WHES DRAWINGS
1 MB Posted
- Attached to
- BES-WHES HVAC 55144-23-RFP-671
- Solicitation number
- 55144-23-671
- Issued by
- Haralson County, Georgia
About this file
Summary of WHES Drawings
This is a set of architectural and engineering construction drawings for the West Haralson Elementary School Gymnasium Modification project in Tallapoosa, Georgia, prepared for Haralson County Schools. The project involves replacing the existing HVAC system in the gymnasium (Building 2030) with a new 25-ton packaged gas/electric rooftop unit (RTU-1), including installation of four new steel columns and beams to support the equipment on the existing metal roof. The scope of work encompasses mechanical, electrical, and structural modifications to support the new HVAC system, removal of existing equipment including gas unit heaters and intake louvers, and installation of supplemental ductless split-system heat pumps (seven units designated AC/HP-1 through AC/HP-7) in various spaces. The existing facility comprises 47,428 square feet with 352 full-time equivalents and 34 inventory units, with no new construction area. The project applies 2018 International Building Code with 2020 and 2022 Georgia Amendments along with applicable mechanical, electrical, fire, and energy codes, and includes design loads for wind speeds of 115 mph with seismic design category C.
The construction drawings include general notes, architectural floor and roof plans with details, structural framing plans with column and footing schedules specifying HSS4x4x1/4 columns and 3'-0"x3'-0"x12" concrete footings, mechanical HVAC floor and roof plans with schedules and connection details, and electrical floor plans with legend and panelboard schedules. Key project partners include Breaux & Associates Architects (design architect), BAA Mechanical Engineers (mechanical engineer), Mathis Consulting Engineers (electrical engineer), and Keystone Structural Engineering (structural engineer). The structural design includes four new W8x13 steel beams with welded connections, horizontal and diagonal bracing using L3x3x1/4 angles, and new roof-mounted curbs with flashing details for equipment penetrations through the existing standing seam metal roof, all coordinated to minimize disruption to the existing educational facility.
Text of this file
DATE
PROJECT NO.
VICINITY MAPPROJECT SCOPEBUILDING CODE DATAAPPLICABLE CODESPROJECT PARTNERS
2018 IBC with 2020 & 2022 Georgia Amendments 2018 IPC with 2020 & 2022 Georgia Amendments
2018 IMC with 2020 Georgia Amendments 2018 IFGC with 2020 & 2022 Georgia Amendments
2020 National Electric Code 2018 NFPA 101 Life Safety Code
2018 International Fire Code Georgia Accessibility Code
2010 ADA Standards for Accessible Design
2004 ADAAG
2015 International Energy Conservation Code (IECC) with 2020 & 2022 Supplements and Amendments
INDEX OF DRAWINGS
SHEET/SUITE/ROOM/DOOR REFERENCE
3A1.20 3A100A 3A100A1
SHEET NUMBERING
SUITE - ROOM NUMBERING
DOOR NUMBERING
DISCIPLINE REFERENCE
BUILDING NUMBER
(1,2 OR 3) - AS NEEDED, IF
NO NUMBER PRESENT
SHEET APPLIES TO CAMPUS
OR ALL BUILDINGS
AREA REFERENCE
AS NEEDED, IF NO LETTER
PRESENT SHEET APPLIES TO
WHOLE BUILDING LEVEL.
OTHERWISE AREAS AS NOTED IN
KEY PLAN.
BUILDING NUMBER
(IF NEEDED, SEE ABOVE)
DOOR LOCATION
REFERENCE (BASED ON
SUITE-ROOM NUMBERING -
SEE ABOVE)
GENERAL SHEET
ORGANIZATION
LEVEL REFERENCE
DOOR NUMBER
SUITE NUMBER
ROOM NUMBER
OWNER
BREAUX & ASSOCIATES
ARCHITECTS
5955 SHILOH ROAD EAST,
SUITE 200
ALPHARETTA, GEORGIA 30005
(678) 585-4508
ConstructionAdmin@BXArch.com
ARCHITECT
ENGINEERS
MECHANICAL
BAA MECHANICAL ENGINEERS,
INC.
500 BISHOP ST., SUITE E-2
ATLANTA, GEORGIA 30318
(404) 355-0050
ELECTRICAL
MATHIS CONSULTING ENGINEERS
244 O'DELL RD., SUITE 6
GRIFFIN, GEORGIA 30224
(404) 237-8632
OCCUPANCY CLASSIFICATION:
CONSTRUCTION TYPE:
SPRINKLERED:
OVERALL AREA:
NO. OF STORIES:
STRUCTURAL
KEYSTONE STRUCTURAL
ENGINEERING, P.C.
531 ROSELANE ST., SUITE 150
MARIETTA, GEORGIA 30060
(404) 483-6921
1/
/2
:5 3:
A
M
G0.0
COVER
O
LD
H W
Y
0, T
AL
LA
PO
O
SA
, G
A
W
ES
T H
AR
AL
SO
N
E
LE
M
EN
TA
R
Y
SC
H O
O L
G
YM
N
AS
IU
M
M O
D
IF
IC
AT
IO
N
01/04/2023
22130
H
AR
AL
SO
N C
O U
N
TY
S C
H O
O
LS
SF
(E
XI
ST
IN
G A
R
EA
S F
(N
EW
A R
EA
S
F (T
O
TA
L
AR
EA
F .T
.E
EX
IS
TI
N
G
F
.T .E
N
EW
F .T
.E
TO
TA
L)
I.U
EX
IS
TI
N
G
I.
U
N
EW
I.U
TO
TA
L)
(F
AC
IL
IT
Y C
O D
E:
-4
0)
WEST HARALSON ELEMENTARY SCHOOL
GYMNASIUM MODIFICATION
4552 OLD HWY 100, TALLAPOOSA, GA 30176
FACILITY CODE: 671-4050
HARALSON COUNTY SCHOOLS
299 ROBERTSON AVENUE
TALLAPOOSA, GA 30176
(770) 547-2500
HARALSON COUNTY SCHOOLS
CONTACT: DR. JERRY BELL
EXISTING EDUCATIONAL AND EXISTING ASSMEBLY
EXISTING
N/A
8277 SF
ONE (NOT AFFECTED BY PROPOSED SCOPE)
NO. DRAWING NAME DATE
GENERAL
G0.0 COVER 01/04/2023
ARCHITECTURAL
A1.0 OVERALL PLAN, FLOOR PLAN, ROOF PLAN, AND DETAIL 01/04/2023
STRUCTURAL
S1.1 GENERAL NOTES, ROOF FRAMING PLAN, SECTIONS AND DETAILS 01/04/2023
MECHANICAL
M1.0 HVAC LEGENDS, SCHEDULES, AND DETAILS 01/04/2023
M1.1 HVAC FLOOR PLAN AND ROOF PLAN 01/04/2023
ELECTRICAL
E0.1 SYMBOL LEGEND, GENERAL NOTES, PANELBOARD SCHEDULES, & RISER DIAGRAM 01/04/2023
E1.1 FLOOR PLANS - ELECTRICAL 01/04/2023
BUILDING
LOCATION
NO DESCRIPTION DATE
PROJECT SCOPE SHALL INCLUDE THE REPLACEMENT OF EXISTING HVAC SYSTEM WITH NEW HVAC SYSTEM FOR THE
GYMNASIUM (BUILDING 2030)
NEW STEEL BEAMS
ABOVE THE ROOF TO
SUPPORT RTU-1-
REFER STRUCTURAL
(4) NEW STEEL COLUMNS -
REFER STRUCTURAL
EXISTING METAL ROOF
TO REMAIN
EXISTING METAL ROOF
TO REMAIN
EXISTING METAL ROOF
TO REMAIN
NEW RTU-1
REF. HVAC
A1.0
Sim
NEW STEEL PIPE COLUMNS
REFER STRUCTURAL
STAINLESS STEEL
DRAWBAND
ROOF JACK (DEKTILE
OR EQUAL) REFER TO MANUFACTURER'S
INSTRUCTIONS FOR INSTALLATION
FASTENER THROUGH FLASHING
AND ROOF PANEL - AVOID DECK
AND STRUCTURE
EXISTING STANDING SEAM METAL
ROOF PANEL
EXISITNG ROOF DECK
EXISTING STEEL BEAM
TO REMAIN
DECK OPENING MUST BE
1" LARGER THAN BASE OF
ROOF JACK
ROOF FIELD CUT HOLE
1" MIN. LARGER THAN PIPE.
M
AX
M
IN
. 4
3"
AREA NOT IN
SCOPE OF WORK
GYMNASIUM
A100
ENTRANCE
CORRIDOR
A101
BOYS RR
A102
GIRL RR
A103
BOYS
A104
STOR.
A105
STOR.
A106
TLT
A107
STOR.
A108
STOR.
A109
STOR.
A110
TLT
A111
GIRLS
A112
EXISTING BUILDING
TO REMAIN
ST
AT
E OF GEORG
IA
R E G
ISTEREDARC
HI
T E C T
C E
R T
I F
CAT E NO. 0 1 3
I
DOUGLAS P.
BREAUX
DATE
PROJECT NO.
1/ 9/
:1
5:
P M
A1.0
OVERALL PLAN,
FLOOR PLAN,
ROOF PLAN, AND
DETAIL
O
LD
H W
Y
0, T
AL
LA
PO
O
SA
, G
A
W
ES
T H
AR
AL
SO
N
E
LE
M
EN
TA
R
Y
SC
H O
O L
G
YM
N
AS
IU
M
M O
D
IF
IC
AT
IO
N
01/04/2023
22130
H
AR
AL
SO
N C
O U
N
TY
S C
H O
O
LS
SF
(E
XI
ST
IN
G A
R
EA
S F
(N
EW
A R
EA
S
F (T
O
TA
L
AR
EA
F .T
.E
EX
IS
TI
N
G
F
.T .E
N
EW
F .T
.E
TO
TA
L)
I.U
EX
IS
TI
N
G
I.
U
N
EW
I.U
TO
TA
L)
(F
AC
IL
IT
Y C
O D
E:
-4
0)
01/04/2023
SCALE: 1/8" = 1'-0"A1.0
2 ROOF PLAN
SCALE: 1 1/2" = 1'-0"A1.0
4 ROOF DETAIL - COLUMN PENETRATION (TYP.)
NO DESCRIPTION DATE
SCALE: N.T.S.A1.0
1 OVERALL FLOOR PLAN
SCALE: 1/8" = 1'-0"A1.0
3 FLOOR PLAN - LEVEL 1
NO DRAWING NOTES
1 NEW STEEL TUBE COLUMNS ADDED TO SUPPORT ROOF TOP EQUIPMENT. REFER STRUCTURAL FOR
FOUNDATION AND COLUMN DETAILS
2 REMOVE ALL EXISTING PLUMBING FIXTURES, PATCH ALL OPENING. FINISH TO MATCH EXISTING
CONDITIONS.
3 REMOVE EXISTING INTAKE LOUVERS. PATCH OPENINGS TO MATCH EXISTING
REFER MECHANICAL FOR ADDITIONAL WORKS ON ROOF
REFER MECHANICAL FOR ADDITION WORKS ON PLAN
GENERAL NOTES:
(THESE SPECIFICATIONS ARE IN ADDITION TO AND DO NOT EXCLUDE ANY FOUND IN THE GENERAL SPECIFICATIONS FOR THE PROJECT)
1. THE CONTRACT STRUCTURAL DOCUMENTS REPRESENT THE FINISHED STRUCTURE. THE CONTRACTOR IS RESPONSIBLE FOR THE MEANS AND METHODS OF CONSTRUCTION. PROVIDE ALL MEASURES REQUIRED TO PROTECT THE STRUCTURE, WORKMEN, AND OTHER PERSONS DURING CONSTRUCTION; INCLUDING BRACING, SHORING FOR CONSTRUCTION EQUIPMENT, SHORING FOR THE BUILDING, FORMS AND SCAFFOLDING, SHORING OF RETAINING WALLS AND OTHER TEMPORARY SUPPORTS REQUIRED. COMPLY WITH APPLICABLE REQUIREMENTS OF OSHA AND OTHER GOVERNING BODIES HAVING JURISDICTION AT THE SITE.
2. SHOP DRAWINGS FOR CONCRETE AND MASONRY REINFORCING, STRUCTURAL STEEL, JOIST, AND METAL FLOOR AND ROOF
DECKING SUBMITTALS SHALL COMPLY WITH THE FOLLOWING:
A. CONTRACTOR SHALL FURNISH COMPLETE AND DETAILED SHOP DRAWINGS PREPARED UNDER SUPERVISION OF A REGISTERED STRUCTURAL ENGINEER. THESE DRAWINGS SHALL SHOW SIZES, LOCATION, TYPE AND EXTENT OF ALL MEMBERS, BOLTS AND WELDS.
B. INDICATE THE DATE OF THE STRUCTURAL DRAWINGS USED FOR SHOP DRAWING PREPARATION.
C. INDICATE WELDS BY STANDARD AWS SYMBOLS AND SHOW SIZE LENGTH AND TYPE OF EACH WELD.
D. PROVIDE SETTING DRAWINGS, TEMPLATES AND DIRECTIONS FOR INSTALLATION OF ANCHOR BOLTS AND OTHER ANCHORAGES TO
BE INSTALLED BY OTHERS.
E. CONTRACTOR SHALL REVIEW AND STAMP ALL SHOP DRAWINGS PRIOR TO SUBMITTAL FOR ENGINEERING REVIEW.
F. CONTRACTOR SHALL HAVE AN APPROVED SET OF STRUCTURAL STEEL SHOP DRAWINGS AND PROOF OF WELDER CERTIFICATION AT
THE JOBSITE AT ALL TIMES.
G. COORDINATE ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS.
H. SEE ARCHITECTURAL AND CIVIL DRAWINGS FOR BUILDING LOCATION AND ORIENTATION. COORDINATE ALL DIMENSIONS WITH ARCH.
DRAWINGS. DO NOT SCALE DRAWING.
I. WHERE A DETAIL IS SHOWN FOR ONE CONDITION, IT SHALL APPLY FOR ALL LIKE AND SIMILAR CONDITIONS EVEN THOUGH NOT
SPECIFICALLY MARKED ON THE DRAWINGS.
3. DESIGN LOADS:
THE BUILDING STRUCTURE DESCRIBED IN THESE PLANS SHALL BE CONSTRUCTED IN COMPLIANCE WITH 2018 IBC WITH ALL GEORGIA
AMENDMENTS.
A. GRAVITY LOADS
DEAD LOADS:
ROOF: 10.0 PSF
LIVE LOADS:
ROOF: 20.0 PSF
B. SNOW LOADS:
GROUND SNOW LOAD (Pg): 5 PSF BALANCED ROOF SNOW LOAD (Pf+RAIN): 10.5 PSF SNOW EXPOSURE FACTOR (Ce): .9 SNOW IMPORTANCE FACTOR (Is): 1.1 THERMAL FACTOR (Ct): 1.0
C. WIND LOADS ULTIMATE LOADS:
BASIC WIND SPEED (3 SEC. GUST): 115 MPH
RISK CATEGORY: III
EXPOSURE CATEGORY: B
INTERNAL PRESSURE (GCpi): +/-0.18
SEE ASCE-7 FOR COMPONENT & CLADDING LOADS BASED ON
TRIBUTARY AREAS FOR INDIVIDUAL ELEMENTS
D. SEISMIC DESIGN CRITERIA:
SEISMIC IMPORTANCE FACTOR (Ie): 1.25
RISK CATEGORY: III
MAPPED SPECTRAL RESPONSE ACCELERATIONS:
Ss: 0.2184g S1: 0.0958g
SITE CLASS: D
S(DS): 0.233g S(D1): 0.153g
SITE COEFFICIENT
Fa = 1.60 Fv = 2.40
SEISMIC DESIGN CATEGORY: C
BASIC SEISMIC FORCE RESISTING SYSTEM:
STEEL SYSTEM NOT SPECIFICALLY DETAILED FOR SEISMIC RESISTANCE
SEISMIC RESPONSE COEFFICIENT (Cs): 0.0971
DESIGN RESPONSE MODIFICATION FACTOR (R): 3.0
ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE PROCEDURE
FOUNDATION NOTES:
1. CONCRETE COMPRESSIVE STRENGTH SHALL BE 3000 PSI U.N.O.. EXTERIOR CONCRETE SHALL BE AIR ENTRAINED TO 6% +/- 11/2%
2. SEE ARCHITECTURAL DRAWINGS FOR SIDE WALK EXTENTS, PLANTER, AND PAVER LOCATIONS, CONCRETE PADS AND STAIRS, SEE ARCH. FOR DIMENSIONS AT INTERIOR MASONRY PARTITIONS, AND DETAILS.
3. COORDINATE FINISHED FLOOR ELEVATIONS (F.F.E.) WITH ARCH. AND CIVIL DRAWINGS.
4. REFERENCE F.F.E = (SEE CIVIL)
5. ALL FOOTINGS HAVE BEEN DESIGNED BASED UPON ANASSUMED SOIL BEARING PRESSURE OF 2000 PSF.
6. ALL FOUNDATION EXCAVATIONS SHALL BE EVALUATED BY THE GEOTECHNICAL ENGINEER OR TESTING AGENCY PRIOR TO PLACING ANY FOUNDATION CONCRETE. CONTACT STRUCTURAL ENGINEER IF THE ALLOWABLE SOIL BEARING PRESSURE IS LESS
THAN 2500 PSF.
7. ALL EXTERIOR FOOTINGS SHALL BEAR A MINIMUM OF 1' - 4" BELOW F.F.E. OR THE ADJACENT EXTERIOR FINISH GRADE, UNLESS
NOTED OTHERWISE.
8. TOP OF INTERIOR FOOTINGS SHALL BE A MINIMUM OF 0 - 8" BELOW F.F.E. COORDINATE TOP OF FOOTING ELEV. W/ PLUMBING AND
LOWER FOOTING IF NECESSARY
9. PRIOR TO COMMENCING ANY FOUNDATION WORK, COORDINATE WORK WITH ANY EXISTING OR NEW UTILITIES. LOWER FOUNDATION AS REQUIRED TO AVOID INTERFERENCE WITH UTILITIES, EXCEPT WHERE ZERO LOT LINE FOOTINGS ARE LOCATED PARALLEL TO ADJACENT BUILDINGS. REFER TO THE FOUNDATION PLAN FOR FOOTING STEPS AT ADJACENT BUILDINGS - CONTACT
ARCH./STRUCTURAL ENGINEER IF A CONFLICT OCCURS.
10. PROTECT PIPES AND CONDUITS RUNNING THROUGH WALLS AND SLABS WITH 1/2" INCH EXPANSION MATERIAL. LOWER CONTINUOUS FOOTING AND GRADE BEAMS PERPENDICULAR TO PIPE RUNS TO ALLOW PIPES TO PASS ABOVE THE FOOTINGS OR THROUGH THE GRADE BEAMS. ALTERNATIVELY, PROVIDE A CONCRETE JACKET IF PIPES ARE LOW ENOUGH TO BE PLACED BELOW THE FOOTINGS AND GRADE BEAMS PARALLEL TO PIPE RUNS TO AVOID SURCHARGE ONTO ADJACENT TRENCH EXCAVATIONS.
11. ARRANGE FOR OWNER'S INDEPENDENT TESTING AGENCY TO MONTIOR CUT AND FILL OPERATIONS AND PERFORM FIELD DENSITY AND MOISTURE CONTENT TESTS TO VERIFY COMPACTION AND APPROVE FOOTING SUBGRADES PRIOR TO PLACING
CONCRETE.
