Amendment_0002_W912QR26RA016_Plans0002 (1).pdf
PDF 7 MB Posted
- Solicitation number
- W912QR26RA016
About this file
This document is a comprehensive set of construction drawings and specifications for a 5-story UEPH (Unaccompanied Enlisted Personnel Housing) Barracks project at Fort Campbell, Kentucky, issued in February 2026 with amendments in April 2026. The project involves the design and construction of military residential housing with associated mechanical, electrical, telecommunications, and utility systems.
The facility comprises approximately 140 residential suites distributed across five floors with supporting common areas including mechanical rooms, electrical rooms, laundry facilities, fitness room, day room, and administrative spaces. The mechanical systems feature modular air-to-water heat pumps (MAWHP-1 and MAWHP-2) serving as the primary heating and cooling source, supplemented by dedicated outdoor air systems (DOAS-1 through DOAS-5) for ventilation and an electric backup boiler for heating. All heating and cooling is delivered via hydronic piping with fan coil units (FCUs) and cabinet unit heaters distributed throughout dwelling units and common areas. The electrical service consists of two main services: 1500 kVA at 208/120V and 2000 kVA at 480/277V, with extensive submetering for HVAC equipment, interior lighting, exterior lighting, and receptacles. The telecommunications infrastructure includes CAT6 copper cabling throughout with fiber optic connections, wireless access points in all suites, and a comprehensive grounding and bonding system compliant with TIA 607-D standards. Utility connections include water, sanitary sewer, fire protection lines, storm drainage, and force main systems, with all utilities owned and operated by Jacobs per the specifications. Building control systems utilize BACnet MSTP protocol with direct digital control for HVAC equipment, energy monitoring, and integration with the Fort Campbell Utility Monitoring and Control System (UMCS) via a Niagara Framework Supervisory Gateway, with all points and sequences of operation fully documented in the control system drawings.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Pl ot
D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
C
ER
TI
FI
ED
F
IN
AL
LO
U
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
FE
BR
U
AR
Y
FT
. C
AM
PB
EL
L, K
Y.
U
EP
H
B
AR
R
AC
KS
PN
FY
P2
Fi le
P at h:
4/
/2
7:
:5
AM
C
:\U se rs \H
2E D
D
KA
S\ D oc um en ts
\5
6_
R ev it2
5_
SI
TE
_U
EP
H
_h 2e dd ka s.
rv t
GI002
SH
EE
T
IN
D
EX
K.
SA
N
TO
S
K.
SA
N
TO
S
M .B
AR
R
Y
M .B
AR
R
Y
INDEX OF DRAWINGS -VOL. 1
SHEET NUMBER Sheet Name
GENERAL
GI000 COVER SHEET VOLUME 1
GI002 SHEET INDEX
GI003 SHEET INDEX
GI004 SITE AREA, LOCATION, AND VICINITY MAP
GI005 CONTRACTOR HAUL ROUTE
GI006 LIFE SAFETY / FIRE PROTECTION CODE REVIEW (FOR REFERENCE ONLY)
GI007 CODE COMPLIANCE SITE PLAN
GI008 FIRST FLOOR - LIFE SAFETY PLAN
GI009 SECOND FLOOR - LIFE SAFETY PLAN
GI010 THIRD FLOOR - LIFE SAFETY PLAN
GI011 FOURTH FLOOR - LIFE SAFETY PLAN
GI012 FIFTH FLOOR - LIFE SAFETY PLAN
GI013 OCCUPANT LOAD SCHEDULE - FIRST FLOOR
GI014 OCCUPANT LOAD SCHEDULE - SECOND FLOOR
GI015 OCCUPANT LOAD SCHEDULE - THIRD FLOOR
GI016 OCCUPANT LOAD SCHEDULE - FOURTH FLOOR
GI017 OCCUPANT LOAD SCHEDULE - FIFTH FLOOR
GEOTECHNICAL
B-001 SOIL AND ROCK CLASSIFICATION
B-101 BORING AND TEST PIT LOCATION PLAN
B-102 GEOPHYSICAL RESULTS 1
B-103 GEOPHYSICAL RESULTS 2
BB201 BORING LOGS AND TEST PITS
BB202 BORING LOGS AND TEST PITS
BB203 BORING LOGS AND TEST PITS
BB204 BORING LOGS AND TEST PITS
BB205 BORING LOGS AND TEST PITS
BB206 BORING LOGS AND TEST PITS
BB207 BORING LOGS AND TEST PITS
BS301 SOIL PROFILE 1
BS302 SOIL PROFILE 2
SURVEY MAPPING
VA101 AERIAL PHOTOGRAPH WITH SITE OVERLAY
VF101 OVERALL EXISTING CONDITIONS
VF102 EXISTING CONDITIONS
VF103 EXISTING CONDITIONS
VF104 EXISTING CONDITIONS
VF105 EXISTING CONDITIONS
VF106 EXISTING CONDITIONS
VF107 EXISTING CONDITIONS
VF401 CONTROL POINT DESCRIPTIONS
CIVIL
GC101 OVERALL EROSION CONTROL PLAN
GC102 EROSION CONTROL PLAN
GC103 EROSION CONTROL PLAN
GC104 EROSION CONTROL PLAN
GC105 EROSION CONTROL PLAN
GC501 EROSION CONTROL DETAIL
GC502 EROSION CONTROL DETAIL
GC503 EROSION CONTROL DETAIL
CD101 OVERALL DEMOLITION PLAN
CD102 DEMOLITION PLAN
CD103 DEMOLITION PLAN
CD104 DEMOLITION PLAN
CD105 DEMOLITION PLAN
CD106 DEMOLITION PLAN
CD107 DEMOLITION PLAN
CS101 OVERALL CIVIL SITE PLAN
CS102 CIVIL SITE PLAN
CS103 CIVIL SITE PLAN
CS104 CIVIL SITE PLAN
CS105 CIVIL SITE PLAN
CS401 OVERALL JOINT PLAN
CS402 JOINT PLAN
CS403 JOINT PLAN
CS404 JOINT PLAN
CS405 JOINT PLAN
CS501 CIVIL SITE DETAILS
CS502 CIVIL SITE DETAILS
CS503 CIVIL SITE DETAILS
CS504 CIVIL SITE DETAILS
CG101 OVERALL GRADING AND DRAINAGE PLAN
CG102 GRADING AND DRAINAGE PLAN
CG103 GRADING AND DRAINAGE PLAN
CG104 GRADING AND DRAINAGE PLAN
CG105 GRADING AND DRAINAGE PLAN
CG201 STORM SEWER PROFILES
CG202 STORM SEWER PROFILES
CG203 STORM SEWER PROFILES
CG501 GRADING DETAILS
CG502 GRADING DETAILS
CG503 GRADING DETAILS
CG504 GRADING DETAILS
CG505 GRADING DETAILS
CU101 OVERALL UTILITY PLAN
CU102 UTILITY PLAN
CU103 UTILITY PLAN
INDEX OF DRAWINGS -VOL. 1
SHEET NUMBER Sheet Name
A-151 FIFTH FLOOR PLAN - AREA 5A
A-152 FIFTH FLOOR PLAN - AREA 5B
A-153 FIFTH FLOOR PLAN - AREA 5C
A-160 ROOF PLAN
A-170 FIRST FLOOR REFLECTED CEILING PLAN - COMPREHENSIVE
A-171 FIRST FLOOR REFLECTED CEILING PLAN - AREA 1A
A-172 FIRST FLOOR REFLECTED CEILING PLAN - AREA 1B
A-173 FIRST FLOOR REFLECTED CEILING PLAN - AREA 1C
A-174 SECOND FLOOR REFLECTED CEILING PLAN - COMPREHENSIVE
A-175 SECOND FLOOR REFLECTED CEILING PLAN - AERA 2A
A-176 SECOND FLOOR REFLECTED CEILING PLAN - AERA 2B
A-177 SECOND FLOOR REFLECTED CEILING PLAN - AERA 2C
A-178 THIRD FLOOR REFLECTED CEILING PLAN - COMPREHENSIVE
A-179 THIRD FLOOR REFLECTED CEILING PLAN - AERA 3A
A-180 THIRD FLOOR REFLECTED CEILING PLAN - AERA 3B
A-181 THIRD FLOOR REFLECTED CEILING PLAN - AERA 3C
A-182 FOURTH FLOOR REFLECTED CEILING PLAN - COMPREHENSIVE
A-183 FOURTH FLOOR REFLECTED CEILING PLAN - AERA 4A
A-184 FOURTH FLOOR REFLECTED CEILING PLAN - AERA 4B
A-185 FOURTH FLOOR REFLECTED CEILING PLAN - AERA 4C
A-186 FIFTH FLOOR REFLECTED CEILING PLAN - COMPREHENSIVE
A-187 FIFTH FLOOR REFLECTED CEILING PLAN - AERA 5A
A-188 FIFTH FLOOR REFLECTED CEILING PLAN - AERA 5B
A-189 FIFTH FLOOR REFLECTED CEILING PLAN - AERA 5C
A-190 ENLARGED TYPICAL DWELLING UNITS - REFLECTED CEILING PLANS
A-201 EXTERIOR NORTH AND SOUTH ELEVATIONS
A-202 EXTERIOR WEST ELEVATION
A-203 EXTERIOR EAST ELEVATION
A-204 EXTERIOR ENLARGED NORTH ELEVATION
A-205 EXTERIOR ENLARGED SOUTH ELEVATION
A-301 BUILDING LONGITUDINAL & CROSS SECTIONS
A-311 WALL SECTIONS
