Appendix I.pdf

PDF 4 MB Posted

Attached to
Fish Barrier Controls Replacement, Romeoville, IL (USACE-CHICAGO DISTRICT)
Solicitation number
W912P6-20-R-0009
Issued by

About this file

This document contains technical specifications and requirements for a federal contract solicitation to replace the pulse-generating control systems for Fish Barriers IIA and IIB located on the Chicago Sanitary and Shipping Canal in Romeoville, Illinois. The U.S. Army Corps of Engineers - Chicago District is seeking proposals to furnish and install a complete and functional pulse-generating control system for Barrier IIA by April 1, 2021, with optional work to furnish and install controls for Barrier IIB by November 1, 2021. The new control systems must allow the barriers to operate safely and effectively while maintaining minimum existing functionality and providing additional capabilities. The specifications require the control systems to consist of components such as IGBT assembly controls, HVPS controls, HVPPS controls, PMS controls, CCS controls, backup generator monitoring controls, and database controls. Proposals are due by the date specified in the solicitation document.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

32 32

2A, 2B (2200V), Demo 2A, 2B (2200V), Demo

Date &Time

Pulser 1

Pulser 2 Pulser 3

Pulser 1

Pulser 2 Pulser 3

Pulser 1

Pulser 2

Pulser 3 Pulser 4

Parasitic 1 Switch PS1 SW

PS1 & PS2 Isolation Switch ISW1

Parasitic 2 Switch PS2 SW

PS2 & PS3 Isolation Switch ISW2 Parasitic 3 Switch PS3 SW

Air Temperature (°F)

Canal Temperature (°F)

Humidity (%)

Dew Point (°F)

Ambient Canal Conductivity (µS/cm)

Temp. Corrected Canal Conductivity (µS/cm)

Ground conditions (wet, moist, dry / snow) Rain in last 24 hours (yes or no)

Imperceptible (< 2 mA)

Perceptible >= 2 mA < 32 mA

Exceeds safe value >=32 mA

Map Pt Description 500Ω 1000Ω OPEN CIRCUIT 500Ω 1000Ω OPEN CIRCUIT pt511 USACE Trailer steps 1.6 V 2.5 V 3.0 V 1.4 V 1.9 V 2.9 V pt815

34kV utility feed to 2B, static line to ground, south of ComEd substation pt21 ComEd substation fence, southwest corner 9.7 V 12.4 V 17.2 V 6.4 V 10.4 V 26.1 V

BLC

Naviagtion Lights Enclosure handle, under bridge, east of tracks 4.3 V 4.6 V 4.9 V 7.8 V 7.9 V 8.3 V pt412.1 Lewis property fence, northwest corner 15.6 V 16.1 V 18.1 V 11.8 V 12.6 V 13.3 V pt412.2 Reach from Citco to residential fence

RR3W

Touch to west rail from 10 ft away‐midpoint of

2A building 8.9 V 11.8 V 17.4 V 11.6 V 13.5 V 16.8 V

RR1W

Touch to west rail from 10 ft away‐midpoint of

2B building 5.8 V 9.1 V 22.1 V 13.6 V 16.5 V 22.3 V pt412 Citgo fence at midpoint of 2B 1.0 V 1.9 V 5.7 V 1.1 V 1.9 V 5.8 V pt112

Citgo Fence North of 2B, in line with parallering gear building 2.2 V 2.9 V 3.9 V 3.8 V 4.8 V 6.1 V pt1201 Citgo fence, midpoint of PB1 1.8 V 2.3 V 3.1 V 1.2 V 1.5 V 2.2 V

RR10W

Touch to west rail from 10 ft away midpoint of new PB 1 1.5 V 3.9 V 19.7 V 4.0 V 6.7 V 18.2 V pt1202 Citgo fence, at northern boundary of site 2.6 V 3.6 V 5.1 V 1.2 V 1.6 V 2.1 V pt409 Enbridge Utility Box 0.8 V 1.2 V 2.2 V 2.8 V 3.5 V 5.2 V

LPN

Lightning protection ground paralleling gear building, north side 0.9 V 1.7 V 6.7 V 0.3 V 0.6 V 6.9 V

