CSSC Dispersal Barrier 1, Project B - Building W912P6-14-B-0011
AMD0002
TABLE OF CONTENTS
DIVISION 00 PROCUREMENT & CONTRACTING REQUIREMENTS
00010 SOLICITATION, OFFER, AND AWARD, SF 1442, BIDDING SCHEDULE
00100 INSTRUCTIONS, CONDITIONS, AND NOTICES TO BIDDERS
00600 REPRESENTATIONS, CERTIFICATIONS, AND OTHER STATEMENTS OF BIDDERS
00700 CONTRACT CLAUSES
00800 SPECIAL CONTRACT REQUIREMENTS
WAGE RATES
DIVISION 00 – Level 2 – AVAILABLE INFORMATION
00 31 32.13 03 SUBSURFACE DRILLING AND SAMPLING INFORMATION
DIVISION 01 - GENERAL REQUIREMENTS
01 10 00 GENERAL PROVISIONS
01 22 00 MEASUREMENT AND PAYMENT
01 32 01 PROJECT SCHEDULE
01 33 00 SUBMITTAL PROCEDURES
01 35 26 GOVERNMENTAL SAFETY REQUIREMENTS
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.00 QUALITY CONTROL
01 45 00.10 QUALITY CONTROL SYSTEM (QCS)
01 52 02 TEMPORARY CONSTRUCTION FACILITIES
01 56 26.03 TEMPORARY CHAIN-LINK FENCE AND GATE
01 57 20.01 ENVIRONMENTAL PROTECTION FOR ILLINOIS
01 58 00 PROJECT SIGN AND SAFETY SIGN
01 78 00 CLOSEOUT SUBMITTALS
01 78 23 OPERATION AND MAINTENANCE DATA
DIVISION 03 - CONCRETE
03 11 13.00 10 STRUCTURAL CAST-IN-PLACE CONCRETE FORMING
03 15 00.00 10 CONCRETE ACCESSORIES
03 20 00.00 10 CONCRETE REINFORCING
03 30 00.00 10 CAST-IN-PLACE CONCRETE
03 35 00.00 10 CONCRETE FINISHING
03 45 33 PRECAST PRESTRESSED STRUCTURAL CONCRETE
DIVISION 04 - MASONRY
04 20 00 MASONRY
04 21 13.13 NONBEARING MASONRY VENEER/STEEL STUD WALLS
DIVISION 05 - METALS
05 12 00 STRUCTURAL STEEL
05 40 00 COLD-FORMED METAL FRAMING
05 50 13 MISCELLANEOUS METAL FABRICATIONS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 00 ROUGH CARPENTRY
06 73 01 FIBERGLASS REINFORCED PLASTIC (FRP) GRATING
06 82 14 FIBERGLASS REINFORCED PLASTIC (FRP) PIPE AND TUBE RAILINGS
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 22 00 ROOF AND DECK INSULATION
07 54 19 POLYVINYL-CHLORIDE ROOFING
07 60 00 FLASHING AND SHEET METAL
07 84 00 FIRESTOPPING
07 92 00 JOINT SEALANTS
AMD0002
DIVISION 08 - OPENINGS
08 11 13 STEEL DOORS AND FRAMES
08 33 23 OVERHEAD COILING DOORS
08 56 53 BLAST RESISTANT TEMPERED GLASS WINDOWS
08 71 00 DOOR HARDWARE
08 91 00 METAL WALL LOUVERS
DIVISION 09 - FINISHES
09 06 90 COLOR SCHEDULE
09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD
09 29 00 GYPSUM BOARD
09 67 23.13 STANDARD RESINOUS FLOORING
09 69 13 RIGID GRID ACCESS FLOORING
09 90 00 PAINTS AND COATINGS
DIVISION 10 - SPECIALTIES
10 14 00.20 INTERIOR SIGNAGE
10 21 13 TOILET COMPARTMENTS
10 28 13 TOILET ACCESSORIES
10 44 16 FIRE EXTINGUISHERS
DIVISION 21 - FIRE SUPPRESSION
21 22 00.00 CLEAN AGENT FIRE EXTINGUISHING SYSTEMS
DIVISION 22 - PLUMBING
22 00 00 PLUMBING, GENERAL PURPOSE
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING
23 00 00 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS
23 03 00 BASIC MECHANICAL MATERIALS AND METHODS
23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 08 00 COMMISSIONING OF HVAC SYSTEMS
23 23 00 REFRIGERANT PIPING
23 31 13 METAL DUCTS
23 64 10 WATER CHILLERS, VAPOR COMPRESSION TYPE
23 64 26 CHILLED, CHILLED-HOT, AND CONDENSER WATER PIPING SYSTEMS
23 81 23.00 20 COMPUTER ROOM AIR CONDITIONING UNITS
23 81 47 WATER-LOOP AND GROUND-LOOP HEAT PUMP SYSTEMS
23 82 02 UNITARY HEATING AND COOLING EQUIPMENT
23 82 46 ELECTRIC UNIT HEATERS
DIVISION 26 - ELECTRICAL
26 08 00 APPARATUS INSPECTION AND TESTING
26 12 19.10 THREE-PHASE PAD-MOUNTED TRANSFORMERS
26 20 00 INTERIOR DISTRIBUTION SYSTEM
26 23 00 SWITCHBOARDS AND SWITCHGEAR
26 29 23 VARIABLE FREQUENCY DRIVE SYSTEMS UNDER 600 VOLTS
26 32 33.00 10 UNINTERRUPTIBLE POWER SUPPLY (UPS) SYSTEM ABOVE 15 KVA
CAPACITY
26 41 00 LIGHTNING PROTECTION SYSTEM
26 51 00 INTERIOR LIGHTING
DIVISION 27 - COMMUNICATIONS
27 05 14.00 CABLE TELEVISION PREMISES DISTRIBUTION SYSTEM
27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 31 64.00 10 FIRE DETECTION AND ALARM SYSTEM, ADDRESSABLE
DIVISION 31 - EARTHWORK
31 60 00 FOUNDATION PREPARATION
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 11 23 AGGREGATE AND/OR GRADED-CRUSHED AGGREGATE BASE COURSE
32 12 10 BITUMINOUS TACK AND PRIME COATS
32 12 16 HOT-MIX ASPHALT (HMA) FOR ROADS
32 16 13 CONCRETE SIDEWALKS AND CURBS AND GUTTERS
DIVISION 33 - UTILITIES
33 20 00 WATER WELLS
33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION
DIVISION 43 - PROCESS GAS AND LIQUID HANDLING, PURIFICATION, AND STORAGE
EQUIPMENT
43 15 00 AIR COMPRESSOR
-- End of Project Table of Contents --
CSSC Dispersal Barrier 1, Project B - Building W912P6-B-14-0011
SECTION TABLE OF CONTENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
SECTION 00 31 32.13 03
SUBSURFACE DRILLING AND SAMPLING INFORMATION
PART 1 GENERAL
1.1 SUBSURFACE CONDITIONS
1.2 SITE SPECIFIC DATA
PART 2 PRODUCTS (NOT USED)
PART 3 EXECUTION (NOT USED)
-- End of Section Table of Contents --
DOCUMENT 00 31 32.13 03 - Page 1
SECTION 00 31 32.13 03
SUBSURFACE DRILLING AND SAMPLING INFORMATION
PART 1 GENERAL
1.1 SUBSURFACE CONDITIONS
Subsurface exploratory borings have been obtained by the Government to determine the general character of the subsurface materials within the project area. Four borings were drilled in 2000 on the east side of the canal near the Demonstration Barrier while one core was drilled on the west side of the canal across from Barrier IIB. Locations of the borings are shown on the Drawings, and the logs of those borings that fall within the area of this contract are included for the convenience of the Contractor in Attachment A. In addition, three wells were drilled on the west side of the canal (one near Barrier IIA and two near Barrier IIB). Geophysical logs of these three wells are also included for the convenience of the Contractor. Video logs of the wells are also available upon request from the contractor. The Government assumes no responsibility for any interpretation or deductions made by the Contractor from the logs and data. While the borings and geophysical data are generally representative of subsurface conditions at their respective locations and for their respective vertical reaches, localized variations of characteristics of the subsurface materials of this region should be anticipated. Groundwater elevations, shown on the boring logs and geophysical logs, are those encountered at the time when the logs were taken and will fluctuate due to factors such as rainfall, lake, river and/or canal stages.
1.2 SITE SPECIFIC DATA
Boring logs and geophysical logs are provided at the end of this section.
PART 2 PRODUCTS (NOT USED)
PART 3 EXECUTION (NOT USED)
-- End of Section --
DOCUMENT 00 31 32.13 03 - Page 2
Attachment A
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
00 31 32.13 03_Attachment A
DRILLING LOG
DIVISION
1. PROJECT
2. LOCATION (Coordinates or Station)
3. DRILLING AGENCY
4. HOLE NO. (As shown on drawing title and �le number)
5. NAME OF DRILLER
6. DIRECTION OF HOLE
VERTICAL INCLINED DEG. FROM VERTICAL
7. THICKNESS OF OVERBURDEN
8. DEPTH DRILLED INTO ROCK
9. TOTAL DEPTH OF HOLE
INSTALLATION SHEET
OF 11 SHEETS
10. SIZE AND TYPE OF BIT
11. DATUM FOR ELEVATION SHOWN (TBM or MSL)
12. MANUFACTURER’S DESIGNATION OF DRILL
13. TOTAL NO. OF OVERBURDEN
SAMPLES TAKEN
DISTURBED UNDISTURBED
14. TOTAL NUMBER OF CORE BOXES
15. ELEVATION OF GROUNDWATER
16. DATE HOLE STARTED COMPLETED
17. ELEVATION TOP OF HOLE
18. TOTAL CORE RECOVERY FOR BORING %
19. SIGNATURE OF INSPECTOR
ELEVATION
a
DEPTH LEGEND
b c
CLASSIFICATION OF MATERIALS
(Description) d
% CORE
RECOVERY
e
BOX OR
SAMPLE
NO.
f
REMARKS
(Drilling time, water loss, depth of weathering, etc., if signi�cant) g
LRD
FISH BARRIER
USACE - SAM
B-5-10 x
199.4 ft.
201.4 ft.
Chicago District
10-SEP-2010 15-SEP-2010
No Coring from 0-6.4’ Set PVC casing @ 6.4’ and began coring
DOLOMITE - Pervasive small vugs, highly fractured with brown clay in�lling
Drilling time: 30 minutes No water loss, smooth drilling5.0/5.0
100%
RQD: 1.9/5.0 = 38%
@ 12.6’ less oxidized and fractured
lt. grey-bu� mottled color slightly larger vugs
11.4-21.4
10.0/10.0
100%
Started drilling: 8.55 am
Stopped drilling: 9:10 am
- smooth drilling no chatter
-water loss 0-10%
RQD: 7.2/10.0 = 72%
Eddie Woods
2 ft.
NQ, Diamond embedded rotary n/a n/a
NAVD 88
585 ft.
578.6 ft.
1812259 N, 1058806 E (Illinois State Plane East NAD 83)
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
1. PROJECT
2. LOCATION (Coordinates or Station)
3. DRILLING AGENCY
4. HOLE NO. (As shown on drawing title and �le number)
5. NAME OF DRILLER
6. DIRECTION OF HOLE
VERTICAL INCLINED DEG. FROM VERTICAL
7. THICKNESS OF OVERBURDEN
8. DEPTH DRILLED INTO ROCK
9. TOTAL DEPTH OF HOLE
INSTALLATION SHEET
OF 11 SHEETS
10. SIZE AND TYPE OF BIT
11. DATUM FOR ELEVATION SHOWN (TBM or MSL)
12. MANUFACTURER’S DESIGNATION OF DRILL
13. TOTAL NO. OF OVERBURDEN
SAMPLES TAKEN
DISTURBED UNDISTURBED
14. TOTAL NUMBER OF CORE BOXES
15. ELEVATION OF GROUNDWATER
16. DATE HOLE STARTED COMPLETED
17. ELEVATION TOP OF HOLE
18. TOTAL CORE RECOVERY FOR BORING %
19. SIGNATURE OF INSPECTOR
ELEVATION
a
DEPTH LEGEND
b c
CLASSIFICATION OF MATERIALS
(Description) d
% CORE
RECOVERY
e
BOX OR
SAMPLE
NO.
f
REMARKS
(Drilling time, water loss, depth of weathering, etc., if signi�cant) g
LRD
USACE - SAM
x
201.4 ft.
Chicago District
10-SEP-2010 15-SEP-2010
sub-vertical fracture 20.0-20.7’
@ 21.7’ less vuggy, loses bu� color
lt. gray w/ some stylolites
21.4- 24.3
2.9/2.9
100%
Started drilling: 9:30am Stopped drilling:
-equipment problems, stuck core barrel @ 23.6’ 9:48am
RQD: 53%
lt. gray clay layer 23.6-24.0’ large chert nodule @ 25.0’ 24.3- 31.4
6.7/7.1
94%
Started drilling: 10:00am @ 24.3’
Ended run : 10:25am
- some drill chatter @ start some water loss ~10% water started clear and changed to milky white
Good RQD: 94% massive w/ some small vugs small vugs large chert nodule @ 33.7’
31.4- 41.4
10.0/ 10.0
100% clay �lled fracture @ 36.3’
Started run: 10:45am Ended run: 11:00am
- smooth drilling water return looks darker gray or black
RQD: 74%
FISH BARRIER
B-5-10
199.4 ft.
2 ft.
NQ, Diamond embedded rotary n/a n/a
NAVD 88
585 ft.
578.6 ft.
1812259 N, 1058806 E (Illinois State Plane East NAD 83)
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
1. PROJECT
2. LOCATION (Coordinates or Station)
3. DRILLING AGENCY
4. HOLE NO. (As shown on drawing title and �le number)
5. NAME OF DRILLER
6. DIRECTION OF HOLE
VERTICAL INCLINED DEG. FROM VERTICAL
7. THICKNESS OF OVERBURDEN
8. DEPTH DRILLED INTO ROCK
9. TOTAL DEPTH OF HOLE
INSTALLATION SHEET
OF 11 SHEETS
10. SIZE AND TYPE OF BIT
11. DATUM FOR ELEVATION SHOWN (TBM or MSL)
12. MANUFACTURER’S DESIGNATION OF DRILL
13. TOTAL NO. OF OVERBURDEN
SAMPLES TAKEN
DISTURBED UNDISTURBED
14. TOTAL NUMBER OF CORE BOXES
15. ELEVATION OF GROUNDWATER
16. DATE HOLE STARTED COMPLETED
17. ELEVATION TOP OF HOLE
18. TOTAL CORE RECOVERY FOR BORING %
19. SIGNATURE OF INSPECTOR
ELEVATION
a
DEPTH LEGEND
b c
CLASSIFICATION OF MATERIALS
(Description) d
% CORE
RECOVERY
e
BOX OR
SAMPLE
NO.
f
REMARKS
(Drilling time, water loss, depth of weathering, etc., if signi�cant) g
LRD
USACE - SAM
x
201.4 ft.
Chicago District
10-SEP-2010 15-SEP-2010
Eddie Woods
39.2-41.4’ sub vertical fractures
Joint at 42.4’, brownished oxidized color, very little clay �lling, some MnOx on fracture surface 42.4-49.6’ massive lt. gray dolomite, some small vugs
41.4-51.4
10.0/ 10.0
100%
Started run: 11:15 am Ended run: 11:36 am
- smooth drillling no chatter water loss = 0-10%
Break for lunch @ 12:10 pm
RQD = 2.2/10.0 = 22%
@ 54.1’ abundant green shale partings
51.4-61.4
10.0/ 10.0
100%
Started run: 1:10 pm Ended run: 1:35 pm
Intermittent loss of circulation between 52-55’
Some chattering at ~ 55’
RQD: 94% (good clean rock)
FISH BARRIER
B-5-10
199.4 ft.
2 ft.
NQ, Diamond embedded rotary n/a n/a
NAVD 88
585 ft.
578.6 ft.
1812259 N, 1058806 E (Illinois State Plane East NAD 83)
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
1. PROJECT
2. LOCATION (Coordinates or Station)
3. DRILLING AGENCY
4. HOLE NO. (As shown on drawing title and �le number)
5. NAME OF DRILLER
6. DIRECTION OF HOLE
VERTICAL INCLINED DEG. FROM VERTICAL
7. THICKNESS OF OVERBURDEN
8. DEPTH DRILLED INTO ROCK
9. TOTAL DEPTH OF HOLE
INSTALLATION SHEET
OF 11 SHEETS
10. SIZE AND TYPE OF BIT
11. DATUM FOR ELEVATION SHOWN (TBM or MSL)
12. MANUFACTURER’S DESIGNATION OF DRILL
13. TOTAL NO. OF OVERBURDEN
SAMPLES TAKEN
DISTURBED UNDISTURBED
14. TOTAL NUMBER OF CORE BOXES
15. ELEVATION OF GROUNDWATER
16. DATE HOLE STARTED COMPLETED
17. ELEVATION TOP OF HOLE
18. TOTAL CORE RECOVERY FOR BORING %
19. SIGNATURE OF INSPECTOR
ELEVATION
a
DEPTH LEGEND
b c
CLASSIFICATION OF MATERIALS
(Description) d
% CORE
RECOVERY
e
BOX OR
SAMPLE
NO.
f
REMARKS
(Drilling time, water loss, depth of weathering, etc., if signi�cant) g
LRD
USACE - SAM
x
201.4 ft.
Chicago District
10-SEP-2010 15-SEP-2010
Eddie Woods
63.4-66.5 DOLOMITIC MUDSTONE
greenish-gray color, soft
61.4- 71.4
50%
Started run: 14:00 lost circulation/stuck core barrel @ 63.4’ pulled up after 2’ of drilling lost water ~65-66’ ~80% Rough drilling, rig shaking
Ended run @ 15:10 Core stuck @ 69.6’
Pulled rods to recover core Recovery 50%
RQD: 0%
Clay �lled fracture @ 66.1’
Bad recovery Highly fractured dolomite gravel
Likely fractured due to drilling?
Ended day at 4:10 pm 9/11/2010
71.4- 81.4
10.0/ 10.0
100%
Not onsite while this run was drilled
Drilled Monday 9/13/2010 between 8-9 am
RQD: 51%
DOLOMITE:
clean light gray, some minor vugs
Numerous fractures 71.4-72.4’
Fractured 75.9-76.4’
FISH BARRIER
B-5-10
199.4 ft.
2 ft.
NQ, Diamond embedded rotary n/a n/a
NAVD 88
585 ft.
578.6 ft.
1812259 N, 1058806 E (Illinois State Plane East NAD 83)
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
1. PROJECT
2. LOCATION (Coordinates or Station)
3. DRILLING AGENCY
4. HOLE NO. (As shown on drawing title and �le number)
5. NAME OF DRILLER
6. DIRECTION OF HOLE
VERTICAL INCLINED DEG. FROM VERTICAL
7. THICKNESS OF OVERBURDEN
8. DEPTH DRILLED INTO ROCK
9. TOTAL DEPTH OF HOLE
INSTALLATION SHEET
OF 11 SHEETS
10. SIZE AND TYPE OF BIT
11. DATUM FOR ELEVATION SHOWN (TBM or MSL)
12. MANUFACTURER’S DESIGNATION OF DRILL
13. TOTAL NO. OF OVERBURDEN
SAMPLES TAKEN
DISTURBED UNDISTURBED
14. TOTAL NUMBER OF CORE BOXES
15. ELEVATION OF GROUNDWATER
16. DATE HOLE STARTED COMPLETED
17. ELEVATION TOP OF HOLE
18. TOTAL CORE RECOVERY FOR BORING %
19. SIGNATURE OF INSPECTOR
ELEVATION
a
DEPTH LEGEND
b c
CLASSIFICATION OF MATERIALS
(Description) d
% CORE
RECOVERY
e
BOX OR
SAMPLE
NO.
f
REMARKS
(Drilling time, water loss, depth of weathering, etc., if signi�cant) g
LRD
USACE - SAM
x
201.4 ft.
Chicago District
10-SEP-2010 15-SEP-2010
Eddie Woods
81.4- 91.4
10.0/ 10.0
100%
Smooth drilling Water loss: 0-10%
RQD: 37%
DOLOMITE:
lt. gray, numerous horizontal fractures w/ some gray clay �lling
@ 85.6’ fracture w/ gray clay
@ 88.1’ horizontal fracture w/ gray clay
87.4-90.0’ fracture zone
91.4- 101.4
100%
Started run: 10:28 am Ended run: 10:45 am
- smooth drilling, good water return water loss 0-10%
RQD: 62%
Fracture @ 92.8’
Some shale partings every 2-6”
Fracture zone 98.1-99.4’
FISH BARRIER
B-5-10
199.4 ft.
2 ft.
NQ, Diamond embedded rotary n/a n/a
NAVD 88
585 ft.
578.6 ft.
1812259 N, 1058806 E (Illinois State Plane East NAD 83)
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
1. PROJECT
2. LOCATION (Coordinates or Station)
3. DRILLING AGENCY
4. HOLE NO. (As shown on drawing title and �le number)
5. NAME OF DRILLER
6. DIRECTION OF HOLE
VERTICAL INCLINED DEG. FROM VERTICAL
7. THICKNESS OF OVERBURDEN
8. DEPTH DRILLED INTO ROCK
9. TOTAL DEPTH OF HOLE
INSTALLATION SHEET
OF 11 SHEETS
10. SIZE AND TYPE OF BIT
11. DATUM FOR ELEVATION SHOWN (TBM or MSL)
12. MANUFACTURER’S DESIGNATION OF DRILL
13. TOTAL NO. OF OVERBURDEN
SAMPLES TAKEN
DISTURBED UNDISTURBED
14. TOTAL NUMBER OF CORE BOXES
15. ELEVATION OF GROUNDWATER
16. DATE HOLE STARTED COMPLETED
17. ELEVATION TOP OF HOLE
18. TOTAL CORE RECOVERY FOR BORING %
19. SIGNATURE OF INSPECTOR
ELEVATION
a
DEPTH LEGEND
b c
CLASSIFICATION OF MATERIALS
(Description) d
% CORE
RECOVERY
e
BOX OR
SAMPLE
NO.
f
REMARKS
(Drilling time, water loss, depth of weathering, etc., if signi�cant) g
LRD
USACE - SAM
x
201.4 ft.
Chicago District
10-SEP-2010 15-SEP-2010
Eddie Woods increasingly vuggy starting at 101.6’
Chert band 103.5-103.7’
Fractured chert band 104.2-104.4’
Chert band 111.6-112.0’
Chert band 113.2-113.5’
Chert band 116.6-116.8’
Abundant chert nodules 1-3” in diameter
Fracture zone 107.6-108.4’
Abundant fracturing along chert bands/ nodules
101.4- 111.4
10.0/ 10.0
100%
Not onsite when drilled; Drilling occurred between 7-9 am, 9/14/2010
RQD: 7.5/10.0 = 75%
111.4- 121.4’
10.0/ 10.0
100%
Not onsite when drilled
Good recovery, good intact rock
RQD: 96%
FISH BARRIER
B-5-10
199.4 ft.
2 ft.
NQ, Diamond embedded rotary n/a n/a
NAVD 88
585 ft.
578.6 ft.
1812259 N, 1058806 E (Illinois State Plane East NAD 83)
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
1. PROJECT
2. LOCATION (Coordinates or Station)
3. DRILLING AGENCY
4. HOLE NO. (As shown on drawing title and �le number)
5. NAME OF DRILLER
6. DIRECTION OF HOLE
VERTICAL INCLINED DEG. FROM VERTICAL
7. THICKNESS OF OVERBURDEN
8. DEPTH DRILLED INTO ROCK
9. TOTAL DEPTH OF HOLE
INSTALLATION SHEET
OF 11 SHEETS
10. SIZE AND TYPE OF BIT
11. DATUM FOR ELEVATION SHOWN (TBM or MSL)
12. MANUFACTURER’S DESIGNATION OF DRILL
13. TOTAL NO. OF OVERBURDEN
SAMPLES TAKEN
DISTURBED UNDISTURBED
14. TOTAL NUMBER OF CORE BOXES
15. ELEVATION OF GROUNDWATER
16. DATE HOLE STARTED COMPLETED
17. ELEVATION TOP OF HOLE
18. TOTAL CORE RECOVERY FOR BORING %
19. SIGNATURE OF INSPECTOR
ELEVATION
a
DEPTH LEGEND
b c
CLASSIFICATION OF MATERIALS
(Description) d
% CORE
RECOVERY
e
BOX OR
SAMPLE
NO.
f
REMARKS
(Drilling time, water loss, depth of weathering, etc., if signi�cant) g
LRD
USACE - SAM
x
201.4 ft.
Chicago District
10-SEP-2010 15-SEP-2010
Eddie Woods
Increasingly vuggy, small vugs
128.4-128.8 : large fossiliferous/calcite �lled cavity
Sharp contact @ 129.8’
SHALE:
Green-gray, horizontal, laminated bedding
Slaking more apparent from 129.8-131.4
121.4- 131.4
10.0/ 10.0
100%
Not onsite when drilled:
9-10 am, 9/14/2010
RQD: 84%
Mostly good quality rock w/ some small vugs
Not onsite when drilled:
10-11am?
RQD: 25%
131.4- 141.4
10.0/ 10.0
100%
FISH BARRIER
B-5-10
199.4 ft.
2 ft.
NQ, Diamond embedded rotary n/a n/a
NAVD 88
585 ft.
578.6 ft.
1812259 N, 1058806 E (Illinois State Plane East NAD 83)
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
1. PROJECT
2. LOCATION (Coordinates or Station)
3. DRILLING AGENCY
4. HOLE NO. (As shown on drawing title and �le number)
5. NAME OF DRILLER
6. DIRECTION OF HOLE
VERTICAL INCLINED DEG. FROM VERTICAL
7. THICKNESS OF OVERBURDEN
8. DEPTH DRILLED INTO ROCK
9. TOTAL DEPTH OF HOLE
INSTALLATION SHEET
OF 11 SHEETS
10. SIZE AND TYPE OF BIT
11. DATUM FOR ELEVATION SHOWN (TBM or MSL)
12. MANUFACTURER’S DESIGNATION OF DRILL
13. TOTAL NO. OF OVERBURDEN
SAMPLES TAKEN
DISTURBED UNDISTURBED
14. TOTAL NUMBER OF CORE BOXES
15. ELEVATION OF GROUNDWATER
16. DATE HOLE STARTED COMPLETED
17. ELEVATION TOP OF HOLE
18. TOTAL CORE RECOVERY FOR BORING %
19. SIGNATURE OF INSPECTOR
ELEVATION
a
DEPTH LEGEND
b c
CLASSIFICATION OF MATERIALS
(Description) d
% CORE
RECOVERY
e
BOX OR
SAMPLE
NO.
f
REMARKS
(Drilling time, water loss, depth of weathering, etc., if signi�cant) g
LRD
USACE - SAM
x
201.4 ft.
Chicago District
10-SEP-2010 15-SEP-2010
Eddie Woods
141.4- 151.4
10.0/ 10.0
100%
Smooth drilling, approx. 45 min. for 10 ft. run
Soft rock w/ some dessication but relatively intact
RQD: 90%
SHALE:
dark-gray, thinly bedded, relatively soft (scratches w/�ngernail), some thin red interbeds gets darker at approx. 140.0’
@ 145.0’ Fracture w/ dark gray clay
@ 146.1’ fracture w/ clay
146.4-148.6’ some dark maroon coloring
More ‘massive’ looking, not laminated, dark gray w/ some black beds, soft (easily scratched w/ �ngernail) dolomitic shale?
@ 155.1’ dessication not as apparent
Started run: 13:30 Ended run: 14:55
- Stuck core barrel, stopped and pulled up, started re-drilling at 14:20 relatively smooth drilling after re-start
RQD: 95%
151.4- 161.4
10.0/ 10.0
100%
FISH BARRIER
B-5-10
199.4 ft.
2 ft.
HQ, Diamond embedded rotary n/a n/a
NAVD 88
585 ft.
578.6 ft.
1812259 N, 1058806 E (Illinois State Plane East NAD 83)
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
1. PROJECT
2. LOCATION (Coordinates or Station)
3. DRILLING AGENCY
4. HOLE NO. (As shown on drawing title and �le number)
5. NAME OF DRILLER
6. DIRECTION OF HOLE
VERTICAL INCLINED DEG. FROM VERTICAL
7. THICKNESS OF OVERBURDEN
8. DEPTH DRILLED INTO ROCK
9. TOTAL DEPTH OF HOLE
INSTALLATION SHEET
OF 11 SHEETS
10. SIZE AND TYPE OF BIT
11. DATUM FOR ELEVATION SHOWN (TBM or MSL)
12. MANUFACTURER’S DESIGNATION OF DRILL
13. TOTAL NO. OF OVERBURDEN
SAMPLES TAKEN
DISTURBED UNDISTURBED
14. TOTAL NUMBER OF CORE BOXES
15. ELEVATION OF GROUNDWATER
16. DATE HOLE STARTED COMPLETED
17. ELEVATION TOP OF HOLE
18. TOTAL CORE RECOVERY FOR BORING %
19. SIGNATURE OF INSPECTOR
ELEVATION
a
DEPTH LEGEND
b c
CLASSIFICATION OF MATERIALS
(Description) d
% CORE
RECOVERY
e
BOX OR
SAMPLE
NO.
f
REMARKS
(Drilling time, water loss, depth of weathering, etc., if signi�cant) g
LRD
USACE - SAM
x
201.4 ft.
Chicago District
10-SEP-2010 15-SEP-2010
Eddie Woods
SHALE:
dark gray, thinly bedded w/ occasional darker bands 2-4” thick
161.4- 171.4
9.7/ 10.0
97%
Started run: 15:00 Ended run: 15:20
Good rock soft but virtually no fractures
RQD: 98%
171.4- 181.4
8.9/ 10.0
89%
Started run: 15:40 Ended run: 15:55
- smooth drilling, no troubles
RQD: 92%
Hit soft material at bottom of run lost ~ 1ft. of core
Very uniform material virtually no fractures
Occasional black laminated bed
FISH BARRIER
B-5-10
199.4 ft.
2 ft.
HQ, Diamond embedded rotary n/a n/a
NAVD 88
585 ft.
578.6 ft.
1812259 N, 1058806 E (Illinois State Plane East NAD 83)
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
1. PROJECT
2. LOCATION (Coordinates or Station)
3. DRILLING AGENCY
4. HOLE NO. (As shown on drawing title and �le number)
5. NAME OF DRILLER
6. DIRECTION OF HOLE
VERTICAL INCLINED DEG. FROM VERTICAL
7. THICKNESS OF OVERBURDEN
8. DEPTH DRILLED INTO ROCK
9. TOTAL DEPTH OF HOLE
INSTALLATION SHEET
OF 11 SHEETS
10. SIZE AND TYPE OF BIT
11. DATUM FOR ELEVATION SHOWN (TBM or MSL)
12. MANUFACTURER’S DESIGNATION OF DRILL
13. TOTAL NO. OF OVERBURDEN
SAMPLES TAKEN
DISTURBED UNDISTURBED
14. TOTAL NUMBER OF CORE BOXES
15. ELEVATION OF GROUNDWATER
16. DATE HOLE STARTED COMPLETED
17. ELEVATION TOP OF HOLE
18. TOTAL CORE RECOVERY FOR BORING %
19. SIGNATURE OF INSPECTOR
ELEVATION
a
DEPTH LEGEND
b c
CLASSIFICATION OF MATERIALS
(Description) d
% CORE
RECOVERY
e
BOX OR
SAMPLE
NO.
f
REMARKS
(Drilling time, water loss, depth of weathering, etc., if signi�cant) g
LRD
USACE - SAM
x
201.4 ft.
Chicago District
10-SEP-2010 15-SEP-2010
Eddie Woods
NR
SHALE:
dark gray, thinly bedded-laminated shale, soft
No recovery 180.4-181.4’
181.4- 191.4
9.0/10.0
90%
Started run: 16:20 Ended run: 16:40
Drill chattering 182-184’ smooth drilling after 184, no water loss
RQD: 7.6/9.0= 78%
some driller breaks, RQD hard to determine clay-�lled fracture at 190.0’
191.4- 201.4
10.0/ 10.0
100%
Not onsite when drilled Drilled between 7-8 am, 9/15/2010
RQD: 70%
FISH BARRIER
B-5-10
199.4 ft.
2 ft.
HQ, Diamond embedded rotary n/a n/a
NAVD 88
585 ft.
578.6 ft.
1812259 N, 1058806 E (Illinois State Plane East NAD 83)
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
1. PROJECT
2. LOCATION (Coordinates or Station)
3. DRILLING AGENCY
4. HOLE NO. (As shown on drawing title and �le number)
5. NAME OF DRILLER
6. DIRECTION OF HOLE
VERTICAL INCLINED DEG. FROM VERTICAL
7. THICKNESS OF OVERBURDEN
8. DEPTH DRILLED INTO ROCK
9. TOTAL DEPTH OF HOLE
INSTALLATION SHEET
OF 11 SHEETS
10. SIZE AND TYPE OF BIT
11. DATUM FOR ELEVATION SHOWN (TBM or MSL)
12. MANUFACTURER’S DESIGNATION OF DRILL
13. TOTAL NO. OF OVERBURDEN
SAMPLES TAKEN
DISTURBED UNDISTURBED
14. TOTAL NUMBER OF CORE BOXES
15. ELEVATION OF GROUNDWATER
16. DATE HOLE STARTED COMPLETED
17. ELEVATION TOP OF HOLE
18. TOTAL CORE RECOVERY FOR BORING %
19. SIGNATURE OF INSPECTOR
ELEVATION
a
DEPTH LEGEND
b c
CLASSIFICATION OF MATERIALS
(Description) d
% CORE
RECOVERY
e
BOX OR
SAMPLE
NO.
f
REMARKS
(Drilling time, water loss, depth of weathering, etc., if signi�cant) g
LRD
USACE - SAM
x
201.4 ft.
Chicago District
10-SEP-2010 15-SEP-2010
Eddie Woods
Ended Boring at 201.4’ Drilling stopped between 7-8am 9/15/2010
Fractured from 200.4-200.9’
FISH BARRIER
B-5-10
199.4 ft.
2 ft.
HQ, Diamond embedded rotary n/a n/a
NAVD 88
585 ft.
578.6 ft.
1812259 N, 1058806 E (Illinois State Plane East NAD 83)
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
Fish Barrier Geotech Appendix - 100% Review 05/04/12
Attachment 2
Geophysical Logs
B-5-10 and Wells 1 through 3
Project�Name
Contractor
Project�No. Client/Site
State/County
Geophysical�Log
Gamma�(CPS) Temperature�(C)D ep th �(f t)
Drilling�Date(s) Logged�By Logged�On
Equipmet�Type�=
Logging�Speed
Driller Depth�to�Water�(ft.)
Calibration
DRILL�HOLE�Vertical�Scale�=�1":10'
El ev ft .�M
SL
Notes:
Tool�Legth�(Cable�Detector)�=
Module�Settings Recorder�Settings
0 350 0 20
Sheet
ElevationRaimonde�Drilling�Corporation 770�W.�Factory�Rd.���1st�Flr Addison,�IL��60101 Tel.�(630)�458�0590 www.raimonde�drilling.com 1�of�3
Latitude
Longitude
Well�#1 Fish�(Dispersal)�Barrier�IIB�Building EP�Doyle���Romeoville3019
Illinois�/�Will11/2/2010�11/3/2010
12�ft./min
Chris�Matherly B.�Renwick 11/11/2010��12:55
11/11/2010
Mt.�Sopris�Instruments�2PGA�100�Gamma�&�2PFA�1000�Temp,�MGX�II�Console�with�4MXA�500M�Winch�(1/8"�Cable)��Denver,�CO
Gamma�=�23.2"��Temp�=�14.7"
Sunny/Clear/55�Degrees,�No�Equipment�Issues�������Gamma�Detector�=�Sodium�Iodide�Crystal
8.11�Feet
Record�Depth�Down,�Manual�Speed�Control
Will�County�Well�&�Pump
0.05M�(0.16Ft.)
88.05953
41.64305
0 10 20
0 10 20
0 58 117
0 58 117
0 5 1 1 2 2 3
CEFB 2B
Submittal #33 20 00 11.3 & 11.4 J. Pankros, 11-23-2010
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
Project�No. Client/Site
State/County
Geophysical�Log
Gamma�(CPS) Temperature�(C)D ep th �(f t)
Drilling�Date(s) Logged�By Logged�On
Equipmet�Type�=
Logging�Speed
Driller Depth�to�Water�(ft.)
Calibration
DRILL�HOLE�Vertical�Scale�=�1":10'
El ev ft .�M
SL
Notes:
Tool�Legth�(Cable�Detector)�=
Module�Settings Recorder�Settings
0 350 0 20
Sheet
ElevationRaimonde�Drilling�Corporation 770�W.�Factory�Rd.���1st�Flr Addison,�IL��60101 Tel.�(630)�458�0590 www.raimonde�drilling.com 2�of�3
Latitude
Longitude
Well�#1 Fish�(Dispersal)�Barrier�IIB�Building EP�Doyle���Romeoville3019
Illinois�/�Will11/2/2010�11/3/2010
12�ft./min
Chris�Matherly B.�Renwick 11/11/2010��12:55
11/11/2010
Mt.�Sopris�Instruments�2PGA�100�Gamma�&�2PFA�1000�Temp,�MGX�II�Console�with�4MXA�500M�Winch�(1/8"�Cable)��Denver,�CO
Gamma�=�23.2"��Temp�=�14.7"
Sunny/Clear/55�Degrees,�No�Equipment�Issues�������Gamma�Detector�=�Sodium�Iodide�Crystal
8.11�Feet
Record�Depth�Down,�Manual�Speed�Control
Will�County�Well�&�Pump
0.05M�(0.16Ft.)
88.05953
41.64305
0 10 20
0 10 20
0 10 20
0 58 117
0 58 117
0 58 117
0 5 1 1 2 2 3
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
Project�No. Client/Site
State/County
Geophysical�Log
Gamma�(CPS) Temperature�(C)D ep th �(f t)
Drilling�Date(s) Logged�By Logged�On
Equipmet�Type�=
Logging�Speed
Driller Depth�to�Water�(ft.)
Calibration
DRILL�HOLE�Vertical�Scale�=�1":10'
El ev ft .�M
SL
Notes:
Tool�Legth�(Cable�Detector)�=
Module�Settings Recorder�Settings
0 350 0 20
Sheet
ElevationRaimonde�Drilling�Corporation 770�W.�Factory�Rd.���1st�Flr Addison,�IL��60101 Tel.�(630)�458�0590 www.raimonde�drilling.com 3�of�3
Latitude
Longitude
Well�#1 Fish�(Dispersal)�Barrier�IIB�Building EP�Doyle���Romeoville3019
Illinois�/�Will11/2/2010�11/3/2010
12�ft./min
Chris�Matherly B.�Renwick 11/11/2010��12:55
11/11/2010
Mt.�Sopris�Instruments�2PGA�100�Gamma�&�2PFA�1000�Temp,�MGX�II�Console�with�4MXA�500M�Winch�(1/8"�Cable)��Denver,�CO
Gamma�=�23.2"��Temp�=�14.7"
Sunny/Clear/55�Degrees,�No�Equipment�Issues�������Gamma�Detector�=�Sodium�Iodide�Crystal
8.11�Feet
Record�Depth�Down,�Manual�Speed�Control
Will�County�Well�&�Pump
0.05M�(0.16Ft.)
88.05953
41.64305
0 10 20
0 58 117
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
Project�No. Client/Site
State/County
Geophysical�Log
Gamma�(CPS) Temperature�(C)D ep th �(f t)
Drilling�Date(s) Logged�By Logged�On
Equipmet�Type�=
Logging�Speed
Driller Depth�to�Water�(ft.)
Calibration
DRILL�HOLE�Vertical�Scale�=�1":10'
El ev ft .�M
SL
Notes:
Tool�Legth�(Cable�Detector)�=
Module�Settings Recorder�Settings
0 350 0 20
Sheet
ElevationRaimonde�Drilling�Corporation 770�W.�Factory�Rd.���1st�Flr Addison,�IL��60101 Tel.�(630)�458�0590 www.raimonde�drilling.com 1�of�4
Latitude
Longitude
Well#2 Fish�(Dispersal)�Barrier�IIB�Building EP�Doyle���Romeoville3019
Illinois�/�Will10/1/2010�10/7/2010
12�ft./min
Chris�Matherly B.�Renwick 11/12/2010��08:25
11/11/2010
Mt.�Sopris�Instruments�2PGA�100�Gamma�&�2PFA�1000�Temp,�MGX�II�Console�with�4MXA�500M�Winch�(1/8"�Cable)��Denver,�CO
Gamma�=�23.2"��Temp�=�14.7"
Sunny/Clear/55�Degrees,�No�Equipment�Issues�������Gamma�Detector�=�Sodium�Iodide�Crystal
8.91
Record�Depth�Down,�Manual�Speed�Control
Will�County�Well�&�Pump
0.05M�(0.16Ft.)
88.05961
41.64256
0 10 20
0 10 20
0 58 117
0 58 117
0 5 1 1 2 2 3
CEFB 2B
Submittal #33 20 00 11 & 11.1 J. Pankros, 11-23-2010
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
Project�No. Client/Site
State/County
Geophysical�Log
Gamma�(CPS) Temperature�(C)D ep th �(f t)
Drilling�Date(s) Logged�By Logged�On
Equipmet�Type�=
Logging�Speed
Driller Depth�to�Water�(ft.)
Calibration
DRILL�HOLE�Vertical�Scale�=�1":10'
El ev ft .�M
SL
Notes:
Tool�Legth�(Cable�Detector)�=
Module�Settings Recorder�Settings
0 350 0 20
Sheet
ElevationRaimonde�Drilling�Corporation 770�W.�Factory�Rd.���1st�Flr Addison,�IL��60101 Tel.�(630)�458�0590 www.raimonde�drilling.com 2�of�4
Latitude
Longitude
Well#2 Fish�(Dispersal)�Barrier�IIB�Building EP�Doyle���Romeoville3019
Illinois�/�Will10/1/2010�10/7/2010
12�ft./min
Chris�Matherly B.�Renwick 11/12/2010��08:25
11/11/2010
Mt.�Sopris�Instruments�2PGA�100�Gamma�&�2PFA�1000�Temp,�MGX�II�Console�with�4MXA�500M�Winch�(1/8"�Cable)��Denver,�CO
Gamma�=�23.2"��Temp�=�14.7"
Sunny/Clear/55�Degrees,�No�Equipment�Issues�������Gamma�Detector�=�Sodium�Iodide�Crystal
8.91
Record�Depth�Down,�Manual�Speed�Control
Will�County�Well�&�Pump
0.05M�(0.16Ft.)
88.05961
41.64256
0 10 20
0 10 20
0 10 20
0 58 117
0 58 117
0 58 117
0 5 1 1 2 2 3
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
Project�No. Client/Site
State/County
Geophysical�Log
Gamma�(CPS) Temperature�(C)D ep th �(f t)
Drilling�Date(s) Logged�By Logged�On
Equipmet�Type�=
Logging�Speed
Driller Depth�to�Water�(ft.)
Calibration
DRILL�HOLE�Vertical�Scale�=�1":10'
El ev ft .�M
SL
Notes:
Tool�Legth�(Cable�Detector)�=
Module�Settings Recorder�Settings
0 350 0 20
Sheet
ElevationRaimonde�Drilling�Corporation 770�W.�Factory�Rd.���1st�Flr Addison,�IL��60101 Tel.�(630)�458�0590 www.raimonde�drilling.com 3�of�4
Latitude
Longitude
Well#2 Fish�(Dispersal)�Barrier�IIB�Building EP�Doyle���Romeoville3019
Illinois�/�Will10/1/2010�10/7/2010
12�ft./min
Chris�Matherly B.�Renwick 11/12/2010��08:25
11/11/2010
Mt.�Sopris�Instruments�2PGA�100�Gamma�&�2PFA�1000�Temp,�MGX�II�Console�with�4MXA�500M�Winch�(1/8"�Cable)��Denver,�CO
Gamma�=�23.2"��Temp�=�14.7"
Sunny/Clear/55�Degrees,�No�Equipment�Issues�������Gamma�Detector�=�Sodium�Iodide�Crystal
8.91
Record�Depth�Down,�Manual�Speed�Control
Will�County�Well�&�Pump
0.05M�(0.16Ft.)
88.05961
41.64256
0 10 20
0 10 20
0 10 20
0 58 117
0 58 117
0 58 117
0 5 1 1 2 2 3
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
Project�No. Client/Site
State/County
Geophysical�Log
Gamma�(CPS) Temperature�(C)D ep th �(f t)
Drilling�Date(s) Logged�By Logged�On
Equipmet�Type�=
Logging�Speed
Driller Depth�to�Water�(ft.)
Calibration
DRILL�HOLE�Vertical�Scale�=�1":10'
El ev ft .�M
SL
Notes:
Tool�Legth�(Cable�Detector)�=
Module�Settings Recorder�Settings
0 350 0 20
Sheet
ElevationRaimonde�Drilling�Corporation 770�W.�Factory�Rd.���1st�Flr Addison,�IL��60101 Tel.�(630)�458�0590 www.raimonde�drilling.com 4�of�4
Latitude
Longitude
Well#2 Fish�(Dispersal)�Barrier�IIB�Building EP�Doyle���Romeoville3019
Illinois�/�Will10/1/2010�10/7/2010
12�ft./min
Chris�Matherly B.�Renwick 11/12/2010��08:25
11/11/2010
Mt.�Sopris�Instruments�2PGA�100�Gamma�&�2PFA�1000�Temp,�MGX�II�Console�with�4MXA�500M�Winch�(1/8"�Cable)��Denver,�CO
Gamma�=�23.2"��Temp�=�14.7"
Sunny/Clear/55�Degrees,�No�Equipment�Issues�������Gamma�Detector�=�Sodium�Iodide�Crystal
8.91
Record�Depth�Down,�Manual�Speed�Control
Will�County�Well�&�Pump
0.05M�(0.16Ft.)
88.05961
41.64256
0 10 20
0 58 117
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
Project�No. Client/Site
State/County
Geophysical�Log
Gamma�(CPS) Temperature�(C)D ep th �(f t)
Drilling�Date(s) Logged�By Logged�On
Equipmet�Type�=
Logging�Speed
Driller Depth�to�Water�(ft.)
Calibration
DRILL�HOLE�Vertical�Scale�=�1":10'
El ev ft .�M
SL
Notes:
Tool�Legth�(Cable�Detector)�=
Module�Settings Recorder�Settings
0 350 0 20
Sheet
ElevationRaimonde�Drilling�Corporation 770�W.�Factory�Rd.���1st�Flr Addison,�IL��60101 Tel.�(630)�458�0590 www.raimonde�drilling.com 1�of�4
Latitude
Longitude
Well#3 Fish�(Dispersal)�Barrier�IIB�Building EP�Doyle���Romeoville3019
Illinois�/�Will11/9/2010�11/10/2010
12�ft./min
Chris�Matherly B.�Renwick 11/11/2010��14:10
11/11/2010
Mt.�Sopris�Instruments�2PGA�100�Gamma�&�2PFA�1000�Temp,�MGX�II�Console�with�4MXA�500M�Winch�(1/8"�Cable)��Denver,�CO
Gamma�=�23.2"��Temp�=�14.7"
Sunny/Clear/55�Degrees,�No�Equipment�Issues�������Gamma�Detector�=�Sodium�Iodide�Crystal
8.42
Record�Depth�Down,�Manual�Speed�Control
Will�County�Well�&�Pump
0.05M�(0.16Ft.)
88.05953
41.64091
0 10 20
0 10 20
0 58 117
0 58 117
0 5 1 1 2 2 3
CEFB 2B
Submittal #33 20 00 11.6 & 11.7 J. Pankros, 11-23-2010
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
Project�No. Client/Site
State/County
Geophysical�Log
Gamma�(CPS) Temperature�(C)D ep th �(f t)
Drilling�Date(s) Logged�By Logged�On
Equipmet�Type�=
Logging�Speed
Driller Depth�to�Water�(ft.)
Calibration
DRILL�HOLE�Vertical�Scale�=�1":10'
El ev ft .�M
SL
Notes:
Tool�Legth�(Cable�Detector)�=
Module�Settings Recorder�Settings
0 350 0 20
Sheet
ElevationRaimonde�Drilling�Corporation 770�W.�Factory�Rd.���1st�Flr Addison,�IL��60101 Tel.�(630)�458�0590 www.raimonde�drilling.com 2�of�4
Latitude
Longitude
Well#3 Fish�(Dispersal)�Barrier�IIB�Building EP�Doyle���Romeoville3019
Illinois�/�Will11/9/2010�11/10/2010
12�ft./min
Chris�Matherly B.�Renwick 11/11/2010��14:10
11/11/2010
Mt.�Sopris�Instruments�2PGA�100�Gamma�&�2PFA�1000�Temp,�MGX�II�Console�with�4MXA�500M�Winch�(1/8"�Cable)��Denver,�CO
Gamma�=�23.2"��Temp�=�14.7"
Sunny/Clear/55�Degrees,�No�Equipment�Issues�������Gamma�Detector�=�Sodium�Iodide�Crystal
8.42
Record�Depth�Down,�Manual�Speed�Control
Will�County�Well�&�Pump
0.05M�(0.16Ft.)
88.05953
41.64091
0 10 20
0 10 20
0 10 20
0 58 117
0 58 117
0 58 117
0 5 1 1 2 2 3
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
Project�No. Client/Site
State/County
Geophysical�Log
Gamma�(CPS) Temperature�(C)D ep th �(f t)
Drilling�Date(s) Logged�By Logged�On
Equipmet�Type�=
Logging�Speed
Driller Depth�to�Water�(ft.)
Calibration
DRILL�HOLE�Vertical�Scale�=�1":10'
El ev ft .�M
SL
Notes:
Tool�Legth�(Cable�Detector)�=
Module�Settings Recorder�Settings
0 350 0 20
Sheet
ElevationRaimonde�Drilling�Corporation 770�W.�Factory�Rd.���1st�Flr Addison,�IL��60101 Tel.�(630)�458�0590 www.raimonde�drilling.com 3�of�4
Latitude
Longitude
Well#3 Fish�(Dispersal)�Barrier�IIB�Building EP�Doyle���Romeoville3019
Illinois�/�Will11/9/2010�11/10/2010
12�ft./min
Chris�Matherly B.�Renwick 11/11/2010��14:10
11/11/2010
Mt.�Sopris�Instruments�2PGA�100�Gamma�&�2PFA�1000�Temp,�MGX�II�Console�with�4MXA�500M�Winch�(1/8"�Cable)��Denver,�CO
Gamma�=�23.2"��Temp�=�14.7"
Sunny/Clear/55�Degrees,�No�Equipment�Issues�������Gamma�Detector�=�Sodium�Iodide�Crystal
8.42
Record�Depth�Down,�Manual�Speed�Control
Will�County�Well�&�Pump
0.05M�(0.16Ft.)
88.05953
41.64091
0 10 20
0 10 20
0 10 20
0 58 117
0 58 117
0 58 117
0 5 1 1 2 2 3
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
Project�No. Client/Site
State/County
Geophysical�Log
Gamma�(CPS) Temperature�(C)D ep th �(f t)
Drilling�Date(s) Logged�By Logged�On
Equipmet�Type�=
Logging�Speed
Driller Depth�to�Water�(ft.)
Calibration
DRILL�HOLE�Vertical�Scale�=�1":10'
El ev ft .�M
SL
Notes:
Tool�Legth�(Cable�Detector)�=
Module�Settings Recorder�Settings
0 350 0 20
Sheet
ElevationRaimonde�Drilling�Corporation 770�W.�Factory�Rd.���1st�Flr Addison,�IL��60101 Tel.�(630)�458�0590 www.raimonde�drilling.com 4�of�4
Latitude
Longitude
Well#3 Fish�(Dispersal)�Barrier�IIB�Building EP�Doyle���Romeoville3019
Illinois�/�Will11/9/2010�11/10/2010
12�ft./min
Chris�Matherly B.�Renwick 11/11/2010��14:10
11/11/2010
Mt.�Sopris�Instruments�2PGA�100�Gamma�&�2PFA�1000�Temp,�MGX�II�Console�with�4MXA�500M�Winch�(1/8"�Cable)��Denver,�CO
Gamma�=�23.2"��Temp�=�14.7"
Sunny/Clear/55�Degrees,�No�Equipment�Issues�������Gamma�Detector�=�Sodium�Iodide�Crystal
8.42
Record�Depth�Down,�Manual�Speed�Control
Will�County�Well�&�Pump
0.05M�(0.16Ft.)
88.05953
41.64091
0 10 20
0 58 117
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
Fish Barrier Geotech Appendix - 100% Review 05/04/12
Attachment 3
Water Well Installation Documentation
CEFB 2B
Submittal #33 20 00 8 J. Pankros, 1-27-2011
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
Submittal #33 20 00 8.1 J. Pankros, 1-27-2011
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
Submittal #33 20 00 8.2 J. Pankros, 1-27-2011
CSSC Dispersal Barrier 1, Project B - Building
00 31 32.13 03_Attachment A
DIVISION 03 - CONCRETE
SECTION 03 45 33
PRECAST PRESTRESSED STRUCTURAL CONCRETE
PART 1 GENERAL
1.1 REFERENCES
1.2 SYSTEM DESCRIPTION
1.2.1 Design Requirements
1.2.1.1 Loads
1.2.1.2 Drawing and Design Calculation Information
1.2.2 Performance Requirements
1.3 MODIFICATION TO REFERENCE
1.4 SUBMITTALS
1.5 QUALITY ASSURANCE
1.5.1 Qualifications
1.5.1.1 Manufacturer Qualifications
1.5.1.2 Designer Qualifications
1.5.1.3 Erector Qualifications
1.5.1.4 Welding Qualifications
1.5.2 Regulatory Requirements
1.5.3 Concrete Mix Design
1.5.4 Certificates: Record Requirement
1.6 DELIVERY, STORAGE, AND HANDLING
1.6.1 Transportation
1.6.1.1 Transporting Members
1.6.1.2 Lateral Deflection or Vibration
1.6.2 Storage
1.6.2.1 Storage Areas
1.6.2.2 Stacked members
1.6.3 Handling of Members
PART 2 PRODUCTS
2.1 CONTRACTOR-FURNISHED MIX DESIGN
2.2 MATERIALS
2.2.1 Cement
2.2.1.1 Fly Ash and Pozzolan
2.2.1.2 Ground Iron Blast-Furnace Slag
2.2.1.3 Silica Fume
2.2.2 Water
2.2.3 Aggregates
2.2.3.1 Aggregates Selection
2.2.3.2 Alkali-Silica Reactivity
2.2.4 Admixtures
2.2.4.1 Air-Entraining
2.2.4.2 Accelerating
2.2.4.3 Water Reducing
2.2.5 Reinforcement
2.2.5.1 Reinforcing Bars
SECTION 03 45 33 - Page 1
2.2.5.2 Wire
2.2.5.3 Welded Wire Fabric
2.2.6 Prestressing Strands
2.2.7 Metal Accessories
2.2.7.1 Inserts
2.2.7.2 Structural Steel
2.2.7.3 Bolts
2.2.7.4 Nuts
2.2.7.5 Washers
2.2.8 Bearing Pads
2.2.8.1 Elastomeric
2.3 PRODUCTION QUALITY CONTROL PROCEDURES
2.3.1 Forms
2.3.2 Reinforcement Placement
2.3.3 Inserts
2.3.4 Concrete
2.3.4.1 Concrete Mixing
2.3.4.2 Concrete Placing
2.3.4.3 Concrete Curing
2.3.5 Prestressing
2.3.6 Surface Finish
2.3.6.1 Unformed Surfaces
2.3.6.2 Formed Surfaces
2.3.7 Acceptance/Rejection of Defects
2.3.7.1 Minor Defects
2.3.7.2 Major Defects
2.4 TESTS, INSPECTIONS, AND VERIFICATIONS
2.4.1 Chloride Ion Concentration Test
2.4.2 Chloride Ion Penetration Test
2.4.3 Factory Inspection
PART 3 EXECUTION
3.1 EXAMINATION
3.2 ERECTION
3.3 BEARING SURFACES
3.4 ANCHORAGE
3.5 WELDING
3.6 OPENINGS
3.7 GALVANIZING REPAIR
3.8 SEALANTS
3.9 CONCRETE TOPPING
3.10 CONSTRUCTION RECORDS
-- End of Section Table of Contents --
SECTION 03 45 33 - Page 2
SECTION 03 45 33
PRECAST PRESTRESSED STRUCTURAL CONCRETE
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
AMERICAN ASSOCIATION OF STATE HIGHWAY AND TRANSPORTATION OFFICIALS
(AASHTO)
AASHTO HB-17 (2002; Errata 2003; Errata 2005, 17th Edition) Standard Specifications for Highway Bridges
AASHTO T 259 (2002; R 2012) Standard Method of Test for Resistance of Concrete to Chloride Ion Penetration
AMERICAN CONCRETE INSTITUTE INTERNATIONAL (ACI)
ACI 304R (2000; R 2009) Guide for Measuring, Mixing, Transporting, and Placing Concrete
ACI 305R (2010) Guide to Hot Weather Concreting
ACI 306.1 (1990; R 2002) Standard Specification for Cold Weather Concreting
ACI 309R (2005) Guide for Consolidation of Concrete
ACI 318 (2011; Errata 1 2011; Errata 2 2012;
Errata 3-4 2013) Building Code Requirements for Structural Concrete and Commentary
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2010; Errata 2011) Structural Welding Code - Steel
AWS D1.4/D1.4M (2011) Structural Welding Code - Reinforcing Steel
ASTM INTERNATIONAL (ASTM)
ASTM A1064/A1064M (2013) Standard Specification for Carbon-Steel Wire and Welded Wire Reinforcement, Plain and Deformed, for Concrete
ASTM A123/A123M (2013) Standard Specification for Zinc
SECTION 03 45 33 - Page 3
(Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A153/A153M (2009) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A27/A27M (2013) Standard Specification for Steel Castings, Carbon, for General Application
ASTM A307 (2012) Standard Specification for Carbon Steel Bolts and Studs, 60 000 PSI Tensile Strength
ASTM A325 (2010; E 2013) Standard Specification for Structural Bolts, Steel, Heat Treated, 120/105 ksi Minimum Tensile Strength
ASTM A36/A36M (2012) Standard Specification for Carbon Structural Steel
ASTM A416/A416M (2012) Standard Specification for Steel Strand, Uncoated Seven-Wire for Prestressed Concrete
ASTM A421/A421M (2010) Standard Specification for Uncoated Stress-Relieved Steel Wire for Prestressed Concrete
ASTM A47/A47M (1999; R 2009) Standard Specification for Ferritic Malleable Iron Castings
ASTM A563 (2007a) Standard Specification for Carbon and Alloy Steel Nuts
ASTM A615/A615M (2013) Standard Specification for Deformed and Plain Carbon-Steel Bars for Concrete Reinforcement
ASTM A780/A780M (2009) Standard Practice for Repair of Damaged and Uncoated Areas of Hot-Dip Galvanized Coatings
ASTM C1069 (2009) Standard Test Method for Specific Surface Area of Alumina or Quartz by Nitrogen Adsorption
ASTM C1202 (2012) Standard Test Method for Electrical Indication of Concrete's Ability to Resist Chloride Ion Penetration
ASTM C1218/C1218M (1999; R 2008) Standard Specification for Water-Soluble Chloride in Mortar and Concrete
ASTM C1240 (2012) Standard Specification for Silica Fume Used in Cementitious Mixtures
ASTM C1260 (2007) Standard Test Method for Potential
SECTION 03 45 33 - Page 4
Alkali Reactivity of Aggregates (Mortar-Bar Method)
ASTM C150/C150M (2012) Standard Specification for Portland Cement
ASTM C260/C260M (2010a) Standard Specification for Air-Entraining Admixtures for Concrete
ASTM C311/C311M (2013) Sampling and Testing Fly Ash or Natural Pozzolans for Use as a Mineral Admixture in Portland-Cement Concrete
ASTM C33/C33M (2013) Standard Specification for Concrete Aggregates
ASTM C430 (2008) Fineness of Hydraulic Cement by the 45-Micrometer (No. 325) Sieve
ASTM C494/C494M (2013) Standard Specification for Chemical Admixtures for Concrete
ASTM C618 (2012a) Standard Specification for Coal Fly Ash and Raw or Calcined Natural Pozzolan for Use in Concrete
ASTM C94/C94M (2014) Standard Specification for Ready-Mixed Concrete
ASTM C989/C989M (2013) Standard Specification for Slag Cement for Use in Concrete and Mortars
ASTM F436 (2011) Hardened Steel Washers
ASTM F844 (2007a; R 2013) Washers, Steel, Plain (Flat), Unhardened for General Use
PRECAST/PRESTRESSED CONCRETE INSTITUTE (PCI)
PCI MNL-116 (1999) Manual for Quality Control for Plants and Production of Structural Precast Concrete Products, 4th Edition
PCI MNL-120 (2010) PCI Design Handbook - Precast and Prestressed Concrete, 6th Edition
PCI MNL-124 (2011) Design for Fire Resistance of Precast Prestressed Concrete, Third Edition
UNDERWRITERS LABORATORIES (UL)
UL Fire Resistance (2012) Fire Resistance Directory
1.2 SYSTEM DESCRIPTION
The work includes the provision of precast non-prestressed concrete herein referred to as precast members and precast, prestressed concrete herein referred to as prestressed members Precast and Prestressed members shall be the product of a manufacturer specializing in the production of precast
SECTION 03 45 33 - Page 5 prestressed concrete members.
1.2.1 Design Requirements
Design precast prestressed members in accordance with ACI 318 and the PCI MNL-120. Design precast prestressed members (including connections) for the design load conditions and spans indicated, and handling and erection stresses, and for additional loads imposed by openings and supports of the work of other trades. Design precast prestressed members for handling without cracking in accordance with the PCI MNL-120. Concrete toppings shall be used in establishing the design strength of the precast prestressed members.
1.2.1.1 Loads
Loadings for members and connections shall include all dead load, live load, applicable lateral loads such as wind and earthquake, applicable construction loads such as handling, erection loads, and other applicable loads.
1.2.1.2 Drawing and Design Calculation Information
Submit drawings and design calculations indicating complete information for the fabrication, handling, and erection of the precast prestressed member.
Drawings shall not be reproductions of contract drawings. Design calculations, and drawings of precast prestressed concrete members (including connections) shall be made by a registered professional engineer experienced in the design of precast prestressed concrete members and submitted for approval prior to fabrication. The drawings shall indicate, as a minimum, the following information:
a. Plans, elevations and other drawing views showing the following:
(1) Member piece marks locating and defining products furnished by the manufacturer.
(2) Headers for openings.
(3) Location and size of openings.
(4) Relationships to adjacent material.
(5) Joints and openings between members and between members and other construction.
(6) Location of field installed anchors.
(7) Erection sequences and handling requirements
(8) Areas receiving toppings and magnitude of topping thickness.
Identify areas where topping is an integral part of the structural capacity of the precast members.
(9) Lifting and erection inserts
b. Elevations, sections and other details for each member showing the following:
(1) Connections between members and connections between members and
SECTION 03 45 33 - Page 6 other construction.
(2) Connections for work of other trades and cast-in items and their relation to other trades.
(3) Dimensioned size and shape for each member with quantities, position and other details of reinforcing steel, anchors, inserts and other embedded items.
(4) Lifting, erection and other handling devices and inserts.
(5) Surface finishes of each member.
(6) Estimated cambers
c. All dead, live, handling, erection and other applicable loads used in the design.
1.2.2 Performance Requirements
Precast prestressed members shall have a fire rating of 2-hours in accordance with UL Fire Resistance, or as designed in accordance with
PCI MNL-124.
1.3 MODIFICATION TO REFERENCE
In the ACI publications, the advisory provisions shall be considered to be mandatory, as though the word "shall" has been substituted for "should" wherever it appears; reference to the "Building Official," the "Structural Engineer" and the "Architect/Engineer" shall be interpreted to mean the Contracting Officer.
1.4 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. The following shall be submitted in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Drawings of precast members; G, DT
Drawings of precast prestressed concrete members; G, DT
SD-03 Product Data
Anchorage and lifting inserts and devices
Bearing pads
SD-05 Design Data
Precast Prestressed concrete members design calculations; G, DT
Concrete mix design; G, DT
SD-06 Test Reports
SECTION 03 45 33 - Page 7
Contractor-furnished mix design; G, DT
Submit copies of laboratory test reports showing that the mix has been successfully tested to produce concrete with the properties specified and that mix will be suitable for the job conditions.
The laboratory test reports shall include mill test and all other test for cement, [silica fume, ]aggregates, and admixtures.
Provide maximum nominal aggregate size, gradation analysis, percentage retained and passing sieve, and a graph of percentage retained versus sieve size. Test reports shall be submitted along with the concrete mix design. Obtain approval before concrete placement.
SD-07 Certificates
Quality control procedures
Submit quality control procedures established in accordance with PCI MNL-116 by the precast manufacturer.
Construction Records; G
Construction records of the manufacturing, handling, and erection of the precast prestressed concrete members shall be submitted.
1.5 QUALITY ASSURANCE
1.5.1 Qualifications
1.5.1.1 Manufacturer Qualifications
PCI MNL-116. Plants shall be certified by the PCI Plant Certification Program. At the Contracting Officer's option, PCI Plant quality control program records shall be available for review.
1.5.1.2 Designer Qualifications
The designer shall be a registered professional engineer experienced in the design of precast prestressed concrete.
1.5.1.3 Erector Qualifications
The erector shall be regularly engaged for at least three years in the erection of precast prestressed structural concrete similar to the requirements of this project.
1.5.1.4 Welding Qualifications
Provide AWS D1.1/D1.1M qualified welders who are currently certified at contract award date and have maintained their certificates over the past year.
1.5.2 Regulatory Requirements
Provide precast [prestressed] members in conformance with ACI 318 and
AWS D1.4/D1.4M.
SECTION 03 45 33 - Page 8
1.5.3 Concrete Mix Design
Thirty days minimum prior to concrete placement, submit a mix design for each strength and type of concrete. Submit a complete list of materials including type; brand; source and amount of cement, fly ash, pozzolans, ground slag, and admixtures, and applicable reference specification.
Provide mix proportion data using at least three different water-cement ratios for each class and type of concrete required. If source material changes, resubmit mix proportion data using revised source material. No material shall be provided unless proven by trial mix studies to meet the requirements of this specification, unless otherwise approved in writing by the Contracting Officer.