Record of testing a separation plant in accordance with DIN 1999-100
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
First examination
Recurrent examinitation
Revisal from:
Continuation of examinitation from:
Safety against outflow of light liquids from the separator plant or the manhole rings (camber/warning devices.)
Structural condition and tightness of the separator plant condition of the mounting parts and the electrical equipment (if existing), coalescence devices and automatic closing
Taring of the automatic closing device
Existence of an operation log
Existence and completeness of required admittances and documents
Actual wastewater amount (origin, quantity, contents, boundary conditions to avoid stable emulsions.)
Assessment, suitability and efficiency of the separator plant with respect to the actual wastewater amount
1.2 Executed activities/examinations
1.1 Type of examination
1. Details on the examination
Start of examination: 16.07.2014
Kind of Operation: Heli-Fueling Pads
For the orderer taking part in testing:
Business place: Katterbach
Building: Heli-Fueling Pads 1-4
Inspector: Klaus Gaede
End of examination: 18.07.2014
Location: Katterbach
Camp: Heliport Katterbach
Plant no.: Heli-Fueling Pads 1-4
Operator: USAG Ansbach
Company:
Street:
ZIP / City:
Customer: ECCO GmbH
Company: ECCO GmbH
Street: Richard-Wagner-Str. 1
ZIP / 67655City: Kaiserslautern
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
Heli-Fueling Pads 1-4
381Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
2. Details on the separator plant
Inflow depth [m]: 1,47
Shaft construction in accordance with norm
Remarks:
Business place: Katterbach
Building: Heli-Fueling Pads 1-4
2.1 Order, dimensioning of the separator plant
S
II
I
P
Parallel plantNominal size size of the entire plant: 40
State of: Plant exists in this state no more
Components:
Camp: Heliport Katterbach
Plant no: Heli-Fueling Pads 1-4
Location: Katterbach
Revisions history:
m
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
382Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Flowing scheme:
Legende / Caption:
S = Schlammfang / Sludge Trap II = Lfa Kl. II / Sep. Cl. II
I = Lfa Kl. I / Sep. Cl. I
P = Probenahmeschacht / Sampling Shaft
R = Revisionsschacht / Revision Shaft
C = Sammelschacht / Collecting Shaft
B = Speicherbecken, Rückhaltebecken, Stauraumkanal / Storage Basin, Storage Channel U = Umlenkschacht / Switching Shaft
WA = Wasseraufbereitung / Water Treatment
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
383Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Container:
Container type: Collecting shaft
Name: S1-S4
Manufacturer:
Type:
Year of construction:
NS:
Test certificate no:
SF volume [l]:
Oil storage volume [l]:
Coating: keine/none
Static water level over container level [m]:
0,00
Nominal diameter inflow:
Nominal diameter outflow:
Cover: 625 D
Automatic closing at inflow
Warning device with layer thickness control
Warning device with backwater signal
Automatic closing at the outflow
Remarks:
x x x x
Structure: stehender Zylinder/vertical cylinder
Oil tank volume [l]:
Shaft number:
i.D. / width of container [m]: 1,00
Container length [m]:
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
384Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Container type: Sludge trap
Name: S
Manufacturer: Dywidag
Type:
Year of construction:
NS:
Test certificate no:
SF volume [l]: 3700
Oil storage volume [l]:
Coating: Farbe/Paint
Static water level over container level [m]:
1,13
Nominal diameter inflow: 200
Nominal diameter outflow: 310
Cover: 625 D
Automatic closing at inflow
Warning device with layer thickness control
Warning device with backwater signal
Automatic closing at the outflow
Remarks:
x x x x
Structure: stehender Zylinder/vertical cylinder
Oil tank volume [l]:
Shaft number:
i.D. / width of container [m]: 2,04
Container length [m]:
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
385Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Container type: Petrol separator (Class-II-Separator)
Name: II
Manufacturer: Dywidag
Type:
Year of construction:
NS:
Test certificate no: PA-II 2729
SF volume [l]:
Oil storage volume [l]: 2475
Coating: Farbe/Paint
Static water level over container level [m]:
1,35
Nominal diameter inflow: 310
Nominal diameter outflow: 320
Cover: 625 D
Automatic closing at inflow
Warning device with layer thickness control
Warning device with backwater signal
Automatic closing at the outflow
Remarks:
x x x x
Structure: rechteck/rectangle
Oil tank volume [l]:
Shaft number:
i.D. / width of container [m]: 1,50
Container length [m]: 6,07