CONCRETE SLAB NOTES:
1. FLOOR SLABS ON GRADE SHALL BE 4" THICK 3000 PSI MINIMUM COMPRESSIVE STRENGTH NORMAL WEIGHT CONCRETE.
REINFORCED w/ 6X6-W1.4/W1.4 (10GA) WWF UNLESS NOTED OTHERWISE. LOCATE SINGE LAYER OF WWF AT MID DEPTH OF SLAB.
PROVIDE 15 MIL (MIN) POLYOLEFIN VAPOR BARRIER WITH JOINTS LAPPED 6" AND TAPED UNDER ALL INTERIOR SLABS.
2. PROVIDE A 4" THICK #57 STONE DRAINAGE FILL BELOW ALL INTERIOR SLABS ON GRADE UNLESS NOTED OR DETAILED
OTHERWISE.
3. WHERE CONTROL/CONSTRUCTION JOINTS ARE NOT INDICATED, PROVIDE CONTROL/CONSTRUCTION JOINTS AT 12'-0" O.C. IN EACH DIRECTION. THE LENGTH OF ANY PANEL SHALL NOT EXCEED 1.5 TIMES THE WIDTH. CONSTRUCTION JOINTS ADJACENT TO INTERIOR WALLS SHALL BE DOWELED WITH 3/4" DIAMETER SMOOTH RODS AT 24" O.C. LOCATED AT MID DEPTH OF SLAB.
4. CONDUITS AND PIPES EMBEDDED IN SLABS ON GRADE:
SHALL NOT BE LARGER IN OUTSIDE DIMENSION THAN ONE-THIRD THE OVERALL THICKNESS OF THE SLAB. THEY SHALL NOT BE SPACED CLOSER THAN THREE DIAMETERS OR WIDTHS ON CENTER. A MINIMUM SLAB THICKNESS OF 2/3 THE SLAB THICKNESS
MUST BE MAINTAINED OVER THE EMBEDDED CONDUITS OR PIPES.
5. COORDINATE THE EXACT LOCATION AND EXTENTS OF ALL FLOOR SLOPES, RECESSED AREAS, DRAIN AND TRENCH LOCATIONS
WITH OWNER, ARCHITECTURAL AND PLUMBING DRAWINGS.
SPECIAL INSPECTION NOTES:
A. THE SPECIAL INSPECTOR SHALL BE ENGAGED BY THE OWNER. SPECIAL INSPECTOR SHALL BE FULLY QUALIFIED, APPROVED BY THE BUILDING OFFICIAL, REGISTERED BY APPLICABLE REGISTRATION BOARD IF REQUIRED BY THE LOCAL BUILDING OFFICIAL, AND SHALL BE ACCEPTABLE TO THE ARCHITECT.
B. THE SPECIAL INSPECTOR SHALL PROVIDE VERIFICATION OF CONSTRUCTION QUALITY CONTROL INSPECTIONS AND TESTING.
THE SPECIAL INSPECTOR SHALL CERTIFY THAT ALL WORK REQUIRING INSPECTION IS PERFORMED IN COMPLIANCE WITH ALL REQUIREMENTS OF THE CONTRACT DOCUMENTS, BUILDING CODE REQUIREMENTS AND LOCAL BUILDING DEPARTMENT
REQUIREMENTS.
C. SPECIAL INSPECTIONS ARE REQUIRED FOR THE ITEMS NOTED IN THE STATEMENT OF SPECIAL INSPECTIONS AND THE 2012 IBC CHAPTER 17. THE CONTRACTOR SHALL OBTAIN A COPY OF THE STATEMENT OF SPECIAL INSPECTIONS AND NOTIFY THE SPECIAL
INSPECTOR WHEN WORK IS READY TO BE INSPECTED.
D. FAILURE TO NOTIFY THE SPECIAL INSPECTOR PRIOR TO OBSCURING AN ITEM REQUIRING INSPECTION MAY RESULT IN THE CONTRACTOR REMOVING OTHER WORK TO ALLOW INSPECTION. THIS WORK WILL BE REMOVED AND REPLACED AT THE CONTRACTORS EXPENSE. FAILURE TO HAVE REQUIRED ITEMS INSPECTED IS REASON FOR REJECTION OF THE WORK.
E. PREMATURE NOTIFICATION FOR INSPECTIONS WILL RESULT IN ADDITIONAL INSPECTION WITH ALL EXPENSES AND FEES PAID
FOR BY THE CONTRACTOR.
F. SEE SHEET S5.1 FOR SPECIAL INSPECTION CHECKLIST.
REINFORCED CONCRETE NOTES:
1. STRUCTURAL MEMBERS OF REINFORCED CONCRETE SHALL BE CONSTRUCTED IN ACCORDANCE WITH ACI318.
2. ALL CONCRETE SHALL HAVE A SLUMP OF 4" (+/-1") AND A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 3000 PSI U.N.O..
CONCRETE EXPOSED TO FREEZE-THAW SHALL BE AIR ENTRAINED TO 6% AIR CONTENT +/- 1 1/2%.
3. ALL STEEL REINFORCEMENT SHALL BE ASTM 615-GRADE 60. ALL WELDED STEEL REINFORCEMENT SHALL BE ASTM A706-GRADE
60. WELDED WIRE REINFORCEMENT SHALL BE ASTM A 185, PLAIN, FABRICATED FROM AS DRAWN STEEL WIRE INTO FLAT SHEETS.
4. UNLESS NOTED OTHERWISE, CAST IN PLACE CONCRETE WALLS AND FLOORS SHALL HAVE THE FOLLOWING STEEL ADDED AROUND ALL OPENINGS: 2-#5 (LENGTH OF OPENING + 48") ALONG EACH SIDE OF OPENING AND TWO (2)-#5X5'-0" DIAGONALLY AT
EACH CORNER.
5. ALL CONCRETE COMPRESSIVE STRENGTH TESTS SHALL BE AVAILABLE AT JOB SITE.
6. ALL LAP SPLICE LENGTHS SHALL BE AS SHOWN IN TABLE ON THIS SHEET.
7. MINIMUM CONCRETE COVER FOR REINFORCING STEEL: (UNO)
A. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3"
B. CONCRETE EXPOSED TO EARTH AND WEATHER:
#5 REBAR AND SMALLER: 2"
#6 REBAR AND LARGER: 2"
C. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH EARTH:
SLABS, WALLS, AND JOISTS:
#14 OR #18 BARS: 1 1/2"
#11 BARS AND SMALLER: 2"
BEAMS AND COLUMNS: 2"
8. CONTRACTOR SHALL COORDINATE DIMENSIONS OF EMBEDDED STEEL ITEMS FOR EQUIPMENT AND OTHER ITEMS.
STRUCTURAL ENGINEER OF RECORD SITE OBSERVATIONS:
THE SPECIAL INSPECTOR IS RESPONSIBLE FOR CONTINUOUS AND PERIODIC INSPECTION OF ALL WORK AS REQUIRED IN THE STATEMENT OF SPECIAL INSPECTIONS. THE STRUCTURAL ENGINEER OF RECORD OBSERVATION IS IN ADDITION TO THE SPECIAL INSPECTION AND DOES NOT SERVE AS THE SPECIAL INSPECTION FOR THE ITEMS NOTED. THE STRUCTURAL ENGINEER OF RECORD WILL OBSERVE THE INITIAL AREAS WHERE THE WORK NOTED IN THE FOLLOWING LIST IS BEING PERFORMED. CORRECTIONS TO THE WORK PERFORMED IN THE INITIAL AREAS NOTED BY THE ENGINEER OF RECORD SHALL BE FOLLOWED IN SUBSEQUENT AREAS WHERE SIMILAR
WORK IS TO BE PERFORMED.
1. CONTRACTOR SHALL NOTIFY THE ARCHITECT FIVE WORKING DAYS PRIOR TO THE FOLLOWING CONSTRUCTION MILESTONES SO
THE PROJECT ENGINEER CAN OBSERVE THE WORK :
A. SPREAD FOOTING FOUNDATIONS, EACH TYPE OF RETAINING WALL FOUNDATIONS - AFTER FOUNDATION REINFORCING IS
PLACED AND PRIOR TO PLACING CONCRETE FOR THE FOUNDATIONS.
B. EACH TYPE OF RETAINING WALL - AFTER WALL REINFORCING IS PLACED AND PRIOR TO PLACING CONCRETE FOR THE WALL.
C. FIRST SLAB ON GRADE PLACEMENT - AFTER SLAB REINFORCING IS PLACED AND BEFORE PLACING SLAB ON GRADE.
D. REINFORCED MASONRY WALLS - AFTER WALLS AND REINFORCING ARE INSTALLED AND PRIOR TO GROUTING.
E. STEEL STRUCTURE - AFTER FLOOR AND ROOF FRAMING AND ROOF DECK IS FULLY INSTALLED AND PRIOR TO INSTALLING
INSULATION OR ROOFING.
F. FLOOR SLAB ON METAL DECK PLACEMENT - AFTER SLAB REINFORCING IS PLACED AND BEFORE PLACING SLAB.
2. FAILURE TO NOTIFY THE STRUCTURAL ENGINEER PRIOR TO ANY CONSTRUCTION MILESTONE OBSERVATION MAY RESULT IN THE CONTRACTOR REMOVING OTHER WORK TO ALLOW OBSERVATION. THIS WORK WILL BE REMOVED AND REPLACED AT THE
CONTRACTORS EXPENSE.
3. PREMATURE NOTIFICATION FOR SITE VISIT WILL RESULT IN ADDITIONAL OBSERVATION WITH ALL EXPENSES AND FEES PAID FOR BY
THE CONTRACTOR.
STEEL NOTES:
1. STRUCTURAL STEEL:
A. SHALL CONFORM TO THE LATEST STANDARDS OF ASTM:
WIDE FLANGE BEAMS: A992
OTHER STRUCTURAL STEEL SHAPES, PLATES AND BARS: A36
HOLLOW STRUCTURAL STEEL SECTIONS (ROUND AND RECTANGULAR): A500 GRADE B
STRUCTURAL STEEL PIPE: A53 GRADE B
B. STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED AND ERECTED IN ACCORDANCE WITH THE STANDARDS AND SPECIFICATIONS OF THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC 360-10) USING LOAD AND RESISTANCE FACTOR DESIGN.
