IN NON-BEARING MASONRY CAN BE SIZED PER THE FOLLOWING:
* ALL ANGLES THAT ARE BACK-TO-BACK SHALL BE WELDED TOP AND BOTTOM 3"
AT 12" OC MINIMUM.
4. ALL LINTELS SHALL HAVE A MINIMUM OF 8” END BEARING AND DO NOT REQUIRE
BEARING PLATES, UNO.
5. ALL LINTELS IN EXTERIOR WALL CONSTRUCTION SHALL BE HOT-DIP GALVANIZED,
UNO.
POST-INSTALLED ANCHORS
1. ANCHORS SERVING AS THE BASIS OF DESIGN ARE SHOWN ON THE DRAWINGS.
ACCEPTABLE ALTERNATIVE ANCHORS MAY BE SUPPLIED PROVIDED THE QUANTITY
AND CONFIGURATION MATCH THE CAPACITY OF THE DESIGN ANCHOR QUANTITY
AND CONFIGURATION. ANY ALTERNATES ARE TO BE SUBMITTED TO THE
STRUCTURAL ENGINEER FOR REVIEW. INSTALL IN ACCORDANCE WITH
MANUFACTURER’S WRITTEN INSTRUCTIONS. BELOW SUMMARIZES EACH ANCHOR
TYPE USED ON THE PROJECT.
2. MECHANICAL ANCHORS:
EXPANSION ANCHORS
THREADED SCREW ANCHORS
3. ADHESIVE ANCHORS: SHALL CONSIST OF DEFORMED REINFORCING BARS OR
ASTM A193 GRADE B7 RODS, HEAVY DUTY NUTS AND WASHERS AND A TWO
COMPONENT STRUCTURAL ADHESIVE. WHERE ANCHORING INTO HOLLOW
MASONRY, A SCREEN TUBE SHALL BE PROVIDED.
4. CRACKED CONCRETE REPRESENTS ALL CONCRETE FOR PROJECTS LOCATED IN
SEISMIC DESIGN CATEGORY C OR HIGHER, TENSILE ZONES SUCH AS BOTTOMS OF
BEAMS AND SLABS, OR WHERE NOTED ON THE DRAWINGS.
SPAN, L
0'-0" < L < 2'-0"
STEEL OPTION (FOR
EACH 4" OF MASONRY
WIDTH)*
5/16" PLATE
MASONRY BOND BEAM OPTIONS
8" DEEP WITH
(1) #4
6" BLOCK 8" BLOCK 10" BLOCK
8" DEEP WITH
(1) #4
8" DEEP WITH
(1) #5
2'-0" < L < 4'-0" L3 1/2x3 1/2x1/4
8" DEEP WITH
(1) #4
8" DEEP WITH
(1) #4
8" DEEP WITH
(1) #5
4'-0" < L < 6'-0" L4x3 1/2x5/16 (LLV)
12" DEEP WITH
(1) #4
12" DEEP WITH
(1) #5
12" DEEP WITH
(2) #5
6'-0" < L < 8'-0" L5x3 1/2x5/16 (LLV)
12" DEEP WITH
(1) #5
12" DEEP WITH
(2) #5
12" DEEP WITH
(2) #5
8'-0" < L < 10'-0" L6x3 1/2x3/8 (LLV)
16" DEEP WITH
(1) #5
16" DEEP WITH
(2) #5
16" DEEP WITH
(2) #5
ANCHORED
INTO
GROUTED
MASONRY
BASIS OF DESIGN ACCEPTABLE ALTERNATES
HILTI KWIK BOLT 3 [ESR-1385]
DEWALT POWER STUD+ SD1 [ESR-2966]
SIMPSON WEDGE-ALL [ESR-1396]
UNCRACKED
CONCRETE
HILTI KWIK BOLT 3 [ESR-2302]
DEWALT POWER STUD+ SD2 [ESR-2502]
RED HEAD TRUBOLT+ [ESR-2427]
SIMPSON STRONG BOLT 2 [ESR-3037]
CRACKED
CONCRETE
HILTI KWIK BOLT TZ [ESR-1917]
DEWALT POWER STUD+ SD2 [ESR-2502]
RED HEAD TRUBOLT+ [ESR-2427]
SIMPSON STRONG BOLT 2 [ESR-3037]
ANCHORED
INTO
GROUTED
MASONRY
BASIS OF DESIGN ACCEPTABLE ALTERNATES
HILTI KWIK HUS-EZ [ESR-3056]
DEWALT WEDGE-BOLT+ [ESR-1678]
SIMPSON TITEN HD [ESR-1056]
UNCRACKED
CONCRETE
HILTI KWIK HUS-EZ [ESR-3027]
DEWALT POWER SCREW-BOLT+ [ESR-3889]
SIMPSON TITEN HD [ESR-2713]
CRACKED
CONCRETE
DEWALT POWER SCREW-BOLT+ [ESR-3889]
SIMPSON TITEN HD [ESR-2713]
HILTI KWIK HUS-EZ [ESR-3027]
ANCHORED
INTO
HOLLOW
MASONRY
BASIS OF DESIGN ACCEPTABLE ALTERNATES
HILTI HIT-HY 270 [ESR-4143]
DEWALT AC 100+ GOLD [ESR-3200]
SIMPSON SET-XP [ESR-0265]
GROUTED
MASONRY
DEWALT AC 100+ GOLD [ESR-3200]
RED HEAD A7 ACRYLIC [ESR-3951]
SIMPSON SET-XP [ESR-0265]
CONCRETE
DEWALT AC 200+ [ESR-4027]
SIMPSON SET-3G [ESR-4057]
HILTI HIT-HY 270 [ESR-4143]
HILTI HIT-HY 200 [ESR-3187]
CAST-IN-PLACE CONCRETE
1. ALL CONCRETE WORK SHALL CONFORM TO THE AMERICAN CONCRETE INSTITUTE
PUBLICATIONS: ACI 117, ACI 301, ACI 305.1, ACI 306.1, ACI 308.1, ACI 318 AND SP-066, UNO.
2. CONCRETE MATERIALS SHALL CONFORM TO:
CEMENT ASTM C150, TYPE I OR II
FLY ASH ASTM C618, TYPE C OR F
FINE AND COARSE AGGREGATE ASTM C33
LIGHTWEIGHT AGGREGATE ASTM C330
WATER POTABLE
AIR-ENTRAINING ADMIXTURE ASTM C260
WATER-REDUCING ADMIXTURE ASTM C494
3. CONCRETE STRENGTHS SHALL CONFORM TO:
4. LIGHTWEIGHT CONCRETE SHALL HAVE A DRY DENSITY OF 107-116 PCF.
5. DRYPACK SHALL BE 1:3-1/2 PORTLAND CEMENT TO SAND WITH A MINIMUM 28-DAY
STRENGTH OF 7000 PSI.