LPS

Lightning protection ground paralleling gear building, south side

LBN

Lightning protection PVC pipe 2B, northeast corner

S2B Air supply nozzle, 2B northeast corner 7.7 V 13.6 V 49.6 V 5.6 V 10.5 V 62.0 V

BB

2B earth to bollard adjacent to 4th door from north, northern bollard (reading uncovered ‐ usually covered) 3.8 V 6.2 V 35.8 V 1.5 V 5.6 V 44.0 V

LBM

Lightning protection PVC pipe 2B midpoint, east side, southern ground pt419 Utility pole at entrance to Centennial park pt901.9 Light pole entrance to Centennial park pt32.1 Earth to bridge deck 8.2 V 9.2 V 9.6 V 7.6 V 9.7 V 10.8 V

MWRDS MWRD fence, south end, under bridge 3.1 V 4.6 V 8.3 V 0.0 V 0.0 V 0.0 V

NRG1 NRG fence, west of USACE fence near canal pt78

Sign, northwest post, west side of canal, 20 ft

North of Bridge

78SE Maintenance shed utility box

78S

Maintenance shed concrete to south door handle

78N Northwest Corner of shed, by the door

78NE East side of shed to painted surface pt404

Fence bolt, west side of canal, by gate, northern post 2.2 V 4.0 V 64.0 V 0.5 V 0.7 V 1.2 V

Touch Potential Chest to Left Hand (Peak‐to‐

Peak VDC)

DRY

NO

Voltage

Parasitic Switches

Operational State

Barrier 2A Pulsers

Output (VDC)

Barrier 2B Pulsers

Output (VDC)

Barrier D Pulsers

Output (VDC)

12/4/17 0:00

OFF

OFF

OFF

OFF

OFF

OFF

ON

ON

OFF

ON

ON

OFF

9/28/17 0:00

OFF

ON

Weather Data

DRY

NO

Voltage

ON

ON

OFF

ON

Date &Time

Pulser 1

Pulser 2 Pulser 3

Pulser 1

Pulser 2 Pulser 3

Pulser 1

Pulser 2

Pulser 3 Pulser 4

Parasitic 1 Switch PS1 SW

PS1 & PS2 Isolation Switch ISW1

Parasitic 2 Switch PS2 SW

PS2 & PS3 Isolation Switch ISW2 Parasitic 3 Switch PS3 SW

Air Temperature (°F)

Canal Temperature (°F)

Humidity (%)

Dew Point (°F)

Ambient Canal Conductivity (µS/cm)

Temp. Corrected Canal Conductivity (µS/cm)

Ground conditions (wet, moist, dry / snow) Rain in last 24 hours (yes or no)

Imperceptible (< 2 mA)

Perceptible >= 2 mA < 32 mA

Exceeds safe value >=32 mA

Map Pt Description pt511 USACE Trailer steps pt815

34kV utility feed to 2B, static line to ground, south of ComEd substation pt21 ComEd substation fence, southwest corner

BLC

Naviagtion Lights Enclosure handle, under bridge, east of tracks pt412.1 Lewis property fence, northwest corner pt412.2 Reach from Citco to residential fence

RR3W

Touch to west rail from 10 ft away‐midpoint of

2A building

RR1W

Touch to west rail from 10 ft away‐midpoint of

2B building pt412 Citgo fence at midpoint of 2B pt112

Citgo Fence North of 2B, in line with parallering gear building pt1201 Citgo fence, midpoint of PB1

RR10W

Touch to west rail from 10 ft away midpoint of new PB 1 pt1202 Citgo fence, at northern boundary of site pt409 Enbridge Utility Box

LPN

Lightning protection ground paralleling gear building, north side

LPS

Lightning protection ground paralleling gear building, south side

LBN

Lightning protection PVC pipe 2B, northeast corner

S2B Air supply nozzle, 2B northeast corner

BB

2B earth to bollard adjacent to 4th door from north, northern bollard (reading uncovered ‐ usually covered)

LBM

Lightning protection PVC pipe 2B midpoint, east side, southern ground pt419 Utility pole at entrance to Centennial park pt901.9 Light pole entrance to Centennial park pt32.1 Earth to bridge deck

