Attachment 11- Historic ESS Maintenance Tracker.xlsx

XLSX spreadsheet 31 KB Posted

Attached to
Electronic Security System (ESS) Maintenance and Service- Amend 0001
Solicitation number
W91QF426RA010
Issued by

About this file

This is a historical maintenance tracker for Electronic Security Systems (ESS), Intrusion Detection Systems (IDS), and Closed-Circuit Television (CCTV) systems documenting support activities from March 2023 through March 2026 across multiple Fort Leavenworth facilities. The tracker records 200+ service incidents including motion sensor replacements, system reconfigurations, panel resets, reader troubleshooting, battery replacements, wiring repairs, and software updates. Notable major projects include the migration of access control systems from Lenel to C-Cure platforms at multiple locations (Headquarters 1 and 2, Joint Facility 1), implementation of two-factor authentication, VLAN reconfiguration for 14 cameras and 5 IDS panels, elevator access reconfiguration for restricted sections, and emergency lockdown system programming and testing. The tracker reflects ongoing operational maintenance with common issues including nuisance motion sensor alarms (requiring multiple replacement cycles), loss of communications following power outages, battery failures, card reader malfunctions, lock solenoid failures, and software synchronization problems between panels and servers.

The document demonstrates the scope and complexity of ESS/IDS/CCTV maintenance operations at Fort Leavenworth, recording labor hours expended per incident and noting coordination with contractors, physical security offices, IT departments, and external vendors such as C-Cure, NEC, and DPW. Critical system failures documented include extended downtime at University Campus facilities with database corruption issues requiring rewiring of multiple readers and server repairs, communications failures at Joint Facility 1 requiring AES radio backup diagnostics, and weather-related power outages causing widespread panel offline conditions across multiple installations. The tracker serves as a record of 200+ discrete maintenance activities supporting continuous operation of security infrastructure across garrison buildings and specialized facilities including SCIFs, training centers, dog facilities, and mission-critical spaces.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ESS_IDS

Electronic Security / IDS / CCTV Support Provided
DateHoursESS/IDS/CCTVRequesting OrganizationISSUEWork PerformedNotes
3/24/2310IDSJOINT FACILITY 1Requested support to replace existing motion sensorsMotion Sensors Replaced and testedMonitoring for reduction of nuisance alarms.
4/4/235IDSGarrisonAlarm Receivers throwing hardware substitution errors.Researched the codes being generated. Identified a corrective action and effected a fix with the permission of Garrison PS office.
4/5/231IDSJOINT FACILITY 2Keypad Beeping - No notification from DispatchResponded to facility and corrected system trouble.
5/19/232IDSGarrisonInvalid Account NumberIdentified incorrect account number coming from LRC facility. Notified Garrison PS office. At request of the PS office, attempted to gain access to the facility on 2 separate occations. LRC was not able to get someone to open the facility. Notified PS.
6/2/233IDSGarrisonCentral Station AssessmentAssessed System V Receiver, retrieved IP & MAC Addresses, Downloaded and reviewed setup information.Need Garrison IMO to install software on Server to allow management of System V Reciever. Then it can be configured to go online.
6/23/234CCTVHEADQUARTERS 1Reprogramming Cameras for VLANReprogrammed 14 Cameras to new security VLANCoordinated with NEC and reprogrammed Cameras within CAC for new VLAN.
6/23/232IDSHEADQUARTERS 1Reprogramming IDS for VLANReprogrammed 5 IDS Panels for new security VLANCoordinated with NEC and reprogrammed IDS within CAC for new VLAN.
7/7/234ESSMISSION TRAININGCard Readers not workingReset Readers in Building 46, & 61Showed Security Manager how to reset power/readers on panel.
5/30/233IDSDOG FACILITYIDS at MWD Explosives BunkerIdentified issue (power outage) and contacted DPW for repair. Performed system test after power restored.
7/11/232IDSHEADQUARTERS 1IDS in CAC HQ downCommunications Board needed to be reset after power outage. Reset DATE/TIME. Conducted System Test.
7/14/233IDS/FIREGarrisonLoss of communications IDS & FireFound communication loss with some Fire and Security Systems. Reported to PS Office and assisted in diagnosing cause so Garrison could fix the issue.Issues with notification to end users with dispatch addressed again.
7/18/2315ESSHEADQUARTERS 1Reconfigure Elevator Access to lock G3 SectionReprogrammed Elevator setup in C-Cure server, assisted the elevator contractor in tracing and connecting output wiring. Completed Programming and set up all G3 personnel Access CredentialsCost savings is based on estimate provided by C-Cure Contractor to perform work described.