6. GROUT SHALL BE 1:3:2 PORTLAND CEMENT TO SAND TO PEA GRAVEL WITH A
MINIMUM 28-DAY STRENGTH OF 7000 PSI.
7. CROSS REFERENCE ARCHITECTURAL AND STRUCTURAL DRAWINGS TO ASSURE
PROPER DIMENSIONS AND PLACEMENT OF ALL ANCHOR BOLTS, INSERTS,
NOTCHES, EDGES OF WALLS/GRADE BEAMS AND PIERS.
8. UNO, ALL FOOTINGS SHALL BE CENTERED UNDER WALLS, PIERS OR COLUMNS.
9. PROVIDE SLEEVES FOR PLUMBING AND ELECTRICAL PENETRATIONS THROUGH
CONCRETE BEFORE PLACING. SECURE SUCH SLEEVES TO PREVENT MOVEMENT
DURING PLACING OPERATIONS. REFER TO MECHANICAL AND ELECTRICAL
DRAWINGS FOR LOCATIONS OF PENETRATIONS.
10. CORE DRILLING CONCRETE IS NOT PERMITTED UNLESS NOTED OTHERWISE OR
APPROVED IN WRITING BY THE ARCHITECT. NOTIFY THE ARCHITECT IN ADVANCE
OF CONDITIONS NOT SHOWN ON THE DRAWINGS.
11. THE OUTSIDE DIAMETER OF EMBEDDED CONDUIT OR PIPE SHALL NOT EXCEED 1/3
OF THE STRUCTURAL SLAB THICKNESS, INCLUDING AT CROSS-OVERS, AND SHALL
BE PLACED BETWEEN THE TOP AND BOTTOM REINFORCING WITH A MINIMUM 3”
CLEAR COVER. CONDUIT OR PIPE RUNNING PARALLEL TO EACH OTHER SHALL BE
SPACED AT LEAST 8” APART AND NO MORE THAN 2 RUNS STACKED VERTICALLY IN
THE SLAB. CONDUIT OR PIPE SHALL NOT BE EMBEDDED IN SLAB THICKNESSES
LESS THAN 6 INCHES.
12. DO NOT PLACE PIPES, DUCTS, REGLETS OR CHASES IN STRUCTURAL CONCRETE
WITHOUT APPROVAL OF THE STRUCTURAL ENGINEER THROUGH THE ARCHITECT.
13. NO ALUMINUM SHALL BE ALLOWED IN THE CONCRETE WORK UNLESS COATED TO
PREVENT ALUMINUM-CONCRETE REACTION.
14. PROJECTING CORNERS OF BEAMS, WALLS, COLUMNS, ETC., SHALL BE FORMED
WITH A 3/4 INCH CHAMFER, UNLESS NOTED OTHERWISE ON ARCHITECTURAL
DRAWINGS.
15. INTERNALLY VIBRATE ALL CAST-IN-PLACE CONCRETE EXCEPT SLABS-ON-GRADE
WHICH NEED ONLY BE VIBRATED AROUND UNDER FLOOR DUCTS AND OTHER
EMBEDDED ITEMS. VIBRATE TOPS OF COLUMNS.
16. CONCRETE SHALL NOT BE PERMITTED TO DROP MORE THAN 5 FEET.
17. CONCRETE SLABS SHALL BE CURED BY KEEPING CONTINUOUSLY WET FOR 7
DAYS. FORMS FOR CONCRETE WALLS SHALL BE LEFT IN PLACE FOR 7 DAYS OR
MAY BE STRIPPED AFTER 3 DAYS AND COATED WITH AN APPROVED CURING
COMPOUND.
18. NO CONCRETE SHALL BE PLACED ONTO OR AGAINST SUBGRADES CONTAINING
FREE WATER, FROST, ICE OR SNOW.
19. THE CONCRETE CONTRACTOR SHALL FURNISH MIX DESIGN SHOP DRAWINGS FOR
REVIEW.
INTENDED USE
28-DAY STRENGTH
(PSI)
MAX W/C
RATIO
A/E SLUMP
FOUNDATIONS 4000 0.45 5-8% 1"-4"
33533 W. Twelve Mile Rd.
Farmington Hills, Michigan 48331
(248) 932-3088
(248) 932-2010
Waterford Montessori Academy Midland Campus HVAC Improvements
Project. No. 1021
Bidding / For Permits: 12 July, 2021
S10
Structural General Notes
EPOXY ANCHORS
1. INTENDED FOR USE WITH REINFORCING BARS AND THREADED RODS.
2. ALL EPOXY ON THE JOB, UNLESS OTHERWISE NOTED, SHALL BE “SET-3G” AS
MANUFACTURED BY SIMPSON STRONG-TIE [ICC ESR-4057] OR APPROVED EQUIVALENT.
3. WORKERS SHALL BE CERTIFIED FOR ANCHOR INSTALLATION EQUIPMENT AND
PROCEDURES USING THEIR EPOXY.
4. CONTINUOUS INSPECTION IS REQUIRED FOR INSTALLATION OF REBAR OR THREADED
RODS.
5. FOR REQUIRED HOLES, THE DIAMETERS SHALL BE PER MANUFACTURER’S
REQUIREMENTS. MINIMUM HOLE LENGTH SHALL BE PER STRUCTURAL DRAWINGS, OR
PER THE ICC MINIMUM (FOR MAXIMUM TENSION) IF NOT SHOWN.
6. FOR HORIZONTAL HOLES COMPLETELY THROUGH WALLS OR BEAMS AND FOR TIES
AROUND COLUMNS, PROVIDE A DAM AT ONE END, FLOOD WITH EPOXY AND DAM THE
OTHER SIDE. VIBRATE TIES TO ENSURE FULL COVERAGE. REMOVE DAMS ONCE FLUID
EPOXY HAS SET. FILL ANY VOIDS WITH ADDITIONAL EPOXY.
STEEL
1. STRUCTURAL STEEL SHALL BE DETAILED IN ACCORDANCE WITH THE AMERICAN
INSTITUTE OF STEEL CONSTRUCTION (AISC) “DETAILING FOR STEEL
CONSTRUCTION” AND FABRICATED AND ERECTED IN ACCORDANCE WITH THE
“SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS”.
