W912PL-20-R-0004_Plans_SCICLC_Solicitation_VOL2F_Part3.pdf
PDF 7 MB Posted
- Solicitation number
- W912PL-20-R-0004
About this file
This solicitation seeks proposals for the construction of a new Spinal Cord Injury and Community Living Center Building and parking structure at the Veterans Affairs Healthcare System campus in San Diego, California. Key details include the construction of a new approximately 197,000 square foot facility containing a 50-bed spinal cord injury center, 33-bed community living center, outpatient clinic, and physical/occupational and aquatic therapy spaces. An 800-car parking structure is also included. The project cost range is estimated between $100-250 million. The solicitation will be available on October 31, 2019, with proposals due January 21, 2020. The contract will be awarded as a firm fixed-price contract with a 1096 calendar day performance period. The North American Industry Classification code is 236220. This is an unrestricted procurement with HUBZone price evaluation preference conducted by the Department of the Army Corps of Engineers Los Angeles District.
Plans - SCICLC - Volume 2F Part 3
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
R E
G
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
T E
OF CA L I FORN
I A
No. M029768
Exp. 06/30/20
M
E C H A N I C A
L
P A
U L
Q I P I NG
DO
N G
(949) 250-1500
2355 Main Street Suite 220
Irvine
Drawing Title
Approved: Project Director
Project Title
Date
Location
Reviewed
Building Number
Project Number
Drawing Number
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
D
Department of Veterans Affairs
2 3 4 5 6
C
B
A
/1
/2
:4 :2
P
M C
R e v it
L o c a l F il e s \V
A S
C I_
M E ll ie
. T ra n .r v t
SEISMIC DEFICIENCY -
SCI & CLC HOSPITAL
3350 La Jolla Village Dr.
San Diego, CA 92037
EBA
MECHANICAL SCHEDULES - 9
MH609
664-401
07/19/2019
S
I
T A
E
T S
L
N
E C C
N
O
CFO FILA
R
A I
T
I
CRADE H
E T
REN.: 10-31-19
NO. C-28367
DAVID HUNT
Solicitation Number: W912PL20R0004
G
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
T E
OF CA L I FORN
I A
No. M029768
Exp. 06/30/20
M
E C H A N I C A
L
P A
U L
Q I P I NG
DO
N G
(949) 250-1500
2355 Main Street Suite 220
Irvine
Drawing Title
Approved: Project Director
Project Title
Date
Location
Reviewed
Building Number
Project Number
Drawing Number
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
D
Department of Veterans Affairs
2 3 4 5 6
C
B
A
/1
/2
:4 :2
P
M C
R e v it
L o c a l F il e s \V
A S
C I_
M E ll ie
. T ra n .r v t
SEISMIC DEFICIENCY -
SCI & CLC HOSPITAL
3350 La Jolla Village Dr.
San Diego, CA 92037
EBA
MECHANICAL SCHEDULES - 10
MH610
664-401
07/19/2019
S
I
T A
E
T S
L
N
E C C
N
O
CFO FILA
R
A I
T
I
CRADE H
E T
REN.: 10-31-19
NO. C-28367
G
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
T E
OF CA L I FORN
I A
No. M029768
Exp. 06/30/20
M
E C H A N I C A
L
P A
U L
Q I P I NG
DO
N G
(949) 250-1500
2355 Main Street Suite 220
Irvine
Drawing Title
Approved: Project Director
Project Title
Date
Location
Reviewed
Building Number
Project Number
Drawing Number
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
D
Department of Veterans Affairs
2 3 4 5 6
C
B
A
/1
/2
:4 :2
P
M C
R e v it
L o c a l F il e s \V
A S
C I_
M E ll ie
. T ra n .r v t
SEISMIC DEFICIENCY -
SCI & CLC HOSPITAL
3350 La Jolla Village Dr.
San Diego, CA 92037
EBA
MECHANICAL SCHEDULES - 11
MH611
664-401
07/19/2019
S
I
T A
E
T S
L
N
E C C
N
O
CFO FILA
R
A I
T
I
CRADE H
E T
REN.: 10-31-19
NO. C-28367
G
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
T E
OF CA L I FORN
I A
No. M029768
Exp. 06/30/20
M
E C H A N I C A
L
P A
U L
Q I P I NG
DO
N G
(949) 250-1500
2355 Main Street Suite 220
Irvine
Drawing Title
Approved: Project Director
Project Title
Date
Location
Reviewed
Building Number
Project Number
Drawing Number
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
D
Department of Veterans Affairs
2 3 4 5 6
C
B
A
/1
/2
:4 :3
P
M C
R e v it
L o c a l F il e s \V
A S
C I_
M E ll ie
. T ra n .r v t
SEISMIC DEFICIENCY -
SCI & CLC HOSPITAL
3350 La Jolla Village Dr.
San Diego, CA 92037
EBA
MECHANICAL SCHEDULES - 12
MH612
664-401
07/19/2019
S
I
T A
E
T S
L
N
E C C
N
O
CFO FILA
R
A I
T
I
CRADE H
E T
REN.: 10-31-19
NO. C-28367
G
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
T E
OF CA L I FORN
I A
No. M029768
Exp. 06/30/20
M
E C H A N I C A
L
P A
U L
Q I P I NG
DO
N G
(949) 250-1500
2355 Main Street Suite 220
Irvine
Drawing Title
Approved: Project Director
Project Title
Date
Location
Reviewed
Building Number
Project Number
Drawing Number
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
D
Department of Veterans Affairs
2 3 4 5 6
C
B
A
/1
/2
:4 :3
P
M C
R e v it
L o c a l F il e s \V
A S
C I_
M E ll ie
. T ra n .r v t
SEISMIC DEFICIENCY -
SCI & CLC HOSPITAL
3350 La Jolla Village Dr.
San Diego, CA 92037
Checker
MECHANICAL SCHEDULES - 13
MH613
664-401
Author
Approver 07/19/2019
S
I
T A
E
T S
L
N
E C C
N
O
CFO FILA
R
A I
T
I
CRADE H
E T
REN.: 10-31-19
NO. C-28367
DAVID HUNT
CLEAN STEAM GENERATOR SCHEDULE
STEAM HUMIDIFIERS SCHEDULE
MARK
AIR HANDLING UNITS
SERVED
MANUFACTURER MODEL TYPE
LOCATION REMARKS
CATALOG DATA CLEAN STEAM CONTROL PANEL
FLOODED
WEIGHT (LBS)
PRODUCED STEAM
FLOW (LBS/HR)FLOW (GPM)
ENT CONTROL
VALVE
(LBS/HR)
ENT HEAT
EXCHANGER
(PSIG)
SUPPORT DETAIL
MARK
SHEET NO.
CATALOG DATA
MANUFACTURER MODEL TYPE
SERVING
STEAM
CFM
DUCT SIZE
IN x IN
NON-WETTING
DISTANCE IN
HUMIDIFIER
OPERATING
WT. LBS.
REMARKSCONTROL VALVE
POWER
REQUIREMENT
EMERGENCY
POWER
SUPPLY
ELECTRICAL DATA
CAPACITY LB/HR
STEAM WORKING
PRESSURE (PSIG)
SOURCE STEAM
POWER REQUIREMENTS (V-PH-∅)Cv
115-1-60
MECHANICAL SCHEDULES
THERMAFLO AHU-1 THRU AHU-9 MH 401 1, 2, 3THCSV-4000-EL26-SG1 -
QUALITY PRESS PSIG
2,261
91,500
18,700
119x52YES
106x44
106x44
119x52
YES
YES
YES
YES
YES
83x29YES
DRISTEEM
DRISTEEM
DRISTEEM
DRISTEEM
DRISTEEM
DRISTEEM
DRISTEEM
26-H2
26-H1
ULTRA-SORB MP-1.5"
119x52
106x44
MH 404
MH 404
MH 402
115-1-60/
24V STEP DOWN
MH 403
MH 403
DRISTEEM
DRISTEEM
YES
YES
115-1-60/
24V STEP DOWN
115-1-60/
24V STEP DOWN
115-1-60/
24V STEP DOWN
115-1-60/
24V STEP DOWN
115-1-60/
24V STEP DOWN
115-1-60/
24V STEP DOWN
115-1-60/
24V STEP DOWN
115-1-60/
24V STEP DOWN
125222,502
TREATED WATER
<1.0 GRAINS/GAL.
SOFT WATER
MIN. WATER
PRESSURE PSIG
1, 2, 3, 426 AHU-1 185
342.7
314.8
286.8
275.1
278.0
282.4
310.4
285.3
126.5
26-H3
26-H4
26-H5
26-H6
26-H7
26-H8
26-H9
ULTRA-SORB MP-1.5"
ULTRA-SORB MP-1.5"
ULTRA-SORB MP-1.5"
ULTRA-SORB MP-1.5"
ULTRA-SORB MP-1.5"
ULTRA-SORB MP-1.5"
ULTRA-SORB MP-1.5"
ULTRA-SORB MP-1.5"
MH 404
MH 404
MH 402
MH 402
26 AHU-2
26 AHU-3
26 AHU-4
26 AHU-5
26 AHU-6
26 AHU-7
26 AHU-8
26 AHU-9
23,300
21,400
18,900
18,900
21,100
19,200
8,600
1, 2, 3, 4
1, 2, 3, 4
1, 2, 3, 4
1, 2, 3, 4
1, 2, 3, 4
1, 2, 3, 4
1, 2, 3, 4
1, 2, 3, 4
106x44
106x44
CONDITION
DE-IONIZED OR
REVERSE-OSMOSIS
1. UNIT SHALL HAVE BACNET COMMUNICATION.
2. PRVIDE SIEMENS DLC CONTROL SYSTEM.
3. PRVIDE AUTOMATIC PUMP TRAP FOR CONDENSATE LIFT, SIGHT LEVEL GAUGE AND LEVEL CONTROL, ELECTRONIC FAIL SAFE STEAM CONTROL VALVE, ELECTRONIC MODULATING
MAKEUP WATER CONTROL VALVE, PRESSURE RELIEF VALVE, ELECTRONIC CONDUCTIVITY CONTROLER, CONDUCTIVITY SENSOR PROBE, DIGITAL PRESSURE GAUGE TRANSMITTER
WITH SYPHON AND ISOLATION VALVE, VACUUM BREAKER.
1. HUMIDIFIER SHALL CONSIST OF HIGH EFFICIENCY INSULATED TUBES.
2. STEAM VALVE SHALL BE PROVIDED BY HUMIDIFIER MANUFACTURER (ELECTRIC CONTROL, 24V, SIZE = 1/2", CV = 7.5; VALVE MAX. CAPACITY PER MANUFACTURER, CAST ITRON STRAINER, STRAINER SIZE = 1 1/2", CAST IRON F & T STEAM
TRAP).
3. SECONDARY LIMIT CONTROL SHALL BE BY TEMP AND FLOAT SWITCH
4. MECHANICAL CONTRACTOR SHALL COORDINATE WITH PLUMBING CONTRACTOR FOR THE PROVISION OF DISPERSION DRAIN COOLER AND DISPOSAL OF STEAM CONDENSATE.