A-312 CURTAIN WALL SECTIONS
A-401 ENLARGED COMMON AREA - FIRST FLOOR
A-402 ENLARGED COMMON AREA - FIRST FLOOR
A-403 ENLARGED COMMON AREA 2ND TO 5TH FLOOR
A-404 ENLARGED LAUNDRY ROOMS PLAN AND ELEVATIONS
A-405 ENLARGED FITNESS ROOM
A-411 ENLARGED TYPICAL DWELLING UNITS PLANS
A-412 ENLARGED KITCHEN / LIVING / BATHROOM PLANS AND ELEVATIONS AND SCHEDULE
A-413 ENLARGED ABA TOILET AND JANITOR AND DAYROOM ELEVATIONS AND SCHEDULE
A-414 ENLARGED CQ DESK PLANS AND ELEVATIONS AND CASEWORK SECTIONS
A-415 KITCHEN / DAYROOM / BATHROOM CASEWORK SECTIONS
A-420 ENLARGED STAIR PLANS
A-421 ENLARGED STAIR SECTIONS
A-422 ENLARGED STAIR PLANS
A-423 ENLARGED STAIR SECTIONS
A-424 ENLARGED STAIR PLANS
A-425 ENLARGED STAIR SECTIONS
A-426 STAIR DETAILS
A-431 ENLARGED ELEVATOR PLANS
A-432 ELEVATOR SECTIONS
A-433 ELEVATOR DETAILS
A-441 ENLARGED CANOPY PLANS AND SECTION AND DETAILS
A-442 ENLARGED MAIL KIOSK PLAN AND ELEVATIONS
A-443 ENLARGED ROOF PLANS - MAIL KIOSK AND BIKE STAND - SHADE STRUCTURES AND DETAILS
A-444 ENLARGED BUILDING SIGNAGE PLAN AND ELEVATIONS AND SECTIONS AND DETAILS
A-445 ENLARGED BIKE STAND SHADE STRUCTURE AND DETAILS
A-451 ENLARGED MECHANICAL YARD PLANS AND DETAILS
A-452 ENLARGED DUMPTER PLANS AND SECTION AND DETAILS
A-501 WALL SECTION DETAILS
A-511 ROOF DETAILS
A-512 ROOF ISOMETRIC DETAILS
A-513 ROOF ISOMETRIC DETAILS
A-514 ROOF HATCH SECTIONS AND PLAN
A-521 EXTERIOR PLAN DETAILS
A-522 INTERIOR PLAN & CEILING DETAILS
A-541 MISC DETAILS
A-601 PARTITION TYPES, SCHEDULE, AND DETAILS
A-602 FIRE-RATED PARTITION DETAILS (DWELLING UNIT)
A-603 FIRE-RATED PARTITION DETAILS (DWELLING UNIT)
A-604 FIRE-RATED PARTITION DETAILS
A-611 DOORS AND FRAMES SCHEDULE AND DETAILS - FIRST FLOOR 1 of 3 A-612 DOORS AND FRAMES SCHEDULE AND DETAILS - FIRST FLOOR 2 of 3 A-613 DOORS AND FRAMES SCHEDULE AND DETAILS - FIRST FLOOR 3 of 3 A-621 DOORS AND FRAMES SCHEDULE AND DETAILS - SECOND FLOOR 1 of 3 A-622 DOORS AND FRAMES SCHEDULE AND DETAILS - SECOND FLOOR 2 of 3 A-623 DOORS AND FRAMES SCHEDULE AND DETAILS - SECOND FLOOR 3 of 3 A-631 DOORS AND FRAMES SCHEDULE AND DETAILS - THIRD FLOOR 1 of 3 A-632 DOORS AND FRAMES SCHEDULE AND DETAILS - THIRD FLOOR 2 of 3 A-633 DOORS AND FRAMES SCHEDULE AND DETAILS - THIRD FLOOR 3 of 3 A-641 DOORS AND FRAMES SCHEDULE AND DETAILS - FOURTH FLOOR 1 of 3 A-642 DOORS AND FRAMES SCHEDULE AND DETAILS - FOURTH FLOOR 2 of 3 A-643 DOORS AND FRAMES SCHEDULE AND DETAILS - FOURTH FLOOR 3 of 3 A-651 DOORS AND FRAMES SCHEDULE AND DETAILS - FIFTH FLOOR 1 of 3 A-652 DOORS AND FRAMES SCHEDULE AND DETAILS - FIFTH FLOOR 2 of 3 A-653 DOORS AND FRAMES SCHEDULE AND DETAILS - FIFTH FLOOR 3 of 3
A-661 DOOR DETAILS - ALUMINUM STOREFRONT (S/F)
A-662 DOOR DETAILS - HOLLOW METAL (HM)
A-663 DOOR DETAILS - HOLLOW METAL (HM) & ALUMINUM CURTAIN GLASS WALL
A-671 WINDOW AND FRAMES SCHEDULES AND TYPES AND DETAILS
A-672 WINDOW AND FRAMES SCHEDULES AND TYPES AND DETAILS
A-681 ALUMINUM CURTAIN GLASS WALL TYPES & ELEVATIONS
A-682 ALUMINUM CURTAIN GLASS WALL DETAILS
A-683 ALUMINUM CURTAIN GLASS WALL DETAILS
A-691 LOUVER AND FRAMES SCHEDULES AND TYPES AND DETAILS
A-801 AIR BARRIER PLANS, SECTIONS, AND NOTES
Grand total: 264
INDEX OF DRAWINGS -VOL. 1
SHEET NUMBER Sheet Name
CU104 UTILITY PLAN
CU105 UTILITY PLAN
CU106 UTILITY PLAN
CU107 UTILITY PLAN
CU201 SANITARY SEWER PROFILES
CU202 WATER LINE PROFILE
CU501 UTILITY DETAILS
CU502 UTILITY DETAILS
SITE ELECTRICAL
ES101 ELECTRICAL SITE PLAN
ES102 AREA LIGHTING SITE PLAN
SITE TELECOMMUNICATION
TS101 TELECOMMUNICATIONS SITE PLAN
STRUCTURAL
S-001 GENERAL STRUCTURAL NOTES, DESIGN LOADS & ABBREVIATIONS
S-002 GENERAL STRUCTURAL NOTES
S-003 LIVE AND SNOW LOAD DIAGRAMS
S-004 WIND LOAD DIAGRAMS
S-005 HORIZONTAL BUILDING TIE DIAGRAMS
S-110 FOUNDATION PLAN - COMPREHENSIVE
S-111 FOUNDATION PLAN - AREA 1A
S-112 FOUNDATION PLAN - AREA 1B
S-113 FOUNDATION PLAN - AREA 1C
S-120 SECOND FLOOR FRAMING PLAN - COMPREHENSIVE
S-121 SECOND FLOOR FRAMING PLAN - AREA 2A
S-122 SECOND FLOOR FRAMING PLAN - AREA 2B
S-123 SECOND FLOOR FRAMING PLAN - AREA 2C
S-130 THIRD FLOOR FRAMING PLAN - COMPREHENSIVE
S-131 THIRD FLOOR FRAMING PLAN - AREA 3A
S-132 THIRD FLOOR FRAMING PLAN - AREA 3B
S-133 THIRD FLOOR FRAMING PLAN - AREA 3C
S-140 FOURTH FLOOR FRAMING PLAN - COMPREHENSIVE
S-141 FOURTH FLOOR FRAMING PLAN - AREA 4A
S-142 FOURTH FLOOR FRAMING PLAN - AREA 4B
S-143 FOURTH FLOOR FRAMING PLAN - AREA 4C
S-150 FIFTH FLOOR FRAMING PLAN - COMPREHENSIVE
S-151 FIFTH FLOOR FRAMING PLAN - AREA 5A
S-152 FIFTH FLOOR FRAMING PLAN - AREA 5B
S-153 FIFTH FLOOR FRAMING PLAN - AREA 5C
S-160 LOWER FRAMING PLAN - COMPREHENSIVE
S-161 LOWER ROOF FRAMING PLAN - AREA A
S-162 LOWER ROOF FRAMING PLAN - AREA B
S-163 LOWER ROOF FRAMING PLAN - AREA C
S-170 UPPER ROOF FRAMING PLAN - COMPREHENSIVE
S-171 UPPER ROOF FRAMING PLAN - AREA A
S-172 UPPER ROOF FRAMING PLAN - AREA B
S-173 UPPER ROOF FRAMING PLAN - AREA C
S-311 BRACED FRAME ELEVATIONS
S-312 BRACED FRAME ELEVATIONS
S-313 BRACED FRAME ELEVATIONS
S-314 BRACED FRAME ELEVATIONS
S-401 ENLARGED FOUNDATION PLANS
S-501 TYPICAL FOUNDATION DETAILS
S-502 TYPICAL FOUNDATION DETAILS
S-503 TYPICAL FOUNDATION DETAILS
S-504 TYPICAL FOUNDATION DETAIL
S-511 FOUNDATION SECTIONS AND DETAILS
S-521 TYPICAL FRAMING DETAILS
S-522 TYPICAL FRAMING DETAILS
S-523 TYPICAL FRAMING DETAILS
S-524 TYPICAL FRAMING DETAILS
S-531 FRAMING SECTIONS AND DETAILS
S-532 FRAMING SECTIONS AND DETAILS
S-533 FRAMING SECTIONS AND DETAILS
S-601 COLUMN SCHEDULE
S-901 3D REPRESENTATION
ARCHITECTURAL
A-001 GENERAL NOTES, ABBREVIATIONS
A-002 ABA ACCESSIBILITY GUIDELINES ( FOR REFERENCE ONLY )
A-003 SEALANT, MASONRY JOINTS & MISC. STANDARD DETAILS
A-110 FIRST FLOOR PLAN - COMPREHENSIVE
A-111 FIRST FLOOR PLAN - AREA 1A
A-112 FIRST FLOOR PLAN - AREA 1B
A-113 FIRST FLOOR PLAN - AREA 1C
A-120 SECOND FLOOR PLAN - COMPREHENSIVE
A-121 SECOND FLOOR PLAN - AREA 2A
A-122 SECOND FLOOR PLAN - AREA 2B
A-123 SECOND FLOOR PLAN - AREA 2C
A-130 THIRD FLOOR PLAN - COMPREHENSIVE
A-131 THIRD FLOOR PLAN - AREA 3A
A-132 THIRD FLOOR PLAN - AREA 3B
A-133 THIRD FLOOR PLAN - AREA 3C
A-140 FOURTH FLOOR PLAN - COMPREHENSIVE
A-141 FOURTH FLOOR PLAN - AREA 4A
A-142 FOURTH FLOOR PLAN - AREA 4B
A-143 FOURTH FLOOR PLAN - AREA 4C
A-150 FIFTH FLOOR PLAN - COMPREHENSIVE
AM
EN
D
M
EN
T
AP
R
IL
AM
EN
D
M
EN
T
AP
R
IL
W
2Q R
R
A0
_P la ns -0
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Pl ot
D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
C
ER
TI
FI
ED
F
IN
AL
LO
U
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
FE
BR
U
AR
Y
FT
. C
AM
PB
EL
L, K
Y.
U
EP
H
B
AR
R
AC
KS
PN
FY
P2
Fi le
P at h:
4/
/2
9:
:2
AM
C
:\U se rs \H
2E D
D
KA
S\ D oc um en ts
\5
6_
R ev it2
5_
SI
TE
_U
EP
H
_h 2e dd ka s.
rv t
GI003
SH
EE
T
IN
D
EX
K.
S
AN
TO
S
K.