MWRDS MWRD fence, south end, under bridge

NRG1 NRG fence, west of USACE fence near canal pt78

Sign, northwest post, west side of canal, 20 ft

North of Bridge

78SE Maintenance shed utility box

78S

Maintenance shed concrete to south door handle

78N Northwest Corner of shed, by the door

78NE East side of shed to painted surface pt404

Fence bolt, west side of canal, by gate, northern post

Touch Potential Chest to Left Hand (Peak‐to‐

Peak VDC)

Parasitic Switches

Operational State

Barrier 2A Pulsers

Output (VDC)

Barrier 2B Pulsers

Output (VDC)

Barrier D Pulsers

Output (VDC)

Weather Data

32 32

2A, 2B, Demo 2A, 2B, Demo

500Ω 1000Ω OPEN CIRCUIT 500Ω 1000Ω OPEN CIRCUIT

20.3 V 24.3 V 30.7 V 22.4 V 24.4 V 27.6 V

2.5 V 4.4 V 4.4 V 1.4 V 1.5 V 1.5 V

12.5 V 12.7 V 13.4 V 13.1 V 13.9 V 14.1 V

2.6 V 4.5 V 11.8 V 4.7 V 7.3 V 12.9 V

7.0 V 10.4 V 16.4 V

10.8 V 14.4 V 21.9 V

0.8 V 1.2 V 6.0 V 2.8 V 3.2 V 3.7 V

6.0 V 6.7 V 7.7 V 3.8 V 4.3 V 4.9 V

0.7 V 1.5 V 1.8 V 1.3 V 1.4 V 1.5 V

8.5 V 11.5 V 18.6 V 11.5 V 13.7 V 21.7 V

0.4 V 0.6 V 0.9 V 1.5 V 1.6 V 1.7 V

1.6 V 1.9 V 2.4 V 1.1 V 1.5 V 1.6 V

1.2 V 1.7 V 7.5 V 1.3 V 2.2 V 5.8 V

6.8 V 11.0 V 24.9 V 8.8 V 10.5 V 20.0 V

8.8 V 9.0 V 9.5 V 7.9 V 8.3 V 8.8 V

0.1 V 0.1 V 0.2 V 0.4 V 0.4 V 0.7 V

20.1 V 30.1 V 56.8 V 20.1 V 28.9 V 40.3 V

1.1 V 1.5 V 2.5 V 0.4 V 0.6 V 0.9 V

DRY

NO

Voltage

4/11/18 0:00

OFF

OFF

ON

ON

OFF

ON

ON

7/24/18 0:00

OFF

ON

ON

OFF

ON

OFF

DRY

NO

Voltage

ON

Pulser 2 Pulser 3

Pulser 1

Pulser 2 Pulser 3

Pulser 1

Pulser 2

Pulser 3 Pulser 4

Parasitic 1 Switch PS1 SW

PS1 & PS2 Isolation Switch ISW1

Parasitic 2 Switch PS2 SW

PS2 & PS3 Isolation Switch ISW2 Parasitic 3 Switch PS3 SW

Air Temperature (°F)

Canal Temperature (°F)

Humidity (%)

Dew Point (°F)

Ambient Canal Conductivity (µS/cm)

Temp. Corrected Canal Conductivity (µS/cm)

Ground conditions (wet, moist, dry / snow) Rain in last 24 hours (yes or no)

Imperceptible (< 2 mA)

Perceptible >= 2 mA < 32 mA

Exceeds safe value >=32 mA

Map Pt Description pt511 USACE Trailer steps pt815

34kV utility feed to 2B, static line to ground, south of ComEd substation pt21 ComEd substation fence, southwest corner

BLC

Naviagtion Lights Enclosure handle, under bridge, east of tracks pt412.1 Lewis property fence, northwest corner pt412.2 Reach from Citco to residential fence

RR3W

Touch to west rail from 10 ft away‐midpoint of

2A building

RR1W

Touch to west rail from 10 ft away‐midpoint of

2B building pt412 Citgo fence at midpoint of 2B pt112

Citgo Fence North of 2B, in line with parallering gear building pt1201 Citgo fence, midpoint of PB1

