J_1502000_03_Optional_equipment_Inventory.xlsx

XLSX spreadsheet 32 KB Posted

Attached to
Fort Jackson Preventative Maintenance Services
Solicitation number
W912HP-16-R-0026
Issued by

About this file

Optional Equipment Inventory

View the file

Other files

File Type Posted
AMD_8_16R26_PMS_Ft._Jackson_2017.03.24.pdf PDF
AMD_6_Bidder_Inquiries__2017.03.23_UPDATE.pdf PDF
J-02_00_000-13_Record_of_Environmental_Consideration_(REC).pdf PDF
J_02_00_000_07_ELINs_R4.xlsx XLSX spreadsheet
AMD_7_16R26_PMS_Ft._Jackson_2017.03.22.pdf PDF
16R26_PMS_Ft._Jackson_-_conformed_thru_AMD_7.pdf PDF
AMD_6_Bidder_Inquiries.pdf PDF
AMD_6_16R26_PMS_Ft._Jackson_2017.03.20.pdf PDF
J_02_00_000_07_ELINs_R3.xlsx XLSX spreadsheet
16R26_PMS_Ft._Jackson_-_conformed_thru_AMD_6.pdf PDF
AMD_5_16R26_PMS_Ft._Jackson_2017.03.11.pdf PDF
J_15_02_000_06_GFEBS_Role_Authorization_Form.pdf PDF
J_15_02_000_08_ALMS_GFEBS_directions.doc DOC document
J_15_02_000_09_Building_Inventory.xlsx XLSX spreadsheet
J_02_00_000_07_ELINs_R2.xlsx XLSX spreadsheet
J_15_02_000_07_2017_02_17_Work_Orders_with_total_cost.xlsx XLSX spreadsheet
J_15_02_000_05_DFAC_Equipment_Listings.pdf PDF
J_15_02-000_10_Work_Order_Status.xlsx XLSX spreadsheet
J_02_00_000_12_Employee_Background_check_information.pdf PDF
J_15_02_000_03_Optional_equipment_Inventory_R1.xlsx XLSX spreadsheet
16R26_PMS_Ft._Jackson_-_conformed_thru_AMD_5.pdf PDF
16R26_PMS_Ft._Jackson_SF30.pdf PDF
16R26_PMS_Ft._Jackson_-_conformed.pdf PDF
AMD_3_16R26_Ft._Jackson_-_Conformed.pdf PDF
Section_J_02_00_000_07_ELINS_R1.xlsx XLSX spreadsheet
AMD_3_16R26_PMS_Ft._Jackson__2017.02.09.pdf PDF
Preproposal_Sign-in_sheet_2.pdf PDF
Preproposal_Sign-In_Sheet.pdf PDF
AMD_2_16R26_-_conformed.pdf PDF
APPENDIX_D1_Proposal_Data_Sheet.docx DOCX document
APPENDIX_D2_Corp_Experience_Data_Sheet.docx DOCX document
APPENDIX_D3_Past_Performance_Questionnaire.docx DOCX document
AMD_2_16R26_-_SF30.pdf PDF
AMD_1_16R26_PMS_Ft_Jackson.pdf PDF
AMD_1_16R26_PMS_Ft_Jackson_-_Conformed.pdf PDF
J_0200000_06_Government_Funished_Property_Materials_and_Services.pdf PDF
J_0200000_02_Wage_Determinations.pdf PDF
Section_J_15_02_000_02__Service_call_History.xlsx XLSX spreadsheet
J_0200000_05_Forms.pdf PDF
J_0200000_07_Exhibit_Line_Item_Number_(ELINS).xlsx XLSX spreadsheet
J_0200000_04_Invoicing_Procedures_.pdf PDF
J_0200000_03_References_Instructions_and_Directives_.pdf PDF
J_1502000_05_Fort_Jackson_Map.pdf PDF
J_0200000_01_Acronyms_and_Abbreviations.pdf PDF
J_1502000_01_Expected_Service_Call_Amount.pdf PDF
J_0200000_10__Sample_IDIQ_proposal.pdf PDF
W912HP-16-R-0026_PMS_Ft._Jackson.pdf PDF
J_1502000_04_Building_Inventory.xlsx XLSX spreadsheet
DRAFT_PWS_Fort_Jackson_FIS_90__REV_2016.12.06.pdf PDF
Show all 49

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Generators

FORT JACKSON REAL PROPERTY GENERATORS
Building NumberServiced BySpecific LocationBuilding FunctionEngine ManufacturerEngine Model NumberEngine Serial NumberGenset ManufacturerGenset Model NumberGenset Serial NumberFuelGenerator Output (kW)Engine HPManufacture DateStack configuration
(vertical, horizontal)Associated Fuel Storage Tank
(AST, UST or None)Capacity
(gallons)Needed Service
2400DPWBehind buildingHeadquartersCumminsTD400-01P-8376Diesel400536Jun-15In addition to regular maintenance, the following services need to occur:

a. Oil and filter every 500 hours or annually

b. Inspect air cleaner every 1000 hours or annually. Change as needed

c. Inspect all hoses and belts every 500 hours or annually. Change as needed.

d. Document maintenance and include meter reading at the time of maintenance. Submit documentation to Fort Jackson 2609 DPW Behind building, inside fence NEC Mitsubishi 4D34-T(?) Unknown Generac 3931290100 2076879 Diesel 60 80 Apr-04 Vertical AST Unknown In addition to regular maintenance, the following services need to occur:

a. Oil and filter every 500 hours or annually

b. Inspect air cleaner every 1000 hours or annually. Change as needed

c. Inspect all hoses and belts every 500 hours or annually. Change as needed.

d. Document maintenance and include meter reading at the time of maintenance. Submit documentation to Fort Jackson 3100 DPW Next to building, inside fence NEC Cummins Unknown Unknown Cummins DSFAE-7295859 F110221737 Diesel 80 107 Jun-11 Vertical AST Unknown In addition to regular maintenance, the following services need to occur:

a. Oil and filter every 500 hours or annually

b. Inspect air cleaner every 1000 hours or annually. Change as needed

c. Inspect all hoses and belts every 500 hours or annually. Change as needed.

d. Document maintenance and include meter reading at the time of maintenance. Submit documentation to Fort Jackson J4236 DPW Next to building, inside fence NEC Mitsubishi 4D34-T 0D5825 Generac 3617980100 2074860 Diesel 80 107 Nov-03 In addition to regular maintenance, the following services need to occur:

a. Oil and filter every 500 hours or annually

b. Inspect air cleaner every 1000 hours or annually. Change as needed

c. Inspect all hoses and belts every 500 hours or annually. Change as needed.

d. Document maintenance and include meter reading at the time of maintenance. Submit documentation to Fort Jackson 4282 DPW Behind building NEC Cummins Q5X15-G9 79635574 Cummins DFEH-1220445 A130452520 Diesel 354 475? Jan-13 In addition to regular maintenance, the following services need to occur:

a. Oil and filter every 500 hours or annually

b. Inspect air cleaner every 1000 hours or annually. Change as needed

c. Inspect all hoses and belts every 500 hours or annually. Change as needed.

d. Document maintenance and include meter reading at the time of maintenance. Submit documentation to Fort Jackson 5499 DPW N/A EMS/Fire Department Cummins GTA855C1 25273798 Elliot Power Systems 180RN BX01J193 Natural Gas 180 293 Nov-01 Vertical None N/A In addition to regular maintenance, the following services need to occur:

a. Oil and filter every 500 hours or annually

b. Inspect spark plugs every 1000 hours or annually. Change as needed

c. Inspect all hoses and belts every 500 hours or annually. Change as needed.

d. Document maintenance and include meter reading at the time of maintenance. Submit documentation to Fort Jackson 5615 DPW Behind building, inside fence NEC Cummins QSM11-G4NR3 2003245 Cummins DQHAB-8086897 J110256725 Diesel 300 402 Sep-11 Vertical AST 600 In addition to regular maintenance, the following services need to occur:

a. Oil and filter every 500 hours or annually

b. Inspect air cleaner every 1000 hours or annually. Change as needed

c. Inspect all hoses and belts every 500 hours or annually. Change as needed.

d. Document maintenance and include meter reading at the time of maintenance. Submit documentation to Fort Jackson 12020 DPW N/A NEC Cummins Unknown Unknown Cummins DSFAE-7295845 F110221739 Diesel 80 107 Jun-11 Vertical AST Unknown In addition to regular maintenance, the following services need to occur:

a. Oil and filter every 500 hours or annually

b. Inspect air cleaner every 1000 hours or annually. Change as needed

c. Inspect all hoses and belts every 500 hours or annually. Change as needed.

d. Document maintenance and include meter reading at the time of maintenance. Submit documentation to Fort Jackson JRR DPW Johnson Rifle Road NEC Unknown Unknown Generac 14861230100 2118091 Diesel 50 67 Dec-16 Vertical AST Unknown In addition to regular maintenance, the following services need to occur:

a. Oil and filter every 500 hours or annually

b. Inspect air cleaner every 1000 hours or annually. Change as needed

c. Inspect all hoses and belts every 500 hours or annually. Change as needed.

d. Document maintenance and include meter reading at the time of maintenance. Submit documentation to Fort Jackson 7533 DPW N/A Emergency Operations Center (EOC) MTU 6R1600G70S 16301001230 MTU/Marathon Electric 433PSL6216 MX159004 PH Diesel 275 369 2010 In addition to regular maintenance, the following services need to occur:

a. Oil and filter every 500 hours or annually

b. Inspect air cleaner every 1000 hours or annually. Change as needed

c. Inspect all hoses and belts every 500 hours or annually. Change as needed.

d. Document maintenance and include meter reading at the time of maintenance. Submit documentation to Fort Jackson

4500MACHRm. 1-112DHospitalWaukeshaL6670DSTU363969Kato Engineering1000-69336111188612Diesel1,0001,341~1982VerticalUST20,000Hospital Maintains
4500MACHRm. 1-112BHospitalGM Power12-645-E169-E1-1773Electric Machinery Manufacturing Co.BEMACII168199511Diesel1,0001,341~1969VerticalUST20,000Hospital Maintains
4500MACHOutside west of bldgHospitalMitsubishiS12H-Y2PTAW-131530KatolightD1000FRY4T235128142023-0907Diesel1,0001,528Jun-07VerticalAST3,400Hospital Maintains

USTs

FORT JACKSON UNDERGROUND STORAGE TANKS
USTsBldg NoNo.TypeCapacity (gal)Permit No.Services needed.
Gate 1 Shoppette24201Gasoline (Reg)12000184581. Regular maintenance and repair as needed.

2. Annual line and tank tightness testing.

3. Veeder Root leak detector tests

4. Overfill protection system tests.

5. All sensors inspected and checked.

Gate 1 Shoppette24202Gasoline (Reg)1200018458
Gate 1 Shoppette24203Gasoline (Prem)1200018458
Gate 1 Veeder Roort System 450 Plus
Gate 2 Shoppette41201Gasoline (Reg)12000130331. Regular maintenance and repair as needed.

2. Annual line and tank tightness testing.

3. Veeder Root leak detector tests

4. Overfill protection system tests.

5. All sensors inspected and checked.

Gate 2 Shoppette41202Gasoline (Reg)1200013033
Gate 2 Shoppette41203Gasoline (Reg)1200013033
Gate 2 Shoppette41204Gasoline (Prem)1200013033
Gate 2 Veeder Roort System 450 Plus
Moncrief Hospital4500Diesel2000016333Regular maintenance is performed by the hospital.

Need to perform cathodic protection testing in 2017.

Hospital Maintains
Energy Plant 122881No. 6 Fuel Oil50000N/AMay be removed
Energy Plant 122882No. 6 Fuel Oil50000N/AMay be removed
Energy Plant 122883No. 6 Fuel Oil50000N/AMay be removed
Energy Plant 122884No. 6 Fuel Oil50000N/AMay be removed
Energy Plant 243331No. 6 Fuel Oil50000N/AMay be removed
Energy Plant 243332No. 6 Fuel Oil50000N/AMay be removed
Energy Plant 243333No. 6 Fuel Oil50000N/AMay be removed
Energy Plant 243334No. 6 Fuel Oil50000N/AMay be removed
Energy Plant 243335No. 6 Fuel Oil50000N/AMay be removed
Energy Plant 243336No. 6 Fuel Oil50000N/AMay be removed
Energy Plant 243337No. 6 Fuel Oil50000N/AMay be removed
Energy Plant 243338No. 6 Fuel Oil50000N/AMay be removed

ASTs

FORT JACKSON ABOVEGROUND STORAGE TANKS
Bldg NoNo.TypeCapacity (gal)DescriptionNotes
4282Diesel3000NECNeeds painting, labeling and integrity testing.
4500Diesel500Hospital BasementMaintained by the hospital
4500Diesel500Hospital BasementMaintained by the hospital
K5520DieselAmmo Supply PointNeeds painting, labeling and integrity testing.
N7651Diesel1000Wanat RangeNeeds painting, labeling and integrity testing.

OWS

FORT JACKSON OIL WATER SEPERATORS
BuildingOrganizationSediment Trap/ Grit ChamberLocationTypeConfigurationConstruction MaterialAccessibility (Top Of Tank)OWS SizeHolding capacityAlarmEffluent Discharge To:Recommend Cleaning FrequencyRecommend Cleaning
2604TACOM Motor PoolNOOWS west of buildingStandard GravityCylindricalSteelClosed w/ manholes (Bolted)**********YesSanitary sewer POTWAnnuallyOWS
2607DPW Bus WashYESOWS located immediately west of bus wash rack building. (location also has Grit Chamber located west of bus wash)Coalescing Standard Gravity-Parallel plates/ Corrugated PlatesCylindricalSteelClosed w/ manholes (Bolted)350 gallons140 gallonsYesSanitary sewer POTWAnnuallyOWS & Grit Chamber
2610DPW/ LRC maintenance ComplexNOOWS located next to wash rackCoalescing Standard Gravity-Parallel plates/ Corrugated PlatesCylindricalSteelClosed w/ manholes (Bolted)2000 gallons800 gallons (Integral)YesSanitary sewer POTWAnnuallyOWS
5669FMWR Autocraft ShopNOOWS at west end of buildingStandard GravityRectangularReinforce ConcreteClosed w/ manhole1000 gallons?NoSanitary sewer POTWAnnuallyOWS
5672Car WashNONot yet installedExpected to be Standard GravityExpected to be RectangularReinforced ConcreteClosed w/ manholeApprox 1500 gal?YesSanitary sewer POTWSemiannualOWS
9408AMC/ Tacom Motor PoolNOOWS south of wash rackCoalescing Standard Gravity-Parallel plates/ Corrugated PlatesCylindricalSteelClosed w/ manholes (Bolted)2000 gallons800 gallons (Integral)NoSanitary sewer POTWAnnuallyOWS

&"Arial Narrow,Bold"&24&K03+000 Fort Jackson OWS and Washrack Inventory

Washracks

FORT JACKSON WASH RACKS
BuildingOrganizationSediment Trap/ Grit ChamberLocationEffluent Discharge To:Recommend Cleaning FrequencyRecommend Cleaning
2607 (Bus wash)DPW Bus WashYESLocation also has Grit Chamber located west of bus wash)Sanitary sewer POTWAnnuallyWashrack
2610 (Washrack)DPW/ LRC maintenance ComplexYesOWS located next to wash rackSanitary sewer POTWAnnuallyWashrack
9408 (Washrack)AMC/ Tacom Motor PoolNOOWS south of wash rackSanitary sewer POTWAnnuallyWashrack

&"Arial Narrow,Bold"&24&K03+000 Fort Jackson OWS and Washrack Inventory

Crane

FJ Overhead Cranes
BuildingHoist ManufacturerCrane ManufacturerCrane TypeRated CapacitySpanLiftVoltage
2604YaleRJ MackUHSG7.5 ton54 ft20 ft460
2602YaleRJ MackUHSG7.5 ton54 ft20 ft460
2602R&MCleveland TamrailUHSG2 ton1815230
2603YaleRJ MackUHSG7.5 ton54 ft20 ft460
2603YaleRJ MackUHSG7.5 ton54 ft20 ft460