PENTHOUSE
ROOF
4TH FLOOR
3RD FLOOR
2ND FLOOR
1ST FLOORTHERAPEUTIC POOL
ELECTRICAL ROOM
4B131
ELECTRICAL ROOM
3B126
ELECTRICAL ROOM
2B132
ELECTRICAL ROOM
4A109
ELECTRICAL ROOM
3A104
ELECTRICAL ROOM
2A104
1A27
IDF ROOM
1A27
ELECTRICAL ROOM
1B32E
IDF RM
1B132
ELECTRICAL ROOM
1B132F
MDF RM
C102
SERVICE VESTIBULE
C101
CONNECTOR VESTIBULE
ELECTRICAL ROOM
4A173
ELECTRICAL ROOM
4A143
ELECTRICAL ROOM
3A169
ELECTRICAL ROOM
3A136
ELECTRICAL ROOM
2B160
ELECTRICAL ROOM
2A106
ELEV. MACHINE RM.
1B132E
EMERGENCY POWER
1C105
SERVICE ELEV.
MACHINE RM.
1B132G
FIRE PUMP ROOM
1B132C/D
PUMP/MECHANICAL ROOM
1B132T
AREA WAY
NORTH WINGNORTH WING
(IST & 2ND FLR-EAST SIDE) (3RD & 4TH FLR-EAST SIDE)
SOUTH WING
(3RD & 4TH FLR-EAST SIDE)
SOUTH WINGSOUTH WING
(IST & 2ND FLR-EAST SIDE)
SOUTH WING
(3RD & 4TH FLR-WEST SIDE)
NORTH WING
(3RD & 4TH FLR-WEST SIDE)
NORTH WING
(IST & 2ND FLR-WEST SIDE) (HALLWAY/BALCONY)
26-AHU2
46x40 SA (17780 CFM)
F/S DPR 48x24 RA (6390 CFM)
F/S DPR
44x18 RA (6460 CFM)
F/S DPR
F/S DPR
F/S DPR
F/S DPR
56x40 RA (12850 CFM)56x40 RA(13030 CFM)
46x24 SA (8990 CFM)F/S DPR
26-AHU1
26-TU-2.14
26-TU-2.29
THRU
56x40 RA (12850 CFM)
46x22 SA (8790 CFM)
44x18 RA (6460 CFM)
46x22 SA (8790 CFM)
F/S DPR
26-TU-2.1
26-TU-2.13
THRU
42x24 SA (8180 CFM)
44x20 RA (6260 CFM)
42x24 SA (10450 CFM)
44x20 RA (6770 CFM)
26-TU-1.9
26-TU-1.23
THRU
42x24 SA (8180 CFM)
44x20 RA (6260 CFM)
26-TU-1.1a
26-TU-1.8
THRU
56x40 SA ( 18630 CFM) 56x40 RA (13030)
MECHANICAL SHAFT
26-AHU8 26-AHU7
F/S DPR
48x20 RA (7150) CFM)
F/S DPR
48x24 SA (10130 CFM)
F/S DPR
F/S DPR
F/S DPR
F/S DPR
F/S DPR
46x22 SA (7970 CFM) 40x20 RA ( 5570 CFM)
48x28 SA (12260 CFM)
48x28 RA (6780 CFM)
26-TU-3.15
26-TU-3.29
THRU
46x22 SA (7970 CFM)
40x20 RA (5570 CFM)
F/S DPR
F/S DPR
46x40 RA (13300 CFM)
52x34 SA(18400 CFM) 52x 34 RA (13300 CFM)
46x24 SA (5480 CFM)
48x24 RA (7470 CFM)
52x24 SA (5000 CFM)
F/S DPR
F/S DPR
40x20 RA (5830CFM)
26-TU-8.1
26-TU-8.13
THRU
26-TU-8.14
26-TU-8.28
THRU
40x34 SA (8 440 CFM)
40x20 RA (5830) CFM)
46x40 RA (17780 CFM)
52x34 SA(22040 CFM) 52x 34 RA (17780 CFM)
52x24 SA (11360 CFM)
F/S DPR
F/S DPR
40x20 RA (9640 CFM)
26-PDU1
68x18 SA (10680 CFM)
46x16 RA (8140 CFM
56x22 SA (10680 CFM)
56x22 RA (8140 CFM)
F/S DPR
F/S DPR
MECHANICAL SHAFT
48x48 RA (15520 CFM)52x36 RA(12350 CFM)
26-AHU9 26-AHU6
(3RD & 4TH FLR-WEST SIDE)
26-AHU5
52x36 SA(19320CFM) 52x 36 RA (17160 CFM)
F/S DPR
F/S DPR50x28SA (11370 CFM)
50x28 RA (10480 CFM)
26-TU-6.13
26-TU-6.25b
THRU
26-TU-6.1
26-TU-6.12
THRU
40x24 SA (7950 CFM)
40x22 RA (6680) CFM)
F/S DPR
F/S DPR40x24 SA (7950 CFM)
40x22 RA (6680) CFM)
44x44 RA (17160 CFM)
F/S DPR
F/S DPR46x24 SA (9320 CFM)
46x22 RA (8230) CFM)
26-TU-5.1
26-TU-5.12
THRU
46x24 SA (9320 CFM)
46x22 RA (8230) CFM)
F/S DPR
F/S DPR
26-TU-5.13
26-TU-5.25
THRU 50x24 SA (10080 CFM)
50x24 RA (8870) CFM)
46x40 SA (19400 CFM) 56x40 RA (17100 CFM)
44x44 RA (17100 CFM)
48x48 SA (20230CFM)
26-AHU3 26-AHU4
48x48 RA (12350 CFM)
48x24 SA (10130 CFM)
48x20 RA (7150) CFM)
48x20 RA (8370) CFM)
48x30 SA (11400 CFM)48x48 RA (21530 CFM)
26-TU-4.13
26-TU-4.31
THRU
26-TU-4.1
26-TU-4-12
THRU
26-TU-3.1
26-TU-3.14
THRU
26-TU-9.4
26-TU-9.3
26x16 SA (7100 CFM)
26-TU-9.1a
F/S DPR
42x22 RA (6770 CFM)
F/S DPR
F/S DPR
F/S DPR
30x30 SA (7100 CFM)
30x32 SA (7900CFM)
30x30 RA (5970CFM)
18x10 SA (800 CFM)
18x10 RA (690 CFM)
40x36 RA (7460 CFM)
30x32 SA (8700 CFM)
18x10 SA (800 CFM)
28x16 SA (3600 CFM)
20x22 RA (3600 CFM)
MECHANICAL SHAFT MECHANICAL SHAFT MECHANICAL SHAFT
26-FCU6.1
26-FCU4.3
26-FCU3.3
26-FCU2.3
26-FCU4.1
26-FCU3.1
26-FCU2.1
WALL MOUNT
FAN COIL UNI
(TYP.)
26-FCU1.126-FCU1.226-FCU1.4
26-FCU1.3b26-FCU1.3a
(2700 CFM) DUCTED CEILING
SUSPENDED
(TYP.)
(2700 CFM)
(2700 CFM) (2700 CFM)
(950 CFM)
(950 CFM)
26-FCU1.626-FCU1.8
(400 CFM)
(400 CFM)
26-FCU4.4 26-FCU4.2
26-FCU3.4 26-FCU3.2
26-FCU2.4 26-FCU2.2
(800 CFM)
(800 CFM)
26-FCU1.5
(400 CFM)
(400 CFM)
26-FCU1.7
26-TU-7.10
26-TU-7.21
THRU
26-TU-7.1
26-TU-7.9b
THRU
26-TU-7.24a
26-TU-7.24b
26-TU-7.22
26-TU-7.23
(4000 CFM)
(4000 CFM)
(19 IN TOTAL)
(13 IN TOTAL)
(18 IN TOTAL)
(16 IN TOTAL)
(14 IN TOTAL)
(12 IN TOTAL)
(13 IN TOTAL)
(13 IN TOTAL)
26-TU-9.2
THRU
(5 IN TOTAL)(9 IN TOTAL)
(16 IN TOTAL)
(13 IN TOTAL)
(16 IN TOTAL)(17 IN TOTAL)
(13 IN TOTAL)
(17 IN TOTAL)
(13 IN TOTAL)
SERVED BY 26-TU-7.9a AND 26-TU-7.9b
26-TU-7.25
26-SF10
30x18 SA (4200 CFM)
