S-SU0312.pdf
PDF 1 MB Posted
- Attached to
- Radial Forge Infrastructure Project
- Solicitation number
- W912DS24R0009
About this file
This document package includes structural drawings and notes for a radial forge infrastructure project at Watervliet Arsenal in New York. The project involves constructing a new control room and related structures. Key details include:
-
The project is solicited under solicitation number W912DS24R0009 issued by the Department of the Army Corps of Engineers New York District.
-
Structural drawings cover concrete foundations, a control room building with CMU walls and a steel framed roof, a control tower, electrical vaults, and an underground utility trench.
-
Concrete mix designs, reinforcing details, and structural notes provide specifications for the concrete and reinforced masonry construction.
-
Steel elements include W-shapes, HSS columns, and metal decking. Welding must follow AWS D1.1.
-
The project will require site excavation and utility trenching according to geotechnical recommendations. Temporary shoring and dewatering will be the contractor's responsibility.
-
Structural drawings are dated January 15, 2024 and were prepared by an engineering firm for the Army Corps of Engineers.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A.DESIGN INFORMATION
1. CODES
a. DESIGN CONFORMS TO UFC 1-200-01, WITH CHANGE 1, DATED 1-OCTOBER 2020
(REFERENCES INTERNATIONAL BUILDING CODE (IBC) 2018) .
b. AMERICAN CONCRETE INSTITUTE (ACI) - "BUILDING CODE REQUIREMENTS FOR
STRUCTURAL CONCRETE", ACI 318-14.
c. AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) - "SPECIFICATION FOR
STRUCTURAL STEEL BUILDINGS", AISC 360-16.
d. AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE) - "MINIMUM DESIGN LOADS
AND ASSOCIATED CRITERIA FOR BUILDINGS AND OTHER STRUCTURES", ASCE
7-16.
e. AMERICAN WELDING SOCIETY (AWS) - "STRUCTURAL WELDING CODE - STEEL", AWS D1.1-2015.
f. STEEL DECK INSTITUTE (SDI) - "SPECIFICATIONS FOR STEEL ROOF DECK".
2. LOADS
a. FLOOR LIVE LOAD
· GROUND FLOOR: 250 PSF
· MECHANICAL AND ELECTRICAL ROOMS: 125 PSF
b. ROOF LIVE LOAD: 20 PSF
c. EQUIPMENT LOADS
· DUST COLLECTOR: 12,500 LBS
· DUST COLLECTOR FAN: 4,381 LBS
· EHOUSE ENCLOSURE: 125 PSF (94,500 LBS TOTAL)
· TRANSFORMERS: 33,300 LBS EA
· EXISTING COOLING TOWER (TO BE REMOVED): 38,040 LBS
· NEW COOLING TOWER: 57,170 LBS
· COOLING TOWER PUMPS: 1,247 LBS EA
· AIR COMPRESSOR AND ENCLOSURE: 22,500 LBS
· AIR HANDLING UNITS: 3,785 LBS EA
d. BUILDING RISK CATEGORY: IV
e. GROUND SNOW LOAD, Pg: 40 PSF
· FLAT ROOF SNOW LOAD, Pf: 31 PSF
· SNOW EXPOSURE FACTOR, Ce: 0.9
· SNOW IMPORTANCE FACTOR, Is: 1.2
· THERMAL FACTOR, Ct: 1.0
f. WIND LOADS
· ULTIMATE DESIGN WIND SPEED, Vult: 123 MPH
· NOMINAL DESIGN WIND SPEED, Vasd: 95 MPH
· WIND IMPORTANCE FACTOR, Iw: 1.0
· WIND EXPOSURE CATEGORY: C
· INTERNAL PRESSURE COEFFICIENT: +/- 0.18
g. SEISMIC LOADS
· SEISMIC IMPORTANCE FACTOR, Ie: 1.5
· PROJECT LATITUDE: 42.718 N
· PROJECT LONGITUDE: -73.712 W
· 0.2 SEC SPECTRAL RESPONSE, Ss: 0.198
· 1.0 SEC SPECTRAL RESPONSE, S1: 0.060
· SOIL SITE CLASS: C
· SITE COEFFICIENT SHORT PERIOD, Fa: 1.3
· SITE COEFFICIENT LONG PERIOD, Fv: 1.5
· Sms: 0.257
· Sm1: 0.091
· Sds: 0.171
· Sd1: 0.060
· SEISMIC DESIGN CATEGORY: C
· BASIC SEISMIC-FORCE-RESISTING SYSTEM: STEEL SYSTEMS NOT
SPECIFICALLY DETAILED FOR SEISMIC RESISTANCE
· RESPONSE MODIFICATION FACTOR, R: 3.0
· DEFLECTION AMPLIFICATION FACTOR, Cd: 3.0
· OVERSTRENGTH FACTOR, Ω: 3.0
B.FOUNDATIONS
1. FOUNDATION DESIGN IS BASED ON THE REQUIREMENTS CONTAINED IN THE
PROJECT GEOTECHNICAL REPORT ENTITLED “WATERVLIET ARSENAL RADIAL
FORGE GEOTECHNICAL ENGINEERING REPORT (REV 1)” DATED MAY 22, 2023,
PREPARED BY TERRACON.
2. ALL EARTHWORK AND FOUNDATION WORK SHALL CONFORM TO THE INFORMATION
AND RECOMMENDATIONS CONTAINED IN THE PROJECT GEOTECHNICAL REPORT.
ALL CONTRACTORS PERFORMING, SUPERVISING OR APPROVING EARTHWORK
AND FOUNDATION CONSTRUCTION SHALL OBTAIN A COPY OF THE GEOTECHNICAL
REPORT.
3. FOUNDATION SYSTEM IS A SHALLOW FOUNDATION SYSTEM BEARING ON
WEATHERED ROCK WITH A BEARING CAPACITY OF 1,000 PSF.
4. FROST DEPTH = 4'-0”
5. HEAVY EQUIPMENT SHALL NOT BE PERMITTED CLOSER THAN 10 FEET FROM ANY
FOUNDATION WALL. IF CONTRACTOR DEEMS IT NECESSARY TO OPERATE SUCH
HEAVY EQUIPMENT CLOSER THAN 10 FEET, THE CONTRACTOR SHALL BE SOLELY
RESPONSIBLE AND, AT HIS OWN EXPENSE, SHALL PROVIDE ADEQUATE
TEMPORARY WALL BRACING TO WITHSTAND THE ADDITIONAL LOADS
SUPERIMPOSED FROM SUCH EQUIPMENT.
6. ALL FOUNDATIONS SHALL BE POURED ON DRY SOIL. ALL EXCAVATIONS SHALL BE
ADEQUATELY DEWATERED PRIOR TO POURING OF CONCRETE.
7. PROVIDE DOWELS IN FOUNDATION FOR ALL WALLS, COLUMNS AND PIERS. DOWEL
QUANTITY AND SIZE SHALL MATCH THE VERTICAL REINFORCEMENT ABOVE,
UNLESS NOTED.
8. PLACE AND COMPACT ALL STRUCTURAL BACK FILL AND LOAD BEARING FILL IN
ACCORDANCE WITH THE REQUIREMENTS CONTAINED IN THE GEOTECHNICAL
REPORT.
9. PROPERLY GUARD AND PROTECT EXCAVATIONS SO AS TO PREVENT THEM FROM
BECOMING DANGEROUS TO PERSON OR PROPERTY. PROPERLY SLOPE SIDES OF
EXCAVATION OR PROVIDE EXCAVATION BRACING TO PREVENT CAVING OR
EROSION OF SIDES OF EXCAVATION AS PER OSHA AND BUILDING CODE
REQUIREMENTS.
10.IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT EXISTING ADJACENT
STRUCTURES/FOUNDATIONS OR NEWLY CONSTRUCTED ADJACENT FOUNDATIONS
ARE NOT DISTURBED AND UNDERMINED DURING ALL CONSTRUCTION AND
EXCAVATION OPERATIONS. CONTRACTOR SHALL TAKE ALL PRECAUTIONS TO
TEMPORARILY SUPPORT AND/OR PROVIDE UNDERPINNING FOR THE EXISTING
STRUCTURES/FOUNDATIONS AS REQUIRED. SUBMIT DETAILS, CALCULATIONS OF
TEMPORARY SUPPORT AND UNDERPINNING TO THE ENGINEER FOR REVIEW. THE
DETAILS AND CALCULATIONS SHALL BE PREPARED BY A PROFESSIONAL
ENGINEER REGISTERED IN THE STATE OF NEW YORK.
