This solicitation is for construction services for a General Instruction Building at Thayer Swing in New York. The Army Corps of Engineers Engineering District New York is seeking bids to construct a new building under solicitation number W912DS21R0005. Offerors must submit bids by April 30, 2021 for consideration. The selected contractor will be responsible for all aspects of construction according to the specifications provided. This includes site work, foundations, structural components, exterior walls and roofing. Mechanical, electrical and plumbing systems must also be installed along with finishes, fixtures and related site work. The anticipated period of performance is 420 calendar days from the notice to proceed.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR PROPOSAL
GENERAL INSTRUCTION BUILDING
THAYER SWING
FY21 UMMCA
PROJECT NUMBER 094363
Solicitation No. W912DS-21-R-0005
Part 5 – Prescriptive Specifications
United States Military Academy
West Point, NY
1 APRIL 2021
U.S. ARMY CORPS
OF ENGINEERS
NEW YORK DISTRICT
General Instruction Building, Thayer Swing FY21 UMMCA Project No. 094363 U.S. Military Academy, West Point, NY
Part 5 Table of Contents
PART 5 – 01 10 00 STATEMENT OF WORK - PRESCRIPTIVE SPECIFICATIONS
5-1 Sprung Instant Structure 5-1A Sprung Drawings 5-1B Stressed Membrane Structure Prescriptive Criteria 5-1C Sprung Sample Guarantee 5-2 Monaco Enterprises 5-2A Monaco Catalog Cut Sheets 5-2B Fire Alarm Matrix 5-3C Script for fire alarm and mass notification messages 5-3 Best Lock 5-3A BEST: Standard Cores and Keys 5-4 C Squared Systems 5-5 Electro Industries 5-6 Identiv 5-7 City Light & Power 5-7A Service Application Form 5-7B Electric Service Connection Standards Manual 5-7C Proposal for the Government Furnished Government Installed Scope of Work 5-8 American Water 5-8A Capital Service Request Form 5-8B Design Guide for Water and Wastewater Facilities 5-8C Proposal for the Government Furnished Government Installed Scope of Work
The supplies and services included in Part 5 are prescriptive specifications because there is only one responsible source, and no other supplies or services will satisfy the Government’s requirements.
For the supplies and services included in Part 5, substitutions are prohibited.
Variations from Part 5 prescriptive requirements require Contracting Officer approval pursuant to contract Clause FAR 52.236-21 Specifications and Drawings for Construction. Refer to Section 01 33 00 paragraph 1.9.
105.1
'-0
8 PANELS @ 15'-0" = 120'-0"
CB
2 3 4 5 6 7 8 9
A
B
C
D
E
F
G
H
FREESTANDING
FRAME, GLAZING &
DOORS BY OTHERS
(14'0X19'0)
FREESTANDING
FRAME, GLAZING &
DOORS BY OTHERS
(14'0x19'0)
WINDOW
(7'-1"x5'-3")
WINDOW
(7'-1"x5'-3")
WINDOW
(7'-1"x5'-3")
WINDOW
(7'-1"x5'-3")
WINDOW
(7'-1"x5'-3")
WINDOW
(7'-1"x5'-3")
WINDOW
(7'-1"x5'-3")
WINDOW
(7'-1"x5'-3")
WINDOW
(7'-1"x5'-3")
WINDOW
(7'-1"x5'-3")
WINDOW
(7'-1"x5'-3")
WINDOW
(7'-1"x5'-3")
WINDOW
(7'-1"x5'-3")
WINDOW
(7'-1"x5'-3")
WINDOW
(7'-1"x5'-3")
10'-0"w HOOD (4"x3") C/W DOUBLE PERSONNEL DOOR (6'-0"x7'-0") (W/
TOP LITES & HOOD LIGHT)
CB CB CB
WINDOW
(3'-3"x3'-3")
WINDOW
(3'-3"x3'-3")
U/S BASEPLATE
0"
STRUCTURE PEAK
38'-6"
105.1
CB
2 3 4 5 6 7 8 9
CB CB CB
MEMBRANE
FLAT END WALL
C/W UPRIGHTS
MEMBRANE
FLAT END WALL
C/W UPRIGHTS
SANDSTONE
MEMBRANE
PANTONE COOL
GRAY
5C/#B2B4B3
U/S BASEPLATE
0"
STRUCTURE PEAK
38'-6"
105.1
123456789
SPRUNG LOGO
SUBJECT TO GOVERNMENT APPROVAL
CB CB CB CB
MEMBRANE
FLAT END WALL
C/W UPRIGHTS MEMBRANE
FLAT END WALL
C/W UPRIGHTS
SANDSTONE
MEMBRANE
PANTONE COOL
GRAY
5C/#B2B4B3
U/S BASEPLATE
0"
STRUCTURE PEAK
38'-6"
A B C D E F G H
12'-6" 8'-10" 18'-0" 11'-4" 18'-0" 8'-10" 12'-6"
90'-0"
26°
5'-8" 5'-8"
8"x12" ALUM.
I BEAM
PANTONE COOL
GRAY
5C/#B2B4B3
SANDSTONE
MEMBRANE
MEMBRANE
FLAT END WALL
C/W UPRIGHTS
'-4
/8
U/S BASEPLATE
0"
STRUCTURE PEAK
38'-6"
ABCDEFGH
5'-8"
12'-6" 8'-10" 18'-0" 11'-4" 18'-0" 8'-10" 12'-6"
90'-0"
26°
5'-8"
PANTONE COOL
GRAY
5C/#B2B4B3
SANDSTONE
MEMBRANE
8"x12" ALUM.
I BEAM
MEMBRANE
FLAT END WALL
C/W UPRIGHTS
TOLL FREE: 1-800-528-9899
(403) 601-2292 www.sprung.com
DRAWN BY:DATE:
Th is d ra w in g is p ro te ct ed b y co py rig ht in th e
U ni te d
St at es o f A m er ic a, C an ad a an d al l o th er c ou nt rie s of th e w or ld
. I t, an d al l o f t he d es ig ns
, t ec hn ic al d at a an d en gi ne er in g se rv ic es re pr es en te d by it a nd o rig in at ed o r r en de re d by
SP
R U
N G
IN
ST
A N
T S
TR
U
C
TU
R
ES
IN
C
. a re th e ex cl us iv e pr op er ty o f ©
SP
R U
N G
IN
ST
A N
T
ST
R U
C
TU
R
ES
IN
C
. a nd m us t n ei th er b e us ed in m an uf ac tu rin g no r d is cl os ed n or re pr od uc ed in w ho le o r i n pa rt ex ce pt w ith th e pr io r w rit te n co ns en t o f ©
SP
R
U N
G
IN
ST
A
N T
ST
R
U C
TU
R
E S
IN
C
. A ny c op yi ng o f t hi s dr aw in g in w ho le o r i n pa rt an d an y us e of it to c on st ru ct th e su bj ec t m at te r i llu st ra te d in it w ith ou t p rio r w rit te n pe rm is si on o f ©
SP
R U
N G
IN
ST
A N
T
ST
R U
C
TU
R
ES
IN
C
. i s pr oh ib ite d.
-0
-1
:2
:2
P
M I:
\2 D ra w in g s -F u ll
S iz e \R
-1
\R
-1
-R
.r v t
FLOOR PLAN &
ELEVATIONS
P A
T T
O N
C O
M P
LE
X
U .S
M
IL
IT
A R
Y A
C A
D E
M Y
W E
S T
P O
IN
T
01/28/2021 P. DUMONT
R21-105.0
W E
S T
P O
IN
T
, N E
W Y
O R
K , U
N
IT
E D
S T
A T
E S
0" x
0"
SIGNATURE SERIES
ACCESSORIES
CATEGORY TYPE SIZE COMMENT COUNT
GLAZING FE GLAZING 14'-7" x 18'-11 1/2" FRAME ONLY 2
WINDOW FLAT END 3'-3" x 3'-3" 4
WINDOW FLAT END 7'-1" x 5'-3" 15
1/16" = 1'-0"105.0
OPEN PLAN VIEW1
GENERAL NOTES:
1. ALL PERSONNEL DOORS C/W PANIC
HARDWARE & HOODS, AS NOTED.
2. STRUCTURE TO BE INSULATED WITH
FIBERGLASS BATT INSULATION C/W INNER
LINER, TO PEAK.
3. INNER & OUTER MEMBRANE TO BE
FINISHED TO CONCRETE USING ALUM. FLAT
BAR
4. STRUCTURE MEMBRANE MEETS:
NFPA 701, CALIFORNIA STATE FIRE MARSHAL,
ASTM E84, CAN/ULC-S-109 & CAN/ULC-S-102
SPECIFICATIONS.
5. THIS STRUCTURE IS DESIGNED TO
SHED/RELEASE SNOW. THE PERIMETER OF
THE STRUCTURE SHALL BE KEPT CLEAR.
6. WHEN DESIGNING A HEATING,
VENTILATION OR AIR CONDITIONING SYSTEM
FOR ANY TYPE OF BUILDING, IT IS
IMPORTANT TO ENSURE THAT THIS SYSTEM
INTAKES MORE AIR THAN IS BEING
EXHAUSTED AT ANY GIVEN TIME. THIS
PROCESS WILL RESULT IN A POSITIVE
PRESSURE BEING MAINTAINED.
CONVERSELY, IF NEGATIVE PRESSURE
EXISTS WITHIN THE STRUCTURE, IT WILL BE
DIFFICULT TO OPEN DOORS AND MOISTURE
WILL BE DRAWN INTO THE STRUCTURE.
7. ALL INTERIOR WALLS & PARTITIONS (IF
APPLICABLE) TO BE FREE STANDING &
INDEPENDENT OF SPRUNG STRUCTURE.
PERSONNEL DOORS
CATEGORY TYPE HOOD WIDTH BEAM DOOR SIZE COMMENT SWING COUNT
HOOD DPD 10'-0" 4"x3" 6'-0"x7'-0" TOP LITES STANDARD 1
CB = CABLE BRACING
1/16" = 1'-0"105.0
FRONT ELEVATION2
1/16" = 1'-0"105.0
REAR ELEVATION3 1/16" = 1'-0"105.0
LEFT ELEVATION6
1/16" = 1'-0"105.0
RIGHT ELEVATION5
COLORS ON THESE ELEVATIONS MAY VARY
SIGNIFICANTLY DEPENDING ON PRINTER OR
MONITOR. PLEASE REFER TO MEMBRANE
SAMPLES FOR ACTUAL COLORS.
REV. MM/DD/YY BY DESCRIPTION
2 02/09/21 BP REVISE MEMBRANE &
ACCESSORIES
3 02/19/21 NB REMOVE COLOR OPTION 1
DRAWING APPROVAL
APPROVED
DATE:
APPROVED W/ CHANGES NOTED
CONFIRMATION OF DESIGN LOADS AT
SITE PER THE LOCAL BUILDING DEPT.
SIGNATURE:
BUILDING CODE
w/ YEAR:
WIND LOAD:
EXPOSURE: RISK:
SNOW LOAD:
105.0
EXTERIOR VIEW4
NOTE TO BIDDERS: THIS DRAWING IS
PROVIDED ONLY TO CONVEY INTENT FOR
ARCHITECTURAL MEMBRANE COLOR AND
PATTERNS. ALL DIMENSIONS, STRUCTURAL
ELEMENTS, DETAILS AND OPENINGS DEPICTED ON
THIS DRAWING ARE SUBJECT TO REVISION
BY THE DESIGNER OF RECORD. THE SELECTED
PANTONE COOL GRAY IS A PREMIUM COLOR.
PROVIDE PNATONE COOL GRAY AS DEPICTED
U/S BASEPLATE
0"
STRUCTURE PEAK
38'-6"
90'-0"
A H
26°8"x12" ALUM.
I BEAM
10'-0"
'-4
/8
4"x3" HOLLOW
ALUM. BEAM
ARCHITECTURAL
MEMBRANE
INTERIOR
MEMBRANE
8x12 ALUM.
I BEAM
EXTERIOR
ARCH CAP
INTERIOR
ARCH CAP
FIBERGLASS
INSULATION (R30)
TOLL FREE: 1-800-528-9899
(403) 601-2292 www.sprung.com
DRAWN BY:DATE:
Th is d ra w in g is p ro te ct ed b y co py rig ht in th e
U ni te d
St at es o f A m er ic a, C an ad a an d al l o th er c ou nt rie s of th e w or ld
. I t, an d al l o f t he d es ig ns
, t ec hn ic al d at a an d en gi ne er in g se rv ic es re pr es en te d by it a nd o rig in at ed o r r en de re d by
SP
R U
N G
IN
ST
A N
T S
TR
U
C
TU
R
ES
IN
C
. a re th e ex cl us iv e pr op er ty o f ©
SP
R U
N G
IN
ST
A N
T
ST
R U
C
TU
R
ES
IN
C
. a nd m us t n ei th er b e us ed in m an uf ac tu rin g no r d is cl os ed n or re pr od uc ed in w ho le o r i n pa rt ex ce pt w ith th e pr io r w rit te n co ns en t o f ©
SP
R
U N
G
IN
ST
A
N T
ST
R
U C
TU
R
E S
IN
C
. A ny c op yi ng o f t hi s dr aw in g in w ho le o r i n pa rt an d an y us e of it to c on st ru ct th e su bj ec t m at te r i llu st ra te d in it w ith ou t p rio r w rit te n pe rm is si on o f ©
SP
R U
N G
IN
ST
A N
T
ST
R U
C
TU
R
ES
IN
C
. i s pr oh ib ite d.