S
AN
TO
S
M . B
AR
R
Y
M . B
AR
R
Y
INDEX OF DRAWINGS - VOL. 2
SHEET NUMBER Sheet Name
INTERIOR
I-110 1ST FLOOR FINISH AND SPECIAL ITEMS PLAN - COMPREHENSIVE
I-111 1ST FLOOR FINISH AND SPECIAL ITEMS PLAN - AREA 1A
I-112 1ST FLOOR FINISH AND SPECIAL ITEMS PLAN - AREA 1B
I-113 1ST FLOOR FINISH AND SPECIAL ITEMS PLAN - AREA 1C
I-120 2ND, 3RD, 4TH, & 5TH FLOOR FINISH AND SPECIAL ITEMS PLAN -
COMPREHENSIVE
I-121 2ND, 3RD, 4TH & 5TH FLOOR FINISH AND SPECIAL ITEMS PLAN - AREA 2A
I-122 2ND, 3RD, 4TH & 5TH FLOOR FINISH AND SPECIAL ITEMS PLAN - AREA 2B
I-123 2ND, 3RD, 4TH & 5TH FLOOR FINISH AND SPECIAL ITEMS PLAN - AREA 2C
I-401 ENLARGED BATHROOM AND KITCHEN PLAN - 1ST, 2ND, 3RD, 4TH, AND 5TH
FLOORS
I-402 ENLARGED CQ DESK PLANS AND ELEVATIONS - 1ST FLOOR
I-403 ENLARGED FLOOR TILING PLANS - 1ST FLOOR
I-404 ENLARGED FLOOR TILING PLANS - 1ST, 2ND, 3RD, 4TH, AND 5TH FLOORS
I-405 ENLARGED FLOOR TILING PLANS - 2ND, 3RD, 4TH, AND 5TH FLOORS
I-501 FLOOR AND WALL TRANSITION DETAILS
I-601 INTERIOR COLOR SCHEDULE
I-602 ROOM FINISH SCHEDULE
I-603 ROOM FINISH SCHEDULE
I-604 ROOM FINISH SCHEDULE
I-605 ROOM FINISH SCHEDULE
I-606 ROOM FINISH SCHEDULE
I-607 ROOM FINISH SCHEDULE
I-608 ROOM FINISH SCHEDULE
IF001 FURNITURE LEGEND
IF110 1ST FLOOR FURNITURE PLAN - COMPREHENSIVE
IF111 1ST FLOOR FURNITURE PLAN - AREA 1A
IF112 1ST FLOOR FURNITURE PLAN - AREA 1B
IF113 1ST FLOOR FURNITURE PLAN - AREA 1C
IF120 2ND, 3RD, 4TH & 5TH FLOOR FURNITURE PLAN - COMPREHENSIVE
IF121 2ND, 3RD, 4TH & 5TH FLOOR FURNITURE PLAN - AREA 2A
IF122 2ND, 3RD, 4TH & 5TH FLOOR FURNITURE PLAN - AREA 2B
IF123 2ND, 3RD, 4TH & 5TH FLOOR FURNITURE PLAN - AREA 2C
IG110 1ST FLOOR SIGNAGE PLAN - COMPREHENSIVE
IG111 1ST FLOOR SIGNAGE PLAN - AREA 1A
IG112 1ST FLOOR SIGNAGE PLAN - AREA 1B
IG113 1ST FLOOR SIGNAGE PLAN - AREA 1C
IG120 2ND FLOOR SIGNAGE PLAN - COMPREHENSIVE
IG121 2ND FLOOR SIGNAGE PLAN - AREA 2A
IG122 2ND FLOOR SIGNAGE PLAN - AREA 2B
IG123 2ND FLOOR SIGNAGE PLAN - AREA 2C
IG130 3RD FLOOR SIGNAGE PLAN - COMPREHENSIVE
IG131 3RD FLOOR SIGNAGE PLAN - AREA 3A
IG132 3RD FLOOR SIGNAGE PLAN - AREA 3B
IG133 3RD FLOOR SIGNAGE PLAN - AREA 3C
IG140 4TH FLOOR SIGNAGE PLAN - COMPREHENSIVE
IG141 4TH FLOOR SIGNAGE PLAN - AREA 4A
IG142 4TH FLOOR SIGNAGE PLAN - AREA 4B
IG143 4TH FLOOR SIGNAGE PLAN - AREA 4C
IG150 5TH FLOOR SIGNAGE PLAN - COMPREHENSIVE
IG151 5TH FLOOR SIGNAGE PLAN - AREA 5A
IG152 5TH FLOOR SIGNAGE PLAN - AREA 5B
IG153 5TH FLOOR SIGNAGE PLAN - AREA 5C
IG501 SIGNAGE DETAILS
IG502 SIGNAGE DETAILS
IG601 SIGNAGE SCHEDULE
FIRE PROTECTION
FP001 GENERAL NOTES, ABBREVIATIONS, AND LEGEND
FP110 FIRST FLOOR PLAN - COMPREHENSIVE
FP111 FIRST FLOOR PLAN - AREA 1A
FP112 FIRST FLOOR PLAN - AREA 1B
FP113 FIRST FLOOR PLAN - AREA 1C
FP120 SECOND FLOOR PLAN - COMPREHENSIVE
FP121 SECOND FLOOR PLAN - AREA 2A
FP122 SECOND FLOOR PLAN - AREA 2B
FP123 SECOND FLOOR PLAN - AREA 2C
FP130 THIRD FLOOR PLAN - COMPREHENSIVE
FP131 THIRD FLOOR PLAN - AREA 3A
FP132 THIRD FLOOR PLAN - AREA 3B
FP133 THIRD FLOOR PLAN - AREA 3C
FP140 FOURTH FLOOR PLAN - COMPREHENSIVE
FP141 FOURTH FLOOR PLAN - AREA 4A
FP142 FOURTH FLOOR PLAN - AREA 4B
FP143 FOURTH FLOOR PLAN - AREA 4C
FP150 FIFTH FLOOR PLAN - COMPREHENSIVE
FP151 FIFTH FLOOR PLAN - AREA 5A
FP152 FIFTH FLOOR PLAN - AREA 5B
FP153 FIFTH FLOOR PLAN - AREA 5C
FP401 FIRE PROTECTION ENLARGED PUMP ROOM PLANS
FP402 FIRE PROTECTION STANDPIPE SECTIONS
FP403 FIRE PROTECTION CORRIDOR REMOTE SECTIONS
FP501 DETAILS
FP502 DETAILS
FP601 FIRE PROTECTION SCHEDULES
FP901 FIRE SUPPRESSION RISER DIAGRAM
FIRE ALARM
FA-001 FIRE ALARM AND MASS NOTIFICATION LEGEND
FA-101 FIRST FLOOR FAMNS PLAN - BUILDING EXTERIOR
FA-102 FIRST FLOOR FAMNS PLAN ENLARGED AREA "A"
FA-103 FIRST FLOOR FAMNS PLAN ENLARGED AREA "B"
FA-104 FIRST FLOOR FAMNS PLAN ENLARGED AREA "C"
FA-105 SECOND THRU FIFTH FLOOR FAMNS PLAN ENLARGED AREA "A"
FA-106 SECOND THRU FIFTH FLOOR FAMNS PLAN ENLARGED AREA "B"
FA-107 SECOND THRU FIFTH FLOOR FAMNS PLAN ENLARGED AREA "C"
FA-501 FIRE ALARM/MASS NOTIFICATION SYSTEMS SEQUENCE OF OPERATION MATRIX
FA-701 FIRE ALARM/MASS NOTIFICATION RISER DIAGRAM
INDEX OF DRAWINGS - VOL. 2
SHEET NUMBER Sheet Name
PLUMBING
P-001 GENERAL NOTES, ABBREVIATIONS, AND LEGEND
P-110 FIRST FLOOR SANITARY PIPING PLAN - COMPREHENSIVE
P-111 FIRST FLOOR SANITARY PIPING PLAN - AREA 1A
P-112 FIRST FLOOR SANITARY PIPING PLAN - AREA 1B
P-113 FIRST FLOOR SANITARY PIPING PLAN - AREA 1C
P-114 FIRST FLOOR DOMESTIC PIPING PLAN - COMPREHENSIVE
P-115 FIRST FLOOR DOMESTIC PIPING PLAN - AREA 1A
P-116 FIRST FLOOR DOMESTIC PIPING PLAN - AREA 1B
P-117 FIRST FLOOR DOMESTIC PIPING PLAN - AREA 1C
P-118 FIRST FLOOR RADON PLAN
P-120 SECOND FLOOR SANITARY PIPING PLAN - COMPREHENSIVE
P-121 SECOND FLOOR SANITARY PIPING PLAN - AREA 2A
P-122 SECOND FLOOR SANITARY PIPING PLAN - AREA 2B
P-123 SECOND FLOOR SANITARY PIPING PLAN - AREA 2C
P-124 SECOND FLOOR DOMESTIC PIPING PLAN - COMPREHENSIVE
P-125 SECOND FLOOR DOMESTIC PIPING PLAN - AREA 2A
P-126 SECOND FLOOR DOMESTIC PIPING PLAN - AREA 2B
P-127 SECOND FLOOR DOMESTIC PIPING PLAN - AREA 2C
P-130 THIRD FLOOR SANITARY PIPING PLAN - COMPREHENSIVE
P-131 THIRD FLOOR SANITARY PIPING PLAN - AREA 3A
P-132 THIRD FLOOR SANITARY PIPING PLAN - AREA 3B
P-133 THIRD FLOOR SANITARY PIPING PLAN - AREA 3C
P-134 THIRD FLOOR DOMESTIC PIPING PLAN - COMPREHENSIVE
P-135 THIRD FLOOR DOMESTIC PIPING PLAN - AREA 3A
P-136 THIRD FLOOR DOMESTIC PIPING PLAN - AREA 3B
P-137 THIRD FLOOR DOMESTIC PIPING PLAN - AREA 3C
P-140 FOURTH FLOOR SANITARY PIPING PLAN - COMPREHENSIVE
P-141 FOURTH FLOOR SANITARY PIPING PLAN - AREA 4A
P-142 FOURTH FLOOR SANITARY PIPING PLAN - AREA 4B
P-143 FOURTH FLOOR SANITARY PIPING PLAN - AREA 4C
P-144 FOURTH FLOOR DOMESTIC PIPING PLAN - COMPREHENSIVE
P-145 FOURTH FLOOR DOMESTIC PIPING PLAN - AREA 4A
P-146 FOURTH FLOOR DOMESTIC PIPING PLAN - AREA 4B
P-147 FOURTH FLOOR DOMESTIC PIPING PLAN - AREA 4C
P-150 FIFTH FLOOR SANITARY PIPING PLAN - COMPREHENSIVE
P-151 FIFTH FLOOR SANITARY PIPING PLAN - AREA 5A
P-152 FIFTH FLOOR SANITARY PIPING PLAN - AREA 5B
P-153 FIFTH FLOOR SANITARY PIPING PLAN - AREA 5C
P-154 FIFTH FLOOR DOMESTIC PIPING PLAN - COMPREHENSIVE
P-155 FIFTH FLOOR DOMESTIC PIPING PLAN - AREA 5A
P-156 FIFTH FLOOR DOMESTIC PIPING PLAN - AREA 5B
P-157 FIFTH FLOOR DOMESTIC PIPING PLAN - AREA 5C
P-401 ENLARGED MECHANICAL ROOM PLANS
P-402 ENLARGED MECHANICAL ROOM PLANS
P-403 ENLARGED MECHANICAL ROOM PLANS
P-404 ENLARGED DOMESTIC PIPING PLANS
P-405 ENLARGED SANITARY PIPING PLANS
P-501 PLUMBING DETAILS
P-502 PLUMBING DETAILS
P-503 PLUMBING DETAILS
P-504 PLUMBING DETAILS
P-601 EQUIPMENT SCHEDULES
P-602 EQUIPMENT SCHEDULES
P-701 DOMESTIC HOT WATER SYSTEM CONTROLS
P-702 DOMESTIC HOT WATER SYSTEM CONTROLS
P-703 BOOSTER PUMP CONTROLS
P-901 FIRST FLOOR SANITARY PIPING RISER DIAGRAM
P-902 SECOND FLOOR SANITARY PIPING RISER DIAGRAM
P-903 THIRD FLOOR SANITARY PIPING RISER DIAGRAM