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
386Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
S
S
S
II
II
II
II
I
I
I
I
Separate sampling shaft:
Sample taking possibility by:
2.2 Equipment of the separator plant
Automatic closing at the outflow:
Automatic closing at the outflow:
Warning system with layer thickness control:
Warning device with backwater signal:
Sampling, further equipment:Sampling, further equipment:Sampling, further equipment:Sampling, further equipment:
Automatic closing, warning devices:Automatic closing, warning devices:Automatic closing, warning devices:Automatic closing, warning devices:
Container type: Sampling shaft
Name: P
Manufacturer:
Type:
Year of construction:
NS:
Test certificate no:
SF volume [l]:
Oil storage volume [l]:
Coating: keine/none
Static water level over container level [m]:
0,00
Nominal diameter inflow: 300
Nominal diameter outflow: 300
Cover: 625 D
Automatic closing at inflow
Warning device with layer thickness control
Warning device with backwater signal
Automatic closing at the outflow
Remarks:
x x x x
Structure: stehender Zylinder/vertical cylinder
Oil tank volume [l]:
Shaft number:
i.D. / width of container [m]: 1,00
Container length [m]:
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
387Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Further equipment:
Drain delimiter present Drain delimiter sufficient
Remarks on equipment:
Transmission to ZLT installed
Transmission to ZLT functioning
Connection to central control station (ZLT)Connection to central control station (ZLT)Connection to central control station (ZLT)Connection to central control station (ZLT) potential equalization
2.3 Surface characteristics:
Type around separator:Type around separator:Type around separator:Type around separator:
Asphalt
Concrete
Green space
Gravel unsurfaced
Paving others:
Asphalt
Concrete
WHG sealed surface others:
Type work surface:Type work surface:Type work surface:Type work surface:
Connected to the separator
Not determinable if connected to the separator
2.4 Pipes:
Indication: Rohr/pipe 1-3; 8
Constructor: unbekannt/unknown
Type:
Construction year: unbekannt/unknown
Certificate: unbekannt/unknown
Nominal diameter: DN 150-300
Length:
Between following shafts:
mm
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
388Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Indication: Rohr/pipe 4-7; 9-10
Constructor: unbekannt/unknown
Type:
Construction year: unbekannt/unknown
Certificate: unbekannt/unknown
Nominal diameter: DN 150-300
Length:
Between following shafts:
mm
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
389Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875 kept in sludge trap
Light liquid separator class II (petrol separator) kept in
Light liquid separator class I (coalescence separator) kept in
Remark:
3. Camber
Not kept, however warning device existing
4. Deficiencies surface
Free of deficiencies
Deficiencies:
leaky joints in concrete area
Rips in the concrete
Cracks in asphalt
Others:
Surface condition around separator:Surface condition around separator:Surface condition around separator:Surface condition around separator:
Free of deficiencies
Deficiencies:
leaky joints in concrete area
Rips in the concrete
Cracks in asphalt
Others:
Surface condition work surface:Surface condition work surface:Surface condition work surface:Surface condition work surface:
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3810Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
5. Visual assessment
Container: Collecting shaft indication: S1-S4 yes no
N/A: not applicable / not determinable state of basin and case OK
Shaft construction OK
Non-corrosive
Inside coating/HDPE-liners OK mounting parts functioning float OK float identification with float guide OK
Warning device OK
Electrical facilities functioning, zone 0 coalescence device OK
Cover compliant to standards
N/A
Container: Sludge trap indication: S yes no
N/A: not applicable / not determinable state of basin and case OK
Shaft construction OK
Non-corrosive
Inside coating/HDPE-liners OK mounting parts functioning float OK float identification with float guide OK
Warning device OK
Electrical facilities functioning, zone 0 coalescence device OK
Cover compliant to standards
N/A
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3811Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Container: Petrol separator (Class-II-Separator) indication: II yes no
N/A: not applicable / not determinable state of basin and case OK
Shaft construction OK
Non-corrosive
Inside coating/HDPE-liners OK mounting parts functioning float OK float identification with float guide OK