2. STRUCTURAL STEEL SHALL CONFORM TO ASTM STANDARDS AS NOTED BELOW:
WIDE FLANGE SHAPES ASTM A992 Fy = 50 KSI OTHER ROLLED SHAPES ASTM A36 Fy = 36 KSI PIPE SECTIONS ASTM A53, GR B Fy = 35 KSI HSS SECTIONS, ROUND ASTM A500, GR C Fy = 46 KSI HSS SECTIONS, SQ/RECT ASTM A500, GR B Fy = 46 KSI BASE AND CONNECTION PLATES ASTM A36 A572 Fy = 36 50 KSI ANCHOR RODS ASTM F1554, GR 36 55 Fy = 36 55 KSI HIGH STRENGTH BOLTS ASTM F3125, GR A325 Fv = 120 KSI HIGH STRENGTH BOLTS ASTM F3125, GR A490 Fv = 150 KSI HIGH STRENGTH TWIST-OFF BOLTS ASTM F3125, GR F1852 Fv = 120 KSI HIGH STRENGTH TWIST-OFF BOLTS ASTM F3125, GR F2280 Fv = 150 KSI
HEAVY HEX NUTS ASTM A563
WASHERS ASTM F436
HEADED STUDS ASTM A108, TYPE B
ELECTRODES FOR ARC WELDING AWS 5.1, E70XX
3. HIGH STRENGTH BOLTS SHALL BE INSTALLED IN ACCORDANCE WITH AISC
“SPECIFICATIONS FOR STRUCTURAL JOINTS USING HIGH-STRENGTH BOLTS”.
REFER TO DETAILS FOR BOLT SIZE AND MATERIAL ASTM DESIGNATION.
4. USE TENSION-CONTROL, “TWIST-OFF”, BOLTS FOR ALL HIGH STRENGTH BOLTS
REQUIRING FULL TENSION AS INDICATED ON THE DRAWINGS.
5. ALL HIGH STRENGTH BOLTS SHALL CONFORM TO ASTM F3125, GRADE A325N, UNO.
FOR ALL DRAG STRUT BOLTS, HIGH STRENGTH BOLTS SHALL CONFORM TO ASTM
F3125, GRADE A490SC.
6. ALL BOLTED CONNECTIONS SHALL BE BEARING TYPE, UNLESS NOTED
OTHERWISE.
7. STANDARD BOLT HOLES IN STEEL SHALL BE 1/16 INCH LARGER IN DIAMETER THAN
NOMINAL SIZE OF BOLT USED, UNO.
8. BOLTS IN SLOTTED HOLES SHALL BE LOCATED IN THE CENTER OF THE HOLE
AFTER FIELD ASSEMBLY IS COMPLETE, UNLESS DETAILED OTHERWISE.
9. ALL WELDS SHALL CONFORM TO THE AMERICAN WELDING SOCIETY “STRUCTURAL
WELDING CODE - STEEL” (AWS D1.1), “STRUCTURAL WELDING CODE - SEISMIC
SUPPLEMENT” (AWS D1.8), AND BE MADE WITH APPROVED ELECTRODES.
10. WELD LENGTHS INDICATED ON THE DRAWINGS ARE THE NET EFFECTIVE LENGTH
REQUIRED.
11. ALL WELDING OF STRUCTURAL STEEL SHALL BE PERFORMED BY CERTIFIED
WELDERS WITH EXPERIENCE AND CERTIFICATION IN THE TYPES OF WELDING
CALLED FOR. WELDERS SHALL HAVE BEEN RECENTLY QUALIFIED AS PRESCRIBED
IN “QUALIFICATION PROCEDURES” OF THE AMERICAN WELDING SOCIETY (AWS).
12. FIELD CONNECTIONS SHALL BE WELDED OR BOLTED. SHOP CONNECTIONS SHALL
BE WELDED, UNO. WELDS INDICATED WITH A SHOP WELD SYMBOL MAY BE MADE
IN THE FIELD WITH THE APPROVAL OF THE STRUCTURAL ENGINEER. LOCATIONS
OF ALL FIELD WELDS SHALL BE CLEARLY SHOWN ON THE SHOP DRAWINGS.
WELDS SHALL BE DESIGNED TO BE FULLY EQUIVALENT IN STRENGTH TO BOLTED
CONNECTIONS DETAILED TO MINIMIZE BENDING IN THE CONNECTION.
13. ALL STEEL EXPOSED TO WEATHER SHALL BE HOT-DIP GALVANIZED AFTER
FABRICATION. ABRADED AREAS TO BE TOUCHED UP WITH GALVALOY. ALL
HOLLOW SECTIONS SHALL HAVE WELDED CAP PLATES TO SEAL EXPOSED ENDS.
14. PROVIDE ONE SHOP COAT OF PAINT ON STRUCTURAL STEEL EXPOSED TO PUBLIC
VIEW ONLY.
15. REFER TO DRAWINGS FOR DETAIL OF DECK OPENINGS. REFER TO
ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS, ETC. FOR EXACT
SIZE, LOCATION, AND COUNT OF REQUIRED OPENINGS.
16. CUTS, HOLES, OPENINGS, ETC., REQUIRED IN STRUCTURAL STEEL MEMBERS FOR
THE WORK OF OTHER TRADES SHALL BE SHOWN ON THE SHOP DRAWINGS.
BURNING OF HOLES AND CUTS IN THE FIELD SHALL NOT BE ALLOWED, EXCEPT BY
WRITTEN AUTHORIZATION FROM THE STRUCTURAL ENGINEER. NO HOLES SHALL
BE CUT IN STRUCTURAL STEEL BY OTHER TRADES UNLESS SHOWN ON
STRUCTURAL DRAWINGS OR APPROVED IN WRITING BY THE STRUCTURAL
ENGINEER.
17. FURNISH AND INSTALL MISCELLANEOUS STEEL (CURBS, HANGERS, EXPANSION
JOINT ANGLES, STRUTS, ETC.) AS CALLED FOR OR AS NECESSARY PER
ARCHITECTURAL AND MECHANICAL/ELECTRICAL DRAWINGS.
18. NON-SHRINK GROUT FOR BASE AND BEARING PLATES SHALL BE A PRE-MIXED,
NON-METALLIC, NON-CORROSIVE, NON-STAINING PRODUCT CONTAINING
SELECTED SILICA SAND, PORTLAND CEMENT, SHRINKAGE COMPENSATING
AGENTS AND PLASTICIZING/WATER REDUCING AGENTS. MINIMUM COMPRESSIVE
STRENGTH AT 28 DAYS SHALL BE 7000 PSI.
19. THE STRUCTURAL STEEL FABRICATOR SHALL FURNISH SHOP DRAWINGS OF ALL
STRUCTURAL STEEL FOR ARCHITECT/STRUCTURAL ENGINEER’S REVIEW BEFORE
FABRICATION.
