RFI_Questions_1-3.pdf

PDF 14 KB Posted

Attached to
Repair Fuel Cell Hangar and Add to Fuel Cell Hangar
Solicitation number
W912PQ-16-B-0001
Issued by

About this file

RFI Questions 1-3

View the file

Other files

File Type Posted
Attendance_Sheet.pdf PDF
OF_1419_Page_2.pdf PDF
OF_1419_Page_1.pdf PDF
OF_1419_Page_3.pdf PDF
IFB_Questions_19-23_Response.pdf PDF
IFB_Questions_25-36_Response.pdf PDF
IFB_Questions_24.pdf PDF
IFB_Question_17-18_Response.pdf PDF
Boring_Location_Plan.pdf PDF
IFB_Questions_4-16_Response.pdf PDF
Boring_Log_B101.pdf PDF
W912PQ-16-B-0001.pdf PDF
Boring_Log_B103.pdf PDF
Boring_Log_B102.pdf PDF
2016_08_23_12_55_31.pdf PDF
PREBID_Slides_-_Hangar_A.pptx PPTX presentation
Wage_Determination.pdf PDF
W912PQ-16-B-0001.pdf PDF
Addendum_1_to_Specifications.pdf PDF
Specifications_Vol_1.pdf PDF
Specifications_Vol_2.pdf PDF
Drawings_Burns_and_Mac.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

23 August 2016

RFI Questions 1-3

Project: WKVB142002, Repair Fuel Cell Hangar and WKVB139016 Add Fuel Cell Hangar

106th Rescue Wing, Gabreski ANG Base, Westhampton Beach, New York

Q1. The title of SECTION 09 67 23.15, "ELECTRO-STATIC DISSIPATIVE FUEL RESISTIVE RESINOUS FLOORING, 3-COAT SYSTEM", indicates the flooring is intended to have static dissipative (ESD) properties. However, the products listed in SECTION 09 67 23.15, TABLE II, "PRE-APPROVED MATERIALS", are not ESD materials. What products are intended to be installed? Standard/ insulative or ESD flooring?

A1: The design calls for Standard Fuel Resistive Resinous Flooring, 3-Coat System. Electro- Static Dissipative materials are not required.

Q2. The Room Finish Schedule, A-701, indicates that the "EDU", Electrostatic Dissipative Chemical Resistant Urethane, is to be installed only in Rooms 104 and 105. Is this flooring in fact required to be static dissipative?

A2: No, only Standard Fuel Resistive Resinous Flooring, 3-Coat System is required for these rooms. Refer to spec section 09 67 23.15.

Q3. In the Room Finish Schedule, Room 101, Hangar Bay, Flooring, indicates "ETR", Existing Finishes to Remain. And in Paragraph 3.6.4 Coating Systems, "c. Coatings for Surfaces Not Specified Otherwise: Coat surfaces which have not been specified, the same as surfaces having similar conditions of exposure." In SECTION 09 90 00, we see the statement, "3.8 COATING SYSTEMS FOR CONCRETE AND CEMENTITIOUS SUBSTRATES -- Apply coatings of Tables in Division 3, 4 and 9 for Exterior and Interior." Does this mean that the existing hangar floor finishes in Room 101 are to be recoated? If yes, what is the existing finish? Does it have static dissipative properties?

A3: No, the existing hangar floor is not scheduled to be recoated. However, if the floor is damaged during the course of construction due to demolition or construction related activities or if areas are uncovered that were not previously coated, then patching and repairing to match existing adjacent flooring is required. Base to confirm existing coating system which is assumed to be a fuel resistive resinous coating system.

A1: The design calls for Standard Fuel Resistive Resinous Flooring, 3-Coat System. Electro- Static Dissipative materials are not required.
A2: No, only Standard Fuel Resistive Resinous Flooring, 3-Coat System is required for these rooms. Refer to spec section 09 67 23.15.
A3: No, the existing hangar floor is not scheduled to be recoated. However, if the floor is damaged during the course of construction due to demolition or construction related activities or if areas are uncovered that were not previously coated, then ...