P-904 FOURTH FLOOR SANITARY PIPING RISER DIAGRAM
P-905 FIFTH FLOOR SANITARY PIPING RISER DIAGRAM
P-906 FIRST FLOOR DOMESTIC PIPING RISER DIAGRAM
P-907 SECOND FLOOR DOMESTIC PIPING RISER DIAGRAM
P-908 THIRD FLOOR DOMESTIC PIPING RISER DIAGRAM
P-909 FOURTH FLOOR DOMESTIC PIPING RISER DIAGRAM
P-910 FIFTH FLOOR DOMESTIC PIPING RISER DIAGRAM
MECHANICAL
M-001 GENERAL NOTES, ABBREVIATIONS, AND LEGEND
M-110 FIRST FLOOR HVAC DUCTWORK PLAN - COMPREHENSIVE
M-111 FIRST FLOOR HVAC DUCTWORK PLAN - AREA 1A
M-112 FIRST FLOOR HVAC DUCTWORK PLAN - AREA 1B
M-113 FIRST FLOOR HVAC DUCTWORK PLAN - AREA 1C
M-114 FIRST FLOOR HVAC PIPING PLAN - COMPREHENSIVE
M-115 FIRST FLOOR HVAC PIPING PLAN - AREA 1A
M-116 FIRST FLOOR HVAC PIPING PLAN - AREA 1B
M-117 FIRST FLOOR HVAC PIPING PLAN - AREA 1C
M-120 SECOND FLOOR HVAC DUCTWORK PLAN - COMPREHENSIVE
M-121 SECOND FLOOR HVAC DUCTWORK PLAN - AREA 2A
M-122 SECOND FLOOR HVAC DUCTWORK PLAN - AREA 2B
M-123 SECOND FLOOR HVAC DUCTWORK PLAN - AREA 2C
M-124 SECOND FLOOR HVAC PIPING PLAN - COMPREHENSIVE
M-125 SECOND FLOOR HVAC PIPING PLAN - AREA 2A
M-126 SECOND FLOOR HVAC PIPING PLAN - AREA 2B
M-127 SECOND FLOOR HVAC PIPING PLAN - AREA 2C
M-130 THIRD FLOOR HVAC DUCTWORK PLAN - COMPREHENSIVE
M-131 THIRD FLOOR HVAC DUCTWORK PLAN - AREA 3A
M-132 THIRD FLOOR HVAC DUCTWORK PLAN - AREA 3B
M-133 THIRD FLOOR HVAC DUCTWORK PLAN - AREA 3C
M-134 THIRD FLOOR HVAC PIPING PLAN - COMPREHENSIVE
M-135 THIRD FLOOR HVAC PIPING PLAN - AREA 3A
M-136 THIRD FLOOR HVAC PIPING PLAN - AREA 3B
M-137 THIRD FLOOR HVAC PIPING PLAN - AREA 3C
M-140 FOURTH FLOOR HVAC DUCTWORK PLAN - COMPREHENSIVE
M-141 FOURTH FLOOR HVAC DUCTWORK PLAN - AREA 4A
M-142 FOURTH FLOOR HVAC DUCTWORK PLAN - AREA 4B
M-143 FOURTH FLOOR HVAC DUCTWORK PLAN - AREA 4C
M-144 FOURTH FLOOR HVAC PIPING PLAN - COMPREHENSIVE
M-145 FOURTH FLOOR HVAC PIPING PLAN - AREA 4A
M-146 FOURTH FLOOR HVAC PIPING PLAN - AREA 4B
M-147 FOURTH FLOOR HVAC PIPING PLAN - AREA 4C
M-150 FIFTH FLOOR HVAC DUCTWORK PLAN - COMPREHENSIVE
M-151 FIFTH FLOOR HVAC DUCTWORK PLAN - AREA 5A
M-152 FIFTH FLOOR HVAC DUCTWORK PLAN - AREA 5B
M-153 FIFTH FLOOR HVAC DUCTWORK PLAN - AREA 5C
M-154 FIFTH FLOOR HVAC PIPING PLAN - COMPREHENSIVE
M-155 FIFTH FLOOR HVAC PIPING PLAN - AREA 5A
M-156 FIFTH FLOOR HVAC PIPING PLAN - AREA 5B
INDEX OF DRAWINGS - VOL. 2
SHEET NUMBER Sheet Name
M-157 FIFTH FLOOR HVAC PIPING PLAN - AREA 5C
M-301 MECHANICAL SECTIONS
M-401 FIRST FLOOR MECHANICAL ROOM
M-402 SECOND AND THIRD FLOOR MECHANICAL ROOMS
M-403 ENLARGED HVAC PLAN
M-501 MECHANICAL DETAILS
M-502 MECHANICAL DETAILS
M-503 MECHANICAL DETAILS
M-504 MECHANICAL DETAILS
M-505 MECHANICAL DETAILS
M-601 MECHANICAL EQUIPMENT SCHEDULES
M-602 MECHANICAL EQUIPMENT SCHEDULES
M-603 MECHANICAL EQUIPMENT SCHEDULES
M-604 MECHANICAL EQUIPMENT SCHEDULES
M-605 MECHANICAL EQUIPMENT SCHEDULE
M-700 HVAC CONTROLS LEGEND
M-701 POINTS SCHEDULE INSTRUCTIONS
M-702 CONTROL SYSTEM NETWORK
M-703 MAWHP-1 & 2 CONTROL SCHEMATIC
M-704 MAWHP SEQUENCE OF OPERATION & LADDER DIAGRAM
M-705 MAWHP CONTROL POINTS SCHEDULE
M-706 MAWHP PRIMARY & SECONDARY PUMP CONTROL POINTS SCHEDULE
M-707 DOAS-1 THRU DOAS-5 CONTROL SCHEMATIC
M-708 DOAS LADDER DIAGRAM
M-709 DOAS SEQUENCE OF OPERATION
M-710 DOAS CONTROL POINTS SCHEDULE
M-711 MAKE-UP AIR UNIT CONTROL SCHEMATIC
M-712 MAKE-UP AIR UNIT LOGIC DIAGRAMS & POINT SCHEDULE
M-713 FCU SCHEMATIC AND SEQUENCE OF OPERATION
M-714 FCU POINTS SCHEDULE
M-715 CABINET/UNIT HEATER CONTROLS
M-716 ENERGY CONTROLS MONITORING
M-717 ENERGY CONTROLS MONITORING
ELECTRICAL
E-001 LEGEND AND ABBREVIATIONS
E-101 FIRST FLOOR LIGHTING PLAN
E-102 FIRST FLOOR LIGHTING PLAN ENLARGED AREA "A"
E-103 FIRST FLOOR LIGHTING PLAN ENLARGED AREA "B"
E-104 FIRST FLOOR LIGHTING PLAN ENLARGED AREA "C"
E-105 SECOND FLOOR LIGHTING PLAN
E-106 SECOND FLOOR LIGHTING PLAN ENLARGED AREA "A"
E-107 SECOND FLOOR LIGHTING PLAN ENLARGED AREA "B"
E-108 SECOND FLOOR LIGHTING PLAN ENLARGED AREA "C"
E-109 THIRD FLOOR LIGHTING PLAN
E-110 THIRD FLOOR LIGHTING PLAN ENLARGED AREA "A"
E-111 THIRD FLOOR LIGHTING PLAN ENLARGED AREA "B"
E-112 THIRD FLOOR LIGHTING PLAN ENLARGED AREA "C"
E-113 FOURTH FLOOR LIGHTING PLAN
E-114 FOURTH FLOOR LIGHTING PLAN ENLARGED AREA "A"
E-115 FOURTH FLOOR LIGHTING PLAN ENLARGED AREA "B"
E-116 FOURTH FLOOR LIGHTING PLAN ENLARGED AREA "C"
E-117 FIFTH FLOOR LIGHTING PLAN
E-118 FIFTH FLOOR LIGHTING PLAN ENLARGED AREA "A"
E-119 FIFTH FLOOR LIGHTING PLAN ENLARGED AREA "B"
E-120 FIFTH FLOOR LIGHTING PLAN ENLARGED AREA "C"
E-121 FIRST FLOOR POWER PLAN - COMPREHENSIVE
E-122 FIRST FLOOR POWER PLAN ENLARGED AREA "A"
E-123 FIRST FLOOR POWER PLAN ENLARGED AREA "B"
E-124 FIRST FLOOR POWER PLAN ENLARGED AREA "C"
E-125 SECOND FLOOR POWER PLAN - COMPREHENSIVE
E-126 SECOND FLOOR POWER PLAN ENLARGED AREA "A"
E-127 SECOND FLOOR POWER PLAN ENLARGED AREA "B"
E-128 SECOND FLOOR POWER PLAN ENLARGED AREA "C"
E-129 THIRD FLOOR POWER PLAN - COMPREHENSIVE
E-130 THIRD FLOOR POWER PLAN ENLARGED AREA "A"
E-131 THIRD FLOOR POWER PLAN ENLARGED AREA "B"
E-132 THIRD FLOOR POWER PLAN ENLARGED AREA "C"
E-133 FOURTH FLOOR POWER PLAN - COMPREHENSIVE
E-134 FOURTH FLOOR POWER PLAN ENLARGED AREA "A"
E-135 FOURTH FLOOR POWER PLAN ENLARGED AREA "B"
E-136 FOURTH FLOOR POWER PLAN ENLARGED AREA "C"
E-137 FIFTH FLOOR POWER PLAN - COMPREHENSIVE
E-138 FIFTH FLOOR POWER PLAN ENLARGED AREA "A"
E-139 FIFTH FLOOR POWER PLAN ENLARGED AREA "B"
E-140 FIFTH FLOOR POWER PLAN ENLARGED AREA "C"
E-150 MECHANICAL FIRST FLOOR POWER PLAN - COMPREHENSIVE
E-151 MECHANICAL FIRST FLOOR POWER PLAN ENLARGED AREA "A"
E-152 MECHANICAL FIRST FLOOR POWER PLAN ENLARGED AREA "B"
E-153 MECHANICAL FIRST FLOOR POWER PLAN ENLARGED AREA "C"
E-154 MECHANICAL SECOND FLOOR POWER PLAN - COMPREHENSIVE
E-155 MECHANICAL SECOND FLOOR POWER PLAN ENLARGED AREA "A"
E-156 MECHANICAL SECOND FLOOR POWER PLAN ENLARGED AREA "B"
E-157 MECHANICAL SECOND FLOOR POWER PLAN ENLARGED AREA "C"
E-158 MECHANICAL THIRD FLOOR POWER PLAN - COMPREHENSIVE
E-159 MECHANICAL THIRD FLOOR POWER PLAN ENLARGED AREA "A"
E-160 MECHANICAL THIRD FLOOR POWER PLAN ENLARGED AREA "B"
E-161 MECHANICAL THIRD FLOOR POWER PLAN ENLARGED AREA "C"
E-162 MECHANICAL FOURTH FLOOR POWER PLAN - COMPREHENSIVE
E-163 MECHANICAL FOURTH FLOOR POWER PLAN ENLARGED AREA "A"
E-164 MECHANICAL FOURTH FLOOR POWER PLAN ENLARGED AREA "B"
E-165 MECHANICAL FOURTH FLOOR POWER PLAN ENLARGED AREA "C"
E-166 MECHANICAL FIFTH FLOOR POWER PLAN - COMPREHENSIVE
E-167 MECHANICAL FIFTH FLOOR POWER PLAN ENLARGED AREA "A"
E-168 MECHANICAL FIFTH FLOOR POWER PLAN ENLARGED AREA "B"
E-169 MECHANICAL FIFTH FLOOR POWER PLAN ENLARGED AREA "C"
E-170 LIGHTNING PROTECTION PLAN VIEW
E-401 ENLARGED PLAN VIEWS - TYPICAL SUITE AND LAUNDRY SPACES
E-402 ENLARGED PLAN VIEWS - 1ST AND 2ND FLOOR ELECTRICAL ROOM
E-403 ENLARGED PLAN VIEWS - 3RD TO 5TH FLOOR ELECTRICAL ROOMS