8/2/231ESSSIM 2Loss of communication ESS PanelReset Panelafter power outage
8/3/232ESSMISSION TRAININGESS system locked upReset power and identified issue with batteriesafter power outage
8/4/231ESSSIM 2Loss of communication ESS PanelReset Panelafter power outage
8/4/231ESSUNIVERSITY CAMPUSContractor having problems getting new card readers to read CAC.Pulled CHUID info from Post C-Cure and sent to SSO
8/11/236IDSFCOESystem Design / Cost Estimate BarracksDesigned a minimal solution and IGCE for FCOE to assist with budgeting estimate for the Safe & Secure initiative
8/22/232ESSMISSION TRAININGSome Cards Not ReadingFound that new cards are reading differently in Bridgepoint Readers. Trained security personnel in identifying proper ID numbers to input in C-Cure.
8/22/231ESSSIM 2Loss of communication ESS PanelReset Panel
8/28/235ESSUNIVERSITY CAMPUSContractor having problems getting new card readers to read CAC.Worked with contractor to identify proper data format and input CHUID in C-Cure system.
8/30/232ESSFMPCNew users not able to access CAAPanel was offline. Reset and tested system
9/11/232IDSDOG FACILITYSystem not communicatingCoordinated with PS to get power restored to the bunkerFuse in the transformer blown. No one notified of power outage on 9 Sept. Was not repaired until reported on Monday and contractor dispatched to fix power.
9/18/231ESSSIM 1Readers not working on a couple doors.Reset Front Door Reader. Checked 2 others.Found front door reader needed to be power cycled and possibly an issue with the tamper switch. Other readers are fine. Some CAC cards are not working wirelessly. Contact card works.
9/19/232ESSSIM 12 Readers need to be moved due to construction.Moved 2 readers up to make room for wall panels.
10/5/231ESSMISSION TRAININGBad BatteriesProvided instruction to MCTP Security Manager on the correct procedures to verify and replace backup batteries.
10/17/231IDSHEADQUARTERS 1Loss of CommunicationRestarted Panel due to network issue.
10/17/232IDS/ESSUNIVERSITY CAMPUSLoss of Communication /Access ControlRestarted Panel due to network issue. Configured new prox cards for personnel
10/17/231IDSHEADQUARTERS 1Loss of CommunicationRestarted Panel due to network issue.
10/17/231ESSSIM 2Panel Loss of CommunicationRestarted Panel due to network issue.
11/8/234ESST2COM TRAININGPanel Loss of CommunicationReinstalled software, reconfigured/reset panel to factory, multiple attempt to restore communications.Still not working
11/9/233ESST2COM TRAININGPanel Loss of CommunicationReinstalled software, reconfigured/reset panel to factory, multiple attempt to restore communications.Still not working. Recommended getting Vendor in to repair system. Vendor came out and found the version of software needed patching as well. All working as of 19 Dec 2023.
12/13/234IDSJOINT FACILITY 1 & 2NUISANCE ALARMSReplaced motion sensors on 2nd and 3rd floor (6 devices).
12/19/232IDSJOINT FACILITY 2NUISANCE ALARMSReplaced additional motion sensor and traced room 305 (actually room 303)
1/23/241IDSGarrisonPMI and Functional TestChecked system power and batteries, Updated Keypad Labels and performed full functional test of the system.
1/29/242.5ESSMISSION TRAININGReader on Rm 206 not accepting PINsDisassembled and cleaned reader. Swapped with reader from security office.Buttons 5 & 6 not consistency working. Attempted to clean contacts multiple times. Some succes but only worked for a few button presses. Ended up swapping readers from another room.
1/30/241IDSHEADQUARTERS 1System Trouble CG's Office AlarmRestarted panel (power down/up)
1/30/242.5IDSHEADQUARTERS 1B322 System TroubleReset Panel & tested. Had to go to DES Dispatch to verify due to lack of access to the Central Station Software
2/1/241IDSHEADQUARTERS 1CG's Office sending frequent trouble alarms.
2/6/241IDSHEADQUARTERS 1System Trouble CG's Office AlarmReplaced batteries and checked system voltagesMay need to run line to connect 4th floor keypad to 3rd floor power supply.
2/6/243ESSSIM 1 / SIM 2Implement 2 Factor AuthenticationReprogrammed 6 card readers at B45 and B73
2/12/242ESSMISSION TRAININGProblems with the unlock scheduleFound an old trigger that caused the unlock schedule to not work correctly. Also powered down the old IDS in B196.
2/20/242ESSSHARPAccess Control not working on OSAFound that several readers were affected. Identified shorted wire at a door that was being worked on by a contractor the cause.Was able to isolate the problem and get the system functional again.