C. PROVIDE 1" (MINIMUM) NON-SHRINK 5000 PSI GROUT UNDER ALL BASE PLATES.
D. SHOP OR FIELD SPLICES BETWEEN SUPPORTS THAT ARE NOT REQUIRED BY DESIGN WILL NOT BE ALLOWED. ANY MEMBERS CONTAINING SUCH SPLICES FOUND IN THE FIELD SHALL BE REMOVED AND REPLACED WITH UNSPLICED MEMBERS AT THE FABRICATOR'S EXPENSE.
2. STEEL CONNECTIONS:
A. WHERE BEAM REACTIONS OR DETAILS ARE NOT SHOWN IN THE CONSTRUCTION DOCUMENTS. CONNECTIONS SHALL BE DESIGNED FOR ONE- HALF THE MAXIMUM (SIMPLE SPAN) UNIFORM LOAD WHICH THE MEMBER WILL SUPPORT FOR THE SPAN SHOWN ON THE DRAWINGS.
B. UNLESS LARGER REACTION IS SHOWN ON DRAWINGS, PROVIDE MINIMUM DESIGN FORCES AS FOLLOWS:
1. NON COMPOSITE BEAMS: BEAM-TO-BEAM OR BEAM-TO-COLUMN CONNECTION TO DEVELOP THE REACTION OF CONNECTED BEAM. OBTAIN END REACTION FROM ALLOWABLE UNIFORM LOAD TABLES IN PART 2 OF THE AISC MANUAL OF STEEL CONSTRUCTION.
C. ADD TO REACTIONS LISTED ABOVE, LOADS OR REACTIONS OF MEMBERS SUPPORTED BY BEAM WITHIN THREE FEET OF BEAM END AND
VERTICAL COMPONENTS OF FORCES IN BRACE MEMBERS FRAMING INTO BEAM.
D. BRACE CONNECTIONS SHALL BE IN ACCORDANCE WITH THE DETAILS SHOWN ON THE DRAWINGS. ANGLE SIZES, PLATE SIZES, AND SIZE AND
LENGTHS OF WELDS SHALL BE DESIGNED IN ACCORDANCE WITH THE FOLLOWING:
(1) DESIGN CONNECTIONS OF DIAGONAL MEMBERS TO DEVELOP THE LOADS SHOWN ON THE BRACE DETAILS.
(2) WHERE FORCES ARE NOT INDICATED ON THE DETAILS, DESIGN CONNECTIONS OF DIAGONAL MEMBERS TO DEVELOP THE FULL TENSILE
CAPACITY OF THE DIAGONAL MEMBER.
(3) SIZE GUSSET PLATES AND ALL WELDS TO RESIST THE FORCE OF THE DIAGONAL MEMBERS. PLATES AND WELDS SHALL BE SIZED FOR
TENSIONS, SHEARS, AND MOMENTS CAUSED BY CONCENTRIC AND ECCENTRIC FORCES.
(4) ALL BRACE CONNECTIONS SHALL USE WELDS OR FULLY TENSIONED A325 CLASS A SLIP CRITICAL BOLTS.
(5) BOLTS SHALL BE HIGH STRENGTH A-325 BOLTS OF SAME SIZE AND NUMBER AS SHOWN ON DRAWINGS. CONNECTIONS SHALL CONFORM TO THE SPECIFICATIONS FOR STRUCTURAL JOINTS USING ASTM A-325 OR A-490 BOLTS. CONNECTIONS ARE BEARING TYPE.
E. BOLTS SHALL BE TIGHTENED TO THE SNUG TIGHT CONDITION UNLESS OTHERWISE NOTED ON THE DRAWINGS.
3. WELDS:
A. PROVIDE MINIMUM SIZE OF FILLET WELDS AS SPECIFIED IN TABLE J2.4 OF THE AISC MANUAL.
B. ALL WELDING SHALL CONFORM TO THE LATEST "STRUCTURAL WELDING CODE" BY THE AMERICAN WELDING SOCIETY. ALL WORK SHALL BE PERFORMED BY CERTIFIED WELDERS EXPERIENCED IN THE TYPE OF CONSTRUCTION INVOLVED. PROOF OF WELDER CERTIFICATION SHALL BE
AVAILABLE AT THE JOB SITE.
C. DEVELOP THE FULL TENSILE STRENGTH OF THE MEMBER ELEMENT JOINED, ON ALL SHOP AND FIELD WELDS, UNLESS NOTED OTHERWISE ON
THE DRAWINGS.
D. ALL WELDS ARE CONTINUOUS FOR THE FULL LENGTH OF THE CONNECTION UNLESS NOTED OTHERWISE ON DRAWINGS.
E. HEADED STUDS (SHEAR AND ANCHOR) AND DEFORMED ANCHORS:
PROVIDE HEADED STUDS (SHEAR AND ANCHOR) MADE OF MATERIAL CONFORMING TO ASTM A108.
(1) PROVIDE DEFORMED ANCHORS MADE OF MATERIAL CONFORMING TO ASTM A496.
(2) WELD STUDS ACCORDING TO MANUFACTURER'S RECOMMENDATIONS. MANUAL ARC (STICK) WELDING OF HEADED STUDS AND/OR
DEFORMED ANCHORS IS NOT ALLOWED.
4. COLUMN BASEPLATES THAT DO NOT HAVE THREE ANCHORS SHALL BE ADEQUATELY BRACED OR SUPPORTED BY OTHER MEANS DURING
ERECTION TO SATISFY OSHA REQUIREMENTS.
REINFORCED CONCRETE
TENSION LAP SPLICE LENGTH
BAR SIZE f'c=3000 PSI f'c=4000 PSI #3 25"
#4
#5
#6
#7
33"
41"
49"
72"
29"
36"
43"
62"
21"
(FIELD VERIFY)
(F
IE
LD
V
ER
IF
Y)
(F
IE
LD
V
ER
IF
Y)
0"
(F
IE
LD
V
ER
IF
Y)
EXISTING W12 TO REMAIN
EXISTING W12 TO REMAIN
(FIELD VERIFY)
EQ
R
TU
M
AN
U
FA
C
TU
R
ER
C O
O R
D
IN
AT
E w
EQ
6' - 6" 7' - 0" +/-
2 1/2"
L3x3x1/4 HORIZONTAL
'X' - BRACING
L3x3x1/4" KNEE BRACE
@ 45 DEG. - TYP. @
ALL 4 CORNERS IN
BOTH DIRECTIONS
S1.1
W8x13
W8x13
W8x13
W8x13
W 8x
W 8x
F3 C-1
TOP OF FTG.
MATCH EXISTING
F3 C-1
TOP OF FTG.
MATCH EXISTING
NOTES;
• SUPPORTING THE (4) 150# HP UNITS ON THE EXISTING
FRONT AND REAR CAST-IN-PLACE CONCRETE WALL (2
EACH AT FRONT AND REAR WALLS). THERE ARE ALREADY
WALL MOUNTED HP UNITS ON-SITE ALREADY. NEW (4) 150#
HP UNITS TO BE SUPPORT WITH APPROVED PROPRITARY
WALL MOUNTING FRAMES
• SEE ARCHITECTURAL DRAWINGS FOR REQUIRED ROOF
FLASHING @ (4) PIPE COLUMN PENETRATIONS THROUGH
EXISTING ROOF
C POST & BEAML
END/BEAM
3"
EX. T/STEEL.=
(FIELD COORD.)
T/STEEL.=
PROPOSED W8x13
STEEL BEAM
(SEE PLAN)
EXISTING W12 STEEL
BEAM TO REMAIN
(SEE PLAN)
EXISTING STANDING
SEAM ROOF TO REMAIN
3/16
3" STANDARD
PIPE COL - TYP.
L3x3x1/4" KNEE BRACE @ 45
DEG. - TYP. @ ALL 4 CORNERS
IN BOTH DIRECTIONS
PROPOSED W8x13 STEEL
CROSS BEAM @ SUPPORT
ENDS (SEE PLAN)
L3x3x1/4 HORIZONTAL
'X' - BRACING
NOTE:
1. TOP OF RTU-1 SUPPORT BEAM SHALL BE LEVEL AND STUB
COLUM LENGTHS WILL VARY TO MATCH ROOF SLOPE
PROPOSED RTU-1 AND ASSOCIATED CURB
(CONTRACTOR COORDINATE FAMING LAYOUT
AND DIMENSIONS WITH MECHANICAL
EQUIPMENT PROVIDER
(M
AX
IM
U
M
3'
0"
M
IN
4"
PROPOSED W8x13 STEEL
CROSS BEAM @ PROPOSED
RTU COURB (SEE PLAN)
(FIELD COORD.)
3/8" A36 FULL DEPTH WEB STIFFENER
EACH SIDE OF EXISTING STEEL BEAM WEB
@ RTU SUPPORT FRAME COLUMNS (x4)
BP-1
NOTES:
1. DESIGNATES THAT
WELD SIZE SHOULD MATCH
COLUMN WALL THICKNESS
MINUS 1/16" FOR WALL
THICKNESS GREATER THAN 1/4".
AT COLUMNS WITH WALL
THICKNESSES 1/4" OR LESS,
WELD SIZE SHOULD MATCH
COLUMN WALL THICKNESS.
2. ANCHOR BOLT PROJECTION
TO BE 6" (TYP. - U.N.O.)
T/FTG.
ANCHOR ROD 'A'
3/4" DIA. ASTM F1554 GR36
ANCHOR ROD w/ HEAVY HEX-NUT OR A36 THREADED RODS w/ A
PROJECTION OF 6" (TOP 6" TO BE
THREADED)
CONCRETE FTG.
(SEE PLAN)
1' - 0"
C COL.L
C C
O L.