E-404 ENLARGED PLAN VIEWS - 1ST FLOOR MECHANICAL AND PUMP ROOMS
E-405 ENLARGED PLAN VIEWS - 2ND FLOOR MECHANICAL ROOM AND 5TH FLOOR
ELEVATOR CONTROL ROOM
E-406 ENLARGED PLAN VIEWS - 3RD FLOOR MECHANICAL ROOM
E-407 ENLARGED PLAN VIEWS - 4TH FLOOR MECHANICAL ROOM
E-408 ENLARGED PLAN VIEWS - 5TH FLOOR MECHANICAL ROOM
E-409 SECTIONAL VIEWS - STAIRWELL POWER AND LIGHTS - ALL FLOORS
INDEX OF DRAWINGS - VOL. 2
SHEET NUMBER Sheet Name
E-410 SECTIONAL VIEWS - ELEVATOR SUMP PIT AND TOH MECHANICAL
E-411 SECTIONAL VIEWS - ELECTRICAL ROOM ARRANGEMENTS WITH FEEDER
CONDUITS
E-501 INTERIOR LED LIGHTING SCHEDULE
E-502 LIGHTING AND SWITCHED OUTLET CONTROL DETAILS
E-503 LIGHTNING PROTECTION DETAILS
E-601 RISER DIAGRAM - 208/120V POWER SYSTEM
E-602 RISER DIAGRAM - 480/277V POWER SYSTEM
E-603 RISER DIAGRAM - MECHANICAL POWER SYSTEM
E-604 ONE-LINE DIAGRAMS
E-605 THREE PHASE FEEDER SCHEDULE AND MAIN GROUND BUS DETAIL
E-606 SINGLE PHASE SUITE FEEDER SCHEDULES
E-607 MECHANICAL AND HVAC ELECTRICAL LOAD SCHEDULE
E-608 PANEL SCHEDULES - TYPICAL SUITE LOAD CENTER AND 1ST/2ND FLOOR
COMMON AREAS
E-609 PANEL SCHEDULES - 3RD-5TH FLOOR COMMON AREAS
E-610 PANEL SCHEDULES - 1ST - 2ND FLOOR TELECOM ROOM PANELS
E-611 PANEL SCHEDULES - 3RD - 5TH FLOOR TELECOM ROOM PANELS
E-612 PANEL SCHEDULES - 1ST FLOOR 208/120V SUITE FEEDER AND LAUNDRY
PANELS
E-613 PANEL SCHEDULES - 2ND FLOOR 208/120V SUITE FEEDER AND LAUNDRY
PANELS
E-614 PANEL SCHEDULES - 3RD FLOOR 208/120V SUITE FEEDER AND LAUNDRY
PANELS
E-615 PANEL SCHEDULES - 4TH FLOOR 208/120V SUITE FEEDER AND LAUNDRY
PANELS
E-616 PANEL SCHEDULES - 5TH FLOOR 208/120V SUITE FEEDER AND LAUNDRY
PANELS
E-617 PANEL SCHEDULES - 1ST - 3RD FLOOR MECHANICAL AND DOMESTIC WATER
E-618 PANEL SCHEDULES - 4TH - 5TH FLOOR MECHANICAL AND DOMESTIC WATER
E-619 SCHEDULES - 480V AND 208V SERVICE ENTRANCE / SWITCHGEAR
TELECOMMUNICATIONS
T-001 GENERAL TELECOMMUNICATIONS NOTES
T-101 FIRST FLOOR TELECOMMUNICATIONS PLAN - COMPREHENSIVE
T-102 FIRST FLOOR TELECOMMUNICATIONS PLAN ENLARGED AREA "A"
T-103 FIRST FLOOR TELECOMMUNICATIONS PLAN ENLARGED AREA "B"
T-104 FIRST FLOOR TELECOMMUNICATIONS PLAN ENLARGED AREA "C"
T-105 SECOND FLOOR TELECOMMUNICATIONS PLAN - COMPREHENSIVE
T-106 SECOND FLOOR TELECOMMUNICATIONS PLAN ENLARGED AREA "A"
T-107 SECOND FLOOR TELECOMMUNICATIONS PLAN ENLARGED AREA "B"
T-108 SECOND FLOOR TELECOMMUNICATIONS PLAN ENLARGED AREA "C"
T-109 THIRD FLOOR TELECOMMUNICATIONS PLAN - COMPREHENSIVE
T-110 THIRD FLOOR TELECOMMUNICATIONS PLAN ENLARGED AREA "A"
T-111 THIRD FLOOR TELECOMMUNICATIONS PLAN ENLARGED AREA "B"
T-112 THIRD FLOOR TELECOMMUNICATIONS PLAN ENLARGED AREA "C"
T-113 FOURTH FLOOR TELECOMMUNICATIONS PLAN - COMPREHENSIVE
T-114 FOURTH FLOOR TELECOMMUNICATIONS PLAN ENLARGED AREA "A"
T-115 FOURTH FLOOR TELECOMMUNICATIONS PLAN ENLARGED AREA "B"
T-116 FOURTH FLOOR TELECOMMUNICATIONS PLAN ENLARGED AREA "C"
T-117 FIFTH FLOOR TELECOMMUNICATIONS PLAN - COMPREHENSIVE
T-118 FIFTH FLOOR TELECOMMUNICATIONS PLAN ENLARGED AREA "A"
T-119 FIFTH FLOOR TELECOMMUNICATIONS PLAN ENLARGED AREA "B"
T-120 FIFTH FLOOR TELECOMMUNICATIONS PLAN ENLARGED AREA "C"
T-401 ENLARGED TELECOM ROOM PLANS
T-402 FIRST AND SECOND FLOOR TELECOMMUNICATIONS SECTION VIEWS
T-403 THIRD AND FOURTH FLOOR TELECOMMUNICATIONS SECTION VIEWS
T-404 FIFTH FLOOR TELECOMMUNICATIONS SECTION VIEWS
T-501 TELECOM OSP ENTRANCE AND GROUNDING DETAILS
T-502 TELECOM GROUNDING AND MARKING DETAILS
T-503 TELECOM VOICE AND DATA OUTLET DETAILS
T-504 DOOR ALARM RISER AND DETAILS
Grand total: 355
INDEX OF DRAWINGS - VOL 2
SHEET NUMBER Sheet Name
GENERAL
GI001 COVER SHEET VOLUME 2
GI002 SHEET INDEX
GI003 SHEET INDEX
AM
EN
D
M
EN
T
AP
R
IL
W
2Q R
R
A0
_P la ns -0
S
CB
D
S
CB
S
CBCB
S
CB
SS
CB
S
S
CB
C C
CB
CB
S
S
S
COMMCOMMCOMMCOMMCOMMCOMMCOMMCOMMCOMMCOMMCOMMCOMMCOMMCOMMCOMM
SD SD
SD SD SD
SD
SD
SDSDSDSD
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SAN SAN SAN SAN SAN
SA
N
SA
N
SAN
SAN
SAN
SAN
SAN
SANSANSANSANSAN
SD
SD
SD
SD
SD
SD
SD
W
W
W W
W
W
W W
WW W
W
SD
SD SD
SD
SD
SD
SD
CB
CB
CB CB
CB CB CB CB
CB CB CB
CB
CB
CB
CB
CB
SD
SD
CB CB CB CBSD SD CB
SD
CB
CB
CB
CB CB
SD
SD
CB
CB
SD
CB
CB
CB
CB
STSTST
ST ST ST
ST ST ST
ST ST ST
ST
ST
ST
ST
ST
ST
W W W W W W W W W W
W W
W W
W W
W W
W W
W
WWWWWWW
W W
W W
W W
W W
W W
W W W
W W
W W
W
PIV
SAN
SA
N
SA
N
S
SCO
F
SSSSSSSS
WWWWWWW
5 STORY UEPH
BARRACKS
E
ES
5 STORY UEPH
BARRACKS
SS SS SS SS SS SS SS SS S
CU102 CU103
CU105 CU106
CU104
CU107
GENERAL SHEET NOTES - UTILITY
1. CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL UTILITIES AND FIELD
VERIFYING ALL EXISTING UTILITIES. THE CONTRACTING OFFICER SHALL BE
NOTIFIED OF ANY CONFLICTS OR DISCREPANCIES PRIOR TO INSTALLATION.
2. LOCATION OF EXISTING UTILITIES ARE PROVIDED FROM SURVEY, BASE MAPS,
AND UTILITY FEATURES. ACTUAL LOCATION MUST BE VERIFIED BY
CONTRACTOR IN THE FIELD.
3. SANITARY SEWER AND WATER UTILITIES ARE OWNED AND OPERATED BY
JACOBS.
4. SEE SHEETS CU501-502 FOR UTILITY DETAILS.
5. SEE SHEETS CU201-202 FOR UTILITY PROFILES.
6. SEE CG SHEET SERIES FOR GRADING AND STORM SEWER INFORMATION.
7. JACOBS TO APPLY THRUST BLOCKS TO WATER MAIN UNTIL 5 FEET OUTSIDE OF
THE BUILDING BASED ON CH2M DETAIL. SEE SHEET CU502 DETAIL A1.
8. ALL EXISTING AND PROPOSED MANHOLES, VALVE BOXES, HANDHOLES,
CLEANOUTS, FIRE HYDRANTS, CASTINGS, AND ANY OTHER APPURTENANCE
MUST BE ADJUSTED TO MATCH FINISHED GRADE.
9. CONTRACTOR MUST BE VACATED FROM THE FY27 UEPH BARRACKS WORK SITE
PRIOR TO FY27 BARRACKS AWARD (MAY 2027).
10. FOR ELECTRICAL AND TELECOMMUNICATION SITE PLANS, SEE SHEET SERIES ES
AND TS RESPECTIVELY.
11. AT THE BUILDING CONNECTION, THE WATER LINE MUST HAVE 54 INCHES OF
COVER AT MINIMUM IN ORDER TO PASS UNDER THE GRADE BEAMS.
KEYPLAN
102 103
106105
LEGEND - UTILTIY
CONTRACTOR WORK LIMITS AND FY27 DEMARCATION
WATER LINE SIZE AS NOTED
FIRE WATER LINE AS NOTED
SANITARY LINE - 8 INCH SDR35 PVC
FORCE MAIN - 6 INCH C900 PVC
SANITARY MANHOLE, SEE SHEET CU502 DETAIL A8
SANITARY CLEANOUT, SEE SHEET CU501 DETAIL A15
FIRE HYDRANT, SEE SHEET CU501 DETAIL A1
POST INDICATOR VALVE, SEE SHEET CU501 DETAIL H8
WATER LINE GATE VALVE, SIZE AS NOTED
(CONTRACTOR TO CONFIRM SIZES OF EXISTING WATER
LINES WHERE GATE VALVES ARE TO BE INSTALLED)
WW
FF
SAN
S
CO
PIV
SSSS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
E
SHEET ID
US Army Corps of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R
LO
U
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
FE
B
AN
SI
D
FT
. C
AM
PB
EL
L, K Y
U
EP
H B
AR
R
AC
KS
FY
, P N
, P
C
ER
TI
FI
ED
F
IN
AL
S.
M
AC
FA
R
LA
N D
C . C
AR
TE
R
C . C
AR
TE
R
M . B
AR
Y
O
VE
R
AL
L U
TI
LI
TY
P
LA
N
CU101
A1 SCALE: 1" = 50'
OVERALL UTILITY PLAN
PLAN
NORTH
50' 100'0
R
EV
IS
ED
IN
A C
C O
R D
AN
C
E W
IT
H
A M
EN
D
M
EN
T
AP
R
IL
R
EV
IS
ED
IN
A
C C
O R
D
AN
C E
W
IT
H A
M
EN
D M
EN
T
AP
R
IL
W
2Q R
R
A0
_P la ns -0
5 STORY UEPH
BARRACKS
6.
0.
6.00'
24.00'
E E E E E E E E E E E E E E E E E E E E E E E E E
SAN
SAN
SAN
SAN
SAN
SAN
SAN
SAN
SD
SD
SD
SD
SD
SD
SD
SD
EX. 66" CMP STORM CULVERT
EXISTING 6 INCH FORCE MAIN
SD SD SDCB
CB CB CB
CB
SD
SDSDSDSDSDSD
SD
SD
SD
SD
SD
SD
CB
SD
SD
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
W W
W W
W W
W W
W W
W W
W W
W W W W W
SSSSSSSSSSSSSSSSSSSS
2 2
5 STORY UEPH
BARRACKS
GENERAL SHEET NOTES - UTILITY
1. CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL UTILITIES AND FIELD
VERIFYING ALL EXISTING UTILITIES. THE CONTRACTING OFFICER SHALL BE
NOTIFIED OF ANY CONFLICTS OR DISCREPANCIES PRIOR TO INSTALLATION.
2. LOCATION OF EXISTING UTILITIES ARE PROVIDED FROM SURVEY, BASE MAPS,
AND UTILITY FEATURES. ACTUAL LOCATION MUST BE VERIFIED BY
CONTRACTOR IN THE FIELD.
3. SANITARY SEWER AND WATER UTILITIES ARE OWNED AND OPERATED BY
JACOBS.
4. SEE SHEETS CU501-502 FOR UTILITY DETAILS.
5. SEE SHEETS CU201-202 FOR UTILITY PROFILES.
6. SEE CG SHEET SERIES FOR GRADING AND STORM SEWER INFORMATION.
7. JACOBS TO APPLY THRUST BLOCKS TO WATER MAIN UNTIL 5 FEET OUTSIDE OF
THE BUILDING BASED ON CH2M DETAIL. SEE SHEET CU502 DETAIL A1.
8. ALL EXISTING AND PROPOSED MANHOLES, VALVE BOXES, HANDHOLES,
CLEANOUTS, FIRE HYDRANTS, CASTINGS, AND ANY OTHER APPURTENANCE
MUST BE ADJUSTED TO MATCH FINISHED GRADE.
9. CONTRACTOR MUST BE VACATED FROM THE FY27 UEPH BARRACKS WORK SITE
PRIOR TO FY27 BARRACKS AWARD (MAY 2027).
10. FOR ELECTRICAL AND TELECOMMUNICATION SITE PLANS, SEE SHEET SERIES ES
AND TS RESPECTIVELY.
11. AT THE BUILDING CONNECTION, THE WATER LINE MUST HAVE 54 INCHES OF
COVER AT MINIMUM IN ORDER TO PASS UNDER THE GRADE BEAMS.
SHEET KEYNOTES - UTILITY
1. 12 INCH C900 PVC WATER LINE LOOP WITH VALVES TO BE CONSTRUCTED BY
JACOBS PRIOR TO CONSTRUCTION.
2. FORCE MAIN REALIGNMENT TO BE CONSTRUCTED BY JACOBS PRIOR TO
CONSTRUCTION. SEE SHEET CU201 FOR PROFILE INFORMATION.
3. JACOBS TO PROVIDE 6 INCH C900 PVC DOMESTIC WATER LINE SERVICE TO
FACILITY.
4. JACOBS TO PROVIDE 6 INCH C900 PVC FIRE PROTECTION WATER LINE.
5. JACOBS TO PROVIDE FIRE HYDRANT SEE SHEET CU501 DETAIL A1.
6. JACOBS TO PROVIDE POST INDICATOR VALVE SEE SHEET CU501, DETAIL H8.
7. JACOBS TO PROVIDE 8" SDR 35 PVC SANITARY SEWER LINE.
8. JACOBS TO PROVIDE SANITARY SEWER CLEANOUT, SEE SHEET CU501, DETAIL
A15.
9. JACOBS TO PROVIDE SANITARY SEWER MANHOLE, SEE SHEET CU502, DETAIL
A8.
10. 8 INCH WATER MAIN SERVICE TO FACILITY TO BE CONSTRUCTED BY JACOBS.
11. JACOBS TO TIE FORCE MAIN TO PROPOSED SANITARY SEWER MANHOLE. SEE
SHEET CU502, DETAIL H1.
12. JACOBS TO PROVIDE 12 INCH GATE VALVE, SEE SHEET CU501 DETAIL A8.
13. JACOBS TO PROVIDE 6 INCH GATE VALVE, SEE SHEET CU501 DETAIL A8.
14. JACOBS TO PROVIDE 8 INCH GATE VALVE, SEE SHEET CU501 DETAIL A8.
15. JACOBS TO PROVIDE 8 INCH C900 PVC WATER MAIN SERVING FACILITY.
16. JACOBS TO PROVIDE 90 DEGREE BEND.
17. JACOBS TO PROVIDE 22.5 DEGREE BEND.
KEYPLAN
102 103
106105
LEGEND - UTILTIY
CONTRACTOR WORK LIMITS AND FY27 DEMARCATION
WATER LINE SIZE AS NOTED
FIRE WATER LINE AS NOTED
SANITARY LINE - 8 INCH SDR35 PVC
FORCE MAIN - 6 INCH C900 PVC
SANITARY MANHOLE, SEE SHEET CU502 DETAIL A8
SANITARY CLEANOUT, SEE SHEET CU501 DETAIL A15
FIRE HYDRANT, SEE SHEET CU501 DETAIL A1
POST INDICATOR VALVE, SEE SHEET CU501 DETAIL H8
WATER LINE GATE VALVE, SIZE AS NOTED
(CONTRACTOR TO CONFIRM SIZES OF EXISTING WATER
LINES WHERE GATE VALVES ARE TO BE INSTALLED)
WW
FF
SAN
S
CO
PIV
SSSS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
E
SHEET ID
US Army Corps of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
FE
B
AM
PB
EL
L, K Y
U
EP
H B
AR
R
AC
KS
FY
, P N
, P
TI
FI
ED
F
AC
FA
R
LA
N D
C . C
AR
TE
R
C . C
AR
TE
R
M . B
AR
TI
LI
TY
P
LA
N
CU102
A1 SCALE: 1" = 20'
UTILITY PLAN - 1 OF 4
20' 40'0
MATCHLINE CU105
M
AT
C H
LI
N
E C
U
R
EV
IS
ED
IN
A C
C O
R D
AN
C
E W
IT
H
A M
EN
D
M
EN
T
AP
R
IL
R
EV
IS
ED
IN
A
C C
O R
D
AN
C E
W
IT
H A
M
EN
D M
EN
T
AP
R
IL
W
2Q R
R
A0
_P la ns -0
5 STORY UEPH
BARRACKS
TIE TO EXISTING SIDEWALK
CBCB
S
CB
SS
CB
CI
C I
S
U
C C
ELECEELECCP
C I
CB
EEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE COMMCOMMCOMMCOMMCOMMCOMMCOMMCOMMCOMMCOMMCOMMCOMMCOMMCOMMCOMMCOMMCOMMCOMM
SD SD SD SD SD SD SD SD
SD
SD
SDSDSDSDSDSDSDSA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
SA
N
INV EL. 542.54
INV EL. 542.23 INV EL. 541.88
INV EL. 541.62
INV EL. 541.92
INV EL. 543.40
IN
V
EL
. 5
.8
IN
V
EL
. 5
.3
INV EL. 541.86
INV EL. 541.87
12" VCP
INV EL. 544.07
INV EL. 541.62
INV EL. 542.20
INV EL. 543.47
SAN SANSANSANSANSANSANSANSANSANSANSANSANSANSAN
CB
2X
SQ
UA
RE
RI
M
E L.
.3
" R
CP
IN
V
EL
. 5
.4
" R
C P
IN
V
EL
. 5
.8
15" R
CP
INV EL. 549.03
" R
CP
IN
V
EL
. 5
.1
12" VCP
15" VCP
" R
C P
18" CMP15" ADS
8" P
VC
IN
V
EL
. 5
.2
IN
V
EL
. 5
.5
MH 5204
RIM EL. 551.12
MH 5191
RIM EL. 548.80
BASE MHG19A
MH 20368
RIM EL. 549.11
BASE MHG19
MH 20369
RIM EL. 548.63
MH 10755
RIM EL. 547.72
12" RCP
INV EL. 548.52
6" PVC
INV EL. 549.45
6" PVC
INV EL. 549.51
MH
RIM EL. 552.08
12" RPC
INV EL. 546.05
CB 5187
CB 20582
SQUARE
RIM EL. 546.81
SD
SD
SD
SD
CB
CB
CB CB CB CBSDSDSDSDSDSDSD
CB SD CBSD SD SD SD SD SD
SD
SD
SD
SD
SD
CB
CB
SD
CB
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST ST ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
ST
WWWW
W W
W W
W W
W W
W W
W W
W W
W W
W
F F
5 STORY UEPH
BARRACKS
GENERAL SHEET NOTES - UTILITY
1. CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL UTILITIES AND FIELD
VERIFYING ALL EXISTING UTILITIES. THE CONTRACTING OFFICER SHALL BE
NOTIFIED OF ANY CONFLICTS OR DISCREPANCIES PRIOR TO INSTALLATION.
2. LOCATION OF EXISTING UTILITIES ARE PROVIDED FROM SURVEY, BASE MAPS,
AND UTILITY FEATURES. ACTUAL LOCATION MUST BE VERIFIED BY
CONTRACTOR IN THE FIELD.
3. SANITARY SEWER AND WATER UTILITIES ARE OWNED AND OPERATED BY
JACOBS.
4. SEE SHEETS CU501-502 FOR UTILITY DETAILS.
5. SEE SHEETS CU201-202 FOR UTILITY PROFILES.
6. SEE CG SHEET SERIES FOR GRADING AND STORM SEWER INFORMATION.
7. JACOBS TO APPLY THRUST BLOCKS TO WATER MAIN UNTIL 5 FEET OUTSIDE OF
THE BUILDING BASED ON CH2M DETAIL. SEE SHEET CU502 DETAIL A1.
8. ALL EXISTING AND PROPOSED MANHOLES, VALVE BOXES, HANDHOLES,
CLEANOUTS, FIRE HYDRANTS, CASTINGS, AND ANY OTHER APPURTENANCE
MUST BE ADJUSTED TO MATCH FINISHED GRADE.
9. CONTRACTOR MUST BE VACATED FROM THE FY27 UEPH BARRACKS WORK SITE
PRIOR TO FY27 BARRACKS AWARD (MAY 2027).
10. FOR ELECTRICAL AND TELECOMMUNICATION SITE PLANS, SEE SHEET SERIES ES
AND TS RESPECTIVELY.
11. AT THE BUILDING CONNECTION, THE WATER LINE MUST HAVE 54 INCHES OF
COVER AT MINIMUM IN ORDER TO PASS UNDER THE GRADE BEAMS.
SHEET KEYNOTES - UTILITY
1. 12 INCH C900 PVC WATER LINE LOOP WITH VALVES TO BE CONSTRUCTED BY
JACOBS PRIOR TO CONSTRUCTION.
2. FORCE MAIN REALIGNMENT TO BE CONSTRUCTED BY JACOBS PRIOR TO
CONSTRUCTION. SEE SHEET CU201 FOR PROFILE INFORMATION.
3. JACOBS TO PROVIDE 6 INCH C900 PVC DOMESTIC WATER LINE SERVICE TO
FACILITY.