33533 W. Twelve Mile Rd.
Farmington Hills, Michigan 48331
(248) 932-3088
(248) 932-2010
Waterford Montessori Academy Midland Campus HVAC Improvements
Project. No. 1021
Bidding / For Permits: 12 July, 2021
S11
WOOD
1. SHEATHING
A. SHALL CONFORM TO:
ROOF SHEATHING, FLAT 3/4" THICK PRESSURE TREATED
B. REFER TO TYPICAL DETAILS AND WALL SCHEDULES FOR FASTENING
REQUIREMENTS. WHERE NOT NOTED, PROVIDE 6d NAILS AT 6” OC ALONG ALL
EDGES AND AT 12” OC AT INTERMEDIATE SUPPORTS.
C. ALL SHEATHING WHICH IS EXPOSED TO OUTDOOR APPLICATIONS SHALL BE
EXTERIOR TYPE. SHEATHING EXPOSED TO WEATHER ONLY DURING
CONSTRUCTION SHALL BE EXPOSURE 1. ALL WOOD STRUCTURAL PANELS SHALL
CONFORM TO 2303.1.4 AND WHEN USED IN HORIZONTAL DIAPHRAGM AND
VERTICAL SHEAR WALLS SHALL BE FIVE-PLY MINIMUM.
D. FLOOR SHEATHING SHALL BE GLUED TO ALL SUPPORTING MEMBERS WITH AN
ELASTOMERIC ADHESIVE CONFORMING TO ASTM D3498.
E. WHERE ORIENTED STRAND BOARD SHEATHING IS USED HORIZONTALLY, REMOVE
AND REPLACE IF SHEATHING REMAINS WET FOR EXTENDED PERIODS OF TIME
WHEREBY REDUCING THE STIFFNESS.
2. DIMENSIONAL LUMBER
A. FRAMING SHALL BE DOUGLAS FIR (LARCH), HEM FIR, SPRUCE PINE FIR OR
SOUTHERN PINE:
BEARING/EXTERIOR WALL STUDS #2 OR BETTER
B. COMPLY WITH ANSI/AWC NATIONAL DESIGN SPECIFICATION (NDS) FOR WOOD
CONSTRUCTION.
C. ALL LUMBER STRESSES SHOWN ABOVE ARE FOR VISUALLY STRESS-RATED
LUMBER USED AT 19% MAXIMUM MOISTURE CONTENT, SINGLE MEMBER USE. ALL
LUMBER SHALL BE GRADE MARKED.
D. PROVIDE A MINIMUM OF 3” OF BEARING.
E. DOUBLE UP FLOOR JOISTS UNDER ALL PARTITIONS.
F. PROVIDE METAL OR 1x3 WOOD CROSS BRACING AT 8 FT ON CENTER WHEN JOIST
DEPTH-TO-THICKNESS RATIO EXCEEDS 6:1.
G. PROVIDE 2x SOLID BLOCKING AT JOIST SUPPORTS EXCEPT WHERE THE JOIST
ENDS ARE SUPPORTED BY JOIST HANGERS.
H. ADD JOISTS WHEN CONCENTRATED LOAD EXCEEDS 100 LBS, MAXIMUM
CONCENTRATED LOAD.
I. OPENINGS NOT IDENTIFIED ARE TO BE TREATED AS FOLLOWS:
1) WHERE OPENING FITS BETWEEN JOISTS, FRAME WITH LUMBER EQUALING
THE NOMINAL DIMENSIONS OF THE EXISTING JOISTS.
2) WHERE OPENING CUTS ONE JOIST, FRAME WITH LUMBER EQUALING THE
NOMINAL DIMENSIONS OF THE EXISTING JOISTS. USE THIS FRAMING AS A
HEADER FOR THE INTERRUPTED JOIST. FOR EACH JOIST BYPASSING THE
OPENING, CUT AND SISTER A NEW JOIST. USE 1/2”ø LAG SCREWS AT 12” OC TO
SISTER JOISTS TOGETHER. PENETRATIONS WHERE MORE THAN ONE JOIST IS
CUT TO BE REVIEWED BY SEOR.
3. MANUFACTURED WOOD PRODUCTS
A. STRENGTHS SHALL CONFORM TO:
WOOD I-JOIST (BASIS OF DESIGN) _____ [ICC ESR-####]
LAMINATED VENEER LUMBER (LVL) Fb = 2600 PSI E = 1900 KSI
[ICC ESR-####]
PARALLEL STRAND LUMBER (PSL) Fb = 2900 PSI E = 2000 KSI
[ICC ESR-####]
B. I-JOIST, IF STORED PRIOR TO ERECTION, SHALL BE STORED IN A VERTICAL
POSITION.
C. I-JOISTS SHALL HAVE ERECTION BRACING TO KEEP THE JOIST STRAIGHT, TRUE
AND PLUMB, AS REQUIRED AND TO ASSURE ADEQUATE LATERAL SUPPORT FOR
THE INDIVIDUAL JOIST AND THE ENTIRE SYSTEM UNTIL THE SHEATHING MATERIAL
HAS BEEN APPLIED.
D. LATERAL SUPPORT SHALL BE PROVIDED AT ALL BEARING LOCATIONS. FOR JOIST
SPANS GREATER THAN 16’-0”, ONE ROW OF BRIDGING OR FULL DEPTH BLOCKING
SHALL BE INSTALLED AT MIDSPAN.
E. NOTCHES AND HOLES IN I-JOISTS ARE ONLY ALLOWED AS DETAILED OR
APPROVED BY THE STRUCTURAL ENGINEER.
F. DO NOT NAIL PARALLEL TO GLUE LINE LAMINATIONS ON THE NARROW FACE OF AN
I-JOIST TOP/BOTTOM CHORD.
G. REFER TO MANUFACTURER REQUIREMENTS FOR LVL MINIMUM BEARING
LENGTHS.
H. LVL BEAMS SHALL BE LATERALLY SUPPORTED AT ALL POINTS OF BEARING. SIDE
MOUNTED JOIST HANGERS, NAILING TO SHOULDER STUDS AND NAILING
SHEATHING TO LVL WILL SATISFY THIS REQUIREMENT.
I. NAILS INSTALLED PARALLEL TO THE GLUE LINES ON THE NARROW FACE SHALL
NOT BE SPACED CLOSER THAN 4” FOR 10d NAILS OR 3” FOR 8d.
J. NAILS INSTALLED PERPENDICULAR TO THE GLUE LINES ON THE WIDE FACE SHALL
BE INSTALLED IN ACCORDANCE WITH THE BUILDING CODE. ASSEMBLE LVL BEAMS
WITH A MINIMUM OF (3) 10d NAILS PER FOOT, FULLY PENETRATING EACH PIECE, UNO.