L
(ANCHOR ROD 'A')
(4) - 3/4" DIA. ANCHOR RODS
HSS4x4 COL.
(SEE PLAN)
3/4" THICK BASE PLATE
TACK WELD
ROD TO NUT
1'
0" 0'
6"
1/
2"
1/ 2"
1 1/2" 1 1/2"
BEAM SIZE PLATE LENGTH
"L"
NUMBER OF BOLTS
"N"
W18 1'-3" 5
W16 1'-0" 4
W14 0' - 11" 3
W12 0'-9" 3
3/8" x "L" A36 SINGLE
SHEAR PLATE
5/16"
3/4" DIA. A325 BOLTS TYPE N "N"
= NUMBER OF BOLTS
COLUMN
SEE PLAN
STEEL BEAM
(SEE PLAN)
W10 0'-6" 2
W8 0'-6" 2
C COL. & PLATEL
STEEL COLUMN
(SEE PLAN)
(4) 3/4" DIA. BOLTS
STEEL PLATE 1/2" x FLANGE WIDTH x GREATER OF 1' - 0" OR COLUMN
WIDTH + 1/2" (MIN.)
STEEL STIFF. PLATE 1/2"
THICK ON EACH SIDE OF
BEAM WEB
STEEL BEAM
(SEE PLAN)
3/16
NOTES:
1. DESIGNATES THAT WELD SIZE SHOULD MATCH COLUMN WALL
THICKNESS MINUS 1/16" FOR WALL THICKNESS GREATER THAN 1/4". AT
COLUMNS WITH WALL THICKNESSES 1/4" OR LESS, WELD SIZE SHOULD
MATCH COLUMN WALL THICKNESS.
SEE FOOTING
SCHEDULE
1'
0"
C O
O R
D
IN
AT
E
FI
EL
D
EXISTING CONC. SLAB
(SEE PLAN)
T/SLAB
(SEE PLAN)
EX. WALL & FTG.
T/FTG.
(SEE PLAN)
(FIELD COORDINATE)
PROPOSED NEW
FOOTING
CLR.
3"
HSS4x4x1/4" COL.
SEE PLAN
#5 DOWELS @ 12" o.c. INSTALL w/ HILTI HY 200 ADHESIVE
ANCHORING SYSTEM PER THE
MANUFACTURERS
SPECIFICATIONS. EMBED 10"
MIN.
COLUMN & FTG
EXISTING MASONRY WALL
(SEE PLAN)
1 1/2" NON-
SHRINK GROUT
SCHEDULE
SEE FTG.
EQ
EQ
C
LR
3"
COORD.
FIELD
COORD.
FIELD
(4) 3/4" DIA. THREADED RODS.
INSTALL w/ HILTI HY 200 ADHESIVE
ANCHORING SYSTEM PER THE
MANUFACTURERS SPECIFICATIONS.
EMBED 8" MIN.
EXISTING WALL
FOOTING
NOTES:
1.) CONTRACTOR IS RESPONSIBLE FOR SHORING AND BRACING EXISTING MASONRY DURING CONSTRUCTION 2.) DO NOT LOCATE CLOSEST JAMB OF PROPOSED NEW OPENING IN MASONRY WALL WITHIN 4'-0" OF EXISTING
MASONRY OPENING
L6x4x3/8" EACH
SIDE (2 TOTAL)
EXISTING MASONRY
TO REMAIN
(SEE ARCH.) (6' - 4" MAX.)
PROPOSED NEW OPENING
(S
EE
A R
C H
PR
O
PO
SE
D N
EW
O
PE
N
IN
G
BOT. ANGLE
(FIELD COORD.)
EXISTING MASONRY
BEYOND
EXISTING CMU WALL
TO REMAIN (FIELD
VERIFY)
L6x4x3/8" CONT. EACH
SIDE OF EXISTING
MASONRY. FIELD
COORD.
1/4 2@6
1/4 2@63/8" x (FIELD COORDINATE)
CONT. A36 BOT. PLATE.
INSTALL AFTER EXISTING
MASONRY IS REMOVED
3/4" DIA. A325 THROUGH
BOLTS @ 16" o.c. 1
1/ 2"
1/
2"
CL
1' - 4"
6' - 4" MAX.
(SEE PLAN) 1' - 4"
1/
2"
3/4" dia. A325
THROUGH BOLTS
@ 16" o.c.
4" 8" 1' - 4". 1' - 4" 1' - 4" 8" 4"
DATE
PROJECT NO.
531 Roselane Street Suite 150
Marietta, GA 30060
(404) 483 6921
1/ 5/
:5
0:
A M
S1.1
GENERAL NOTES,
ROOF FRAMING
PLAN, SECTIONS
AND DETAILS
O
LD
H W
Y
0, T
AL
LA
PO
O
SA
, G
A
W
ES
T H
AR
AL
SO
N
E
LE
M
EN
TA
R
Y
SC
H O
O L
G
YM
N
AS
IU
M
M O
D
IF
IC
AT
IO
N
01/04/2023
22130
H
AR
AL
SO
N C
O U
N
TY
S C
H O
O
LS
SF
S .F
EX
IS
TI
N G
A R
EA
S
F S.
F.
(N
EW
A
R
EA
S F
S.
F.
(T O
TA
L
AR
EA
F
.T .E
EX
IS
TI
N G
F .T
.E
N
EW
F
.T .E
TO
TA
L)
I.U
EX
IS
TI
N G
I.
U
N
EW
I.U
TO
TA
L)
(F
AC
IL
IT
Y C
O D
E:
-4
0)
1/8" = 1'-0"S1.1
1 Roof Framing Plan
3/4" = 1'-0"S1.1
2 RTU Support Framing
3/4" = 1'-0"S1.1
4 BASE PLATE DETAILS
3/4" = 1'-0"S1.1
5 BEAM TO COLUMN DETAIL
3/4" = 1'-0"S1.1
3 BEAM OVER COLUMN DETAIL
3/4" = 1'-0"S1.1
6 PROPOSED/EXISTING COLUMN SECTION
3/4" = 1'-0"S1.1
7 NEW/REPAIR OPENING IN EX. MASONRY WALL (EXPOSED STRUCTURE)
NO DESCRIPTION DATE
Column Schedule
COLUMN SIZE Comments
C-1 HSS4X4X1/4
Structural Footing Schedule
Mark
DIMENSIONS L X W X
THICKNESS Reinforcing F3 3'-0"x3'-0"x12" (3) #5's EACH WAY
M1.0
HVAC LEGENDS,
SCHEDULES,
AND DETAILS
DATE
PROJECT NO.
/2
7/
:1 8:
P
M
O
LD
H W
Y
0, T
A
LL
A
PO
O
SA
, G A
W
ES
T H
A R
A
LS
O N
E
LE
M
EN
TA
R
Y
SC
H O
O L
G
YM
N A
SI
U
M M
O D
IF
IC
A
TI
O N
01/04/2023
22130
H
AR
AL
SO
N C
O U
N
TY
S C
H O
O
LS
(F
AC
IL
IT
Y C
O D
E:
-4
0)
NO DESCRIPTION DATE
M E
C H
A N
IC
A
L
EN
G
IN
EE
RS
, I
NC
Bi sh op
S tre et
Su ite
E -2
At la nt a, G a
| 4
-3
-0
01-04-2023
GEORG I A
REGI STERED
No. 22997
PROFESSIONAL
E NG I N E E R
JEFFREY L . LEE
AutoCAD SHX Text
ON ROOF
AutoCAD SHX Text
SWING JOINT FOR
AutoCAD SHX Text
GAS MAIN
AutoCAD SHX Text
%%UGAS UNIT
AutoCAD SHX Text
UNION
AutoCAD SHX Text
GAS COCK
AutoCAD SHX Text
%%UGAS CONN. TO GAS UNIT
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
EXPANSION. MINIMUM
AutoCAD SHX Text
DIRT LEG, 6" LONG
AutoCAD SHX Text
AT BASE OF VERTICAL
AutoCAD SHX Text
THREE ELBOWS.
AutoCAD SHX Text 12"
AutoCAD SHX Text
MAX
AutoCAD SHX Text
%%UNOTE:
AutoCAD SHX Text
LOCATE GAS PIPING SO
AutoCAD SHX Text
AS NOT TO BLOCK
AutoCAD SHX Text
UNIT ACCESS PANELS
AutoCAD SHX Text
PACKAGED GAS/ELECTRIC ROOFTOP UNIT SCHEDULE
AutoCAD SHX Text
REQUIRED COOLING UNIT CAPACITIES ARE AT 95%%DF DB AMBIENT OAT.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MBH
AutoCAD SHX Text
MARK
AutoCAD SHX Text
TONS
AutoCAD SHX Text
NOM.
AutoCAD SHX Text
TOT
AutoCAD SHX Text
OUTPUT
AutoCAD SHX Text
AutoCAD SHX Text
COOLING
AutoCAD SHX Text
SEN
AutoCAD SHX Text
DB%%DF
AutoCAD SHX Text E.A.T.
AutoCAD SHX Text
WB%%DF
AutoCAD SHX Text
MBH
AutoCAD SHX Text
MBH
AutoCAD SHX Text
GAS HEATING
AutoCAD SHX Text
INPUT
AutoCAD SHX Text E.S.P.
AutoCAD SHX Text
IN.WC.
AutoCAD SHX Text
CFM
AutoCAD SHX Text
SUPPLY AIR FAN
AutoCAD SHX Text
OCCUPIED
AutoCAD SHX Text
OA CFM
AutoCAD SHX Text
BASIS OF DESIGN
AutoCAD SHX Text
TRANE
AutoCAD SHX Text
RTU-1
AutoCAD SHX Text
SEER/EER
AutoCAD SHX Text
MINIMUM
AutoCAD SHX Text
AutoCAD SHX Text PROVIDE (3) ION GENERATOR EQUAL TO GLOBAL PLASMA SOLUTIONS GPS-FC48-AC MOUNTED IN FAN SECTION OF UNIT.