4. JACOBS TO PROVIDE 6 INCH C900 PVC FIRE PROTECTION WATER LINE.
5. JACOBS TO PROVIDE FIRE HYDRANT SEE SHEET CU501 DETAIL A1.
6. JACOBS TO PROVIDE POST INDICATOR VALVE SEE SHEET CU501, DETAIL H8.
7. JACOBS TO PROVIDE 8" SDR 35 PVC SANITARY SEWER LINE.
8. JACOBS TO PROVIDE SANITARY SEWER CLEANOUT, SEE SHEET CU501, DETAIL
A15.
9. JACOBS TO PROVIDE SANITARY SEWER MANHOLE, SEE SHEET CU502, DETAIL
A8.
10. 8 INCH WATER MAIN SERVICE TO FACILITY TO BE CONSTRUCTED BY JACOBS.
11. JACOBS TO TIE FORCE MAIN TO PROPOSED SANITARY SEWER MANHOLE. SEE
SHEET CU502, DETAIL H1.
12. JACOBS TO PROVIDE 12 INCH GATE VALVE, SEE SHEET CU501 DETAIL A8.
13. JACOBS TO PROVIDE 6 INCH GATE VALVE, SEE SHEET CU501 DETAIL A8.
14. JACOBS TO PROVIDE 8 INCH GATE VALVE, SEE SHEET CU501 DETAIL A8.
15. JACOBS TO PROVIDE 8 INCH C900 PVC WATER MAIN SERVING FACILITY.
16. JACOBS TO PROVIDE 90 DEGREE BEND.
17. JACOBS TO PROVIDE 22.5 DEGREE BEND.
KEYPLAN
102 103
106105
LEGEND - UTILTIY
CONTRACTOR WORK LIMITS AND FY27 DEMARCATION
WATER LINE SIZE AS NOTED
FIRE WATER LINE AS NOTED
SANITARY LINE - 8 INCH SDR35 PVC
FORCE MAIN - 6 INCH C900 PVC
SANITARY MANHOLE, SEE SHEET CU502 DETAIL A8
SANITARY CLEANOUT, SEE SHEET CU501 DETAIL A15
FIRE HYDRANT, SEE SHEET CU501 DETAIL A1
POST INDICATOR VALVE, SEE SHEET CU501 DETAIL H8
WATER LINE GATE VALVE, SIZE AS NOTED
(CONTRACTOR TO CONFIRM SIZES OF EXISTING WATER
LINES WHERE GATE VALVES ARE TO BE INSTALLED)
W
FF
SAN
S
CO
PIV
SS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
E
SHEET ID
US Army Corps of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
FE
B
AM
PB
EL
L, K Y
U
EP
H B
AR
R
AC
KS
FY
, P N
, P
TI
FI
ED
F
AC
FA
R
LA
N D
C . C
AR
TE
R
C . C
AR
TE
R
M . B
AR
TI
LI
TY
P
LA
N
CU105
A1 SCALE: 1" = 20'
UTILITY PLAN - 4 OF 6
20' 40'0
MATCHLINE CU102
M
AT
C H
LI
N
E C
U
R
EV
IS
ED
IN
A C
C O
R D
AN
C
E W
IT
H
A M
EN
D
M
EN
T
AP
R
IL
R
EV
IS
ED
IN
A
C C
O R
D
AN
C E
W
IT
H A
M
EN
D M
EN
T
AP
R
IL
W
2Q R
R
A0
_P la ns -0
D D D D D D DD DDD
W W W W W W W W
PL3-100A
PL-121
PL3-100B
SL3-001
208/120Y
1500KVA
SERVICE
480/277Y
2000KVA
SERVICE
PL3-002
SH3-001
PL-125 PL-129
PL-133 PL-137 PL-141 PL-145
PL-140 PL-144PL-136PL-132PL-128PL-124PL-120
PL-166 PL-170
PL-169
PL-174
PL-173 PL-177
PL-178
PL-181
PL-182
PL-185
PL-186
PL-189
PL-190
PL-193
PUMP ROOM
MECHANICAL
ROOM
ELECTRICAL
ROOM
LAUNDRY
ACCESS
LAUNDRY
STAIR
S101
LOBBY
JAN./STOR.
TELECOM
STAIR
S102
STAIR
S103
1. FOR SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES REFER TO
SHEET E-001.
2. VERIFY ALL WIRE SIZING ONCE ALL CONDUIT PATHS ARE FULLY DEFINED.
ALL BRANCH CIRCUITS MUST NOT EXCEED 3% VOLTAGE DROP AND
COMBINED BRANCH+FEEDER CIRCUIT PATHS MUST NOT EXCEED 5%.
SUITE FEEDERS AND RECEPTACLE-ONLY CIRCUITS CALCULATED AT
80% OF CIRCUIT RATING.
3. ALL CONDUIT PATHS SHOWN ARE DIAGRAMMATIC ONLY.
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Pl ot
D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
C
ER
TI
FI
ED
F
IN
AL
LO
U
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
FE
BR
U
AR
Y
KEY PLAN
FT
. C
AM
PB
EL
L, K Y.
U
EP
H B
AR
R
AC
KS
PN
FY
P2
Fi le
P at h:
AREA 1A
AREA 1B
AREA 1C
PLAN NORTH
M . B
AR
R
Y
4/
/2
9:
:0
AM
C :\U se rs
\H 2E
D D
JM
9\
D oc um en ts \5
6_ R ev it2
5_
E_ U
EP
H
_H 2E
D D
JM
9.
rv t
E-121
FI
R
ST
F
LO
O
R P
O W
ER
P
LA
N
C
O M
PR
EH
EN
SI
VE
J.
M
O O
R E
J.
M
O O
R E
B.
G
AD
D
IE
1/16" = 1'-0"A1 1ST FLOOR POWER PLAN
GENERAL NOTES - POWER PLANS
KEY NOTES
1 1ST FLOOR 208/120V SINGLE PHASE 125A SUITE FEEDERS DEFINED IN FEEDER
SCHEDULES LOCATED ON SHEET E-606, ROUTED IN/UNDER/THROUGH
FOUNDATION IN SCHEDULE 80 PVC CONDUIT. COORDINATE CONDUIT
ROUTING WITH OTHER DISCIPLINES AS REQUIRED.
AM
EN
D
M
EN
T
Ap ril
W
2Q R
R
A0
_P la ns -0
-5
WP
GFCI
-5
GFCI GFCI
-5
GFCI
-5
GFCI
-5
GFCI
-5
GFCI
-5
GFCI
-5
-5
GFCI
-5
GFCI
-5
GFCI
-5
GFCI
-5
GFCI
-5
GFCI
W P
GF
CI
WP
GFCI
WP
GFCI
WP
GFCI
WP
GFCI
WP
GFCI
WP
GFCI
W P
GF
CI
E-401 B1
CLOSET
121E
KITCHEN
121B
LIVING
121A
MECH.
LIVING
129A
LIVING
145A
BATHROOM
121C
BEDROOM
121D
A1 E-409
PL3-201 - 27
PL3-201 - 33
LIVING
125A
LIVING
137A
LIVING
124A
LIVING
132A
LIVING
140A
LIVING
133A
LIVING
141A
LIVING
120A
LIVING
128A
LIVING
136A
LIVING
144A
LEFT SIDE
CORRIDOR
100F
STAIR
S102
PL-121 PL-125 PL-129 PL-133 PL-137 PL-141 PL-145
PL-120 PL-124 PL-128 PL-132 PL-136 PL-140 PL-144
PL3-201 - 38
PL3-201 - 39
1. FOR SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES REFER TO
SHEET E-001.
2. VERIFY ALL WIRE SIZING ONCE ALL CONDUIT PATHS ARE FULLY DEFINED.
ALL BRANCH CIRCUITS MUST NOT EXCEED 3% VOLTAGE DROP AND
COMBINED BRANCH+FEEDER CIRCUIT PATHS MUST NOT EXCEED 5%.
SUITE FEEDERS AND RECEPTACLE-ONLY CIRCUITS CALCULATED AT
80% OF CIRCUIT RATING.
3. ALL CONDUIT PATHS SHOWN ARE DIAGRAMMATIC ONLY.
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Pl ot
D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
C
ER
TI
FI
ED
F
IN
AL
LO
U
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
FE
BR
U
AR
Y
KEY PLAN
FT
. C
AM
PB
EL
L, K Y.
U
EP
H B
AR
R
AC
KS
PN
FY
P2
Fi le
P at h:
AREA 1A
PLAN NORTH
M . B
AR
R
Y
4/
/2
1:
:4
PM
C :\U se rs
\H 2E
D D
JM
9\
D oc um en ts \5
6_ R ev it2
5_
E_ U
EP
H
_H 2E
D D
JM
9.
rv t
E-122
FI
R
ST
F
LO
O
R P
O W
ER
P
LA
N
E N
LA
R
G
ED
A R
EA
"A
J.
M
O O
R E
J.
M
O O
R E
B.
G
AD
D
IE
1/8" = 1'-0"A1 1ST FLOOR POWER PLAN - AREA 1A
GENERAL NOTES - POWER PLANS
KEY NOTES
1 #10 AWG CONDUCTORS (MIN) REQUIRED TO MAINTAIN BRANCH CIRCUIT
VOLTAGE DROP BELOW 3% IN ALL CIRCUIT CONDUCTORS.
2 #6 AWG CONDUCTORS (MIN) REQUIRED TO MAINTAIN BRANCH CIRCUIT
VOLTAGE DROP BELOW 3% BETWEEN JBOX AND POWER PANEL.
3 #8 AWG CONDUCTORS (MIN) REQUIRED TO MAINTAIN BRANCH CIRCUIT
VOLTAGE DROP BELOW 3%.
4 CORRIDOR RECEPTACLE OUTLETS AT 18” ABOVE FINISHED FLOOR, NO POINT
ALONG A CORRIDOR WALL CAN BE MORE THAN 25 FEET FROM A RECEPTACLE
TO MEET BOTH NEC 210.63(A) AND UFC 3-520-01 3-6.1.2(g) REQUIREMENTS.
5 REFERENCE SHEET E-401 FOR TYPICAL SUITE AND LAUNDRY ROOM
ENLARGED VIEWS.
6 SPLICE LARGER HOMERUN CABLE TO SMALLER CONDUCTORS IN ACCESSIBLE
SPACE AT APPROXIMATE LOCATION SHOWN (IN JUNCTION BOX).
7 EXTERIOR GFCI RECEPTACLES, LINE SIDE CONNECTIONS ONLY - INSTALL
WHERE INDICATED AT 18 INCHES AFF, WITHIN 10FT FROM EXTERIOR DOORS
THEN AT 50FT INTERVALS AROUND PERIMETER OF BUILDING.
AM
EN
D
M
EN
T
Ap ril
W
2Q R
R
A0
_P la ns -0
GFCI
GF
CI
OS OS OS OS
GFCI
OS OS OS
GFCI
GFCI
O S
WP
GFCI
GFCI
GFCI
GF
CI
GF
CI
GF
CI
GFCIGFCI
GFCI
GF
CI
GF
CI
GF
CI
GFCI
GF
CI
TV
TV
TV
GF
CI
GF
CI
TVTV
WP
GFCI
WP
GFCI
WP
GFCI
WP
GFCI
WP
GFCI
WP
GFCI
SL3-001B
SL3-001A
SL3-001
SH3-001
SH3-001A
SH3-001B
PL3-100B
JAN./STOR.
PUMP ROOM
VESTIBULE
100E
LOBBY
TELECOM
ELEV.