11.DEWATERING DURING CONSTRUCTION INCLUDING THE SELECTION OF THE
METHOD AND ASSOCIATED CALCULATIONS, IS SOLELY THE RESPONSIBILITY OF
THE CONTRACTOR.
12.ALL FOOTINGS ARE TO BE CENTERED ON COLUMNS ABOVE, UNLESS NOTED.
C.CONCRETE
1. MATERIALS:
a. CONCRETE, 28 DAY COMPRESSIVE STRENGTH (MIN)
· f'c = 5,000 PSI EXTERIOR FOUNDATIONS AND SLABS
(NORMAL WT)
· f'c = 5,000 PSI INTERIOR FOUNDATIONS (NORMAL WT)
· f'c = 4,000 PSI INTERIOR SLABS-ON-GRADE AND
ELEVATED SLABS (NORMAL WT)
· f'c = 1,000 PSI LEAN CONCRETE, BACKFILL FOR OVER
EXCAVATED AREAS
· CONCRETE TO BE GIVEN A HARD-TROWELED FINISH SHALL NOT CONTAIN
AN AIR ENTRAINING AGENT. TOTAL AIR CONTENT SHALL NOT EXCEED 3%.
b. REINFORCING STEEL:
· BAR REINFORCING - ASTM A615 GRADE 60
· BAR REINFORCING (WELDED) - ASTM A706 GRADE 60
· WELDED WIRE REINFORCEMENT (WWR) - ASTM A1064 (FLAT SHEET)
c. CONCRETE COVER FOR REINFORCING BARS SHALL BE AS FOLLOWS (UNLESS
NOTED):
· FOOTINGS AND SLABS CAST AGAINST GROUND - 3”
· CONCRETE TO BE IN CONTACT WITH GROUND OR WEATHER:
AT BARS LARGER THAN #5 - 2”
AT #5 BARS AND SMALLER - 1 1/2”
· CONCRETE NOT TO BE EXPOSED TO GROUND OR WEATHER:
BEAMS, GIRDERS, OR COLUMNS - 1 1/2”
SLABS AND WALLS - 3/4”
· PROVIDE CHAIRS FOR SUPPORT OF ALL REINFORCEMENT. LIFTING OF BARS
OR MESH DURING PLACEMENT OF CONCRETE IS NOT PERMITTED.
2. CONCRETE CONSTRUCTION SHALL CONFORM TO “SPECIFICATIONS FOR
STRUCTURAL CONCRETE”, ACI 301-10.
3. CONSTRUCTION TOLERANCES SHALL BE IN ACCORDANCE WITH ACI 117 EXCEPT
AS FOLLOWS:
· CHARGE AND DISCHARGE CONVEYOR TOP OF CONCRETE ELEVATION SHALL
BE +/- 1/4”.
4. SHOP DRAWINGS SHALL CONFORM TO ACI DETAILING MANUAL, ACI SP-66-04.
5. PROVIDE SUPPLEMENTARY REINFORCING AT ALL RE-ENTRANT CORNERS PER
DETAIL ON SHEET S-501.
6. LOCATION OF CONSTRUCTION JOINTS NOT SHOWN ON DRAWINGS SHALL BE
SUBMITTED TO THE ENGINEER FOR APPROVAL PRIOR TO SUBMISSION OF
REINFORCING DETAILS. ALL CONSTRUCTION JOINTS SHALL BE CLEARLY SHOWN IN
REBAR DETAIL DRAWINGS. ENGINEER MAY REQUIRE ADDITIONAL REINFORCING AT
CONSTRUCTION JOINTS.
7. CHAMFER EDGES OF ALL EXPOSED CONCRETE 3/4", UNLESS NOTED.
8. SUBMIT MIX DESIGNS, ADMIXTURES, CURING COMPOUNDS, ETC. FOR APPROVAL
PRIOR TO PLACING CONCRETE.
9. SEE THE CONCRETE REINFORCING DEVELOPMENT LENGTH TABLE ON SHEET S-501
FOR DIMENSIONS “Ld” AND LAP SPLICE LENGTHS.
10.MECHANICAL BAR SPLICING IS PERMITTED PROVIDED THAT MANUFACTURER'S
LITERATURE INDICATES A CAPACITY EQUAL TO 125% OF THE FULL TENSION LAP
SPLICE CAPACITY.
D.STRUCTURAL STEEL
1. MATERIALS
a. STRUCTURAL STEEL- ASTM A992, UNLESS NOTED
b. ANGLES, CHANNELS AND CONN PLATES - ASTM A36
c. BASE, SPLICE, CAP, MOMENT AND STIFF PLATES - ASTM A572, GR 50
d. ANCHOR RODS - ASTM F1554, GRADE 36
e. HIGH STRENGTH BOLTS - ASTM F3125, UNLESS NOTED
f. WELDING ELECTRODES - AWS A5.1 (E70XX)
g. PIPE - ASTM A53, GRADE B
h. HOLLOW STRUCTURAL SECTIONS (HSS) - ASTM A500, GRADE C
i. HEADED ANCHORS - AWS D1.1, TYPE B
2. STEEL CONSTRUCTION SHALL CONFORM TO “SPECIFICATIONS FOR STRUCTURAL
STEEL FOR BUILDINGS” AISC 360.
3. WELDING SHALL CONFORM TO “STRUCTURAL WELDING CODE” AWS D1.1.
4. FOR MISCELLANEOUS STEEL CONSTRUCTION NOT SHOWN ON STRUCTURAL
DRAWINGS, SEE ARCHITECTURAL DRAWINGS.
5. ALL WELDING SHALL BE PERFORMED BY AN AWS CERTIFIED WELDER.
E.MASONRY
1. MATERIALS
a. HOLLOW CONCRETE
MASONRY UNITS (CMU) - ASTM C90, TYPE 1 NORMAL WEIGHT (UNLESS NOTED)
UNIT STRENGTH - 1,900 PSI ON NET AREA
b. MORTAR- ASTM C270, TYPE S
MORTAR STRENGTH - 1,800 PSI IN 28 DAYS
c. GROUT- 28 DAY COMPRESSIVE STRENGTH - ASTM C476, f'c=3,000PSI
d. REINFORCING STEEL - ASTM A615, GRADE 60
e. HORIZONTAL JOINT REINFORCING - ASTM A1064, W1.7, GALV
f. COMPRESSIVE STRENGTH OF MASONRY ASSEMBLAGE - f'm=1,900 PSI (UNLESS
NOTED)
2. MASONRY CONSTRUCTION SHALL CONFORM TO “SPECIFICATIONS FOR MASONRY
STRUCTURES” ASCE 6-05 (ACI 530.1)
3. MINIMUM SPLICES SHALL BE AS FOLLOWS:
#3 TO #5 40 BAR DIA
#6 TO #7 52 BAR DIA
#8 TO #11 60 BAR DIA
4. HORIZONTAL REINFORCING SHALL BE LADDER TYPE AND SHALL BE PLACED IN
EVERY OTHER COURSE UNLESS NOTED.
5. ALL BLOCK SHALL BE PLACED IN STACKED BOND.
6. ALL CORES CONTAINING VERTICAL REINFORCING SHALL BE GROUTED SOLID.
7. ALL VERTICAL REINFORCING SHALL EXTEND TO WITHIN 2” OF TOP OF WALLS.
8. ALL CMU SHALL BE LAID IN FACE SHELL BED OF MORTAR, EXCEPT AT GROUTED
CELL LOCATIONS WHERE CMU SHALL BE PLACED IN FULL BED OF MORTAR .
F.METAL DECK
1. MATERIALS
a. ROOF DECK: 1 1/2”, 20 GAGE WIDE RIB (GALVANIZED) UNLESS NOTED
b. FLOOR DECK: 1 1/2”, 20 GAGE COMPOSITE METAL DECK (GALVANIZED) UNLESS
NOTED
2. ALL METAL DECKING HAS BEEN DESIGNED FOR UNSHORED CONSTRUCTION,
UNLESS NOTED. WHERE POSSIBLE, DECK SHALL EXTEND OVER THREE OR MORE
SUPPORTS.
3. METAL DECK FABRICATION AND INSTALLATION MUST COMPLY WITH STEEL DECK
INSTITUTE (SDI) STANDARDS. DECK MANUFACTURER SHALL BE A MEMBER OF THE
SDI.
4. SUSPENDED CEILINGS, LIGHT FIXTURES, DUCTS, PIPES OR OTHER UTILITIES
SHALL NOT BE SUPPORTED BY THE METAL DECK.