2/20/242.5IDSSIM 1NUISANCE ALARMSTracked down the correct device and replaced with a used motion pulled from B48.Recommend replacement of all motion sensors in the facility.
2/23/241ESSSHARP AcademyPanel Loss of CommunicationReset Panel and checked system
2/23/241IDSDOG FACILITYPanel Loss of CommunicationReplaced backup battery
3/8/241IDSHEADQUARTERS 1Troubles showing on main system supporting Secure Comms RoomReplaced batteries in main panel and sub panel (Command Conf Room).
3/8/241ESSSIM 1Main doors won't lockFuse blown on power supply. Swapped with unused output.
3/11/243ESSMISSION TRAININGREX not functioning properly on new OSA.Met with contractor and provided verification of C-Cure status to assist in troubleshooting.Issue was unusual. Solution was to change wiring on resistor pack to 1K ohms and connect in series between REX and panel. Then set the supervision for 1K/2K NC. This resolved the problem.
3/13/243IDSSIM 1SCIF Nuisance AlarmsMoved 1 motion and bypassed the other until replacement devices are received.
3/19/241ESSCOMMAND EXCELLENCE 2Card Reader Won't Accept PINFound one button stuck under the lip of the face plate. Adjusted and tested the buttons.
3/21/241ESSHEADQUARTERS 1Card Reader not reading CAC CardsReader bad. Swapped with reader from door not being used.
3/22/241ESSSIM 2Panel Loss of CommunicationReset the panel
3/27/243ESSSIM 1System DownStarted Process to rebuild the server and install the software.
3/27/242IDSJOINT FACILITY 2Defective Motion SensorsCompleted replacing remaining motion sensors.
3/28/241ESSCTCDPanel Loss of CommunicationReset panel and diconnected batteries (they were dead and not taking a charge)
3/28/241IDSHEADQUARTERS 1Duress Button disabledReplaced battery and checked system
4/2/245IDSJOINT FACILITY 2Replaced Remaining Motion SensorsAll motions now Bravo 5 (360)
4/5/241ESSSIM 1Reader not workingSwapped with a known good. Reader was bad.
4/5/243IDSSIM 1Motion Sensor ReplacementAll motions now Bravo 5 (360) and zone labels updated
5/13/243ESSSIM 1Access Control SystemVerified licensing issue and requested new license from SWH. New license received and tested. Working.
5/14/243ESSSIM 1Access Control SystemStarted system configuration and traced out locks & door switches.
5/14/241ESSSIM 1South Entrance door reader not working.Tested and determined device was bad. Replaced with a spare onsite. Resolved the issue.
5/15/244ESSSIM 1Access Control SystemFinished system configuration, created doors, clearances and personnel. Tested system functions (minor corrections completed). System now functional. Provided initial training to SCIF personnel.
5/21/242ESSSIM 1Access Control SystemReaders reconfigured to send PIN to panel. Adjusted some programming and did additional training with the end users.
5/22/241IDSDOG FACILITYIDS Loss of communicationReset System and verified communication restored
5/23/242IDST2COM TRAININGIDS Loss of communicationReset System and verified communication restoredAfter hours call. Customer called dispatch due to trouble light. Was told all o.k. Then Ernest Called me to notify of comms fail about 30 minutes later. Had to come in to reset panel before long weekend.
5/28/241IDSSIM 2IDS Loss of communicationReset System and verified communication restored
5/28/241IDSSIM 1IDS Loss of communicationReset System and verified communication restored
5/28/241IDSCOMMAND EXCELLENCE 1IDS Loss of communicationReset System and verified communication restored
5/28/241.5ESSCOMMAND EXCELLENCE 2Access Control Panel OfflineReset System and verified communication restored12v18AH Battery ruptured and not fuctional. Replaced with 12v7AH. Trouble getting access to NEC room required 2nd trip.
5/28/241IDSUNIVERSITY CAMPUSIDS Loss of communicationReset System and verified communication restored
5/28/241IDSRESIDENCESystem TroublesLow Battery on 2 Glassbreaks and 1 door. Only able to replace batteries on Glassbreaks.
5/29/242ESSMISSION TRAININGADA Door not workingTroubleshot power supplies, system function and found the ADA Door Opener had power disabled.
5/30/241IDSDOG FACILITYIDS Loss of communicationReset System and verified communication restored
5/31/241IDSJOINT FACILITY 2IDS Loss of communicationReset System and verified communication restoredDES did not notify premises. Call came from Ernest.
6/10/241IDSSIM 1Entry Delay Not WorkingRe-aligned BMSDoor had been worked on by contractor - affected alignment.
6/20/243IDSSIM 2System TroublesReplaced batteries on 73B and reprogrammed communicators on 73A & 73B.
6/21/241IDSSIM 2Network TroubleVerified programming & switched RX1 & RX2 back.
