This document provides details on a federal solicitation opportunity from the Department of the Army Corps of Engineers Engineering District Seattle. Solicitation number W912DW21B0008 is seeking offers to repair Building 09175, a permanent party unaccompanied housing (UH) facility located on Joint Base Lewis-McChord in Washington. The solicitation involves repairing the existing UH building to address deficiencies. The Department of the Army Corps of Engineers Engineering District Seattle is the contracting agency managing this project. No other information is provided on response dates, pricing terms, set asides, or incumbent contractors.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FINAL
ENVIRONMENTAL INVESTIGATION SERVICES REPORT
BUILDING 9175
JOINT BASE LEWIS-MCCHORD, WASHINGTON
Prepared For:
YAEGER ARCHITECTURE, INC.
7780 West 119th Street
Overland Park, KS 66213
Prepared by:
TEHAMA, LLC
1600 Genessee Street, Suite 754
Kansas City, MO 64102
PROJECT NO. F0119.00
December 2020
TABLE OF CONTENTS
SECTION I ASBESTOS CONTAINING MATERIALS (ACM)
1.0 INTRODUCTION
2.0 FIELD INVESTIGATION PROCEDURES AND SAMPLE ANALYSIS METHODS
3.0 INSPECTION SCOPE AND MATERIAL ASSESSMENT
4.0 INSPECTION RESULTS
5.0 CONDITION AND FRIABLITY ASSESSMENT
6.0 AREAS NOT ACCESSIBLE
7.0 POLYCHLORINATED BIPHENYLS
8.0 UNIVERSAL WASTES
9.0 CONCLUSIONS AND RECOMMENDATIONS
10.0 LIMITATIONS, EXCEPTIONS AND ASSUMPTIONS
11.0 REPORT CERTIFICATIONS
SECTION II LEAD-BASED PAINT (LBP)
1.0 INTRODUCTION
2.0 FIELD SURVEY PROCEDURES AND SAMPLE ANALYSIS METHODS
3.0 SUMMARY OF INSPECTION
4.0 INSPECTION RESULTS
5.0 CONCLUSIONS AND RECOMMENDATIONS
6.0 LIMITATIONS, EXCEPTIONS AND ASSUMPTIONS
7.0 REPORT CERTIFICATIONS
APPENDICES
APPENDIX A TEHAMA PERSONNEL CERTIFICATIONS
APPENDIX B LABORATORY CERTIFICATIONS
APPENDIX C FIGURES
APPENDIX D SAMPLE CHAIN OF CUSTODIES, LABORATORY RESULTS & XRF RESULTS
APPENDIX E PHOTOGRAPHS
SECTION I
ASBESTOS CONTAINING MATERIALS (ACM)
Environmental Investigation Services Report for Building 9175, JBLM, Washington
1.0 INTRODUCTION
Tehama, LLC (Tehama) has performed a full interior and exterior inspection for the presence or absence of Asbestos- Containing Materials (ACM) for Building 9175 at Joint Base Lewis-McChord (JBLM), Washington. The inspection was conducted at the request of Yaeger Architecture, Inc. (Yaeger) for use in their design-build package for renovation of Building 9175. The scope of work for this project was based on Yaeger’s scope of work, drawings and emails, and Tehama’s proposal, dated August 2, 2019. The intent of this inspection was to locate, identify and quantify ACM that will be impacted during the upcoming renovation project.
Building 9175 was constructed in the late 1980’s and was used as a dormitory until it was abandoned in the mid-2010’s.
The building is comprised of 3 floors with 3 different building sections per floor. Building sections A and C are the main dormitory areas, while building section B had the lobby/day rooms, storage, and a few additional dorm rooms. Although the building no longer serves as a dormitory, furniture and a few personal items were left behind in each room throughout the building.
Anne Eiseman and Megan Perez-Utter, certified Environmental Protection Agency (EPA) Asbestos Hazard Emergency Response Act (AHERA) Asbestos Inspectors with Tehama, performed the inspection on October 21st-24th, 2019.
Certifications for inspectors are located in Appendix A.
2.0 FIELD INVESTIGATION PROCEDURES AND SAMPLE ANALYSIS METHODS
Guidelines used for the inspection were established by the EPA in the “Guidance for Controlling Asbestos Containing Materials in Buildings”, 40 CFR 763, 29 CFR 1926.1101, 40 CFR 61, 29 CFR 1910.134, AHERA, National Emission Standards for Hazardous Air Pollutants (NESHAP) regulations, and where applicable Washington Administrative Code (WAC 296-62-077 through 296-62-07755).
Field information was organized in accordance with the AHERA methodology of homogenous area (HA). An HA contains material that is uniform in texture and color and appears to be identical in every other respect. Building materials that were installed at different times or that do not appear to be similar in any other way are considered separate homogenous materials/areas. Bulk sampling for each HA was completed and specific sampling locations were chosen at random.
All bulk samples were sent to QuanTEM Laboratories and analyzed by Polarized Light Microscopy (PLM) coupled with dispersion staining techniques as outlined in the EPA 600/R-93/116 Method. The laboratory provides the approximate percentage of asbestos fibers in the sample and also identifies the crystal form of the asbestos. The EPA considers materials to be ACM if they contain greater than one-percent (1%) asbestos fibers. Occupational Safety and Health Administration (OSHA) regulations cover materials containing asbestos in any concentration.
The EPA considers the following materials to be non-suspect ACM, and consequently, they were not sampled:
• Glass • Fiberglass
• Metal • Rubber
• Concrete
• Brick
Tehama subcontracted laboratory analysis procedures to QuanTEM Laboratories located at 2033 Heritage Park Drive, Oklahoma City, Oklahoma 73120. The laboratory maintains accreditation from the following agencies:
• National Voluntary Laboratory Accreditation Program (Lab Code 101959-0)
• American Industrial Hygiene Association Accredited Laboratory (Lab No. 101352)
Laboratory certifications are presented in Appendix B of this report.