AutoCAD SHX Text 266.9
AutoCAD SHX Text 207.5
AutoCAD SHX Text 80.0
AutoCAD SHX Text 67.0
AutoCAD SHX Text 1.0
AutoCAD SHX Text 10,000
AutoCAD SHX Text 1,250
AutoCAD SHX Text
AutoCAD SHX Text 320.0
AutoCAD SHX Text 259.0
AutoCAD SHX Text -/9.8
AutoCAD SHX Text
YSJ300
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CONDENSATE DRAIN TRAP DETAIL
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
DX COIL CONNECTION DETAIL
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text FOR ROOF MOUNTED EQUIPMENT OR DRAINS, EXTEND LINE 5'-0" FROM UNIT TOWARDS NEAREST ROOF DRAIN OR GUTTER, SEE ARCHITECTURAL. FOR INDOOR COILS, SEE PLANS FOR ROUTING
AutoCAD SHX Text
NOTE: APPLIES TO ALL COOLING COILS
AutoCAD SHX Text
UNION
AutoCAD SHX Text 4-1/2"
AutoCAD SHX Text 2-1/2"
AutoCAD SHX Text
SLOPE AS REQUIRED BY CODE
AutoCAD SHX Text
OPEN VENT, COVER TOP WITH CLOTH #3 MESH
AutoCAD SHX Text
TOP OF DRAIN PAN
AutoCAD SHX Text
COIL
AutoCAD SHX Text
DRAIN PAN
AutoCAD SHX Text 1/2"
AutoCAD SHX Text
VAPOR LINE
AutoCAD SHX Text
INSULATED
AutoCAD SHX Text
PITCH
AutoCAD SHX Text
PROVIDE DOUBLE SUCTION
AutoCAD SHX Text
EVAPORATOR COILS WHEN REQUIRED
AutoCAD SHX Text
CONDENSING UNITS LOCATED ABOVE
AutoCAD SHX Text
(OR UNLOADING SINGLE COMPRESSOR)
AutoCAD SHX Text
RISERS FOR MULTIPLE COMPRESSORS
AutoCAD SHX Text
RL
AutoCAD SHX Text
IN MANUFACTURER'S DATA
AutoCAD SHX Text
RS
AutoCAD SHX Text
PITCH
AutoCAD SHX Text
FILTER DRYER (FIELD
AutoCAD SHX Text
SUPPLIED). BI-FLOW FOR
AutoCAD SHX Text
HEAT PUMP APPLICATIONS
AutoCAD SHX Text
(FIELD SUPPLIED)
AutoCAD SHX Text
(FIELD SUPPLIED)
AutoCAD SHX Text
EXPANSION VALVE
AutoCAD SHX Text
SIGHT GLASS
AutoCAD SHX Text
SOLENOID VALVE
AutoCAD SHX Text
COIL
AutoCAD SHX Text
DX
AutoCAD SHX Text PROVIDE DUCT-MOUNTED SMOKE DETECTOR (BY DIV. 26), WIRED TO SHUT DOWN UNIT UPON DETECTION OF SMOKE. SEE PLANS FOR LOCATION.
AutoCAD SHX Text UNIT SHALL HAVE DEMAND CONTROL VENTILATION. OA DAMPER SHALL MODULATE DURING OCCUPIED TIME BASED ON SPACE CO2 SENSOR. BASE OA CFM SHALL BE 410.
AutoCAD SHX Text
HVAC LEGEND
AutoCAD SHX Text
SPEC
AutoCAD SHX Text
SPECIFICATIONS
AutoCAD SHX Text
HUMIDISTAT
AutoCAD SHX Text
SMOKE DETECTOR IN
AutoCAD SHX Text
VERTICAL DUCT
AutoCAD SHX Text
AIR FLOW DIRECTION
AutoCAD SHX Text
THERMOSTAT
AutoCAD SHX Text
MARK (SEE SCHEDULE)
AutoCAD SHX Text
AIR DISTRIBUTION DEVICE
AutoCAD SHX Text
CFM (AIR FLOW)
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text
SD
AutoCAD SHX Text
SD
AutoCAD SHX Text
SD
AutoCAD SHX Text
SD
AutoCAD SHX Text
NOT APPEAR ON DWGS.
AutoCAD SHX Text
** NOTE: ALL SYMBOLS/ABBREVIATIONS MAY
AutoCAD SHX Text
HORSEPOWER, HEAT PUMP
AutoCAD SHX Text
KILOWATT
AutoCAD SHX Text
VOLUME CONTROL DAMPER
AutoCAD SHX Text
HP
AutoCAD SHX Text
KW
AutoCAD SHX Text
VCD
AutoCAD SHX Text
CONDENSATE DRAIN
AutoCAD SHX Text
UNLESS NOTED OTHERWISE
AutoCAD SHX Text
DRY BULB
AutoCAD SHX Text
WET BULB
AutoCAD SHX Text BTU per HOUR x 1000
AutoCAD SHX Text
EXTERNAL STATIC PRESSURE
AutoCAD SHX Text
MBH
AutoCAD SHX Text
DB
AutoCAD SHX Text
WB
AutoCAD SHX Text
ESP
AutoCAD SHX Text D
AutoCAD SHX Text
UNO
AutoCAD SHX Text
LINED DUCTWORK
AutoCAD SHX Text
FIRE DAMPER IN
AutoCAD SHX Text
HORIZONTAL DUCT
AutoCAD SHX Text
SQUARE TURN WITH
AutoCAD SHX Text
VANE ELBOW
AutoCAD SHX Text
HORIZONTAL DUCT
AutoCAD SHX Text
FLEXIBLE AIR DUCT
AutoCAD SHX Text
SMOKE DAMPER IN
AutoCAD SHX Text
VERTICAL DUCT
AutoCAD SHX Text
FIRE DAMPER IN
AutoCAD SHX Text
DAMPER
AutoCAD SHX Text
DAMPER
AutoCAD SHX Text
BACKDRAFT DAMPER
AutoCAD SHX Text
VOLUME CONTROL
AutoCAD SHX Text
MOTOR OPERATED
AutoCAD SHX Text
HORIZONTAL DUCT
AutoCAD SHX Text
SMOKE DETECTOR IN
AutoCAD SHX Text
BDD
AutoCAD SHX Text
BDD
AutoCAD SHX Text M
AutoCAD SHX Text M
AutoCAD SHX Text
VCD
AutoCAD SHX Text
VCD
AutoCAD SHX Text
ABOVE CEILING
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
TIGHT TO STRUCTURE
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
DRAWING
AutoCAD SHX Text
CEILING
AutoCAD SHX Text
TYP
AutoCAD SHX Text
DWG
AutoCAD SHX Text
CLG
AutoCAD SHX Text
TTS
AutoCAD SHX Text
AFF
AutoCAD SHX Text A/C
AutoCAD SHX Text
INCHES OF WATER COLUMN
AutoCAD SHX Text
TRANSFER DUCT
AutoCAD SHX Text
CUBIC FEET PER MINUTE
AutoCAD SHX Text
OUTSIDE AIR
AutoCAD SHX Text
RETURN AIR
AutoCAD SHX Text
SUPPLY AIR
AutoCAD SHX Text
OA
AutoCAD SHX Text
TD
AutoCAD SHX Text
RA
AutoCAD SHX Text
SA
AutoCAD SHX Text
IN.WC.
AutoCAD SHX Text
ABBREVIATIONS
AutoCAD SHX Text
CFM
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
HVAC DUCT SYMBOLS
AutoCAD SHX Text
DROP
AutoCAD SHX Text
RISE
AutoCAD SHX Text
SPLITTER DAMPER
AutoCAD SHX Text
DUCT TURN WITH
AutoCAD SHX Text
RADIUS ELBOW
AutoCAD SHX Text
DUCT SIZE TRANSITION
AutoCAD SHX Text
END OF DUCT RUN
AutoCAD SHX Text R
AutoCAD SHX Text
SD
AutoCAD SHX Text
SD
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text 12x6
AutoCAD SHX Text 12x6
AutoCAD SHX Text
SINGLE
AutoCAD SHX Text
LINE
AutoCAD SHX Text
DOUBLE
AutoCAD SHX Text
LINE
AutoCAD SHX Text
OF AIR FLOW
AutoCAD SHX Text
IN DIRECTION
AutoCAD SHX Text
(RETURN OR EXHAUST)
AutoCAD SHX Text
DUCT TURNED DOWN
AutoCAD SHX Text
(RETURN OR EXHAUST)
AutoCAD SHX Text
DUCT TURNED DOWN
AutoCAD SHX Text
(SUPPLY OR DISCHARGE)
AutoCAD SHX Text
DUCT TURNED UP
AutoCAD SHX Text
DUCT TURNED UP
AutoCAD SHX Text
(SUPPLY OR DISCHARGE)
AutoCAD SHX Text DUCT (WIDTH x DEPTH)
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
AutoCAD SHX Text
INTERLOCK WITH
AutoCAD SHX Text INw
AutoCAD SHX Text
FIRE-RATED DOOR LOUVER
AutoCAD SHX Text
FDL
AutoCAD SHX Text
FAN COIL UNIT
AutoCAD SHX Text
FCU
AutoCAD SHX Text
ELECTRIC UNIT HEATER
AutoCAD SHX Text
EUH
AutoCAD SHX Text
ELECTRIC CEILING HEATER
AutoCAD SHX Text
ECH
AutoCAD SHX Text
ELECTRIC WALL HEATER
AutoCAD SHX Text
EWH
AutoCAD SHX Text
ENERGY RECOVERY VENTILATOR
AutoCAD SHX Text
ERV
AutoCAD SHX Text
IN JOIST SPACE
AutoCAD SHX Text
IJS
AutoCAD SHX Text
THRU JOIST WEBS
AutoCAD SHX Text
TJW
AutoCAD SHX Text
SMK
AutoCAD SHX Text
SMK
AutoCAD SHX Text
%%US-1
AutoCAD SHX Text
AutoCAD SHX Text
TC
AutoCAD SHX Text
TC
AutoCAD SHX Text
TIME CLOCK
AutoCAD SHX Text
E=EXHAUST AIR; R=RETURN AIR; TA=TRANSFER AIR.