6/24/241ESSCOMMAND EXCELLENCE 2Reported that doors did not lock on weekend.Checked system history & programming, no issues. Went to site and checked lock function. All o.k. Had the end user manually lock the door in C-Cure. Lock functioning o.k. Found that the door handle had been unlocked. Notified end user who is locating the key to lock the door.
6/24/241IDSJOINT FACILITY 1Network TroubleBad network cable. IT will replace cable.
7/15/241ESSMISSION TRAININGADA Door not workingFound that door was pushing on the lock. Adjusted the strike out so the door latch would no put pressure on it. Appears to be working now.
7/15/241IDST2COM TRAININGMotion Nuisance AlarmsReplaced 2 motion sensors
7/15/241.5ESSJOINT FACILITY 2Main door not workingChecked / swapped reader, reset panel, restarted computer. After eliminating other options, reviewed the programming. Found the door configuration was missing. It was deleted over the weekend. Likely and accident by new personnel working in the security office. Reconfigured the door. Now working.
7/23/242ESSSIM 2First Floor A Wing door not unlocking properly.Verified activity in C-Cure. Went to site and troubleshot the door. Verified voltage to lock (panic latch retraction) for duration of unlock time. Lock would retract for a fraction of a second then relock. Appears to be a bad solinoid. Unable to repair. Advised security manager to submit a service request to an authorized vendor to get it repaired.
7/29/242IDSSIM 2IDS showing comms trouble.Attempted to reprogram and reset panel. Additional work needed.
7/30/241IDSSIM 2IDS showing comms trouble.Performed additional programming and testing. Problem appears to be corrected.
8/21/242ESSMISSION TRAININGMain entrance won't lock.Pulled cover for panic bar. Found the latch bolt spring was broken. Referred back to DPW.Came in from telework day.
9/6/241ESSSIM 2First Floor A Wing iSTAR offline.
9/12/241ESSSIM 2iSTAR offlineReset panel.
9/30/242ESST2COM TRAININGVerify Preventative Maintenance and Provided SSR some training
10/1/242ESSSIM 1Lobby door not locking properly.Found duplicate schedule/event that was interfering with locking procedure. Removed duplicate event.
10/15/241IDSDOG FACILITYIP Communicator not workingReset communicator and verified function.
10/25/241IDSDOG FACILITYIP Communicator not workingReset communicator and verified function.
10/25/241ESSMISSION TRAININGReaders not working on a couple doors.Cycled power on the readers.System may have wiring issue with power supplies. ADA door opener also not unlocking door when pressed. MCTP working with contractor for maintenance.
10/25/241ESSSIM 2Panel #2 Rm A122 not connectingWorked with NEC to reset the port and also reset the panel.
10/25/241ESSSIM 1Door 1W not workingCycled power on the reader.
10/28/246IDSJOINT FACILITY 1Loss of CommunicationT-Link bad Ethernet Connector. AES unit not working properly.More Work to be done on this.
10/29/241IDSJOINT FACILITY 1Loss of CommunicationAttempted to reprogram some sections. Didn't workMore Work to be done on this.
10/31/241IDSJOINT FACILITY 1Loss of CommunicationRemoved O/C from backup AES routing and reset panel.More Work to be done on this.
10/31/240.5ESSCTCDCardreader - North Door not working.Reader bad. Likely damaged during storms the night before.Need new reader.
10/31/240.5ESSDOG FACILITYDoors didn't work during previous power outage.Replaced 4 backup batteries for lock power supplies. Main panel still needs replacement battery.
11/7/242IDSJOINT FACILITY 1Loss of CommunicationWorked on AES Radio Backup, reset AES, changed programming in main panel and performed testing. Main issues appear to be resolved. Need to check CONTACT ID format for zone info.
12/10/241IDSSJASystem TroubleBattery old and not connected to panel. Replaced.Performed test of panic buttons. Test successful. Button in courtroom was loose so I remounted it.
12/17/241ESSSHARPMain entrance latch gets stuckFrame mounted strike was out of alignment. Missing 1 screw and nut. Adjusted and tightened. Appears to be working.Note: Door handle does not appear to retract the bolt all the way. May be a life safety issue.
12/18/241IDSUNIVERSITY CAMPUSNUISANCE ALARMSMain Double Doors periodically falsing. Drilled out the door to allow more clearance for the magnets. Monitoring for further issues.
12/19/242ESSMP DETACHMENTNo network Connection to CCURE Panel.Ran new network cable from the panel to the comms room. Still need to terminate it.
12/19/241ESSHEADQUARTERS 1Door near elevator on the 1st floor of Sheridan not latching when closed.Cleaned and lubricated the door latch (fixed).
