W912QR25BA016_Specs-0002.pdf
PDF 2 MB Posted
- Attached to
- March Air Reserve Base, CA B600 Flight Simulator Federal contract opportunity
- Solicitation number
- W912QR25BA016
About this file
This document is an amendment (Amendment 0002) to a federal solicitation for a Design/Bid/Build project at March Air Reserve Base, California. The amendment modifies specifications for the addition and alteration of Building 600 for a KC-46 Flight Simulator, specifically updating electrical grounding details, plan sheets, and specification sections. Key changes include removing Detail F7 from an electrical grounding details sheet, changing a ground rod symbol on a grounding rider diagram, and modifying paragraphs in sections related to rigid grid access flooring and grounding/bonding for electrical systems.
The amendment also provides details for a mandatory site visit scheduled for Wednesday, 13 August 2025 at 9:00 AM PDT, with participants meeting at 1250 Y Street, Building 600 at March ARB. Attendees must submit a base pass request sheet to the Visitor Control Center by close of business on 06 August 2025. The point of contact is Pete Gauer, a Resident Engineer, who can be reached at various contact numbers and email. The solicitation requires electronic bid submission through the Procurement Integrated Enterprise Environment (PIEE) Solicitation Module, with bids to be opened via teleconference on 20 August 2025.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Bid Opening Results - W912QR25BA016.pdf | ||
| W912QR25BA016_Plans-0005.pdf | ||
| 2nd Site Visit Sign In Sheet B600.pdf | ||
| W912QR25BA016_Specs-0004.pdf | ||
| W912QR25BA016_Plans-0004.pdf | ||
| W912QR25BA016_Specs-0003.pdf | ||
| W912QR25BA016_Plans-0002.pdf | ||
| W912QR25BA016-0001.pdf | ||
| Sign in B600 8 July Site walk.pdf | ||
| W912QR25BA016_Plans-0000.pdf | ||
| W912QR25BA016_Specs_Vol1-0000.pdf | ||
| W912QR25BA016_Specs_Vol2-0000.pdf | ||
| W912QR25BA016_SID-0000.pdf | ||
| W912QR25BA016_FFE-0000.pdf | ||
| W912QR25BA016_Specs_Vol3-0000.pdf |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended. is not extended.
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
(a) By completing items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of theoffer submitted;
or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE
RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER.
If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER
NUMBER IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print) 16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
15B. CONTRACTOR/OFFEROR
(Signature of person authorized to sign)
15C. DATE SIGNED 16B. UNITED STATES OF AMERICA
(Signature of Contracting Officer)
16C. DATE SIGNED
Previous edition unusable STANDARD FORM 30 (REV. 11/2016) Prescribed by GSA FAR (48 CFR) 53.243
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
1. CONTRACT ID CODE PAGE OF PAGES
2. AMENDMENT/MODIFICATION NUMBER 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)
6. ISSUED BY CODE 7. ADMINISTERED BY (If other than Item 6) CODE
8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X) 9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED (SEE ITEM 11)
10A. MODIFICATION OF CONTRACT/ORDER NUMBE
10B. DATED (SEE ITEM 13)
CODE FACILITY CODE
J 1 5
0002 04 AUG 2025 504650
W912QR
W072 ENDIST LOUISVILLE
KO CONTRACTING DIVISION, 600 DR MARTIN LUTHER KING JR PL
LOUISVILLE, KY 40202-2230
UNITED STATES
LINDSAY LAWRENCE, EMAIL: LINDSAY.B.LAWRENCE@USACE.ARMY.MIL
SCD: PAS:
W912QR25BA016
26 JUN 2025
SEE SECTION G - CONTRACT ADMINISTRATION DATA
SEE SCHEDULE
W912QR25BA016_Specs-0002
W912QR25BA0160002
Page 2 of5
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
Block 14 (Description of Amendment/Modification): Solicitation W912QR25RA036 for the Design /Bid/Build for the Addition/ Alteration of Building 600 for KC-46 Flight Simulator at March ARB, CA is hereby amended as follows:
a) The following PLAN SHEETS have been revised and replaced in their entirety:
EG501 ELECTRICAL GROUNDING DETAILS
Detail F7 has been removed.
EG601 ELECTRICAL GROUNDING RIDER DIAGRAM
Detail H5 changed symbol from test well to ground rod.
b) The following SPECIFICATION SECTIONS have been revised and replaced in their entirety:
KC-46A B600 Flight Simulator (PN PDPG 221013):
09 69 13 RIGID GRID ACCESS FLOORING
Paragraph 2.2.4.1 Static-Dissipative Vinyl Tile has been modified.
26 05 26.00 40 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
Paragraph 1.2 SUBMITTALS has been modified.
Paragraph 2.1.4 TEST WELLS has been deleted.
c) A second site visit is being offered. Please review 52.236-27 for requirements.
d) All other terms and conditions remain unchanged.