AutoCAD SHX Text PROVIDE ALUMINUM DEVICES (INCLUDING DAMPERS) FOR "WET" ROOMS (TOILETS, LOCKERS, SHOWERS, ETC.)
AutoCAD SHX Text PROVIDE FULL-FACE DEVICES ONLY; PANEL-MOUNTED WILL NOT BE ACCEPTED FOR ANY DEVICES.
AutoCAD SHX Text
ALL DEVICES SHALL BE FACTORY PAINTED POWDER COAT B12 WHITE, U.N.O.
AutoCAD SHX Text
ALL OPPOSED BLADE DAMPERS SHALL BE FACTORY PAINTED BLACK.
AutoCAD SHX Text ALL CEILING-MOUNTED SUPPLY DIFFUSERS SHALL BE 4-WAY (FIELD ADJUSTABLE) DISCHARGE, UNLESS NOTED OTHERWISE.
AutoCAD SHX Text ALL DEVICES SPECIFIED AS ADJUSTABLE, SHALL BE ADJUSTABLE WITHOUT USING SPECIAL TOOLS.
AutoCAD SHX Text
SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
AutoCAD SHX Text
NOTES:
AutoCAD SHX Text 8.
AutoCAD SHX Text 1.
AutoCAD SHX Text 2.
AutoCAD SHX Text 3.
AutoCAD SHX Text 4.
AutoCAD SHX Text 5.
AutoCAD SHX Text 6.
AutoCAD SHX Text 7.
AutoCAD SHX Text
DIFFUSERS, REGISTERS, AND GRILLES
AutoCAD SHX Text
HEAVY-DUTY ALUMINUM BAR RETURN AIR GRILLE
AutoCAD SHX Text
CORE BLADES SHALL BE HELD BY MANDREL TUBES NOT TO EXCEED 12" ON CENTER.
AutoCAD SHX Text
1/2" BLADE SPACING, O° DEFLECTION, PARALLEL TO LONG/HORIZONTAL DIMENSION.
AutoCAD SHX Text
SURFACE-MOUNT ALUMINUM BORDER SHALL BE CONTINUOUSLY WELDED.
AutoCAD SHX Text
PRICE SERIES 97 OR APPROVED PRODUCT.
AutoCAD SHX Text
SIZE SHOWN ON DWGS
AutoCAD SHX Text
NECK SIZE
AutoCAD SHX Text R-1
AutoCAD SHX Text
MARK
AutoCAD SHX Text
RELOCATE EXISTING
AutoCAD SHX Text
READJUST TO NEW AIR QUANTITY
AutoCAD SHX Text Rxxx
AutoCAD SHX Text R
AutoCAD SHX Text
AC DEMOLITION LEGEND
AutoCAD SHX Text
EXISTING TO REMAIN
AutoCAD SHX Text
EXISTING TO BE REMOVED
AutoCAD SHX Text
CAP EXISTING AND REMOVE
AutoCAD SHX Text
CONNECT NEW TO EXISTING
AutoCAD SHX Text
NEW WORK
AutoCAD SHX Text
CAP
AutoCAD SHX Text C
AutoCAD SHX Text
SYMBOL
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
MARK
AutoCAD SHX Text
SONES
AutoCAD SHX Text
FAN DATA
AutoCAD SHX Text E.S.P.
AutoCAD SHX Text
IN.WC.
AutoCAD SHX Text
CFM
AutoCAD SHX Text
MAX
AutoCAD SHX Text
WATTS
AutoCAD SHX Text
RPM
AutoCAD SHX Text
FAN SCHEDULE
AutoCAD SHX Text
DRIVE
AutoCAD SHX Text
BASIS OF DESIGN
AutoCAD SHX Text
FAN TYPE
AutoCAD SHX Text
GREENHECK U.N.O.
AutoCAD SHX Text
EF-1
AutoCAD SHX Text
SP-B150
AutoCAD SHX Text
DIRECT
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1.0
AutoCAD SHX Text 0.25
AutoCAD SHX Text
AutoCAD SHX Text
CONTROL
AutoCAD SHX Text
CEILING EXHAUST FAN
AutoCAD SHX Text
LIGHTING
AutoCAD SHX Text
EF-2
AutoCAD SHX Text
SP-B150
AutoCAD SHX Text
DIRECT
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1.0
AutoCAD SHX Text 0.25
AutoCAD SHX Text
AutoCAD SHX Text
CEILING EXHAUST FAN
AutoCAD SHX Text
LIGHTING
AutoCAD SHX Text
SIDE ENTRY ROOF PIPE CURB DETAIL
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
FLASHING AND COUNTER- FLASHING
AutoCAD SHX Text
12" HIGH INSULATED ROOF CURB
AutoCAD SHX Text
REMOVABLE GALVANIZED COVER
AutoCAD SHX Text INSULATED (1-1/2" RIGID FIBERGLASS) SIDE ENTRY ROOF BOX PERMANENTLY ATTACHED TO ROOF CURB. SIZE AS REQUIRED FOR UTILITIES. ALL SEAMS WELDED WITH FULL MITERED CORNERS, PROVIDE PRESSURE TREATED WOOD NAILER STRIP
AutoCAD SHX Text
SEAL PENETRATIONS WATER-TIGHT USING SIGRIST EXIT SEALS BY ALTA PRODUCTS
AutoCAD SHX Text
MAINTAIN 6" MINIMUM CLEAR ON BOTH ENDS OF UNIT.
AutoCAD SHX Text
INDOOR UNIT DETAIL - CMU WALL
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
DUCTLESS MINI-SPLIT SYSTEM HIGH-SIDEWALL
AutoCAD SHX Text
CMU WALL
AutoCAD SHX Text HIGH-SIDEWALL FAN-COIL UNIT. MOUNT IN STRICT COMPLIANCE WITH ALL MANUFACTURER REQUIREMENTS.
AutoCAD SHX Text ALL PIPING AND WIRING SHALL BE PIPING AND WIRING SHALL BE RUN INSIDE FIELD-FABICATED, INSIDE FIELD-FABICATED, PAINTED, SHEET METAL ENCLOSURE, AND EXTENDED TO SPACE ABOVE CEILING FOR ROUTING (SEE DRAWINGS FOR CONTINUATION.).
AutoCAD SHX Text PROVIDE OPTIONAL, SURFACE- MOUNTED, EXTERNAL-TYPE, LITTLE GIANT EC-OP-K (OR APPROVED EQUIVALENT PRODUCT) CONDENSATE PUMP. 1.2 GPH @ 20' DISCHARGE HEAD, 230v, w/ WALL-MOUNTING BRACKET & COVER. WIRE THRU UNIT.
AutoCAD SHX Text
HARD-WIRED, WALL-MOUNTED CONTROLLER/THERMOSTAT. 4'-0" A.F.F.
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text
SIDE VIEW
AutoCAD SHX Text
FRONT VIEW
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text
PIPING SUPPORT DETAILS
AutoCAD SHX Text
%%UTWO ROD ROLLER HANGER
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
%%UGANG HANGER
AutoCAD SHX Text
REQUIRED)
AutoCAD SHX Text
INSULATION (AS
AutoCAD SHX Text
INSERTS.
AutoCAD SHX Text
INSULATION (AS
AutoCAD SHX Text
HANGER MAY TOUCH PIPE.
AutoCAD SHX Text
COPPER PIPE SHALL BE
AutoCAD SHX Text
COPPER OR HAVE COPPER
AutoCAD SHX Text
HANGERS IN CONTACT W/
AutoCAD SHX Text
14 GAUGE SHIELD
AutoCAD SHX Text
REQUIRED)
AutoCAD SHX Text
INSULATED PIPING PROTECTION DETAILS
AutoCAD SHX Text
NOTES:
AutoCAD SHX Text
NOTE: TO BE USED
AutoCAD SHX Text
AND INCLUDING 4"
AutoCAD SHX Text
FOR PIPING UP TO
AutoCAD SHX Text
PROVIDE CLEVIS
AutoCAD SHX Text
HANGER ROD (TYP)
AutoCAD SHX Text
FOR COLD PIPE
AutoCAD SHX Text
%%UCLEVIS HANGER
AutoCAD SHX Text
DETAILS (TYP)
AutoCAD SHX Text
SEE PROTECTION
AutoCAD SHX Text
FOR INSULATED PIPE
AutoCAD SHX Text
BARE PIPE
AutoCAD SHX Text
AROUND PIPE
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
DETAIL
AutoCAD SHX Text
SEE PIPING PROTECTION
AutoCAD SHX Text
INSULATION (AS REQ'D)
AutoCAD SHX Text
%%UHOT
AutoCAD SHX Text
%%UCOLD
AutoCAD SHX Text
%%UPIPING
AutoCAD SHX Text
%%UPIPING
AutoCAD SHX Text
%%USPLIT RING HANGER
AutoCAD SHX Text
1. VAPOR BARRIER TO BE CONTINUOUS AT ALL JOINTS.
AutoCAD SHX Text
2. DETAIL SIMILAR FOR PIPES SUPPORTED FROM WALLS.
AutoCAD SHX Text
MARK
AutoCAD SHX Text
TONS
AutoCAD SHX Text 3/4
AutoCAD SHX Text
SEER
AutoCAD SHX Text
NOM.
AutoCAD SHX Text
DUCTLESS SPLIT-SYSTEM HEAT PUMP SCHEDULE
AutoCAD SHX Text
EAT
AutoCAD SHX Text
MBH
AutoCAD SHX Text
SEN
AutoCAD SHX Text
TOT
AutoCAD SHX Text
AutoCAD SHX Text
DB
AutoCAD SHX Text
COOLING *
AutoCAD SHX Text
WB
AutoCAD SHX Text
AutoCAD SHX Text
MITSUBISHI
AutoCAD SHX Text
INDOOR
AutoCAD SHX Text
BASIS FOR DESIGN
AutoCAD SHX Text
CFM
AutoCAD SHX Text
INDOOR UNIT
AutoCAD SHX Text
OUTDOOR
AutoCAD SHX Text
HEATING **
AutoCAD SHX Text
REV. CYCLE
AutoCAD SHX Text 10.9
AutoCAD SHX Text
MBH
AutoCAD SHX Text
HSPF
AutoCAD SHX Text
** REVERSE CYCLE HEATING & COP IS AT AHRI HIGH TEMPERATURE.
AutoCAD SHX Text
* REQUIRED COOLING - UNIT CAPACITIES ARE AT 95%%DF DB AMBIENT OAT.
AutoCAD SHX Text
AutoCAD SHX Text 12.8
AutoCAD SHX Text 6.7
AutoCAD SHX Text 9.0
AutoCAD SHX Text 24.6
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
MSZ-GL09NA
AutoCAD SHX Text
MUZ-GL09NA
AutoCAD SHX Text
AutoCAD SHX Text
NOTE: PROVIDE INTERFACE TO ALLOW CONTROL OF UNITS THROUGH EXISTING CONTROLS.
AutoCAD SHX Text
AC/HP-1 THRU 7
AutoCAD SHX Text
HIGH SIDEWALL
GYMNASIUM
A���
STOR.
A���
STOR.
A���
STOR.
A���
STOR.
A���
STOR.
A���
STOR.
A���
STOR.
A���
STOR.
A���
STOR.
A���
ENTRANCE
CORRIDOR
A���
BOYS RR
A���
GIRL RR
A���
M1.1
HVAC FLOOR
PLAN AND ROOF
PLAN
1/8" = 1'-0"M1.1
1 HVAC FLOOR PLAN
1/8" = 1'-0"M1.1
2 HVAC ROOF PLAN
DATE
PROJECT NO.
/2
7/
:1 8:
P
M
O
LD
H W
Y
0, T
A
LL
A
PO
O
SA
, G A
W
ES
T H
A R
A
LS
O N
E
LE
M
EN
TA
R
Y
SC
H O
O L
G
YM
N A
SI
U
M M
O D
IF
IC
A
TI
O N
01/04/2023
22130
H
AR
AL
SO
N C
O U
N
TY
S C
H O
O
LS
(F
AC
IL
IT
Y C
O D
E:
-4
0)
NO DESCRI3TION DATE
M E
C H
A N
IC
A
L
EN
G
IN
EE
RS
, I
NC
Bi sh op
S tre et
Su ite
E -2
At la nt a, G a
| 4
-3
-0
01-04-2023
GEORG I A
REGI STERED
No. 22997
PROFESSIONAL
E NG I N E E R
JEFFREY L . LEE
AutoCAD SHX Text
%%URTU-1
AutoCAD SHX Text
%%URTU-1
AutoCAD SHX Text
%%UHP-1
AutoCAD SHX Text
%%UHP-2
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
%%UAC-4
AutoCAD SHX Text
%%UAC-3
AutoCAD SHX Text
%%UAC-1
AutoCAD SHX Text
%%UAC-2
AutoCAD SHX Text
AutoCAD SHX Text NEW 25-TON PACKAGED GAS/ELECTRIC ROOFTOP UNIT. MOUNT ON LOW ROOF ON NEW ROOF CURB. 34x34 INTERNALLY LINED SA DUCT RISE TIGHT TO WALL. UTILIZE EXISTING EXHAUST FAN OPENING FOR NEW PENETRATION. PATCH UNUSED PORTION TO MATCH EXISTING. TRANSITION FLAT ON BOTTOM FROM UNIT RA INTAKE TO 48x48 RETURN GRILLE.. FLASH AND COUNTERFLASH DUCT PENETRATION. R-1 RETURN GRILLE. BOTTOM OF GRILLE ±20" ABOVE LOW ROOF.ALL EXPOSED DUCTWORK TO BE INTERNALLY LINED WITH EXTERNAL DUCT CLADDING. SEE SPECIFICATIONS. REMOVE EXISTING EXHAUST FAN. OPENING TO BE UTILIZED FOR NEW DUCT PENETRATION. PATCH UNUSED PORTION TO MATCH EXISTING. NEW DUCTLESS SPLIT-SYSTEM HIGH SIDEWALL INDOOR UNIT. SEE THIS SHEET FOR DETAIL. NOT USED. NOT USED. 1"D THRU EXTERIOR WALL. ROUTE AND TIE-INTO NEAREST DOWNSPOUT. REMOVE EXISTING GAS UNIT HEATER, CONTROLS, AND FLUE. PATCH ROOF TO MATCH EXISTING. REMOVE EXISTING ABANDONED FLUE. PATCH ROOF TO MATCH EXISTING. NEW DUCTLESS SPLIT-SYSTEM OUTDOOR HEAT PUMP. PROVIDE WALL BRACKET AND MOUNT ON EXTERIOR WALL. REF. LINES UP TIGHT TO WALL. PROVIDE LINESET COVER AND PAINT TO MATCH EXISTING WALL. NEW CEILING EXHAUST FAN. PROVIDE NEW 8" ROUND EXH. DUCT UP THRU ROOF WITH CAP. IF THERE IS AN EXISTING GRAVITY ROOF VENT, 8" MAY BE CONNECTED TO EXISTING.3/4"D ROUTE TO EXTERIOR WALL AND TIE-INTO NEAREST DOWNSPOUT. 1"D ROUTE TO EXTERIOR WALL AND TIE-INTO NEAREST DOWNSPOUT. CONNECT NEW 1-1/4"G AT METER AND ROUTE ON LOW ROOF TO NEW UNIT. CONNECT TO UNIT WITH UNION, GAS COCK, AND DIRT LEG, SEE SHEET M1.0 FOR DETAIL. REMOVE OR ABANDON EXISTING GAS BELOW GRADE PAST POINT OF NEW CONNECTION. REMOVE OR ABANDON ALL EXISTING GAS PIPING INSIDE BUILDING. REMOVE EXISTING INTAKE LOUVER. PATCH OPENING TO MATCH EXISTING.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
%%UKEY NOTES:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FABRIC DUCT, TYPICAL. ROUTE TIGHT TO STRUCTURE. SEE SPECIFICATIONS.
AutoCAD SHX Text
FABRIC DUCT, TYPICAL. ROUTE TIGHT TO STRUCTURE. SEE SPECIFICATIONS.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 3/4"D
AutoCAD SHX Text 3/4"D
AutoCAD SHX Text 3/4"D
AutoCAD SHX Text 3/4"D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
%%UEF-2
AutoCAD SHX Text
%%UEF-1
AutoCAD SHX Text
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text
CO
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text T
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
%%UAC-5
AutoCAD SHX Text
%%UAC-6
AutoCAD SHX Text
%%UAC-7
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
%%UHP-7
AutoCAD SHX Text
%%UHP-5
AutoCAD SHX Text
%%UHP-6
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 3/4"D
AutoCAD SHX Text 3/4"D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 34x34
AutoCAD SHX Text 1-1/4"G
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
%%UHP-3
AutoCAD SHX Text
%%UHP-4
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SD
DATE
PROJECT NO.
W es t H ar al so n El em S ch oo l G ym
M od ifi ca tio ns
NO DESCRIPTION DATE
01/04/2023
22130
JK
M
-1 07G
R
IF
F
IN
, G E
O R
G
IA
T
E L
E P
H O
N E
-2
-8
O 'D
E L
L R
O A
D S
U
IT
E
M A
T H
IS
C
O N
S U
L T
I N
G E
N G
I N
E E
R S
O
LD
H W
Y
0, T
A
LL
A
PO
O
SA
, G A
W
ES
T H
A R
A
LS
O N
E
LE
M
EN
TA
R
Y
SC
H O
O L
G
YM
N A
SI
U
M M
O D
IF
IC
A
TI
O N
H
AR
AL
SO
N C
O U
N
TY
S C
H O
O
LS
(F
AC
IL
IT
Y C
O D
E:
-4
0)
E0.1
SYMBOL LEGEND,
GENERAL NOTES,
PANELBOARD
SCHEDULES, &
RISER DIAGRAM
1/4" / 1'-0"1/4" / 1'-0"
4"
1' -0
4"
1'
-0
DATE
PROJECT NO.
W es t H ar al so n El em S ch oo l G ym
M od ifi ca tio ns
NO DESCRIPTION DATE
01/04/2023
22130
JK
M
-1 07G
R
IF
F
IN
, G E
O R
G
IA
T
E L
E P
H O
N E
-2
-8
O 'D
E L
L R
O A
D S
U
IT
E
M A
T H
IS
C
O N
S U
L T
I N
G E
N G
I N
E E
R S
O
LD
H W
Y
0, T
A
LL
A
PO
O
SA
, G A
W
ES
T H
A R
A
LS
O N
E
LE
M
EN
TA
R
Y
SC
H O
O L
G
YM
N A
SI
U
M M
O D
IF
IC
A
TI
O N
H
AR
AL
SO
N C
O U
N
TY
S C
H O
O
LS
(F
AC
IL
IT
Y C
O D
E:
-4
0)
E1.1
FLOOR PLANS -
ELECTRICAL
| 00 22130 G0.0 |
| Sheets |
| G0.0 - COVER |
| 01 22130 A1.0 |
| Sheets |
| A1.0 - OVERALL PLAN, FLOOR PLAN, ROOF PLAN, AND DETAIL |
| 02 22130 S1.1 |
| Sheets |
| S1.1 - GENERAL NOTES, ROOF FRAMING PLAN, SECTIONS AND DETAILS |
| 03 22130 M1.0 |
| Sheets and Views |
| M1.0 |
| 03 22130 M1.1 |
| Sheets and Views |
| M1.1 |
| 04 22130 E0.1 |
| 04 22130 E1.1 |
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .