Attachment 6 - UFGS 28 10 05 - IDS.pdf

PDF 346 KB Posted

Attached to
Electronic Security System (ESS) Maintenance and Service- Amend 0001
Solicitation number
W91QF426RA010
Issued by

About this file

This is a Unified Facilities Guide Specifications (UFGS) document for Electronic Security Systems (ESS) prepared by USACE, NAVFAC, and AFCEC, effective May 2024. It establishes comprehensive technical and performance requirements for the design, installation, and integration of commercial off-the-shelf (COTS) security equipment across federal facilities.

The specification covers four primary subsystems: Intrusion Detection System (IDS), Access Control System (ACS), Video Surveillance System (VSS), and Security Command Center (SCC), along with optional Medical Facility Systems and Infant Protection Alarm Systems (IPAS). Key technical requirements include detection sensitivity with 0.9 to 0.95 probability of detection, false alarm rates not exceeding one per 30-day period for interior zones and one per 24-hour period for exterior zones, backup battery capacity calculations with 25 percent spare capacity (50 percent for cold environments), and video storage capacity based on operational requirements. The specification mandates integration of subsystems under a single operating environment with seamless database connectivity, TCP/IP communications infrastructure, and comprehensive line supervision for all sensor and communication links. Installation standards require compliance with NFPA 70, UL 681, UL 1076, and applicable service-specific security instructions (ICS 705-1 for SCIFs, AR 380-5 for Army facilities). Contractor qualifications must include Value Added Reseller (VAR) or Authorized Dealer status from the manufacturer, technicians with manufacturer-certified training, and documented experience installing similar systems for at least 12 months. The specification requires detailed submittals including shop drawings, product data, design calculations, certificates of qualification, and as-built drawings, with government approval required for components designated with "G" classifications. Training deliverables include comprehensive manuals, administrator and operator training sessions (totaling minimum 8-10 training days), and maintenance personnel instruction with follow-up sessions over two months post-installation.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

USACE / NAVFAC / AFCEC UFGS-28 10 05 (May 2024)

Preparing Activity: USACE Superseding UFGS-28 10 05 (May 2016)

UNIFIED FACILITIES GUIDE SPECIFICATIONS

References are in agreement with UMRL dated October 2025

SECTION TABLE OF CONTENTS

DIVISION 28 - ELECTRONIC SAFETY AND SECURITY

SECTION 28 10 05

ELECTRONIC SECURITY SYSTEMS (ESS)