3.0 INSPECTION SCOPE AND MATERIAL ASSESSMENT
This survey was conducted to determine whether asbestos is present in interior and exterior areas of the building, in preparation for building renovation activities. The sampler’s discretion was used for determining the number of samples to be taken of suspect ACM in each HA.
The inspection was characterized by observations of accessible areas. Suspect materials examined and quantified during the inspection included:
• White 12”x12” floor tile
• White 2’x3’ ceiling tile
• Brown baseboard
• Black window caulk
• White popcorn ceiling
• Black sink coating
• Tan 1”x1” tile
• White bathtub caulk
• Grey 12”x12” floor tile
• Cobble 12”x12” linoleum floor tile
• White wall plaster
• Yellow carpet mastic
• Yellow caulk
• Black Caulk
• Black roofing paper
• Red caulk
• White plaster fabric
• White boiler rope
• White concrete sealant
• White pipe wrap
• White pipe caulk
• Grey pipe caulk
• Metallic and Brown pipe wrap paper
• Black baseboard
• Brown 1”x1” tile
• White drywall
• White tile grout
• Grey 12”x12” linoleum floor tile
• Brown 12”x12” linoleum floor tile
• Black 12”x12” linoleum floor tile
• White dryer exhaust fabric
• Tan stair caulk
• Black tar paper
• Black insulation paper
• Yellow pipe insulation
A total of 87 bulk samples were collected from suspect ACM during the survey at Building 9175. Bulk sample locations are presented on Figures 01 through 09 in Appendix C of this report.
4.0 INSPECTION RESULTS
Analytical results of the bulk samples collected indicated that none of the sampled materials contain greater than 1% asbestos. Complete laboratory analytical results are presented in Appendix D.
5.0 CONDITION AND FRIABLITY ASSESSMENT
For each inspection conducted, the inspector classifies ACM materials by friability and condition. This helps to determine the extent of damage in certain areas as well as the potential for further damage and asbestos release due to disturbance of the material.
No sampled materials were found to be ACM, so no materials are classified by friability nor condition.
6.0 AREAS NOT ACCESSIBLE
Void Spaces within Walls and Ceilings: Tehama preformed destructive sampling on concealed spaces on walls to access plenum or chases. Due to the nature and outcome of the materials sampled Tehama did not observe any “suspect” materials continuing into plenums, etc. Although destructive sampling occurred, Tehama cannot account for all plenums/void spaces that exist in these facilities. Tehama recommends periodic oversight during demolition in order to assess any hidden/unforeseen materials that might be revealed.
7.0 POLYCHLORINATED BIPHENYLS
Polychlorinated biphenyls (PCBs) are regulated pursuant to the United States Environmental Protection Agency Code of Federal Regulations (40 CFR 761) and the Toxic Substances Control Act (TSCA – 15 U.S.C. 2605).
These regulations require certain testing and reporting requirements to determine management, recycling and disposal options for PCBs. Multiple ballasts throughout the building were checked and contained a sticker indicating that they did not contain PCBs. Although this sticker was present, Tehama cannot guarantee that all of the ballasts do not contain PCBs. A photograph of the sticker is provided in Appendix E. Please see the below table itemizing the number of Fluorescent Lighting Ballasts with the potential to contain PCBs:
Facility (Floor/Level) Ballast Quantity 1st Floor 268 2nd Floor 277 3rd Floor 277
APPROX. TOTALS 822
8.0 UNIVERSAL WASTES
Universal Wastes (i.e., batteries, thermostats, lamps, mercury-containing equipment, and pesticides) are regulated pursuant to the EPA Universal Waste Requirements (40 CFR Part 273). Similarly, these sampling procedures may also be used to determine disposal/management or clean-up options for Universal Wastes. Typical equipment that might contain universal wastes are emergency light batteries, CFC containing refrigerators, water fountains, mercury containing bulbs, thermostats and thermometers. Fluorescent bulbs were found loose throughout the building, in addition to the bulbs installed in the ballasts. Please see the below table itemizing the number of assumed universal wastes:
Facility (Floor/Level)
Fluorescent Bulbs
CFC
Containing Equipment
Mercury Containing Equipment
Water Fountains
AC
Units
1st Floor 422 2 0 2 1 2nd Floor 585 2 0 2 0 3rd Floor 560 2 0 2 0
TOTALS 1,567 6 0 6 1
At various locations within the building, Tehama noted other wastes that could potentially be considered hazardous if disposed of incorrectly. The following is a list of materials observed:
• 2.5-Gallons of Paint Stripper
• 2-Gallons of Floor Finish
• 2-Gallons Boiler Water Treatment
• Miscellaneous Cleaning Supplies (ex. Disinfectants)
9.0 CONCLUSIONS AND RECOMMENDATIONS
No ACM was identified during the survey of Building 9175. The asbestos inspection was based on the scope of work proposed by Yaeger for use in their design-build project. Any change in the scope of work beyond what was identified in the scope of work drawings and subsequent emails will require further investigation to accurately classify any additional ACM/Hazardous Materials resulting from the modified or updated scope of work.
10.0 LIMITATIONS, EXCEPTIONS AND ASSUMPTIONS
Opinions and recommendations presented in this report apply to site conditions and features as they existed at the time of Tehama’s site visit, and those reasonably foreseeable. They cannot necessarily apply to conditions and features of which Tehama is unaware and has not had the opportunity to evaluate.
It is important to recognize that even the most comprehensive scope of services may fail to detect all ACM that may be associated with the property. Therefore, Tehama cannot act as insurers and cannot “certify” that all ACM associated with the property has been identified, and no expressed or implied representation or warranty is included or intended in our reports, except that our services were performed, within the limits prescribed by our client, with the customary thoroughness and competence of our profession.
11.0 REPORT CERTIFICATIONS
This report, and the supporting data, findings, conclusions, opinions, and recommendations it contains represents the result of Tehama’s efforts for the asbestos survey work as per the scope of work as described in the scope of work drawings and emails.
Opinions and recommendations presented in this report apply to site conditions and features as they existed at the time of Tehama’s site visit, and those reasonably foreseeable. They cannot necessarily apply to conditions and features of which Tehama is unaware and has not had the opportunity to evaluate.
