2021-09-03-JBLM-B9175-DWGS-REVISION 03-AMENDMENT 5.pdf

PDF 3 MB Posted

Attached to
“Repair Building 09175, Permanent Party UH” located on Joint Base Lewis-McChord, WA
Solicitation number
W912DW21B0008
Issued by

About this file

This solicitation is for repair and construction services for Building 09175, a permanent party unaccompanied housing (UH) facility located on Joint Base Lewis-McChord in Washington. The scope of work includes repairs and renovations to mechanical, electrical, plumbing and architectural systems. Drawings and specifications are provided to guide the work. The solicitation will result in an award of a firm-fixed-price contract for design and construction management services. The period of performance is 18 months from NTP. The Army Corps of Engineers Seattle District is the contracting agency.

View the file

Other files

File Type Posted
Abstract REV1 W912DW21B0008 Repair Building 9175 Permanent Party UH (SAM.gov).pdf PDF
Abstract W912DW21B0008 Repair Building 9175 Permanent Party UH (SAM.gov).pdf PDF
2021-09-09_JBLM-B9175-REV-04-DWGS_AMENDMENT 6.pdf PDF
Amendment 0006 W912DW21B0008 Repair Bldg 9175.pdf PDF
JBLM DPW Geospatial BIM CIM GIS and CAD Contract Requirements FY21_AMENDMENT 6.pdf PDF
2021-09-09-JBLM-B9175-REV-04-SPECS_AMENDMENT 6.pdf PDF
202109XX_CE0849 SOW_09175_AMENDMENT 6.pdf PDF
26 20 00-INTERIOR DISTRIBUTION SYSTEM-REVISION 03_AMENDMENT 5.pdf PDF
Amendment 0005 W912DW21B0008 Repair Bldg 9175.pdf PDF
20210831_Sign in Roster Repair Bldg 09175 Site Visit 2_AMENDMENT 5.pdf PDF
DDC Controls As-Builts_AMENDMENT 0004.pdf PDF
Amendment 0004 W912DW21B0008 Repair Bldg 9175.pdf PDF
2021-08-20-JBLM-B9175-DWGS-REVISION 01-AMENDMENT 2.pdf PDF
2021-08-20-JBLM-B9175-SPECS-REVISION 01-AMENDMENT 2.pdf PDF
Amendment 0003 W912DW21B0008 Repair Bldg 9175.pdf PDF
Amendment 0002 W912DW21B0008 Repair Bldg 9175.pdf PDF
12 32 00-Manufactured Wood Casework-EDITED-REV 02-ISSUED_AMENDMENT 0003.pdf PDF
20210824_9175 Meeting Attendance Roster_AMENDMENT 0003.pdf PDF
01 30 00-Administrative Requirements-EDITED-REV 02_AMENDMENT 0003.pdf PDF
9175-Submittal Register_AMENDMENT 2.xlsx XLSX spreadsheet
20210820_CE0849 SOW_09175_AMENDMENT 2.pdf PDF
W912DW21B0008 Repair Bldg 9175.pdf PDF
9175 Location Site Visit Map.pdf PDF
2021-08-11_B9175 Submittal Register.xlsx XLSX spreadsheet
2021-08-10-JBLM 9175-SPECS-RTA REV001.pdf PDF
20210810_CE0849 SOW_09175.pdf PDF
JA Brand Names or Equal_JBLM 9175-Interior Finishes_Redacted.pdf PDF
Bldg 9175-Final Environmental Report.pdf PDF
Amendment 0001 W912DW21B0008 Repair Bldg 9175.pdf PDF
Barracks Buildings 9175 and 9176 as builts.pdf PDF
2021-08-10_JBLM-B9175-RTA-DWGS-REV01_Part2.pdf PDF
2021-08-10_JBLM-B9175-RTA-DWGS-REV01_Part1.pdf PDF
Show all 32

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

INDEX OF DRAWINGS

NUMBERING SYSTEM:

XX100

DISCIPLINE:

C - CIVIL

L - LANDSCAPE

A - ARCHITECTURE

M - MECHANICAL

E - ELECTRICAL

P - PLUMBING

S - STRUCTURAL

K - FOOD SERVICE

DISCIPLINE MODIFIER

SHEET NUMBER WITHIN

SERIES

REFER TO AEC CAD

STANDARDS FOR PROPER

SHEET NUMBERING

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

GI002

S H

E E

T I

N D

E X

J O

IN

T

B A

S E

L E

W

IS

-M C

C H

O R

D W

A

S E

A T

T L E

D

IS

T R

IC

T

E

M

A R

G

IN

A L W

A Y

S O

U T

H B

L D

G

S E

A T

T L E

W

A

-2

Y A

E G

E R

A R

C H

IT

E

C T

U R

E

P

E N

R O

S E

L A

N E

S

U

IT

E

L E

N E

X A

K

S

K C

O U

G H

L

IN

K C

O U

G H

L

IN

C P

R Z

Y G

O D

A

M T

U R

N E

R

A

U G

U S

T

T B

D

T B

D

REVISION 03, AMENDMENT

R E

P A

IR

B

U

IL

D

IN

G

D E

S

IG

N C

O N

S T

R U

C T

IO

N

P K

G N

O C

E C

E

INDEX OF DRAWINGS

SHEET

NUMBER SHEET TITLE

RTA

SUBMITTAL

REVISION

REVISION

M-603 MECHANICAL SCHEDULES X

M-701 TEMPERATURE CONTROLS X

M-702 TEMPERATURE CONTROLS X

M-703 TEMPERATURE CONTROLS X

M-704 TEMPERATURE CONTROLS X X

M-705 TEMPERATURE CONTROLS X X

ELECTRICAL

E-001 ELECTRICAL GENERAL NOTES AND SYMBOLS X

ED101 ELECTRICAL OVERALL FIRST FLOOR DEMOLITION PLAN X

ED111 ELECTRICAL OVERALL SECOND FLOOR DEMOLITION PLAN X

ED121 ELECTRICAL OVERALL THIRD FLOOR DEMOLITION PLAN X

ED100 ELECTRICAL SITE DEMOLITION PLAN X

ES101 ELECTRICAL SITE PLAN X

EP102 ELECTRICAL FIRST FLOOR POWER PLAN - AREA B X

EP103 ELECTRICAL FIRST FLOOR POWER PLAN - AREAS A AND C X

EP112 ELECTRICAL SECOND FLOOR POWER PLAN - AREA B X

EP113 ELECTRICAL SECOND FLOOR POWER PLAN - AREAS A AND C X

EP122 ELECTRICAL THIRD FLOOR POWER PLAN - AREA B X

EP123 ELECTRICAL THIRD FLOOR POWER PLAN - AREAS A AND C X

EP401 ELECTRICAL ENLARGED POWER PLANS X

EP402 ELECTRICAL ENLARGED POWER PLANS X

EL102 ELECTRICAL FIRST FLOOR LIGHTING PLAN - AREA B X

EL103 ELECTRICAL FIRST FLOOR LIGHTING PLAN - AREAS A AND C X

EL112 ELECTRICAL SECOND FLOOR LIGHTING PLAN - AREA B X

EL113 ELECTRICAL SECOND FLOOR LIGHTING PLAN - AREAS A AND C X

EL122 ELECTRICAL THIRD FLOOR LIGHTING PLAN - AREA B X

EL123 ELECTRICAL THIRD FLOOR LIGHTING PLAN - AREAS A AND C X

EL401 ELECTRICAL ENLARGED LIGHTING PLANS X

E-501 ELECTRICAL DETAILS X

E-502 ELECTRICAL DETAILS X

E-601 ELECTRICAL ONE-LINE DIAGRAM - DEMOLITION X

E-602 ELECTRICAL ONE-LINE DIAGRAM - PROPOSED X

E-603 ELECTRICAL SCHEDULES X

E-604 ELECTRICAL SCHEDULES X

E-605 ELECTRICAL SCHEDULES X

E-606 ELECTRICAL SCHEDULES X

E-607 ELECTRICAL SCHEDULES X

E-608 ELECTRICAL SCHEDULES X

E-609 ELECTRICAL SCHEDULES X

TELECOMMUNICATIONS

T0-01 TELECOMMUNICATIONS GENERAL NOTES AND SYMBOLS X

T0-02 TELECOMMUNICATIONS SITE PLAN X

T0-03 TELECOMMUNICATIONS SITE PLAN X

T0-04 TELECOM MANHOLE BUTTERFLY DIAGRAMS X

T1-01 TELECOMMUNICATIONS FIRST FLOOR DEMO PLAN X

T1-02 TELECOMMUNICATIONS SECOND FLOOR DEMO PLAN X

T1-03 TELECOMMUNICATIONS THIRD FLOOR DEMO PLAN X

T1-11 TELECOMMUNICATIONS FIRST FLOOR DISTRIBUTION PLAN X

T1-12 TELECOMMUNICATIONS SECOND FLOOR DISTRIBUTION PLAN X

T1-13 TELECOMMUNICATIONS THIRD FLOOR DISTRIBUTION PLAN X

T1-21 TELECOMMUNICATIONS FIRST FLOOR PATHWAY PLAN X

T1-22 TELECOMMUNICATIONS SECOND FLOOR PATHWAY PLAN X

T1-23 TELECOMMUNICATIONS THIRD FLOOR PATHWAY PLAN X

T2-11 TELECOMMUNICATIONS FIRST FLOOR PLAN - AREA B X

T2-12 TELECOMMUNICATIONS FIRST FLOOR PLAN - AREAS A AND C X

T2-21 TELECOMMUNICATIONS SECOND FLOOR PLAN - AREA B X

T2-22 TELECOMMUNICATIONS SECOND FLOOR PLAN - AREAS A AND C X

T2-31 TELECOMMUNICATIONS THIRD FLOOR PLAN - AREA B X

T2-32 TELECOMMUNICATIONS THIRD FLOOR PLAN - AREAS A AND C X

T3-01 TELECOMMUNICATIONS ENLARGED FLOOR PLANS X

T3-02 NEC COMM 154 ELEVATIONS X

T3-03 NEC COMM 258 ELEVATIONS X

T3-04 NEC COMM 358 ELEVATIONS X

T3-05 NEC COMM 109 ELEVATIONS X

T3-06 NEC COMM 209 ELEVATIONS X

T3-07 NEC COMM 309 ELEVATIONS X

T4-01 TELECOMMUNICATIONS DETAILS X

T4-02 TELECOMMUNICATIONS DETAILS X

T4-03 TELECOMMUNICATIONS RISER DIAGRAMS X

INDEX OF DRAWINGS

SHEET

NUMBER SHEET TITLE

RTA

SUBMITTAL

REVISION

REVISION

AE606 DOOR HARDWARE X

AE607 WINDOW SCHEDULE AND TYPES X X

INTERIOR DESIGN

IN102 FIRST FLOOR AREA-B FINISH PLAN X

IN201 ENLARGED UNIT FINISH PLANS X

IN252 FIRST FLOOR SIGNAGE PLAN - AREA B X

IN253 FIRST FLOOR SIGNAGE PLAN - AREA A AND C X

IN262 SECOND FLOOR SIGNAGE PLAN - AREA B X

IN263 SECOND FLOOR SIGNAGE PLAN - AREA A AND C X

IN272 THIRD FLOOR SIGNAGE PLAN - AREA B X

IN273 THIRD FLOOR SIGNAGE PLAN - AREA A AND C X

IN401 INTERIOR ELEVATIONS X X

IN402 INTERIOR ELEVATIONS X

IN501 INTERIOR DETAILS X

IN531 SIGNAGE DETAILS X

IN532 SIGNAGE DETAILS X

IN601 INTERIOR FINISH LEGEND X

IN602 INTERIOR FINISH SCHEDULE X

FURNITURE

IF101 OVERALL FIRST FLOOR FURNITURE PLAN X

IF102 FIRST FLOOR AREA-B FURNITURE PLAN X

IF111 OVERALL SECOND FLOOR FURNITURE PLAN X

IF121 OVERALL THIRD FLOOR FURNITURE PLAN X

IF401 ENLARGED UNIT FURNITURE PLANS X

FIRE PROTECTION

FA001 FIRE ALARM NOTES AND DETAILS X

FX001 FIRE SPRINKLER NOTES AND DETAILS X

FD101 FIRE ALARM DEMOLITION PLAN - FIRST FLOOR X

FD111 FIRE ALARM DEMOLITION PLAN - SECOND FLOOR X

FD121 FIRE ALARM DEMOLITON PLAN - THIRD FLOOR X

FA101 FIRE ALARM PLAN FIRST FLOOR X

FA102 FIRE ALARM PLAN FIRST FLOOR - AREA B X

FA103 FIRE ALARM PLAN FIRST FLOOR - AREA A & C X

FA111 FIRE ALARM PLAN SECOND FLOOR X

FA112 FIRE ALARM PLAN SECOND FLOOR - AREA B X

FA113 FIRE ALARM PLAN SECOND FLOOR - AREA A & C X

FA121 FIRE ALARM PLAN THIRD FLOOR X

FA122 FIRE ALARM PLAN THIRD FLOOR - AREA B X

FA123 FIRE ALARM PLAN THIRD FLOOR - AREA A & C X

FX101 FIRE SPRINKLER PLAN FIRST FLOOR X

FX102 FIRE SPRINKLER PLAN FIRST FLOOR - AREA B X

FX103 FIRE SPRINKLER PLAN FIRST FLOOR - AREA A & C X

FX111 FIRE SPRINKLER PLAN SECOND FLOOR X

FX112 FIRE SPRINKLER PLAN SECOND FLOOR - AREA B X

FX113 FIRE SPRINKLER PLAN SECOND FLOOR - AREA A & C X

FX121 FIRE SPRINKLER PLAN THIRD FLOOR X

FX122 FIRE SPRINKLER PLAN THIRD FLOOR - AREA B X

FX123 FIRE SPRINKLER PLAN THIRD FLOOR - AREA A & C X

PLUMBING

M-001 MECHANICAL COVER SHEET X

PD101 PLUMBING DEMOLITION PLAN - FIRST FLOOR X

PD111 PLUMBING DEMOLITION PLAN - SECOND FLOOR X

PD121 PLUMBING DEMOLITION PLAN - THIRD FLOOR X

PP101 OVERALL FIRST FLOOR PLUMBING PLAN X

PP102 FIRST FLOOR AREA B PLUMBING PLAN X

PP103 FIRST FLOOR AREA A AND C PLUMBING PLAN X

PP111 OVERALL SECOND FLOOR PLUMBING PLAN X

PP112 SECOND FLOOR AREA B PLUMBING PLAN X

PP113 SECOND FLOOR AREA A AND C PLUMBING PLAN X

PP121 OVERALL THIRD FLOOR PLUMBING PLAN X

PP122 THIRD FLOOR AREA B PLUMBING PLAN X

PP123 THIRD FLOOR AREA A AND C PLUMBING PLAN X

P-401 ENLARGED PLUMBING PLANS X

P-402 ENLARGED PLUMBING PLANS X

P-403 ENLARGED PLUMBING PLANS - AREA B X

P-501 PLUMBING DETAILS X

P-502 PLUMBING DETAILS X

P-601 PLUMBING SCHEDULES X

P-901 PLUMBING ISOMETRICS X

P-902 PLUMBING ISOMETRICS X

P-903 PLUMBING ISOMETRICS X

P-904 PLUMBING ISOMETRICS X

MECHANICAL

MD101 OVERALL FIRST FLOOR HVAC DEMOLITION PLAN X

MD111 OVERALL SECOND FLOOR HVAC DEMOLITION PLAN X

MD121 OVERALL THIRD FLOOR HVAC DEMOLITION PLAN X

MD131 OVERALL ATTIC HVAC DEMOLITION PLAN X

MH101 OVERALL FIRST FLOOR HVAC PLAN X

MH102 FIRST FLOOR AREA B HVAC PLAN X

MH103 FIRST FLOOR AREA A AND C HVAC PLAN X

MH111 OVERALL SECOND FLOOR HVAC PLAN X

MH112 SECOND FLOOR AREA B HVAC PLAN X

MH113 SECOND FLOOR AREA A AND C HVAC PLAN X

MH121 OVERALL THIRD FLOOR HVAC PLAN X

MH122 THIRD FLOOR AREA B HVAC PLAN X

MH123 THIRD FLOOR AREA A AND C HVAC PLAN X

MH131 ATTIC PLAN AREA B X

MH132 ATTIC PLAN AREA A AND C X

MP101 OVERALL FIRST FLOOR HYDRONIC PLAN X

MP102 FIRST FLOOR AREA B HYDRONIC PLAN X X

MP103 FIRST FLOOR AREA A AND C HYDRONIC PLAN X X

MP111 OVERALL SECOND FLOOR HYDRONIC PLAN X

MP112 SECOND FLOOR AREA B HYDRONIC PLAN X X

MP113 SECOND FLOOR AREA A AND C HYDRONIC PLAN X X

MP121 THIRD FLOOR OVERALL HYDRONIC PLAN X

MP122 THIRD FLOOR AREA B HYDRONIC PLAN X X