05/24

PART 1 GENERAL

1.1 REFERENCES

1.2 SUBMITTALS

1.3 QUALITY ASSURANCE

1.3.1 Regulatory Requirements

1.3.2 Standard Products

1.3.2.1 Alternative Qualifications

1.3.2.2 Material and Equipment Manufacturing Date

1.3.2.3 Product Safety

1.3.3 Shop Drawings

1.3.3.1 ESS Components

1.3.4 Evidence of Experience and Qualifications

1.3.4.1 Contractor Qualifications

1.3.4.2 Instructor Qualifications

1.4 ENVIRONMENTAL CONDITIONS

1.4.1 Interior Conditions

1.4.1.1 Temperature

1.4.1.2 Pressure

1.4.1.3 Relative Humidity

1.4.1.4 Fungus

1.4.1.5 Acoustical Noise

1.4.2 Exterior Conditions

1.4.2.1 Temperature

1.4.2.2 Pressure

1.4.2.3 Solar Radiation

1.4.2.4 Sand and Dust

1.4.2.5 Rain

1.4.2.6 Humidity

1.4.2.7 Fungus

1.4.2.8 Salt Fog

1.4.2.9 Snow

1.4.2.10 Ice Accretion

1.4.2.11 Wind

SECTION 28 10 05 Page 1

1.4.2.12 Acoustical Noise

1.5 SYSTEM CALCULATIONS AND ANALYSIS

1.5.1 Backup Battery Capacity Calculations

1.5.2 Video Surveillance System (VSS) Storage Calculations

1.6 ESS SOFTWARE, DATA PACKAGE 4

1.7 AS-BUILT DRAWINGS

PART 2 PRODUCTS

2.1 SYSTEM DESCRIPTION

2.2 PERFORMANCE REQUIREMENTS

2.2.1 Growth Capability

2.2.2 Hazardous Locations

2.2.3 Maintainability

2.2.4 Availability

2.2.5 Fail-Safe Capability

2.2.6 Line Supervision

2.2.7 Power Loss Detection

2.2.8 Controls and Designations

2.2.9 Special Test Equipment

2.2.10 Electromagnetic Interference (EMI)

2.2.11 Electromagnetic Radiation (EMR)

2.2.12 Interchangeability

2.2.13 Date and Time Generator

2.3 INTRUSION DETECTION SYSTEM (IDS)

2.3.1 IDS Components

2.3.2 Detection Sensitivity

2.3.3 Detection Alarm and Reporting Capacity

2.3.4 False Alarm Rate

2.3.5 Nuisance Alarm Rate

2.3.6 Premise Control Unit (PCU)

2.3.6.1 PCU Capabilities

2.3.6.2 Overcurrent Protection and Indication

2.3.6.3 Manual and Self-Test

2.3.7 Detection Sensors

2.3.7.1 Interior Sensors

2.3.7.1.1 High Security Switch (HSS)

2.3.7.1.1.1 Level 1 Switch

2.3.7.1.1.2 Level 2 Switch

2.3.7.1.2 Glass Break Detection

2.3.7.1.2.1 Window-Mounted Glass Break Shock Sensor

2.3.7.1.2.2 Ceiling Or Wall-Mounted Dual Technology Glass

Break Sensor

2.3.7.1.2.3 Ceiling or Wall-Mounted Recessed Glass Break Sensor

2.3.7.1.3 Vibration Vault Sensor

2.3.7.1.4 Fiber Optic Mesh Sensors

2.3.7.1.5 Utility Inlet Opening Protection

2.3.7.1.6 Passive Infrared Sensors

2.3.7.1.7 Microwave Sensors

2.3.7.1.8 Dual Technology Sensors

2.3.7.1.9 Photoelectric Sensors

2.3.7.2 Exterior Sensors

2.3.7.2.1 Wide Gap High Security Switch (HSS)

2.3.7.2.2 Fence Mounted Sensors

2.3.7.2.2.1 Fiber Optic Sensor

2.3.7.2.2.2 Strain-Sensitive

2.3.7.2.2.3 Gate Units

2.3.7.2.3 Electrostatic Field Sensors

2.3.7.2.4 Taut-Wire Sensors

SECTION 28 10 05 Page 2

2.3.7.2.5 Dual Technology Sensors

2.3.7.2.6 Bistatic Microwave Sensor

2.3.7.2.7 Monostatic Microwave Sensor

2.3.7.2.8 Passive Infrared Sensor (Exterior)

2.3.7.2.9 Buried Ported Cable

2.3.7.2.10 Active Infrared Sensor (Exterior)

2.3.7.2.11 Video Motion Sensor (Exterior)

2.3.7.2.12 Radar

2.3.7.3 Duress Alarms (Hold Up Switch)

2.3.7.3.1 Hardwire Duress Alarms

2.3.7.3.2 Wireless Duress Alarms

2.3.7.4 Tamper Switches

2.3.7.4.1 Tamper Switch Performance Requirements

2.3.8 Intrusion Detection System Date and Time

2.4 ACCESS CONTROL SYSTEM (ACS)

2.4.1 ACS Badging Requirements

2.4.2 ACS Programming

2.4.2.1 Time Schedules

2.4.2.2 Special Days

2.4.2.3 ACU Daylight Savings Time Adjustment

2.4.2.4 Scheduled Events

2.4.2.5 Maximum User Capability

2.4.2.6 Access Groups

2.4.2.7 Active and Expire Dates

2.4.2.8 Maximum Use Settings

2.4.2.9 Door Outputs

2.4.2.10 Anti-Passback

2.4.2.11 Two Person Rule

2.4.2.12 User List or Who's In (Muster Reports)

2.4.2.13 Crisis Mode

2.4.2.14 Door Groups

2.4.2.15 Door Interlocking

2.4.2.16 PIN Required

2.4.2.17 Remote Door Control

2.4.2.18 Key Control

2.4.2.19 Guard Tour

2.4.2.20 Reader Disable

2.4.2.21 Disable Event Messages

2.4.2.22 Input and Output Groups

2.4.2.23 Delays

2.4.2.24 Remote Input Control

2.4.2.25 Output Configuration

2.4.2.26 Remote Output Control

2.4.2.27 Remote Reset Command

2.4.2.28 Time Zone

2.4.2.29 User-Selected LED Behavior

2.4.2.30 Traced Cards

2.4.2.31 Badge Print Tracking

2.4.3 Error and Throughput Rates

2.4.4 Access Control System Central Processing

2.4.5 Access Control Unit(ACU)

2.4.6 Access Control Devices

2.4.6.1 Card Readers

2.4.6.1.1 Contact Card Readers

2.4.6.1.2 Contactless Card Readers

2.4.6.1.3 Card Readers With Integral Keypad and Biometric Reader

2.4.6.1.4 Card Readers with Integral Keypad

2.4.6.1.5 Card Reader Display

2.4.6.1.6 Card Reader Response Time

SECTION 28 10 05 Page 3

2.4.6.1.7 Card Reader Power

2.4.6.1.8 Card Reader Mounting Method

2.4.6.2 Keypads

2.4.6.2.1 Keypad Display

2.4.6.2.2 Keypad Response Time

2.4.6.2.3 Keypad Power

2.4.6.2.4 Keypad Mounting Method

2.4.6.2.5 Keypad Duress Codes

2.4.6.3 Access Control Cards

2.4.6.3.1 Credential Card Modification

2.4.6.3.2 Card Size and Dimensional Stability

2.4.6.3.3 Card Materials and Physical Characteristics

2.4.6.3.4 Card Construction

2.4.6.3.5 Card Durability and Maintainability

2.4.6.3.6 Warranty

2.4.6.4 Personal Identity Verification Equipment

2.4.6.4.1 Hand Geometry

2.4.6.4.1.1 Template Update and Acceptance Tolerances

2.4.6.4.1.2 Average Verification Time

2.4.6.4.1.3 Modes

2.4.6.4.1.4 Reports

2.4.6.4.1.5 Electrical

2.4.6.4.1.6 Mounting Method

2.4.6.4.1.7 Communications Protocol

2.4.6.4.2 Fingerprint Analysis Scanner

2.4.6.4.2.1 Template Update and Acceptance Tolerances

2.4.6.4.2.2 Average Verification Time

2.4.6.4.2.3 Modes

2.4.6.4.2.4 Reports

2.4.6.4.2.5 Electrical

2.4.6.4.2.6 Mounting Method

2.4.6.4.2.7 Communications Protocol

2.4.6.4.3 Iris Scan Device

2.4.6.4.3.1 Display Type

2.4.6.4.3.2 Template Update and Acceptance Tolerances

2.4.6.4.3.3 Average Verification Time

2.4.6.4.3.4 Modes

2.4.6.4.3.5 Reports

2.4.6.4.3.6 Electrical

2.4.6.4.3.7 Mounting Method

2.4.6.4.4 Facial Scanner

2.4.6.4.4.1 Template Update and Acceptance Tolerances

2.4.6.4.4.2 Average Verification Time

2.4.6.4.4.3 Modes

2.4.6.4.4.4 Reports

2.4.6.4.4.5 Electrical

2.4.6.4.4.6 Mounting Method

2.4.6.4.4.7 Communications Protocol

2.4.6.4.5 Palm Scanner

2.4.6.4.5.1 Template Update and Acceptance Tolerances

2.4.6.4.5.2 Average Verification Time