K. NOTCHING OR DRILLED HOLES IN LVL MEMBERS NOT PREVIOUSLY APPROVED BY
THE MANUFACTURER SHALL NOT BE PERMITTED.
L. CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER INSTALLATION PER DETAILED
INSTALLATION SUGGESTIONS AND GUIDELINES OF THE MANUFACTURER.
M. ALL FRAMING HARDWARE MUST BE THE TYPE SPECIFIED FOR THE PRODUCT AND
APPROVED BY THE MANUFACTURER FOR INSTALLATION.
4. FASTENING
A. ALL NAILS SHALL BE COMMON WIRE NAILS. AT ALL EXPOSED NAILING TO
WEATHER, (IE-DECKING & SIDING), USE HOT-DIPPED GALVANIZED NAILS. USE OF
PLASTIC COATED OR CASING NAILS IS NOT ALLOWED. NAIL DESIGNATIONS SHALL
MEET THE FOLLOWING LENGTHS AND DIAMETERS:
6d 2" x 0.113" 12d 3 1/4" x 0.148" 8d 2 1/2" x 0.131" 16d 3 1/2" x 0.162" 10d 3" x 0.148" 20d 4" x 0.192"
B. THE NUMBER AND SIZE OF NAILS CONNECTING WOOD MEMBERS SHALL NOT BE
LESS THAN THE FOLLOWING:
STRUCTURAL TESTS AND INSPECTION
1. UNLESS NOTED, MATERIALS SHALL CONFORM AND TESTS AND INSPECTIONS
SHALL BE PERFORMED BY THE INSPECTION AGENCY WHO IS APPROVED THE
ARCHITECT AND THE STRUCTURAL ENGINEER. CONTINUOUS AND PERIODIC
TESTING AND INSPECTION SHALL CONFORM TO IBC CHAPTER 17, AND AS
FOLLOWS:
A. DRIVEN DEEP FOUNDATIONS 1704.8 1705.7
B. CAST-IN-PLACE DEEP FOUNDATIONS 1704.9 1705.8
C. HELICAL PILE FOUNDATIONS 1704.10 1705.9
D. CONCRETE CONSTRUCTION 1704.4 1705.3
E. MASONRY CONSTRUCTION 1704.5 1705.4
F. STEEL CONSTRUCTION 1704.3 1705.2 CHAPTER N OF AISC 360
G. WOOD CONSTRUCTION 1704.6 1705.5
H. SOILS 1704.7 1705.6
I. WIND RESISTANCE 1705.10 1705.11
J. SEISMIC RESISTANCE 1705.11, 1705.12 1705.12, 1705.13
2. REFER TO ARCHITECTURAL, CIVIL, MECHANICAL, PLUMBING AND ELECTRICAL
DRAWINGS OR SPECIFICATIONS FOR TESTING AND INSPECTION REQUIREMENTS
OF NON-STRUCTURAL COMPONENTS.
3. DUTIES OF THE INSPECTION AGENCY PER IBC CHAPTER 17:
A. SUBMIT A PROPOSED TESTING AND INSPECTION PROGRAM TO THE OWNER,
THE ARCHITECT AND THE STRUCTURAL ENGINEER FOR REVIEW AND
APPROVAL AT LEAST TWO WEEKS PRIOR TO COMMENCEMENT OF WORK.
B. PERFORM ALL TESTING AND INSPECTION REQUIRED PER APPROVED TESTING
AND INSPECTION PROGRAM.
C. FURNISH INSPECTION REPORT TO THE BUILDING OFFICIAL, THE OWNER, THE
ARCHITECT, STRUCTURAL ENGINEER AND THE GENERAL CONTRACTOR. THE
REPORTS SHALL BE COMPLETED AND FURNISHED WITHIN 48 HOURS OF
INSPECTED WORK.
D. SUBMIT A FINAL SIGNED REPORT STATING WHETHER THE WORK REQUIRING
SPECIAL INSPECTION WAS, TO THE BEST OF THE SPECIAL INSPECTION
AGENCY’S KNOWLEDGE, IN CONFORMANCE WITH THE APPROVED PLANS AND
SPECIFICATIONS.
CONNECTION
JOIST TO SILL, TOP PLATE OR GIRDER
BRIDGING OR BLOCKING BETWEEN JOISTS
OR TRUSSES NOT AT WALL TOP PLATE
FASTENING
(3) 8d TOENAILS
SILL PLATE TO JOIST, RIM JOIST OR BLOCKING
TOP PLATE TO 2x STUD AND STUD TO SILL PLATE
TOP PLATE TO 3x STUD AND STUD TO SILL PLATE
2x STUD TO TOP OR SILL PLATE
(2) 8d TOENAILS, EACH END OR (2) 16d END NAILS
16d @ 16" OC, FACE NAIL
(2) 16d END NAILS
(3) 16d END NAILS
(4) 8d TOENAILS OR
(2) 16d END NAILS
3x STUD TO SOLE PLATE
(6) 8d TOENAILS OR
(3) 16d END NAILS
STUD TO STUD 16d @ 24" OC, FACE NAIL
DOUBLE TOP PLATES 16d @ 16" OC, FACE NAIL
DOUBLE TOP PLATES, LAP SPLICE (12) 16d EACH SIDE OF SPLICE
BLOCKING BETWEEN JOISTS OR RAFTERS TO TOP PLATE (3) 8d TOENAILS
RIM JOIST TO TOP PLATE OR FRAMING BELOW 8d @ 6" OC, TOENAIL
JOIST TO RIM JOIST (3) 16d END NAILS
TOP PLATE LAPS AT CORNERS AND INTERSECTIONS (2) 16d, FACE NAIL
BUILT-UP HEADER 16d @ 16" OC ALONG EACH EDGE
CEILING JOIST TO TOP PLATE (3) 8d TOENAILS
CONTINUOUS HEADER TO STUD (4) 8d, TOENAIL
CEILING JOIST, LAPS OVER PARTITIONS (3) 16d FACE NAILS
CEILING JOISTS TO PARALLEL RAFTERS REFER TO TABLE 2308.7.3.1
RAFTER OR ROOF TRUSS TO PLATE (3) 10d TOENAILS
BUILT-UP CORNER STUDS 16d @ 24" OC
BUILT-UP GIRDERS AND BEAMS, 2x LUMBER LAYERS
20d FACE NAILS @ 32" OC ALONG
TOP AND BOTTOM, STAGGERED
OPPOSITE SIDES, AND (2) 20d AT
ENDS AND AT EACH SPLICE
FLAT BLOCKING TO TRUSS AND WEB FILLER 16d @ 16" OC, FACE NAIL
MULTI-PLY LAMINATED VENEER LUMBER (LVL) PER MANUF RECOMMENDATIONS
A. PILOT HOLES SHALL BE PROVIDED FOR ALL NAILS 20d AND LARGER. PILOT HOLES
SHALL HAVE A DIAMETER OF APPROXIMATELY 75% OF THE NAIL SHANK DIAMETER.