MP123 THIRD FLOOR AREA A AND C HYDRONIC PLAN X X

M-501 MECHANICAL DETAILS X

M-502 MECHANICAL DETAILS X

M-503 MECHANICAL DETAILS X

M-505 MECHANICAL SCHEMATICS X

M-504 MECHANICAL DETAILS X

M-601 MECHANICAL SCHEDULES X

M-602 MECHANICAL SCHEDULES X

INDEX OF DRAWINGS

SHEET

NUMBER SHEET TITLE

RTA

SUBMITTAL

REVISION

REVISION

GENERAL

GI001 COVER SHEET X

GI002 SHEET INDEX X X X

GI003 GENERAL NOTES, ABBREVIATIONS X

GI004 LAYDOWN AREAS MAP X

GI005 JBLM TRUCK ROUTES MAP X

GI010 LIFE SAFETY NARRATIVE X

GI101 LIFE SAFETY PLAN FIRST FLOOR - OVERALL X

GI102 LIFE SAFETY PLAN FIRST FLOOR - AREA B X

GI103 LIFE SAFETY PLAN FIRST FLOOR - AREA A & C X

GI111 LIFE SAFETY PLAN SECOND FLOOR - OVERALL X

GI112 LIFE SAFETY PLAN SECOND FLOOR - AREA B X

GI113 LIFE SAFETY PLAN SECOND FLOOR - AREA A & C X

GI121 LIFE SAFETY PLAN THIRD FLOOR - OVERALL X

GI122 LIFE SAFETY PLAN THIRD FLOOR - AREA B X

GI123 LIFE SAFETY PLAN THIRD FLOOR - AREA A & C X

CIVIL

C-001 CIVIL GENERAL NOTES X

VF101 EXISTING CONDITIONS X

CD101 DEMOLITION PLAN X

CS101 SITE PLAN X

CS102 SITE ARCHITECTURAL PLAN X

CS103 AMENITIES LAYOUT PLAN X

CS104 AMENITIES GRADING PLAN X X

CS105 COURT LAYOUT PLAN X X

CS501 SITE DETAILS X X

CS502 AMENITY DETAILS X X

CS503 SHELTER DETAILS X

CS504 MISCELLANEOUS DETAILS X

CG101 GRADING AND DRAINAGE PLAN X

CG102 SIDEWALK GRADING PLAN X

CG501 STORM WATER DETAILS X

CU101 UTILITY PLAN X X

CU201 FIRE MAIN PLAN AND PROFILE X

CU202 SANITARY SEWER PLAN AND PROFILE X

CU501 SANITARY SEWER DETAILS X

CU502 SANITARY SEWER DETAILS X

CU503 WATERLINE DETAILS X

CU504 WATERLINE DETAILS X

LANDSCAPE

LP101 PLANTING PLAN X

LP102 PLANTING SCHEDULE X

STRUCTURAL

S-001 GENERAL NOTES X

S-002 GENERAL NOTES X

SB112 FIRST FLOOR PLAN AREA B X

SB113 FIRST FLOOR PLAN AREA A AND C X

SF112 SECOND/THIRD FLOOR AREA B PLAN X

SF113 SECOND/THIRD FLOOR AREA A AND C PLAN X

SF122 ATTIC PLAN AREA B X

SF123 ATTIC PLAN AREA A AND C X

SF132 ROOF PLAN AREA B X

SF133 ROOF PLAN AREA A AND C X

S-501 STRUCTURAL DETAILS X

S-502 STRUCTURAL DETAILS X

S-503 STRUCTURAL DETAILS X

ARCHITECTURAL

AD101 OVERALL FIRST FLOOR DEMOLITION PLAN X

AD102 FIRST FLOOR AREA-B DEMOLITION PLAN X

AD103 FIRST FLOOR AREA-A AND C DEMOLITION PLAN X

AD111 OVERALL SECOND FLOOR DEMOLITION PLAN X

AD112 SECOND FLOOR AREA-B DEMOLITION PLAN X

AD113 SECOND FLOOR AREA-A AND C DEMOLITION PLAN X

AD121 OVERALL THIRD FLOOR DEMOLITION PLAN X

AD122 THIRD FLOOR AREA-B DEMOLITION PLAN X

AD123 THIRD FLOOR AREA-A AND C DEMOLITION PLAN X

AD141 OVERALL ROOF DEMOLITION PLAN X

AE101 OVERALL FIRST FLOOR PLAN X

AE102 FIRST FLOOR AREA-B PLAN X

AE103 FIRST FLOOR AREA-A AND C PLAN X X

AE111 OVERALL SECOND FLOOR PLAN X

AE112 SECOND FLOOR AREA-B PLAN X X

AE113 SECOND FLOOR AREA-A AND C PLAN X

AE121 OVERALL THIRD FLOOR PLAN X

AE122 THIRD FLOOR AREA-B PLAN X X

AE123 THIRD FLOOR AREA-A AND C PLAN X

AE141 OVERALL ROOF PLAN X X

AE142 ROOF AREA-B PLAN X X

AE143 ROOF AREA-A AND C PLAN X X

AE151 OVERALL FIRST FLOOR REFLECTED CEILING PLAN X X

AE152 FIRST FLOOR AREA-B REFLECTED CEILING PLAN X X

AE161 OVERALL SECOND FLOOR REFLECTED CEILING PLAN X X

AE171 OVERALL THIRD FLOOR REFLECTED CEILING PLAN X X

AE201 AREA-A ELEVATIONS X

AE202 AREA-A ELEVATIONS X

AE203 AREA-B ELEVATIONS X

AE204 AREA-B ELEVATIONS X

AE205 AREA-C ELEVATIONS X

AE206 AREA-C ELEVATIONS X

AE301 BUILDING SECTIONS X

AE311 WALL SECTIONS X

AE401 LIVING UNIT ENLARGED FLOOR PLANS X X

AE402 ENLARGED FLOOR PLANS X X

AE403 ENLARGED UNIT CEILING PLANS X X

AE501 WALL AND PLAN DETAILS X

AE510 ROOF DETAILS X X

AE511 ROOF DETAILS X X

AE520 CEILING DETAILS X

AE530 DOOR DETAILS X

AE531 DOOR AND OPENING DETAILS X

AE540 WINDOW DETAILS X

AE601 PARTITION TYPES AND SCHEDULE X X

AE603 FIRST FLOOR DOOR SCHEDULE AND TYPES X

AE604 SECOND FLOOR DOOR SCHEDULE AND TYPES X

AE605 THIRD FLOOR DOOR SCHEDULE AND TYPES X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

TYPE A TYPE B TYPE C TYPE L1

4' - 0"

3' - 0"

2' - 8"

4' - 0"

1. EXISTING WINDOW ROWLOCK BRICK SILLS

WILL BE REPAIRED AND PROPER FLASHING

WILL INSTALLED AROUND PERIMETER OF

NEW WINDOWS.

2. SIZES PROVIDED ARE BASED OFF EXISTING

CONDITIONS DOCUMENTATION. FIELD VERIFY

OPENING SIZES.

3. WINDOW TYPES A, B, AND C SHALL RECEIVE

ROLLER SHADE RS-1.

WINDOW NOTES:

GL-1 = INSULATED LAMINATED GLAZING

3' - 6"

TYPE L2 TYPE L3

WINDOW TYPES A-D ARE SINGLE-HUNG WINDOWS.

TYPE D

4' - 0"

GL-1 GL-1 GL-1 GL-2

GL-2 = INSULATED LAMINATED GLAZING

1' - 0"

1' - 4"

1' - 6"

TYPE L4 TYPE L5

F.V.

15' - 7"

F .V

4' - 9 1/2"6' - 0"4' - 9 1/2"

GL-1 GL-1 GL-1 GL-1

D6

AE540

F6

AE540

SIM

SIM

C1

AE530

E1

AE530

A1

AE530

F .V

F.V.

15' - 7"

4' - 9 1/2"6' - 0"4' - 9 1/2"

GL-1 GL-1 GL-1 GL-1

D6

AE540

SIM

E1

AE530

F6

AE540

SIM

C1

AE530

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

AE607

W

IN

D O

W S

C H

E D

U L E

A N

D T

Y P

E S

J O

IN

T

B A

S E

L E

W

IS

-M C

C H

O R

D W

A

S E

A T

T L E

D

IS

T R

IC

T

E

M

A R

G

IN

A L W

A Y

S O

U T

H B

L D

G

S E

A T

T L E

W

A

-2

Y A

E G

E R

A R

C H

IT

E

C T

U R

E

P

E N

R O

S E

L A

N E

S

U

IT

E

L E

N E

X A

K

S

K C

O U

G H

L

IN

K C

O U

G H

L

IN

C P

R Z

Y G

O D

A

M T

U R

N E

R

A

U G

U S

T

T B

D

T B

D

REVISION 03, AMENDMENT

R E

P A

IR

B

U

IL

D

IN

G

D E

S

IG

N C

O N

S T

R U

C T

IO

N

P K

G N

O C

E C

E

WINDOW / LOUVER SCHEDULE

MARK

R.O. FRAME GLAZING DETAILS

REMARKSWIDTH HEIGHT FINISH MATERIAL TYPE THICKNESS HEAD JAMB SILL

A 4' - 0" 4' - 0" CLEAR ANODIZED ALUMINUM GL-1 1" F6/AE540 D6/AE540 A6/AE540

B 3' - 0" 4' - 0" CLEAR ANODIZED ALUMINUM GL-1 1" F6/AE540 D6/AE540 A6/AE540

C 2' - 8" 4' - 0" CLEAR ANODIZED ALUMINUM GL-1 1" F6/AE540 D6/AE540 A6/AE540

D 4' - 0" 4' - 0" CLEAR ANODIZED ALUMINUM GL-2 1" F6/AE540 D6/AE540 A6/AE540

L1 4' - 0" 4' - 0" CLEAR ANODIZED ALUMINUM F9AE540 D9/AE540 A9/AE540

L2 3' - 6" 1' - 4" CLEAR ANODIZED ALUMINUM F9AE540 D9/AE540 A9/AE540

L3 1' - 0" 1' - 0" CLEAR ANODIZED ALUMINUM F9AE540 D9/AE540 A9/AE540

L4 1' - 4" 1' - 4" CLEAR ANODIZED ALUMINUM F9AE540 D9/AE540 A9/AE540

L5 1' - 6" 1' - 6" CLEAR ANODIZED ALUMINUM F9AE540 D9/AE540 A9/AE540

1/4" = 1'-0"

WINDOW / LOUVER TYPES

1/4" = 1'-0"E7

EXTERIOR STOREFRONT WALL

1/4" = 1'-0"E9

INTERIOR STOREFRONT WALL

0 2' 4' 8'

SCALE: 1/4" = 1'

R

E V

IS

IO

N

A

M E

N D

M E

N T

/0

/2

3 3

09/02/2021

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

C1 C2 C3 C4

C3.5C2.5

A1

A2

A2.5

B1

B2

B4

B5

B3

HWSP-1&2

(STACKED)

ST-1

3/4"HWS/R &

3/4"CWS/R PIPING UP

TO SECOND FLOOR

1"HWS/R & 3/4"CWS/R PIPING

UP TO SECOND FLOOR

FCU-114

FCU-111

MSS-101CU-101

CU-201

CU-301

FCU-112

FCU-113

FCU-110

FCU-109

MSS-103

FCU-108

CU-203

CU-103

CU-303

FCU-115

FCU-116

MSS-102

FCU-117 FCU-118

A2 / MP103

A

/ M P

UH-106

TF-103

CU-302CU-202CU-102

TF-101

UH-104

TF-102

3/4"3/4"HWS

3/4"3/4"HWR

EF-103

1AGP-2

UH-105

SF-101

ET-2

3"HWS/R UP TO

SECOND FLOOR

B-2

B-1

3"3"HWR

3"3"HWS

3"3"HWS

AS-2

FIRE RISER / UTILITY

NEC COMM

SWITCHGEAR

UNIT

STAIR B

B1

UNIT

LOBBY

VESTIBULE

UNISEX

MAIL ACCESS ROOM

STORAGE

104B

UTILITY

104A

FIRE ALARM

MUDROOM

MUDROOM

152A

FCU-124

FIRE ALARM

153A

FOYER

ISOLATION VALVE (TYP)

3/4"3/4"HWR

3/4"3/4"HWS

WH-1

WH-2

EF-104

ELEC / COMMERCIAL TELECOMM

BP-1

BP-2

JAN

UNIT

CORRIDOR

UNIT

NEC COMM

STAIR C

C1

UNIT

MECH

MAINTAIN MANUFACTURER'S

RECOMMENDED SERVICE

CLEARANCE (TYPICAL).

3"3"HWR

1"1"HWR

1"1"HWS

3"3"HWS

EF-105

A

B

C

MECHANICAL GENERAL NOTES

1. FOR ALL NEW PENETRATIONS IN PRECAST

HOLLOW CORE SLABS, THE EXISTING

REINFORCING MUST BE LOCATED BY NON-

DESTRUCTIVE TESTING METHODS PRIOR

TO ANY CUTTING OR CORE DRILLING.

REFER TO DETAIL F4/S-501 FOR APPROVED

OPENING LOCATIONS.

2. REFERENCE MECHANICAL SCHEDULES

FOR RUN OUT SIZES TO HOT WATER AND

CHILLED WATER COILS.