2.4.6.4.5.3 Modes

2.4.6.4.5.4 Reports

2.4.6.4.5.5 Electrical

2.4.6.4.5.6 Mounting Method

2.4.6.4.5.7 Communications Protocol

2.4.6.5 Portal Control Devices

2.4.6.5.1 Push-Button Switches

2.4.6.5.2 Panic Bar

SECTION 28 10 05 Page 4

2.4.6.5.2.1 Emergency Egress With Alarm

2.4.6.5.2.2 Normal Egress

2.4.6.5.2.3 Delay Egress With Alarm

2.4.6.5.3 Electric Door Strikes and Bolts

2.4.6.5.3.1 Solenoid

2.4.6.5.3.2 Signal Switches

2.4.6.5.3.3 Tamper Resistance

2.4.6.5.3.4 Size and Weight

2.4.6.5.3.5 Mounting Method

2.4.6.5.3.6 Astragals

2.4.6.5.4 Electrified Mortise Lock

2.4.6.5.4.1 Solenoid

2.4.6.5.4.2 Signal Switches

2.4.6.5.4.3 Power Transfer

2.4.6.5.4.4 Size and Weight

2.4.6.5.4.5 Mounting Method

2.4.6.5.5 Electromagnetic Lock

2.4.6.5.5.1 Armature

2.4.6.5.5.2 Tamper Resistance

2.4.6.5.5.3 Mounting Method

2.4.6.5.6 Entry Booth

2.4.6.5.6.1 Local Alarm Annunciation

2.4.6.5.6.2 Terminal and Facility Interface Device Support

2.4.6.5.6.3 Response Times

2.4.6.5.6.4 Autonomous Local Control

2.4.6.5.6.5 Entry Booth Local Processor Subsystem Capacities

2.4.6.5.6.6 Diagnostics

2.4.6.5.6.7 Memory Type and Size

2.4.6.5.6.8 Tamper Protection

2.4.6.5.6.9 Entry Booth Configuration

2.4.6.5.6.10 Entry Booth Operation

2.4.6.5.6.11 Display Type

2.4.6.5.6.12 Lighting

2.4.6.5.6.13 Heating and Ventilation Equipment

2.4.6.5.6.14 Entry Booth Wall and Frame Construction

2.4.6.5.6.15 Entry Booth Doors

2.4.6.5.6.16 Entry Booth Floor Construction

2.4.6.5.6.17 Electrical Requirements

2.4.6.5.6.18 VSS Camera

2.4.6.5.6.19 Weight Check Monitor

2.4.6.5.6.20 Double Occupancy Sensor

2.4.6.5.6.21 Intercom

2.4.6.5.6.22 Voice Prompts

2.4.6.5.7 Vehicle Gate Operator

2.4.6.5.7.1 Input Power

2.4.6.5.7.2 Audible Warning

2.4.6.5.7.3 Maximum Run Timer

2.4.6.5.7.4 Adjustable Load Monitor for Obstruction Sensing

2.4.6.5.7.5 Operator Override Controls

2.4.6.5.7.6 Limit Switches

2.4.6.5.7.7 Type of Gate

2.4.6.5.7.8 Safety

2.4.6.6 Active Barrier Interface

2.4.7 Elevator Control

2.4.7.1 Control Elevator Operation with Entry Control Terminal

Devices

2.4.7.2 Floor Tracking

2.4.8 Access Control System Date and Time

2.5 VIDEO SURVEILLANCE SYSTEM (VSS)

SECTION 28 10 05 Page 5

2.5.1 Cameras

2.5.1.1 VSS Camera

2.5.1.1.1 Sensitivity

2.5.1.1.2 Signal-To-Noise Ratio

2.5.1.1.3 Resolution

2.5.1.1.4 Synchronization

2.5.1.1.5 Low Light Level

2.5.1.2 Camera Lenses

2.5.1.3 Camera Housing and Mounts

2.5.1.3.1 Environmentally Sealed Camera Housing

2.5.1.3.2 Indoor Camera Housing

2.5.1.3.3 Interior Mount

2.5.1.3.4 Low Profile Ceiling Mount

2.5.1.3.5 Interior Dome Housing

2.5.1.3.6 Exterior Dome Housing

2.5.1.3.7 Exterior Wall Mount

2.5.1.3.8 Pan-Tilt Mount

2.5.1.3.9 Explosion Proof Housing

2.5.2 Thermal Imaging System

2.5.3 Video Analytics (VA)

2.5.3.1 Software

2.5.3.1.1 Basic Motion Detection

2.5.3.1.2 Advanced VA

2.5.3.1.2.1 Intruder Identification

2.5.3.1.2.2 Environmental Compensation

2.5.3.1.2.3 Counting

2.5.3.1.2.4 Directional Identification

2.5.3.1.2.5 Item Recognition

2.5.3.1.2.6 Subject Tracking

2.5.3.1.2.7 Multiple Subject Tracking

2.5.3.1.2.8 Object Left Behind

2.5.3.2 Embedded VA

2.5.3.2.1 Intelligent Video Analysis

2.5.3.2.2 Motion Tracking with PTZ Cameras

2.5.4 Color Computer Monitors

2.5.4.1 Mounting

2.5.4.2 Video and Signal Input

2.5.5 Ancillary Equipment

2.5.5.1 Video System Date and Time

2.5.5.2 Camera Identifiers

2.5.5.3 Video Recording

2.5.5.3.1 Analog to IP Video Converter

2.5.5.3.2 IP Based Video Recording Device/System

2.5.5.3.3 Video Recording Performance

2.5.5.3.4 Recording Audio With Video

2.5.5.4 Camera Control

2.5.6 Camera Mounting Structures

2.5.7 Video Surveillance System (VSS) Schedule

2.6 SECURITY COMMAND CENTER (SCC)

2.6.1 ESS Software

2.6.1.1 Alarm Call up

2.6.1.2 Programming

2.6.1.2.1 Daylight Savings Time Adjustment

2.6.1.2.2 Operator Privileges

2.6.1.2.3 Alarm Priorities

2.6.1.2.4 Reports

2.6.1.2.5 User Interface

2.6.1.2.6 Messages

2.6.1.2.7 Graphics

SECTION 28 10 05 Page 6

2.6.1.2.8 Device Status

2.6.1.2.9 Diagnostics

2.6.1.2.10 Mandatory Data Fields

2.6.1.2.11 User Defined Data Fields

2.6.1.2.12 Archive Database

2.6.1.2.13 Programmable Database Backup

2.6.1.2.14 Programmable Database Purging

2.6.1.2.15 Database Importing

2.6.1.2.16 Data Exporting

2.6.1.2.17 Event Log Output

2.6.1.2.18 Data Audit Trail

2.6.1.2.19 Alarm Forwarding

2.6.2 ESS Monitor Display Software

2.6.3 Graphical Interactive Map Software

2.6.4 Printers

2.6.4.1 Report Printer

2.6.4.2 Alarm Printer

2.6.4.3 Badge Printer

2.6.5 Control and Display Integration

2.6.6 Enrollment Center Equipment

2.6.6.1 Enrollment Client Accessories

2.6.6.2 Enrollment Center I.D. Production

2.6.6.3 Enrollment Client Software

2.7 COMMUNICATIONS

2.7.1 Link Supervision

2.7.1.1 Hardwire Direct Current Line Supervision

2.7.1.2 Hardwire Alternating Current Supervision

2.7.1.3 Hardwire Digital Supervision

2.7.2 Hardwire

2.7.2.1 Electrical Conductor Lines

2.7.2.2 Communication Link

2.7.3 Radio Frequency Link

2.7.4 Data Encryption

2.7.5 Network Switch

2.7.5.1 Inside Plant

2.7.5.2 Outside Plant

2.7.6 Video and ESS Transmission

2.7.7 Wire and Cable

2.7.8 Digital Data Interconnection Wiring

2.7.9 Aboveground Sensor Wiring

2.7.10 Direct Burial Sensor Wiring

2.7.11 Local Area Network (LAN) Cabling

2.7.12 Cable Construction

2.8 SECURITY LIGHTING INTERFACE

2.9 MEDICAL FACILITY SYSTEM

2.9.1 Infant Protection Alarm System (IPAS) Performance Requirements

2.9.2 Infant Protection Alarm System (IPAS) Major Components

2.9.3 Infant Protection Operator Workstations

2.9.4 Remote Display Unit

2.9.5 Operator Interface

2.9.6 Alarm Management

2.9.6.1 Tamper Alarm

2.9.6.2 Near Exit Alarm

2.9.6.3 Battery Alarm

2.9.6.4 Failed Communications Alarm

2.9.6.5 Lost Alarm

2.9.7 IPAS Area Wireless Tag Readers

2.9.8 IPAS Door Wireless Reader

2.9.9 Infant Tags and Straps

SECTION 28 10 05 Page 7

2.9.9.1 Tag Characteristics

2.9.9.2 Tag Features

2.9.10 IPAS Dome Lights

2.9.11 Radio Page Interface

2.10 SURVEILLANCE AND DETECTION EQUIPMENT

2.10.1 Article Surveillance and X-Ray

2.10.1.1 Size and Weight

2.10.1.2 Local Audible Alarms

2.10.1.3 Maximum Package Size

2.10.1.4 X-Ray Tube

2.10.1.5 Electrical

2.10.1.6 Safety

2.10.1.7 Display

2.10.1.8 Conveyor