The conclusions presented in this report are professional opinions based solely upon Tehama’s visual observations of accessible areas, laboratory test data, and current regulatory requirements. These conclusions are intended exclusively for the purpose stated herein, at the site indicated, and for the project indicated.
If you have any questions concerning this report, please feel free to contact Megan Perez-Utter at (816) 533-2246.
Prepared by:
Megan Perez-Utter, Tehama, LLC
Reviewed by:
Summer Manning, Tehama, LLC
SECTION II
LEAD-BASED PAINT (LBP)
1.0 INTRODUCTION
Tehama has performed a full interior and exterior inspection for the presence or absence of Lead-Based Paint (LBP) for Building 9175 at JBLM, Washington. The inspection was conducted at the request of Yaeger for use in their design-build package for renovation of Building 9175. The scope of work for this project was based on Yaeger’s scope of work, drawings and emails, and Tehama’s proposal, dated August 2, 2019.The intent of this inspection was to locate, identify and quantify LBP that will be impacted during renovation of the building.
Inspectors Megan Perez-Utter and Anne Eiseman performed the inspection from October 21-24, 2019. Megan Perez- Utter and Anne Eiseman are certified Lead Inspectors by the State of Washington Department of Commerce.
Certifications for inspectors are located in Appendix A.
2.0 FIELD SURVEY PROCEDURES AND SAMPLE ANALYSIS METHODS
The purpose of the LBP survey was to conduct a surface-by-surface investigation of painted components inside and outside of the building in an effort to identify which painted surfaces contain lead.
Some of the test locations exhibited lead-in-paint levels below the level that EPA identifies as LBP, specifically 0.5% by weight or 1.0 mg/cm2. Such surfaces could create dust-lead or soil-lead hazards if the paint is turned into dust by abrasion, scraping, or sanding. Should these or any lead containing components or surfaces be disturbed in any manner that generates dust, care should be taken to limit worker exposure and the spread of dust.
The lead regulatory levels provided below are those used when preparing this LBP evaluation or when evaluating data collected. The EPA regulatory levels are the same as the state regulatory levels provided in the following table:
EPA Levels
Lead-Based Paint
1.0 mg/cm2 or 0.5% by weight (or 5,000 pm)
Testing was accomplished through the use of an Olympus DELTA Series handheld x-ray fluorescence (XRF) to collect lead levels on painted surfaces. The XRF determines the chemistry of a sample by measuring the fluorescent x-rays emitted from the sample that returns to the XRF after irradiated energy is released onto the sample. A total of 273 XRF tests were performed on different paint variations on the interior and exterior of the structures. Field validation checks of the XRF were also performed at the beginning and end of test operations on the day of testing. Validation checks were performed through a series of three tests on a NIST SRM paint film. Results of the validation checks indicated that the XRF unit was calibrated properly.
Tehama also collected one paint chip sample that was submitted to the subcontracted laboratory, QuanTEM Laboratories, located at 2033 Heritage Park Drive, Oklahoma City, Oklahoma 73120. The laboratory maintains accreditation from the following agencies:
• National Voluntary Laboratory Accreditation Program (Lab Code 101959-0)
• American Industrial Hygiene Association Accredited Laboratory (Lab No. 101352)
Laboratory accreditations are presented in Appendix B of this report.
3.0 SUMMARY OF INSPECTION
A visual assessment of each unique combination of suspect LBP was completed. Unique sampling combinations of suspect LBP were then analyzed using a handheld XRF. The inspection was characterized by observations of accessible areas.
XRF results indicated that none of the materials tested contained LBP greater than or equal to 1.0 mg/cm2. Although none of the materials tested contained LBP greater than or equal to 1.0 mg/cm2, a polyvinyl chloride (PVC) pipe in Room 113 resulted in a positive test result on the XRF. Tehama tested the pipe three times in three different locations as the team thought it was unusual that a PVC pipe with the same color paint as the walls (XRF indicated 0.00 mg/cm2 on the walls), tested positive. Paint was scraped off the pipe and the unpainted PVC pipe was tested. The unpainted section tested positive at 1.13 mg/cm2. Readings for the other two painted locations on the PVC pipe were 0.99 mg/cm2 and 1.09 mg/cm2. Tehama then collected a paint chip sample to be tested at the off-site laboratory to confirm the paint did not contain lead. Based on the paint-chip sample result from the laboratory (<0.005%), the paint on the pipe is negative for lead. It is unclear why the black PVC pipe is showing results of lead over 1.0 mg/cm2, below are two possibilities:
• The PVC pipe is covering a lead pipe.
• The PVC pipe contains minimal amounts of lead, but this is unlikely based on the age of the building as lead was banned from being used as a stabilizer in PVC in the United States in the late 1970’s.
The location of the tested PVC pipe is shown on Figure 11 in Appendix C, and a photograph is provided in Appendix E.
4.0 INSPECTION RESULTS
The LBP inspection involved a thorough visual examination of accessible areas, field XRF testing of painted surfaces, and laboratory analysis of a confirmatory paint chip sample. XRF results presented in Appendix D of this report provide information on test locations, substrate tested, condition of paint, and concentration.
All sample locations are detailed on Figures 10 through 18 located in Appendix C of this report.
In total, one paint chip sample was collected and analyzed, which did not test positive for lead. The painted surface where the chip sample was collected was found to be in fair condition as defined by the EPA and Housing and Urban Development (HUD) guidelines. As explained in Section 3.0, the paint chip sample did not correlate with the XRF result because the PVC pipe interfered with the LBP testing on that particular pipe.
5.0 CONCLUSIONS AND RECOMMENDATIONS
Any work which disturbs painted surfaces containing lead shall be performed in accordance with the OSHA, 29 CFR
1926.62 (Lead in Construction Standard) and EPA’s 40 CFR 745 regulation. Personal air monitoring should be conducted when disturbing lead based paints and lead containing materials as per 29 CFR 1926.62 (OSHA).