3. REFERENCE TEMPERATURE CONTROL

DRAWINGS FOR LOCATIONS OF

OCCUPANCY SENSORS AND WINDOW

CONTACT SWITCHES.

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

P R

O F

E S

S

IO

N A

L E

N G

IN

E

E R

IN

G

C O

N S

U L T

A N

T S

P

.A

S

T O

P E

K A

W

IC

H

IT

A K

S

C P

R Z

Y G

O D

A

MP102

F

IR

S T

F L O

O R

A R

E A

B H

Y D

R O

N

IC

P L A

N

J O

IN

T

B A

S E

L E

W

IS

-M C

C H

O R

D W

A

S E

A T

T L E

D

IS

T R

IC

T

E

M

A R

G

IN

A L W

A Y

S O

U T

H B

L D

G

S E

A T

T L E

W

A

-2

D E

W

IN

G

M N

E W

M A

N

C W

A P

E L H

O R

S T

A

U G

U S

T

T B

D

T B

D

REVISION 03, AMENDMENT

R E

P A

IR

B

U

IL

D

IN

G

D E

S

IG

N C

O N

S T

R U

C T

IO

N

P K

G N

O C

E C

E

1/8" = 1'-0"A4

HYDRONICS PLAN - FIRST FLOOR AREA-B

PLAN NORTH

0 4' 8' 16'

SCALE: 1/8" = 1'

PLAN NOTES

1 3/4"HWS/R & 3/4"CWS/R UP TO SECOND

FLOOR. MAKE CONNECTIONS TO FAN

COIL UNIT PER DETAIL D5/M-503.

2 SIZE AND ROUTE REFRIGERANT PIPING

TO INDOOR UNIT PER MANUFACTURER'S

RECOMMENDATIONS. INSULATE PER

SPECIFICATIONS.

3 INSTALL EMERGENCY HVAC SHUTDOWN

PER DETAILS A4/M-501 AND F6/M-705.

4 ROUTE PIPING THROUGH WALL FROM

JANITOR 151 TO BACK OF FCU-113 TO

CONCEAL PIPING FROM VIEW IN

VESTIBULE 100.

5 EXISTING BUILDING SEISMIC JOINT,

REFERENCE STRUCTURAL. PROVIDE

FLEXIBLE JOINTS IN HVAC, PLUMBING

AND PIPING SYSTEMS PER

SPECIFICATIONS SECTION 13 48 00.00 10.

R

E V

IS

IO

N

A

M E

N D

M E

N T

/1

/2

R

E V

IS

IO

N

A

M E

N D

M E

N T

/3

/2

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T$

T

T

T

A3

A4

A5

A6

A7

A8

A2.5

A3.5

A4.5

A5.5

A6.5

A7.5

FCU-101

FCU-102

FCU-104

FCU-105

FCU-106

FCU-107

FCU-108

3/4"CWS/R & 3/4"HWS/R PIPING

UP TO SECOND FLOOR

UH-103

A4 / MP102

UH-102

UH-101

EF-101

3/4"HWS/R UP TO

SECOND FLOOR

CU-203

CU-303

JAN

ELEC / COMMERCIAL TELECOMM

UTILITY

CORRIDOR

STAIR A

A1

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

FCU-103

3/4"3/4"HWS

3/4"3/4"HWR

C4 C5 C6 C7 C8

C4.5 C5.5 C6.5 C7.5

CB

CC

CH-1

DECOUPLER

AGP-1

ET-1

3/4"HWS/R & 4"CWS/R PIPING

UP TO SECOND FLOOR

FCU-118

FCU-119

FCU-120

FCU-122

FCU-123

CWPP-1

CWSP-1

3/4"CWS/R & 3/4"HWS/R PIPING

UP TO SECOND FLOOR.

A

/ M P

EF-102

4"4"CWS

4"4"CWR

UH-107

4"4"CWR

4"4"CWS

1 1 1 1

UH-108

UH-109

AS-1

EXTEND CONCRETE

HOUSEKEEPING PAD MINIMUM 6"

BEYOND PERIMETER OF CHILLER.

REFERENCE DETAIL A4/S-502 FOR

CHILLER PAD REQUIREMENTS.

CORRIDOR

ROUTE CWS/R PIPING

ABOVE GRADE. INSULATE

PER SPECIFICATIONS AND

COVER WITH ALUMINUM

JACKET.

JAN

MECH

UNIT

STAIR D

D1

UNIT

UNIT

UNIT

UNIT

FCU-121

A

B

C

MECHANICAL GENERAL NOTES

1. FOR ALL NEW PENETRATIONS IN PRECAST

HOLLOW CORE SLABS, THE EXISTING

REINFORCING MUST BE LOCATED BY NON-

DESTRUCTIVE TESTING METHODS PRIOR

TO ANY CUTTING OR CORE DRILLING.

REFER TO DETAIL F4/S-501 FOR APPROVED

OPENING LOCATIONS.

2. REFERENCE MECHANICAL SCHEDULES

FOR RUN OUT SIZES TO HOT WATER AND

CHILLED WATER COILS.

3. REFERENCE TEMPERATURE CONTROL

DRAWINGS FOR LOCATIONS OF

OCCUPANCY SENSORS AND WINDOW

CONTACT SWITCHES.

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

P R

O F

E S

S

IO

N A

L E

N G

IN

E

E R

IN

G

C O

N S

U L T

A N

T S

P

.A

S

T O

P E

K A

W

IC

H

IT

A K

S

C P

R Z

Y G

O D

A

MP103

F

IR

S T

F L O

O R

A R

E A

A A

N D

C H

Y D

R O

N

IC

P L A

N

J O

IN

T

B A

S E

L E

W

IS

-M C

C H

O R

D W

A

S E

A T

T L E

D

IS

T R

IC

T

E

M

A R

G

IN

A L W

A Y

S O

U T

H B

L D

G

S E

A T

T L E

W

A

-2

D E

W

IN

G

M N

E W

M A

N

C W

A P

E L H

O R

S T

A

U G

U S

T

T B

D

T B

D

REVISION 03, AMENDMENT

R E

P A

IR

B

U

IL

D

IN

G

D E

S

IG

N C

O N

S T

R U

C T

IO

N

P K

G N

O C

E C

E

PLAN NORTH

0 4' 8' 16'

SCALE: 1/8" = 1'

1/8" = 1'-0"A2

HYDRONICS PLAN - FIRST FLOOR AREA-A

1/8" = 1'-0"A6

HYDRONICS PLAN - FIRST FLOOR AREA-C

PLAN NOTES

1 3/4"HWS/R & 3/4"CWS/R UP TO SECOND

FLOOR. MAKE CONNECTIONS TO FAN

COIL UNIT PER DETAIL D5/M-503.

2 INSTALL EMERGENCY HVAC SHUTDOWN

PER DETAILS A4/M-501 AND F6/M-705.

3 ROUTE CWS/CWR/HWS/HWR PIPING

THROUGH WALL FROM JANITOR'S

CLOSET THROUGH SIDE ACCESS OF FCU

TO CONCEAL PIPING FROM VIEW IN

CORRIDOR.

4 HEAT TRACE EXTERIOR PIPING FROM

CHILLER TO BUILDING.

R

E V

IS

IO

N

A

M E

N D

M E

N T

/3

/2

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T T

T

T

C1 C2 C3 C4

C3.5C2.5

A1

A2

A2.5

B1

B2

B4

B5

B3

STOR

UNIT

UNIT

UNIT

UTILITY

256C

UNIT

STAIR C

C2

NEC COMM

UNIT

UNIT

UNIT

JAN

256A

ELEC

NEC COMM

FIRE RISER

256D

UNIT

UNIT

STAIR B

B2

ELEC / COMMERCIAL TELECOMM

UTILITY

3/4"HWS/R & CWS/R PIPING

DOWN TO FIRST FLOOR

AND UP TO THIRD FLOOR

1"HWS/R & 3/4"CWS/R PIPING

DOWN TO FIRST FLOOR.

1"HWS/R & 3/4"CWS/R PIPING UP

TO THIRD FLOOR.

MSS-203

FCU-209

FCU-210

MSS-201

FCU-211

FCU-212

FCU-213

FCU-214

FCU-215 MSS-202

FCU-216

FCU-217

A

/ M P

A2 / MP113

TF-201

TF-202

TF-204

UH-207

UH-206

EF-203

UH-205

UH-203

TF-203

EF-204

1 1 1 1

4"CWS/R & 3/4"HWS/R

DOWN TO FIRST FLOOR

3"3"CWR

3"3"CWS

3"3"CWS

3"3"CWR

3/4"HWS/R & 3/4"CWS/R

UP TO THIRD FLOOR

3"HWS/R UP TO THIRD

FLOOR AND DOWN TO

FIRST FLOOR.

3"3"CWS

3"3"CWR

4"4"CWS

4"4"CWR

4"4"CWS

4"4"CWR

UTILITY

ISOLATION VALVES (TYP)

ISOLATION VALVES (TYP)

ISOLATION VALVES (TYP)

FIRE ALARM

256B

FCU-224

EF-205

3/4"3/4"HWS

3/4"3/4"HWR

3/4"3/4"HWR

3/4"3/4"HWS

A

B

C

MECHANICAL GENERAL NOTES

1. FOR ALL NEW PENETRATIONS IN PRECAST

HOLLOW CORE SLABS, THE EXISTING

REINFORCING MUST BE LOCATED BY NON-

DESTRUCTIVE TESTING METHODS PRIOR

TO ANY CUTTING OR CORE DRILLING.

REFER TO DETAIL F4/S-501 FOR APPROVED

OPENING LOCATIONS.

2. REFERENCE MECHANICAL SCHEDULES

FOR RUN OUT SIZES TO HOT WATER AND

CHILLED WATER COILS.

3. REFERENCE TEMPERATURE CONTROL

DRAWINGS FOR LOCATIONS OF

OCCUPANCY SENSORS AND WINDOW

CONTACT SWITCHES.