5. PLACE CONDUITS SHOWN ON OTHER DISCIPLINE DRAWINGS ABOVE OR BELOW
CONCRETE ON METAL FLOORS WHENEVER POSSIBLE. CONDUIT PLACED WITHIN
CONCRETE SLABS ON METAL DECK SHALL COMPLY WITH THE LATEST VERSION OF
“THE DESIGN MANUAL FOR COMPOSITE DECKS, FORM DECKS AND ROOF DECKS”.
WHERE CONDUIT MUST BE INSTALLED IN ELEVATED SLABS, THE CONTRACTOR
SHALL NOTIFY THE ENGINEER AND OBTAIN WRITTEN APPROVAL PRIOR TO
INSTALLATION. SUBMIT CONDUIT LAYOUTS FOR CONDUITS PLACED IN CONCRETE
ON METAL DECK FLOORS TO THE ENGINEER FOR REVIEW PRIOR TO INSTALLATION.
G.POST INSTALLED ANCHORS
1. POST-INSTALLED ANCHORS SHALL BE INSTALLED TO RESIST THE MAXIMUM,
TENSION/SHEAR FORCE BASED ON ANCHOR MANUFACTURER'S LITERATURE
AND DIAMETER AND EMBEDMENT SHOWN
2. USE OF ANCHORING SYSTEMS MUST BE APPROVED IN WRITING BY THE
STRUCTURAL ENGINEER OF RECORD PRIOR TO USE.
3. REINFORCING BARS SHALL BE EMBEDDED TO DEVELOP THE YIELD STRENGTH OF
THE BAR.
4. DESIGN OF ALL POST-INSTALLED ANCHORS SHALL BE BASED ON THE CRACKED
CONCRETE DESIGN CONDITION, UNLESS NOTED.
5. ALL POST-INSTALLED ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS.
6. ANCHOR CAPACITY IS DEPENDENT UPON SPACING BETWEEN ADJACENT
ANCHORS AND PROXIMITY OF ANCHORS TO THE EDGE OF CONCRETE OR
MASONRY. INSTALL ANCHORS IN ACCORDANCE WITH SPACING AND EDGE
CLEARANCES INDICATED ON THE DRAWINGS.
7. LOCATE BY NON-DESTRUCTIVE MEANS, AND AVOID ALL EXISTING
REINFORCEMENT PRIOR TO THE INSTALLATION OF ANCHORS. IF THE EXISTING
REINFORCING LAYOUT PROHIBITS THE INSTALLATION OF ANCHORS AS INDICATED
ON THE DRAWINGS, THE CONTRACTOR SHALL NOTIFY THE ENGINEER
IMMEDIATELY.
8. POST-INSTALLED ANCHORS SHALL BE INSTALLED WITH EMBEDMENT DEPTH
NOTED IN SECTIONS/DETAILS UNLESS NOTED.
9. POST-INSTALLED ANCHORS SHALL BE INSPECTED DURING INSTALLATION PER IBC
CHAPTER 17, TABLE 1705.3.
10.ADHESIVE ANCHORS THAT ARE INSTALLED HORIZONTALLY OR UPWARDLY
INCLINED, AND THAT ARE REQUIRED TO RESIST SUSTAINED TENSION LOADS
SHALL BE CONTINUOUSLY INSPECTED DURING INSTALLATION PER ACI 318.
11.INSTALLATION OF ADHESIVE ANCHORS SHALL BE PERFORMED BY PERSONNEL
TRAINED AND QUALIFIED TO INSTALL ADHESIVE ANCHORS.
12.FOR INSTALLATION OF HORIZONTAL AND UPWARDLY INCLINED ADHESIVE
ANCHORS, THE INSTALLER SHALL BE CERTIFIED BY AN ACI/CRSI ADHESIVE
ANCHOR INSTALLER CERTIFICATION PROGRAM OR EQUIVALENT.
H.MISCELLANEOUS
1. DIMENSIONS OF EQUIPMENT OPENINGS, SUPPORTS, PADS, SLAB DEPRESSIONS,
FOUNDATIONS AND ANCHORAGE HAVE BEEN DETERMINED USING SPECIFIC
MANUFACTURER'S EQUIPMENT. FINAL DIMENSIONS SHALL BE VERIFIED WITH THE
ACTUAL EQUIPMENT PURCHASED. DIMENSIONS SHALL BE CHANGED ONLY WITH
APPROVAL OF THE ENGINEER.
2. SEE PLUMBING SHEETS FOR ADDITIONAL UNDERGROUND PIPING NOT SHOWN ON
STRUCTURAL SHEETS.
3. CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS AND EXISTING
CONDITIONS PRIOR TO PROCEEDING WITH THE WORK. VARIATIONS BETWEEN THE
INFORMATION SHOWN ON THE DRAWINGS AND THE ACTUAL EXISTING CONDITIONS
SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER PRIOR TO
PROCEEDING WITH THE WORK.
4. NOTES, TYPICAL DETAILS, AND SCHEDULES APPLY TO ALL STRUCTURAL WORK
UNLESS NOTED. FOR CONDITIONS NOT SPECIFICALLY SHOWN, PROVIDE DETAILS
OF A SIMILAR NATURE. VERIFY APPLICABILITY BY SUBMITTING SHOP DRAWINGS
FOR REVIEW.
5. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH OTHER
DISCIPLINES DRAWINGS. IF THERE IS A DISCREPANCY BETWEEN DRAWINGS, IT IS
THE CONTRACTORS RESPONSIBILITY TO NOTIFY THE ENGINEER PRIOR TO
PERFORMING THE WORK.
6. THE STRUCTURE HAS BEEN DESIGNED TO BE SELF-SUPPORTING AND STABLE
AFTER THE CONSTRUCTION OF THE STRUCTURE HAS BEEN COMPLETED. THE
STABILITY OF THE STRUCTURE PRIOR TO COMPLETION IS SOLELY THE
RESPONSIBILITY OF THE CONTRACTOR. THIS RESPONSIBILITY INCLUDES ALL
RELATED ASPECTS OF CONSTRUCTION ACTIVITY INCLUDING BUT NOT LIMITED TO,
ERECTION METHODS, ERECTION SEQUENCE, TEMPORARY BRACING, FORMS,
SHORING, USE OF EQUIPMENT AND SIMILAR CONSTRUCTION PROCEDURES.
7. DO NOT SCALE DRAWINGS TO OBTAIN DIMENSIONAL INFORMATION.
8. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE CONDITIONS OF THE JOB
SITE INCLUDING MEANS AND METHODS OF CONSTRUCTION AND SAFETY OF
PERSONS AND PROPERTY. THE ENGINEERS PRESENCE OR REVIEW OF WORK AT
THE JOB SITE IS FOR GENERAL COMPLIANCE WITH THE DESIGN INTENT ONLY AND
IS NOT TO BE CONSTRUED AS A REVIEW OF MEANS AND METHODS OF
CONSTRUCTION AND/OR SAFETY METHODS.
9. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING ALLOWABLE
CONSTRUCTION LOADS AND PROTECTING THE COMPLETED OR UNCOMPLETED
STRUCTURE FROM DAMAGE DUE TO TEMPORARY CONSTRUCTION LOADS.
10.IF THE EXISTING FIELD CONDITIONS DO NOT PERMIT THE INSTALLATION OF THE
WORK IN ACCORDANCE WITH THE DETAILS SHOWN, THE CONTRACTOR SHALL
NOTIFY THE ENGINEER IMMEDIATELY.
J.DEMOLITION
1. THE CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS (NEW AND
EXISTING) AND NOTIFY THE ENGINEER OF ANY DISCREPENCIES PRIOR TO
STARTING DEMOLITION.
2. THE CONTRACTOR SHALL COORDINATE ALL DEMOLITION ACTIVITIES WITH THE
CONTRACTING OFFICER.
3. CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN AND INSTALLATION OF
ANY SHORING REQUIRED TO FACILITATE THE DEMOLITION ACTIVITIES.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR DESIGN AND INSTALLATION OF ALL
TEMPORARY DUST PROOFING AND WATERPROOFING REQUIRED TO PREVENT
DEBRIS OR WATER FROM ENTERING AREAS OF THE FACILITY THAT ARE NOT
INCLUDED WITHIN THE WORK. THE CONTRACTOR SHALL COORDINATE THE
LOCATION AND INSTALLATION OF THE TEMPORARY DUST PROOFING AND
WATERPROOFING WITH THE OWNER OR OWNERS REPRESENTATIVE.