RR10W

Touch to west rail from 10 ft away midpoint of new PB 1 pt1202 Citgo fence, at northern boundary of site pt409 Enbridge Utility Box

LPN

Lightning protection ground paralleling gear building, north side

LPS

Lightning protection ground paralleling gear building, south side

LBN

Lightning protection PVC pipe 2B, northeast corner

S2B Air supply nozzle, 2B northeast corner

BB

2B earth to bollard adjacent to 4th door from north, northern bollard (reading uncovered ‐ usually covered)

LBM

Lightning protection PVC pipe 2B midpoint, east side, southern ground pt419 Utility pole at entrance to Centennial park pt901.9 Light pole entrance to Centennial park pt32.1 Earth to bridge deck

MWRDS MWRD fence, south end, under bridge

NRG1 NRG fence, west of USACE fence near canal pt78

Sign, northwest post, west side of canal, 20 ft

North of Bridge

78SE Maintenance shed utility box

78S

Maintenance shed concrete to south door handle

78N Northwest Corner of shed, by the door

78NE East side of shed to painted surface pt404

Fence bolt, west side of canal, by gate, northern post

Touch Potential Chest to Left Hand (Peak‐to‐

Peak VDC)

Parasitic Switches

Operational State

Barrier 2A Pulsers

Output (VDC)

Barrier 2B Pulsers

Output (VDC)

Barrier D Pulsers

Output (VDC)

Weather Data

32 32

2A, 2B, Demo 2A + 2B (1600V), Demo Off

500Ω 1000Ω OPEN CIRCUIT 500Ω 1000Ω OPEN CIRCUIT

14.1 V 15.7 V 17.6 V 10.8 V 12.8 V 15.9 V

2.0 V 2.1 V 2.1 V 0.7 V 0.7 V 0.7 V

12.1 V 12.8 V 13.8 V 9.5 V 10.3 V 11.0 V

5.7 V 6.7 V 9.8 V 3.0 V 4.2 V 7.8 V

8.1 V 12.0 V 16.5 V 5.0 V 9.0 V 13.9 V

11.8 V 15.1 V 22.8 V 8.0 V 13.9 V 19.3 V

2.3 V 3.0 V 4.1 V 1.3 V 1.7 V 3.0 V

3.7 V 4.1 V 4.5 V 3.1 V 3.7 V 4.8 V

0.4 V 0.5 V 0.6 V 0.9 V 1.0 V 1.0 V

9.1 V 12.1 V 17.7 V 6.7 V 10.0 V 15.1 V

1.5 V 1.7 V 1.8 V 0.6 V 0.7 V 0.7 V

8.0 V 9.3 V 10.2 V 5.1 V 5.8 V 13.6 V

0.9 V 1.6 V 5.6 V 0.5 V 1.0 V 6.3 V

9.6 V 12.8 V 18.6 V 6.3 V 10.0 V 19.1 V

7.6 V 8.3 V 8.6 V 4.4 V 5.0 V 5.4 V

0.2 V 0.2 V 0.2 V 0.0 V 0.0 V 0.1 V

24.1 V 31.7 V 46.3 V 7.5 V 11.5 V 19.4 V

0.4 V 0.6 V 0.8 V 0.0 V 0.1 V 1.1 V

MOIST

YES

Voltage

OFF

OFF

ON

ON

OFF

ON

ON

12/20/18 0:00

OFF

OFF

OFF

OFF

10/9/18 0:00

OFF

OFF

MOIST

NO

Voltage

ON

ON

OFF

ON

ON

Pulser 2 Pulser 3

Pulser 1

Pulser 2 Pulser 3

Pulser 1

Pulser 2

Pulser 3 Pulser 4

Parasitic 1 Switch PS1 SW

PS1 & PS2 Isolation Switch ISW1

Parasitic 2 Switch PS2 SW

PS2 & PS3 Isolation Switch ISW2 Parasitic 3 Switch PS3 SW

Air Temperature (°F)

Canal Temperature (°F)

Humidity (%)

Dew Point (°F)

Ambient Canal Conductivity (µS/cm)

Temp. Corrected Canal Conductivity (µS/cm)

Ground conditions (wet, moist, dry / snow) Rain in last 24 hours (yes or no)

Imperceptible (< 2 mA)

Perceptible >= 2 mA < 32 mA

Exceeds safe value >=32 mA

Map Pt Description pt511 USACE Trailer steps pt815

34kV utility feed to 2B, static line to ground, south of ComEd substation pt21 ComEd substation fence, southwest corner

BLC

Naviagtion Lights Enclosure handle, under bridge, east of tracks pt412.1 Lewis property fence, northwest corner pt412.2 Reach from Citco to residential fence

RR3W

Touch to west rail from 10 ft away‐midpoint of

2A building

RR1W

Touch to west rail from 10 ft away‐midpoint of

2B building pt412 Citgo fence at midpoint of 2B pt112

Citgo Fence North of 2B, in line with parallering gear building pt1201 Citgo fence, midpoint of PB1

RR10W

Touch to west rail from 10 ft away midpoint of new PB 1 pt1202 Citgo fence, at northern boundary of site pt409 Enbridge Utility Box

LPN

Lightning protection ground paralleling gear building, north side

LPS

Lightning protection ground paralleling gear building, south side

LBN

Lightning protection PVC pipe 2B, northeast corner

S2B Air supply nozzle, 2B northeast corner

BB

2B earth to bollard adjacent to 4th door from north, northern bollard (reading uncovered ‐ usually covered)

LBM

Lightning protection PVC pipe 2B midpoint, east side, southern ground pt419 Utility pole at entrance to Centennial park pt901.9 Light pole entrance to Centennial park pt32.1 Earth to bridge deck

MWRDS MWRD fence, south end, under bridge

NRG1 NRG fence, west of USACE fence near canal pt78

Sign, northwest post, west side of canal, 20 ft

North of Bridge

78SE Maintenance shed utility box

78S

Maintenance shed concrete to south door handle

78N Northwest Corner of shed, by the door

78NE East side of shed to painted surface pt404

Fence bolt, west side of canal, by gate, northern post

Touch Potential Chest to Left Hand (Peak‐to‐

Peak VDC)

Parasitic Switches

Operational State

Barrier 2A Pulsers

Output (VDC)

Barrier 2B Pulsers

Output (VDC)

Barrier D Pulsers

Output (VDC)

Weather Data

32 32

2A + 2B (off), Demo 2A (off), 2B, Demo

500Ω 1000Ω OPEN CIRCUIT 500Ω 1000Ω OPEN CIRCUIT

0.3 V 0.4 V 0.4 V 16.4 V 18.9 V 23.7 V

0.2 V 0.2 V 0.2 V 2.0 V 2.0 V 2.1 V

0.3 V 0.4 V 1.0 V 0.6 V 0.8 V 1.1 V

0.5 V 0.7 V 0.9 V 7.3 V 9.1 V 9.5 V

7.2 V 7.7 V 8.7 V 5.9 V 7.0 V 10.6 V

6.0 V 9.0 V 15.9 V 8.1 V 11.6 V 19.7 V

0.2 V 0.3 V 0.5 V 1.7 V 2.1 V 3.0 V

0.3 V 0.5 V 0.7 V 4.2 V 5.2 V 6.9 V

0.3 V 0.3 V 0.4 V 0.8 V 0.9 V 1.1 V

4.4 V 7.1 V 15.1 V 4.0 V 6.0 V 11.3 V

2.6 V 3.0 V 3.6 V 1.5 V 1.9 V 2.6 V

1.3 V 1.4 V 2.3 V 19.0 V 19.7 V 22.1 V

0.0 V 0.0 V 0.4 V 1.3 V 2.4 V 9.9 V

0.0 V 0.0 V 0.1 V 6.5 V 7.4 V 12.2 V

0.5 V 0.7 V 1.3 V 5.7 V 6.0 V 7.1 V

0.1 V 0.1 V 0.1 V 0.1 V 0.2 V 0.3 V

0.5 V 0.6 V 2.1 V 5.6 V 7.6 V 14.3 V

0.0 V 0.1 V 2.3 V 1.8 V 2.6 V 4.6 V

ON

ON

OFF

ON

ON

4/8/19 0:00

OFF

OFF

OFF

OFF

2/25/19 0:00

OFF

OFF

OFF

OFF

OFF

OFF

ON

ON

OFF

ON

ON

‐2

DRY

NO

Voltage

MOIST

YES

Voltage

Pulser 2 Pulser 3

Pulser 1

Pulser 2 Pulser 3

Pulser 1

Pulser 2

Pulser 3 Pulser 4

Parasitic 1 Switch PS1 SW

PS1 & PS2 Isolation Switch ISW1

Parasitic 2 Switch PS2 SW

PS2 & PS3 Isolation Switch ISW2 Parasitic 3 Switch PS3 SW

Air Temperature (°F)

Canal Temperature (°F)

Humidity (%)

Dew Point (°F)

Ambient Canal Conductivity (µS/cm)

Temp. Corrected Canal Conductivity (µS/cm)

Ground conditions (wet, moist, dry / snow) Rain in last 24 hours (yes or no)

Imperceptible (< 2 mA)

Perceptible >= 2 mA < 32 mA

Exceeds safe value >=32 mA

Map Pt Description pt511 USACE Trailer steps pt815

34kV utility feed to 2B, static line to ground, south of ComEd substation pt21 ComEd substation fence, southwest corner

BLC

Naviagtion Lights Enclosure handle, under bridge, east of tracks pt412.1 Lewis property fence, northwest corner pt412.2 Reach from Citco to residential fence

RR3W

Touch to west rail from 10 ft away‐midpoint of

2A building

RR1W

Touch to west rail from 10 ft away‐midpoint of

2B building pt412 Citgo fence at midpoint of 2B pt112

Citgo Fence North of 2B, in line with parallering gear building pt1201 Citgo fence, midpoint of PB1

RR10W

Touch to west rail from 10 ft away midpoint of new PB 1 pt1202 Citgo fence, at northern boundary of site pt409 Enbridge Utility Box

LPN

Lightning protection ground paralleling gear building, north side

LPS

Lightning protection ground paralleling gear building, south side

LBN

Lightning protection PVC pipe 2B, northeast corner

S2B Air supply nozzle, 2B northeast corner

BB

2B earth to bollard adjacent to 4th door from north, northern bollard (reading uncovered ‐ usually covered)

LBM

Lightning protection PVC pipe 2B midpoint, east side, southern ground pt419 Utility pole at entrance to Centennial park pt901.9 Light pole entrance to Centennial park pt32.1 Earth to bridge deck

MWRDS MWRD fence, south end, under bridge

NRG1 NRG fence, west of USACE fence near canal pt78

Sign, northwest post, west side of canal, 20 ft

North of Bridge

78SE Maintenance shed utility box

78S

Maintenance shed concrete to south door handle

78N Northwest Corner of shed, by the door

78NE East side of shed to painted surface pt404

Fence bolt, west side of canal, by gate, northern post

Touch Potential Chest to Left Hand (Peak‐to‐

Peak VDC)

Parasitic Switches

Operational State

Barrier 2A Pulsers

Output (VDC)

Barrier 2B Pulsers

Output (VDC)

Barrier D Pulsers

Output (VDC)

Weather Data

2A (off), 2B (1700V), Demo

500Ω 1000Ω OPEN CIRCUIT

3.3 V 4.3 V 5.7 V

0.5 V 0.5 V 0.5 V

0.8 V 1.0 V 1.3 V

5.9 V 8.0 V 9.0 V

4.0 V 4.8 V 13.2 V

1.6 V 1.9 V 3.2 V

5.4 V 7.4 V 10.1 V

1.6 V 1.9 V 2.3 V

2.0 V 4.0 V 10.0 V

2.4 V 2.8 V 3.4 V

8.0 V 9.0 V 10.8 V

0.6 V 1.3 V 17.0 V

5.4 V 5.8 V 7.4 V

0.1 V 0.2 V 0.4 V

2.3 V 2.6 V 8.4 V

1.5 V 3.2 V 5.7 V

DRY

NO

Voltage

2/20/20 0:00

OFF

OFF

OFF

OFF

ON

ON

OFF

ON

ON