2.10.1.9 Material Identification and Resolution

2.10.2 Metal Detector

2.10.2.1 Size and Weight

2.10.2.2 Local Alarms

2.10.2.3 Material Identification and Sensitivity

2.10.2.4 Traffic Counter

2.10.2.5 Electrical

2.11 BACKUP POWER

2.11.1 Uninterruptible Power Supply (UPS)

2.11.2 Batteries

2.12 SURGE SUPPRESSION DEVICES

2.12.1 Powerline Surge Protection

2.12.2 Powerline Sensor Device Wiring and Communication Circuit

Surge Protection

2.13 COMPONENT ENCLOSURE

2.13.1 Interior Sensor

2.13.2 Exterior Sensor

2.13.3 Interior Enclosures

2.13.4 Exposed-to-Weather Enclosures

2.13.5 Corrosion-Resistant Enclosures

2.13.6 Hazardous Environment Equipment

2.13.7 Metal Thickness

2.13.8 Doors and Covers

2.13.9 Ventilation

2.13.10 Mounting

2.13.11 Labels

2.13.12 Test Points

2.14 EQUIPMENT RACK

2.14.1 Labels

2.15 LOCKS AND KEY LOCK

2.15.1 Lock

2.15.2 Key-Lock Operated Switches

2.15.3 Construction Locks

2.16 FIELD FABRICATED NAMEPLATES

2.16.1 Manufacturer's Nameplate

2.17 FACTORY APPLIED FINISH

PART 3 EXECUTION

3.1 INSTALLATION

3.1.1 Existing Equipment

3.1.2 Software Installation

3.1.3 Enclosure Penetrations

3.1.4 Cable and Wire Runs

3.1.5 Soldering

SECTION 28 10 05 Page 8

3.1.6 Galvanizing

3.1.7 Conduits

3.1.8 Underground Cable Installation

3.1.9 Exterior Fences

3.1.10 Camera Housings, Mounts, and Poles

3.1.11 Field Applied Painting

3.1.12 Bonding, Grounding, and Shielding

3.1.12.1 Grounding

3.1.12.1.1 Earth Electrode Subsystem

3.1.12.1.1.1 Ground Rod

3.1.12.1.1.2 Perimeter Fence

3.1.12.1.1.3 Field Distribution Boxes (FDBs)

3.1.12.1.1.4 Towers and Structures

3.1.12.2 Surge Protection Subsystem

3.1.12.2.1 Exterior Equipment

3.1.12.2.2 Interior Equipment

3.1.12.2.3 Fault Protection Subsystem

3.1.12.2.4 Signal Reference Subsystem

3.1.12.3 Bonding

3.1.12.4 Shielding

3.1.13 Nameplate Mounting

3.2 ADJUSTMENT, ALIGNMENT, SYNCHRONIZATION, AND CLEANING

3.3 SYSTEM STARTUP

3.4 SUPPLEMENTAL CONTRACTOR QUALITY CONTROL

3.5 ESS SYSTEM TESTING

3.6 ESS TRAINING

3.6.1 ESS Training Outline

3.6.2 Typical Training Day

3.6.3 ESS Administrator Training

3.6.4 ESS Operator Training

3.6.5 Maintenance Personnel Training

3.6.6 Follow-up Training

-- End of Section Table of Contents --

SECTION 28 10 05 Page 9

USACE / NAVFAC / AFCEC UFGS-28 10 05 (May 2024)

Preparing Activity: USACE Superseding UFGS-28 10 05 (May 2016)

UNIFIED FACILITIES GUIDE SPECIFICATIONS

References are in agreement with UMRL dated October 2025

SECTION 28 10 05

ELECTRONIC SECURITY SYSTEMS (ESS)

05/24

NOTE: This guide specification covers the requirements for Electronic Security Systems (ESS) consisting of commercial off-the-shelf equipment which is limited to:

1. Intrusion Detection System (IDS)

2. Access Control System (ACS)

3. Video Surveillance System (VSS)

4. Medical Facility System

5. Security Command Center

6. Security Lighting

7. Infant Protection Alarm System (IPAS)

System requirements must conform to UFC 4-021-02, "Electronic Security Systems". Consult the appropriate governing authority - the US Naval Facilities Engineering Command, the US Army Corps of Engineers, the US Air Force Civil Engineering Support Agency, or the National Aeronautics and Space Administration - for questions concerning system design. Coordinate requirements with the Project Manager, Base/Regional Security Personnel, and the Accrediting Official. ESS is typically provided for the protection of designated assets.

Adhere to UFC 1-300-02 Unified Facilities Guide Specifications (UFGS) Format Standard when editing this guide specification or preparing new project specification sections. Edit this guide specification for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable item(s) or insert appropriate information.

Remove information and requirements not required in respective project, whether or not brackets are present.

Comments, suggestions and recommended changes for

SECTION 28 10 05 Page 10 this guide specification are welcome and should be submitted as a Criteria Change Request (CCR) .

PART 1 GENERAL

NOTE: This section will be used in conjunction with Sections: 26 20 00 INTERIOR DISTRIBUTION SYSTEM;

27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM;

33 71 01 OVERHEAD TRANSMISSION AND DISTRIBUTION;

33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION;

33 82 00 TELECOMMUNICATIONS OUTSIDE PLANT (OSP);

28 08 10 ELECTRONIC SECURITY SYSTEM ACCEPTANCE

TESTING; Section 34 75 13.13 CRASH RATED ACTIVE VEHICLE BARRIERS AND CONTROLS; and any other guide specification sections required by the design.

1.1 REFERENCES

NOTE: This paragraph is used to list the publications cited in the text of the guide specification. The publications are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.

Use the Reference Wizard's Check Reference feature when you add a Reference Identifier (RID) outside of the Section's Reference Article to automatically place the reference in the Reference Article. Also use the Reference Wizard's Check Reference feature to update the issue dates.

References not used in the text will automatically be deleted from this section of the project specification when you choose to reconcile references in the publish print process.

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)

ASC/X9 X9.52 (1998) Triple Data Encryption Algorithm Modes of Operation

ASTM INTERNATIONAL (ASTM)

ASTM A123/A123M (2024) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products

ASTM B32 (2020) Standard Specification for Solder Metal

SECTION 28 10 05 Page 11

ASTM D709 (2017) Standard Specification for Laminated Thermosetting Materials

ASTM E84 (2024) Standard Test Method for Surface Burning Characteristics of Building Materials

BUILDERS HARDWARE MANUFACTURERS ASSOCIATION (BHMA)

ANSI/BHMA A156.23 (2010) Electromagnetic Locks

ELECTRONIC COMPONENTS INDUSTRY ASSOCIATION (ECIA)

ECIA EIA/ECA 310-E (2005) Cabinets, Racks, Panels, and Associated Equipment

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

IEEE 802.3 (2022; CORR 2024) Ethernet

IEEE C62.41.1 (2002; R 2008) Guide on the Surges Environment in Low-Voltage (1000 V and Less) AC Power Circuits

IEEE C62.41.2 (2002) Recommended Practice on Characterization of Surges in Low-Voltage (1000 V and Less) AC Power Circuits

INTELLIGENCE COMMUNITY STANDARD (ICS)