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

P R

O F

E S

S

IO

N A

L E

N G

IN

E

E R

IN

G

C O

N S

U L T

A N

T S

P

.A

S

T O

P E

K A

W

IC

H

IT

A K

S

C P

R Z

Y G

O D

A

MP112

S E

C O

N D

F L O

O R

A R

E A

B H

Y D

R O

N

IC

P L A

N

J O

IN

T

B A

S E

L E

W

IS

-M C

C H

O R

D W

A

S E

A T

T L E

D

IS

T R

IC

T

E

M

A R

G

IN

A L W

A Y

S O

U T

H B

L D

G

S E

A T

T L E

W

A

-2

D E

W

IN

G

M N

E W

M A

N

C W

A P

E L H

O R

S T

A

U G

U S

T

T B

D

T B

D

REVISION 03, AMENDMENT

R E

P A

IR

B

U

IL

D

IN

G

D E

S

IG

N C

O N

S T

R U

C T

IO

N

P K

G N

O C

E C

E

PLAN NORTH

0 4' 8' 16'

SCALE: 1/8" = 1'1/8" = 1'-0"A4

HYDRONICS PLAN - SECOND FLOOR AREA-B

PLAN NOTES

1 1"CWS & 1"CWR RUNOUT TO FAN COIL

UNIT RISERS. MAKE CONNECTIONS TO

FAN COIL UNIT PER DETAIL D5/M-503.

REFER TO M-601 FOR CONNECTION

SIZES TO FAN COIL UNITS. ROUTE

PIPING UP TO THIRD FLOOR AND DOWN

TO 1ST FLOOR.

2 SIZE AND ROUTE REFRIGERANT PIPING

TO INDOOR UNIT PER MANUFACTURER'S

RECOMMENDATIONS. INSULATE PER

SPECIFICATIONS.

3 3/4"HWS/R & 3/4"CWS/R TO FAN COIL

UNIT SHOWN. MAKE CONNECTIONS TO

FAN COIL UNIT PER DETAIL D5/M-503.

4 EXISTING BUILDING SEISMIC JOINT,

REFERENCE STRUCTURAL. PROVIDE

FLEXIBLE JOINTS IN HVAC, PLUMBING

AND PIPING SYSTEMS PER

SPECIFICATIONS SECTION 13 48 00.00 10.

5 MAKE CONNECTIONS TO FAN COIL UNIT

PER DETAIL D5/M-503. REFER TO M-601

FOR CONNECTION SIZES TO FAN COIL

UNITS. ROUTE 3/4"HWS/R PIPING UP TO

THIRD FLOOR AND DOWN TO 1ST FLOOR.

R

E V

IS

IO

N

A

M E

N D

M E

N T

/1

/2

R

E V

IS

IO

N

A

M E

N D

M E

N T

/3

/2

T

T

T

T

T

T

T

T

T

T

T

T T

T

T

TT

T

T

A3

A4

A5

A6

A7

A8

A2.5

A3.5

A4.5

A5.5

A6.5

A7.5

1-1/2"CWS/R UP TO DOAS-1

ON THIRD FLOOR. 3/4"HWS/R

TO FIRST FLOOR AND UP TO

THIRD FLOOR.

FCU-201

FCU-202

FCU-204

FCU-205

FCU-206

FCU-207

FCU-208

A4 / MP112

UH-201

UH-202

EF-201

3/4"HWS/R UP & DOWN

3/4"CWS/R UP & DOWN

2"2"CWS

2"2"CWR

2 1/2"2 1/2"CWS

2 1/2"2 1/2"CWR

3"3"CWS

3"3"CWR

2"2"CWR

DP

CHILLED WATER DIFFERENTIAL

PRESSURE SENSOR - REFER

TO SHEET M-702.

ISOLATION VALVE (TYP)

2"2"CWS

2 1/2"2 1/2"CWS

2 1/2"2 1/2"CWR

ISOLATION VALVE (TYP)

STAIR A

A2

JAN

UNIT

UNIT

UNIT

UNIT

UNIT

UTILITY

UNIT

UNIT

STAIR B

B2

FCU-203

C4 C5 C6 C7 C8

C4.5 C5.5 C6.5 C7.5

CB

CC

FCU-218

FCU-219

FCU-220

FCU-222

FCU-223

3/4"HWS/R & 4"CWS/R

DOWN TO FIRST FLOOR.

A

/ M P

UH-203

EF-202

UH-204

1 1

4"4"CWS

4"4"CWR

2"2"CWR

2"2"CWS

2"2"CWR

2"2"CWS

1 1/2"1 1/2"CWS

1 1/2"1 1/2"CWR

14"4"CWS

4"4"CWR

ISOLATION VALVE (TYP)

ISOLATION

VALVES (TYP)

UNIT

UTILITY

UNIT

UNIT

UNIT

221 STAIR D

D2

UNIT

JAN

3/4"CWS/R & 3/4"HWS UP TO THIRD FLOOR

3/4"CWS/R & 3/4"HWS DOWN TO FIRST FLOOR

FCU-22122

2"CWS/R & 3/4"HWS/R

UP TO THIRD FLOOR.

2"2"CWS

2"2"CWR

A

B

C

MECHANICAL GENERAL NOTES

1. FOR ALL NEW PENETRATIONS IN PRECAST

HOLLOW CORE SLABS, THE EXISTING

REINFORCING MUST BE LOCATED BY NON-

DESTRUCTIVE TESTING METHODS PRIOR

TO ANY CUTTING OR CORE DRILLING.

REFER TO DETAIL F4/S-501 FOR APPROVED

OPENING LOCATIONS.

2. REFERENCE MECHANICAL SCHEDULES

FOR RUN OUT SIZES TO HOT WATER AND

CHILLED WATER COILS.

3. REFERENCE TEMPERATURE CONTROL

DRAWINGS FOR LOCATIONS OF

OCCUPANCY SENSORS AND WINDOW

CONTACT SWITCHES.

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

P R

O F

E S

S

IO

N A

L E

N G

IN

E

E R

IN

G

C O

N S

U L T

A N

T S

P

.A

S

T O

P E

K A

W

IC

H

IT

A K

S

C P

R Z

Y G

O D

A

MP113

S E

C O

N D

F L O

O R

A R

E A

A A

N D

C H

Y D

R O

N

IC

P L A

N

J O

IN

T

B A

S E

L E

W

IS

-M C

C H

O R

D W

A

S E

A T

T L E

D

IS

T R

IC

T

E

M

A R

G

IN

A L W

A Y

S O

U T

H B

L D

G

S E

A T

T L E

W

A

-2

D E

W

IN

G

M N

E W

M A

N

C W

A P

E L H

O R

S T

A

U G

U S

T

T B

D

T B

D

REVISION 03, AMENDMENT

R E

P A

IR

B

U

IL

D

IN

G

D E

S

IG

N C

O N

S T

R U

C T

IO

N

P K

G N

O C

E C

E

PLAN NORTH

0 4' 8' 16'

SCALE: 1/8" = 1'

1/8" = 1'-0"A2

HYDRONICS PLAN - SECOND FLOOR AREA-A

1/8" = 1'-0"A6

HYDRONICS PLAN - SECOND FLOOR AREA-C

PLAN NOTES

1 1"CWS & 1"CWR RUNOUT TO FAN COIL

UNIT RISERS. MAKE CONNECTIONS TO

FAN COIL UNIT PER DETAIL D5/M-503.

REFER TO M-601 FOR CONNECTION

SIZES TO FAN COIL UNITS. ROUTE

PIPING UP TO THIRD FLOOR AND DOWN

TO 1ST FLOOR.

2 MAKE CONNECTIONS TO FAN COIL UNIT

PER DETAIL D5/M-503. REFER TO M-601

FOR CONNECTION SIZES TO FAN COIL

UNITS. ROUTE 3/4"HWS/R PIPING UP TO

THIRD FLOOR AND DOWN TO 1ST FLOOR.

3 ROUTE CWS/CWR/HWS/HWR PIPING

THROUGH WALL FROM JANITOR'S

CLOSET THROUGH SIDE ACCESS OF FCU

TO CONCEAL PIPING FROM VIEW IN

CORRIDOR.

R

E V

IS

IO

N

A

M E

N D

M E

N T

/1

/2

R

E V

IS

IO

N

A

M E

N D

M E

N T

/3

/2

T

T

T

T

T T

T

T

T

T

T

T

T

T

T

T

T

T

C1 C2 C3 C4

C3.5C2.5

A1

A2

A2.5

B1

B2

B4

B5

B3

MSS-303

FCU-309

FCU-310

MSS-301

FCU-311

FCU-312

FCU-313

FCU-314

FCU-315 MSS-302 FCU-316

FCU-317

A

/ M P

A2 / MP123

TF-301

TF-304

TF-302

UH-307

UH-306

EF-303

UH-305

TF-303

EF-304

STORAGE

UNIT

UNIT

UTILITY

356C

FIRE RISER

356D

NEC COMM

JAN

356A

ELEC

UNIT

UNIT

STAIR B

B3

ELEC / COMMERCIAL TELECOMM

UNIT

UNIT

ELEC

STAIR C

C3

NEC COMM

UNIT

UNIT

FCU-324

UNIT

EF-305

LADDER

3"HWS/R DOWN TO

SECOND FLOOR

1 1/4"1 1/4"HWR

3/4"3/4"HWR

1 1/4"1 1/4"HWS

3/4"3/4"HWS

2"2"HWR

2"2"HWS

2 1/2"2 1/2"HWR

2 1/2"2 1/2"HWS

2 1/2"2 1/2"HWR

2 1/2"2 1/2"HWS

2"2"HWR

2"2"HWS

2"2"HWR

2"2"HWS

2 1/2"2 1/2"HWS

2 1/2"2 1/2"HWR

2 1/2"2 1/2"HWS

2 1/2"2 1/2"HWR

2 1/2"2 1/2"HWS

2 1/2"2 1/2"HWR

3/4"3/4"HWR

3/4"3/4"HWS

A

B

C

MECHANICAL GENERAL NOTES

1. FOR ALL NEW PENETRATIONS IN PRECAST

HOLLOW CORE SLABS, THE EXISTING

REINFORCING MUST BE LOCATED BY NON-

DESTRUCTIVE TESTING METHODS PRIOR

TO ANY CUTTING OR CORE DRILLING.

REFER TO DETAIL F4/S-501 FOR APPROVED

OPENING LOCATIONS.