1/23/252ESSUNIVERSITY CAMPUSMultiple access control failures and possible database issues.Met with contractor and started assessing system issues. Checked several readers and received information on past issues and what was done. Looked through the Lenel Server to assess data status and system function.
1/30/253ESSUNIVERSITY CAMPUSMultiple access control failures and possible database issues.Rewired 11 readers in 3 panels. Assessing possible improvements in function.
1/31/251ESSMP DETACHMENTReconnect Panel to NetworkTerminated CAT 6 Cable in panel. Pending NEC connection in comms room.
2/4/251ESSMP DETACHMENTCommunications Not WorkingMet with NEC personnel. They had it connected to the wrong port.
2/4/251ESSCOMMAND EXCELLENCE 2North Keypdad not workingKeypad was locked up. Power cycled the reader. Fixed.
2/7/256ESSUNIVERSITY CAMPUSMultiple access control failures and possible database issues.Reqired 16 readers with the contractor. Database repair utility run and Debug file turned on to track Lenel activity. Found an issue with some of the end user "Time Zones". Implemented a correction and will monitor for improvement. Fixed the reader on the security manager's office (bad reader swapped with classroom). Combed through settings to identify other issues. Holding on additional changes until current fixes can be evaluated. All panels received downloads from the server to ensure systems is up to date with the database fix and configuration changes made today.
2/7/255IDSUNIVERSITY CAMPUSLoss of CommsAttempted to reset the panel several times. No success.After hours / Weekend service
2/8/254IDSUNIVERSITY CAMPUSLoss of CommsWorked with NEC to reset the port and also reset the panel.After hours / Weekend service
2/10/251IDST2COM TRAININGNot sending Close ReportsChecked programming. Unable to determine reason for failure to send.
2/10/251ESSMP DETACHMENTDoor Not Unlocking on valid cardFuse blown on power supply. Swapped with unused output.
2/10/252ESSUNIVERSITY CAMPUSMIFARE Cards Not WorkingAttempted to build new CHUID profiles. Appears readers were not configured to accept MIFARE.
2/21/257ESSUNIVERSITY CAMPUSMultiple access control failures and possible database issues.Verified rewiring of card readers appears to successfully resolve intermittent issues with reader function. Traced schedule timing issues. Eventually found the panels were not getting time sync from server. Reconfigured for manual entry and pushed time updates from workstation. Resolved time lag in schedules. One panel went bad, was swapped with one from 3rd floor.
2/25/252ESSSJAReader on west end of building not working.Bad reader. Swapped with functional one from Garrison PS office spares.
2/27/252IDSUNIVERSITY CAMPUSSystem troublesIdentified low battery on suplemental power supply. Unable to locate panel. Will require a return service.
2/27/251IDSSJAPanel throwing comms failure restoresReplaced defective battery in Wireless Mesh TX. Still getting signals (panel showing trouble on comms periodically). Will check programming on next call.
2/28/256ESSUNIVERSITY CAMPUSMultiple access control failures and possible database issues.Continued working issues. Rewired 25 doors today.
3/4/251IDST2COM TRAININGIDS showing low batteryReplaced battery on main panel and 5204 power supply
3/5/252IDSInstallation-WideMultiple issues due to severe winter storm/blizzard/power outageProvided support to SCIFS, OSAs and e911 PSAP to identify and clarify scope and extent of impacts
3/5/252ESSUNIVERSITY CAMPUSChecking Back on CARL LibraryWalked through facility with IT dept. Verified function and found possible bad reader on supply room.
3/5/251IDSJOINT FACILITY 1Communications IssueAES panel kept sending runaway alarms. Reset panel.
3/6/252IDSJOINT FACILITY 1Communications IssueReprogrammed panel to be compatible with SIA and Contact ID. AES may have bad 7794.
3/7/256ESSUNIVERSITY CAMPUSMultiple access control failures and possible database issues.Worked with contractor to identify faulty panel. Swapped with panel from B102. Changed server and workstation Time Server to correct IP addresses. Panels still won't connect to time server. Rechecked several card readers identified as bad by the contractor. Fixed 3 of 4 by rewiring power and pushing firmware update. Fourth reader had water damage. With the card reader procedure identified, contractor now has all the procedures necessary to fully implement corrective action and stabilize the system. Will now only provide assistance as requested.
3/7/251IDSJOINT FACILITY 1Communications IssueReplaced 7794. Cleared up some issues but still sending multiple "test" signals.
3/10/251IDSJOINT FACILITY 2Communications issueReset after NETMOD updates
3/10/251IDSJOINT FACILITY 1Communications IssueReset after NETMOD updates
3/10/251ESSSIM 1Communications IssueReset after NETMOD updates
3/11/251IDSJOINT FACILITY 1Communications IssueReplaced battery in AES
3/11/251ESSCTCDCommunications issueReset after NETMOD updates
3/11/252IDS/ESSSIM 2Multiple panels offlineReset Ccure Panels. IDS panel would not reconnect to network.
3/11/251ESSDOG FACILITYPanel offline.Unable to access comms room. Fixed sticky door while there.
3/12/252IDSSIM 2IDS in 73A not communicating.Possible issue with alarm receiver. Correcting programming error that prevented the AES from being used by the IDS.
3/12/250.5IDSSWING SPACEIDS activated by person going out emergency exit.Helped dispatch get the alarm cleared.
3/13/251IDST2COM TRAININGTrouble On systemCleared battery trouble but now has comms trouble. May be an alarm receiver.
3/17/253ESSUNIVERSITY CAMPUSAccess Control DownPanel locked up. Was able to get it to restart after several attempts. Functionally tested all doors.
3/17/251IDSJOINT FACILITY 1Communications IssueReset panel and AES. Came back online after several attempts.
3/17/251IDS/ESSDOG FACILITYCommunications IssuesIDS and ESS were offline. Restarted both and both came back online.
3/17/251IDSSIM 2Communications IssueAES dropped offline for 73A. Came back online once I openned the panel and connected the buttset to the communicator input. Unknown cause of comms interrup[tion.
3/18/251ESSMISSION TRAININGCard Reader Not workingPower cycled the reader. May need to look at replacing the HID readers. Further evaluation needed.
3/18/253IDSSIM 2Communications IssuesOngoing issues with 73A. Intermittent communications. Possible bad boards.
3/19/252IDSSIM 2Communications IssuesReplaced 9974 coms board in AES. Now working. Still have likely back TL-280. But system is functional.
3/19/252IDSUNIVERSITY CAMPUSCommunications IssuesSystem knocked off network due to NETMOD. Was able to get the system back online and communicating. Checked status of all sensitive facility IDS at e911 Dispatch.ERROR:#REF!FY24 COSTS/SAVINGS
3/21/252ESSUNIVERSITY CAMPUSFunctional Test of Active Shooter Lockdown - FailedFound that programmed Lockdown event was incorrectly built in the software. Reprogrammed the event and performed functional test - Successful. Will reschedule full test with Army U at a later date.
3/21/251ESSCOMMAND EXCELLENCE 2Door Not Unlocking on valid cardWent to site and tested doors. No issues found.
3/24/251IDST2COM TRAININGCommunications IssueReset after NETMOD updates
3/24/251IDST2COM TRAININGCommunications IssueReset after NETMOD updates
3/25/254.5ESSHEADQUARTERS 2Converting Access Control from Lenel to C-CureReceived equipment from Garrison/Physical Security (CAC equipment stored at Garrison). Identified/labelled wiring, removed old panel. Installed iSTAR PRO and started wiring panel.
3/26/251ESST2COM TRAININGCommunications IssueReset after NETMOD updates
3/26/251ESSMP DETACHMENTCommunications Issue / Reader LooseReset after NETMOD updates. Reattached mounting box for reader (was installed incorrectly).
3/26/251IDSSJADuress buttion not communicating properly.Replaced AES 7794. Communications restored.
3/26/251ESSUNIVERSITY CAMPUSLenel System unlock schedule issue.Time is correct on the system. Found the Timezone was off 5 min. Corrected programming. Also reprogrammed lockdown event. Changed reader status from "Locked" to "Card Only".
3/27/257ESSHEADQUARTERS 2Swapping out Lenel for C-CureChanged out readers and connected all RDR wiring in the panel.
3/28/255.5ESSHEADQUARTERS 2Swapping out Lenel for C-CureCompleted wiring panel and powered up the system. Pending Programming and Network Connection to finish system.
3/31/255ESSHEADQUARTERS 2Swapping out Lenel for C-CureConnected to network, programmed software, functional testing and troubleshooting. System fully functional. Minor work left.
4/1/254.5ESSHEADQUARTERS 2Swapping out Lenel for C-CureFinal clean up and dressing wires in panel. System 12 volt power supply has a defective charging circuit for the batteries. Will likely need replacement. System needs new batteries (7 years old).
4/4/251ESSHEADQUARTERS 1Panel offline.Reset after NETMOD update
4/15/252ESSJOINT FACILITY 1Migration of system to Installation Server.Prepping for migration to Installation Server. Workstation setup.
4/17/253ESSMISSION TRAININGSIPR Room not functional & Card reader on West door not working.Found the door latch had been removed from the SIPR Room. Reinstalled and adjusted to allow the card access to function properly. Reset the West door reader
4/18/251IDST2COM TRAININGNuisance Alarm on 2nd Mantrap DoorChecked system history and tested BMS function. Unable to locate an issue. Will watch this device and recommend replacement if it has another issue. POC also incorrectly entered his PIN too many times which locked out the keypad.
4/18/251IDST2COM TRAININGTrouble On systemBattery needed replacement. Looked at activity in Manitou, found that this system may need some programming correction (reported Account# 1A34 instead of 1034).
4/23/254ESSUNIVERSITY CAMPUSReaders on Loading Doc, Front Door and Rare Books are not showing up in reports (since 21 MAR 2025).Pushed Firmware updates and tested the doors. Initially couldn't find any problems but first firmware push failed on these readers. Resent one at a time and success. Found the readers were having trouble with PINs after reconnecting. It was a procedure change needed as well. All doors apprear to be functional now.
4/23/251IDSJOINT FACILITY 1Panel TroubleLow battery. Replaced main panel battery.
4/24/251IDSSIM 1Nuisance Alarm Hall 143 motionChecked device. Couldn't find any issues. Replaced batteries in the panel.
4/24/252IDSUNIVERSITY CAMPUSResponse Tests and Preventative Maintenance
4/24/252.5IDSSIM 1Motion Detector FailureMotion detector that falsed earlier in the morning failed by the end of the day. Caused another alarm. I had to respond in after hours to effect repairs. Motion detector replaced.
4/28/251CCTVJOINT FACILITY 2Reconnect Vetting CameraOld monitor died and cable had been cut off. Put new connector on the cable and plugged it into a TV provided by the end user.
4/28/252ESSJOINT FACILITY 1Migration of system to Installation Server.Started the process of building the system in C-Cure server. Panel, door contacts, REX, readers and doors all created.
5/24/254IDST2COM TRAININGLoss of CommunicationsFound that a power outage caused circuit breakers in the main power distribution closet to trip. Had to call in DPW to reset the power. Brought C-Cure, IDS and KeyGuard Systems back online.
5/27/253ESSUNIVERSITY CAMPUSFour doors on 2nd floor not working.Power outages from the weekend damaged the power supply for classrooms 2307-2310.
5/30/252ESSUNIVERSITY CAMPUSRechecked power supply & worked with contractor to clarify work to be completedIsolated the suspected defective power supply from the door controllers. Retested everything. Power supply does not provide DC out and blows fuses with nothing connected to the output.
6/4/251.5IDSHEADQUARTERS 1CG's Aide's panic not workingReplaced battery and recycled power on main panel after test failed to report. Reset of the panel seemed to resolve the issue.
6/5/253ESSUNIVERSITY CAMPUSTime on workstation off by 5 hours.Checked log, server and panels, all on the correct time. Just the workstation that was off. Need ATSD to login to the workstation and reset the time/date. Also fixed a reader to the hall outside the SCIF.
6/10/253ESSJOINT FACILITY 1Migration of system to Installation Server.Set up CHUID, Clearances and started migrating people. Also got admin login working.
6/27/251.5ESSCOMMAND EXCELLENCE 2C-Cure offline after power outageReset panel. Had to involve NEC due to network issues.
6/27/251.5IDSJOINT FACILITY 1IDS Comms FailPower Outage. Restarted panel and provided training to security manager on C-Cure.
6/29/259IDSUNIVERSITY CAMPUSExtended power outage and disruption of IDSFound alarm receiver in B120 was not communicating signals. Worked with G2 and dispatch throughout the emergency.
6/30/253IDSUNIVERSITY CAMPUSWorked with Physical Security Office to get alarm receiver back onlineReceiver dropped time. Unknown cause.
7/8/251ESSSWING SPACEIssue with west doorUnable to identify the problem. Seemed to be working . Will check back and check again.
7/8/252ESSUNIVERSITY CAMPUSDoors not locking/unlocking on timeFound a panel not responding. Reloaded firmware. Also provided instruction on resetting the panel clocks.
7/31/252ESSSHARPConfigure and test Emergency Lockdown CardsInitial programming did not work. Had to reconfigure the programming an function to meet organization requirements.
7/31/252ESSSWING SPACEWest Main Entry not unlocking.Completely disassembled the latch retraction panic bar. Identified the solenoid is burned out. Will need to get repacement parts or contract repair out. Also found the left side of the double doors was not properly latching. It prevents the building from being secured at night.
8/1/252ESSMISSION TRAININGRoom 107 door not unlockingLatch retraction was stuck. Was able to disassemble and reassemble the in-door lock assembly. Now functional. Second door on comms room had similar symptoms but the latch retraction mechanism was fuctional. It is just not unlocking. Will need support from DPW to remove lock core and check hardware.
8/4/252ESSMISSION TRAININGRoom 107 door not unlockingWorked on the lock mechanism with DPW locksmith. I can see what it is happening but not sure why or how to fix. Locksmith getting a cost for replacement.
8/6/251ESST2COM TRAININGDoor not unlocking long enough to let people in.Door position switch is out of alignment. Unable to fix the root cause without removing the door. Reprogrammed the software to delay relocking 5 seconds. This fixed the problem.
9/29/251IDSSIM 1Trouble On systemComms trouble. Reset panals.
10/16/252ESSFLKSC-Cure Server Not RespondingRestarted serverCalled in during Furlough
10/24/254IDSSIM 1OSA triggering multiple alarmsBMS on 2 East was in complete failure. No parts to replace it. Moved motion sensor from a portion of the building not using IDS. Installed Motion and rewired panel to have the motion protect the door and provide E/E delay.
11/13/251IDSHEADQUARTERS 1CG's office alarm LTTReset Panel
11/14/251IDSMISSION TRAININGLoss of CommsReset Panel
11/14/251IDSMISSION TRAININGIDS Trouble LightBad Battery. Replaced all 3 panel batteries.
11/14/251IDSDOG FACILITYLoss of Primary CommsReset Panel
11/24/251ESSHEADQUARTERS 1SHERIDAN DOOR NOT WORKINGRESET READER
11/24/251.5ESSLESSONS LEARNEDHaving trouble accessing SIPR Coms. Room. Reset the reader but it looks like the panel is offline.Checked power, reset panel.
11/24/251ESSSIM 1Intermittent reads on 1W door. Checked/reset the reader but was working while there. Also getting intermitent troubles on IDS. Checking with DES/PS office.
11/25/251ESSLESSONS LEARNEDTried to reset panel. Shows defective USB card.Working on replacement USB
11.26.20252IDSHEADQUARTERS 1CG AID DURESS BUTTON TRIGGEREDRESET BUTTON AND PANEL. PROVIDED TRAINING ON BUTTON USE TO PERSONNEL
12/8/02251IDSHEADQUARTERS 1TROUBLE WITH DURESS BUTTONS.REPLACED BATTERIES AND RESET COMMUNICATOR ON PANEL.
12/16/253IDSHEADQUARTERS 1REPLACE KEYPADSREMOVED TOUCHSCREEN AND REPLACED WITH LCD5500REDUCE POWER LOAD ON THE PANEL.
1/8/263IDSHEADQUARTERS 1DEMOLITION OF IDS IN STARRY CONF ROOMREMOVED WIRING, CONDUIT AND UTILITY CAN IN THE MAIN CONFERENCE ROOM DUE TO CONSTRUCTION.
1/22/262ESSSIM 1Reader in B73 having trouble with keypad for PIN entry.Attempted to swap with a reader NSC had. Neither worked. Tried swaping the pin-pad components. Finally swapped with another door that was working and doesn't need PIN.
1/28/263ESSHEADQUARTERS 1GRANT SALLY PORT DOOR NOT WORKINGNo power to REX or doors. Checked panel. PS good Batteries bad. Replaced. Still not working.
1/29/265ESSHEADQUARTERS 1GRANT SALLY PORT DOOR NOT WORKINGTraced wires back from doors to panel. Hooked up batteries directly to locks (working).
2/2/263ESSHEADQUARTERS 1GRANT SALLY PORT DOOR NOT WORKINGFinally able to find intermediate power supply in 2nd floor Sprimkler Equipment Closet. Batteries and Power Supply bad. Was able to replace batteries and power supply. Used power supply salvaged (known good) from old system in B102. Fully tested and functional. Updated documentation in C-Cure.
2/17/262IDSUNIVERSITY CAMPUSFront Door not clearing.Responded in after hours and was able to get the door contact working. May need replacement in the future.
2/18/262ESSC-CURE SYSTEM UPDATESecurity certificates expiringreconfigured software for host based certs
2/20/263ESSLESSONS LEARNEDAccess Panels offline.Was able to successfully update certs and get 2 panels online. 3rd panel is bad and needs replacement. Found burn marks on board traces. Likely the cause of SD card showing failure.
2/24/261IDSDOG FACILITYIDS comms down.Reset the panel.
3/10/263ESSLESSONS LEARNEDiSTAR panel in basement badEnd user acquired replacement. Board installed and configured. Programmed the new panel (including firmware updates). System back online and functional.
3/13/266ESSUNIVERSITY CAMPUSAccess control downPanel certificate expired and computer received a power strike. Power cycled the computer and was eventually able to get it working. Panel required default and firmware update. After multiple attempts, panel came back online and was functioning when I left.

File details come from the government source that posted it. Updated .