FD
FD FD
FD FD
FD FD
FD
FD
FD
FD
FD FD
FD FD
FD FD
FD
26-TU-7.26
R E
G
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
T E
OF CA L I FORN
I A
No. M029768
Exp. 06/30/20
M
E C H A N I C A
L
P A
U L
Q I P I NG
DO
N G
(949) 250-1500
2355 Main Street Suite 220
Irvine
Drawing Title
Approved: Project Director
Project Title
Date
Location
Reviewed
Building Number
Project Number
Drawing Number
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
D
Department of Veterans Affairs
2 3 4 5 6
C
B
A
/1
/2
:4 :3
P
M C
R e v it
L o c a l F il e s \V
A S
C I_
M E ll ie
. T ra n .r v t
SEISMIC DEFICIENCY -
SCI & CLC HOSPITAL
3350 La Jolla Village Dr.
San Diego, CA 92037
EBA
MECHANICAL HVAC FLOW DIAGRAM-1
(SPPLY/RETURN SYSTEM)
MH701
664-401
07/19/2019
S
I
T A
E
T S
L
N
E C C
N
O
CFO FILA
R
A I
T
I
CRADE H
E T
REN.: 10-31-19
NO. C-28367
1B132G
FIRE PUMP ROOM
1B132C/D
PUMP/MECHANICAL ROOM
1B132T
AREA WAY
2ND FLOOR
1ST FLOOR
4TH FLOOR
3RD FLOOR
ROOF
NORTH WING (WEST SIDE)
THERAPEUTIC POOL
26-EF826-EF7
F/S DPR
F/S DPR
F/S DPR
F/S DPR
26-EF11
24x24 (5240 CFM)
20x20 (2420 CFM)
20x20 (2820 CFM)
24x20 (4820 CFM)
24x18 (2750 CFM)
20x18 (2070 CFM)
NORTH WING ( EAST SIDE)
ISO. RM. EXH.26-EF1
26-EF2
26-EF9
F/S DPR
F/S DPR
F/S DPR
F/S DPR
24x24 (6480 CFM)
20x20 (4530 CFM)
30x16 (1950 CFM)
24x24 (5170 CFM)
24x18 (2230 CFM)
20x18 (2940 CFM)
F/S DPR
F/S DPR
F/S DPR
20x20 (2695 CFM)
18x12 (1115 CFM)
18x16 (870 CFM)
18x10 (710 CFM)
20x20 (1580 CFM)
24x24 (5240 CFM)
SOUTH WING ( MID SHAFT)
ISO. RM. EXH.26-EF6
26-EF5
26-EF10
F/S DPR
F/S DPR
F/S DPR
F/S DPR
14x10 (1860 CFM)
16x12 (1100 CFM)
12x12 (890 CFM)
16x14 (1460 CFM)
F/S DPR
F/S DPR
14x10 (905 CFM)
18x10 (705 CFM)
16x14 (1510 CFM)
20x18 (2960 CFM)
SOUTH WING (EAST SIDE)
26-EF426-EF3
F/S DPR
F/S DPR
F/S DPR
F/S DPR
32x24 (8045 CFM)
28x20 (5705 CFM)
24x16 (2340 CFM)
30x22 (6230 CFM)
18x18 (2900 CFM)
20x18 (3330 CFM)
32x24 (8045 CFM)
MECHANICAL SHAFT MECHANICAL SHAFT MECHANICAL SHAFT MECHANICAL SHAFT
PENTHOUSE
24x24 (6480 CFM)
30x16 (3800 CFM)
26-EF12
42x24 (4200 CFM)
20x18 (2350 CFM) 20x18(2960 CFM)
16x14 (1610 CFM)
FDFD FDFD FDFD
FDFD
R E
G
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
T E
OF CA L I FORN
I A
No. M029768
Exp. 06/30/20
M
E C H A N I C A
L
P A
U L
Q I P I NG
DO
N G
(949) 250-1500
2355 Main Street Suite 220
Irvine
Drawing Title
Approved: Project Director
Project Title
Date
Location
Reviewed
Building Number
Project Number
Drawing Number
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
D
Department of Veterans Affairs
2 3 4 5 6
C
B
A
/1
/2
:4 :4
P
M C
R e v it
L o c a l F il e s \V
A S
C I_
M E ll ie
. T ra n .r v t
SEISMIC DEFICIENCY -
SCI & CLC HOSPITAL
3350 La Jolla Village Dr.
San Diego, CA 92037
EBA
MECHANICAL HVAC FLOW DIAGRAM-2
(EXHAUST SYTEM)
MH702
664-401
07/19/2019
S
I
T A
E
T S
L
N
E C C
N
O
CFO FILA
R
A I
T
I
CRADE H
E T
REN.: 10-31-19
NO. C-28367
ELECTRICAL ROOM
3B142
ELECTRICAL ROOM
2B132
ELECTRICAL ROOM
3A136
ELECTRICAL ROOM
2A106
IDF ROOM
3A104
IDF ROOM
2A104
1A127
IDF ROOM
1A128A
ELECTRICAL ROOM
1B32E
IDF ROOM
1B132
ELECTRICAL ROOM
1B132F
MDF RM
C102
SERVICE VESTIBULE
C101
CONNECTOR VESTIBULE
ELECTRICAL ROOM
4B131
IDF ROOM
4A173
IDF ROOM
2B160
ELECTRICAL ROOM
4A143
IDF ROOM
4A109
IDF ROOM
3B131
1B132E
EMERGENCY POWER
1C105
SERVICE ELEV.
MACHINE RM.
4 TONS4 TONS
4 TONS
4 TONS
3 TONS
2 TONS 8 TONS
8 TONS
3 TONS
2 TONS
3 TONS
2 TONS
3 TONS
2 TONS
2ND FLOOR
1ST FLOOR
4TH FLOOR
3RD FLOOR
PENTHOUSE (SOUTH WING)
26-AHU926-AHU2
26-AHU7 26-AHU1 26-AHU826-AHU4
26-AHU6 26-AHU3
PENTHOUSE
ROOF
26-FCU6.1
26-FCU3.3
26-FCU2.3
26-FCU3.2
26-FCU2.2
WALL MOUNT
FAN COIL UNIT
(TYP.)
26-FCU3.1B
26-FCU2.1A
26-FCU1.1B
26-FCU1.2
26-FCU1.4A
26-FCU1.3b
26-FCU1.3a
DUCTED CEILING
SUSPENDED
(TYP.)
26-FCU1.5
26-FCU1.8
CHS
CHR
MECHANICAL SHAFT
CHS
CHR
CHS
CHR
8" CHS/R (869.7 GPM)
6" CHS/R (379.0 GPM)
CHR
CHS
1-1/2" CHS/R (13.6 GPM)
3" CHS/R (98.5 GPM)
3" CHS/R (79.1 GPM)
3" CHS/R (86.1 GPM) 2" CHS/R (33.6 GPM)
6" CHS/R (397.2)
3" CHS/R (86.3 GPM)4" CHS/R (133.5 GPM)
26-AHU5
CHS
CHR
CHS
CHRCHR
CHS
CHR
CHS
3" CHS/R (75.6 GPM) 3" CHS/R (99.4 GPM)
3" CHS/R (78.0 GPM) 3" CHS/R (92.6 GPM)
CHR
CHS
6" CHS/R (345.6 GPM)
26-FCU4.3
CHR
CHS
1-1/4" (8.2 GPM)
C H
R C
H S
2" CHS/R CAP FOR
FUTURE CONNECTION
3/4" (3.3 GPM)
CHS
CHR
1-1/4" (9.2 GPM)
FLOOR MOUNT
FAN COIL UNIT
26-FCU4.4
3/4" (3.3 GPM)
26-FCU2.4
CHR
CHS
1-1/4" (8.2 GPM)
3/4" (3.3 GPM)
3/4" (2.4 GPM)
CHS
CHR
1-1/4" (9.2 GPM)
1-1/2" (16.4 GPM)
1-1/2" (16.4 GPM)
CHS
CHR
3/4" (3.3 GPM)
3/4" (3.1 GPM) 3/4" (1.7 GPM)
C H
R C
H S
6" CHS/R (372.2 GPM)
MECHANICAL SHAFT
26-FCU4.2 26-FCU4.1
3/4" (3.3 GPM)
CHS
CHR
1-1/4" (8.2 GPM)
26-FCU3.4
CHR
CHS
1-1/4" (8.2 GPM)
3/4" (3.3 GPM)
26-FCU1.6B
26-FCU1.73/4" (1.6 GPM)
4" 4"
4" CHS/R (177.6 GPM)
4" CHS/R (170.6 GPM)
4" CHS/R (219.6 GPM)
CHS
CHR
PENTHOUSE (NORTH WING)
TO UTILITY TUNNEL
2" CHS/R CAP FOR
FUTURE CONNECTION
2" CHS/R CAP FOR
FUTURE CONNECTION
2" CHS/R CAP FOR
FUTURE CONNECTION
CHS
CHR
6" CHS/R (421.8 GPM)
6" CHS/R (424.7 GPM)
6" CHS/R (444.6 GPM)
6" CHS/R (421.8 GPM)
2" CHS/R CAP FOR
FUTURE CONNECTION
2" CHS/R CAP FOR
FUTURE CONNECTION
2" CHS/R CAP FOR
FUTURE CONNECTION
2" CHS/R CAP FOR
FUTURE CONNECTION
26-FCU1.1A
26-FCU1.6A
26-FCU1.4B
26-FCU2.1B
26-FCU3.1A
1 (3.5 GPM)
1" (3.5 GPM)
3/4" (2.4 GPM)
1-1/4" (11.9 GPM)
1-1/4" (11.9 GPM)
1-1/2" (15 GPM)
1" (3.5 GPM)
3/4" (2.4 GPM)
3/4" (3.3 GPM)
1" (3.5 GPM) 1" (4.9 GPM)
1" (4.9 GPM)
1" (4.9 GPM)1" (4.9 GPM)
3/4" (2.4 GPM)
R E
G
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
T E
OF CA L I FORN
I A
No. M029768
Exp. 06/30/20
M
E C H A N I C A
L
P A
U L
Q I P I NG
DO
N G
(949) 250-1500
2355 Main Street Suite 220
Irvine
Drawing Title
Approved: Project Director
Project Title
Date
Location
Reviewed
Building Number
Project Number
Drawing Number
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
D
Department of Veterans Affairs
2 3 4 5 6
C
B
A
/1
/2
:4 :4
P
M C
R e v it
L o c a l F il e s \V
A S
C I_
M E ll ie
. T ra n .r v t
SEISMIC DEFICIENCY -
SCI & CLC HOSPITAL
3350 La Jolla Village Dr.
San Diego, CA 92037
EBA
MECHANICAL HVAC PIPING DIAGRAM -
MH703
664-401
07/19/2019
S
I
T A
E
T S
L
N
E C C
N
O
CFO FILA
R
A I
T
I
CRADE H
E T
REN.: 10-31-19
NO. C-28367
C102
SERVICE VESTIBULE
C101
CONNECTOR VESTIBULE
2ND FLOOR
1ST FLOOR
4TH FLOOR
3RD FLOOR
PENTHOUSE
ROOF
26-FCU1.8
HWS
HWR
MECHANICAL SHAFT
H
W R
H W
S
H W
R H
W S
4" HWS/R
MECHANICAL SHAFT
HWS
HWR
SOUTH WING
6" HWS/R
2" HWS/R- SEE MH204A, MH204B
3" HWS/R
2" HWS/R- SEE MH203A, MH203B
2" HWS/R- SEE MH202A, MH202B
3" HWS/R
NORTH WING SOUTH WING
2" HWS/R- SEE MH204C
2" HWS/R- SEE MH203C
2" HWS/R- SEE MH202C
4" HWS/R
3" HWS/R- SEE MH201C, MH201D
2" HWS/R- SEE MH201A
4" HWS/R
3" HWS/R
4" HWS/R
NORTH WING
26-TU-9.1a
26-TU-9.2
THRU
1-1/2" HWS/R -
SEE MH201B
26-TU-7.1
26-TU-7.9b
THRU
26-TU-1.1
26-TU-1.8
THRU
26-TU-7.22
26-TU-7.23
THRU
26-TU-1.9
26-TU-1.31
THRU
26-TU-7.18
26-TU-8.1
26-TU-8.13
THRU
26-TU-2.2
26-TU-2.13
THRU
26-TU-9.4
26-TU-9.3
26-TU-8.14
26-TU-8.20
THRU
26-TU-2.14
26-TU-2.29
THRU
26-TU-6.13
26-TU-6.25b
THRU
26-TU-4.13
26-TU-4.31
THRU
26-TU-6.1
26-TU-6.12
THRU
26-TU-4.1
26-TU-4.12
THRU
26-TU-5.13
26-TU-5.34
THRU
26-TU-3.15
26-TU-3.34
THRU
26-TU-5.1
26-TU-5.12
THRU
26-TU-3.1
26-TU-3.14
THRU
3" HWS/R 4" HWS/R
TO/FROM MECHANICAL ROOM 1B132D
26-AFCV-5.16S
26-TU-7.10
26-TU-7.16
26-AFCV7.17S
THRU
26-TU-7.25
26-TU-4.32
26-TU-4.37
THRU
26-AFCV-4.3S 26-TU-6.26
26-TU-6.30
THRU
26-AFCV-2.15S
26-TU-8.22
26-TU-8.28
THRU
26-TU-8.29
26-TU-8.31
THRU
26-AFCV-2.1S
26-TU-2.16
26-TU-2.30
26-TU-2.36
THRU
26-TU-2.37
26-AFCV-8.21S
26-TU-7.26
26-TU-7.27
THRU
26-TU-7.34
3/4" HWS/R
3/4" HWS/R
3/4" HWS/R
R E
G
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
T E
OF CA L I FORN
I A
No. M029768
Exp. 06/30/20
M
E C H A N I C A
L
P A
U L
Q I P I NG
DO
N G
(949) 250-1500
2355 Main Street Suite 220
Irvine
Drawing Title
Approved: Project Director
Project Title
Date
Location
Reviewed
Building Number
Project Number
Drawing Number
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
D
Department of Veterans Affairs
2 3 4 5 6
C
B
A
/1
/2
:4 :4
P
M C
R e v it
L o c a l F il e s \V
A S
C I_
M E ll ie
. T ra n .r v t
SEISMIC DEFICIENCY -
SCI & CLC HOSPITAL
3350 La Jolla Village Dr.
San Diego, CA 92037
EBA
MECHANICAL HVAC PIPING DIAGRAM -
MH704
664-401
07/19/2019
S
I
T A
E
T S
L
N
E C C
N
O
CFO FILA
R
A I
T
I
CRADE H
E T
REN.: 10-31-19
NO. C-28367
ROOF
LEVEL 2
LEVEL-4
LEVEL 3
P
P
N.C. N.C.
N.C.
N.C.
N.C.
N.C.
P
P
P
S
VB VB
S
P
P
P
N.C.
P
P
N.C.N.C.
P
N.C.
P
RLF
DD
V
6" MPS (30 PSIG) 6" MPS (30 PSIG)
V
2" P
C R
VTR
R
LF
PRV STATION
(1 - STAGE)
(125-30 PSIG)
N.C.N.C.
LP
R
D
D
OVERFLOW
8" MPS (30 PSIG)
LPR
6" H
P S
P
S
IG
8" MPS (30 PSIG)
LP
R
POC
V
GENERAL NOTES:
1. PROVIDE DRIP POCKET AND STEAM TRAP AHEAD OF ALL STEAM GATE VALVES.
2. DRIP POCKET PIPE SIZE SHALL BE SAME AS STEAM MAIN UNLESS OTHERWISE NOTED.
3. PROVIDE WARM-UP BYPASS FOR ALL STEAM MAIN GATE VALVES.
4. RUN FULL SIZE VENT FROM FLASH TANK TO ROOF.
5. FLASH TANK SHALL BE KEPT AT 0 PSIG.
6. START UP AIR VENT LINE TO BE PIPED TO NEARBY DRAIN.
7. PREFABRICATED SKID SHALL INCLUDE RESERVOIR, PUMP, AIR VENT, CHECK VALVES, MOTIVE STEAM DRIP TRAP STATION.
8. AIR VENT AND CHECK VAVLE ON BALANCE LINE TO BE HIGHER THAN STEAM INLET TO HEAT EXCHANGER.
VTR
RLFRLF RLF
MS-101
MS-101
2" P
C R
8" MPS (30 PSIG)
4" MPS
FIRST FLOOR MECHANICAL ROOM
2,416 #/HR
(30 PSIG)
2,416 #/HR
(30 PSIG)
4,455 #/HR
(30 PSIG)
4,455 #/HR
(30 PSIG)
8" MPS (30 PSIG)
D
8" MPS (30 PSIG)
(STANDBY)
(STANDBY)
DD
8" MPS (30 PSIG)
RLF
3/4" MPS
8" MPS (30 PSIG)
D
8" MPS (30 PSIG)
A
A
B
B
4" MPS
3/4" MPS4" MPS
26-HX1
26-HX2
26-HEX1
26-HEX2
26-FT1
26-CRP1
26-PRV1
26-SFM1
STEAM FLOW METER
26-SMS1
STEAM MOISTURE
SEPARATION
FLASH TANK
KEY NOTES:
D
26-HEX5
83 #/HR
(30 PSIG)
26-HEX6
83 #/HR
(30 PSIG)
2,416 #/HR
(30 PSIG)
26-HEX3
2,416 #/HR
(30 PSIG)
(STANDBY)
26-HEX4
DLPR LPR
LPR LPR LPR LPR
4"4"
1-1/2"3/4"1-1/2"
3/4"1-1/2"1-1/2"
3 3 3
FLOAT TYPE STEAM TRAP, SEE DETAIL 2/MH507.
SPT-1, AUTOMATIC PUMP TRAP, FLOW RATE = 2,416 LB/HR, DISCHARGE PRESSURE = 10 PSIG, AIR VENT
ST-1, THERMO-DYNAMIC STEAM TRAP, OPERATING PRESSURE = 30 PSIG, MIN. CAP. = 10 LB/HR, MAX. CAP. = 600 LB/HR.
SPT-2, AUTOMATIC PUMP TRAP, FLOW RATE = 83 LB/HR, DISCHARGE PRESSURE = 10 PSIG, MOTIVE STEAM PRESSURE = 30 PSIG, INLET = 3/4", OUTLET = 3/4", WT. = 114 LBS, SEE GENERAL NOTES 6 THRU 8.
SPT-3, FLOAT & THERMOSTATIC STEAM TRAP, FLOW RATE = 4,455 LB/HR, SIZE = 2", CAST IRON BODY, NPT CONNECTION, INTEGRAL VACUUM BREAKER GAUGE GLASS.7 MOTIVE STEAM PRESSURE = 30 PSIG, INLET = 3", OUTLET = 1.5", WT. = 470 LBS, SEE GENERAL NOTES 6 THRU 8.
C
LPR LPR
LPR LPR LPR
C
1-1/2"
6"
6"
4"
3"
2"
4"
6" GRAVITY CONDENSATE RETURN HEADER
4"
4"
4"
4"
1-1/4"
1-1/4"
1-1/4"
1-1/4"
1-1/4"
1-1/4"
4"
5 5 5
1"
1"
3/4"
3/4"
3"
3"
4" RESERVOIR1-1/2" RESERVOIR
1-1/2" RESERVOIR
1"
1"
3"
3"
4" RESERVOIR
1"
1"
3"
3"
4" RESERVOIR
1"
1"
3"
3"
4" RESERVOIR
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
1-1/4"
4" MPS
1-1/4" 1-1/4"
3" 3" 3"
1-1/2"
3"
1-1/2" 1-1/2" 2" 2"
4" 4" 4"
POCPOC
POC POC POC
POC
(TYP.)
26-PRV2/
THERMAL ERADICATION UNDER DIV. 22, SEE PLUMBING DWG.9
8 8 9
D
FOR SPACE HEATING.10
10 10
THERMODYNAMIC STEAM TRAP WITH INTEGRAL STRAINER, FLOW RATE = 700 LB/HR, 3/4" CONSTRUCTED OF11
HARDENED STAINLESS STEEL WITH OPERATING RANGE UP TO 600 PSIG.
INVERTED BUCKET STEAM TRAP, FLOW RATE = 700 LB/HR, 3/4" CONSTRUCTED OF CAST IRON BODY & STAINLESS12
STEEL BUCKET.
4 MEDIUM PRESSURE STEAM TRAP, SEE DETAIL 9/MH507.
DOMESTIC WATER HEATER UNDER DIV. 22, SEE PLUMBING DWG.8
F.S.
1/2" COLD WATER CONNECTION BY
PLUMBING, SEE PLUMBING DWG
DRAIN COOLER
POCPOC
POC POC POC
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
6"
6"5"
3"
5"
3"
4"4" 3/4"
4" 4" 3/4"
2"
1-1/4"
2-1/2"
TRAP BY
MANUFACTURER
TRAP BY
MANUFACTURER
TRAP BY
MANUFACTURER
TRAP BY
MANUFACTURER
TRAP BY
MANUFACTURER
TRAP BY
MANUFACTURER
26-SG1
CLEAN STEAM GENERATOR
6" HPS
C O
N N
E C
T E
D S
T E
A M
L O
A D
2, LB
S /H
R
PUMP
TRAP
STRAINER
STEAM CONTROL
VALVE
13 85 % DIVERSITY FACTOR IS USED FOR SIZING HPS
14 AUTOMATIC PUMP TRAP FOR CONDENSATE LIFT PROVIDED BY STEAM GENERATOR
MANUFACTURER.
15 6" LPS CLEAN STEAM (15 PSIG) TO AHU'S IN PENTHOUSE
SEE MH201C & MH401 FOR CONTINUATION.
R E
G
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
T E
OF CA L I FORN
I A
No. M029768
Exp. 06/30/20
M
E C H A N I C A
L
P A
U L
Q I P I NG
DO
N G
(949) 250-1500
2355 Main Street Suite 220
Irvine
Drawing Title
Approved: Project Director
Project Title
Date
Location
Reviewed
Building Number
Project Number
Drawing Number
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
D
Department of Veterans Affairs
2 3 4 5 6
C
B
A
/1
/2
:4 :5
P
M C
R e v it
L o c a l F il e s \V
A S
C I_
M E ll ie
. T ra n .r v t
SEISMIC DEFICIENCY -
SCI & CLC HOSPITAL
3350 La Jolla Village Dr.
San Diego, CA 92037
EBA
MECHANICAL STEAM PIPING DIAGRAM
MH705
664-401
07/19/2019
S
I
T A
E
T S
L
N
E C C
N
O
CFO FILA
R
A I
T
I
CRADE H
E T
REN.: 10-31-19
NO. C-28367
NAE
NAE
NCE
esc
NAE
NAE
NAE
NAE
NAE
PRESSURE SWITCH LOW
TO DISABLE RETURN FAN WHEN
SMOKE DAMPER IN RETURN DUCT
CLOSES
PRESSURE SWITCH HIGH
TO DISABLE FAN WHEN HIGH
PRESSURE LIMIT SETPOINT IS
REACHED
ALARM
PROCESSING
D U
T Y
C Y
C
LE
F U
N C
T
IO
N
S C
H E
D U
L E
S T A
R T /S
T O
P
RETURN FAN VSMC ALARM
SUPPLY FAN VSMC ALARM
RETURN FAN STATUS
STATIC PRESSURE HIGH LIMIT
SUPPLY AIR FLOW (CFM)
RETURN LOW PRESSURE
S T A
T U
S
SYSTEM
A L A R
M
P R
IO
R
IT
Y
/A D
D -A
LT
E
R N
A T E
N O
E L E
C T R
IC
D
E V
IC
E
S P
E E D
C O
M M
A N
D
P O
IN
T I D
DISCHARGE STATIC PRESSURE
DISCHARGE AIR HUMIDITY
DISCHARGE AIR TEMPERATURE
MIXED AIR TEMPERATURE
COOLING COIL TEMPERATURE
SYSTEM COMPONENT:
RETURN AIR FLOW (CFM)
RETURN AIR TEMPERATURE
-- O P
E N
/C L O
S E
S T A
R T /S
T O
P -- V
A L V
E P
O S
IT
IO
N
D A
M P
E R
P O
S
IT
IO
N
VAV AIR HANDLER
SYSTEM:
LEGEND
POINT
BINARY
T E
M P
E R
A T U
R E
T I)
L o ca l A la rm P a n e l
M a st er A la rm
P a n e l
A re a A la rm
P a n e l
H
IG
H S
T A
T
IC
P R
E S
S U
R E
H
IG
H H
U M
ID
IT
Y
P R
E S
S U
R E
--L O
W T
E M
P E
R A
T U
R E
P E
R C
E N
T
D
IF
F E
R E
N T
IA
L P
R E
S S
U R
E
P O
S
IT
IO
N
F L O
W
H
IG
H L
IM
IT
L O
W L
IM
IT
SYSTEM INPUTS
ANA- BINARY ANALOG
S P
A C
E T
E M
P . C
O N
T R
O L
--S T A
T
IC
P R
E S
S U
R E
R E
S E
T
A L A
R M
I N
S T R
U C
T
IO
N S
D E
M A
N D
L
IM
IT
IN
G
T E
M P E
R A
T U
R E
R E
S E
T
T E
M P
E R
A T U
R E
O V
E R
R
ID
E
E N
T H
A L P Y
E C
O N
O M
IZ
E
R
T E
M P E
R A
T U
R E
E C
O N
O M
IZ
E
R
F A
IL
U
R E
M O
D E
P R
E S
S U
R E
/V O
L U
M E
C O
N T R
O L
REMARKS
F U
L L C
O M
M U
N
IC
A T
IO
N
SYSTEM SOFTWARE/CONTROL
APPLICATION/FUNCTION
PAGE:
RETURN AIR HUMIDITY
SUPPLY FAN STATUS
MIXED AIR LOW LIMIT
RETURN AIR DAMPER
RETURN FAN START/STOP
COOLING VALVE V-1
EXHAUST AIR DAMPER
SUPPLY FAN VSMC
OUTSIDE AIR DAMPER
RETURN FAN VSMC
S T A
T
IC
P R
E S
S U
R E
C A
R B
O N
M O
N O
X
ID
E
H U
M
ID
IT
Y
V A
C U
U M
SUPPLY FAN START/STOP
AI-1
AI-2
AI-3
AI-4
AI-6
AI-7
AI-8
AI-9
AI-10
T R
E N
D
IN
G
OUTSIDE AIR TEMPERATURE AI-11
BI-1
BI-2
BI-3
BI-4
BI-5
BI-7
BI-8
AO-1
AO-2
AO-3
AO-4
AO-5
AO-9
BO-1
BO-2
FULL COMMUNICATION
FULL COMMUNICATION
A B
B R
E V
IA
T
IO
N
RAT
RAH
RAF
MAT
CCT
DAT
DASP
DAH
SAF
OAT
RLP
RF-STS
SF-STS
TSL-1
SPS-2
SF-ALA
RF-ALA
RF-SPD
SF-SPD
OAD
RAD
EAD
CLG-V1
RF-SST
SF-SST
OUTPUTS
LOG
1. GENERAL
1.1 UNIT IS NORMALLY STARTED AND STOPPED REMOTELY AT THE ECC. H-O-A SWITCH SHALL BE KEPT IN
THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR MAINTENANCE. WHEN
THE UNIT IS "OFF", DAMPERS D-1, D-3, SD-1, SD-2 AND VALVE V-1, SHALL BE FULLY CLOSED. WHEN
THE UNIT IS "ON" SD-1 AND SD-2 SHALL BE FULLY OPEN AND D-1 SHALL BE EITHER AT MINIMUM
POSITION OR AT POSITION SELECTED BY ECONOMIZER CYCLE. DURING ALARM CONDITION WHICH
REQUIRES SUPPLY AND RETURN FAN SHUT DOWN, EAD, OAD AND VALVE V-1 SHALL GO TO CLOSE
POSITION. D-1, D-2 AND D-3 SHALL MODULATE IN ACCORDANCE WITH THE FOLLOWING SEQUENCE:
2. TEMPERATURE CONTROL
2.1 SUPPLY AIR TEMPERATURE, SENSED BY TT-1, SHALL BE MAINTAINED AT SETPOINT (58°F/14.4°C -
ADJUSTABLE) VIA DIGITAL CONTROL PANEL BY MODULATING V-1 OR D-2 AND D-3 IN SEQUENCE.
2.2 WHEN THE TEMPERATURE OF THE OUTSIDE AIR, SENSED BY TT-2, IS ABOVE 75°F [23.8°C] (ADJ), THE
DIGITAL CONTROL PANEL SHALL PREVENT THE MODULATION OF D-2 AND D-3 AND SHALL ASSUME THE
OUTSIDE AIR DAMPER POSITION TO A MINIMUM AND RETURN AIR DAMPER D-2 GO TO FULL OPEN
POSITION. THE DIGITAL CONTROL PANEL SHALL MODULATE V-1 TO MAINTAIN THE SUPPLY AIR
TEMPERATURE, SENSED BY TT-1.
2.3 WHEN THE TEMPERATURE OF THE OUTSIDE AIR, SENSED BY TT-2, IS BETWEEN 65°F [18.3°C] AND THE
SUPPLY AIR TEMPERATURE SENSED BY TT-1, DAMPER D-2 SHALL FULLY CLOSE AND D1 AND D3 SHALL
BE FULLY OPEN (MAXIMUM OUTSIDE AIR POSITION). THE DIGITAL CONTROL PANEL SHALL MODULATE
V-1 TO MAINTAIN THE SUPPLY AIR TEMPERATURE, SENSED BY TT-1.
2.4 WHEN THE TEMPERATURE OF THE OUTSIDE AIR, SENSED BY TT-2, IS BELOW THE SUPPLY AIR
TEMPERATURE, SENSED BY TT-1, DAMPERS D-1, D-2 AND D-3 SHALL MODULATE TO MAINTAIN THE
SCHEDULED SUPPLY AIR TEMPERATURE. IF D-2 IS OPEN AND D-3 IS CLOSED TO MINIMUM OUTSIDE
AIR, V-1 SHALL MODULATE OPEN TO MAINTAIN THE SUPPLY AIR TEMPERATURE, SENSED BY TT-1.
HUMIDIFICATION
RETURN AND EXHAUST SHALL BE MONITORED. ON A CALL FOR HUMIDIFICATION, HUMIDIFIER VALVE V-1
SHALL MODULATE TO MAINTAIN THE RETURN (OR EXHAUST) AIR HUMIIDITY SET PONT TO 30%
(ADJUSTABLE). PRIOR TO ACTIVATION OF V-1 THE ON/OFF CONTROL VALVE V-2 SHALL BE BE ENABALED
THROUGH ECC AND JACKET TEMPERATURE SENSED BY TSH SHALL BE WARM
ENOUGH TO PREVENT CONDENSATION. THE HIGH LIMIT HUMIDITY SENSOR, LOCATED IN THE SUPPLY AIR
DUCT 3000mm (10 FEET) AWAY FROM THE HUMIDIFIER AND GIVE AN ALARM SIGNAL TO THE EEC, IF
THE SUPPLY AIR HUMIDITY EXCEEDS 90% RH (ADJUSTABLE). THE AIRFLOW SWITCH SHALL
PROVE AIRFLOW BEFORE HUMIDITY CONTROLS ARE ACTIVATED.
3. AIR FLOW CONTROL
3.1 THE SUPPLY AIR FLOW SHALL BE CONTROLLED BY THE DIGITAL CONTROL PANEL MODULATING THE
SUPPLY FAN VARIABLE SPEED MOTOR CONTROLLER (VSMC) TO MAINTAIN 1.5" [38mm] OF DUCT
STATIC PRESSURE (FIELD ADJUSTABLE), SENSED BY SPS-1. RESET STATIC PRESSURE BASED ON
ACTUAL BUILDING LOAD BY POLLING ALL ATU
3.2 THE DIGITAL CONTROL PANEL, USING TOTAL SUPPLY AIR AND RETURN AIR FLOW SIGNALS, SHALL
RESET THE RETURN AIR FAN VSMC TO MAINTAIN A CONSTANT AIR FLOW DIFFERENCE BETWEEN THE
SUPPLY AIR AND THE RETURN AIR EQUAL TO MINIMUM OUTSIDE AIR.
4. FREEZE PROTECTION
4.1 IF THE AIR TEMPERATURE AS SENSED BY TT-3 FALLS BELOW 45°F [7°C], AN ALARM SIGNAL SHALL
INDICATE AT THE DCP AND ECC. IF THIS TEMPERATURE FALLS BELOW 40°F [4.4°C], AS SENSED BY THE
TSL-1 THE SUPPLY AND RETURN FANS SHALL SHUT DOWN AND A CRITICAL ALARM SHALL INDICATE AT
THE DIGITAL CONTROL PANEL AND ECC. TSL-1 SHALL BE HARDWIRED TO THE SUPPLY & RETURN FAN
VFD'S AND UNIT SHALL BE SHUTDOWN IN HAND,AUTO OR BYPASS MODE. TSL-1 WILL REQUIRE MANUAL
RESET AT THE DEVICE.
5. AUTOMATIC SHUTDOWN/RESTART
5.1 WHEN SMOKE IS DETECTED BY DUCT SMOKE DETECTOR, SD, THE SUPPLY AND RETURN FANS SHALL
SHUT "OFF" AND AN ALARM SIGNAL SHALL BE TRANSMITTED TO THE FIRE ALARM SYSTEM. ALL SMOKE
DAMPERS IN THE SUPPLY AND RETURN DUCTS SHALL CLOSE. FIRE ALARM CONTROL PANEL IS
LOCATED IN ELECTRICAL ROOM 1B132.
5.2 EXHAUST FANS SERVING AREA OF THE SUPPLY FAN SHALL CONTINUE TO RUN. SUPPLY AND RETURN
FANS SHALL RESTART AND SMOKE DAMPERS SHALL OPEN WHEN FIRE ALARM CIRCUIT IS RESET.
6. EMERGENCY CONSTANT SPEED OPERATION
6.1 UPON FAILURE OF THE VSMC, THE SUPPLY AND RETURN FANS SHALL BE STARTED/STOPPED
MANUALLY AT THE DIGITAL CONTROL PANEL OR THE ECC THROUGH THE BY-PASS STARTER. FANS
SHALL THEN BE OPERATED AT CONSTANT SPEED.
6.2 ALL ATU'S OF THE AHU SHALL BE AT MAX. DESIGN CFM.
(TT-4)
(HT-H1)
(TT-3)
(TT-5)
(TT-1)
(SPS-1)
(HT-H2)
(TT-2)
AFTER FILTER
PRE-FILTER
FINAL FILTER
AI-12
AI-13
AI-14
PF-1
PF-2
FF
CENTRAL PLANT (BUILDING 2)
EXISTING EMS FIBER
BACKBONE TO BUILDING 1
BACNET MSTP COMM.
22GA, 3C, STRAND
SHIELDED, PLENUM
EXHAUST FAN ON ROOF
NORTH PENTHOUSE
W/ 5 AHU'S
SOUTH PENTHOUSE
W/ 4 AHU'S
NEW FIBER
BACKBONE
FLOOR 3
FLOOR 4
FLOOR 2
FLOOR 1
ROOF / PENTHOUSE
CAT 5 ETHERNET
CABLE
ROOF
EXHAUST AIR
D-3
D-2
P R
E -F
IL
T
E R
OUTSIDE AIR
D-1
C O
IL
C
O O
L
IN
G
GLOBAL OUTSIDE AIR SENSORS.
LOCATE SENSORS OUTSIDE UNDER
SHIELD ON THE NORTH EXPOSURE
V-1
CHR
CHS
RETURN FAN
SUPPLY FAN
A F
M D
RETURN
AIR
A F
M D
SUPPLY AIR TO
TERMINAL UNIT
TT
TT TT
FTP
R E
-F
IL
T E
R
TT HT
A F
M D
HS
CS
VFD
HSVFD
FT
3 T-5
H1
SD
ONLY WHERE
REQUIRED
CURRENT
TRANSMITTER
FOR FAN
STATUS ,TYP.
PSH
SMOKE
DETECTOR
VARIABLE
FREQUENCY DRIVE,
TYP.
ZC
ZC
ZC
FT
DPS DPS
TT
SST
PSL
CS
SST
SD-2
SD
SD-1
SPS
SPD
ALA
COMM
SPD
IT
F
IN
A L F
IL
T
E R
DPS
NOTE:
FOR SYMBOLS AND ABBREVIATIONS, SEE POINT LIST AND SHEET M001 AND M002
HT
H-2
DIFFUSER
SECTION
TSL
HT
H2
SEQUENCE OF OPERATION:
3.3 USING HIGH PRESSURE SENSOR SPS-1 LOCATED AT THE SUPPLY FAN DISCHARGE, SHALL PREVENT
THE SUPPLY FAN FROM DEVELOPING OVER 3" [75mm] OF STATIC PRESSURE (FIELD ADJUSTABLE). IF
STATIC PRESSURE AT PSH-1 DOES EXCEED 3" [75mm] THE SUPPLY AIR FAN AND RETURN AIR FAN
SHALL STOP; EAD, OAD AND V-1 GO TO CLOSE POSITION AND AN ALARM IS SENT TO THE DCP AND
ECC. PSH-1 SHALL BE HARDWIRED TO THE SUPPLY FAN VSMC AND UNIT SHALL BE SHUTDOWN IN
HAND, AUTO OR BYPASS MODE. PSH-1 WILL REQUIRE MANUAL RESET AT THE DEVICE.
GENERAL NOTES
1. THE EXISTING HOSPITAL EMS (ENERGY MANAGEMENT SYSTEM) IS COMPRISED OF A
JOHNSON CONTROLS METASYS NETWORK. THERE IS AN EXISTING ADX (APPLICATION DATA)
SERVER LOCATED IN THE CENTRAL PLANT WHICH MANAGES THE CAMPUS EMS. THE
EXISTING HOSPITAL CAMPUS NETWORK INCLUDES SEVERAL WORKSTATIONS, NAE/NCE
SUPERVISORY CONTROLLERS, AND NUMEROUS PROGRAMMABLE AND APPLICATION
SPECIFIC CONTROLLERS. THIS PROJECT WILL REQUIRE NEW NAE SUPERVISORY
CONTROLLERS TO SUPPORT THE NEW PROGRAMMABLE AND APPLICATION SPECIFIC
CONTROLLERS REQUIRED TO CONTROL THE EQUIPMENT AS LISTED IN THE MECHANICAL
SCHEDULES. ALL NEW CONTROLS MUST BE SEAMLESSLY INTEGRATED INTO THE EXISTING
ADX SERVER.
2. FIVE (5) SPARE CONTROL POINTS FOR AI, AO, DI AND DO (20 IN TOTAL) SHALL BE PROVIDED
AT THE MISCELLANEOUS CONTROLS FOR FUTURE CONNECTION.
3. THE NEW AHU'S LOCATED IN THE PENTHOUSE AND THE FAN COIL UNITS THROUGH OUT THE
SCI BUILDING WILL BE SERVED FROM THE VARIABLE PRIMARY PUMPING SYSTEM RESIDED AT
THE CUP. PRESSURE TRANSMITTER, WHICH CONTROLS THE PUMP SPEED, ARE LOCATED AT
THE END OF EXISTING CHILLED WATER PIPING SERVING MAIN HOSPITAL. SINCE SCI BUILDING
IS LOCATED LESS THAN 1/2 THE DISTANCE COMPARE TO EXISTING HOSPITAL, EXISTING
CHILLED WATER PUMPS WILL HAVE ENOUGH HEAD TO SERVE THE SCI BUILDING.
KEY NOTES
MISCELLANEOUS CONTROLS INVOLVE FOLLOWING SYSTEM:
a. UPS, REFER TO ELECTRICAL DRAWINGS AND COORDINATE WITH ELECTRICAL
CONTRACTOR FOR SPECIFIC HARDWIRED POINTS.
b. MEDICAL VACUUM PUMP SYSTEM, REFER TO DETAIL 2/MH803 & PLUMBING DRAWINGS
AND COORDINATE WITH PLUMBING CONTRACTOR.
c. DOMESTIC HOT WATER HEATING SYSTEM, REFER TO DETAIL 2/MH803 & PLUMBING
DRAWINGS AND COORDINATE WITH PLUMBING CONTRACTOR.
d. WATER SOFTENER SYSTEM, REFER TO DETAIL 2/MH803 & PLUMBING DRAWINGS AND
COORDINATE WITH PLUMBING CONTRACTOR.
e. MEDICAL AIR COMPRESSOR SYSTEM, REFER TO DETAIL 2/MH803 & PLUMBING
DRAWINGS AND COORDINATE WITH PLUMBING CONTRACTOR.
2C
V-3
LPS
V-4
STEAM
HUMIDIFIER
2C
HT
10'-MIN.
STEAM HUMIDIFIER VALVE V-4
STEAM HUMIDIFIER VALVE V-3
CONTROL ARCHITECTURE 1NTSVARIABLE AIR VOLUME AIR HANDLING UNIT WITH MINIMUM OUTSIDE AIR CONTROL 2NTS
(EXISTING)
ADX SERVER
(EXISTING) NAE-2
(EXISTING)
WORKSTATION
(EXISTING)
WORKSTATION
(EXISTING) NAE-1
(EXISTING) NCE-13
NAE-##
NAE-##
NAE-##
NAE-##
26-TU-#-##
VMA1630
(TYPICAL FOR 58
CAV / VAV BOXES)
26-FCU1.#
FEC2611
(TYPICAL FOR 6
FAN COIL UNITS)
26-TU-#-##
VMA1630
(TYPICAL FOR 61
CAV / VAV BOXES)
26-AFCV#.#
VMA1630
(TYPICAL FOR 2 AIR
VALVE TRACKING PAIRS)
26-EF11
FEC1611
EXHAUST FAN
26-EF12
FEC1611
EXHAUST FAN
26-TU-#-##
VMA1630
(TYPICAL FOR 58
CAV / VAV BOXES)
26-AFCV#.#
VMA1630
(TYPICAL FOR 3 AIR
VALVE TRACKING PAIRS)
26-TU-#-##
VMA1630
(TYPICAL FOR 62
CAV / VAV BOXES)
26-AFCV#.#
VMA1630
(TYPICAL FOR 2 AIR
VALVE TRACKING PAIRS)
NAE-##
26-AHU#
FEC2621
(TYPICAL FOR 4
AIR HANDLING UNITS)
26-AHU#
FEC2622
(TYPICAL FOR 5
AIR HANDLING UNITS)
26-HX1/2
FEC2621
HEATING HOT WATER
SYSTEM
HPS, MPS, PRV
& COND. RTN. SYS.
CHEM. TREAT. SYS.
26-FCU6.1
FEC2611
FAN COIL UNIT
26-EF##
FEC1611
(TYPICAL FOR 10
EXHAUST FANS)
UPS
FEC 2611
PDU-1
(POOL DEH. UNIT)
MIS. CONTROLS
FEC 2611
R E
G
IS
T
ER
ED
PROFESS IONAL
ENG
IN
E E
R
S T
A
T E
OF CA L I FORN
I A
No. M029768
Exp. 06/30/20
M
E C H A N I C A
L
P A
U L
Q I P I NG
DO
N G
(949) 250-1500
2355 Main Street Suite 220
Irvine
Drawing Title
Approved: Project Director
Project Title
Date
Location
Reviewed
Building Number
Project Number
Drawing Number
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS:
Office of Facilities
Management o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231, OCT 1978
D
Department of Veterans Affairs
2 3 4 5 6
C
B
A
/1
/2
:4 :5
P
M C
R e v it
L o c a l F il e s \V
A S
C I_
M E ll ie
. T ra n .r v t
SEISMIC DEFICIENCY -
SCI & CLC HOSPITAL
3350 La Jolla Village Dr.
San Diego, CA 92037
EBA
MECHANICAL CONTROLS - 1
MH801
664-401
07/19/2019
S
I
T A
E
T S
L
N
E C C
N
O
CFO FILA
R
A I
T
I
CRADE H
E T
REN.: 10-31-19
NO. C-28367
I
M
TE
EMCU
AO
FE
FT
AI
AI
I
M
TE
EMCU
E n a b le
/D is a b le
O p e n /C lo s e
Zone Temp
Supply Air Flow
Heating Coil Control
End Switch Open
End Switch Closed
C o n tr o l
S e t P o in t A d ju s tm e n t
S ta tu s
A la rn
K W
P u ls e
E n d S w it c h
T e m p e ra tu re
P re s s u re
F lo w
H u m id it y
E q u ip m e n t A la rm
H ig h L im it
L o w
L im it
R u n T im e
E n a b le
/D is a b le
T e m p e ra tu re
P re s s u re
K W
K
W H
F re q u e n c y
H z
S p e e d F e e d b a c k
L o a d
A m p e ra g e
C F
M F lo w
G P
M F lo w
N O
T E
S
OUTPUTS
S ta rt /S to p
Binary Analog
INPUTS
Analog
ALARM PROCESSING
Analog Analog
APPLICATION/FUNCTION
POINTS LIST FOR CAV TERMINAL UNIT/REHEAT COIL
POINT DESCRIPTION
BMS Communication Point
Power Point
SYSTEM SOFTWARE/CONTROL
Binary Binary Binary
SYSTEM SYSTEM
E n a b le
/D is a b le
O p e n /C lo s e
Zone Temp
Supply Air Flow
Heating Coil Control
End Switch Open
End Switch Closed
C o n tr o l
S e t P o in t A d ju s tm e n t
S ta tu s
A la rn
K W
P u ls e
E n d S w it c h
T e m p e ra tu re
P re s s u re
F lo w
H u m id it y
E q u ip m e n t A la rm
H ig h L im it
L o w
L im it
R u n T im e
E n a b le
/D is a b le
T e m p e ra tu re
P re s s u re
K W
K
W H
F re q u e n c y
H z
S p e e d F e e d b a c k
L o a d
A m p e ra g e
C F
M F lo w
G P
M F lo w
N O
T E
S
OUTPUTS
S ta rt /S to p
Binary Analog
INPUTS
Analog
ALARM PROCESSING
Analog Analog
APPLICATION/FUNCTION
POINTS LIST FOR VAV TERMINAL UNIT/REHEAT COIL
POINT DESCRIPTION
BMS Communication Point
Power Point
SYSTEM SOFTWARE/CONTROL
Binary Binary Binary
SYSTEM SYSTEM
E n a b le
/D is a b le
O p e n /C lo s e
Cooling Coil Control
Heating Coil Control (4-pipe FCU Only)
Discharge Air
Return Air
Filter Loading
C o n tr o l
S e t P o in t A d ju s tm e n t
S ta tu s
A la rn
K W
P u ls e
E n d S w it c h
T e m p e ra tu re
P re s s u re
F lo w
H u m id it y
E q u ip m e n t A la rm
H ig h L im it
L o w
L im it
R u n T im e
E n a b le
/D is a b le
T e m p e ra tu re
P re s s u re
K W
K
W H
F re q u e n c y
H z
S p e e d F e e d b a c k
L o a d
A m p e ra g e
C F
M F lo w
G P
M F lo w
N O
T E
S
OUTPUTS
S ta rt /S to p
Binary Analog
INPUTS
Analog
ALARM PROCESSING
Analog Analog
APPLICATION/FUNCTION
POINTS LIST FOR FAN COIL UNIT
POINT DESCRIPTION
Communication Point
SYSTEM SOFTWARE/CONTROL
Binary Binary Binary
SYSTEM SYSTEM
Supply Fan
E n a b le
/D is a b le
O p e n /C lo s e
Zone Temp
Supply Air Valve
Supply Air Valve
Heating Coil Control
Supply Air Temp
C o n tr o l
S e t P o in t A d ju s tm e n t
S ta tu s
A la rn
K W
P u ls e
E n d S w it c h
T e m p e ra tu re
P re s s u re
F lo w
H u m id it y
E q u ip m e n t A la rm
H ig h L im it
L o w
L im it
R u n T im e
E n a b le
/D is a b le
T e m p e ra tu re
P re s s u re
K W
K
W H
F re q u e n c y
H z
S p e e d F e e d b a c k
L o a d
A m p e ra g e
C F
M F lo w
G P
M F lo w
N O
T E
S
OUTPUTS
S ta rt /S to p
Binary Analog
INPUTS
Analog
ALARM PROCESSING
Analog Analog
APPLICATION/FUNCTION
POINTS LIST FOR SA VALVE WITH REHEAT COIL
POINT DESCRIPTION
SYSTEM SOFTWARE/CONTROL
Binary Binary Binary
SYSTEM SYSTEM
E n a b le
/D is a b le
O p e n /C lo s e
Corridor-Ante Room
Ante Room - Isolation Room
Alarm Strobe
Supply Air Valve
C o n tr o l
S e t P o in t A d ju s tm e n t
S ta tu s
A la rn
K W
P u ls e
E n d S w it c h
T e m p e ra tu re
P re s s u re
F lo w
H u m id it y
E q u ip m e n t A la rm
H ig h L im it
L o w
L im it
R u n T im e
E n a b le
/D is a b le
T e m p e ra tu re
P re s s u re
K W
K
W H
F re q u e n c y
H z
S p e e d F e e d b a c k
L o a d
A m p e ra g e
C F
M F lo w
G P
M F lo w
N O
T E
S
OUTPUTS
S ta rt /S to p
Binary Analog
INPUTS
Analog
ALARM PROCESSING
Analog Analog
APPLICATION/FUNCTION
POINTS LIST FOR ISOLATION ROOM
POINT DESCRIPTION
Exhaust Fan VFD
Exhaust Air Filter
SYSTEM SOFTWARE/CONTROL
Binary Binary Binary
SYSTEM SYSTEM
Corridor-Isolation Room
D is p la y
A m p s
E n a b le
/D is a b le
O p e n /C lo s e
Exhaust Fan
C o n tr o l
S e t P o in t A d ju s tm e n t
S ta tu s
A la rn
K W
P u ls e
E n d S w it c h
T e m p e ra tu re
P re s s u re
F lo w
H u m id it y
E q u ip m e n t A la rm
H ig h L im it
L o w
L im it
R u n T im e
E n a b le
/D is a b le
T e m p e ra tu re
P re s s u re
K W
K
W H
F re q u e n c y
H z
S p e e d F e e d b a c k
L o a d
A m p e ra g e
C F
M F lo w
G P
M F lo w
N O
T E
S
OUTPUTS
S ta rt /S to p
Binary Analog
INPUTS
Analog
ALARM PROCESSING
Analog Analog
APPLICATION/FUNCTION
POINTS LIST FOR EXHAUST FAN
POINT DESCRIPTION
SYSTEM SOFTWARE/CONTROL
Binary Binary Binary
SYSTEM SYSTEM
E n a b le
/D is a b le
O p e n /C lo s e
Exhaust Fan VFD
Exhaust Air Filter
Exhaust Air Static Pressure
Exhaust Air Flow
C o n tr o l
S e t P o in t A d ju s tm e n t
S ta tu s
A la rn
K W
P u ls e
E n d S w it c h
T e m p e ra tu re
P re s s u re
F lo w
H u m id it y
E q u ip m e n t A la rm
H ig h L im it
L o w
L im it
R u n T im e
E n a b le
/D is a b le
T e m p e ra tu re
P re s s u re
K W
K
W H
F re q u e n c y
H z
S p e e d F e e d b a c k
L o a d
A m p e ra g e
C F
M F lo w
G P
M F lo w
N O
T E
S
OUTPUTS
S ta rt /S to p
Binary Analog
INPUTS
Analog
ALARM PROCESSING
Analog Analog
APPLICATION/FUNCTION
POINTS LIST FOR CRITICAL EXHAUST FAN CONTROL
POINT DESCRIPTION
SYSTEM SOFTWARE/CONTROL
Binary Binary Binary
SYSTEM SYSTEM
A m p s
E n a b le
/D is a b le
O p e n /C lo s e
HX-1 Supply Temp
Heating Water Supply Temp
C o n tr o l
S e t P o in t A d ju s tm e n t
S ta tu s
A la rn
K W
P u ls e
E n d S w it c h
T e m p e ra tu re
P re s s u re
F lo w
H u m id it y
E q u ip m e n t A la rm
H ig h L im it
L o w
L im it
R u n T im e
E n a b le
/D is a b le
T e m p e ra tu re
P re s s u re
K W
K
W H
F re q u e n c y
H z
S p e e d F e e d b a c k
L o a d
A m p e ra g e
C F
M F lo w
G P
M F lo w
N O
T E
S
OUTPUTS
S ta rt /S to p
Binary Analog
INPUTS
Analog
ALARM PROCESSING
Analog Analog
APPLICATION/FUNCTION
POINTS LIST FOR HEAT EXCHANGER CONTROL
POINT DESCRIPTION
SYSTEM SOFTWARE/CONTROL
Binary Binary Binary
SYSTEM SYSTEM
HX-2 Supply Temp
Heating Water Return Temp
Steam Valve V-1 (HX-1 1/3)
Steam Valve V-2 (HX-1 2/3)
Steam Valve V-3 (HX-2 1/3)
Steam Valve V-4 (HX-2 2/3)
Hot Water Pump HWP-1
Outside Air Temperature
Hot Water Pump HWP-2
CONTROL VALVES (N.C.).
SIZE VALVES IN 1/3 - 2/3
VALVE ARRANGEMENT
HEAT EXCHANGERS
TEMPERATURE SENSOR (TYP)
PUMP
MPS
HS
PUMP
HS
HWS
V-1
V-2
TC
LPS
V-3
V-4
TT
AMBIENT TEMPERATURE TRANSMITTER WITH SUN
SHIELD
CONTROL VALVES
(N.C.). SIZE VALVES IN
1/3 - 2/3 VALVE
ARRANGEMENT
O.A.
150°F (66°C)
(MIN.)
180°F (82°C)
(MAX.)
SEQUENCE OF OPERATION:
1. STEAM CONTROL VALVE SHALL MODULATE TO MAINTAIN THE LEAVING HOT WATER TEMPERATURE AT SET POINT. (180°F/82.2°C -
ADJUSTABLE)
2. THE LEAVING HOT WATER TEMPERATURE SHALL BE RESET INVERSELY WITH THE OUTDOOR TEMPERATURE AS SCHEDULED.
3. THE LEAD AND LAG PUMPS AND HEAT EXCHANGERS SHALL BE SEQUENTIAL BY THE OPERATOR CONTROLS AT THE PRE-DETERMINED
INTERVAL (USUALLY 7 DAYS). IN THE EVENT THE PUMP FAILS TO START WITHIN 30 SECONDS, AN ALARM SHALL BE INITIATED AND THE
SECOND PUMP SHALL START AUTOMATICALLY.
VALVE SEQUENCE: (26-HX1 OPERATIONAL)
1. THE VALVES V1 (1/3 CAPACITY) AND V2 (2/3 CAPACITY) SHALL OPERATE IN SEQUENCE.
2. AT LIGHT LOADS, V1 SHALL MODULATE OPEN IN AN EFFECT TO ACHIEVE AND MAINTAIN LEAVING HOT WATER TEMPERATURE SETPOINT.
3. AS DEMAND INCREASES, THE SMALLER VALVE V1 REACHES ITS FULL OPEN POSITION, AND THE LARGER VALVE V2 BEGINS TO MODULATE
OPEN.
VALVE SEQUENCE: (26-HX2 OPERATIONAL)
1. THE VALVES V3 (1/3 CAPACITY) AND V4 (2/3 CAPACITY) SHALL OPERATE IN SEQUENCE.
2. AT LIGHT LOADS, V3 SHALL MODULATE OPEN IN AN EFFECT TO ACHIEVE AND MAINTAIN LEAVING HOT WATER TEMPERATURE SETPOINT.
3. AS DEMAND INCREASES, THE SMALLER VALVE V3 REACHES ITS FULL OPEN POSITION, AND THE LARGER VALVE V4 BEGINS TO MODULATE
OPEN.
HWR
PC
V2-C
1-HX-1
1-HX-2
V3-C
V4-C
HWP-1
HWP-2
CS
CS
SST
SST
O.A.
140°F (60°C)
(MIN.)
180°F (82°C)
(MAX.)
TYP OSA RESET
SCHEDULE
TT
TT
V1-C
FAN
COOLING COIL
FILTER
RA
CHS
CHR
T-1
V-1
ROOM TEMPERATURE SENSOR, WALL MOUNTED
48" [1200mm] AFF.
TT
PC
HS
SEQUENCE OF OPERATION:
1. FAN COIL UNIT SHALL OPERATE ON A SCHEDULE AS SET BY THE DCC SYSTEM.
2a. FOUR PIPE FCU:
THE SYSTEM CONTROLLER, SENSING THE SUPPLY AIR TEMPERATURE, MODULATES THE CHILLED WATER CONTROL VALVE OR HOT WATER
CONTROL VALVE AS REQUIRED TO MAINTAIN ITS SETPOINT (ADJUSTABLE). THE SETPOINT CAN BE RESET FROM DIGITAL SYSTEM
CONTROLLER.
2b. TWO PIPE FCU :
THE SYSTEM CONTROLLER, SENSING THE SUPPLY AIR TEMPERATURE, MODULATES THE CHILLED WATER CONTROL VALVE AS REQUIRED TO
MAINTAIN ITS SETPOINT(ADJUSTABLE). THE SETPOINT CAN BE RESET FROM DIGITAL SYSTEM CONTROLLER.
3. THE SET POINT TEMPERATURE CAN BE RESET FROM DDC SYSTEM.
4. ALARM IF SPACE TEMPERATURE OUTSIDE OF RANGE.
5. ANALOG INPUT/OUTPUT, DIGITAL INPUT/OUTPUT SENSORS, TRANSMITTER, DETECTORS SIMILAR TO 8/MH802.
SHARED ARRANGEMENT IF FEASIBLE
SST
HEATING COIL (FOR 4-PIPE FCU)
HWS
HWR
V-2
SD
SEE NOTE 1
NOTES:
1. DUCT MOUNTED SMOKE
DETECTOR FOR AUTOMATIC
SHUT-OFF. SEE SCHEDULE FOR UNIT
WHICH REQUIRES SMOKE DETECTOR.
2. FOR FAN COIL UNIT SERVING
MDF/IDF ROOM WITH TWO UNITS SET
ONE UNIT 2 DEGREE FAHRENHEIT
HIGHER THAN THE OTHER.
1NTS
2NTSTYPICAL GENERAL EXHAUST FAN CONTROL 4NTSTYPICAL CRITICAL EXHAUST FAN CONTROL 6NTS
3NTS
5NTS
8NTS
TYPICAL AIRBORNE INFECTION ISOLATION ROOM
TYPICAL CAV TB WITH RE-HEAT COIL CONTROL DIAGRAM
7NTS
TYPICAL VENTURI SA VALVE WITH REHEAT COIL CONTROL DIAGRAM
DUAL HEAT EXCHANGER CONTROLS (HEATING SYSTEM)
FAN COIL UNIT CONTROLS TYPICAL VAV TB WITH RE-HEAT COIL CONTROL DIAGRAM
EXHAUST FAN
EXHAUST AIR
STOP/
STARTOFF/ON
1.
2.
3.
4.
GENERAL NOTES:
FACTORY INSTALLED BY BOX MANUFACTURER.
FACTORY INSTALLED BY BOX MANUFACTURER.
PROVIDE MIN. 12" CLEARANCE IN FRONT OF ALL EMCU.
FLOW SENSOR FURNISHED BY BOX MANUFACTURER.
DAMPER OPERATOR FURNISHED BY BMS CONTRACTOR.
DDC CONTROLLER FURNISHED BY BMS CONTRACTOR.
HWR
HWS
PETE'S PLUG(TYP.)
SUPPLY AIR
AI
ROOM TEMPERATURE
NO
AIR DUCT
TRANSFORMER
120V
COMMUNICATION
5. AIR TERMINAL BOX HEATING AND COOLING FUNCTIONAL
PERFORMANCE TEST SHALL INCLUDE CFM SET POINT, CFM
MEASURED, REHEAT VALVE % OPEN COMMAND, SPACE
TEMPERATURE, SPACE TEMPERATURE SET POINT, AND
TEMPERATURE LEAVING REHEAT COIL.
EXHAUST AIR
AIR FLOW
EXHAUST FAN
STATIC
PRESSURE
FAN
STATUS
STOP/
ES
MIN. 3
DIAMETERS
FT
LOOP
6. PROVIDE DISCHARGE AIR TEMPERATURE READING.
VARIABLE
SPEED
SEQUENCE OF OPERATION:
1.
2.
HANDLER, PACKAGED DEHUMIDIFICATION UNIT,
THROUGH THE DDC SYSTEM WITH THE AIR
THE EXHAUST FAN SHALL BE INTERLOCKED
CURRENT SENSOR.
FAN OPERATION SHALL BE PROVEN BY A
THE EXHAUST FAN SHALL BE AUTOMATICALLY
STARTED AND STOPPED BY THE DDC SYSTEM
WHENEVER THE 'HAND-OFF-AUTOMATIC' SWITCH
IS IN THE AUTOMATIC POSITION, AND MANUALLY
STARTED AND STOPPED BY THE HAND POSITION.
SEQUENCE OF OPERATION:
1.
2.
SEQUENCE OF OPERATION:
FT
HWR
SUPPLY AIR
ROOM TEMPERATURE
FROM BMS
HWS
120V
TRANSFORMER
COMMUNICATION LOOP
SA
FROM BMS
SET POINTS SHALL SET AS FOLLOWS:
COOLING 75°F (ADJ)
HEATING 70°F (ADJ)
DEADBAND OF 5° F BETWEEN HEATING AND COOLING
SET POINT WILL BE MAINTAINED.
UPON FALL IN SPACE TEMPERATURE BELOW SETPOINT
HEATING CONTROL VALVE WILL MODULATE TO
MAINTAIN SETPOINT ± .5°, THE ADJUSTABLE TOLERANCE
OF ± .5° HAS BEEN SELECTED TO PREVENT VALVE
HUNTING.
THE REVERSE SHALL OCCUR ON RISE IN SPACE
TEMPERATURE.
A.
B.
C.
1.
2.
3.
4.
GENERAL NOTES:
FACTORY INSTALLED BY BOX MANUFACTURER.
FACTORY INSTALLED BY BOX MANUFACTURER.
PROVIDE MIN. 12" CLEARANCE IN FRONT OF ALL EMCU.
FLOW SENSOR FURNISHED BY BOX MANUFACTURER.
DAMPER OPERATOR FURNISHED BY BMS CONTRACTOR.
DDC CONTROLLER FURNISHED BY BMS CONTRACTOR.
HWR
HWS
PETE'S PLUG(TYP.)
TCV
SUPPLY AIR
AI
ROOM TEMPERATURE
FC
NO
AO
TRANSFORMER
120V
COMMUNICATION
AO
TT
TE
AI
5. AIR TERMINAL BOX HEATING AND COOLING FUNCTIONAL
PERFORMANCE TEST SHALL INCLUDE CFM SET POINT, CFM
MEASURED, REHEAT VALVE % OPEN COMMAND, SPACE
TEMPERATURE, SPACE TEMPERATURE SET POINT, AND
TEMPERATURE LEAVING REHEAT COIL.
FT
FE
LOOP
6. PROVIDE DISCHARGE AIR TEMPERATURE READING.
SEQUENCE OF OPERATION:
AO
FROM BMS
SET POINTS SHALL SET AS FOLLOWS:
COOLING 75°F (ADJ)
HEATING 70°F (ADJ)
DEADBAND OF 5° F BETWEEN HEATING AND COOLING
SET POINT WILL BE MAINTAINED.
UPON FALL IN SPACE TEMPERATURE THE VAV DAMPER
WILL MODULATE TO MINIMUM POSITION.
UPON FURTHER DROP IN SPACE TEMPERATURE
HEATING CONTROL VALVE WILL MODULATE TO
MAINTAIN SET POINT ± .5°, THE ADJUSTABLE
TOLERANCE OF ± .5° HAS BEEN SELECTED TO PREVENT
VALVE HUNTING.
THE REVERSE SHALL OCCUR ON RISE IN SPACE
TEMPERATURE.
A.
B.
C.
D.
APPLICABLE: 26-EF1 TO 26-EF8, 26-EF11 & 26-EF12
APPLICABLE: 26-EF9 & 26-EF10
UNIT AND SUPPLY FAN SERVING THE SPACE.
CORRIDOR
ANTE
ROOM
AIR BORNE
INFECTION
ISOLATION
(AII) ROOM
TOILET ROOM
ROOF
EXHAUST
BLOWER
V1
[3 m m
HS
S/A
BED
M
IN
VSMC
3. MAINTAIN THE ATTACHED TOILET AT NEGATIVE AIR PRESSURE WITH RESPECT TO THE AII ROOM.
4. PROVIDE A DEDICATED EXHAUST SYSTEM FOR THE AII ROOMS WITHOUT MIXING IT WITH ANY OTHER
EXHAUST.
5. MISC. ALARMS:
5.1. A LOCAL ALARM WILL BE GENERATED OUTSIDE THE ISOLATION ROOM, AT THE NURSES' STATION AND
ON THE BMS ANYTIME THE MEASURED ISOLATION ROOM PRESSURE RISES ABOVE -0.01" W.G.
CONTINUOUSLY FOR 60 SECONDS.
5.2. A LOCAL ALARM WILL BE GENERATED OUTSIDE THE ISOLATION ROOM, AT THE NURSES' STATION AND
ON THE BMS ANYTIME THE MEASURED ANTE ROOM PRESSURE DROPS BELOW +0.01" W.G.
CONTINUOUSLY FOR 60 SECONDS.
SA
FROM
AHU
FROM
OTHER
AII ROOMS
LOW LEVEL
EXHAUST
VARIABLE SPEED
MOTOR CONTROLLER
DISCHARGE
NOZZLE AT
3500 FPM
AIR FLOW CONTROL
VALVE (CAV)-SUPPLY
W/ DUCT MOUNTED
REHEAT COIL
DPS
ECC
HEPA
FILTER
AIR FLOW CONTROL VALVE
(CAV) - EXHAUST
ROOM
PRESSURE
CONTROLLER
DISPLAY
CABLE
ISOLATION
ROOM
PRESSURE
MONITOR
PRESSURE
SENSOR (TYP.)
COMMUNICATION ALARM
TO NURSE STATION
STROBE LIGHT
MAIN SUPPLY
AIR DUCT
MAIN SUPPLY
DPS
ECC
THE EXHAUST FAN SHALL BE AUTOMATICALLY STARTED
AND STOPPED BY THE DDC SYSTEM WHENEVER THE
'HAND-OFF-AUTOMATIC' SWITCH IS IN THE AUTOMATIC
POSITION, AND MANUALLY STARTED AND STOPPED BY THE
HAND POSITION. FAN OPERATION SHALL BE PROVEN BY A
CURRENT SENSOR.
STATIC PRESSURE CONTROL THE SYSTEM CONTROLLER
SENSING THE EXHAUST AIR STATIC PRESSURE WILL
MODULATE THE EXHAUST FAN VFD TO OVERCOME FILTER
LOADING AS REQUIRED TO MAINTAIN ITS SETPOINT. STATIC
PRESSURE SETPOINT CAN BE RESET FROM THE SYSTEM
CONTROLLER.
SEQUENCE OF OPERATION:
SET POINTS…