E101
LAUNDRY
FITNESS ROOM
VESTIBULE
100A
MECHANICAL
ROOM
DAY ROOM
CQ
FAMNS PANELS
PL3-002
E-401 B9
PL3-002 - 4
PL3-002 - 13
PL3-002 - 17
PL3-002 - 16
PL3-002 - 7
PL3-002 - 3
PL3-002 - 1
PL3-002 - 9 PL3-002 - 2
PL3-002 - 5
PL3-002 - 6
PL3-002 - 15
PL3-002 - 12
PL3-002 - 8
PL3-002 - 10
PL3-002 - 11 PL3-002 - 147
PL3-100C
E-402 C1
PT3-100
208/120Y
1500KVA
SERVICE
480/277Y
2000KVA
SERVICE
PL3-201 - 7,9,11
PL3-201 - 1,3,5
PL3-201 - 21
PL3-201 - 19
PL3-201 - 17
PL3-201 - 35
A7 E-409
PL3-201 - 15
PL3-201 - 29
PL3-201 - 23
PL3-201 - 25
10 10
PL3-100A
T-401 H2
Sim
PL3-100
PL3-100 - 3
ML3-101 - 24
ML3-101
T1
MH3-100
ELECTRICAL
ROOM
13 PL3-201 - 13
PL3-201 - 27
A1 E-411
PT3-100 - 10
PT3-100 - 9
15 16
DDC
ML3-101 - 28
DDC
ML3-101 - 29
1. FOR SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES REFER TO
SHEET E-001.
2. VERIFY ALL WIRE SIZING ONCE ALL CONDUIT PATHS ARE FULLY DEFINED.
ALL BRANCH CIRCUITS MUST NOT EXCEED 3% VOLTAGE DROP AND
COMBINED BRANCH+FEEDER CIRCUIT PATHS MUST NOT EXCEED 5%.
SUITE FEEDERS AND RECEPTACLE-ONLY CIRCUITS CALCULATED AT
80% OF CIRCUIT RATING.
3. ALL CONDUIT PATHS SHOWN ARE DIAGRAMMATIC ONLY.
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Pl ot
D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
C
ER
TI
FI
ED
F
IN
AL
LO
U
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
FE
BR
U
AR
Y
KEY PLAN
FT
. C
AM
PB
EL
L, K Y.
U
EP
H B
AR
R
AC
KS
PN
FY
P2
Fi le
P at h:
AREA 1B
PLAN NORTH
M . B
AR
R
Y
4/
/2
3:
:1
PM
C :\U se rs
\H 2E
D D
JM
9\
D oc um en ts \5
6_ R ev it2
5_
E_ U
EP
H
_H 2E
D D
JM
9.
rv t
E-123
FI
R
ST
F
LO
O
R P
O W
ER
P
LA
N
E N
LA
R
G
ED
A R
EA
"B
J.
M
O O
R E
J.
M
O O
R E
B.
G
AD
D
IE
1/8" = 1'-0"A1 1ST FLOOR POWER PLAN - AREA 1B
GENERAL NOTES - POWER PLANS
KEY NOTES
1 DEDICATED VENDING MACHINE OUTLETS. GFCI IS INCORPORATED WITH CIRCUIT
PROTECTIVE DEVICE IN RESPECTIVE SUPPLY PANEL.
2 REFERENCE SHEET E-502, DETAIL A1 FOR ASHRAE 90.1 SWITCHED OUTLET
REQUIREMENTS AND BASIC WIRING OF OUTLETS TO OCCUPANCY SENSOR
CONTROLLER/RELAY (OS)
3 MOUNT GFCI PROTECTED RECEPTACLES 12" ABOVE VANITY/COUNTERTOPS.
RECEPTACLES DESIGNATED AS "GFCI" HAVE TRADITIONAL RESET/TEST BUTTONS AT
THE OUTLET LOCATION, ALL OTHER RECEPTACLES ARE GFCI/AFCI PROTECTED WITH
COMBINATION BREAKERS (AT SUITE LOAD CENTER) AS SPECIFIED IN SUITE PANEL
SCHEDULE.
4 UNLESS OTHERWISE SPECIFIED, MOUNT ALL LOBBY, DAYROOM, CORRIDOR,
STAIRWELLS, JANITOR CLOSET, FITNESS ROOM AND VESTIBULE RECEPTACLE
OUTLETS AT 18"AFF
5 WATER FOUNTAIN/CHILLER GFCI RECEPTACLE OUTLETS (QTY (2) DUPLEX), MOUNTED
AS REQUIRED FOR EQUIPMENT MOUNTING AND CLEARANCE.
6 CQ STATION DEDICATED OUTLETS MOUNTED ABOVE DESK SURFACE, 3'AFF
7 FOR ALL TEN (10) FITNESS ROOM EQUIPMENT OUTLETS ON DEDICATED 20A BRANCH
CIRCUITS - UTILIZE NEMA 5-20 RECEPTACLES, SPACED 5' APART AND 18"AFF. UTILIZE
#10 AWG CONDUCTORS FOR ALL THESE DEDICATED BRANCH CIRCUITS.
8 GFCI OUTLETS, LINE SIDE CONNECTIONS ONLY - COORDINATE OUTLET LOCATION
AND QUANTITY WITH MECHANICAL.
9 #8 AWG CONDUCTORS (MIN) REQUIRED TO MAINTAIN BRANCH CIRCUIT VOLTAGE
DROP BELOW 3%.
10 #10 AWG CONDUCTORS (MIN) REQUIRED TO MAINTAIN BRANCH CIRCUIT VOLTAGE
DROP BELOW 3% IN ALL CIRCUIT CONDUCTORS.
11 WALL-MOUNT TV RECEPTACLE MOUNTED AT 7' AFF.
12 DEDICATED CIRCUIT FOR WATER SOFTENING UNITS. GFCI RECEPTACLE OUTLETS,
EACH W/ LED INDICATOR LIGHT TO VERIFY CIRCUITS ARE ENERGIZED, MOUNT 4FT
AFF.
13 REFERENCE SHEET E-401 FOR TYPICAL SUITE AND LAUNDRY ROOM ENLARGED
VIEWS.
14 TELECOM ROOM OUTLETS INSTALLED ON BACKBOARDS TO BE SPACED NO FURTHER
THAN 6 FT APART. REFERENCE ENLARGED TELECOM ROOM PLANS ON SHEET T-401
FOR FURTHER SPACING DETAILS, RACK-MOUNTED OUTLET INSTALLATION AND
OTHER TELECOMMUNICATION COORDINATION DETAILS.
15 EXTERIOR HVAC EQUIPMENT SERVICE GFCI RECEPTACLES, LINE SIDE CONNECTIONS
ONLY - COORDINATE OUTLET LOCATION AND QUANTITY WITH MECHANICAL.
16 EXTERIOR GFCI RECEPTACLES, LINE SIDE CONNECTIONS ONLY - INSTALL WHERE
INDICATED AT 18 INCHES AFF, WITHIN 10FT FROM EXTERIOR DOORS THEN AT 50FT
INTERVALS AROUND PERIMETER OF BUILDING.
17 DDC NETWORK AND POWER OUTLET APPROXIMATE LOCATION. PROVIDE AT LEAST
ONE WALL-MOUNTED DDC TELECOMMUNICATIONS OUTLET WITHIN INDICATED
UTILITY ROOMS AND ONE DEDICATED ELECTRICAL OUTLET IN ELECTRICAL AND
MECHANICAL ROOMS (ALL FLOORS) TO ACCOMMODATE CONTROLS, ENERGY
MANAGEMENT AND/OR REPORTING SYSTEMS. MOUNT IN LOCATION AS REQUIRED BY
CONTROL SYSTEM.
AM
EN
D
M
EN
T
Ap ril
2 2
W
2Q R
R
A0
_P la ns -0
WP
GFCI
-5
-5
GFCI
-5
GFCI GFCI
-5
-5
GFCI GFCI
-5
-5
GFCI
GFCI
-5
-5
GFCI GFCI
-5
-5
GFCI GFCI
-5
-5
GFCIGFCI
-5
W P
GF
CI
WP
GFCI
WP
GFCI
WP
GFCI
WP
GFCI
WP
GFCI
WP
GFCI
W P
GF
CI
A11 E-409
PL3-201 - 29 1
PL3-201 - 31
LIVING
169A
LIVING
173A
LIVING
177A
LIVING
181A
LIVING
185A
LIVING
189A
LIVING
193A
LIVING
190A
LIVING
186A
LIVING
182A
LIVING
178A
LIVING
174A
LIVING
170A
LIVING
166A
RIGHT SIDE
CORRIDOR
100G
STAIR
S103
PL-169 PL-173 PL-177 PL-181 PL-185 PL-189 PL-193
PL-190PL-186PL-182PL-178PL-174PL-170PL-166
PL3-201 - 37
PL3-201 - 36
1. FOR SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES REFER TO
SHEET E-001.
2. VERIFY ALL WIRE SIZING ONCE ALL CONDUIT PATHS ARE FULLY DEFINED.
ALL BRANCH CIRCUITS MUST NOT EXCEED 3% VOLTAGE DROP AND
COMBINED BRANCH+FEEDER CIRCUIT PATHS MUST NOT EXCEED 5%.
SUITE FEEDERS AND RECEPTACLE-ONLY CIRCUITS CALCULATED AT
80% OF CIRCUIT RATING.
3. ALL CONDUIT PATHS SHOWN ARE DIAGRAMMATIC ONLY.
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Pl ot
D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
C
ER
TI
FI
ED
F
IN
AL
LO
U
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
FE
BR
U
AR
Y
KEY PLAN
FT
. C
AM
PB
EL
L, K Y.
U
EP
H B
AR
R
AC
KS
PN
FY
P2
Fi le
P at h:
AREA 1C
PLAN NORTH
M . B
AR
R
Y
4/
/2
1:
:1
PM
C :\U se rs
\H 2E
D D
JM
9\
D oc um en ts \5
6_ R ev it2
5_
E_ U
EP
H
_H 2E
D D
JM
9.
rv t
E-124
FI
R
ST
F
LO
O
R P
O W
ER
P
LA
N
E N
LA
R
G
ED
A R
EA
"C
J.
M
O O
R E
J.
M
O O
R E
B.
G
AD
D
IE
1/8" = 1'-0"A1 1ST FLOOR POWER PLAN - AREA 1C
GENERAL NOTES - POWER PLANS
KEY NOTES
1 #8 AWG CONDUCTORS (MIN) REQUIRED TO MAINTAIN BRANCH CIRCUIT
VOLTAGE DROP BELOW 3%.
2 CORRIDOR RECEPTACLE OUTLETS AT 18” ABOVE FINISHED FLOOR, NO POINT
ALONG A CORRIDOR WALL CAN BE MORE THAN 25 FEET FROM A RECEPTACLE
TO MEET BOTH NEC 210.63(A) AND UFC 3-520-01 3-6.1.2(g) REQUIREMENTS.
3 SPLICE LARGER HOMERUN CABLE TO SMALLER CONDUCTORS IN ACCESSIBLE
SPACE AT APPROXIMATE LOCATION SHOWN (IN JUNCTION BOX).
4 #4 AWG CONDUCTORS (MIN) REQUIRED TO MAINTAIN BRANCH CIRCUIT
VOLTAGE DROP BELOW 3% BETWEEN JBOX AND POWER PANEL.
5 #6 AWG CONDUCTORS (MIN) REQUIRED TO MAINTAIN BRANCH CIRCUIT
VOLTAGE DROP BELOW 3% BETWEEN JBOX AND POWER PANEL.
6…