C001A.B.4 – AC ELECTRIC MOTOR
The new ladder hoist winch motor shall be suitable for marine application and sized and designed for continuous operation at rated capacity. The motor shall be designed, constructed, and installed in accordance with ABS Rules and shall be ABS approved. The motor shall be provided with grease fittings and shall have positive means for preventing grease from being forced out upon the motor windings.
The motor will be exposed to the weather and therefore shall have IP-56 (watertight or weather tight) protection. The motor shall have class “H” insulation with a class “F” temperature rise rating based on a 50 degree C ambient temperature.
Anti-condensation space heaters shall be provided for the motor. Motor space heaters shall be powered from 120-VAC control power of the drive and shall be energized whenever the motor is secured and de-energized whenever the motor is operating. All space heaters shall be provided with an “ON”-“OFF”-
“AUTO” selector switch and indicating light on the drive.
C001A.B.13.b - FACTORY ACCEPTANCE TESTING
The Contractor shall perform factory acceptance testing (FAT) for the complete winch system (motor, drive, gearbox, and winch) at the manufacturer’s facility. The Contractor shall perform testing to demonstrate the winches rated capacity at rated line speed at the outermost layer of the winch drum, and a brake test to demonstrate the operation of the braking system at rated capacity. The Contractor shall also demonstrate the full safety braking capacity of the dynamic braking feature with power loss to the winch.
The Contracting Officer shall have the option of witnessing the FAT. The Contracting Officer or his
Representative shall be notified at least 10 (ten) working days prior to the scheduled test date.
C001A.C.4 – AC ELECTRIC MOTOR
The motors will be exposed to the weather and therefore shall have IP-56 (watertight or weather tight) protection. The motors shall have class “H” insulation with a class “F” temperature rise rating based on a
50 degree C ambient temperature.
Anti-condensation space heaters shall be provided for both motors. Motor space heaters shall be powered from 120-VAC control power of the motor controller and shall be energized whenever the motor is secured and de-energized whenever the motor is operating. All space heaters shall be provided with an “ON”-
“OFF”-“AUTO” selector switch and indicating light on the drive.
The Contractor shall provide all engineering and materials required to adapt and install the new motors to the existing hauling winches.
The vessel crew will perform all work to install the new motors on to the existing hauling winches.
L.2 – Proposal Submission Requirements
a. Each volume shall be submitted in a separate binder. Any pages that are changed (as a result of negotiations or proposal revisions) should be of a different color and have changed information clearly marked by a vertical line in the right margin of the page.
The revised pages shall be dated. Each binder shall be clearly labeled with its Title and a copy number (e.g., copy 1 of 5).
b. The following volumes of material shall be submitted:
PRINTED DIGITAL MAXIMUM
VOLUME TITLE COPIES COPIES PAGES
I – Technical/Risk Original 1 70
II - Past Performance Original 1 N/A
III – Price Original 1 N/A
NOTE: Pages that exceed the required page limitations will not be evaluated. Additional pages over the maximum allowed will be removed or not read and will not be evaluated by the Government. All pages will be counted except for the abridged sample of a testing plan and Operations & Maintenance Manual provided for a similar project which is required in Volume I, Tab 4b.