-0
-1
:2
:4 P
M I:
\2 D ra w in g s -F u ll
S iz e \R
-1
\R
-1
-R
.r v t
SECTIONS & DETAILS
P A
T T
O N
C O
M P
LE
X
U .S
M
IL
IT
A R
Y A
C A
D E
M Y
W E
S T
P O
IN
T
01/28/2021 P. DUMONT
R21-105.1
W E
S T
P O
IN
T
, N E
W Y
O R
K , U
N
IT
E D
S T
A T
E S
0" x
0"
SIGNATURE SERIES
3/32" = 1'-0"105.1
SECTION 90'-0" INSULATED STRUCTURE1
1/4" = 1'-0"105.1
SECTION 10'-0" HOOD (4x3)3
REV. MM/DD/YY BY DESCRIPTION
2 02/09/21 BP REVISE MEMBRANE &
ACCESSORIES
3 02/19/21 NB REMOVE COLOR OPTION 1
105.1
EXTERIOR VIEW 22
3" = 1'-0"105.1
8x12 INSULATED BEAM SECTION4
NOTE TO BIDDERS: THIS DRAWING IS
PROVIDED ONLY TO CONVEY INTENT FOR
ARCHITECTURAL MEMBRANE COLOR AND
PATTERNS. ALL DIMENSIONS, STRUCTURAL
ELEMENTS, DETAILS AND OPENINGS DEPICTED ON
THIS DRAWING ARE SUBJECT TO REVISION
BY THE DESIGNER OF RECORD. THE SELECTED
PANTONE COOL GRAY IS A PREMIUM COLOR.
PROVIDE PNATONE COOL GRAY AS DEPICTED
SPECIFICATION CRITERIA FOR STRESSED MEMBRANE STRUCTURES
(USMA West Point General Instruction Building, Thayer Swing)
1. The structure must be a Stressed Membrane Structure.
2. The entire roof slope of the structure, including the peak, shall have a minimum slope of 26 degrees.
3. No exterior guy ropes or cables shall be used for anchoring the structure.
4. There will be no exposed exterior horizontal purlins.
5. The structure shall be completely clear-span with no interior supports of any description.
6. Any required miscellaneous steel components such as anchor bolts, cable bracing, base assemblies or attachment brackets must be zinc plated or galvanized.
7. All bolts used shall be zinc plated or galvanized with a minimum of Grade 5 specification.
8. All personnel doors and windows must be installed in such a way that the vertical and horizontal tension on the architectural membrane is maintained, at all times.
9. The main structural support beams shall be continuous from the ground seal to the peak and manufactured in such a way that no eave will exist.
10. The structure shall be designed to meet the wind loads as outlined IBC 2018, 113mph, exposure ‘C’, Risk Category II.
11. The stressed membrane structure must be designed to shed all snow off the roof. (In accordance with the Alternative Design Section of the building code.)
12. All main structural arches and connecting purlins shall be 100% ALUMINUM utilizing a single I beam configuration and not to exceed 12 inches in depth.
13. All structural aluminum components must have the following minimum structural and mechanical properties.
Tension Shear Bearing
Ultimate Yield Elongation Ultimate Yield Ultimate
KSI KSI % KSI KSI KSI
38 35 10 23 21 80
14. The architectural membrane must not rest upon any part of the substructure and shall be installed in the aluminum frame and tensioned both vertically and horizontally to prevent wear and abrasion. Horizontal tension shall be maintained mechanically with horizontal purlins/spreaders that require no ongoing maintenance. The membrane shall be tensioned to a predetermined level of 20 pounds per lineal inch (pli) in the horizontal direction and 10 pounds per lineal inch (pli) in the vertical direction creating a tension field within the membrane.
15. All aluminum used in the structure shall carry a pro-rata guarantee of not less than 50 years.
16. The architectural membrane, when assembled and tensioned, shall be absolutely wrinkle free, and shall remain so indefinitely in hot and cold temperatures.
17. The structure shall be modular in design consisting of individual membrane panels which do not exceed 15’ in width on the main center modules. (This minimizes future costs of repair and replacement of localized membrane damage and allows future expansion/reduction in reasonable sized modules.)
18. The structure shall be designed so that any section of architectural membrane may be removed or replaced within four hours using a maximum of four workmen.
19. The individual architectural membrane panels on the center modules shall be one continuous section from one side, over the peak and down to the base at the other side and manufactured in such a way that no eave will exist.
20. In order to provide the introduction of natural light for daytime use, a continuous section of highly translucent white architectural membrane (daylight panel) shall be incorporated into the membrane on the roof. To minimize internal solar gain in the structure, the balance of the exterior architectural membrane shall be complete with a blackout layer.
21. (For Tedlar or Kynar Membranes) All exterior architectural membrane on the structure shall come complete with a protective exterior Tedlar PVF film or a Kynar coating on the exterior surface of the membrane and a 25 year pro-rata guarantee. This membrane will possess the following minimum quality and fire rating specifications as shown on Schedule A attached;
Durability, color choices and ease of cleaning are among the many hallmarks of the architectural membrane of your Sprung structure.
DESERT
SAND*
BRIGHT
WHITE*
BAYBERRY
GREEN*
FOREST
GREEN*
SKY
BLUE*
SALEM
BLUE*
SANDSTONE* MISTY
GRAY*
The selected Pantone color numbers are a visual interpretation of the Tedlar colors.
DuPont TM Tedlar®
Architectural Membrane Color Chart
*The above color chips are not true and accurate representations of the actual membrane color. Please request a membrane sample prior to ordering.
Designed for permanent or long-term applications
• Simply the longest-lasting fabric of its type in the world
• Blackout design prevents solar gain and manages climate control
• Weighs approximately 24 oz. per square yard
• Guards against UV and airborne contaminants
• Dramatically extends membrane life
• High strength, rip-stop design
• Exceptional fire-retardant capability
• Available in large selection of colors
• 25-year pro-rata guarantee www.sprung.com info@sprung.com
Membrane Color Pantone Color Desert Sand PMS 726-C
Sandstone PMS 7500-C (70% screen)
Forest Green PMS 568-C
Bayberry Green PMS 5625-C
Bright White White Misty Gray PMS 428-C
Salem Blue PMS 5415-C
Sky Blue PMS 2148-C
TEDLAR® COATED ARCHITECTURAL MEMBRANE
Scrim Type Polyester
Scrim Weight 3.2 oz/sq.yd.
Finish Coated Weight +2
Method 5041 24.0 oz /sq.yd � -1 �
Surface Protection Tedlar ® PVF Film
Tongue Tear
Method 5134 110/110 lbs
8" x 10" sample size
Trapezoid Tear
Method 5136 35/40 lbs
Grab Tensile
Method 5100 260/260 lbs
Strip Tensile
Method 5102 200/200 lbs./in.
Hydrostatic Resistance
Method 5512 350 psi
Dead Load 1 - 1/2" seam
Room Temperature 100 lbs
160�F./71�C. 50 lbs
Cold Crack
MIL-C-20696C LTC Pass -40�F.
Para. 4.4.6.
Flame Resistance Pass 2 second flameout
Method 5903 FR Calf. Fire Marshal Reg.
UL214. NFPA-701
Wicking 1/8" maximum
FIRE RATINGS
1. California Fire Marshal Small & Large Scale Pass
2. National Fire Protection Association-701 Small & Large Scale Pass
3. Underwriters' Laboratories 214 Pass
4. ASTM E84 Pass
5. ULC S109 Pass
6. UBC 31-1 Pass
High Performance Fabric Building Solutions
MEDITERRANEAN
OLIVE*
PMS 7536-C
DARK TAUPEBROWNSTONE
RED*
PMS 7526-C
PATINA
GREEN*
PMS 556-C
CROMWELL
GRAY
BLACK
BLUE PURPLEYELLOW REDORANGE GREEN
Durability, color choices and ease of cleaning are among the many hallmarks of the architectural membrane of your Sprung structure.
The selected Pantone color numbers are a visual interpretation of the Kynar colors.
Kynar®
Architectural Membrane Color Chart
*The above color chips are not true and accurate representations of the actual membrane color. Please request a membrane sample prior to ordering.
Designed for permanent or long-term applications
• 3 coat system provides maximum protection and longevity
• Blackout design prevents solar gain and manages climate control
• Weighs approximately 24 oz. per square yard
• Guards against UV and airborne contaminants
• Dramatically extends membrane life
• High strength, rip-stop design
• Exceptional fire-retardant capability
• Available in large selection of colors (custom colors available)
• 25-year pro-rata guarantee www.sprung.com info@sprung.com
VIRTUALLY ANY CUSTOM COLOR IS AVAILABLE UPON REQUEST.
Base Fabric Type (Scrim) Polyester
Base Fabric Weight (Scrim) 4.3 oz/sq yd
Finish Coated Weight +2
Method ASTM D751 -1
Surface Protection Kynar® Resin Coating
Tongue Tear Method ASTM D751
8" x 10" sample size
Trapezoid Tear Method ASTM D4533
Grab Tensile Method ASTM D751
Strip Tensile Method ASTM D751 Procedure B
Adhesion Method ASTM D751 10 lbf/in Dielectric Weld
Hydrostatic Resistance Method ASTM D751 Procedure A
Dead Load 1" seam, 4 hrs, 1" strip Method ASTM D751 120 lbf (roon temperature)
60 lbf @160°F / 71°C
Cold Crack 1/8" mandrel, 4 hr Method ASTM D2136 Pass -40° F
Flame Resistance 2 seconds flame out Method D6413-
FlRE RATINGS
1 NFPA 701
2 ASTM E 84 Flame spead index <25. Smoke development rating <450 3 California State Fire Marshall
4 CAN/ULC-S-109
5 CAN/ULC-S-102
KYNAR® COATED ARCHITECTURAL MEMBRANE
140/130 lbf
80/65 lbf
400/350 lbf
320/240 lbf/in
500 psi
( )24.0 oz/sq yd rv.04.2014
High Performance Fabric Building Solutions
22. (For Insulation c/w interior liner) The structure shall be supplied with a complete insulation system within all roof and wall sections (except the daylight panel), providing the following minimum specifications:
a) 9" thick fiberglass blanket using formaldehyde free fiberglass insulation.
b) FSK (Foil, scrim, kraft) facing on one side of the insulation blanket to provide both a vapor barrier and to help preserve radiant heat. System to include FSK tape to seal all insulation joints and to seal insulation to structure's supporting members.
c) A white interior liner in a minimum 14oz coated polyester membrane, vertically and horizontally tensioned providing a secondary vapor barrier and clean unwrinkled interior finish to the insulation system.
d) Interior and exterior thermal caps to be installed over the structure's supporting beams to minimize thermal transfer through the supporting member. Each thermal cap c/w neoprene wipers each side to complete thermal break.
e) Peak to grade insulation retention system to ensure insulation will never creep or shift downward under its own weight.
23. Structure Supplier must be SPRUNG INSTANT STRUCTURES, INC.
24. Structure Supplier is to supply all specialized hand tools required for erection of the structure to be returned to Structure Supplier upon completion of erection.
25. Structure Supplier must supply a Technical Consultant on site for the full duration of the erection of the structure to provide information about structure assembly and erection to ensure structure is erected in accordance with its engineered design. All costs for the consultants’ time, travel, meals and accommodation are to be included in the price submission.
26. Upon award of this contract, Structure Supplier is to supply detailed drawings and supporting calculations for the structure stamped by an engineer certified in the State of New York.
27. Point of Contact: Heather Reichwein, Business Development Manager, <heather.reichwein@sprung.com> Office: 610.391.9553 Mobile: 610.704.3745
Sprung Instant Structures Inc - Allentown, Pennsylvania, USA 1-800-528-9899 • • www.sprung.com
Sprung Instant Structures
This Guarantee is presented to:
United States Military Academy
The architectural membrane and aluminum materials utilized in Sprung Structures have been selected for their proven strength, durability and longevity. To show our sincere confidence in our product, Sprung Instant Structures is pleased to issue the following guarantees.
ARCHITECTURAL MEMBRANE WITH TEDLAR PVF FILM or KYNAR COATING
All membranes used are water and mildew resistant, insect proof and flame retardant. These membranes withstand extreme climatic variations and contain ultra-violet inhibitors to reduce degradation by the sun's rays. Flame retardant status has been warranted by the membrane suppliers.
Sprung Instant Structures guarantees to supply new replacement membrane, on a pro-rata basis at the then current price, for all colors of Tedlar or Kynar coated membranes which deteriorate from any of the aforementioned factors within Tedlar/Kynar TWENTY FIVE (25) YEARS from the date of delivery of the structure(s).
EXTRUDED ALUMINUM SUBSTRUCTURE AND COMPONENTS
Aluminum used is professionally engineered and is of the highest quality and structural capability. Sprung Instant Structures guarantees to replace, on a pro-rata basis at the then current price, any aluminum which deteriorates from normal usage within FIFTY (50) years from the date of delivery of the structure(s).
The guarantee will not be valid if a Sprung technical consultant is not present during all erections and dismantling’s of the structure during the guarantee period or if any payments associated with the structure(s) are not made on time.
August 13, 2020
PHIL SPRUNG - PRESIDENT
Detect Manage
Record
227-95x-xx, 227-96x-xx, 227-95x-EN, 227-96x-EN Rev F 5/29/20
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149 Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco-inc.com Web www.monaco-inc.com
Addressable Fire Alarm Control Panels with MNS
Detect Manage
Record
Description MAAP-X is the premier addressable integrated fire and mass notification system (MNS) control panel from Monaco Enterprises, Inc. The MAAP-X comprises a single touch screen enclosure incorporating fire monitoring, addressable point reporting, live voice, and pre-recorded MNS functions which are compatible with the D-21 system.
Key Features Fully integrated panel combines transceiver, addressable fire panel and mass notification Addressable point reporting Touch-screen graphical interface with capability to extend to local operating console/remote display units (LOC/RDU)
Live and pre-recorded MNS functions and fire voice evacuation
Built in MNS microphone
– Optional handheld live voice push-to-talk MNS microphone in separate enclosure
– Optional handheld live voice push-to-talk Paging microphone in separate enclosure Up to 100W of audio amplification without booster circuits Built-in synchronized NAC, up to eight Class B or four
Class A Compatible with the D-21 Central Receiving System Single, seamless upgrade from previous M-series
Monaco panels Flexible configuration achieved with addition of speaker amplifier and addressable cards Built in STIPA tone for audio intelligibility testing Upgrading existing Monaco 28 inch or larger M-series fire-only panels to MAAP-X fire-and-MNS panels is easy using the MAAP-X upgrade kit. The kit provides a cost-effective method to meet current building fire MNS requirements while reusing the existing enclosure, conduits, wiring, and addressable devices.
MAAP-X Base Panel The base MAAP-X includes:
A master control unit (MCU) with a color touch screen for fire and MNS operation An MNS message card with nine standard pre-recorded messages (eight dedicated MNS, one dedicated fire)
An Analog Addressable Controller II (AAC II) backplane
One Addressable Driver Card (ADC) One Speaker Output Card (SOC) On-board circuits:
Eight Class B or four Class A non-loop-powered
Initiating Device Circuits (IDCs) Eight Class B or four Class A regulated or synchronized programmable Notification Appliance Circuits (NACs)
FM
APPROVED
Made in USA
MAAP-X Addressable Fire Alarm MNS Voice Evacuation Panel 227-95x-xx, 227-96x-xx, 227-95x-EN, 227-96x-EN
Addressable Fire Alarm Control Panels with MNS
Record
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149 Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco-inc.com Web www.monaco-inc.com
Addressable Fire Alarm Control Panels with MNS
227-95x-xx, 227-96x-xx, 227-95x-EN, 227-96x-EN Rev F 5/29/20
Detect Manage
Record
Four Form C programmable relays Autosensing power supply, 120/240 VAC 50/60 Hz Dual-rate 4A 24 VDC battery charger that meets the requirements of NFPA 72 and UL 864 24 VDC auxiliary power FSK interface for communication to D-21 through the standard integrated transceiver, or optional network or fiber module
Main Panel and LOC/RDU Touch-Screen Features
Fire and MNS operation for first responders Simple English messages identify alarm, trouble, and supervisory conditions Displays zone input or addressable device programmable descriptions User-defined device and zone descriptions Panel reset, alarm/trouble silence LED status indicators for primary/secondary power, radio communication, general alarm, and trouble Panel maintenance functions, such as:
– Zone and sensor device enable/disable
– Walktest
– Radio key-up test
– Enhanced diagnostic information—identifying panel troubles and loop faults Panel history
Message Card Standard card has eight default pre-recorded MNS messages and one fire evacuation message for a total of nine pre-recorded messages
User-defined messages available with a customer-option message card with eight user-defined pre-recorded MNS messages and one user-defined pre-recorded fire evacuation message
AAC II Backplane The AAC II supports a combination of up to eight cards.
The cards can be either ADCs (up to seven, one included) or SOCs (up to four, one included).
ADC (for addressable devices) Each ADC supports one Class A/X or two Class B Signaling Line Circuits (SLCs) for addressable device pathways. Each card supports 99 smoke or heat detectors and 99 monitor or control modules.
Options such as sounder or relay bases and fault isolator modules reduce the number of addressable devices (198 device equivalents maximum).
SOC (for speakers) Each SOC supports one Class A or two Class B speaker circuits for speaker audio pathways. Each card provides 25 VRMS, 32W of speaker audio power.
LOC/RDU Touch Screen LOC/RDUs are a critical part of every installation, placed at strategic locations throughout the building. With an advanced approach to technology, Monaco’s LOC/RDU touch screen combines the pre-recorded and live voice message functions of an MNS LOC with the functions of a typically separate Fire Alarm Panel Remote Control Annunciator into one combination LOC/RDU.
Record
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149 Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco-inc.com Web www.monaco-inc.com
Addressable Fire Alarm Control Panels with MNS
227-95x-xx, 227-96x-xx, 227-95x-EN, 227-96x-EN Rev F 5/29/20
Features LOC/RDU provides the same functions as the main panel, at key locations within the protected building
Built in MNS microphone
– Optional handheld live voice push-to-talk MNS microphone in separate enclosure
– Optional handheld live voice push-to-talk Paging microphone in separate enclosure Three user programmable modes of operation based on LOC/RDU location needs—Fire and MNS, Fire only, and MNS only
Each LOC/RDU touch screen provides a visual indication for active pre-recorded or live voice MNS;
Touch screen displays an explanation message if a lower priority MNS request is denied
Additional MAAP-X Features Legacy zone-only fire reporting, or point reporting for each addressable device Pre-tone and post-tone options for MNS messages Messages settable for time-outs of 1–60 minutes
MNS display screen can be customized by user MNS prioritized by LOC/RDU locations and message numbers, with live voice override Auxiliary Audio Input: Transformer coupled
600 ohm audio input allows user to select any one of five different audio input levels from .30 to .775v RMS (0dBu) for 3rd party audio to be played through the MAAP-X speakers; requires a closed contact trigger to enable Aux Audio Input
Text display notification using 2010 NFPA 72 compliant textual visual boards for emergency notification programmed to match MAAP-X MNS pre-recorded messages
Local speaker for MNS messages and audible alert for alarm, trouble, and supervisory notification
Additional battery backup expansion options available for increased operation times during AC power failures
Transfer between AC primary power and battery secondary power is automatic
Sensor Grouping
With point reporting enabled, MAAP-X supports the Monaco sensor-group feature:
Smoke detectors function together to control local sounder bases and reduce nuisance alarms Beneficial in dormitory environments, reducing costly response runs and building evacuations for isolated incidents
MNS and Paging Push to Talk Microphones Handheld push to talk MNS microphone for use inside LOC/RDU enclosures. 2 foot cable included.
Handheld push to talk MNS microphone in red
8" H x 6" W x 3" D enclosure. 15 ft cable for connection to MAAP-X included.
Handheld push to talk Paging microphone in red 8" H x 6" W x 3" D enclosure. 15 ft single cable for connection to MAAP-X and LOC included. Dual cable also included if connecting MNS and Paging microphone to the MAAP-X.
Record
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149 Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco-inc.com Web www.monaco-inc.com
Addressable Fire Alarm Control Panels with MNS
227-95x-xx, 227-96x-xx, 227-95x-EN, 227-96x-EN Rev F 5/29/20
Detect Manage
Record
MAAP-X Configuration Programming Software MAAP-X Planner Kit allows the user to program the panel. Planner functions include:
Uploading/downloading the MAAP-X program file to/from the panel Creates a MAAP-X configuration file that can be imported into the D-21 Central; manual information entry to D-21 not needed
Central reporting modes:
– Point reporting (addressable device addresses with zone reporting to D-21 and MNS operation)
– Legacy (zone reporting to D-21 and MNS operation)
– Stand-alone (in-building fire and MNS operation only) Setting D-21 Central communication modes—radio or hard-wire (Ethernet, fiber), single comm or dual comm
Configuring fire and MNS device circuits Configuring MAAP-X and LOC/RDUs for fire and
MNS operation Provides the ability to keep panel configuration files for backup Windows® (XP, 7.0, 8.0, 10) compatible Monaco
MAAP-X Planner software Define zone and device descriptions
MAAP-X D-21 Configuration Options
Panel Configuration
A configuration-file copy is stored at the D-21 that can be used as a backup.
Mass Notification In-building, pre-recorded, and live voice MNS from the main panel, LOC/RDUs, and from D-21 Central systems configured for base-wide MNS
Preconfigured MNS message files streamed from D-21 Central systems configured for broadcast MNS
Fire Zone Reporting MAAP-X can be configured for legacy fire non-point-reporting, compatible with D-21 Central systems configured with an FSK interface
MAAP-X displays the address of the individual device in alarm on its touch screen and reports up to 64 fire zones to the D-21
Fire Point Reporting
MAAP-X:
Supports Monaco’s advanced fire point reporting and is compatible with D-21 Central systems configured for point reporting
Individually reports alarm and trouble status of addressable sensors and monitor modules in real-time to the D-21 Central
D-21 Connectivity MAAP-X supports radio (site-specific narrowband frequency) and hard-wire communication User selects central communication mode— primary only or primary with fallback to secondary Only one antenna system needed for radio communication; hard-wire options include Ethernet and fiber-optic
Panel Clock Synchronization D-21 can be configured to synchronize the MAAP-X internal clock and calendar Synchronizing eliminates the need to adjust each panel for daylight-saving time
Software Version
MAAP-X requires D-21 software with MAAP-X support.
An RFM-X is required for point reporting and MNS.
Record
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149 Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco-inc.com Web www.monaco-inc.com
Addressable Fire Alarm Control Panels with MNS
227-95x-xx, 227-96x-xx, 227-95x-EN, 227-96x-EN Rev F 5/29/20
Hardware Specifications
Electrical
Environmental
IDC (Zone Inputs) Capacity: 4 Class A or 8 Class B Non-loop-power: 4 VDC with EOL, 12 VDC at 25 mA max.
EOL: 3.9 kΩ 1/4W, Class B only Max. loop resistance: 50Ω per leg
NAC (Notification Appliance Circuit
Outputs)
Capacity: 4 Class A or 8 Class B, polarity reversing EOL: 3.9 kΩ 1/4W, Class B only NACs programmed as “regulated”:
Power: 24 VDC 1A Max. loop resistance: 1.5Ω per leg NACs programmed as “special application” (synchronized strobes):
Power: 24 VDC 2A Max. loop resistance: 0.75Ω per leg Wiring: Standard fire-alarm-rated cable
SLC (Addressable) Per ADC:
2 Class B or 1 Class A/X SLC input(s) 99 smoke or heat sensors 99 monitor or control modules Power: 0–29 VDC polling protocol Supervision: open, short, ground fault Max. loop resistance: 40Ω per leg Wiring: Unshielded twisted pair
Speaker Circuits Per SOC: 2 Class B or 1 Class A output(s) Power: 25 VAC RMS, 32W max. each, 100W total Supervision: open, short, ground fault EOL: 3.9 kΩ 1/4W, Class B only Max. loop resistance: 1.5Ω per leg Wiring: Standard fire-alarm-rated cable
AUX PWR Power: 24 VDC 2A Supervision: none Max. loop resistance: 1Ω per leg Wiring: Standard fire-alarm-rated cable
AUX Audio Input Transformer coupled 600 ohm audio input Custom Settings:
0.3000VRMS = 0.85V P-P = 10.46 dBV 0.3535V RMS = 1.00V P-P = -9.03 dBV 0.7071V RMS = 2.00V P-P = -3.01 dBV 0.7750V RMS = 2.19V P-P = -2.21 dBV Requires closed contact trigger Contact Monaco for Assistance
Relays, K1–K4 Contact rating: 30 VDC at 2A max.
Supervision: none
Radio Output Power 4W minimum (2W, some frequencies)
Battery Backup Standard: 2 rechargeable 12V/18 Ah Integrated charger: supervised dual-rate, meets NFPA 72 and UL 864 requirements,
27.6 VDC 4A
Low battery alert: 20.4 VDC Low battery disconnect: 18.5 VDC
AC Power 3-wire autosensing, 120/240 VAC 100 VAC 2.8 Amps (85-110) VAC 120 VAC 2.4 Amps (102-132 VAC) 240 VAC 1.0 Amps (204-264 VAC) 50/60 Hz
Radio Narrowband radio meets requirements of the National Telecommunications and Information Administration Manual of Regulations and Procedures for Federal Frequency Management. FCC certified.
Operating Temperature 32° to 120°F (0 to 49°C)
Relative Humidity 0–90%, noncondensing
Record
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149 Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco-inc.com Web www.monaco-inc.com
Addressable Fire Alarm Control Panels with MNS
227-95x-xx, 227-96x-xx, 227-95x-EN, 227-96x-EN Rev F 5/29/20
Detect Manage
Record
Ordering Information
Panels Integrated Radio, Surface- and Flush-mount
Hard-wire Only (Ethernet), Surface- and Flush-mount
Part Number Description
227-955-xx* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, integrated radio transceiver—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 surface-mount red enclosure
28"H x 18"W x 3.6"D Two 12V/18 Ah batteries
227-956-xx* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, integrated radio transceiver—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 surface-mount red enclosure
43"H x 18"W x 3.6"D Four 12V/18 Ah batteries
227-957-xx* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, integrated radio transceiver—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 surface-mount red enclosure
60"H x 18"W x 3.6"D Four 12V/18 Ah batteries
227-965-xx* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, integrated radio transceiver—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 flush-mount red enclosure
28"H x 18"W x 3.6"D Two 12V/18 Ah batteries
227-966-xx* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, integrated radio transceiver—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 flush-mount red enclosure
43"H x 18"W x 3.6"D Four 12V/18 Ah batteries
227-968-xx* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, integrated radio transceiver—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 4X surface-mount stainless steel enclosure 24"H x 24"W x 8"D
Two 12V/18 Ah batteries
227-969-xx* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, integrated radio transceiver—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 3R surface-mount red enclosure
24"H x 24"W x 8"D Two 12V/18 Ah batteries
*Specify frequency (-xx) when ordering.
Part Number Description
227-955-EN* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, hard-wire—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 surface-mount red enclosure
28"H x 18"W x 3.6"D Two 12V/18 Ah batteries
227-956-EN* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, hard-wire—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 surface-mount red enclosure
43"H x 18"W x 3.6"D Four 12V/18 Ah batteries
227-965-EN* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, hard-wire—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 flush-mount red enclosure
28"H x 18"W x 3.6"D Two 12V/18 Ah batteries
Part Number Description
Record
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149 Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco-inc.com Web www.monaco-inc.com
Addressable Fire Alarm Control Panels with MNS
227-95x-xx, 227-96x-xx, 227-95x-EN, 227-96x-EN Rev F 5/29/20
Standalone - No Radio, Surface- and Flush-mount
Associated Parts 227-966-EN* MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, hard-wire—single comm:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 flush-mount red enclosure
43"H x 18"W x 3.6"D Four 12V/18 Ah batteries
*Does not support D-21 Central live voice; for options contact Monaco.
Part Number Description
227-955-NR MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, Standalone - No Radio:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 surface mount red enclosure
28"H x 18"W x 3.6"D Two 12V/18 Ah batteries
227-956-NR MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, Standalone - No Radio:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 surface mount red enclosure
43"H x 18"W x 3.6"D Four 12V/18 Ah batteries
227-965-NR MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, Standalone - No Radio:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 flush mount red enclosure
28"H x 18"W x 3.6"D Two 12V/18 Ah batteries
227-966-NR MAAP-X point reporting, addressable, fire alarm control, mass notification, voice evacuation panel, Standalone - No Radio:
One AAC II backplane for ADCs/SOCs One ADC supporting 198 addressable devices One SOC, 25 VAC RMS, 32W audio output NEMA 1 flush-mount red enclosure
43"H x 18"W x 3.6"D Four 12V/18 Ah batteries
Part Number Description
Part Number Description
081-156-00 Batteries with enclosure:
-NEMA 1 Red surface mount enclosure, 18" H x 12" W x 6" D, with wire harness for use with M-2 conventional, MAAP+, MAAP-X and Vulcan 1 FACPs
- Two 12 VDC/26 Ah batteries
122-012-00 Handheld Push-to-Talk Microphone and holder for use on LOC/ RDU Touch Screen. Includes 2-foot cable for connection to LOC/RDU Touch Screen.
122-012-05 Handheld Push-to-Talk MNS Microphone in red enclosure, 8"H x 6"W x 3"D with window. Includes 15-foot cable for connecting to MAAP-X or LOC/RDU Touch Screen.
122-012-06 Handheld Non-Emergency Push-to-Talk Paging Microphone in red enclosure, 8"H x 6"W x 3"D.
Includes 15-foot single cable for connecting to MAAP-X, LOC/RDU Touch Screen or LOC Keypad.
Dual cable also included if connecting MNS and Paging microphone to the MAAP-X or LOC/RDU Touch Screen.
708-032-01 HVAC Shutdown kit. Includes shutdown button and cover. (Mini Monitor Module P/N 729-143-00, not included.)
176-194-00 Addressable Driver Card (ADC), supports up to 198 addressable devices on a Signaling Line Circuit
176-268-02 Multiplexer, RS-422 to 8 RS-485 ports with surge suppression, 24 VDC, to support MAAP-X LOC/RDU Touch Screens and LOC Keypads per output. See NOTE 1
176-272-00 Speaker Output Card (SOC)
194-527-07 MAAP-X EN Fiber Optic to Ethernet Converter, single mode 1 Gb kit with mounting hardware.
(1 required per Ethernet MAAP-X EN to convert it to Fiber Optic.)
194-527-01 Fiber Optic to Ethernet Converter, single mode, 1 Gb. (Spare part for 194-527-07)
205-032-00 MAAP Printer Kit, includes optoisolator with power adaptor, RJ-45 DTE to DB-25 male DCE adaptor, RJ-45 cable, DB-25 extension cable
207-625-00 MAAP-X Addressable Planner kit, CD, CAT6 programming cable, 45 DTE-9F DCE adapter
227-912-xx MAAP-X upgrade for M-1, M-2, MAAP(+) Fire only Panels with 28" high or larger enclosures.
Specify frequency (-xx) when ordering.
NOTE Can also use as a spare MAAP-X electronic package.
Record
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149 Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco-inc.com Web www.monaco-inc.com
Addressable Fire Alarm Control Panels with MNS
227-95x-xx, 227-96x-xx, 227-95x-EN, 227-96x-EN Rev F 5/29/20
Detect Manage
Record
MNS Message Card Kit 400-712-00 Battery, SLA, rechargeable, 12V/18 Ah, quick connect, 7.13"L x 3.03"W x 6.59"H, 12.60 lb
513-411-01 MAAP-X Tamper Switch Kit
710-054-01 Remote text annunciator, two-line, 40 characters ea.
710-075-01 MAAP-X Text Display, 24 VDC, two line, multi-color, default text display. Requires MAAP-X Panel firmware version A.4.6 or higher.
See NOTE 2 and NOTE 3.
710-072-01 LOC/RDU with touch screen, fire/MNS, 19"H, surface-mount, 115/230 VAC, 50/60 Hz, 72-hour battery backup. See NOTE 1
710-072-02 LOC/RDU with touch screen, fire/MNS, 19"H, flush-mount, 115/230 VAC, 50/60 Hz, 72-hour battery backup.
See NOTE 1
NOTE 1 The MAAP-X panel can support up to 30 LOCs. Of the 30 LOCs a maximum of 10 can be RDU/LOC Touchscreens, the rest need to be LOC Keypads. All 30 can be LOC Keypads. Each MAAP-X enclosure can support one LOC MUX (P/N 176-268-02) that can support a total of 30 LOCs. Each LOC MUX has eight RS-485 outputs that LOCs can be connected to. Each RS-485 output can support 30 LOC Keypads maximum or 8 LOC/RDU Touchscreens maximum.
Contact Monaco if your system requires more LOCs.
NOTE 2 Requires Text Display Interface, Program Utility and DC Power Supply, see Cutsheet 710-075-01 for more information.
NOTE 3 According to NFPA 72, 2010 24.4.2.21 when the two line, multi-color, text display is mounted more than ten feet above the floor with a viewing distance of more than 21 feet, the display is required to be configured with only a single line of text so the font is large enough to view properly.
Part Number Description
Part Number Description
326-M00-01 MAAP-X standard message card—8 MNS, 1 Carbon Monoxide (CO), 1 Medical Emergency, 1 Fire, for 11 total pre-recorded messages. These are summaries, not the full-message text:
Message 1 Emergency, evacuate to designated area Message 2 Bomb threat, evacuate at nearest exit Message 3 Severe weather warning Message 4 Intruder, follow designated pre-plan Message 5 Shelter in-place Message 6 Emergency, use alternate exit Message 7 Emergency has ended Message 8 Test of Monaco Mass Notification System Message 9 CO Detected Message 10 Medical Emergency (EMS) Dedicated Fire Message
326-M01-01 MAAP-X customer option message card—8 MNS, 1 fire, for 9 total pre-recorded messages:
Message set information must be provided at time of ordering. Contact Monaco for the forms (P/N 001-583-02 for new message sets or P/N 001-583-01 for existing site established message sets). The form is needed to have the message set installed on the card before the MAAP-X panel ships.
326-M10-01 MAAP-X customer option message card field upgrade kit—8 MNS, 1 fire, for 9 total pre-recorded messages:
Message set information must be provided at time of ordering. Contact Monaco for the forms (P/N 001-583-02 for new message sets or P/N 001-583-01 for existing site established message sets). The form is needed to order this upgrade to replace existing messages at your site.
Record
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149 Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco-inc.com Web www.monaco-inc.com
Addressable Fire Alarm Control Panels with MNS
227-95x-xx, 227-96x-xx, 227-95x-EN, 227-96x-EN Rev F 5/29/20
Wiring Diagram
Addressable Circuits
J1
TB8TB7TB6TB5TB4TB3TB2TB1
J17J15J13J12J11
AUDIO J14 AUDIO J16
J21
LED TEST
A+ A- B+ B- A+ A- B+ B- A+ A- B+ B- A+ A- B+ B- A+ A- B+ B- A+ A- B+ B- A+ A- B+ B- A+ A- B+ B-
AUDIO J18
INOUT OUT IN OUT INRS422
R S
-232-A R
S -232-B
DC
RESET
AUDIO INPUTS
RS485
PORT A PORT B
J19
J9
SW2
J3 J10 J2
J6
4(-) (+) 3 (+)(-)
GND
GLB
TXD
RXD
KEY
RST
J8
J7
J5
J22
2(+)(-)
AUDIO
STAT
+24VDC IN
AUDIO J20
CAN
Lo
CAN
Hi
SLOT 6SLOT 5SLOT 4SLOT 3SLOT 2SLOT 1 SLOT 7 SLOT 8INOUT
CD
M
NC
MM
IM
R
R
(No more than 25 devices between isolators)
47k
EOL
Core II PCB P/N 176-271-00
All Circuits Power Limited
Class A (Style 6)
Class B (Style 4)
Class X (Style 7)
3.9k
EOL
Form C Contacts #2Contacts #1
Form C
24 VDC
Aux Pwr
S S
S
Class B
Class A S S
3.9k
EOL
3.9k
EOL
S
3.9k
EOL
Note: To reset the loop-powered (2-wire) conventional detectors connected through the interface module, that shall interrupt power.
or by a relay module configured as "smoke power" auxiliary power must be an interruptible versionRelay P/N 790-013-01
Power Supervisory
A A A
A A A
A AA
A A
A A A
Speaker Output Cards (SOCs) P/N 176-272-xx
24 VDC Input Non-power Limited
Addressable Driver Cards (ADCs) P/N 176-194-xx
Analog Adressable Controller II
(AAC II) P/N 176-273-00
NC
M
MM
IM
Isolator Module
NAC Control Module
Monitor Module
Mini Module
Interface Module
Addressable Initiating Devices:
Smoke Detector
Heat Detector A
A
Notification Appliance
Speaker ApplianceS
S Speaker/MNS Strobe Combo
NAC Devices:
All NACs Supervised
Speaker Configuration:
Up to 8 Class B or 4 Class A
Unused Speaker Circuits A+ A- B+ B- A+ A- B+ B-
Class A
Class B 3.9k 3.9k
Only TB5 TB8 terminals can be used for speaker circuits; requires SOCs
Terminals TB1 TB8 can be addressable circuits (SLC) if ADCs placed in all 8 slots.
R
Conventional Initiating Devices:
Pull Station
Heat Detector
Relay Module
LEGEND
SD Cardu
To NAC defined for MNS strobes
Record
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149 Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco-inc.com Web www.monaco-inc.com
Addressable Fire Alarm Control Panels with MNS
227-95x-xx, 227-96x-xx, 227-95x-EN, 227-96x-EN Rev F 5/29/20
Detect Manage
Record
Conventional Circuits
D C
IN
A
U X
A U
XP
W
R
P
W R
D C
IN
1-
1-
1-
1-
2-
2-
2-
2-
3-
3-
3-
3-
4-
4-
4-
4-
1-
1-
1-
1-
2-
2-
2-
2-
3-
3-
3-
3-
4-
4-
4-
4-
N O
C O
M N
C
N O
C O
M N
C
N O
C O
M N
C
N O
C O
M N
C
NACZONE INPUTS K1 K2 K3 K4
1-
1-
1-
1-
NACZONE INPUTS
1-
1-
1-
1-
1-
1-
1-
1-
NACZONE INPUTS
1-
1-
1-
1-
Auxiliary Power Out;
Power Limited
4 Form C relays, 30 VDC, 2A, non-power limited
3.9k
EOL
Typical Class B
(Style B)
Typical Class A
(Style D)
3.9k
EOL
3.9k
EOL
3.9k
EOL
3.9k
EOL
3.9k
EOL
3.9k
EOL
P/N 790-013-01
DC In; Non-power Limited
P/N 790-013-01
3.9k
Typical Class B (Style Y)
Typical Class A (Style Z)
Unused Class A
(Style D) (Style Z)
(Style B) (Style Y)
Unused Class B
3.9k 3.9k 3.9k
8 Class B or 4 Class A.
All IDCs supervised.
IDC Configuration:
Contact devices;
non-loop power.
8 Class B or 4 Class A.
All NACs supervised.
NAC Configuration:
Power Limited
Power Limited Combined max. current for NACs 1 and 2 is regulated 1A or special application 2A.
Same specification applies to NACs 3 and 4.
Initiating Devices:
Pull Station
Smoke Detector
Heat Detector
Notification Appliance
Strobe
Waterflow Device
LEGEND
NAC Devices:
Notification/Strobe Appliance
Note Class B resistor values in this diagram are
3.9 kΩ, 1/2W (5%), end-of-line (EOL)
Record
Monaco Enterprises, Inc.
P.O. Box 14129, Spokane Valley, WA 99214-0129; 14820 E. Sprague Ave., Spokane Valley, WA 99216-2149 Phone (509) 926-6277 Fax (509) 924-4980 E-mail service@monaco-inc.com Web www.monaco-inc.com
Addressable Fire Alarm Control Panels with MNS
227-95x-xx, 227-96x-xx, 227-95x-EN, 227-96x-EN Rev F 5/29/20
MAAP-X to LOC/RDU Wiring
MAAP-X LOC/RDU
SUPV TBL COM R
Gnd Neut Hot
RCV XMT MIC
J2
C A
N L
C A
N H
C D
K ey
R X
D
TX
D R es et
G N
D
A ud io 2(
A ud io
2(
A ud io 1(
A ud io
1(
TB1
RS-422 Mux Cable P/N 630-025-02
In In
Out Out
Pwr Gnd
In
Gnd
In
J1
(-) (+)INOUT OUT IN OUT INRS422
RS485 J3 J10
J2
INOUT
A ud io
A ud io
Drain and Shield Recommended Maximum Length 2000 ft Absolute Maximum Length 4000 ft
Audio 22 AWG Twisted Pair with
Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 7 Slot 8
A ud io
A ud io
In /O ut In
/O ut
G nd
NC In/Out In/Out (+) (-) NC
RS-485 Audio
Drain and Shield Recommended Maximum Length 2000 ft Absolute Maximum Length 4000 ft
24 AWG Twisted Pair with
Wht/Blue Wht/Vio
Blk
Wht/Grn Wht/Yel
Orn
MAAP-X Unit
MAAP-X AAC II
(Two 12 VDC 18 Ah batteries) 24 VDC to batteries
Ratings:
120 VAC @ 1.8 Amps
(102-132 VAC)
240 VAC @ 1.1 Amps
(204-264 VAC)
45-65 Hz
100 VAC
(85-110 VAC)
O ut
O utInIn
G nd
Vi n
+ 1( +) 1(
A U
X
IN
G N
D
2( +) 2(
N C
C O
M N O
N C
C O
M N O
S P
K R
S P
K R
M
IC
IN
T(
IN
T(
P
TT
N .O
P
TT
C
O M
M
IC
X
FM
R 1(
X
FM
R
1(
O ut
O ut
In In G nd Vi n
X
FM
R 2(
X
FM
R 2(
To 8 devices using RS-485
Wht/Blue Wht/Vio
Blk
Wht/Grn Wht/Yel
Orn
MUX
P/N 176-268-02
AC BAT ALM
service@monaco.com
AC BAT ALM SUPV TBL COM RCV XMT RMIC
TB6
D C
IN
A U
X
A U
X
TB9
C A
N L
C A
N H
P W
R
TB
P W
R
TB7
D C
IN
TB10TB8
K4
K3
K2
K1
J17J15J13J12J11 J21
DC
AUDIO INPUTSPORT A PORT B
J19
J6
GND
GLB
TXD
RXD
RST
J8 24VDC In
Slot 6
CD
Out
In
Ou…