2. REFERENCE MECHANICAL SCHEDULES

FOR RUN OUT SIZES TO HOT WATER AND

CHILLED WATER COILS.

3. REFERENCE TEMPERATURE CONTROL

DRAWINGS FOR LOCATIONS OF

OCCUPANCY SENSORS AND WINDOW

CONTACT SWITCHES.

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

P R

O F

E S

S

IO

N A

L E

N G

IN

E

E R

IN

G

C O

N S

U L T

A N

T S

P

.A

S

T O

P E

K A

W

IC

H

IT

A K

S

C P

R Z

Y G

O D

A

MP122

T H

IR

D

F L O

O R

A R

E A

B H

Y D

R O

N

IC

P L A

N

J O

IN

T

B A

S E

L E

W

IS

-M C

C H

O R

D W

A

S E

A T

T L E

D

IS

T R

IC

T

E

M

A R

G

IN

A L W

A Y

S O

U T

H B

L D

G

S E

A T

T L E

W

A

-2

D E

W

IN

G

M N

E W

M A

N

C W

A P

E L H

O R

S T

A

U G

U S

T

T B

D

T B

D

REVISION 03, AMENDMENT

R E

P A

IR

B

U

IL

D

IN

G

D E

S

IG

N C

O N

S T

R U

C T

IO

N

P K

G N

O C

E C

E

PLAN NORTH

0 4' 8' 16'

SCALE: 1/8" = 1'1/8" = 1'-0"A4

HYDRONICS PLAN - THIRD FLOOR AREA-B

PLAN NOTES

1 1"HWS/R FROM MAINS IN HALLWAY.

MAKE CONNECTIONS TO FAN COIL UNIT

PER DETAIL D5/M-503. 3/4"HWS/R &

3/4"CWS/R DOWN TO SECOND FLOOR.

2 SIZE AND ROUTE REFRIGERANT PIPING

TO INDOOR UNIT PER MANUFACTURER'S

RECOMMENDATIONS. INSULATE PER

SPECIFICATIONS.

3 EXISTING BUILDING SEISMIC JOINT,

REFERENCE STRUCTURAL. PROVIDE

FLEXIBLE JOINTS IN HVAC, PLUMBING

AND PIPING SYSTEMS PER

SPECIFICATIONS SECTION 13 48 00.00 10.

4 1-1/4"HWS/R FROM MAINS IN HALLWAY.

MAKE CONNECTIONS TO FAN COIL UNIT

PER DETAIL D5/M-503. 1"HWS/R &

3/4"CWS/R DOWN TO SECOND FLOOR.

R

E V

IS

IO

N

A

M E

N D

M E

N T

/1

/2

R

E V

IS

IO

N

A

M E

N D

M E

N T

/3

/2

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

A3

A4

A5

A6

A7

A8

A2.5

A3.5

A4.5

A5.5

A6.5

A7.5

DOAS-1

1-1/2"CWS/R & 3/4"HWS/R

DOWN TO SECOND FLOOR

FCU-301

FCU-302

FCU-304

FCU-305

FCU-306

FCU-307

FCU-308

A4 / MP122

UH-301

EF-301

UH-302

3/4"HWS/R & 3/4"CWS/R

DOWN TO SECOND FLOOR

FCU-303

MAINTAIN MANUFACTURER'S

RECOMMENDED SERVICE

CLEARANCE (TYPICAL).

1 1/4"1 1/4"HWS

1 1/4"1 1/4"HWR

DP

HOT WATER DIFFERENTIAL

PRESSURE SENSOR -

REFER TO SHEET M-701.

1"1"HWR

1"1"HWS

1 1/4"1 1/4"HWS

1 1/4"1 1/4"HWR

1 1/2"1 1/2"HWS

1 1/2"1 1/2"HWR

2"2"HWS

2"2"HWR

2"2"HWR

2"2"HWS

1 1/2"1 1/2"HWR

1 1/2"1 1/2"HWS

C4 C5 C6 C7 C8

C4.5 C5.5 C6.5 C7.5

CB

CC

DOAS-2

FCU-318

FCU-319

FCU-320

FCU-322

FCU-323

2"CWS/R & 3/4"HWS/R

DOWN TO SECOND FLOOR

A

/ M P

EF-302 UH-303

UH-304

3/4"HWS/R & 3/4"CWS/R

DOWN TO SECOND FLOOR

FCU-321

MAINTAIN MANUFACTURER'S

RECOMMENDED SERVICE

CLEARANCE (TYPICAL).

1 1/4"1 1/4"HWR

1 1/4"1 1/4"HWS

2"2"HWR

2"2"HWS

1 1/2"1 1/2"HWR

1 1/2"1 1/2"HWS

1 1/4"1 1/4"HWR

1 1/4"1 1/4"HWS

1"1"HWR

1"1"HWS

1 1/4"1 1/4"HWR

1 1/4"1 1/4"HWS1 1/2"1 1/2"HWR

1 1/2"1 1/2"HWS

A

B

C

MECHANICAL GENERAL NOTES

1. FOR ALL NEW PENETRATIONS IN PRECAST

HOLLOW CORE SLABS, THE EXISTING

REINFORCING MUST BE LOCATED BY NON-

DESTRUCTIVE TESTING METHODS PRIOR

TO ANY CUTTING OR CORE DRILLING.

REFER TO DETAIL F4/S-501 FOR APPROVED

OPENING LOCATIONS.

2. REFERENCE MECHANICAL SCHEDULES

FOR RUN OUT SIZES TO HOT WATER AND

CHILLED WATER COILS.

3. REFERENCE TEMPERATURE CONTROL

DRAWINGS FOR LOCATIONS OF

OCCUPANCY SENSORS AND WINDOW

CONTACT SWITCHES.

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

P R

O F

E S

S

IO

N A

L E

N G

IN

E

E R

IN

G

C O

N S

U L T

A N

T S

P

.A

S

T O

P E

K A

W

IC

H

IT

A K

S

C P

R Z

Y G

O D

A

MP123

T H

IR

D

F L O

O R

A R

E A

A A

N D

C H

Y D

R O

N

IC

P L A

N

J O

IN

T

B A

S E

L E

W

IS

-M C

C H

O R

D W

A

S E

A T

T L E

D

IS

T R

IC

T

E

M

A R

G

IN

A L W

A Y

S O

U T

H B

L D

G

S E

A T

T L E

W

A

-2

D E

W

IN

G

M N

E W

M A

N

C W

A P

E L H

O R

S T

A

U G

U S

T

T B

D

T B

D

REVISION 03, AMENDMENT

R E

P A

IR

B

U

IL

D

IN

G

D E

S

IG

N C

O N

S T

R U

C T

IO

N

P K

G N

O C

E C

E

PLAN NORTH

0 4' 8' 16'

SCALE: 1/8" = 1'

1/8" = 1'-0"A2

HYDRONICS PLAN - THIRD FLOOR AREA-A

1/8" = 1'-0"A6

HYDRONICS PLAN - THIRD FLOOR AREA-C

PLAN NOTES

1 1"HWS/R FROM MAINS IN HALLWAY.

MAKE CONNECTIONS TO FAN COIL UNIT

PER DETAIL D5/M-503. 3/4"HWS/R &

3/4"CWS/R DOWN TO SECOND FLOOR.

2 ROUTE CWS/CWR/HWS/HWR PIPING

THROUGH WALL FROM JANITOR'S

CLOSET THROUGH SIDE ACCESS OF FCU

TO CONCEAL PIPING FROM VIEW IN

CORRIDOR.

R

E V

IS

IO

N

A

M E

N D

M E

N T

/1

/2

R

E V

IS

IO

N

A

M E

N D

M E

N T

/3

/2

M M

T

CT

M

CWR CWS HWS HWR

AO - HEATING VALVEAO - COOLING VALVE

BI - ZONE OVERRIDE

AI - ZONE TEMP HEATING

AI - ZONE TEMP COOLING

AI - ZONE SETPOINT ADJUST

DA

AI - DISCHARGE AIR TEMP

BI - FAN STATUS

BO - FAN START/STOP

CW HW

RUN CONDITIONS:

AN OCCUPANCY SENSOR SHALL BE LOCATED IN EACH SLEEPING SPACE AND ONE IN

THE LIVING SPACE. ALL OCCUPANCY SENSORS ARE TIED TO THE ASSOCIATED FAN

COIL UNIT THAT SERVES THE 1-BEDROOM OR 2-BEDROOM UNIT. FAN COIL UNIT SHALL

REMAIN IN OCCUPIED MODE WHEN AN OCCUPANT IS DETECTED. WHEN THE

OCCUPANCY SENSORS DO NOT SENSE ANYONE IN THE 1-BEDROOM OR 2-BEDROOM

UNIT AFTER 30 MINUTES, THE FAN COIL UNIT SHALL SETBACK TO UNOCCUPIED MODE.

WINDOW SWITCHES SHALL BE SURFACE MOUNTED WITH WIRING CONCEALED IN WALL

OR WITH SURFACE MOUTED RACEWAY IF IT CANNOT BE CONCEALED IN EXISTING

MASONRY WALL. WHEN A WINDOW IS OPENED THE ASSOCIATED FAN COIL UNIT

SUPPLY FAN SERVING THAT 1-BEDROOM OR 2 BEDROOM UNIT SHALL BE DISABLED.

ASSOCIATED FAN COIL UNIT HOT AND CHILLED WATER VALVES SHALL BE CLOSED.

ONCE WINDOW IS CLOSED, ASSOCIATED FAN COIL UNIT SUPPLY FAN, HOT WATER

VALVE AND CHILLED WATER VALVES SHALL BE ENABLED.

OCCUPIED MODE: THE UNIT SHALL MAINTAIN

A 78°F (ADJ.) COOLING SETPOINT

A 68°F (ADJ.) HEATING SETPOINT.

A 63ºF (ADJ.) HEATING SETPOINT DURING OVERNIGHT SLEEPING HOURS IN

SLEEPING ROOMS.

UNOCCUPIED MODE: THE UNIT SHALL MAINTAIN

A 85°F (ADJ.) COOLING SETPOINT.

A 55°F (ADJ.) HEATING SETPOINT.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE COOLING

SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.).

LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS LESS THAN THE HEATING

SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.).

ZONE SETPOINT ADJUST: THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE

TEMPERATURE HEATING AND COOLING SETPOINTS AT THE ZONE SENSOR.

BY 3 DEGREES PLUS OR MINUS (ADJ).

ZONE UNOCCUPIED OVERRIDE: A TIMED LOCAL OVERRIDE CONTROL SHALL ALLOW AN

OCCUPANT TO OVERRIDE THE SCHEDULE AND PLACE THE UNIT INTO AN OCCUPIED

MODE FOR AN ADJUSTABLE PERIOD OF TIME. AT THE EXPIRATION OF THIS TIME,

CONTROL OF THE UNIT SHALL AUTOMATICALLY RETURN TO THE SCHEDULE.

SUPPLY FAN: THE FAN SHALL CYCLE ON AND OFF AS REQUIRED WHEN THERE IS A

CALL FOR HEATING OR COOLING, UNLESS SHUTDOWN ON SAFETIES.

COOLING COIL VALVE: WHEN THERE IS A CALL FOR COOLING, THE COOLING COIL CONTROL

VALVE SHALL MODULATE TO MAINTAIN 55 DEG. F (ADJ.) DISCHARGE AIR TEMPERATURE.

THE COOLING SHALL BE ENABLED WHENEVER:

OUTSIDE AIR TEMPERATURE IS GREATER THAN 70°F (ADJ.).

OR THE ZONE TEMPERATURE IS ABOVE COOLING SETPOINT.

AND THE FAN IS ON.

HEATING COIL VALVE:

THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND MODULATE THE HEATING COIL

VALVE TO MAINTAIN ITS HEATING SETPOINT.

THE HEATING SHALL BE ENABLED WHENEVER:

OUTSIDE AIR TEMPERATURE IS LESS THAN 65°F (ADJ.).

OR THE ZONE TEMPERATURE IS BELOW HEATING SETPOINT.

AND THE FAN IS ON.

DISCHARGE AIR TEMPERATURE:

THE CONTROLLER SHALL MONITOR THE DISCHARGE AIR TEMPERATURE.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

HIGH DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS GREATER THAN 120°

F (ADJ.).

LOW DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS LESS THAN 40°F

(ADJ.).

FAN STATUS SHALL BE MONITORED VIA USE OF CT SWITCH.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

FAN RUNTIME EXCEEDED: FAN STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.).

TYPICAL FOR ALL

DUCTED FAN COIL UNITS

NOTE: 2-WAY VALVE ARRANGEMENT

SHOWN. REFER TO SCHEDULES FOR

2-WAY/3-WAY VALVE ARRANGEMENT

FOR EACH FCU.

PIR PASSIVE INFRARED

OCCUPANCY SENSOR (TYP)

WALL-MOUNTED SENSOR

LOCATED IN EACH SLEEPING

ROOM AND IN EACH LIVING

ROOM (TYP)

WINDOW SWITCH AT EACH

WINDOW IN EACH SLEEPING

ROOM AND IN EACH LIVING ROOM

DI - WINDOW STATUS

H

AI - ZONE HUMIDITY SENSOR

PROVIDE HUMIDITY SENSORS IN

THE FOLLOWING SUITES FOR

MONITORING PURPOSES ONLY:

UNIT 116, 121, 174, 175, 216, 221,

274, 275, 316, 321, 374, AND 375

T

DI ROOM TEMPERATURE

SENSING ONLY ROOM TEMPERATURE

SENSOR - LOCATE AT 48"AFF AT

LOCATIONS SHOWN ON DRAWINGS.

T

THERMOSTAT PROVIDED BY DUCTLESS

SPLIT SYSTEM MANUFACTURER.

DUCTLESS SPLIT SYSTEM

OUTDOOR UNIT (TYP)

DUCTLESS SPLIT SYSTEM

INDOOR UNIT (TYP)

DUCTLESS MINI-SPLIT SYSTEMS:

GENERAL:

EACH DUCTLESS MINI-SPLIT SYSTEM SHALL BE PROVIDED WITH ITS OWN

FACTORY CONTROLS AND SHALL OPERATE TO MAINTAIN SPACE TEMPERATURE.

ROOM TEMPERATURE SENSOR SHALL BE SENSING ONLY AND AN ALARM

SHALL BE GENERATED AT THE BTCS WORKSTATION IF THE TEMPERATURE

RISES MORE THAN 3 DEGREES F (ADJ) FROM SETPOINT.

TEMPERATURE

SETPOINT = 74 DEGREES F

CT

BO - COMPRESSOR START/STOP

BI - COMPRESSOR STATUS

COMPRESSOR

LOCATE SENSORS SIDE BY SIDE

UNIT HEATER & CABINET UNIT HEATERS:

GENERAL:

ON A CALL FOR HEAT, HOT WATER CONTROL VALVE SHALL

OPEN AND THE UNIT HEATER SUPPLY FAN SHALL CYCLE TO

MAINTAIN THE SPACE TEMPERATURE AT SETPOINT 55ºF(ADJ).

ROOM TEMPERATURE SHALL BE MONITORED AT THE BTCS. IF

ROOM TEMPERATURE FALLS BELOW SETPOINT (ADJ), AN

ALARM SHALL BE GENERATED AT THE BTCS WORKSTATION.

HWR

HWS

H

C

T

ROOM TEMPERATURE SENSOR -

LOCATE AT 48" AFF AT LOCATIONS

SHOWN ON DRAWINGS.

AI AI - ZONE TEMP HEATING

AI - ZONE SETPOINT ADJUST

AO HEATING VALVE

CT

BO - COMPRESSOR START/STOP

BI - COMPRESSOR STATUS

M

SUPPLY FAN

TEMPERATURE SENSORS AND OTHER CONTROL DEVICES NECESSARY FOR WATER HEATER OPERATION SHALL BE PROVIDED BY THE WATER HEATER MANUFACTURER. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL REQUIRED RELAYS, WIRING, AND CONTROL DEVICES NECESSARY FOR A FUNCTIONAL

SYSTEM. WATER HEATER CONTROL PANEL OR ON-BOARD CONTROLS SHALL HAVE LONWORKS

INTERFACE FOR MONITORING AT THE DDC SYSTEM. CONTROLS OF THE WATER HEATER SHALL BE SUCH THAT THE CONTROL PANEL AT ONE WATER HEATER IS ABLE TO ACT AS A MASTER CONTROLLER FOR

THE WATER HEATER SYSTEM AS A WHOLE.

IF "PARENT" WATER HEATER FAILS OR IS POWERED DOWN. "CHILD" WATER HEATER SHALL

AUTOMATICALLY SWITCH OVER TO "PARENT" MODE.

WATER HEATERS WH-1 & WH-2 SHALL MAINTAIN STORAGE TANK ST-1 TEMPERATURE OF 145 DEGREES F (ADJUSTABLE). WATER HEATER CONTROLS SHALL ENERGIZE THE WATER HEATER PUMP CONTACTS (DRY) WHEN THERE IS A CALL FOR HEAT. ONCE THE CALL FOR HEAT IS SATISFIED, THE PUMP WILL REMAIN ON FOR THE DEFINED PUMP OVERRUN TIME. WATER HEATER SHALL OPERATE SUBJECT TO ITS OWN INTERNAL SAFETIES AND CONTROLS. DOMESTIC HOT WATER RECIRCULATION PUMP (HWSP-1) TO

RUN CONTINUOUSLY.

ALARMS PROVIDED AT A MINIMUM:

HIGH HOT WATER LEAVING TMV TEMPERATURE: IF GREATER THAN 110 DEG F (ADJUSTABLE)

LOW HOT WATER LEAVING TMV TEMPERATURE: IF LOWER THAN 100 DEG F (ADJUSTABLE)

WATER HEATER FAILURE: COMMANDED ON BUT THE STATUS IS OFF.

PRIMARY PUMP FAILURE: COMMANDED ON BUT THE STATUS IS OFF.

DOMESTIC HOT WATER RECIRCULATION PUMP FAILURE: COMMANDED ON BUT THE STATUS IS OFF.

EMERGENCY POWER OFF: HARDWIRED EMERGENCY POWER OFF SWITCH LOCATED AT THE ENTRANCE OT THE MECHANICAL ROOM, UPON ACTIVATION, DISABLES THE BOILERS AND ANY OTHER GAS-FIRED

EQUIPMENT IN THE MECHANICAL ROOM. AN ALARM IS GENERATED AT THE BTCS CETNRAL

WORKSTATION. STATUS OF THE SHUTDOWN SHALL BE MONITORED THRU THE DDC SYSTEM.

DHWP-1

HWRC

TEMPERING VALVE (TMV-1) INSTALL

TMV-1 IN STRICT ACCORDANCE WITH

MFG RECOMMENDATIONS.

LH

HWRC

ET-3

VV

HOUSEKEEPING PAD

FINISH FLOOR

WHP-2

WHP-1

WH-1 WH-2

COLD WATER SERVICE

HW RECIRC FROM BUILDING

HW TO BUILDING

CW TO BUILDING

T

AI - TANK TEMPERATURE

T

AI - HOT WATER SUPPLY TO TMV - TEMPERATURE

T

AI - HOT WATER SUPPLY TO TMV - TEMPERATURE

T

AI - HOT WATER SUPPLY TO FROM

WATER HEATER - TEMPERATURE

T

AI - HOT WATER SUPPLY TO FROM

WATER HEATER WH-1 - TEMPERATURE

T

AI - HOT WATER SUPPLY TO FROM

WATER HEATER WH-2 - TEMPERATURE

M

M CT

BI - WHP-2-STATUS

CT

BI - WHP-1-STATUS

M CT

BI - DHWP-1-STATUS

T

AI - HWRC-TEMPERATURE

T

AI - HOT WATER SUPPLY TO TMV - TEMPERATURE

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

P R

O F

E S

S

IO

N A

L E

N G

IN

E

E R

IN

G

C O

N S

U L T

A N

T S

P

.A

S

T O

P E

K A

W

IC

H

IT

A K

S

C P

R Z

Y G

O D

A

M-704

T E

M P

E R

A T

U R

E C

O N

T R

O L S

J O

IN

T

B A

S E

L E

W

IS

-M C

C H

O R

D W

A

S E

A T

T L E

D

IS

T R

IC

T

E

M

A R

G

IN

A L W

A Y

S O

U T

H B

L D

G

S E

A T

T L E

W

A

-2

D E

W

IN

G

M N

E W

M A

N

C W

A P

E L H

O R

S T

A

U G

U S

T

T B

D

T B

D

REVISION 03, AMENDMENT

R E

P A

IR

B

U

IL

D

IN

G

D E

S

IG

N C

O N

S T

R U

C T

IO

N

P K

G N

O C

E C

E

NO SCALEE1

FAN COIL UNIT CONTROL SCHEMATIC

NO SCALEC1

TELECOM ROOM DUCTLESS SPLIT SYSTEM DETAIL

NO SCALEC6

HOT WATER UNIT HEATER CONTROL DETAIL

NO SCALEA3

DOMESTIC WATER HEATING SYSTEM

R

E V

IS

IO

N

A

M E

N D

M E

N T

/3

/2

CT

TO LOUVER OR ROOF HOOD

BI - FAN STATUS

EXHAUST FANS SEQUENCE OF OPERATION:

EXHAUST FANS SERVING MECHANICAL AND ELECTRICAL ROOMS:

EXHAUST FAN TO OPERATE CONTINUOUSLY WHEN ROOM TEMPERATURE

EXCEEDS 85ºF. ASSOCIATED OUTDOOR AIR INTAKE AND EXHAUST LOW-LEAK

MOTORIZED DAMPERS AT WALL LOUVERS SHALL OPEN UPON EXHAUST FAN

OPERATION. INTAKE AND EXHAUST DAMPERS SHALL CLOSE WHEN EXHAUST

FAN IS DE-ENERGIZED.

ALL EXHAUST FANS SHALL DE-ENERGIZED AND INTAKE AND EXHAUST LOW-

LEAK MOTORIZED DAMPERS SHALL CLOSE WHEN HVAC SHUTDOWN SWITCH IS

ACTIVATED.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

M

BO - FAN START/STOP

M

AO - LOW-LEAK MOTORIZED

EXHAUST DAMPER

EXHAUST AIR

M

TO SPACE

AO - LOW-LEAK MOTORIZED

INTAKE DAMPER

OUTSIDE AIR

T

BI - ZONE OVERRIDE

AI - ZONE TEMP HEATING

AI - ZONE TEMP COOLING

AI - ZONE SETPOINT ADJUST

EMERGENCY SHUT-DOWN SWITCH:

UPON ACTIVATION OF THE SWITCH, THE DEDICATED OUTDOOR

AIR UNIT SHALL SHUTDOWN AND THE LOW-LEAK DAMPERS AT

THE EXTERIOR LOUVERS SHALL CLOSE. FAN COIL UNITS SHALL

SHUTDOWN. DUCTLESS SPLIT SYSTEM INDOOR UNITS SHALL

CONTINUE TO OPERATE. UNIT HEATERS SHALL CONTINUE TO

OPERATE. ALL EXHAUST FANS SHALL SHUTDOWN AND THE

LOW-LEAK DAMPERS AT THE EXTERIOR LOUVERS OR ROOF

HOODS SHALL CLOSE.

BI - EMERGENCY SHUTDOWN SWITCH

WATER METER:

THE CONTROLLER SHALL MONITOR THE WATER METER FOR WATER CONSUMPTION ON A

CONTINUAL BASIS. THESE VALUES SHALL BE MADE AVAILABLE TO THE SYSTEM AT ALL TIMES.

WATER METER

BI - WATER FLOW RATE

NOTE: METERS SHALL BE

COMPATIBLE WITH BASEWIDE

UTILITY MONITORING SYSTEM.

SEE NOTES THIS PAGE FOR

ADDITIONAL REQUIREMENTS

GAS METER:

THE CONTROLLER SHALL MONITOR THE GAS METER FOR GAS CONSUMPTION ON A

CONTINUAL BASIS. THESE VALUES SHALL BE MADE AVAILABLE TO THE SYSTEM AT ALL TIMES.

BI - GAS FLOW RATE

GAS METER

NOTE: METERS SHALL BE

COMPATIBLE WITH BASEWIDE

UTILITY MONITORING SYSTEM.

SEE NOTES THIS PAGE FOR

ADDITIONAL REQUIREMENTS ELECTRIC METER:

THE CONTROLLER SHALL MONITOR THE ELECTRIC METER FOR ELECTRIC

CONSUMPTION, AND ELECTRIC DEMAND ON A CONTINUAL BASIS. THESE

VALUES SHALL BE MADE AVAILABLE TO THE SYSTEM AT ALL TIMES.

ELECTRIC METER

BI - REAL POWER (TOTAL)

BI - TOTAL KWH (TOTAL ENERGY)

BI - HISTORICAL PEAK DEMAND POWER

BI - DEMAND POWER

BI - RMS VOLTAGE FOR PHASE A

BI - RMS VOLTAGE FOR PHASE B

BI - RMS VOLTAGE FOR PHASE C

BI - RMS CURRENT FOR PHASE A

BI - RMS CURRENT FOR PHASE B

BI - RMS CURRENT FOR PHASE C

BI - AVERAGE LINE FREQUENCY

BI - AVERAGE POWER FACTOR

BI - PHASOR DIAGRAM

NOTE: METERS SHALL BE COMPATIBLE

WITH BASEWIDE UTILITY MONITORING

SYSTEM. SEE NOTES THIS PAGE FOR

ADDITIONAL REQUIREMENTS

WATER, GAS AND ELECTRICITY METERS SHALL MEET THE REQUIREMENTS OF THE AMP-MCX ARMY METERING PROGRAM SPECIFICATIONS FOR ADVANCED METERS JBLM SPECIFIC LOCATED IN THE PROJECT SPECIFICATIONS.

METERING DEVICES SHALL BE JBLM COMPATIBLE. REFERENCE THE APL AMP TESTED BUILDING LEVEL DEVICE

LIST FOR JBLM COMPATIBLE DEVICES.

ALL UTILITY METERING SHALL BE THROUGH JBLM EEDRS METERING SYSTEM SEPARATE FROM THE DDC SYSTEM.

UTILITY METER MONITORING NOTES:

CT

SUPPLY AIR TO

MECHANICAL ROOM

BI - FAN STATUS

SUPPLY FAN SEQUENCE OF OPERATION:

SUPPLY FAN SERVING MECHANICAL:

SUPPLY FAN TO OPERATE CONTINUOUSLY WHEN ROOM TEMPERATURE

EXCEEDS 85ºF. ASSOCIATED OUTDOOR AIR INTAKE AND EXHAUST LOW-LEAK

MOTORIZED DAMPERS AT WALL LOUVERS SHALL OPEN UPON SUPPLY FAN

OPERATION. INTAKE AND EXHAUST DAMPERS SHALL CLOSE WHEN SUPPLY FAN

IS DE-ENERGIZED.

SUPPLY FAN SHALL DE-ENERGIZED AND INTAKE AND EXHAUST LOW-LEAK

MOTORIZED DAMPERS SHALL CLOSE WHEN HVAC SHUTDOWN SWITCH IS

ACTIVATED.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

M

BO - FAN START/STOP

INTAKE AIR

FROM WALL

LOUVER

M

TO WALL LOUVER

AO - LOW-LEAK MOTORIZED

EXHAUST DAMPER

EXHAUST AIR

T

BI - ZONE OVERRIDE

AI - ZONE TEMP HEATING

AI - ZONE TEMP COOLING

AI - ZONE SETPOINT ADJUST

M

AO - LOW-LEAK MOTORIZED

EXHAUST DAMPER

CT

TO ROOM

BI - FAN STATUS

TRANSFER FAN SEQUENCE OF OPERATION:

TRANSFER FANS:

TRANSFER FANS TO OPERATE CONTINUOUSLY.

ALL TRANSFER FANS SHALL BE DE-ENERGIZED AND ANY

ASSOCIATED MOTORIZED DAMPERS SHALL CLOSE WHEN

HVAC SHUTDOWN SWITCH IS ACTIVATED.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

M

BO - FAN START/STOP

TRANSFER

AIR

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

P R

O F

E S

S

IO

N A

L E

N G

IN

E

E R

IN

G

C O

N S

U L T

A N

T S

P

.A

S

T O

P E

K A

W

IC

H

IT

A K

S

C P

R Z

Y G

O D

A

M-705

T E

M P

E R

A T

U R

E C

O N

T R

O L S

J O

IN

T

B A

S E

L E

W

IS

-M C

C H

O R

D W

A

S E

A T

T L E

D

IS

T R

IC

T

E

M

A R

G

IN

A L W

A Y

S O

U T

H B

L D

G

S E

A T

T L E

W

A

-2

D E

W

IN

G

M N

E W

M A

N

C W

A P

E L H

O R

S T

A

U G

U S

T

T B

D

T B

D

REVISION 03, AMENDMENT

R E

P A

IR

B

U

IL

D

IN

G

D E

S

IG

N C

O N

S T

R U

C T

IO

N

P K

G N

O C

E C

E

NO SCALEE1

EXHAUST FAN CONTROL SCHEMATIC

NO SCALEE7

HVAC SHUTDOWN CONTROL

NO SCALEA1

WATER METER CONTROL

NO SCALEA4

GAS METER CONTROL

NO SCALEA7

ELECTRIC METER CONTROL

R

E V

IS

IO

N

A

M E

N D

M E

N T

/3

/2

NO SCALEC1

SUPPLY FAN SF-1 CONTROL SCHEMATIC

NO SCALED7

TRANSFER FAN CONTROL SCHEMATIC

2 2

GI002 - SHEET INDEX
AE607 - WINDOW SCHEDULE AND TYPES
MP102 - FIRST FLOOR AREA B HYDRONIC PLAN
MP103 - FIRST FLOOR AREA A AND C HYDRONIC PLAN
MP112 - SECOND FLOOR AREA B HYDRONIC PLAN
MP113 - SECOND FLOOR AREA A AND C HYDRONIC PLAN
MP122 - THIRD FLOOR AREA B HYDRONIC PLAN
MP123 - THIRD FLOOR AREA A AND C HYDRONIC PLAN
M-704 - TEMPERATURE CONTROLS
M-705 - TEMPERATURE CONTROLS