5. DAMAGE TO ANY EXISTING BUILDING ELEMENTS TO REMAIN, AS A RESULT OF OR
ASSOCIATED WITH THE DEMOLITION ACTIVITIES, SHALL BE REPAIRED OR
REPLACED AT THE CONTRACTORS EXPENSE.
6. ALL MATERIALS FROM DEMOLITION SHALL BE REMOVED FROM THE SITE AND
PROPERLY DISPOSED OF BY THE CONTRACTOR.
K.STRUCTURAL SPECIAL INSPECTIONS
1. IN ACCORDANCE WITH SECTION 1704 AND 1705 OF THE 2018 INTERNATIONAL
BUILDING CODE AND ALL APPLICABLE STATE AND LOCAL REQUIREMENTS, AN
INDEPENDENT APPROVED AGENCY SHALL MAKE PERIODIC AND/OR CONTINUOUS
INSPECTIONS OF THE CONSTRUCTION PROGRESS IN ACCORDANCE WITH THE
FOLLOWING REQUIREMENTS:
CONCRETE CONSTRUCTION SECTION 1705.3, TABLE 1705.3
WELDING OF REINFORCING BARS SECTION 1705.3.1
SOILS SECTION 1705.6, TABLE 1705.6
STEEL CONSTRUCTION SECTION 1705.2, AISC CHAPTER N
GENERAL STRUCTURAL NOTES
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
P R
O J E
C T
N O
N E
W Y
O R
K D
IS
T
R
IC
T
N E
W Y
O R
K N
Y
S T
V I N
C O
R P
O R
A T
E D
W
E S
T W
E L S
H D
R
IV
E
D O
U G
L A
S S
V
IL
L E
P
A
-3
-8
R A
D
IA
L F
O R
G E
I N
F R
A S
T R
U C
T U
R E
B U
IL
D
IN
G
A
T W
A T
E R
V L
IE
T A
R S
E N
A L
W A
T E
R V
L
IE
T N
E W
Y O
R K
W D
S F
W D
S S
R
N
E F
F
B
IM
/3
R a d ia l F o rg e I n fr a s tr u c tu re
W a te rv lie t A rs e n a l/ P
N W
D
S D
R
F I_
S T
R U
.r v t
/1
/2
:2
:0
P
M
S-001
G E
N E
R A
L S
T R
U C
T U
R A
L N
O T
E S
S C
H A
M B
E R
S
J M c W
IL
L
IA
M S
J C
A R
D
IL
L O S
-0
/1
/2
EXISTING FINISHED
FIRST FLOOR ELEVATION 0'-0" =
SITE DATUM ELEVATION 71'-2"
A
A A
D D
E N
D U
M
/1
/2
10111213141516
E
F
E
10111213141516 0809
20' - 0" ± 20' - 0" ± 20' - 0" ± 20' - 0" ± 20' - 0" ± 20' - 0" ± 20' - 0" ± 20' - 0" ±
C ROTARY
FORGE
L
C R
O T
A
Y
F
O R
G E
L
EXISTING 12'-0"x6'-0"x5'-6" THICK
FOOTING. TOP OF EXISTING
FOOTING ELEVATION (-)1'-2"± (TYP)
EXISTING 13"± WIDE x
4'-0"± DEEP GRADE
BEAM (TYP)
J9
S-303
12" THICK TURNED
DOWN SLAB w/ #5@12
EW T&B TOC EL 0'-0"
HSS4X4 POST
EQ
137' - 11 1/8"
J9
S-303
SIM
EQ
/8
BOLLARD (TYP)
SEE CIVIL SHEETS
x x x x x x x x x x x
FENCE, SEE
CIVIL SHEETS
D1
S-301
D6
S-301
D11
S-301 D16
S-301
6' - 6"
/8
DS-1
DS-2
D6
S-301
DS-2
/2
12' - 1 1/4" 6' - 11 1/2"
/2
DS-4
1' - 10 7/8"
/2
2' - 10 1/8"
DS-3
ELECTRICAL VAULT
G3
S-303
RE-ENTRANT CORNER BARS
AT ELECTRICAL VAULT (TYP)
SEE SHEET S-501
7' - 2" *
M A
T C
H L
IN
E
B
S -1
38' - 0"*
HSS4X4 POST
EQ
16' - 0" 2
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
P R
O J E
C T
N O
1113151719212325
D
C
E
F
G
79 3 1
B
A
PLAN NORTH
N E
W Y
O R
K D
IS
T
R
IC
T
N E
W Y
O R
K N
Y
S T
V I N
C O
R P
O R
A T
E D
W
E S
T W
E L S
H D
R
IV
E
D O
U G
L A
S S
V
IL
L E
P
A
-3
-8
R A
D
IA
L F
O R
G E
I N
F R
A S
T R
U C
T U
R E
B U
IL
D
IN
G
A
T W
A T
E R
V L
IE
T A
R S
E N
A L
W A
T E
R V
L
IE
T N
E W
Y O
R K
W D
S F
W D
S S
R
N
E F
F
A B C D
E F G H
I J K L
B
IM
/3 d ia l F o rg e I n fr a s tr u c tu re
W a te rv lie t A rs e n a l/ P
N W
D
S D
R
F I_
S T
R U
.r v t
/1
/2
:4
:3
A
M
S-114
F
IR
S T
F L O
O R
S T
R U
C T
U R
A L P
L A
N
A R
E A
C
S C
H A
M B
E R
S
J M c W
IL
L
IA
M S
J C
A R
D
IL
L O S
-1
/1
/2
0 4' 8' 16'
1. FOR GENERAL STRUCTURAL NOTES AND LEGEND, SEE SHEET S-001 AND S-002.
2. FOR FIRST FLOOR STRUCTURAL COMPOSITE PLAN, SEE SHEET S-111.
3. FOR CONCRETE TYPICAL DETAILS, SEE SHEET S-501.
GENERAL SHEET NOTES
1/8" = 1'-0"B7
FIRST FLOOR STRUCTURAL PLAN -
AREA C
COORDINATE SIZES AND LOCATIONS OF EQUIPMENT PADS WITH EQUIPMENT PURCHASED.
COORDINATE DUCT SUPPORT LOCATIONS WITH FINAL DUCT ROUTING.
A
A A
D D
E N
D U
M
/1
/2
SEE ENLARGED PLAN ON S-401
A
A
A
01_LEVEL
0' - 0"
10 9
CONTROL ROOM FLOOR
9' - 7 1/2"
EXISTING
CONCRETE COLUMN
EXISTING
CMU WALL
25' - 4"
C8
3' - 4"
1' - 4"*
2 1/2" CONCRETE ON
1 1/2" METAL DECK
OPEN BOTTOM
BOND BEAM
w/ 2 #5 CONT
01_LEVEL
0' - 0"
CONTROL ROOM FLOOR
9' - 7 1/2"
EXISTING
CONCRETE COLUMN
25' - 4"
EXISTING
CMU WALL
C8
2 1/2" CONCRETE ON
1 1/2" METAL DECK
OPEN BOTTOM
BOND BEAM
w/ 2 #5 CONT
8" CMU WALL
w/ #5@48 (TYP)
01_LEVEL
0' - 0"
CONTROL ROOM FLOOR
9' - 7 1/2"
OPEN BOTTOM
BOND BEAM
w/ 2 #5 CONT
C8
2 1/2" CONCRETE ON
1 1/2" METAL DECK
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
P R
O J E
C T
N O
N E
W Y
O R
K D
IS
T
R
IC
T
N E
W Y
O R
K N
Y
S T
V I N
C O
R P
O R
A T
E D
W
E S
T W
E L S
H D
R
IV
E
D O
U G
L A
S S
V
IL
L E
P
A
-3
-8
R A
D
IA
L F
O R
G E
I N
F R
A S
T R
U C
T U
R E
B U
IL
D
IN
G
A
T W
A T
E R
V L
IE
T A
R S
E N
A L
W A
T E
R V
L
IE
T N
E W
Y O
R K
W D
S F
W D
S S
R
N
E F
F
B
IM
/3 d ia l F o rg e I n fr a s tr u c tu re
W a te rv lie t A rs e n a l/ P
N W
D
S D
R
F I_
S T
R U
.r v t
/1
/2
:4
:3
A
M
S-201
C O
N T
R O
L R
O O
M C
M U
W A
L L E
L E
V A
T
IO
N S
S C
H A
M B
E R
S
R W
E
IM
A R
J C
A R
D
IL
L O S
-2
/1
/2
1/4" = 1'-0"S-201
EAST WALL ELEVATIONK9
1/4" = 1'-0"S-201
WEST WALL ELEVATIONK3
0 2' 4' 8' 0 2' 4' 8'
1. FOR GENERAL STRUCTURAL NOTES AND LEGEND, SEE SHEETS S-001 AND S-002.
GENERAL SHEET NOTES
* COORDINATE SIZE AND LOCATION OF OPENING WITH ARCHITECTURAL SHEETS.
1/4" = 1'-0"S-201
NORTH WALL ELEVATIONF2
0 2' 4' 8'
A
A
A
A A
D D
E N
D U
M
/1
2 #5
#5@12
#5@12 EW T&B
#5@12 EF
TOP OF CONCRETE
EL 0'-0"
6" TO EDGE OF
EQUIPMENT BASE
OR ENCLOSURE
1' - 0"
M
IN
3/4" CHAMFER
12" CRUSHED STONE
Ld
01_LEVEL
0' - 0"
EXISTING
FOUNDATION WALL
2 #5
#5@12
#5@12 EW T&B
#5@12 EF
TOP OF CONCRETE
EL 0'-0"
PRECAST CONCRETE VAULT
WALL, SEE ELEC SHEETS
OUTSIDE FACE OF
EXISTING BUILDING
SUBSTATION
SEE ELEC SHEETS
EQUIPMENT PAD
TOP OF PRECAST CONCRETE
VAULT, SEE ELEC SHEETS
Ld
12" CRUSHED STONE
6" EMBD
#5 x 2' - 6" LONG @ 12" OC
EPOXY ANCHOR TO PRECAST
CONCRETE VAULT
2 #5
TOP OF CONCRETE
EL 0'-0"
PRECAST CONCRETE VAULT
WALL, SEE ELEC SHEETS
TOP OF PRECAST CONCRETE
VAULT, SEE ELEC SHEETS
#5@12 EW EF
TURNED DOWN
SLAB BEYOND
1 '- 3 1/2"±
M
IN
3/4" CHAMFER
#5 @ 12" OC EPOXY
ANCHOR TO PRECAST
CONCRETE VAULT
6" EMBD
F
SAWCUT AND REMOVE 10"± SLAB FOR
INSTALLATION OF OIL/WATER SEPARATOR
PIPING. REPLACE SLAB PER SECTION F15/S-112
1' - 1" ±
EXISTING GRADE BEAM
COREDRILL THROUGH GRADE BEAM
FOR INSTALLATION OF UG SANITARY
OIL/WATER SEPARATOR
SEE PLUMBING SHEETS
UG SANITARY PIPING
SEE PLUMBING SHEETS
EXISTING BUILDING WALL
SEE ARCH SHEETS
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
P R
O J E
C T
N O
N E
W Y
O R
K D
IS
T
R
IC
T
N E
W Y
O R
K N
Y
S T
V I N
C O
R P
O R
A T
E D
W
E S
T W
E L S
H D
R
IV
E
D O
U G
L A
S S
V
IL
L E
P
A
-3
-8
R A
D
IA
L F
O R
G E
I N
F R
A S
T R
U C
T U
R E
B U
IL
D
IN
G
A
T W
A T
E R
V L
IE
T A
R S
E N
A L
W A
T E
R V
L
IE
T N
E W
Y O
R K
W D
S F
W D
S S
R
N
E F
F
B
IM
/3 d ia l F o rg e I n fr a s tr u c tu re
W a te rv lie t A rs e n a l/ P
N W
D
S D
R
F I_
S T
R U
.r v t
/1
/2
:4
:3
A
M
S-303
C O
N C
R E
T E
S E
C T
IO
N
S
S C
H A
M B
E R
S
R W
E
IM
A R
J C
A R
D
IL
L O S
-3
/1
/2
3/4" = 1'-0"S-303
SECTIONJ9
3/4" = 1'-0"S-303
SECTIONG3
0 0.5' 1' 2' 3'
0 0.5' 1' 2' 3'
3/4" = 1'-0"S-303
SECTIONG15
0 0.5' 1' 2' 3'
3/4" = 1'-0"S-303
SECTIONA4
0 0.5' 1' 2' 3'
A
A
A A
D D
E N
D U
M
/1
CONTROL ROOM FLOOR
9' - 7 1/2"
CONTROL ROOM ROOF
TOS
18' - 11"
W8
W12 NS/FS
H S
S X
P
O S
T
H S
S X
P
O S
T
1 1/2" METAL ROOF DECK
EXISTING CONTROL
ROOM ROOF DECK
EXISTING CONTROL
ROOM FLOOR DECK
EXISTING C8X11.5
EXISTING 8" BLOCK WALL
OR EXISTING CONCRETE
COLUMN (SEE PLAN)
EXISTING C9X13.4
4' - 8"
3' - 1 5/8"
2 1/2" CONCRETE ON
1 1/2" METAL DECK
x x x x
G R
O U
T
BASE PL 3/4x5x0' - 10" w/ (4) BOLT CONN
3/16
W8
F L
G G
A
HSS4X4
BASE PL 3/4xXxX w/ (4) ANCHOR RODS
3/16HSS4X4
G2
S-402
7 1/2"
L4X3X3/8 (LLH) w/ (2) EPOXY
ANCHORS INTO EXISTING CMU
WALL OR EXISTING CONCRETE
COLUMN AND (2) BOLT CONN
INTO BOTTOM FLANGE OF W8
3 1/2" (TYP)
EXISTING 8" BLOCK WALL
GAUGE
POUR STOP
2" EOS
W8 W10
A
CONTROL ROOM FLOOR
9' - 7 1/2"
CONTROL ROOM ROOF
TOS
18' - 11"
1/2" (TYP)
C9
H S
S X
HSS WP ROOF SYSTEM
SEE ARCH SHEETS
1 1/2" METAL ROOF DECK
3 5/16"±
L5X3X1/4 (LLV)
L5X3X3/8 (NS/FS)
FACE OF HSS SHALL BE
ALIGNED WITH EXISTING
HSS6X4 BEYOND
2 1/2" CONCRETE ON 1 1/2"
METAL DECK (TOTAL SLAB
THICKNESS = 4")
C8
C8
MITER C8's AT
CORNER CONNECTION
8" CMU WALL
GROUT CMU WALL
BELOW HSS COLUMN BENT
FOR BASE PLATE
SEE SECTION G6/S-312
W8
CONTROL ROOM FLOOR
9' - 7 1/2"
CONTROL ROOM ROOF
TOS
18' - 11"
2 1/2" CONCRETE ON 1 1/2"
METAL DECK (TOTAL SLAB
THICKNESS = 4")
C8
8" CMU WALL
FOR BASE PLATE
SEE SECTION B16 THIS SHEET
W12
HSS4X4 POST
W8
W10 BEYOND
ROOF SYSTEM
SEE ARCH SHEETS
1 1/2" METAL ROOF DECK
L5X3X1/4 (LLV)
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
P R
O J E
C T
N O
N E
W Y
O R
K D
IS
T
R
IC
T
N E
W Y
O R
K N
Y
S T
V I N
C O
R P
O R
A T
E D
W
E S
T W
E L S
H D
R
IV
E
D O
U G
L A
S S
V
IL
L E
P
A
-3
-8
R A
D
IA
L F
O R
G E
I N
F R
A S
T R
U C
T U
R E
B U
IL
D
IN
G
A
T W
A T
E R
V L
IE
T A
R S
E N
A L
W A
T E
R V
L
IE
T N
E W
Y O
R K
W D
S F
W D
S S
R
N
E F
F
B
IM
/3 d ia l F o rg e I n fr a s tr u c tu re
W a te rv lie t A rs e n a l/ P
N W
D
S D
R
F I_
S T
R U
.r v t
/1
/2
:4
:3
A
M
S-311
C O
N T
R O
L T
O W
E R
S E
C T
IO
N
S
S C
H A
M B
E R
S
R W
E
IM
A R
J C
A R
D
IL
L O S
-3
/1
/2
3/4" = 1'-0"S-311
SECTIONB15
0 0.5' 1' 2' 3'
3/4" = 1'-0"S-311
SECTIONG2
3/4" = 1'-0"S-311
SECTIONG9
0 0.5' 1' 2' 3'0 0.5' 1' 2' 3'
A A
A
A A
D D
E N
D U
M
/1
CONTROL ROOM FLOOR
9' - 7 1/2"
C8
HSS6X4
COLUMN BENT
C8
8" CMU WALL
GROUT SOLID BELOW
HSS COLUMN BENT
3/4" BASE PL
3/6
HSS6X4
8" CMU WALL
GROUT SOLID BELOW
HSS COLUMN BENT
(2) 13/16"Ø HOLES FOR
3/4"Ø ANCHOR RODS3/4" GROUT
SLAB EDGE AND C8
OMITTED FOR CLARITY 3/16
45°
C8
C8
3/6
TYP
CONTROL ROOM ROOF
TOS
18' - 11"
1 1/2" METAL ROOF DECK
FOR ROOF SYSTEM
SEE ARCH SHEETS
FOR WALL PANEL
SEE ARCH SHEETS
W
L4X4X1/4 CONT
3/16 2-12
3/16 2-12
4"
CONTROL ROOM FLOOR
9' - 7 1/2"
CONTROL ROOM ROOF
TOS
18' - 11"
WF
W
1 1/2" METAL ROOF DECK
FOR ROOF SYSTEM
SEE ARCH SHEETS
HSS4X4
L4X4X1/4 CONT
3/16 2-12
3/16 2-12
4"
3/4" BASE PL
SEE SECTION B15/S-311
W12
2 1/2" CONCRETE ON
1 1/2" METAL DECK
GAUGE POUR STOP
2" EOS
/2
C8
CONTROL ROOM ROOF
TOS
18' - 11"
EXISTING C9X13.4
EXISTING
ROOF PLANK
EXISTING L5X3
1 1/2" METAL ROOF DECK
W
ROOF SYSTEM
SEE ARCH SHEETS
5"
EXISTING WALL
1/4" CONT BENT PL
3/16 2-12
3/16 2-12
CONTROL ROOM FLOOR
9' - 7 1/2"
EXISTING 1 1/2"
TOPPING SLAB
EXISTING PRECAST PLANK
EXISTING C8
INFILL SLAB
7 7/8"±
7 1/2"
5 1/4"±
GAUGE POUR STOP
CONTROL ROOM ROOF
TOS
18' - 11"
EXISTING
ROOF PLANK
EXISTING L5X3 1 1/2" METAL ROOF DECK
WF BEYOND
ROOF SYSTEM
SEE ARCH SHEETS
EXISTING
SLOPED HSS6X4
1/4" CONT BENT PL
C9
EXISTING C9X13.4
SPLICE PL EXISTING C9X13.4
CONTROL ROOM FLOOR
9' - 7 1/2"
EXISTING 1 1/2"
TOPPING SLAB
EXISTING C8
EXISTING C8 (FS)
INFILL SLAB
7 1/2"
5 1/4"±
WF (FS)
C8
EXISTING HSS6X4
COLUMN BENT
CONTROL ROOM FLOOR
9' - 7 1/2"
75.000°
EXISTING SLOPED HSS6X4
EXISTING C8X11.5
C8
8" CMU WALL
CONT L3X3
4" SLAB NOT SHOWN FOR CLARITY
EXISTING CONCRETE
COLUMN BEYOND
CONTROL ROOM FLOOR
9' - 7 1/2"
HSS6X4
COLUMN BENT
C8
8" CMU WALL
GROUT SOLID BELOW
HSS COLUMN BENT
FACE OF HSS SHALL BE
ALIGNED WITH EXISTING
HSS6X4 BEYOND
75.000°
3/16
45°
6"
BASE PL 3/4x6x1' - 0"
3/16
3/16 0
HSS6X4
8" CMU WALL
GROUT SOLID BELOW
HSS COLUMN BENT
(2) 13/16"Ø HOLES FOR
3/4"Ø ANCHOR RODS
3/4" GROUT
3/16
3/16
45°
45°
SLAB EDGE OMITTED FOR CLARITY
CONTROL ROOM FLOOR
9' - 7 1/2"
8" CMU WALL
CONT L3X3
1/4 2-12
1/4 2-12
6"
/2
COORDINATE NOTCH
WITH ARCH SHEETS
C8
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
P R
O J E
C T
N O
N E
W Y
O R
K D
IS
T
R
IC
T
N E
W Y
O R
K N
Y
S T
V I N
C O
R P
O R
A T
E D
W
E S
T W
E L S
H D
R
IV
E
D O
U G
L A
S S
V
IL
L E
P
A
-3
-8
R A
D
IA
L F
O R
G E
I N
F R
A S
T R
U C
T U
R E
B U
IL
D
IN
G
A
T W
A T
E R
V L
IE
T A
R S
E N
A L
W A
T E
R V
L
IE
T N
E W
Y O
R K
W D
S F
W D
S S
R
N
E F
F
B
IM
/3 d ia l F o rg e I n fr a s tr u c tu re
W a te rv lie t A rs e n a l/ P
N W
D
S D
R
F I_
S T
R U
.r v t
/1
/2
:4
:3
A
M
S-312
C O
N T
R O
L R
O O
M S
E C
T
IO
N S
S C
H A
M B
E R
S
R W
E
IM
A R
J C
A R
D
IL
L O S
-3
/1
/2
3/4" = 1'-0"S-312
SECTIONG6
3/4" = 1'-0"S-312
SECTIONL6
3/4" = 1'-0"S-312
SECTIONG16
3/4" = 1'-0"S-312
SECTIONL2
3/4" = 1'-0"S-312
SECTIONG2
0 0.5' 1' 2' 3' 0 0.5' 1' 2' 3'
0 0.5' 1' 2' 3' 0 0.5' 1' 2' 3' 0 0.5' 1' 2' 3'
3/4" = 1'-0"S-312
SECTIONL11
0 0.5' 1' 2' 3'
3/4" = 1'-0"S-312
SECTIONG11
0 0.5' 1' 2' 3'
3/4" = 1'-0"S-312
SECTIONB2
0 0.5' 1' 2' 3' 3/4" = 1'-0"S-312
SECTIONB6
0 0.5' 1' 2' 3' 3/4" = 1'-0"S-312
SECTIONB12
0 0.5' 1' 2' 3'
A
A
A A
D D
E N
D U
M
/1
/2
3/8" SHEAR
TAB, WELDED
F
3' - 0" ±
EXISTING BASEMENT WALL
EXISTING
GRADE BEAM
1' - 1" ± 14' - 6 1/8"
TRENCH FLOOR
W/ #5@12 EW
EL (-) 1' - 11 5/8"
TRENCH FLOOR
W/ #5@12EW
EL (-) 8' - 0"
TOP OF TRENCH WALL
EL 0' - 0"
8"
5' - 6"
EXISTING GRADE
SEE CIVIL SHEETS
EXISTING BUILDING WALL
SEE ARCH SHEETS
COORDINATE END OF
TRENCH WITH ELECTRICAL
CONDUIT DUCTBANK. SEE
ELECTRICAL SHEETS
9' - 0 1/8"
R O
M O
V E
P O
R T
IO
N
O F
B A
S E
M E
N T
W A
L L
REMOVE PORTION
OF BASEMENT WALL
8" CMU WALL8" CMU WALL
#5@12 EW CENTERED
#5 DWLS @ 12 T&B
01_LEVEL
0' - 0"
F
3' - 0" ±
EXISTING BASEMENT WALL
EXISTING
GRADE BEAM
1' - 1" ± 14' - 6 1/8"
TRENCH FLOOR
EL (-) 1' - 11 5/8"
TRENCH FLOOR
W/ #5@12 EW
EL (-) 8' - 0"
TOP OF TRENCH WALL
BEYOND EL 0' - 0"
8"
EXISTING GRADE
SEE CIVIL SHEETS
EXISTING BUILDING WALL
SEE ARCH SHEETS
COORDINATE END OF
TRENCH WITH ELECTRICAL
CONDUIT DUCTBANK. SEE
ELECTRICAL SHEETS
5' - 6"
8" 4' - 10 7/8"
9' - 0 1/8"
/8
REMOVE PORTION
OF BASEMENT WALL 8" CMU WALL8" CMU WALL
3/8" CHECKERED PL
3/8" CHECKERED PL
PIT GUARD (TYP) SEE
DETAIL ON SHEET S-501
PLATE SUPPORT ANGLE
SEE DETAIL ON SHEET S-501
#5@12 EW
CENTERED
#5 DWLS @12 T&B
#5@12 EW
01_LEVEL
0' - 0"
TOP OF TRENCH WALL
EL 0' - 0" (TYP)
5' - 10"
8"8"
TRENCH FLOOR
W/ #5#12 EW
EL (-) 1' - 11 5/8"
TRENCH WALL AND
FLOOR BEYOND
3/8" CHECKERED PL
PIT GUARD (TYP)
SEE DETAIL
ON SHEET S-501
#5@12 EW#5@12 EW
01_LEVEL
0' - 0"
EXISTING GRADE
BEAM BEYOND
TRENCH FLOOR
W/ #5@12 EW
EL (-) 8' - 0"
5' - 10"
8"8"
TOP OF TRENCH WALL
EL 0' - 0" (TYP)
3/8" CHECKERED PL
PIT GUARD (TYP)
SEE DETAIL ON SHEET S-501
#5 DWLS @12
#5@12
CENTERED
#5 DWLS @12
#5@12
CENTERED
01_LEVEL
0' - 0"
TOP OF TRENCH WALL
EL (-) 0' - 1/2"
TRENCH FLOOR
EL (-) 1' - 11 5/8"
REMOVE WALL AT
END OF TRENCH
EXISTING CMU WALL
01_LEVEL
0' - 0"
TOP OF TRENCH WALL
EL (-) 0' - 1/2"
TRENCH FLOOR
EL (-) 1' - 11 5/8"
EXISTING TRENCH
ENDWALL
EXISTING CMU WALL
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
P R
O J E
C T
N O
N E
W Y
O R
K D
IS
T
R
IC
T
N E
W Y
O R
K N
Y
S T
V I N
C O
R P
O R
A T
E D
W
E S
T W
E L S
H D
R
IV
E
D O
U G
L A
S S
V
IL
L E
P
A
-3
-8
R A
D
IA
L F
O R
G E
I N
F R
A S
T R
U C
T U
R E
B U
IL
D
IN
G
A
T W
A T
E R
V L
IE
T A
R S
E N
A L
W A
T E
R V
L
IE
T N
E W
Y O
R K
W D
S F
W D
S S
R
N
E F
F
B
IM
/3 d ia l F o rg e I n fr a s tr u c tu re
W a te rv lie t A rs e n a l/ P
N W
D
S D
R
F I_
S T
R U
.r v t
/1
/2
:4
:3
A
M
S-321
T R
E N
C H
S E
C T
IO
N
S
S C
H A
M B
E R
S
R W
E
IM
A R
J C
A R
D
IL
L O S
-3
/1
/2
1/2" = 1'-0"S-321
SECTIONJ4
1/2" = 1'-0"S-321
SECTIONB4
0 1' 2' 4'
0 1' 2' 4'
1/2" = 1'-0"S-321
SECTIONJ11
1/2" = 1'-0"S-321
SECTIONC11
1/2" = 1'-0"S-321
SECTIOND16
1/2" = 1'-0"S-321
SECTIONK16
* COORDINATE DEPTH OF TRENCH FLOOR WITH ELECTRICAL SHEETS.
* COORDINATE DEPTH OF TRENCH FLOOR WITH ELECTRICAL SHEETS.
0 1' 2' 4'
0 1' 2' 4'
* COORDINATE DEPTH OF TRENCH FLOOR WITH ELECTRICAL SHEETS.
** TRENCH FLOOR ELEVATION SHALL MATCH EXISTING TRENCH FLOOR ELEVATION.
** TRENCH FLOOF ELEVATION SHALL MATCH EXISTING TRENCH FLOOR ELEVATION.
** TRENCH FLOOF ELEVATION SHALL MATCH EXISTING TRENCH FLOOR ELEVATION.
0 1' 2' 4'
** TRENCH FLOOF ELEVATION SHALL MATCH EXISTING TRENCH FLOOR ELEVATION.
** TRENCH FLOOF ELEVATION SHALL MATCH EXISTING TRENCH FLOOR ELEVATION.
0 1' 2' 4'
A
A
A
A
A
A A
D D
E N
D U
M
/1
10111213
8' - 3 1/2" 16' - 0 1/2"
20' - 0" ± 20' - 0" ± 20' - 0" ± 20' - 0" ± 20' - 0" ±
64' - 11 1/2" ±
/8
5' - 5" ±
F
IE
L D
V E
R
IF
Y
EXISTING 8" BLOCK WALL (TYP)
EXISTING CONCRETE
COLUMN (TYP)
EXISTING CORNER
CONCRETE COLUMN
EXISTING CORNER
CONCRETE COLUMN
CMU WALL
SEE ARCH SHEETS
HSS4X4 POST UP
TO EL 9' - 3 1/2"
HSS4X4 POST UP
TO EL 9' - 3 1/2"
T Y
P
T Y
P
B4
S-321
EXISTING 13"± WIDE x 4'-6"± DEEP
GRADE BEAM
K16
S-321
J4
S-321
D16
S-321
/4
E X
IS
T
IN
G
T R
E N
C H
W
ID
T H
1' - 7 5/8" ±
WIDTH OF
EXISTING
TRENCH WALL
REMOVE WALL AT
END OF TRENCH
SEE SECTION D16/S-321
REMOVE PORTION OF BASEMENT WALL
SEE SECTIONS B4/S-321 AND J4/S-321
S-201
K3
S-201
K9
S-201F2
25' - 4"
(TYP)
3' - 0" ±
(TYP)
3' - 0" ±
F
B4
S-321
20' - 0" ±
/1
F
IE
L
D V
E R
IF
Y
EXISTING 8" BLOCK WALL (TYP)
(ELECTRIC SWITCH ROOM)
EXISTING CORNER
CONCRETE COLUMN
EXISTING CORNER
CONCRETE COLUMN
HSS4X4 POST UP
TO EL 9' - 3 1/2"
EXISTING 13"± WIDE x 4'-6"± DEEP
GRADE BEAM
K16
S-321
4' - 4" 5' - 10"
4' - 6"
5 1/2"
J4
S-321
J11
S-321
C11
S-321
D16
S-321
B3
S-401
/8
3/8" CHKD PL
01_LEVEL
0' - 0"
REMOVE 1' - 7 5/8"
THICK WALL AT
END OF TRENCH
/8
4' - 10 7/8" ±
EXISTING
TRENCH BEYOND
EXISTING
CONCRETE COLUMN EXISTING
CONCRETE COLUMN
EXISTING
CMU WALL
6' - 2 7/8"
8" 8"
TOP OF TRENCH WALL
EL 0' - 0"
3/8" CHECKERED PL
PIT GUARD, SEE DETAIL
ON SHEET S-501
PLATE SUPPORT ANGLE
SEE DETAIL ON SHEET S-501
#5@12 EW
#5@12 EW
CENTERED (TYP)
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
P R
O J E
C T
N O
1113151719212325
D
C
E
F
G
79 3 1
B
A
PLAN NORTH
N E
W Y
O R
K D
IS
T
R
IC
T
N E
W Y
O R
K N
Y
S T
V I N
C O
R P
O R
A T
E D
W
E S
T W
E L S
H D
R
IV
E
D O
U G
L A
S S
V
IL
L E
P
A
-3
-8
R A
D
IA
L F
O R
G E
I N
F R
A S
T R
U C
T U
R E
B U
IL
D
IN
G
A
T W
A T
E R
V L
IE
T A
R S
E N
A L
W A
T E
R V
L
IE
T N
E W
Y O
R K
W D
S F
W D
S S
R
N
E F
F
A B C D
E F G H
I J K L
B
IM
/3 d ia l F o rg e I n fr a s tr u c tu re
W a te rv lie t A rs e n a l/ P
N W
D
S D
R
F I_
S T
R U
.r v t
/1
/2
:4
:3
A
M
S-401
E N
L A
R G
E D
P L A
N S
S C
H A
M B
E R
S
J M c W
IL
L
IA
M S
J C
A R
D
IL
L O S
-4
/1
/2
1/4" = 1'-0"F8
CONTROL ROOM FIRST FLOOR ENLARGED
PLAN - PARTIAL AREAS C AND D
0 2' 4' 8'
1. FOR GENERAL STRUCTURAL NOTES AND LEGEND, SEE SHEET S-001 AND S-002.
2. FOR FIRST FLOOR STRUCTURAL COMPOSITE PLAN, SEE SHEET S-111.
3. FOR CONCRETE TYPICAL DETAILS, SEE SHEET S-501.
GENERAL SHEET NOTES
1/4" = 1'-0"A11
CONTROL ROOM TRENCH PLAN
0 2' 4' 8'
1/2" = 1'-0"S-401
SECTIONB3
0 1' 2' 4'
A
A A
D D
E N
D U
M
/1
G1
S-302
8' - 3 1/2" 15' - 0"
/8
EXISTING HSS6X4X1/4
POST UP (TYP UN)
EXISTING BUILT-UP
COLUMN (TYP UN)
EXISTING
HSS4X4X1/4 POST
EXISTING
HSS4X4X1/4 POST
EXISTING 8" PRECAST
PLANK WITH 1 1/2" TOPPING
EXISTING 8" CMU
WALL BELOW
EXISTING C8X11.5
EXISTING C8X11.5
EXISTING SUPERVISOR'S ROOM
/8
(E X
IS
T
IN
G
C O
N T
R O
L R
O O
M
20' - 0" ± 20' - 0" ± 20' - 0" ± 20' - 0" ± 20' - 0" ±
B15
S-311
28' - 0" ± (EXISTING CONTROL ROOM)
HSS4X4 POST UP
FROM EL 0' - 2"
HSS4X4 POST UP
TO EL 18' - 11"
/8
B15
S-311HSS4X4 POST UP
FROM EL 0' - 2"
HSS4X4 POST UP
TO EL 18' - 11"
S P
A N
D E
C K
S P
A N
D E
C K
2 1/2" CONCRETE ON 1 1/2"
METAL DECK (TOTAL SLAB
THICKNESS = 4")
HSS6X4 COLUMN BENT
POST UP TO EL 18' - 11"
HSS4X4 POST UP
TO EL 18' - 11"
L-1
G9
S-311
G2
S-311
EXISTING CONCRETE
COLUMN BELOW
1 255/256"
G16
S-312
G6
S-312
G2
S-312
E O
S
B6
S-312
B2
S-312
G11
S-312
5' - 0"
29' - 7 5/8"
4' - 7 5/8"
C8X11.5
C X
.5
2" EOS
B12
S-312
1 1/2"x6" NOTCH
HSS6X4 COLUMN BENT
POST UP TO EL 18' - 11"
W X
W12X30 W12X30
W X
W X
CMU BEARING
WALL BELOW
W12X30
REMOVE STEEL POST
CONTROL ROOM FLOOR
9' - 7 1/2"
EXISTING C8X11.5
2 1/2" CONCRETE ON
1 1/2" METAL DECK4 63/128"
6"
W8
3/8" BENT PL w/
(2) BOLT CONN EACH LEG
L4X3X3/8 (LLH) w/ (2) EPOXY
ANCHORS INTO EXISTING CMU
WALL AND (2) BOLT CONN
INTO BOTTOM FLANGE OF W8
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
P R
O J E
C T
N O
1113151719212325
D
C
E
F
G
79 3 1
B
A
PLAN NORTH
N E
W Y
O R
K D
IS
T
R
IC
T
N E
W Y
O R
K N
Y
S T
V I N
C O
R P
O R
A T
E D
W
E S
T W
E L S
H D
R
IV
E
D O
U G
L A
S S
V
IL
L E
P
A
-3
-8
R A
D
IA
L F
O R
G E
I N
F R
A S
T R
U C
T U
R E
B U
IL
D
IN
G
A
T W
A T
E R
V L
IE
T A
R S
E N
A L
W A
T E
R V
L
IE
T N
E W
Y O
R K
W D
S F
W D
S S
R
N
E F
F
A B C D
E F G H
I J K L
B
IM
/3 d ia l F o rg e I n fr a s tr u c tu re
W a te rv lie t A rs e n a l/ P
N W
D
S D
R
F I_
S T
R U
.r v t
/1
/2
:4
:3
A
M
S-402
E N
L A
R G
E D
P L A
N S
S C
H A
M B
E R
S
J M c W
IL
L
IA
M S
J C
A R
D
IL
L O S
-4
/1
/2
0 2' 4' 8'1/4" = 1'-0"F2
CONTROL ROOM SECOND FLOOR
ENLARGED PLAN - AREA C AND D
• TOP OF CONTROL ROOM SLAB ELEVATION SHALL MATCH EXISTING CONTROL ROOM
FINISHED FLOOR ELEVATION 9' - 7 1/2".
• TOP OF STEEL (-) 4" (UNLESS NOTED).
3/4" = 1'-0"S-402
SECTIONG2
0 0.5' 1' 2' 3'
A
A A
D D
E N
D U
M
/1
EXISTING C9X13.4EXISTING C9X13.4
EXISTING C9X13.4 EXISTING C9X13.4
E X
IS
T
IN
G
C X
.4
E X
IS
T
IN
G
C X
.4
E X
IS
T
IN
G
C X
.4
E X
IS
T
IN
G
C X
.4
E X
IS
T
IN
G
C X
.4
E X
IS
T
IN
G
C X
.4
EXISTING HSS6X4X1/4
POST UP FROM SECOND
FLOOR (TYP UN)
/8
EXISTING BUILT-UP
COLUMN (TYP UN)
EXISTING HSS4X4X1/4
POST UP FROM SECOND FLOOR
EXISTING 4"
PRECAST PLANK
EXISTING 4"
PRECAST PLANK
EXISTING HSS4X4X1/4
POST UP FROM SECOND FLOOR
EXISTING SLOPED
HSS6X4X1/4 POST UP
FROM SECOND FLOOR EXISTING SLOPED
HSS6X4X1/4 POST UP
FROM SECOND FLOOR
EXISTING SUPERVISOR'S ROOM ROOF
/8
(E X
IS
T
IN
G
C O
N T
R O
L R
O O
M
20' - 0" ± 20' - 0" ± 20' - 0" ± 20' - 0" ± 20' - 0" ±
B15
S-311
27' - 11 1/8" ± (EXISTING CONTROL ROOM)
B15
S-311
HSS4X4 POST UP
FROM EL 9' - 3 1/2"
HSS4X4 POST UP
FROM EL 9' - 3 1/2"
SPAN
DECK
SPAN
DECK
1 1/2" METAL ROOF DECK
HSS6X4 COLUMN BENT POST
UP FROM SECOND FLOOR
HSS4X4 POST UP
FROM SECOND
FLOOR
L2
S-312
G9
S-311
G2
S-311
G16
S-312
L6
S-312
29' - 7 5/8"4 EQ SPA = 23' - 3 1/2"
2 EQ SPA = 12' - 8 1/8"
L11
S-312 C9X13.4
2 SPA @ 5' - 11 3/4"= 11' - 11 1/2"5' - 0"
W10X30 W10X30
W X
W X
W X
W X
W X
W X
W X
W X
W X
REMOVE STEEL POST
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
P R
O J E
C T
N O
1113151719212325
D
C
E
F
G
79 3 1
B
A
PLAN NORTH
N E
W Y
O R
K D
IS
T
R
IC
T
N E
W Y
O R
K N
Y
S T
V I N
C O
R P
O R
A T
E D
W
E S
T W
E L S
H D
R
IV
E
D O
U G
L A
S S
V
IL
L E
P
A
-3
-8
R A
D
IA
L F
O R
G E
I N
F R
A S
T R
U C
T U
R E
B U
IL
D
IN
G
A
T W
A T
E R
V L
IE
T A
R S
E N
A L
W A
T E
R V
L
IE
T N
E W
Y O
R K
W D
S F
W D
S S
R
N
E F
F
A B C D
E F G H
I J K L
B
IM
/3 d ia l F o rg e I n fr a s tr u c tu re
W a te rv lie t A rs e n a l/ P
N W
D
S D
R
F I_
S T
R U
.r v t
/1
/2
:4
:3
A
M
S-403
E N
L A
R G
E D
P L A
N S
S C
H A
M B
E R
S
J M c W
IL
L
IA
M S
J C
A R
D
IL
L O S
-4
/1
/2
0 2' 4' 8'1/4" = 1'-0"H8
CONTROL ROOM ROOF FRAMING
ENLARGED PLAN - AREAS C AND D
A
A A
D D
E N
D U
M
/1
| Sheets |
| S-001 - GENERAL STRUCTURAL NOTES |
| S-114 - FIRST FLOOR STRUCTURAL PLAN - AREA C |
| S-201 - CONTROL ROOM CMU WALL ELEVATIONS |
| S-303 - CONCRETE SECTIONS |
| S-311 - CONTROL TOWER SECTIONS |
| S-312 - CONTROL ROOM SECTIONS |
| S-321 - TRENCH SECTIONS |
| S-401 - ENLARGED PLANS |
| S-402 - ENLARGED PLANS |
| S-403 - ENLARGED PLANS |
| S-501 - CONCRETE TYPICAL DETAILS |