B. USE OF MACHINE NAILING IS SUBJECT TO A SATISFACTORY JOBSITE
DEMONSTRATION AND THE APPROVAL OF THE ARCHITECT/STRUCTURAL
ENGINEER AND IS SUBJECT TO CONTINUED SATISFACTORY PERFORMANCE.
MACHINE NAILING IS NOT ALLOWED FOR 5/16” SHEATHING. IF THE NAIL HEADS
PENETRATE MORE THAN WOULD BE NORMAL FOR A HANDHELD HAMMER, OR IF
MINIMUM ALLOWABLE EDGE DISTANCES ARE NOT MAINTAINED, THE
PERFORMANCE WILL BE DEEMED UNSATISFACTORY AND MACHINE NAILING WILL
BE DISCONTINUED.
C. ALL BOLTED WOOD CONNECTIONS SHALL BE MADE WITH BOLTS CONFORMING TO
THE REQUIREMENTS OF ANSI/ASME B18.2.6. BOLT HOLES SHALL BE 1/32” TO 1/16”
LARGER THAN THE BOLT. FORCIBLE DRIVING OF BOLTS IS NOT ALLOWED.
RETIGHTEN ALL BOLTS BEFORE CLOSING-IN.
D. USE STANDARD CUT WASHERS BETWEEN THE BOLT HEADS, BOLT NUTS AND LAG
SCREW HEADS AND WOOD FRAMING.
E. ALL WOOD CONNECTIONS MADE WITH LAG SCREWS SHALL BE MADE WITH
SCREWS CONFORMING TO THE REQUIREMENTS OF ANSI/ASME B18.2.6. LEAD
HOLES FOR THE SHANK SHALL HAVE THE SAME DIAMETER AS THE SHANK AND
THE SAME DEPTH AS THE LENGTH OF UNTHREADED SHANK. THE LEAD HOLE FOR
THE THREADED PORTION SHALL HAVE A DIAMETER EQUAL TO 60-75% OF THE
THREADED PORTION.
F. METAL FRAMING CONNECTORS NOTED ON THE DRAWINGS USE SIMPSON
STRONG-TIE AS BASIS OF DESIGN, UNLESS NOTED OTHERWISE. SUBSTITUTIONS
OF ALTERNATE CONNECTOR MANUFACTURERS WILL BE ACCEPTABLE AS LONG AS
LOAD CAPACITIES ARE MET OR EXCEEDED AND ARE SUBSTANTIATED BY AN ICC
REPORT.
G. WHERE THERE ARE CONNECTOR NAILING ALTERNATIVES LISTED IN THE
MANUFACTURER’S CATALOG, THE NAILING PROVIDING THE HIGHEST LOAD
CAPACITY SHALL BE USED.
5. GENERAL CONSTRUCTION REQUIREMENTS:
A. FRAMING PLANS INDICATE GENERAL LAYOUT AND DIMENSIONAL CONTROL ONLY.
REFER TO SHOP DRAWINGS FOR ENGINEERING AND ERECTION.
B. SILL PLATES SHALL HAVE 1/2”ø ANCHOR BOLTS WITH 7” EMBEDMENT SPACED NOT
MORE THAN 6’-0” ON CENTER, UNO. EACH PIECE SHALL HAVE 2 BOLTS MINIMUM
AND HAVE AN ANCHOR LOCATED 4” MINIMUM AND 12” MAXIMUM FROM THE END.
PLATE WASHERS SHALL BE A MINIMUM OF 3/16” THICK x 3”.
C. WHERE MULTIPLE JOISTS OR HEADERS OCCUR, THERE SHALL BE A SHOULDER
STUD FOR EACH PLY (IE - PROVIDE DOUBLE STUDS UNDER DOUBLE JOISTS).
D. SOLID-SAWN LUMBER BEAMS, RAFTERS AND JOISTS SHALL HAVE LATERAL
SUPPORT PREVENTING ROTATION OR DISPLACEMENT AS FOLLOWS BASED UPON
SPAN-TO-DEPTH RATIOS:
1) 2:1, NO LATERAL SUPPORT IS REQUIRED;
2) 3:1 OR 4:1, THE ENDS SHALL BE HELD IN POSITION BY FULL-DEPTH
BLOCKING, BRIDGING, NAILING OR BOLTING TO OTHER FRAMING MEMBERS;
3) 5:1, ONE EDGE SHALL BE HELD IN LINE FOR ITS ENTIRE LENGTH;
4) 6:1, FULL-DEPTH BLOCKING, BRIDGING OR CROSS BRACING SHALL BE
INSTALLED AT INTERVALS NOT EXCEEDING 8 FT UNLESS BOTH EDGES ARE
HELD IN LINE;
5) 7:1, BOTH EDGES SHALL BE HELD IN LINE FOR THE ENTIRE LENGTH.
E. ALL LUMBER, UNLESS NOTED, SHALL BE MILL SIZED AND SURFACED ON FOUR
SIDES AND SHALL BE STRAIGHT STOCK, FREE FROM WARP OR CUP AND SINGLE
LENGTH PIECES.
F. ALL ROUGH CARPENTRY SHALL PRODUCE JOINTS TRUE, TIGHT AND WELL NAILED
WITH MEMBERS ASSEMBLED IN ACCORDANCE WITH THE DRAWINGS AND ALL
PERTINENT BUILDING CODES. THE SHIMMING OF SILLS, JOISTS, SHORT STUDS,
TRIMMERS, HEADERS OR OTHER FRAMING MEMBERS SHALL NOT BE PERMITTED.
ALL WALLS AND PARTITIONS SHALL BE STRAIGHT, PLUMB AND ACCURATELY
LOCATED. CAREFULLY SELECT ALL STRUCTURAL MEMBERS SO KNOTS AND
OBVIOUS MINOR DEFECTS WILL NOT INTERFERE WITH MAKING SOUND
CONNECTIONS.