Warning device OK
Electrical facilities functioning, zone 0 coalescence device OK
Cover compliant to standards
N/A
Container: Sampling shaft indication: P yes no
N/A: not applicable / not determinable state of basin and case OK
Shaft construction OK
Non-corrosive
Inside coating/HDPE-liners OK mounting parts functioning float OK float identification with float guide OK
Warning device OK
Electrical facilities functioning, zone 0 coalescence device OK
Cover compliant to standards
N/A
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3812Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
6. Leak test
Examining duration: mind. 30
Calculated test duration: 11,4 recorded surface: 0,28 most permitted water additon: 250 beginning of the stabilization time: 07:47 end of the stabilization time: 08:47 beginning of test: 08:49 end of test: 09:01
Characteristic:
Testing instrument: Rohrtest ST04
LGA no: 0020220-01
Precision: 0,10 mm leak test passed
Stabilization time required
Remark:
Prüfobjekt: Sammelschacht S1 / test object: collection shaft S1
Checked containers min min m² ml leak test not passed
Parameter:Parameter:Parameter:Parameter:
moistened surface: 4,92 most permitted water additon
(special case):
m² ml testing course:testing course:testing course:testing course:
leak test type: Leak test 20 mm under top ground surface (routine test)
Name:Type:
S1-S4Collecting shaft
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3813Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Examining duration: mind. 30
Calculated test duration: 10,4 recorded surface: 0,28 most permitted water additon: 250 beginning of the stabilization time: 10:33 end of the stabilization time: 11:33 beginning of test: 11:35 end of test: 11:46
Characteristic:
Testing instrument: Rohrtest ST04
LGA no: 0020220-01
Precision: 0,10 mm leak test passed
Stabilization time required
Remark:
Prüfobjekt: Sammelschacht S2 / test object: collection shaft S2
Checked containers min min m² ml leak test not passed
Parameter:Parameter:Parameter:Parameter:
moistened surface: 4,92 most permitted water additon
(special case):
m² ml testing course:testing course:testing course:testing course:
leak test type: Leak test 20 mm under top ground surface (routine test)
Name:Type:
S1-S4Collecting shaft
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3814Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Calculated test duration: 9,6 recorded surface: 0,28 most permitted water additon: 250 beginning of the stabilization time: 11:25 end of the stabilization time: 12:25 beginning of test: 12:25 end of test: 12:36
Characteristic:
Testing instrument: Rohrtest ST04
LGA no: 0020220-01
Precision: 0,10 mm leak test passed
Stabilization time required
Remark:
Prüfobjekt: Sammelschacht S3 / test object: collection shaft S3
Checked containers min min m² ml leak test not passed
Parameter:Parameter:Parameter:Parameter:
moistened surface: 4,92 most permitted water additon
(special case):
m² ml testing course:testing course:testing course:testing course:
leak test type: Leak test 20 mm under top ground surface (routine test)
Name:Type:
S1-S4Collecting shaft
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3815Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Calculated test duration: 8,7 recorded surface: 0,28 most permitted water additon: 250 beginning of the stabilization time: 13:00 end of the stabilization time: 14:00 beginning of test: 14:00 end of test: 14:09
Characteristic:
Testing instrument: Rohrtest ST04
LGA no: 0020220-01
Precision: 0,10 mm leak test passed
Stabilization time required
Remark:
Prüfobjekt: Sammelschacht S4 / test object: collection shaft S4
Checked containers min min m² ml leak test not passed
Parameter:Parameter:Parameter:Parameter:
moistened surface: 6,49 most permitted water additon
(special case):
m² ml testing course:testing course:testing course:testing course:
leak test type: Leak test 20 mm under top ground surface (routine test)
Name:Type:
S1-S4Collecting shaft
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3816Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Calculated test duration: 30 recorded surface: 3,28 most permitted water additon: 250 beginning of the stabilization time: 09:05 end of the stabilization time: 09:58 beginning of test: 09:58 end of test: 10:28
Characteristic:
Testing instrument: Rohrtest ST04
LGA no: 0020220-01
Precision: 0,10 mm leak test passed
Stabilization time required
Remark:
Der Schlammfang wurde zusammen mit Rohr 1 geprüft! / The sludge trap was tested together with pipe 1!
Checked containers min min m² ml leak test not passed
Parameter:Parameter:Parameter:Parameter:
moistened surface: 13,68 most permitted water additon
(special case):
m² ml testing course:testing course:testing course:testing course:
leak test type: Leak test 10 cm above pipe peak (non-routine test)
Name:Type:
SSludge trap
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3817Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Calculated test duration: 30 recorded surface: 1,57 most permitted water additon: 250 beginning of the stabilization time: 09:05 end of the stabilization time: 10:05 beginning of test: 10:06 end of test: 10:36
Characteristic:
Testing instrument: Rohrtest ST04
LGA no: 0020220-01
Precision: 0,10 mm leak test passed
Stabilization time required
Remark:
Checked containers min min m² ml leak test not passed
Parameter:Parameter:Parameter:Parameter:
moistened surface: 44,01 most permitted water additon
(special case):
m² ml testing course:testing course:testing course:testing course:
leak test type: Leak test 10 cm above pipe peak (non-routine test)
Name:Type:
IIPetrol separator (Class-II-Separator)
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3818Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Own density of the float passed instruction and maintenance manual existing:
Maintenance contract existing:
Recurring examinations are carried out till now:
Responsible expert:
monthly internal control proper:
monthly internal control incomplete:
monthly internal control not available:
Waste disposal document was presented:
records concordant with maintenance log:
No disposal carried out yet:
7. Taring of the automatic closing device
8. Internal control, maintenance, operation log
9. Waste disposal documents
Own density of the float not passed
Own density of the float higher than the density of the decisive light liquid
Remark:
Own density of the float not determinable
Building:
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3819Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875 direct indirect
Discharge of wastewater (according to statement of operator)
10. Actual wastewater amount
Precipitation area: 3420
Wash rack is not roofed:
roofed area (driving rain):
Wash rack is roofed:
local rain yield factor: 240
Density of the authoritative light liquid: 0,85
Other:
QR QS
Drainage plan
Information from the operator
Stock-taking on-site no cleaning agents in use
List of the used cleaning agents is available
Rain water volume QR: 82,08 foul water volume QS: 0
Complication factor fx: 2
Density factor fd: 1 required nominal size: 82,08 available nominal size: 40
Wastewater discharge into separator
The aforementioned details derive from:
Used cleaning agents:
Determination of the nominal size:
Remark: Bemessung des Schlammfangs / calculation of sludge trap
Vmin = (100,200,300)* NS/fd
Vmin = 100*82,08 = 8.280 Liter
Volumen des vorhandenen Schlammfangs/ volume of existing sludge trap: = 3.700 Liter => vorhandenes Schlammfangvolumen nicht ausreichend / existing sludge trap volume is not sufficient
NG = (QR + fx * QS) * fd
Outflow valves DN 25:
Outflow valves DN 20:
Outflow valves DN 15:
Portal car washing installations/car wash plants:
High-pressure cleaners:
Required nominal size available? Passed
Not passed
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3820Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Information about the used detergents not available
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3821Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
11. Pipe deficiencies
Remark:
Indication: Rohr/pipe 1-3; 8
Nominal diameter: DN 150-300
NS 40 300--> Minimum-DN
Fouling and incrustation yes no
Visible damages of the pipe yes no
Skew of the pipe yes no
Rootage of the pipe yes no
Minimum nomimal diameter according to EN
858-1 given (depending on the nominal size) yes no
Remark:
Indication: Rohr/pipe 4-7; 9-10
Nominal diameter: DN 150-300
NS 40 300--> Minimum-DN
Fouling and incrustation yes no
Visible damages of the pipe yes no
Skew of the pipe yes no
Rootage of the pipe yes no
Minimum nomimal diameter according to EN
858-1 given (depending on the nominal size) yes no
Remark:
Rohr 2: siehe Prüfprotokoll Nr.140716150036.DAT / pipe 2: see leak test Nr.140716150036.DAT
Rohr 3: siehe Prüfprotokoll Nr. 140716152212.DAT / pipe 3: see leak test Nr. 140716152212.DAT
Rohr 8: siehe Prüfprotokoll Nr. 140716171018.DAT / pipe 8: see leak test Nr. 140716171018.DAT
Indication: Rohr/pipe 1-3; 8
Nominal diameter: DN 150-300
Test standar DIN EN 1610
Test result passed: yes no
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3822Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Remark:
Rohr 4: siehe Prüfprotokoll Nr.140717124654.DAT / pipe 4: see leak test Nr.140717124654.DAT
Rohr 5: siehe Prüfprotokoll Nr.140717131032.DAT / pipe 5: see leak test Nr.140717131032 .DAT
Rohr 6: siehe Prüfprotokoll Nr.140717142345.DAT / pipe 6: see leak test Nr.140717142345 .DAT
Rohr 7: siehe Prüfprotokoll Nr.140717145948.DAT / pipe 7: see leak test Nr.140717145948.DAT
Rohr 9: siehe Prüfprotokoll Nr.140717160829.DAT / pipe 9: see leak test Nr. 140717160829.DAT Rohr 10: siehe Prüfprotokoll Nr.140717164634.DAT / pipe 10: see leak test Nr. 140717164634.DAT
Indication: Rohr/pipe 4-7; 9-10
Nominal diameter: DN 150-300
Test standar DIN EN 1610
Test result passed: yes no
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3823Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Noticed deficiencies
706: Straßeneinlauf beschädigt (16 Stück) / Street inlet damaged
(16 pieces)
708: Entwässerungsrinne stark beschädigt / Trench drain major damaged 901: Verfugung der Abfüllfläche teilweise defekt / Joint sealant at filling area partially in bad condition
906: Beton / Beschichtung der Abfüllfläche stellenweise defekt / Concrete / coating at filling area partially in bad condition
908: Risse in der Betonfläche / Cracks in concrete area
[001]Austausch der Abscheideranlage gegen eine ausreichend dimensionierte Anlage. / Replace the oil/water separator system with one that is sufficiently dimensioned.
Nur Anschluss der Abfüllfläche an die Abscheideranlage => Abklemmen der
Rasenflächen und Direktanschluss an vorhandenen Regenwasserkanal /
Only the fuel filling area should be connected to the separator plant => Disconnection of the grass area and connect it directly to the existing storm sewer system.
Further operating not permitted
Further operating permitted after defects are eliminated plant not rehabilitable, an immediate exchange is recommended
Further operating permitted according to norm
Revisal required and resubmission to the inspector for confirmation of repair of deficiencies
Revisal not required
12. Summary
Further operating
Revisal:
next examination date according to norm:
Deficiencies:
Container: S1-S4
101 manhole rings leaky (in general)
303 inside coating not existing
701 pipe leaky / damaged
Container: S
001 nominal size not sufficient
101 manhole rings leaky (in general)
Container: II
001 nominal size not sufficient
101 manhole rings leaky (in general)
201 tank leaky (in general)
501 camber not adhered to
505 warning device leaky / open
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3824Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
13. Photos
Picture marking: Betriebsstätte / Operating Site
Picture marking: Betriebsstätte / Operating Site
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3825Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Picture marking: Heli-Fueling Pad
Picture marking: Straßeneinlauf / street inlet
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3826Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Picture marking: Straßeneinlauf undicht / street inlet leaky
Picture marking: Kastenrinne und Straßeneinlauf undicht / trench drain and street inlet leaky
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3827Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Picture marking: Entwässerungsrinne stark beschädigt / trench drain major damaged
Picture marking: Die Abscheideranlage entwässert auch Grünflächen. / The separator plant also drains grass areas.
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3828Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Picture marking: Sraßeneinlauf beschädigt /street inlet damaged
Picture marking: Sammelschacht S1 / collection manhole S1
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3829Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Picture marking: Sammelschacht S1: Schachtaufbau undicht (allgemein) / collection manhole S1: manhole rings leaky (in general)
Picture marking: Abscheideranlage / Separator Plant
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3830Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Picture marking: Schlammfang / sludge trap
Picture marking: Schlammfang: Schachtaufbau undicht (allgemein) / sludge trap:
manhole rings leaky (in general)
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3831Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Picture marking: Schlammfang: Einlaufteil / sludge trap: inlet
Picture marking: Schlammfang: Ablaufrohr DN 300 / sludge trap: outlet pipe DN 300
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3832Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Picture marking: Schlammfang: Innenbeschichtung teilweise abgeplatzt / sludge trap:
inside coating partially flaked off
Picture marking: Abscheider Klasse II. Typenschild / separator class II: type plate
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3833Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Picture marking: Abscheider Klasse II: Schachtaufbau undicht (allgemein) / separator class II: manhole rings leaky (in general)
Picture marking: Abscheider Klasse II: WA Einführung undicht/offen / separator class II:
warning device leaky/open
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3834Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Picture marking: Abscheider Klasse II: Einlaufteil DN 300 / separator class II: inlet DN 300
Picture marking: Abscheider Klasse II: Ablaufteil DN 300 / separator class II: outlet DN
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3835Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Picture marking: Abscheider Klasse II: Innenbeschichtung Blasenbildung / separator class II: inside coating bubbling
Picture marking: Abscheider Klasse II: Schwimmer / separator class II: float
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3836Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Picture marking: Abscheider Klasse II: Warnanlage intakt / separator class II: warning device o.k.
Picture marking: Probenahmeschacht / sampling shaft
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3837Page of
Peter Spieleder GmbH ● Gewerbepark II ● Lilienthalring 4 ● 67681 Sembach Tel.: 06303/983870 Fax: 06303/983875
Picture marking: Beton / Beschichtung der Abfüllfläche stellenweise defekt / Concrete / coating at filling area partially in bad condition
Picture marking: Verfugung der Abfüllfläche teilweise defekt / Joint sealant at filling area partially in bad condition
16.07.2014
Heli-Fueling Pads 1-4
Katterbach Heliport Katterbach
3838Page of