ICS 705-1 (2010) Physical and Technical Security Standard for Sensitive Compartmented Information Facilities

INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO)

ANSI ISO/IEC 7816 (R 2009) Identification Cards - Integrated Circuit Cards

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

NEMA 250 (2020) Enclosures for Electrical Equipment (1000 Volts Maximum)

NEMA ICS 1 (2022) Standard for Industrial Control and Systems: General Requirements

NEMA ICS 2 (2000; R 2020) Industrial Control and Systems Controllers, Contactors, and Overload Relays Rated 600 V

NEMA ICS 6 (1993; R 2016) Industrial Control and Systems: Enclosures

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 70 (2026) National Electrical Code

SECTION 28 10 05 Page 12

NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY (NIST)

NIST FIPS 140-2 (2001) Security Requirements for Cryptographic Modules

NIST FIPS 197 (2001) Advance Encryption Standard

NIST FIPS 201-2 (2013) Personal Identity Verification (PIV) of Federal Employees and Contractors

NIST SP 800-116 (2018; Rev 1) Guidelines for the Use of PIV Credentials in Facility Access

OPEN NETWORK VIDEO INTERFACE FORUM (ONVIF)

ONVIF (2017) Core Specification Version 17.06

TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)

ANSI/TIA-568.2 (2024e) Balanced Twisted-Pair Telecommunications Cabling and Components Standards

ANSI/TIA-606 (2021d) Administration Standard for Telecommunications Infrastructure

ANSI/TIA-607 (2019d) Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises

TIA-222 (2018H; Add 1 2019) Structural Standard for Antenna Supporting Structures and Antennas and Small Wind Turbine Support Structures

U.S. DEPARTMENT OF DEFENSE (DOD)

MIL-HDBK-419 (1987; Rev A) Grounding, Bonding, and Shielding for Electronic Equipments and Facilities Volumes 1 of 2 Basic Theory

MIL-STD-188-124 (1998; Rev B; Notice 2 1998; Notice 3 2000; Notice 4 2013) Grounding, Bonding and Shielding for Common Long Haul/Tactical Communications Systems, Including Ground Based Communications - Electronics Facilities and Equipments

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

21 CFR 1020 Performance Standards for Ionizing Radiation Emitting Products

47 CFR 15 Radio Frequency Devices

UL SOLUTIONS (UL)

UL 50 (2024) UL Standard for Safety Enclosures for Electrical Equipment, SECTION 28 10 05 Page 13

Non-Environmental Considerations

UL 294 (2023) UL Standard for Safety Access Control System Units

UL 437 (2013; Reprint Jan 2022) UL Standard for Safety Key Locks

UL 634 (2007; Reprint Sep 2025) Connectors and Switches for Use with Burglar-Alarm Systems

UL 636 (2018) UL Standard for Safety Holdup Alarm Units and Systems

UL 639 (2007; Reprint Jun 2024) Standard for Intrusion Detection Units

UL 681 (2014; Reprint Sep 2025) UL Standard for Safety Installation and Classification of Burglar and Holdup Alarm Systems

UL 796 (2020; Reprint Oct 2023) UL Standard for Safety Printed Wiring Boards

UL 969 (2025) UL Standard for Safety Marking and Labeling Systems

UL 972 (2006; Reprint Nov 2020) UL Standard for Safety Burglary Resisting Glazing Material Type

UL 1037 (2016; Reprint Aug 2023) UL Standard for Safety Antitheft Alarms and Devices

UL 1076 (2018; Reprint Feb 2021) UL Standard for Safety Proprietary Burglar Alarm Units and Systems

UL 1610 (2016; Reprint Apr 2021) UL Standard for Safety Central-Station Burglar-Alarm Units

UL 2050 (2003; 4th Edition) Standard for National Industrial Security Systems for the Protection of Classified Materials (limited distribution publication, direct purchase request with justification to UL)

UL 2802 (2013; Reprint Apr 7 2020) UL Standard for Safety Performance Testing of Camera Image Quality

UL 62368-1 (2025) UL Standard for Audio/Video, Information, and Communication Technology Equipment - Part 1: Safety Requirements

1.2 SUBMITTALS

NOTE: Review submittal description (SD) definitions

SECTION 28 10 05 Page 14 in Section 01 33 00 SUBMITTAL PROCEDURES and edit the following list, and corresponding submittal items in the text, to reflect only the submittals required for the project. The Guide Specification technical editors have classified those items that require Government approval, due to their complexity or criticality, with a "G." Generally, other submittal items can be reviewed by the Contractor's Quality Control System. Only add a “G” to an item, if the submittal is sufficiently important or complex in context of the project.

For Army projects, fill in the empty brackets following the "G" classification, with a code of up to three characters to indicate the approving authority. Codes for Army projects using the Resident Management System (RMS) are: "AE" for Architect-Engineer; "DO" for District Office (Engineering Division or other organization in the District Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project Office. Codes following the "G" typically are not used for Navy and Air Force projects.

The "S" classification indicates submittals required as proof of compliance for sustainability Guiding Principles Validation or Third Party Certification and as described in Section 01 33 00 SUBMITTAL

PROCEDURES.

Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government. Submit the following in accordance with Section

01 33 00 SUBMITTAL PROCEDURES:

[ [The [_____] will review and] [[_____] Division], [Naval Facilities Engineering Command] [_____] will approve submittals requiring special review in this section.

] SD-02 Shop Drawings

ESS Components ; G, [_____]

Access Control System (ACS) ; G, [_____]

Security Hardware Door Schedule ; G, [_____]

Overall System Schematic ; G, [_____]

Video Surveillance System (VSS) Schedule ; G, [_____]

SD-03 Product Data

NOTE: The product data list is not all inclusive.

SECTION 28 10 05 Page 15

Premise Control Unit ; G, [_____]

Detection Sensors ; G, [_____]

Access Control Unit ; G, [_____]

Access Control Devices ; G, [_____]

Cameras ; G, [_____]

Camera Lenses ; G, [_____]

Camera Housing and Mounts ; G, [_____]

Thermal Imaging System ; G, [_____]

Video Recording ; G, [_____]

Printers ; G, [_____]

Communications Interface Devices ; G, [_____]

Radio Frequency Link ; G, [_____]

Network Switch ; G, [_____]

Video and ESS Transmission ; G, [_____]

Infant Protection Alarm System (IPAS) Major Components ; G, [_____]

Uninterruptible Power Supply (UPS) ; G, [_____]

Batteries ; G, [_____]

Component Enclosure ; G, [_____]

Equipment Rack ; G, [_____]

SD-05 Design Data

Backup Battery Capacity Calculations ; G, [_____]

Video Surveillance System (VSS) Storage Calculations ; G, [_____]

Error and Throughput Rates ; G, [_____]

SD-07 Certificates

Contractor Qualifications ; G, [_____]

Instructor Qualifications ; G, [_____]

Contact Card Readers ; G, [_____]

Contactless Card Readers ; G, [_____]

Data Encryption ; G, [_____]

SECTION 28 10 05 Page 16

Wire And Cable ; G, [_____]

Bonding, Grounding, And Shielding ; G, [_____]

SD-10 Operation and Maintenance Data

ESS Components ; G, [_____]

ESS Software, Data Package 4 ; G, [_____]

ESS Training ; G, [_____]

ESS Training Outline ; G, [_____]

Submit data package in accordance with Section 01 78 23

OPERATION AND MAINTENANCE DATA

SD-11 Closeout Submittals

As-Built Drawings ; G, [_____]

Warranty ; G, [_____]

1.3 QUALITY ASSURANCE

1.3.1 Regulatory Requirements

The advisory provisions in each of the publications referred to in this specification are mandatory. Interpret these publications as though the word "must" has been substituted for "should" wherever it appears.

Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer.

Equipment, materials, installation, and workmanship must be in accordance with the mandatory and advisory provisions of NFPA 70 unless more stringent requirements are specified or indicated.

1.3.2 Standard Products

Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship and:

a. Have been in satisfactory commercial or industrial use for 2 years prior to bid opening and have been utilized in applications of equipment and materials under similar circumstances and of similar size.

b. Have been available on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period.

c. Where two or more items of the same class of equipment are required, provide products of a single manufacturer.

d. Provide commercial off-the-shelf (COTS) products in which the manufacturer allows a network of qualified distributors to sell, install, integrate, maintain, and repair the hardware and software

SECTION 28 10 05 Page 17 products that make up the system. All products are to be NDAA and FAR subpart 4.21 compliant.

1.3.2.1 Alternative Qualifications

Products having less than a 2 year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.

1.3.2.2 Material and Equipment Manufacturing Date

Products manufactured more than one year prior to date of delivery to the site are not acceptable.

1.3.2.3 Product Safety

System components are to conform to applicable rules and requirements of NFPA 70 . Equip system components with instruction stickers including warnings and cautions describing physical safety, and special or important procedures to be followed in operating and servicing system equipment.

1.3.3 Shop Drawings

1.3.3.1 ESS Components

Submit the ESS Components, Data Package 4 with the ESS Software submittal package in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA. Submit drawings that clearly and completely indicate each ESS component function that includes:

a. Termination device points

b. Interconnections required for system operation

c. Interconnections between modules and devices

d. Component and device wiring diagrams.

e. Proposed wireway or conduit systems to be used including:

(1) Locations

(2) Sizes

(3) Types

f. Drawings showing:

(1) Device locations and spacing

(2) Mounting and positioning details

(3) Riser Diagrams with cable sizes and types

(4) Bill of Materials (Device make, model and quantities)

(5) Alarm and access control zones

SECTION 28 10 05 Page 18

(6) Video Surveillance System (VSS) and sensor coverage areas

(7) Spare capacity

(8) Tables with ( Security Hardware Door Schedule ) identifying security devices requirements per building, room, and door

(9) Overall system schematic diagram(s).

1.3.4 Evidence of Experience and Qualifications

1.3.4.1 Contractor Qualifications

Contractor or its subcontractor(s) must be a Value Added Resaler (VAR)/Authorized Dealer (AD) of the manufacturer line of products being installed. Provide manufacturer certificate showing current dealership status. Technicians working the project must provide certificates of training for the requirements of the manufacturer, and those certificates must be from the manufacturer or approved by the manufacturer.

Submit experience and certified qualifications data prior to installation. Show that specific installers who will perform the work have a minimum of [2] [_____] years of experience successfully installing ESS of the same type and similar design as specified. Include the names, locations, and points of contact of at least two installations of similar type and design as specified in this document where the installer has installed such systems. Indicate the type of each system installed.

Certify that each system has performed satisfactorily in the manner intended for a period of at least [12] [_____ ] months.[ Installation and maintenances of IDS for the protection of classified information to be performed by US citizens who have been subject to a trustworthiness determination.]

1.3.4.2 Instructor Qualifications

Submit the instructor's experience and certified qualifications data prior to installation. Show that the instructor has received a minimum of 24 hours of ESS training from the manufacturer of the product being installed, and 2 years experience in installing the specified ESS type.

1.4 ENVIRONMENTAL CONDITIONS

1.4.1 Interior Conditions

Equipment installed in environmentally protected interior areas must meet performance requirements specified for the following ambient conditions:

1.4.1.1 Temperature

0 to 50 degrees C. 32 to 120 degrees F. Components installed in unheated security protected areas must meet performance requirements for temperatures as low as minus 17 degrees C 0 degrees F

1.4.1.2 Pressure

Sea level to 4573 m 15,000 feet above sea level

SECTION 28 10 05 Page 19

1.4.1.3 Relative Humidity

5 to 95 percent

1.4.1.4 Fungus

Components must be constructed of non-fungus nutrient materials or be treated to inhibit fungus growth

1.4.1.5 Acoustical Noise

Components must be suitable for use in high noise areas above 100 dB, without adversely affecting their performance

1.4.2 Exterior Conditions

Components in enclosures must meet performance requirements when exposed to the following ambient conditions:

1.4.2.1 Temperature

[Minus 32 to 60] [_____] degrees C [Minus 25 to 140] [_____] degrees F

1.4.2.2 Pressure

Sea level to [4573] [_____] m [15,000] [_____] feet above sea level

1.4.2.3 Solar Radiation

Six [_____] hours of solar radiation per day at dry bulb temperature of 60 [ ] degrees C 120 [_____] degrees F including 4 hours of solar radiation at 0.00112 [ ] watts per square mm 104 [_____] watts per square foot

[ 1.4.2.4 Sand and Dust

Wind driven for up to [9.6] [_____] km per hour (kmph) [6] [_____] miles per hour (mph) in accordance with UL 294 and UL 639 .

] 1.4.2.5 Rain

50 mm 2 inches per hour and 125 mm 5 inches per hour cyclic with wind plus one period of 300 mm 12 inches per hour in accordance with UL 294 and

UL 639 .

1.4.2.6 Humidity

5 to 95 percent

[ 1.4.2.7 Fungus

Warm, humid atmosphere conducive to the growth of heterotrophic plants

][ 1.4.2.8 Salt Fog

Salt atmosphere with [5] [_____] percent salinity

SECTION 28 10 05 Page 20

][ 1.4.2.9 Snow

Snow loading of 234 kg per square m 48 (psf) per hour; blowing snow of

22.5 kg per square m 4.6 psf per hour. Blowing snow from any angle (falling vertically to horizontal blowing from any azimuth) must not penetrate ESS equipment.

][ 1.4.2.10 Ice Accretion

Up to 12.7 mm 1/2 inches of radial ice

] 1.4.2.11 Wind

Continual velocity up to 80 kmph 50 mph with gusts to 106 kmph 66 mph , except that fence sensors must detect intrusions up to 56 kmph 35 mph

1.4.2.12 Acoustical Noise

Visual alert device and components should be used in high noise areas above 110 dB without adversely affecting their performance. Examples areas include flight lines, run-up pads, and generator sites.

1.5 SYSTEM CALCULATIONS AND ANALYSIS

1.5.1 Backup Battery Capacity Calculations

Submit calculations showing that backup battery capacity exceeds sensor operation, communications supervision, and alarm annunciation power requirements for proposed equipment plus 25 percent spare capacity. In environments regularly exposed to conditions of 0 degrees C 32 degrees F provide 50 percent spare capacity. In environments regularly exposed to conditions of 49 degrees C 120 degrees F provide resistance to thermal runaway for lithium based batteries.

1.5.2 Video Surveillance System (VSS) Storage Calculations

Submit calculations showing the required storage capacity for each video storage device. Calculations must be based on the recording parameters specified by the end user/customers operational requirements.

1.6 ESS SOFTWARE, DATA PACKAGE 4

Submit the ESS software, Data Package 4 with the ESS Components submittal package in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA. Describe the functions of all software in the software manual and include:

a. All information necessary to enable proper loading, testing, and operation

b. Terms and functions definitions

c. Use of system and application software

d. Procedures for system initialization, start-up and shutdown

e. Alarm reports

f. Reports generation

SECTION 28 10 05 Page 21

g. Database format and data entry requirements

h. Directory of all files

i. All communication protocol descriptions, including data formats, command characters, and a sample of each type of data transfer

j. Interface definition

k. List of software keys

l. Backup and restore procedures and instructions on how to archive reports and video footage on DVD for forensics investigations.

1.7 AS-BUILT DRAWINGS

NOTE: Designer must verify CAD version with Contracting Officer and clearly state the requirement.

Maintain a separate set of drawings, elementary diagrams, and wiring diagrams of the system to be used for as-built drawings. Keep this set accurately and neatly up to date with all changes and additions. This set is not to be used for installation purposes.

Finish the final drawings submitted with the endurance test report in accordance with Section 01 78 00 CLOSEOUT SUBMITTALS for as-built requirements.

PART 2 PRODUCTS

2.1 SYSTEM DESCRIPTION

NOTE: Use the following for ESS guidance as applicable:

For SCIF and SAPF fill in the first bracketed option with: Intelligence Community Standards (ICD/ICS) 705 Physical and Technical Security Standards for Sensitive Compartmented Information Facilities.

(NOTE: Do not identify "SCIF" or SAPF in Request for Proposal (RFP) or construction drawings. With accrediting official's approval, areas may be identified as "secure area" or "controlled area.")

For Secret, Top Secret or Controlled Access Areas (CAA), fill in the first bracketed option with the appropriate Service instruction: SECNAV M-5510.36A Department of Navy Information Security Program;

Army Regulation AR 380-5 Department of the Army Information Security Program; or Air Force Instruction AFI 31-401 Department of the Air Force Information Security Program.

For Arms, ammunition or explosives (arms rooms, SECTION 28 10 05 Page 22 armories, and magazines), fill in the first bracketed option with the appropriate Service instruction: OPNAV Instruction 5530-13C Department of the Navy Physical Security Instruction for Conventional Arms, Ammunition, and Explosives; MCO 5530.14A Marine Corps Physical Security Program Manual; AR 190-11 Department of the Army Physical Security of Arms, Ammunition and Explosives; or AFMAN 91-201 Department of the Air Force Explosive Safety Standards

For Air Force non-nuclear assets, ensure system utilizes the Air Force Non-Nuclear IDS Approved Equipment List. Contact AFSFC/S5G at afsfc.ibdss@us.af.mil for a copy of the letter or with any questions concerning these items.

For Army projects, contact the Electronic Security System Mandatory Center of Expertise (ESS MCX) for assistance in specifying requirements for IDS zones that will connect to an existing Integrated Commercial Intrusion Detection System (ICIDS). ESS MCX e-mail address is AskESSMCX@usace.army.mil

Provide a complete and integrated electronic security system (ESS) that meets the requirements of [_____]. ESS must be compatible with the Installation's central monitoring system and monitored [within the secure/protected area] [_____] [and] [at the Installation central monitoring station]. [[Installation's][_____] central monitoring system is manufactured by [______], model number [_____].] ESS consisting of the following subsystems and features:

a. Intrusion Detection System (IDS)

b. Access Control System (ACS)

c. Video Surveillance System (VSS)

d. Security Command Center (SCC)

e. Communications System

f. Security Lighting Systems

[ g. Medical Facility Systems

] Include materials not normally furnished by the manufacturer with the ESS equipment as specified in:

[ a. Section 33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION

][ b. Section 33 71 01 OVERHEAD TRANSMISSION AND DISTRIBUTION

][ c. Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM

] 2.2 PERFORMANCE REQUIREMENTS

Integrate the installed and operating subsystems into the overall ESS

SECTION 28 10 05 Page 23 system to detect intrusion, control access, video surveillance, visual verification, and perform as an entity, as specified below. Provide electronic equipment that complies with 47 CFR 15 and are suitable for the environment where they will be installed.

2.2.1 Growth Capability

Provide capability for modular ESS expansion of inputs, outputs, card readers, and remote-control stations with minimal equipment modification.

Software must be able to handle design requirements plus 25 [_____] percent spare capacity. Growth capability is not to be limited by the provided products.

2.2.2 Hazardous Locations

NOTE: Do not locate alarm reporting and display equipment within a hazardous area. If point sensors and volumetric sensors are required in hazardous areas, clearly identify their location on the plans.

Delete this paragraph if no hazardous areas exist in this project.

When located in areas where fire or explosion hazards exist, provide system components rated and installed according to Chapter 5 of NFPA 70 .

2.2.3 Maintainability

Provide components that can be maintained using commercially available tools and equipment. Arrange and assemble components to be readily accessible to maintenance personnel without compromising system defeat resistance and with no degradation in tamper protection, structural integrity, EMI or RFI attenuation, or line supervision after maintenance when it is performed in accordance with manufacturer's instructions.

2.2.4 Availability

Provide components rated for continuous operation. Provide solid-state electronic components mounted on printed circuit boards, conforming to UL 796 . Provide boards that are plug-in, quick-disconnect type. Do not impede maintenance with densely packed circuitry. Provide power-dissipating components with safety margins of not less than 25 percent with respect to dissipation ratings, maximum voltages, and current-carrying capacity. Provide heat sinks or other heat dissipation devices on appropriate components and assemblies. Provide solid-state type or hermetically sealed electromechanical type light duty relays and similar switching devices.

2.2.5 Fail-Safe Capability

Provide fail-safe capability in critical elements of the ESS including, but not be limited to, the capability to monitor communication link integrity and to provide self-test. Provide fault annunciation when diminished functional capabilities are detected. Annunciate fail-safe alarms to clearly distinguish from other types of alarms.

SECTION 28 10 05 Page 24

2.2.6 Line Supervision

Provide the same geographic resolution for fault isolation at the systems level as provided for intrusion detection. Provide either a static or dynamic system with active mode for line supervision of communication links of the ESS.

a. The static system must represent "no-alarm" always by the same signal, which is different than the originally transmitted signal.

b. The dynamic system must represent "no-alarm" with a signal which continually changes with time.

2.2.7 Power Loss Detection

NOTE: Verify if the Uninterruptible Power Supply (UPS) is detecting the loss of power to the critical component.

Detect AC and DC power loss and generate an alarm when a critical component of the system experiences temporary or permanent loss of power.

Annunciate the alarm in [the Secured Area] [_____] [and] [the Security Command Center] to clearly identify the component experiencing power loss.

2.2.8 Controls and Designations

Provide controls and designations in accordance with NEMA ICS 1 .

2.2.9 Special Test Equipment

Provide all special test equipment, special hardware, software, tools, instructions, and programming or initialization equipment needed to start or maintain any part of the system and its components. Special test equipment is defined as any test equipment not normally used in an electronics maintenance facility.

2.2.10 Electromagnetic Interference (EMI)

Configure and provide ESS components employing electromagnetic radiation constructed to provide minimal vulnerability to electronic countermeasures.

2.2.11 Electromagnetic Radiation (EMR)

NOTE: National Post Telephone and Telegraph is normally the approving authority for EMR components overseas.

Provide only ESS communication components which are [Federal Communications Commission (FCC)] [_____] licensed and approved. Provide system components which are electromagnetically compatible.

2.2.12 Interchangeability

Use off-the-shelf components which are physically, electrically, and functionally interchangeable with equivalent components as complete

SECTION 28 10 05 Page 25 items. Equivalent, replacement components must not require new or other component modification. Do not use custom designed or one-of-a-kind items. Interchangeable components or modules must not require trial and error matching in order to meet integrated system requirements, system accuracy, or restore complete system functionality.

2.2.13 Date and Time Generator

NOTE: Provide a time server for larger systems.

The ESS system date and time are to originate from [the ESS network time server] [GPS synchronization system with GPS satellite antenna][_____].

2.3 INTRUSION DETECTION SYSTEM (IDS)

The IDS primary function is to detect intrusion into secured areas.

Utilize a single database for all IDS programming data that seamlessly integrates with the ESS under a single operating environment. The IDS events must be viewable as separate or as a combined list of all ESS events. Control the IDS alarm monitoring through software control from the ESS.

a. Provide both supervised and non-supervised alarm point monitoring.

b. [Arm or disarm] [Secure or access] alarm points both manually and automatically by time of day, day of week or by operator command.

[ c. For classified assets, IDS installation related components and monitoring stations must comply with UL 2050 .

] 2.3.1 IDS Components

Provide components:

a. Premise Control Units (PCU)

b. Detection Sensors

c. Tamper Switches

d. Arm/Disarm Keypads

2.3.2 Detection Sensitivity

The sensitivity of the IDS must allow for the following:

a. Locating intrusions [within [100] [_____] meters 300 [______] feet zones along a line or perimeter] [to one side of the [facility] [building]]

b. Locating intrusions at individually protected assets or at an individual portal

c. Locating intrusions within the coverage on a single volumetric sensor

d. Locating failures or tampering at individual sensors

SECTION 28 10 05 Page 26

2.3.3 Detection Alarm and Reporting Capacity

NOTE: Select system capacity parameters based on the specific facility design requirements. System capacity should be expressed as a binary number.

Include a 25 percent expansion factor to accommodate changes in design caused by reconfiguration of equipment within interior spaces or renovation. The designer should select arming/disarming for Army projects and select secure/access for Air Force and Navy projects.

Collect, communicate, and display up to [12] [32] [64] [128] [256] [_____] sensor zone alarms [and to enable control of [one] [two] [_____] [card reader] [card reader with integral keypad] for [arming and disarming] [secure and access] [inside of the protected area with a delayed alarm] [outside of the protected area with instant alarm]].

Identify individual sensors in alarm if the sensor zone is a multiple alarm source combination. Annunciate a single alarm within [1] [2] [_____] seconds maximum, after sensor transducer or other detection device activation [except that alarms transmitted by radio frequency signaling must communicate in less than 3 seconds].

2.3.4 False Alarm Rate

The false alarm rate for each interior IDS zone must not exceed one false alarm per 30-day period. The false alarm rate for each exterior IDS zone must not exceed one false alarm per 24-hour period.

2.3.5 Nuisance Alarm Rate

The nuisance alarm rate for each interior IDS zone must not exceed three nuisance alarms per 30-day period. The nuisance alarm rate for each exterior IDS zone must not exceed three nuisance alarms per 24-hour period.

2.3.6 Premise Control Unit (PCU)

Install the PCU command processor in a tamper resistant enclosure that is specified in paragraph COMPONENT ENCLOSURE. Package the following with the PCU:

a. Power transformer

b. Battery(s)

c. Network connection cable

d. Keypad(s)

e. Keypad connection cable(s)

f. Additional components as required for full functionality

2.3.6.1 PCU Capabilities

Provide the PCU at a minimum but not limited to, the following

SECTION 28 10 05 Page 27 capabilities;

a. Expansion to a total of at least [10,000] [_____] user codes with [99] [_____] user profile definitions.

b. Support [4] [8] [16] [_____] keypads with alphanumeric display. Each keypad must be capable of [arming and disarming] [securing and accessing] any system area based on a pass code or access control card and or key FOB authorization. Provide keypad alphanumeric display with complete prompt messages during all stages of operation and system programming and display all relevant operating and test data.

c. Four [4] [_____] shift schedules per area.

d. A total of at least [100] [_____] programmable output relay schedules.

e. [32] [64] [_____] individual reporting areas.

NOTE: For installation where dial-up is the only feasible line, two lines of communication are to be used.

f. Data line supervision [or two separate lines of communication].

g. Two-man access code or credentials.

h. Support programming to require the same or different access code entered within a programmed delay time of [1 to 15] [_____] minutes after disarming before activating a silent ambush alarm.

i. Support area programming that disables schedule and time-of-day changes while system is armed so that area can only be disarmed during scheduled times.

j. Provide a minimum of a [4,000] [_____] event log buffer per PCU.

Record and hold alarm activity information in the log buffer until the ESS is connected and receives the information. Provide a software-configurable warning log buffer filling notification for PCU(s) configured with network switch capabilities.

k. Support a Network Interface Card (NIC) plug-in module with built in network router capable of 128 Bit AES Rijndael Encryption process certified by NIST (National Institute of Standards and Technology).

2.3.6.2 Overcurrent Protection and Indication

When overcurrent more than it is rated for is detected by the PCU, communication bus(es) and keypad(s) are to be shut down and an overcurrent notification LED lit to indicate the situation.

2.3.6.3 Manual and Self-Test

All alphanumeric keypad to include testing for: standby battery, alarm bell or siren, and communication to the Security Command Center (SCC).

Include provisions for an automatic, daily, weekly, 30 day, or up to 60 day communication link test from the PCU installation site to the SCC.

Include a provision for displaying the internal system power and wiring

SECTION 28 10 05 Page 28 conditions.

Include the following for internal monitoring points:

a. The bell circuit

b. AC power

c. Battery voltage level

d. Charging voltage

e. Panel box tamper

f. Phone trouble line 1

g. Phone trouble line 2

h. Transmit trouble

i. Network trouble

A battery test must be automatically performed to test the integrity of the standby battery by disconnecting the standby battery from the charging circuit and placing a load on the battery. Perform this test at an interval no greater than 180 days.

2.3.

This is the start of the file's text. The full file is on GovTribe.