G. INSTALL ALL BLOCKING AS REQUIRED TO SUPPORT ALL ITEMS OF FINISH SUCH AS
BULKHEADS AND DOOR BUCKS. PROVIDE FIREBLOCKING TO CUT OFF ALL
CONCEALED DRAFT OPENINGS, BOTH VERTICAL AND HORIZONTAL, BETWEEN
CEILING AND FLOOR AREAS. VERIFY ALL REQUIRED BLOCKING WITH
ARCHITECTURAL DRAWINGS AND LOCAL BUILDING OFFICIAL.
H. ALL LUMBER AND PRODUCTS SHALL BE HANDLED AND STORED TO PREVENT
MARRING AND MOISTURE ABSORPTION FROM RAIN. NO DIRECT CONTACT WITH
THE GROUND IS PERMITTED.
I. ALL LUMBER EXPOSED TO WEATHER SHALL BE TREATED WOOD.
J. PROTECTION AGAINST DECAY AND TERMITES:
1) PLATES, SILLS AND SLEEPERS - WHEN IN DIRECT CONTACT WITH CONCRETE
OR MASONRY, SHALL BE TREATED WOOD. BOTTOM OF SILLS AT EXTERIOR
WALLS SHALL NOT BE LESS THAN 6” ABOVE OUTSIDE GRADE EXCEPT WHERE
GRADE IS PAVED OVER FOR 18” MINIMUM WIDTH AND DRAINING AWAY FROM
THE BUILDING. FOR THAT CONDITION, SILL MAY BE 2” ABOVE.
2) COLUMNS AND POSTS - IN AREAS EXPOSED TO WATER SPLASH AND
EXTERIOR CONDITIONS, COLUMN/POST SHALL BE SUPPORTED BY A METAL
CONNECTOR AND BE TREATED UNLESS BASE IS LIFTED 2” ABOVE THE
CONCRETE SLAB.
3) STRUCTURAL SUPPORTS OF BALCONIES, PORCHES OR SIMILAR
APPURTENANCES - WHEN MEMBERS ARE EXPOSED TO THE WEATHER
WITHOUT ADEQUATE ROOF PROTECTION PREVENTING WATER
ACCUMULATION, THEY SHALL BE TREATED WOOD.
4) MOISTURE CONTENT - WHEN WOOD IS PRESSURE TREATED WITH A
WATERBORNE PRESERVATIVE AND LOCATED IN ENCLOSED SPACES WHERE
DRYING IN SERVICE CANNOT READILY OCCUR, SUCH WOOD SHALL BE AT A
MOISTURE CONTENT OF 19% OR LESS BEFORE BEING COVERED.
K. UNLESS SPECIFICALLY SHOWN ON THESE PLANS, NO STRUCTURAL MEMBER
SHALL BE CUT, NEITHER DRILLED NOR NOTCHED, WITHOUT WRITTEN APPROVAL
FROM THE STRUCTURAL ENGINEER.
1) AT NON-BEARING STUDS: A HOLE NOT GREATER THAN 40% OF THE STUD
WIDTH MAY BE BORED. BORED HOLES NOT GREATER THAN 60% OF THE STUD
WIDTH ARE PERMITTED WHERE EACH BORED STUD IS DOUBLED, PROVIDED
NOT MORE THAN TWO SUCH SUCCESSIVE DOUBLE STUDS ARE SO BORED. IN
NO CASE SHALL THE EDGE OF THE BORE HOLE BE NEARER THAN 5/8” TO THE
STUD EDGE. BORE HOLES SHALL NOT BE LOCATED AT THE SAME SECTION IF
CUT OR NOTCHED.
L. ALL FRAMING APPLICABLE STANDARDS OR GRADING RULES SPECIFIED SHALL BE
SO IDENTIFIED BY THE GRADE MARK OR A CERTIFICATE OF INSPECTION BY AN
APPROVED AGENCY. ALL LUMBER AND PLYWOOD REQUIRED TO BE TREATED
WOOD SHALL BE IDENTIFIED BY THE QUALITY MARK OF AN APPROVED INSPECTION
AGENCY WHICH MAINTAINS CONTINUED SUPERVISION, TESTING AND INSPECTION
OVER THE QUALITY OF THE PRODUCT.
M. WALL STUD CONSTRUCTION IS DESIGNED TO BE BRACED BY THE WALL
SHEATHING (WOOD STRUCTURAL PANEL OR GYPSUM BOARD). CONTRACTOR TO
PROVIDE TEMPORARY BRACING, AS REQUIRED, UNTIL SHEATHING IS INSTALLED.
N. STRUCTURAL HEADERS OR OTHER STRUCTURAL COMPONENTS MAY BE
SUBSTITUTED UPON APPROVAL OF THE STRUCTURAL ENGINEER. SUPPLIER SHALL
PROVIDE SEALED DESIGN CALCULATIONS FOR THE COMPONENTS.
O. CONTRACTOR SHALL SUBMIT A COMPLETE SET OF SHOP DRAWINGS PREPARED
BY THE FABRICATOR/MANUFACTURER FOR REVIEW AND APPROVAL BY THE
ARCHITECT AND STRUCTURAL ENGINEER.
33533 W. Twelve Mile Rd.
Farmington Hills, Michigan 48331
(248) 932-3088
(248) 932-2010
Waterford Montessori Academy Midland Campus HVAC Improvements
Project. No. 1021
Bidding / For Permits: 12 July, 2021
S12
T
14'-6" 14'-6" 14'-6" 14'-6" 14'-6" 14'-6" 14'-6"
FULL DIMENSION
6" x10" CROSS
BEAMS TYP.
EXIST. ROOF DECK:
WOOD 2x6 T&G
TYP. IN ORIG.
BUILDING
3-1/2" x 9"
JOISTS TYP.
DOAS-3
WGT. = 3,100 LBS.
DOAS-2
WGT. = 3,100 LBS.
S32
ROOF FRAMING NOTES
1. SEE GENERAL NOTES FOR TYPICAL
REQUIREMENTS & INFORMATION.
2. ALL EXISTING CONDITIONS & DIMENSIONS
MUST BE FIELD VERIFIED BEFORE
FABRICATION & INSTALLATION BEGINS.
3. THE STRUCTURAL DESIGN SHOWN ON
PLAN AND IN DETAILS ASSUMES ALL
EXISTING BUIDING COMPONENTS ARE IN
GOOD CONDITION AND NO ROT,
DETERIORATION OR OTHER UNUSUAL
CONDITIONS ARE PRESENT.
4. NOTIFY ARCHITECT BEFORE PROCEEDING
IF ANY CONDITIONS NOTED ABOVE ARE
ENCOUNTERED.
33533 W. Twelve Mile Rd.
Farmington Hills, Michigan 48331
(248) 932-3088
(248) 932-2010
Waterford Montessori Academy Midland Campus HVAC Improvements
Project. No. 1021
Bidding / For Permits: 12 July, 2021
S30
Roof Plan - South
1/8" = 1'-0"
Roof Plan - South
STEEL BEAMS
AT HIGH ROOF
EDGE OF EXIST. BUILDING /
1967 ADDITION
A
D D
IT
IO
N O
R
IG
IN
A
L B
U
IL
D
IN
G
DOAS-1
WGT. = 3,900 LBS.
EQUIPMENT ENCLOSURE
AT GRADE
RTU-1
WGT. = 2,850 LBS.
EXIST. 14 GA. x
7 - 1/2" METAL
DECK
(3) HSS5x5x3/16
UNDER DECK
HIGH FLUTES
CONC. PAD
ON GRADE
S32
C8x11.5 VERT WALL
STRONGBACK
EXTEND 2'-6" ABOVE &
BELOW OPENINGS
FASTEN W/ 1/2"Ø
THREADED ROD, SET W/
HILTI HY-270 EPOXY, MIN
3" EMBED, @ 16" OC
USE SCREEN TUBE IF
CMU IS HOLLOW
LINTELS PER
(DH. REF.)
S50
S50
ROOF FRAMING NOTES
1. SEE GENERAL NOTES FOR TYPICAL
REQUIREMENTS & INFORMATION.
2. ALL EXISTING CONDITIONS & DIMENSIONS
MUST BE FIELD VERIFIED BEFORE
FABRICATION & INSTALLATION BEGINS.
3. THE STRUCTURAL DESIGN SHOWN ON
PLAN AND IN DETAILS ASSUMES ALL
EXISTING BUIDING COMPONENTS ARE IN
GOOD CONDITION AND NO ROT,
DETERIORATION OR OTHER UNUSUAL
CONDITIONS ARE PRESENT.
4. NOTIFY ARCHITECT BEFORE PROCEEDING
IF ANY CONDITIONS NOTED ABOVE ARE
ENCOUNTERED.
33533 W. Twelve Mile Rd.
Farmington Hills, Michigan 48331
(248) 932-3088
(248) 932-2010
Waterford Montessori Academy Midland Campus HVAC Improvements
Project. No. 1021
Bidding / For Permits: 12 July, 2021
S31
Roof Plan - North
1/8" = 1'-0"
Roof Plan - North
*93 9/32
*119 1/2
T T
*85 1/8
LVL 1 3/4" x 9"
EA. SIDE OF
EXIST. 4x10
TYP.
PROVIDE CONT. PL 3/16" x 6"
LAG SCREWED TO
BOT. OF 8x10 GIRDER
6x6 PRESSURE TREATED
SUPPORT FRAMING
ON TOP OF 2x6 DECKING
PROVIDE (3) A35 CLIPS
W/ 10d SHORT NAILS
EA. SIDE TYP.
6x6 ALIGNED W/
CURB W/ (2) A35
EA. END
FASTEN CORNERS
W/ (2) 1/2" Ø x 9"
LAG SCREWS TYP.
EXIST. 4x10 JOIST
BELOW TYP.
MAX.
2'-0" 1
S50
TYP. AT
WOOD
DECK
3" Ø STD. PIPE
STAND-OFF
HSS5x5x3/16 BEARING
ON TOP OF CMU WALL
& BELOW DECK
ALIGN W/ DECK HIGH FLUTE
L5x3x1/4 LLV
BELOW DECK
EA. SIDE OPENING
HSS3x3x3/16"
CURB SUPPORT
FRAME
S50
33533 W. Twelve Mile Rd.
Farmington Hills, Michigan 48331
(248) 932-3088
(248) 932-2010
Waterford Montessori Academy Midland Campus HVAC Improvements
Project. No. 1021
Bidding / For Permits: 12 July, 2021
S32
Enlarged Plans
3/8" = 1'-0"
ROOF PLAN - SOUTH
3/8" = 1'-0"
ROOF PLAN - NORTH
ROOF T.O. DECK
EL (15'-0")
3" 1 1/2"
4"
END OF LVL DUCT OPENING
RTU
SEE PLAN
CURB
EXIST 2x6 DECKING
EXIST TOP FLANGE
JOIST HANGERS TYP
3/4" PRESSURE-TREATED
PLYWOOD, FASTEN W/8d
HDG NAILS @ 6" OC EDGE,
12" OC FIELD
A35 CLIP W/ 10d SHORT
TYP
1'-0"
(2) SCREWS EA SIDE AT
ENDS & BELOW CURB
(2) ROWS SCREWS
@ 24" OC, STAGGERED
TYP EA SIDE
CORRIDOR WALL
SIMPSON SDS 1/4x4 1/2"
SCREWS TYP
LVL 1 3/4 x 9 1/4" EA SIDE
EXIST 3 1/2 x 9" JOIST TYP
(2) ROWS 3/4"Ø x 6"
LAG SCREWS
CONT PL 1/4 x 6"
TYP
1" OFFSET
1B
SECTION
REFLECTED PLAN1B
ROOF T.O. DECK
EL (15'-0")
RTU
SEE PLAN
CURB
M E
P
C O
O R
D W
HSS3x3x3/16
CURB SUPPORT
CAP PL 4" SQ
3/16
ACCES HOLE IN
EXIST DECK
EXIST 7 1/2" x 14 GA
LONG SPAN DECK
HSS5x5x3/16
1/4
2"
EA. SIDE, NS &
FS
1/2"
3"Ø STD
PIPE
3/16
/2
CAP PL 1/4"
EXIST CONT
BEARING PL
EXIST CMU
WALL
L3 1/2x3 1/2x1/4
LOOSE BRICK
LINTEL TYP
EXISTING CMU WALL
L4x4x1/4, SLOT IN TO
MORTAR JOINT W/ MIN
6" BEARING EA END,
BOTH SIDES, BEFORE
OPENING DEMO
EXIST BRICK
ADD CONT PL 1/4"
3/16 3@12
M
IN
1'-0"
#4 @ 12" OC
EA WAY, TOP & BOTT
CONT #5
TOP & BOTT
#5 VERT @ 12" OC
33533 W. Twelve Mile Rd.
Farmington Hills, Michigan 48331
(248) 932-3088
(248) 932-2010
Waterford Montessori Academy Midland Campus HVAC Improvements
Project. No. 1021
Bidding / For Permits: 12 July, 2021
S50
Typical Details
1" = 1'-0"
SECTION AT RTU ON WOOD DECK
1 1/2" = 1'-0"
RTU AT STEEL DECK
3/4" = 1'-0"
DOUBLE ANGLE LINTEL
DETAIL AT EXISTING
3/4" = 1'-0"
EQUIPMENT PAD ON GRADE