In addition, all waste generated as part of the project, regardless of the lead content in the paint, shall be tested in accordance with the EPA Resource Conservation and Recovery Act (RCRA) to determine the classification of the waste. Under RCRA, any waste material that when tested by Toxicity Characteristics Leaching Procedure (TCLP) results in a leachate lead concentration of five (5) parts per million or greater must be disposed of at an EPA licensed hazardous waste facility. Tehama did not collect any TCLP samples as no materials came back as positive for LBP.
6.0 LIMITATIONS, EXCEPTIONS AND ASSUMPTIONS
Opinions and recommendations presented in this report apply to site conditions and features as they existed at the time of Tehama’s site visit, and those reasonably foreseeable. They cannot necessarily apply to conditions and features of which Tehama is unaware and has not had the opportunity to evaluate.
Tehama has completed a thorough assessment of each unique painted surface within the interior and exterior areas of the building. If a different painted surface is identified during demolition that has not been tested, it should be assumed positive for LBP. Additional testing may be completed to determine the presence or absence of LBP.
The conclusions presented in this report are professional opinions based solely upon Tehama’s visual observations of accessible areas, laboratory test data, and current regulatory requirements. These conclusions are intended exclusively for the purpose stated herein, at the site indicated, and for the project indicated.
7.0 REPORT CERTIFICATIONS
This report, and the supporting data, findings, conclusions, opinions, and the recommendations it contains, represents the result of Tehama’s efforts. This report is not a lead abatement specification and should not be used for specifying removal methods or techniques.
It is important to recognize that even the most comprehensive scope of services may fail to detect all LBP containing materials that may be associated with the structure. Therefore, Tehama cannot act as insurers and cannot “certify” that all LBP associated with the property has been identified, and no expressed or implied representation or warranty is included or intended in our reports, except that our services were performed, within the limits prescribed by our client, with the customary thoroughness and competence of our profession.
If you have any questions concerning this report, please feel free to contact Megan Perez-Utter at (816) 533-2246.
Prepared by:
Megan Perez-Utter, Tehama, LLC
Reviewed by:
Summer Manning, Tehama, LLC
FINAL ENVIRONMENTAL INVESTIGATION SERVICES REPORT BUILDING 9175, JOINT BASE
LEWIS-MCCHORD, WASHINGTON
Appendix A
TEHAMA PERSONNEL CERTIFICATIONS
STATE OF WASHINGTON
Department of Commerce
Lead-Based Paint Abatement Program
Has fulfilled the certification requirements of
WAC 365-230
and has been certified to conduct lead-based paint activities as a
Inspector
Certification # Issuance Date Expiration Date 7466 01/31/2019 12/27/2020
Anne Eiseman
Appendix B
LABORATORY CERTIFICATIONS
FINAL ENVIRONMENTAL INVESTIGATION SERVICES REPORTBUILDING 9175, JOINT BASE
Appendix C
FIGURES
FIGUREDATE
11/13/2019 01Tehama, LLC
Asbestos Bulk Sample Locations Building 9175 - First Floor Section A
Environmental Investigation Services at Joint Base Lewis-McChord, WA
United States Army Joint Base Lewis-McChord, Washington
Legend Asbestos Sample Results !? Negative (<1% Asbestos Content)
Notes:
- Samples collected 10/21/2019 unless otherwise noted.
- Analytical results of the bulk samples collected indicated that none of the sampled materials contain greater than 1% asbestos.
6-7
FIGUREDATE
11/13/2019 02Tehama, LLC
Environmental Investigation Services at Joint Base Lewis-McChord, WA
United States Army Joint Base Lewis-McChord, Washington
Legend Asbestos Sample Results !? Negative (<1% Asbestos Content)
Notes:
- Samples collected 10/21/2019 unless otherwise noted.
- Analytical results of the bulk samples collected indicated that none of the sampled materials contain greater than 1% asbestos.
Asbestos Bulk Sample Locations Building 9175 - First Floor Section B
26-28
20-21
FIGUREDATE
11/13/2019 03Tehama, LLC
Environmental Investigation Services at Joint Base Lewis-McChord, WA
United States Army Joint Base Lewis-McChord, Washington
Legend Asbestos Sample Results !? Negative (<1% Asbestos Content)
Asbestos Bulk Sample Locations Building 9175 - First Floor Section C
Notes:
- Samples collected 10/21/2019 unless otherwise noted.
- Analytical results of the bulk samples collected indicated that none of the sampled materials contain greater than
47, 48
FIGUREDATE
11/13/2019 04Tehama, LLC
Environmental Investigation Services at Joint Base Lewis-McChord, WA
United States Army Joint Base Lewis-McChord, Washington
Legend Asbestos Sample Results !? Negative (<1% Asbestos Content)
Asbestos Bulk Sample Locations Building 9175 - Second Floor Section A
Notes: Notes:
- SSaammpplleess ccoolllleecctteedd 1100//22//22001199 uunnlleessss ootthheerrwwiissee nnootteedd..
- AAnnaallyyttiiccaall rreessuullttss ooff tthhee bbuullkk ssaammpplleess ccoolllleecctteedd iinnddiiccaatteedd tthhaatt nnoonnee ooff tthhee ssaammpplleedd mmaatteerriiaallss ccoonnttaaiinn ggrreeaatteerr tthhaann 11%% aassbbeessttooss..
FIGUREDATE
11/13/2019 05Tehama, LLC
Environmental Investigation Services at Joint Base Lewis-McChord, WA
United States Army Joint Base Lewis-McChord, Washington
Legend Asbestos Sample Results !? Negative (<1% Asbestos Content)
Asbestos Bulk Sample Locations Building 9175 - Second Floor Section B
Notes: Notes:
- SSaammpplleess ccoolllleecctteedd 1100//22//22001199 uunnlleessss ootthheerrwwiissee nnootteedd..
- AAnnaallyyttiiccaall rreessuullttss ooff tthhee bbuullkk ssaammpplleess ccoolllleecctteedd iinnddiiccaatteedd tthhaatt nnoonnee ooff tthhee ssaammpplleedd mmaatteerriiaallss ccoonnttaaiinn ggrreeaatteerr
65, 66
FIGUREDATE
11/13/2019 06Tehama, LLC
Environmental Investigation Services at Joint Base Lewis-McChord, WA
United States Army Joint Base Lewis-McChord, Washington
Legend Asbestos Sample Results !? Negative (<1% Asbestos Content)
Asbestos Bulk Sample Locations Building 9175 - Second Floor Section C
Notes:
- Samples collected 10/21/2019 unless otherwise noted.
- Analytical results of the bulk samples collected indicated that none of the sampled materials contain greater than 1% asbestos.
Notes:
- Samples collected 10/21/2019 unless otherwise noted.
- Analytical results of the bulk samples collected indicated that none of the sampled materials contain greater than
FIGUREDATE
11/13/2019 07Tehama, LLC
Environmental Investigation Services at Joint Base Lewis-McChord, WA
United States Army Joint Base Lewis-McChord, Washington
Legend Asbestos Sample Results !? Negative (<1% Asbestos Content)
Asbestos Bulk Sample Locations Building 9175 - Third Floor Section A
Notes: Notes:
- SSaammpplleess ccoolllleecctteedd 1100//22//22001199 uunnlleessss ootthheerrwwiissee nnootteedd..
- AAnnaallyyttiiccaall rreessuullttss ooff tthhee bbuullkk ssaammpplleess ccoolllleecctteedd iinnddiiccaatteedd tthhaatt nnoonnee ooff tthhee ssaammpplleedd mmaatteerriiaallss ccoonnttaaiinn ggrreeaatteerr
FIGUREDATE
11/13/2019 08Tehama, LLC
Environmental Investigation Services at Joint Base Lewis-McChord, WA
United States Army Joint Base Lewis-McChord, Washington
Legend Asbestos Sample Results !? Negative (<1% Asbestos Content)
Asbestos Bulk Sample Locations Building 9175 - Third Floor Section B
Notes: Notes:
- SSaammpplleess ccoolllleecctteedd 1100/22//22001199 uunnlleessss ootthheerrwwiissee nnootteedd..
- AAnnaallyyttiiccaall rreessuullttss ooff tthhee bbuullkk ssaammpplleess ccoolllleecctteedd iinnddiiccaatteedd tthhaatt nnoonnee ooff tthhee ssaammpplleedd mmaatteerriiaallss ccoonnttaaiinn ggrreeaatteerr
FIGUREDATE
11/13/2019 09Tehama, LLC
Environmental Investigation Services at Joint Base Lewis-McChord, WA
United States Army Joint Base Lewis-McChord, Washington
Legend Asbestos Sample Results !? Negative (<1% Asbestos Content)
Asbestos Bulk Sample Locations Building 9175 - Third Floor Section C
Notes: Notes:
- SSaammpplleess ccoolllleecctteedd 1100//22//22001199 uunnlleessss ootthheerrwwiissee nnootteedd..
- AAnnaallyyttiiccaall rreessuullttss ooff tthhee bbuullkk ssaammpplleess ccoolllleecctteedd iinnddiiccaatteedd tthhaatt nnoonnee ooff tthhee ssaammpplleedd mmaatteerriiaallss ccoonnttaaiinn ggrreeaatteerr
85-87 72, 73
74, 75
77, 78
83, 84
90, 91 108-110
99, 100 111, 112
FIGUREDATE
11/13/2019 10Tehama, LLC
Lead Based Paint Sample Locations Building 9175 - First Floor Section A
Environmental Investigation Services at Joint Base Lewis-McChord, WA
United States Army Joint Base Lewis-McChord, Washington
Legend LBP Sample Results !? Negative (<1.0 mg/cm²)
Notes:
- Samples with shadowing around number collected 10/21/2019, samples without shadowing collected on 10/24/2019.
24 !?
16-18
64, 66
10, 11
12, 13, 14
21, 23 (10/21/2019) and 125 (10/22/2019)
FIGUREDATE
11/13/2019 11Tehama, LLC
Lead-Based Paint Sample Locations Building 9175 - First Floor Section B
Environmental Investigation Services at Joint Base Lewis-McChord, WA
United States Army Joint Base Lewis-McChord, Washington
Legend LBP Sample Results !? Negative (<1.0 mg/cm²)
!? Positive (>1.0 mg/cm²)
Note: Samples collected 10/21/2019 unless otherwise noted. Samples with no shadowing around the numbers were collected on 10/24/2019.
!?19
!?20
62-63
58-59
56-57
49-5244-45
42-43
40-41
33-37
26-29
FIGUREDATE
11/13/2019 12Tehama, LLC
Environmental Investigation Services at Joint Base Lewis-McChord, WA
United States Army Joint Base Lewis-McChord, Washington
Legend Asbestos Sample Results !? Negative (<1.0 mg/cm²)
Lead Based Paint Sample Locations Building 9175 - First Floor Section C
Notes:
6,7
13 !?10
- Samples with shadowing around number collected 10/21/2019, samples without shadowing collected on 10/24/2019.
137, 138
115, 116119, 120
123, 124
130, 131
FIGUREDATE
11/13/2019 13Tehama, LLC
Environmental Investigation Services at Joint Base Lewis-McChord, WA
United States Army Joint Base Lewis-McChord, Washington
Legend Asbestos Sample Results !? Negative (<1.0 mg/cm²)
Lead Based Paint Sample Locations Building 9175 - Second Floor Section A
Notes:
- Samples collected 10/22/2019 unless otherwise noted.
31 30
15 16
18-20
13, 14
11, 12
22, 23
25, 26
FIGUREDATE
11/13/2019 14Tehama, LLC
Environmental Investigation Services at Joint Base Lewis-McChord, WA
United States Army Joint Base Lewis-McChord, Washington
Legend Asbestos Sample Results !? Negative (<1.0 mg/cm²)
Lead Based Paint Sample Locations Building 9175 - Second Floor Section B
Notes:
63-65
51, 52
37, 38
55, 56
61, 62
33, 34
FIGUREDATE
11/13/2019 15Tehama, LLC
Environmental Investigation Services at Joint Base Lewis-McChord, WA
United States Army Joint Base Lewis-McChord, Washington
Legend Asbestos Sample Results !? Negative (<1.0 mg/cm²)
Lead Based Paint Sample Locations Building 9175 - Second Floor Section C
Notes:
- Samples collected 10/21/2019
102 103
105 97, 98
100, 101
FIGUREDATE
11/13/2019 16Tehama, LLC
Environmental Investigation Services at Joint Base Lewis-McChord, WA
United States Army Joint Base Lewis-McChord, Washington
Legend Asbestos Sample Results !? Negative (<1.0 mg/cm²)
Lead Based Paint Sample Locations Building 9175 - Third Floor Section B
Notes:
106, 107111, 112
117, 118
FIGUREDATE
11/13/2019 17Tehama, LLC
Environmental Investigation Services at Joint Base Lewis-McChord, WA
United States Army Joint Base Lewis-McChord, Washington
Legend Asbestos Sample Results !? Negative (<1.0 mg/cm²)
Asbestos Bulk Sample Locations Building 9175 - Third Floor Section A
Notes:
93-95
79, 80
83, 84
73, 74
87, 88
67, 68
FIGUREDATE
11/13/2019 18Tehama, LLC
Environmental Investigation Services at Joint Base Lewis-McChord, WA
United States Army Joint Base Lewis-McChord, Washington
Legend Asbestos Sample Results !? Negative (<1.0 mg/cm²)
Lead Based Paint Sample Locations Building 9175 - Third Floor Section C
Notes:
Appendix D
XRF DATA AND LABORATORY RESULTS
Date Received: 11/01/2019
Project: JBLM Building 9175
QuanTEM Lab No. 316499
Analyzed By: Cassie Sanborn
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: Washington
Project Number: F0119
Account Number: C238
Received By: Elena LaFarge
Date Analyzed: 11/08/2019
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: Tehama, LLC
1600 Genessee Street, Suite 754
Kansas City, MO 64102
Non Fibrous
001 9175-1 Layered CaCO3
Vinyl
Asbestos Not Present NA
Floor Tile
White
001a Layered TarAsbestos Not Present NA
Mastic
Black
002 9175-2 Homogeneous Perlite
Paint
Asbestos Not Present 50
Cellulose
Glass FiberCeiling Tile
White
003 9175-3 Layered VinylAsbestos Not Present NA
Cove Base
Brown
003a Layered GlueAsbestos Not Present NA
Mastic
Yellow
004 9175-4 Layered CaCO3
Silicone
Asbestos Not Present NA
Caulk
Black
004a Layered FoamAsbestos Not Present NA
Insulation
Yellow
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
Unless otherwise noted, upon receipt the condition of the sample was acceptable for analysis.
QuanTEM Lab No. 316499
Analyzed By: Cassie Sanborn
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: Washington
Project Number: F0119
Account Number: C238
Received By: Elena LaFarge
Date Analyzed: 11/08/2019
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: Tehama, LLC
1600 Genessee Street, Suite 754
Kansas City, MO 64102
Non Fibrous
005 9175-5 Homogeneous CaCO3
Binder
Asbestos Not Present NA
Sealant
White
006 9175-6 Layered CaCO3
Binder
Asbestos Not Present NA
Pipe Wrap
White
006a Layered Asbestos Not Present 100Glass Fiber
Insulation
Yellow
007 9175-7 Homogeneous CaCO3
Silicone
Asbestos Not Present NA
Caulk
White
008 9175-8 Homogeneous CaCO3
Silicone
Asbestos Not Present NA
Caulk
Gray
009 9175-9 Homogeneous Asbestos Not Present 100Cellulose
Pipe Wrap
Metallic / Brown
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
QuanTEM Lab No. 316499
Analyzed By: Cassie Sanborn
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: Washington
Project Number: F0119
Account Number: C238
Received By: Elena LaFarge
Date Analyzed: 11/08/2019
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: Tehama, LLC
1600 Genessee Street, Suite 754
Kansas City, MO 64102
Non Fibrous
010 9175-10 Layered Vinyl
Binder
Asbestos Not Present NA
Cove Base
Black
010a Layered CaCO3
Glue
Asbestos Not Present NA
Mastic
White
011 9175-11 Homogeneous CaCO3
Paint
Asbestos Not Present NA
Ceiling Texture
White
012 9175-12 Homogeneous CaCO3
Binder
Asbestos Not Present NA
Caulk
Yellow
013 9175-13 Homogeneous Plastic
Binder
Asbestos Not Present NA
Sealant
Black
014 9175-14 Homogeneous CaCO3
Tar
Asbestos Not Present NA
Sink Coating
Black
015 9175-15 Layered Clay
Sand
Asbestos Not Present NA
Ceramic Tile
Tan
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
QuanTEM Lab No. 316499
Analyzed By: Cassie Sanborn
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: Washington
Project Number: F0119
Account Number: C238
Received By: Elena LaFarge
Date Analyzed: 11/08/2019
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: Tehama, LLC
1600 Genessee Street, Suite 754
Kansas City, MO 64102
Non Fibrous
015a Layered CaCO3
Sand
Asbestos Not Present NA
Grout
Tan
015b Layered CaCO3
Glue
Asbestos Not Present NA
Mastic
Tan
016 9175-16 Homogeneous CaCO3
Binder
Asbestos Not Present NA
Caulk
White
017 9175-17 Layered CaCO3
Vinyl
Asbestos Not Present NA
Floor Tile
Gray
017a Layered TarAsbestos Not Present NA
Mastic
Black
018 9175-18 Layered CaCO3
Vinyl
Asbestos Not Present NA
Floor Tile
Gray
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
QuanTEM Lab No. 316499
Analyzed By: Cassie Sanborn
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: Washington
Project Number: F0119
Account Number: C238
Received By: Elena LaFarge
Date Analyzed: 11/08/2019
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: Tehama, LLC
1600 Genessee Street, Suite 754
Kansas City, MO 64102
Non Fibrous
018a Layered TarAsbestos Not Present NA
Mastic
Brown
019 9175-19 Layered CaCO3
Vinyl
Asbestos Not Present NA
Floor Tile
White
019a Layered TarAsbestos Not Present NA
Mastic
Brown
020 9175-20 Homogeneous CaCO3
Binder
Asbestos Not Present NA
Sealant
White
021 9175-21 Homogeneous CaCO3
Paint
Asbestos Not Present NA
Ceiling Texture
White
022 9175-22 Layered CaCO3
Vinyl
Asbestos Not Present NA
Cove Base
Brown
022a Layered CaCO3
Glue
Asbestos Not Present NA
Mastic
White
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
QuanTEM Lab No. 316499
Analyzed By: Cassie Sanborn
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: Washington
Project Number: F0119
Account Number: C238
Received By: Elena LaFarge
Date Analyzed: 11/08/2019
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: Tehama, LLC
1600 Genessee Street, Suite 754
Kansas City, MO 64102
Non Fibrous
023 9175-23 Layered CaCO3
Vinyl
Asbestos Not Present NA
Floor Tile
Gray
023a Layered TarAsbestos Not Present NA
Mastic
Black
024 9175-24 Layered CaCO3Asbestos Not Present NA
Joint Compound
White
024a Layered GypsumAsbestos Not Present 15Cellulose
Sheetrock
White
025 9175-25 ** ** Not Analyzed
Insufficient Quantity
026 9175-26 Layered Clay
Sand
Asbestos Not Present NA
Ceramic Tile
Brown
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
QuanTEM Lab No. 316499
Analyzed By: Cassie Sanborn
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: Washington
Project Number: F0119
Account Number: C238
Received By: Elena LaFarge
Date Analyzed: 11/08/2019
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: Tehama, LLC
1600 Genessee Street, Suite 754
Kansas City, MO 64102
Non Fibrous
026a Layered CaCO3
Glue
Asbestos Not Present NA
Mastic
Yellow
027 9175-27 Homogeneous SiliconeAsbestos Not Present NA
Caulk
Clear
028 9175-28 Homogeneous CaCO3
Sand
Asbestos Not Present NA
Grout
White
029 9175-29 Homogeneous CaCO3
Silicone
Asbestos Not Present NA
Caulk
Gray
030 9175-30 Layered CaCO3
Vinyl
Asbestos Not Present NA
Floor Tile
Gray
030a Layered GlueAsbestos Not Present NA
Mastic
Tan
031 9175-31 Homogeneous CaCO3
Vinyl
Asbestos Not Present NA
Floor Tile
Gray
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
QuanTEM Lab No. 316499
Analyzed By: Cassie Sanborn
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: Washington
Project Number: F0119
Account Number: C238
Received By: Elena LaFarge
Date Analyzed: 11/08/2019
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: Tehama, LLC
1600 Genessee Street, Suite 754
Kansas City, MO 64102
Non Fibrous
032 9175-32 Layered CaCO3
Vinyl
Asbestos Not Present NA
Floor Tile
White
032a Layered TarAsbestos Not Present NA
Mastic
Black
033 9175-33 Homogeneous CaCO3
Binder
Asbestos Not Present NA
Sealant
White
034 9175-34 Homogeneous Perlite
Paint
Asbestos Not Present NA
Ceiling Texture
White
035 9175-35 Homogeneous CaCO3
Paint
Asbestos Not Present NA
Plaster
White
036 9175-36 Layered VinylAsbestos Not Present NA
Cove Base
Brown
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
QuanTEM Lab No. 316499
Analyzed By: Cassie Sanborn
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: Washington
Project Number: F0119
Account Number: C238
Received By: Elena LaFarge
Date Analyzed: 11/08/2019
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: Tehama, LLC
1600 Genessee Street, Suite 754
Kansas City, MO 64102
Non Fibrous
036a Layered GlueAsbestos Not Present NA
Mastic
Yellow
037 9175-37 Layered Clay
Sand
Asbestos Not Present NA
Ceramic Tile
Brown
037a Layered CaCO3
Sand
Asbestos Not Present NA
Grout
Gray
037b Layered Glue
CaCO3
Asbestos Not Present NA
Mastic
Cream
038 9175-38 Homogeneous BinderAsbestos Not Present NA
Sink Undercoat
Black
039 9175-39 Layered CaCO3
Vinyl
Asbestos Not Present NA
Floor Tile
White
039a Layered Glue
Tar
Asbestos Not Present NA
Mastic
Yellow/Black
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
QuanTEM Lab No. 316499
Analyzed By: Cassie Sanborn
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: Washington
Project Number: F0119
Account Number: C238
Received By: Elena LaFarge
Date Analyzed: 11/08/2019
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: Tehama, LLC
1600 Genessee Street, Suite 754
Kansas City, MO 64102
Non Fibrous
040 9175-40 Homogeneous CaCO3
Vinyl
Asbestos Not Present 3Synthetic
Linoleum
Brown
041 9175-41 Homogeneous CaCO3
Vinyl
Asbestos Not Present 3Synthetic
Linoleum
Black
042 9175-42 Homogeneous Rubber
CaCO3
Asbestos Not Present NA
Caulk
Black
043 9175-43 Homogeneous CaCO3
Binder
Asbestos Not Present NA
Caulk
Black
044 9175-44 Homogeneous CaCO3
Binder
Asbestos Not Present NA
Caulk
White
045 9175-45 Homogeneous CaCO3
Binder
Asbestos Not Present NA
Caulk
Gray
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
QuanTEM Lab No. 316499
Analyzed By: Cassie Sanborn
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: Washington
Project Number: F0119
Account Number: C238
Received By: Elena LaFarge
Date Analyzed: 11/08/2019
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: Tehama, LLC
1600 Genessee Street, Suite 754
Kansas City, MO 64102
Non Fibrous
046 9175-46 Layered CaCO3
Vinyl
Asbestos Not Present NA
Floor Tile
White
046a Layered TarAsbestos Not Present NA
Mastic
Black
047 9175-47 Layered Clay
Sand
Asbestos Not Present NA
Ceramic Tile
Brown
047a Layered CaCO3
Sand
Asbestos Not Present NA
Grout
Gray
047b Layered Glue
CaCO3
Asbestos Not Present NA
Mastic
Cream
047c Layered CaCO3
Sand
Asbestos Not Present NA
Mortar
White
048 9175-48 Homogeneous SiliconeAsbestos Not Present NA
Caulk
White
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
QuanTEM Lab No. 316499
Analyzed By: Cassie Sanborn
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: Washington
Project Number: F0119
Account Number: C238
Received By: Elena LaFarge
Date Analyzed: 11/08/2019
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: Tehama, LLC
1600 Genessee Street, Suite 754
Kansas City, MO 64102
Non Fibrous
049 9175-49 Homogeneous BinderAsbestos Not Present NA
Sink Undercoat
Black
050 9175-50 Layered VinylAsbestos Not Present NA
Cove Base
Brown
050a Layered Glue
CaCO3
Asbestos Not Present NA
Mastic
White
051 9175-51 Layered CaCO3
Foil
Binder
Asbestos Not Present 30Cellulose
Pipe Wrap
White
051a Layered Asbestos Not Present 100Glass Fiber
Insulation
Yellow
052 9175-52 Homogeneous CaCO3
Paint
Asbestos Not Present NA
Ceiling Texture
White
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
QuanTEM Lab No. 316499
Analyzed By: Cassie Sanborn
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: Washington
Project Number: F0119
Account Number: C238
Received By: Elena LaFarge
Date Analyzed: 11/08/2019
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: Tehama, LLC
1600 Genessee Street, Suite 754
Kansas City, MO 64102
Non Fibrous
053 9175-53 Homogeneous CaCO3
Tar
Asbestos Not Present NA
Sink Undercoat
Black
054 9175-54 Layered CaCO3
Vinyl
Asbestos Not Present NA
Floor Tile
White
054a Layered TarAsbestos Not Present NA
Mastic
Black
055 9175-55 Layered CaCO3
Vinyl
Asbestos Not Present NA
Cove Base
Brown
055a Layered CaCO3
Glue
Asbestos Not Present NA
Mastic
Tan
056 9175-56 Homogeneous CaCO3
Vinyl
Asbestos Not Present NA
Caulk
Gray
057 9175-57 Layered Clay
Sand
Asbestos Not Present NA
Ceramic Tile
Blue
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
QuanTEM Lab No. 316499
Analyzed By: Cassie Sanborn
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: Washington
Project Number: F0119
Account Number: C238
Received By: Elena LaFarge
Date Analyzed: 11/08/2019
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: Tehama, LLC
1600 Genessee Street, Suite 754
Kansas City, MO 64102
Non Fibrous
057a Layered CaCO3Asbestos Not Present NA
Grout
White
057b Layered CaCO3
Glue
Asbestos Not Present NA
Mastic
Tan
058 9175-58 Layered CaCO3
Binder
Asbestos Not Present 40Cellulose
Wrap
White
058a Layered Foil
Binder
Asbestos Not Present 30
Cellulose
Glass FiberWrap
Tan
058b Layered Asbestos Not Present 100Glass Fiber
Insulation
Yellow
059 9175-59 Homogeneous Perlite
Paint
Asbestos Not Present 50
Cellulose
Glass FiberCeiling Tile
White
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
QuanTEM Lab No. 316499
Analyzed By: Cassie Sanborn
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: Washington
Project Number: F0119
Account Number: C238
Received By: Elena LaFarge
Date Analyzed: 11/08/2019
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: Tehama, LLC
1600 Genessee Street, Suite 754
Kansas City, MO 64102
Non Fibrous
060 9175-60 Homogeneous CaCO3
Paint
Asbestos Not Present NA
Ceiling Texture
White
061 9175-61 ** ** Not Analyzed
Insufficient Quantity
062 9175-62 Homogeneous CaCO3
Binder
Asbestos Not Present NA
Caulk
Black
063 9175-63 Layered Clay
Sand
Asbestos Not Present NA
Ceramic Tile
Brown
063a Layered CaCO3
Sand
Asbestos Not Present NA
Grout
Tan
063b Layered CaCO3
Glue
Asbestos Not Present NA
Mastic
Tan
064 9175-64 Layered BinderAsbestos Not Present 90Synthetic
Carpet
Tan
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested. NVLAP accreditation applies only to analysis performed utilizing EPA/600/M4-82-020 and EPA/600/R-93/116 methods. This report may not be used to claim product endorsement by NVLAP or any agency of the US Government. This report may not be reproduced except in full, without the written approval of the laboratory.
QuanTEM Lab No. 316499
Analyzed By: Cassie Sanborn
Methodology: EPA/600/R-93/116
Polarized Light Microscopy Asbestos Analysis Report
Project Location: Washington
Project Number: F0119
Account Number: C238
Received By: Elena LaFarge
Date Analyzed: 11/08/2019
QuanTEM
Sample ID
Client
Sample ID Composition
Color /
Description Asbestos (%)
Non-Asbestos
Fiber (%)
Client: Tehama, LLC
1600 Genessee Street, Suite 754
Kansas City, MO 64102
Non Fibrous
064a Layered CaCO3
Glue
Asbestos Not Present NA
Mastic
Tan
065 9175-65 Homogeneous Silicone
Binder
Asbestos Not Present NA
Caulk
Black
066 9175-66 Homogeneous CaCO3
Binder
Asbestos Not Present NA
Caulk
Yellow
067 9175-67 Homogeneous CaCO3
Binder
Asbestos Not Present NA
Sealant
White
068 9175-68 ** ** Not Analyzed
Insufficient Quantity
069 9175-69 Homogeneous CaCO3
Silicone
Asbestos Not Present NA
Caulk
Black
QuanTEM is a NVLAP accredited PLM laboratory (Lab Code: 101959-0). This report relates only to the specific items tested.