Section 00 20 00 - Instructions for Procurements
FAR Clauses Incorporated by Full Text
52.236-27 Site Visit (Construction). (Alternate I) (Feb 1995) Alternate I (Feb 1995)
Alternate I (Feb 1995). If an organized site visit will be conducted, substitute a paragraph substantially the same as the following for paragraph (b) of the basic provision:
(b) An organized site visit has been scheduled for
Wednesday, 13 August 2025 at 9:00 AM PDT
(c) Participants will meet at-
1250 Y Street, Building 600 March ARB, CA 92518
Site visit attendees are required to submit the attached March ARB Contractor Base Pass Request Sheet noting all attendees from their organization and submit to the Visitor Control Center og e-mail: 452SFS.March.VCC@us.af.mi1 no later than (NLT) close of business (COB) on 06 August 2025.
d) Point of Contact: Pete Gauer, P.E. Resident Engineer - Santa Ana Dams Resident Office Office 951 8986153 Cell 949 212 7480 peter.a.gauer@usace.army.mil
Privacy Act Statement PRIVACY ACT-1974 as Amended applies – This memo may contain information which must be protected IAW DOD 5400-11, and it is For Official Use Only (FOUO)
AUTHORITY: 10 U.S.C. 8013; 44 U.S.C. 3101; and EO 93397 PRINCIPAL PURPOSES: Used to record information and details of criminal activity which may require investigative action by commanders, supervisors, police, special agents, etc. ROUTINE USES: Information may be disclosed to Pass and Registration to determine base access. DISCLOSURE IS VOLUNTARY: SSN is used to positively identify the individual as a conduit to check past criminal activity records. Failure to provide the request information will affect your ability to gain access to
March Air Reserve Base, CA.
ELECTRONIC BID SUBMISSION
Page 3 of5
Bids: ALL SUBMISSIONS TO THIS BID ANNOUNCEMENT SHALL BE SUBMITTED
ELECTRONICALLY THROUGH THE PROCUREMENT INTEGRATED ENTERPRISE
ENVIRONMENT (PIEE) SOLICITATION MODULE BEFORE THE TIME SPECIFIED IN BLOCK
13 OF THE SF1442. No paper copies, CD-ROMS, facsimile, or DoD SAFE submissions will be accepted.
A User ID and Password are required to access PIEE. Offerors are required to self-register as a Vendor or Contractor with the user's CAGE code(s) and must have an active registration in the System for Award
Management (SAM) prior to the PIEE registration process.
1. Instructions for registering in PIEE:
a. Navigate to https://piee.eb.mil/
b. Select Register [top right],or go to https://piee.eb.mil/xhtml/unauth/ registration /notice.xhtml
c. Select Vendor
d. Create a User ID and Password andfollow the prompts [next]
e. Create Security Questions [next]
f. Complete your User Profile Information [next]
g. Complete your Supervisor or Approving Official Information [next]
h. Complete Roles
1. Step 1. Select SOL-Solicitation
11. Step 2. Select Proposal Manager
iii. Step 3. Click Add Roles
iv. Step 4. Fill in your Location Code (CAGE Code) [next]
1. Provide a justification for your registration [ next]
J. Follow the remaining prompts to submit your registration
Section 00 21 00 - Instructions
Miscellaneous text in this section has been modified to:
BID OPENING
All sealed bids must be delivered electronically per the instructions contained within this solicitation. The bid opening will be conducted telephonically via the below conference call-in number. Bids must be received by the time specified in the solicitation, otherwise they will be deemed late and unresponsive. The conference call-in number is as follows:
Conference Call-In Number: 503-207-9433
Phone conference ID: 185 459 090#
The Contracting Officer with assistance from the assigned Contract Specialist will download all of the bid submissions and record all of the pertinent information prior to the conference call. The bid opening teleconference will begin promptly at 3:30 PM ET on 20 August 2025.
At that time, the bid opening officer will 1) read the names of the submitting contractors and their bids, and 2) read the independent government estimate. Once the information has been disseminated, the call will come to an end. The bid abstract will be posted to the SAM website by close of business of the day bids are opened.
Page4 of5
d. The solicitation displays. The information is view only.
e. Scroll down to see the Contract Information and Attachments. The Attachments can be viewed by selecting the File link. Scroll back up to the top of the screen and click the Offer tab.
f. Click the Offer tab to Add and review current offers on the Solicitation. Click the Add button to add an offer to the Solicitation.
g. Select the applicable CAGE Code for which submitting the offer for. The list is prefiltered based on the CAGEs in the Proposal Manager's profile.
h. Upload the attachments that comprise the offer by selecting the Choose Files link.
i. After entering all necessary information enter a Signature Date and Click the Signature button.
j. The Sign Document pop-up will be displayed requiring the user to enter a Digital Pin and One Time Password {OTP).Click the Sign and Submit button to continue.
k. After successfully adding the Offer a success message of the submission will be displayed and the offer displayed collapsed. Users may expand and view all their offers on a Solicitation.
File Naming Convention: To ensure your submission is received and processed appropriately; it is important that interested parties CAREFULLY ensure their electronic files adhere to the following naming convention:
W912QR25BA016_FIRMNAME
NOTE: The PIEE Solicitation Module will replace special characters and spaces in the attachment filename with underscores.
Upload Completion & Deadline: Offerors are highly encouraged to become familiar with the PIEE Solicitation module well in advance of the proposal due date. Interested offerors shall submit proposals no later than the date specified on the solicitation document. The time & date of proposal receipt will be the upload completion /delivery time & date recorded within PIEE Solicitation module. Do not assume that electronic submission will occur instantaneously. Large files will take some time to upload. Offerors should time their upload effort with prudence by not waiting until the last few minutes--this will allow for unexpected delays in the transmittal process. Offerors are encouraged to keep a copy of the upload confirmation for their record. Submissions after the deadline will be considered late and will be processed in accordance with F ARl 5.208.
For training and help using the PIEE Solicitation module, reference the links below.
New User Information and Help: https://piee.eb.mil/xhtml/unauth/help/helpvendors.xhtml
Vendor Customer Support: https:/ /piee.eb.mil/xhtml/unauth/web/homepage /vendorCustomerSupport.xhtml
A Solicitation- Web Based Training: https:/ /pieetraining.eb.mil/wbt/xhtml/wbt/sol/index.xhtml
The Procurement Integrated Enterprise Environment (PIEE) help desk may be reached by calling telephone number 866-618-5988 for assistance.
2. Instructions for Electronic Proposal Submission in PIEE Solicitation Module:
a. Log into PIEE and select the Solicitation Icon.
b. Enter search criteria to find the solicitation. (Search Criteria can be the complete solicitation number, Solicitation Open Date, Response Due Date, Product or Service Code, NAICS, Set Aside code, Place of Performance Zip Code, Contracting Office DODAAC, or Status)
c. The search results display. Select the Solicitation Number link to open the solicitation.
P2# 504650 Addition/Alteration of B600 for Flight Simulator March Air Reserve Base
SECTION 09 69 13
RIGID GRID ACCESS FLOORING
11/15, CHG 1: 08/18
Amendment 0002
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)
ASCE 7-16 (2017; Errata 2018; Supp 1 2018) Minimum Design Loads and Associated Criteria for Buildings and Other Structures
ASTM INTERNATIONAL (ASTM)
ASTM A780/A780M (2021) Standard Practice for Repair of Damaged and Uncoated Areas of Hot-Dip Galvanized Coatings
ASTM B85/B85M (2018) Standard Specification for Aluminum-Alloy Die Castings
ASTM E648 (2023) Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source
ASTM F150 (2006; R 2013) Standard Test Method for Electrical Resistance of Conductive and Static Dissipative Resilient Flooring
ASTM F1700 (2020) Standard Specification for Solid Vinyl Floor Tile
ASTM F1861 (2021) Standard Specification for Resilient Wall Base
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2017; Version 1.2) Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers
CEILINGS AND INTERIOR SYSTEMS CONSTRUCTION ASSOCIATION (CISCA)
CISCA Access Floors (2007) Recommended Test Procedures for Access Floors
GREEN SEAL (GS)
GS-36 (2013) Adhesives for Commercial Use
SECTION 09 69 13 Page 1 Amendment 0002 - Certified Final
ICC EVALUATION SERVICE, INC. (ICC-ES)
ICC-ES AC300 (2014) Acceptance Criteria for Access Floors
INTERNATIONAL CODE COUNCIL (ICC)
ICC IBC (2021) International Building Code
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 75 (2020) Standard for the Protection of Information Technology Equipment
NFPA 99 (2021; TIA 20-1; TIA 21-2) Health Care Facilities Code
NFPA 253 (2011) Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)
SCAQMD Rule 1168 (2022) Adhesive and Sealant Applications
U.S. DEPARTMENT OF DEFENSE (DOD)
UFC 3-301-01 (2023) Structural Engineering
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
FS TT-C-490 (Rev H; 2021) Chemical Conversion Coatings and Pretreatments for Metallic Substrates (Base for Organic Coatings)
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Detailed Installation Drawings; G
Fabrication Drawings; G
SD-03 Product Data
Access Flooring System; G
Recycled Content of Access Flooring System; S
Indoor Air Quality For Pedestal Adhesive; S
SECTION 09 69 13 Page 2
SD-04 Samples
Floor Panels
Floor Covering; G
Panel Support System
Accessories; G
Cut Outs; G
SD-05 Design Data
Seismic Calculations
SD-06 Test Reports
Factory Tests
Concentrated Load
Uniform Live Load
Rolling Load
Impact Load
Ultimate Load
Stringer Load
Pedestal Axial Load
Bonding Strength of Pedestal Adhesive
Electrical Resistance
Field Tests
SD-07 Certificates
Compliance with ICC-ES AC300
Compliance with ICC IBC
Certificate of Compliance
Qualification of Manufacturer
SD-10 Operation and Maintenance Data
Operation and Maintenance Manuals; G
SD-11 Closeout Submittals
Lifting Device
Warranty; G
SECTION 09 69 13 Page 3
1.3 SPARE PARTS
Furnish spare floor panels for each finish including complete pedestal assemblies and stringers at the rate of one for each 100 or fraction thereof required. Provide four floor panels complete with specified floor covering for future use. Provide four spare panels with identical floor covering pedestals and stringers for each 1,000 square feet of access flooring and total of 10 linear feet of cut-out trim. Store extra stock in same manner and location as project materials.
1.4 QUALITY CONTROL
1.4.1 Qualification of Manufacturer
Access flooring manufacturer must have at least 5 years experience in manufacturing access flooring systems. Certify that the manufacturer of the access flooring system meets requirements specified under paragraph entitled QUALIFICATION OF MANUFACTURER.
1.5 DELIVERY, STORAGE, AND HANDLING
1.5.1 Delivery
Deliver materials to site in undamaged condition, in original containers or packages, complete with accessories and instructions. Label packages with manufacturer's name and brand designations. Package materials covered by specific references bearing specification number, type and class as applicable.
1.5.2 Storage
Store all materials in original protective packaging in a safe, dry, and clean location. Store panels at temperatures between 40 and 90 degrees F, and between 20 and 70 percent humidity. Replace defective or damaged materials.
1.5.3 Handling
Handle and protect materials in a manner to prevent damage during the entire construction period.
1.6 WARRANTY
Minimum manufacturer warranty must have no dollar limit, cover full system, and must have a minimum duration of 5 years. Include an agreement to repair or replace floor panels, pedestals or stringers that fail within the warranty period in the standard performance guarantee or warranty.
Failures include, but are not limited to, sagging and warping of panels;
rusting and manufacturers defects of panels or support system. For high pressure laminate, conductive high pressure laminate, and solid vinyl tile, provide manufacturer's standard performance guarantees or warranties that extend beyond a one-year period for finish materials. For conductive and static-dissipative vinyl tile provide manufacturer's standard performance guarantees or warranties that extend beyond one year, standard warranty must not be less than a five year wear warranty and ten year conductivity warranty.
SECTION 09 69 13 Page 4
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
a. Provide for self-alignment of floor panels, adjustable pedestals and readily removable floor panels covered as specified.
b. Lateral stability of floor support system must be independent of panels. Provide a finished assembly that is rigid and free of vibration, noises, and rocking panels. Provide bolted stringer system with equipotential plane grounding.
c. Submit certificate of compliance attesting that the installed access floor system meets specification requirements, including all special equipment loads and specific electrical and or cable requirements for the complete access flooring system including, but not limited to the following:
(1) Compliance with ICC-ES AC300 and Compliance with ICC IBC Acceptance Criteria for Access Floors.
(2) Load-bearing capabilities of pedestals, floor panels, and pedestal adhesive resisting force.
(3) Supporting independent laboratory test reports. For panel, stringer and pedestal load test results include concentrated loads at center of panel, panel edge midpoint, ultimate loads and uniform loads.
(4) Floor electrical characteristics.
(5) Material requirements.
(6) An elevated floor system free of defects in materials, fabrication, finish, and installation, that will remain so for a period of not less than 5 years after completion.
d. Submit manufacturer's product data for access flooring system consisting of descriptive data, catalog cuts, and installation instructions. Include in the data information about any design and production techniques, total system including all accessories and finish coatings of under-floor components, procedures and policies used to conserve energy, reduce material, improve waste management or incorporate green building/recycled products into the manufacturer of their components or products. Include cleaning and maintenance instructions. Systems which contain zinc electroplated anti-corrosion coatings are prohibited.
2.1.1 Design Requirements
Conduct floor panel testing in accordance with CISCA Access Floors . When tested as specified, make all deflection and deformation measurements at the point of load application on the top surface of the panel. Floor panels must be capable of supporting the following loads:
a. Concentrated load of 2000 pounds on one square inch, at any point on panel, without a top-surface deflection more than 0.10 inch, and a permanent set not to exceed 0.01 inch in any of the specified tests.
Testing must be in accordance with CISCA Access Floors , Section 1
SECTION 09 69 13 Page 5
Concentrated Loads with test panels being supported by understructure to be used with installed system instead of steel support blocks.
b. Uniform live load of 400 psf, without a top-surface deflection more than 0.06 inch, and a permanent set not to exceed 0.01 inch in any of the specified tests, when tested in accordance with CISCA Access Floors , Section 7 Uniform Load Test with test panels being supported by understructure to be used with installed system instead of steel support blocks.
c. A rolling load of 1200 pounds applied through hard rubber surfaced wheel 6 inch diameter by 2 inch wide for 10,000 cycles over the same path. Permanent set at conclusion of test must not exceed 0.040 inch when tested in accordance with CISCA Access Floors , Section 3 Rolling Loads.
d. A rolling load of 1250 pounds applied through a 3 inch diameter by 1-13/16 inch wide caster for 10 cycles over the same path, without developing a local overall surface deformation greater than 0.04 inch.
In accordance with CISCA Access Floors , Section 3 Rolling Loads, the permanent deformation limit under rolling load must be satisfied in all of the specified tests.
e. An impact load of 150 pounds anywhere on the panel dropped from a height of 36 inches onto a 1 square inch area without failure of the system, according to CISCA Access Floors , Section 8 Drop Impact Load Test.
f. Ultimate Load. Panels must meet manufacturer's published Ultimate Load rating of 2500 pounds when tested in accordance with CISCA Access Floors , Section 2 Ultimate Loading.
g. Safety Factor. Panels must provide a minimum Safety Factor of 5 times the uniform load specified above in accordance with ICC-ES AC300 .
h. Recycled Content. Provide Access Flooring System (panels, stringers and pedestals) containing a minimum of 20 percent recycled content.
Provide data identifying percentage of recycled content of access flooring system.
2.1.2 Allowable Tolerances
2.1.2.1 Floor Panel Flatness
Plus or minus 0.035 inches on diagonal on top of panel or underneath edge.
2.1.2.2 Floor Panel Length
Plus or minus 0.015 inch.
2.1.2.3 Floor Panel Squareness
Plus or minus 0.02 inch in panel length.
2.1.3 Stringers
Provide stringers capable of supporting a 350 pound concentrated load at midspan without permanent deformation in excess of 0.010 inch, when tested in accordance with CISCA Access Floors , Section 4 Stringer Load Testing.
SECTION 09 69 13 Page 6
2.1.4 Pedestals
Pedestals must be capable of supporting a 5000 pound axial load without permanent deformation, when tested in accordance with CISCA Access Floors , Section 5 Pedestal Axial Load Test.
2.1.5 Bonding Strength of Pedestal Adhesive
Adhesive for anchoring pedestal bases must have a bonding strength capable of resisting an overturning moment of 1,000 lbf-in when a force is applied to the top of the pedestal in any direction, when tested in accordance with CISCA Access Floors , Section 6 Pedestal Overturning Moment Test.
Pedestal adhesive must meet emissions requirement of CDPH SECTION 01350 (use the office or classroom requirements, regardless of space type).
Provide validation of indoor air quality for pedestal adhesive.
2.1.6 Bond Strength of Factory Installed Covering
Bond strength of floor covering must be sufficient to permit handling of the panels by use of the panel lifting device, and to withstand moving caster loads up to 1250 pounds, without separation of the covering from the panel.
2.1.7 Seismic Calculations
2.1.7.1 Project Specific Requirements
Submit seismic calculations for special bracing to resist the effects of seismic or other forces in accordance with UFC 3-301-01 , ICC IBC and ASCE 7-16 , and as shown on the approved detailed installation drawings.
Submit design calculations which demonstrate that the proposed floor system meets requirements for seismic loading. Certified copies of test reports may be submitted in lieu of calculations.
2.2 FLOOR PANELS
2.2.1 Floor System Drawings and Planer Quality
a. Submit Fabrication Drawings for elevated floor systems consisting of fabrication and assembly details to be performed in the factory.
b. Indicate on Location Drawings exact location of pedestals, ventilation openings, cable cutouts, and the panel installation pattern.
c. Provide Detail Drawings showing details of the pedestals, pedestal-floor interlocks, floor panels, panel edging, floor openings, floor opening edging, floor registers, floor grilles, cable cutout treatment, perimeter base, expansion, and peripheral support facilities.
d. Design and workmanship of the floor, as installed, must be completely planar within plus or minus 0.060 inch in 10 feet, 0.100 inch for the entire floor, and 0.030 inch across panel joints.
e. Floor-panel joint-width tolerances must not exceed 0.017 inch as measured with a feeler gauge at any point in any joint when the panels are installed and as long as the air leakage requirements specified in this section are met.
SECTION 09 69 13 Page 7
f. Submit three complete samples of floor panels.
2.2.2 Detailed Installation Drawings
Submit Detailed Installation Drawings that as a minimum indicate the following:
a. Location of panels.
b. Layout of supports, panels, and cutout locations.
c. Sizes and details of components.
d. Details at floor perimeter and height above structural floor.
e. Method of anchorage to structural subfloor.
f. Lateral bracing.
g. Typical cutout details.
h. Gasketing, return air grilles, supply air registers, and perforated panels. Include air transfer capacity of grilles, registers and panels.
i. Description of coating.
j. Floor finishes.
k. Location of connection to building grounding electrode.
2.2.3 Panel Construction
a. Base access floor system on a 24 by 24 inch square module providing minimum of 18 inch clearance between structural floor and underside of panel and stringer. Fabricate so accurate job cutting and fitting may be done using standard sizes for perimeters and around columns.
b. Do not expose metal on finished top surface of panels. Provide cutouts and cutout closures to accommodate utility systems and equipment intercabling. Reinforce cutouts to meet design load requirements. Provide extra support pedestals at each corner of cutout for cutout panels that do not meet specified design load requirements.
c. Panel design must provide for convenient panel removal for underfloor servicing and for openings for new equipment. Use panels of uniform dimensions within specified tolerances. Permanently mark panels to indicate load rating and model number.
d. Machine square floor panels to within plus or minus 0.015 inch with edge straightness plus or minus 0.0025 inch. If plastic edging is applied to the panel, the tolerances apply to the panel before the plastic edging is applied.
e. Provide panels with holes drilled in corners to align precisely with threaded holes in pedestal heads and to accept countersunk corrosion resistant screws with heads that are flush with top of panel.
SECTION 09 69 13 Page 8
2.2.3.1 Aluminum
Provide aluminum panels of die-cast or extruded construction conforming to
ASTM B85/B85M.
2.2.3.2 Hollow Formed Steel
Steel panels must be of die-formed construction, consisting of a flat steel top sheet welded to one or more formed steel stiffener sheets or components. Panels must be chemically cleaned, bonderized, and painted with the manufacturer's standard finish.
2.2.4 Floor Covering
Surface floor panels with factory applied finish materials firmly bonded in place with waterproof adhesive. Provide finish flooring materials in corridors and exits with a critical radiant flux of not less than 0.45 watts per square centimeter (Class 1) when tested in accordance with ASTM E648 or NFPA 253 . The electrical resistance must remain stable over the life expectancy of the floor covering. Any anti-static agent used in the manufacturing process must be an integral part of the material, not surface applied. Bolt heads or similar attachments must not rise above the traffic surface. Submit three separate samples of each specified floor covering finish and color.
Amendment 0002************************************************************
2.2.4.1 Static-Dissipative Vinyl Tile
Provide factory applied static-dissipative vinyl tile that is a homogeneous vinyl product and conforms to ASTM F1700, Class I monolithic, Type A smooth surface. Provide electrical resistance from surface to surface and surface to ground between 1,000,000 ohms (1.0 x 10 6) and
1,000,000,000 ohms (1.0 x 10 9) when tested in accordance with ASTM F150.
Material must consist of one piece to cover the face of the panel.
************************************************************Amendment 0002
2.2.5 Accessories
Provide the manufacturer's standard registers, grilles, perforated panels, and plenum dividers type where indicated. Provide registers, grilles, and perforated panels designed to support the same static loads as floor panels without structural failure, and capable of delivering the air volumes indicated. Registers and perforated panels must be 25 percent open area and equipped with adjustable dampers. Submit three samples and colors of each accessory.
2.2.6 Resilient Base
Conform to ASTM F1861, Type TP (thermoplastic rubber), Style B (coved -installed with resilient flooring). Provide 4 inch high and a minimum 1/8 inch thick wall base. Provide preformed corners in matching height, shape, and color.
2.2.7 Adhesives
Provide adhesives as recommended by the manufacturer. Provide non-aerosol adhesive products that meet either emissions requirements of CDPH SECTION 01350 (use the requirements for either office or classroom, regardless of space type) or VOC content requirements of SCAQMD Rule 1168 .
Provide aerosol adhesives that meet either emissions requirements of
SECTION 09 69 13 Page 9
CDPH SECTION 01350 (use the requirements for office or classroom, regardless of space type) or VOC content requirements of GS-36. Provide validation of indoor air quality for adhesives. Provide conductive adhesive as recommended by the manufacturer of the static-control flooring.
2.2.8 Lifting Device
At turn over provide one floor panel lifting device standard with the floor manufacturer, for each individual floor area (room or corridor).
Furnish a minimum of two devices. For AIR FORCE projects, at turnover, provide a total of two suction-type floor panel lifting devices for each floor area (room or corridor).
2.3 PANEL SUPPORT SYSTEM
Design support system to allow for 360 degree clearance in laying out cable and cutouts for service to machines and so that panel and stringer together take up maximum of 2 inches. Submit one sample of suspension system proposed for use.
2.3.1 Pedestals
Provide pedestals made of steel or aluminum or a combination thereof.
Ferrous materials must have a factory-applied corrosion-resistant finish.
Provide pedestal base plates with a minimum of 16 square inches of bearing surface and a minimum of 1/8 inch thickness. Pedestal shafts must be threaded to permit height adjustment within a range of approximately 2 inches, to permit overall floor adjustment within plus or minus 0.10 inch of the required elevation, and to permit leveling of the finished floor surface within 0.062 inch in 10 feet in all directions. Provide locking devices to positively lock the final pedestal vertical adjustments in place. Pedestal caps must interlock to preclude tilting or rocking of the panels.
2.3.2 Stringers
Provide stringers of rolled steel or extruded aluminum, to interlock with the pedestal heads to prevent lateral movement. Provide stringers that can be added or removed after floor is in place.
2.3.3 Gaskets
Provide continuous gasketing at contact surfaces between panel and stringers to deaden sound and seal off the underfloor cavity from above for air tightness, and to maintain panel alignment.
2.4 FACTORY TESTS
Factory test access flooring, using an independent laboratory, at the same position and maximum design elevation and in the same arrangement as shown on the drawings for installation so as to duplicate service conditions as much as possible.
2.4.1 Load Tests
Conduct floor panel, stringer, and pedestal testing in accordance with CISCA Access Floors to determine deformation and permanent set of panels and system due to concentrated, Uniform, rolling, impact and ultimate loading when panels are supported by actual understructure.
SECTION 09 69 13 Page 10
2.4.2 Bond Strength of Covering
Conduct test for bond strength of covering in accordance with CISCA Access Floors for rolling loads, except as specified. Panels must be tested with specified hard surface flooring and on the pedestals and stringers as specified for the installed floor. Brace the supports as necessary to prevent sideways movement during the test. Impose a test load of 1250 pounds on the test assembly through a 3 inches in diameter and 1 inch wide hard plastic caster. Roll the caster completely across the center of the panel. The panel must withstand 20 passes of the caster with no delamination or separation of the covering.
2.5 CUT OUTS
Provide cable cutouts finished with rigid polyvinylchloride or molded polypropylene edging to conform to the appearance level of the floor surface and to cover raw edges of the cutout panel. Extrusion must be of a configuration to permit its effective and convenient use when new cable openings are required. Provide at least 24 feet of additional extrusion for future use. Submit three color samples for cut outs.
a. Provide non-metallic adapter for openings less than 4 inches wide.
Secure adapter adhesively in cutout to preclude removal from panel.
Provide at least two adapters per 1000 square feet for future use.
b. Openings larger than 4 inches wide must use rigid polyvinylchloride or molded polypropylene edging. Perform cutting of panels, including cutouts, outside of the building.
c. When size of cutout reduces the performance requirement of panel, provide intermediate stringers adjacent to cutouts.
2.6 EDGE CLOSURE
Provide 1/16 inch aluminum closure plate and extruded aluminum nosing at exposed edge of floor. Back up the closure plates with aluminum or steel framing braced diagonally, or anchor at bottom to continuous angle.
2.7 COLOR
Color see finish schedule. Color listed is not intended to limit the selection of equal colors from other manufacturers.
PART 3 EXECUTION
3.1 INSTALLATION
Install access flooring at the location and elevation and in the arrangement shown on the approved detailed installation drawings. The floor system must be of the rigid grid stringer type, complete with all supplemental items, and be the standard product of a manufacturer specializing in access flooring systems.
Install the floor system in accordance with the manufacturer's instructions. Open ends of the floor, where the floor system does not abut wall or other construction, must have positive anchorage and rigid support. Maintain areas to receive access flooring between 60 and 90 degrees F, and between 20 and 70 percent humidity for 24 hours prior to
SECTION 09 69 13 Page 11 and during installation.
3.1.1 Preparation for Installation
Clear out all debris in the area in which the floor system is to be installed. Thoroughly clean structural floor surfaces and remove all dust. Install floor coatings, required for dust or vapor control, prior to installation of pedestals, only if the pedestal adhesive will not damage the coating. If the coating and adhesive are not compatible, apply the coating after the pedestals have been installed and the adhesive has cured.
3.1.2 Pedestals
Pedestals must be accurately spaced, and set plumb and in true alignment.
Set base plates in full and firm contact with the structural floor, and secured to the structural floor with adhesive or steel expansion anchors in accordance with manufacturer's instructions.
3.1.3 Stringers
Interlock stringers with the pedestal caps to preclude lateral movement, spaced uniformly in parallel lines at the indicated elevation.
3.1.4 Auxiliary Framing
Provide auxiliary framing or pedestals around columns and other permanent construction, at sides of ramps, at open ends of the floor, and beneath panels that are substantially cut to accommodate utility systems. Use special framing for additional lateral support as shown on the approved detailed installation drawings. Provide additional pedestals and stringers designed to specific heights and lengths to meet structural irregularities and design loads. Connect auxiliary framing to main framing.
3.1.5 Panels
Interlock panels with supports in a manner that will preclude lateral movement. Fasten perimeter panels, cutout panels, and panels adjoining columns, stairs, and ramps to the supporting components to form a rigid boundary for the interior panels. Level floors within the specified tolerances. Cut edges of steel and wood-core panels must be finished as recommended by the panel manufacturer. Exposed edges of composite panels must be coated with a silicone rubber sealant or with an adhesive recommended by the panel manufacturer. Secure extruded vinyl edging in place at all cut edges of all panel cut-outs to prevent abrasion of cables. Where the space below the floor is a plenum, close cutouts for conduit and similar penetrations using self-extinguishing sponge rubber or air sealing grommets.
3.1.6 Resilient Base
Provide base at vertical wall intersections as indicated in the drawings.
Apply the base after the floor system has been completely installed.
Install wall base in accordance with manufacturer's printed installation instructions. Prepare and apply adhesives in accordance with manufacturer's printed directions. Tighten base joints and make even with adjacent flooring. Fill voids along the top edge of base at masonry walls with caulk. Roll entire vertical surface of base with hand roller, and
SECTION 09 69 13 Page 12 press toe of base with a straight piece of wood to ensure proper alignment. Avoid excess adhesive in corners.
3.1.7 Repair of Zinc Coating
Repair zinc coating that has been damaged, and cut edges of zinc-coated components and accessories, by the application of a galvanizing repair paint conforming to ASTM A780/A780M . Areas to be repaired must be thoroughly cleaned prior to application of the paint.
3.2 FIELD TESTS
Submit certified copies of test reports from an approved testing laboratory, attesting that the proposed floor system components meet the performance requirements specified.
3.2.1 Acceptance Tests
Conduct acceptance tests after installation of floor system. Make at least one test for each 400 square feet of floor area. Conduct tests in presence of Contracting Officer and representatives of manufacturer and installer. Submit certified copies of test reports from an approved testing laboratory, attesting that the proposed floor system components meet the performance requirements specified.
3.2.2 Grounding
Ground the access flooring system for safety hazard and static suppression. Provide positive contact between components for safe, continuous electrical grounding of entire floor system. Total system resistance from wearing surface of floor to building grounding electrode must be within range of 0.5 to 20,000 megohms.
3.2.2.1 Joint Resistance
Electrical joint resistance between individual stringer and pedestal junctions must be less than 0.1 milliohms. Electrical resistance between stringers and floor panels, as mounted in normal use, must be less than 3 ohms when tested in accordance with ASTM F150.
3.2.3 Electrical Resistance
Conduct testing of electrical resistance, in the completed installation, in the presence of the Contracting Officer in accordance with NFPA 99 , modified by placing one electrode on the center of the panel surface and connecting the other electrode to the metal flooring support. Take measurements at five or more locations. Each measurement must be the average of five readings of 15 seconds duration at each location. During the tests, relative humidity must be 45 to 55 percent and temperature set at 69 to 75 degrees F. Select panels used in the testing at random and include two panels most distant from the ground connection. Measure electrical resistance with instruments that are accurate within 2 percent and that have been calibrated within 60 days prior to the performance of the resistance tests. The metal-to-metal resistance from panel to supporting pedestal must not exceed 10 ohms. The resistance between the wearing surface of the floor covering and the ground connection, as measured on the completed installation, must be in accordance with paragraph FLOOR COVERING.
SECTION 09 69 13 Page 13
3.2.4 SEISMIC SPECIAL INSPECTION AND TESTING
Perform special inspections and testing for seismic-resisting systems and components in accordance with UFC 3-301-01 and Section 01 45 35 SPECIAL
INSPECTIONS.
3.3 CLEANING AND PROTECTION
3.3.1 Cleaning
Keep the space below the completed floor free of all debris. Before any traffic or other work on the completed raised floor is started, clean the completed floor in accordance with the floor covering manufacturer's instructions. Do not permit seepage of cleaner between individual panels. Cleaning of ferrous surfaces must conform to FS TT-C-490 .
3.3.2 Protection
Protect traffic areas of raised floor systems with a covering of building paper, fiberboard, or other suitable material to prevent damage to the surface. Cover cutouts with material of sufficient strength to support the loads to be encountered. Place plywood or similar material on the floor to serve as runways for installation of heavy equipment not in excess of design load capacity. Maintain protection until the raised floor system is accepted.
3.3.3 Surplus Material Removal
Clean surfaces of the work, and adjacent surfaces soiled as a result of the work. Remove all installation equipment, surplus materials, and rubbish from the work site.
3.4 FIRE SAFETY
Install an automatic detection system below the raised floor meeting the requirements of NFPA 75 paragraph 5-2.1 to sound an audible and visual alarm. Air space below the raised floor must be subdivided into areas not exceeding 10,000 square feet by tight, noncombustible bulkheads. Seal all penetrations for piping and cables to maintain bulkhead properties.
3.5 OPERATION AND MAINTENANCE MANUALS
Submit maintenance instructions for proper care of the floor panel surface. When conductive flooring is specified, also submit maintenance instructions to identify special cleaning and maintenance requirements to maintain "conductivity" properties of the panel finish.
-- End of Section --
SECTION 09 69 13 Page 14
SECTION 26 05 26.00 40
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
08/19
Amendment 0002
PART 1 GENERAL
Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM applies to work specified in this section.
Section 26 41 00 LIGHTNING PROTECTION SYSTEMS applies to work specified in this section.
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN WELDING SOCIETY (AWS)
AWS A3.0M/A3.0 (2020) Standard Welding Terms and Definitions
AWS B2.1/B2.1M (2021) Specification for Welding Procedure and Performance Qualification
ASTM INTERNATIONAL (ASTM)
ASTM B3 (2013) Standard Specification for Soft or Annealed Copper Wire
ASTM B8 (2011; R 2017) Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft
ASTM B187/B187M (2020) Standard Specification for Copper, Bus Bar, Rod and Shapes and General Purpose Rod, Bar and Shapes
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 81 (2012) Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System
IEEE C2 (2023) National Electrical Safety Code
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
ANSI/NEMA GR 1 (2007) Grounding Rod Electrodes and Grounding Rod Electorode Couplings
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2023) National Electrical Code
SECTION 26 05 26.00 40 Page 1
NFPA 780 (2023) Standard for the Installation of Lightning Protection Systems
TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)
TIA-607 (2019d) Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises
U.S. DEPARTMENT OF DEFENSE (DOD)
MIL-STD-889 (2021; Rev D) Galvanic Compatibility of Electrically Conductive Materials
UNDERWRITERS LABORATORIES (UL)
UL 467 (2022) UL Standard for Safety Grounding and Bonding Equipment
UL 546 (2008) UL Outline of Investigation for Conductor Termination Compounds
Amendment 0002************************************************************
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-03 Product Data
Ground Rods; G
Ground Wires; G
Connectors and Fasteners; G
Deleted
Conductive Corrosion Inhibiting Compounds; G
Ground Buses; G
SD-06 Test Reports
Bond Resistance Test; G
Ground Resistance Tests; G
Ground Isolation Test; G
Equipment Continuity Test; G
SD-07 Certificates
Ground Resistance Test Equipment; G
Micro-Ohmmeter Test Equipment; G
SECTION 26 05 26.00 40 Page 2
SD-11 Closeout Submittals
Record Drawings ************************************************************Amendment 0002
1.3 QUALITY CONTROL
1.3.1 Regulatory Requirements
In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word, "must" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer. Ensure equipment, materials, installation, and workmanship are in accordance with the mandatory and advisory provisions of NFPA 70 , IEEE C2 unless more stringent requirements are specified or indicated.
1.3.2 Standard Products
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship. Provide products which have been in satisfactory commercial or industrial use for 2 years prior to bid opening. Ensure the 2-year period includes applications of equipment and materials under similar circumstances and of similar size. Ensure the product has been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period. Where two or more items of the same class of equipment are required, these items must be products of a single manufacturer.
1.3.3 Ground Resistance Test Equipment
Provide combination 3-point and 4-point type ground resistance test equipment specifically designed for grounding electrode resistance and soil resistivity tests. Submit proof of current equipment calibration with test equipment product data.
1.3.4 Micro-Ohmmeter Test Equipment
Perform bond resistance tests using a micro-ohmmeter with the following characteristics:
a. Resistance range selectable and capable of measuring to 10 micro-Ohms using a minimum of 1 ampere of test current.
b. Positive and negative test leads of the 2-wire balanced type. Provide both clamp and probe type connections to allow measurements across all bonded surfaces. Provide long length balanced test lead to allow measurements from a bonding location to the nearest test well.
Submit proof of current equipment calibration with test equipment product data.
PART 2 PRODUCTS
Submit material, equipment, and fixture lists for grounding systems, including manufacturer's style or catalog numbers, specification and drawing reference numbers, warranty information, and fabrication site
SECTION 26 05 26.00 40 Page 3 information.
2.1 MATERIALS
2.1.1 Ground Rods
Provide ground rods of copper conforming to UL 467 and ANSI/NEMA GR 1 .
Ensure ground rods are not less than 3/4 inch in diameter and 10 feet in length.
2.1.2 Ground Wires
2.1.2.1 Bare
Provide annealed bare copper, Class "B" stranded ground and bond wires in accordance with ASTM B8 for wires #4 AWG and larger and solid in accordance with ASTM B3 for wires #6 AWG and smaller. Provide conductors with 98 percent conductivity and sized wires in accordance with the requirements of NFPA 70 and NFPA 780 .
2.1.2.2 Straps/Jumpers
Provide copper bonding straps and jumpers with a cross-sectional area of not less than No. 6 AWG. Ensure bonding straps and jumpers for shock-mounted devices with pivot joints are made of flexible stranded wire.
2.1.3 Connectors and Fasteners
2.1.3.1 Exothermic Welds
Ensure the molds, materials and powder charges used to make exothermic welds are the standard product of a single manufacturer and listed by the manufacturer for use on the specific type, size, quantity and configuration of conductors to which the weld is applied.
2.1.3.2 Irreversible Compression Lugs
Provide irreversible compression lug type connectors manufactured from tin-plated copper and installed using a hydraulic compression tool and die to apply correct, uniformly distributed, circumferential pressure. Ensure tools and dies are as recommended by the irreversible compression lug type connector manufacturer. Use an embossing die code or other standard method to provide visible indication that a connector has been adequately compressed onto the conductor. Apply irreversible compression lug type connectors in strict accordance with the manufacturer's written instructions and published installation instructions. Use 2-hole lug type connectors for connections to NEMA cable pads and bus bars, and single-hole connectors otherwise.
2.1.3.3 Mechanical
Provide split bolt and clamp style mechanical type connectors…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .