Text version

REFERENCES

No. TITLE DRAWING No.

THIS IS A CAD MAINTAINED DRAWING DEVELOPED

IN AUTOCAD R2013 SOFTWARE. CHANGES SHALL BE

INCORPORATED BY THE DESIGN AUTHORITY

UNDER 12" ±1/8"

12" TO 6'-0" ±1/4"

OVER 6'-0" ±1/2"

DISTRIBUTION STATEMENT D

DISTRIBUTION AUTHORIZED TO THE DEPARTMENT

OF DEFENSE AND U.S. DoD CONTRACTORS ONLY;

CRITICAL TECHNOLOGY, 2/23/2011. OTHER U.S.

REQUESTS SHALL BE REFERRED TO COMMANDER,

NAVAL SEA SYSTEMS COMMAND.

PLAN VIEW 5A

FLT III GTG1H/3H FACILITY

POWER ARRANGEMENT & DETAILS

BUILDING KEY PLAN

SCALE: NONE

REVISION STATUS

REV SH DESCRIPTION

- 1 TITLE SHEET, BUILDING KEY PLAN, REFERENCES, NOTES

- 2 AREA PLAN & ISOMETRIC VIEWS

- 3 EQUIPMENT POWER CIRCUIT ARRANGEMENT

- 4 EQUIPMENT POWER CIRCUIT ARRANGEMENT

- 5 EQUIPMENT POWER CIRCUIT ARRANGEMENT

- 6 EQUIPMENT POWER CIRCUIT ARRANGEMENT

- 7 LIGHTING AND RECEPTACLE CIRCUIT ARRANGMENT

- 8 LIGHTING AND RECEPTACLE CIRCUIT ARRANGMENT

- 9 FOUNDATION AND WELDING DETAILS

- 10 EQUIPMENT FOUNDATION DETAILS

- 11 MISCELLANEOUS DETAILS

- 12 SINGLE LINE DIAGRAM

- 13 ELECTRICAL CONNECTION TABLES

- 14 LIST OF MATERIALS

- 15 LIST OF MATERIALS

NAVAL SURFACE WARFARE CENTER, PHILADELPHIA DIVISION

PHILADELPHIA, PA 19112-5083

DDG 51 LAND BASED ENGINEERING SITE (LBES), BUILDING 77H

FLT III GTG1H/3H FACILITY

POWER ARR & DETAILS

DWG NO.CAGE CODESIZE REV

SCALE : AS NOTED SHEET 1 OF 15

89256D EHQ10998 -

CONTRACT No.

N00178-04-D-4089

OFFICAL SIGNATURE DATE

PREPARED B. Everling 1-13-17

CHECKED D. Purves 2-3-17

QA R. Chranowski

PROJ MGR

APPROVED NSWCPD

TECH REVIEW

PROG MGR

DIMENSIONAL TOLERANCES

UNLESS OTHERWISE SPECIFIED

DIMENSIONS IN FEET & INCHES

DECIMAL DIMENSIONS IN INCHES

TOLERANCE ON ANGLES ±.50°

1 PL ±.2, 2 PL ±.06, 3 PL ±.005

INTERPRET DIMENSIONS AND TOLERANCES

PER ASME Y14.5 - 1994

REVISION HISTORY

DESCRIPTIONREVZONE DATE APPROVED

D

C

B

A

D

C

B

A

12345678

12345678 A C A D F

IL

E N

A M E A C A D E

H P 1/ A C A D N

S W C P D D D G M O D

IF

IC

A T

IO

N S E H Q .D W G

NORTH

SEE SHEET 2 PLAN VIEW 14A

NOTES:

1. DEVIATIONS FROM THIS DRAWING ARE NOT PERMITTED WITHOUT APPROVAL

FROM THE NSWCPD CONSTRUCTION MANAGER (CODE 212).

2. FOLLOW THE LATEST VERSION NEC FOR ANY ELECTRICAL INSTALLATION

DETAIL NOT COVERED WITHIN THIS DRAWING.

3. ELEVATIONS GIVEN ON THIS DRAWING ARE REFERENCED FROM THE FINISHED

FLOOR OF BUILDING 77H (EL 0'-0") AND ARE TO BE VERIFIED AT THE TIME OF

INSTALLATION.

4. PHANTOM LINES INDICATE EXISTING EQUIPMENT NOT SHOWN.

5. DIMENSIONS SHALL BE FIELD VERIFIED PRIOR TO BEGINNING ANY WORK. MINOR

DEVIATIONS MAY BE PERMITTED WITH THE APPROVAL OF THE NSWCCD-SSES

CONSTRUCTION MANAGER (CODE 212).

6. VERIFY ALL CIRCUITS ARE TAGGED OUT PRIOR TO CONNECTION TO POWER

SOURCES.

7. ALL POWER CIRCUITS REQUIRE AN EQUIPMENT GROUND CONDUCTOR TO BE

ROUTED WITH THE POWER CABLE. IN MOST CASES AN EXTRA CONDUCTOR IS

CONTAINED WITHIN EACH POWER CABLE THAT SHALL BE CONNECTED AS AN

EQUIPMENT GROUND CONDUCTOR.

8. MISCELLANEOUS HARDWARE NOT INCLUDED IN THE MATERIAL LIST MUST BE

PROVIDED BY THE INSTALLER.

9. ALL CABLE HANGERS ARE SPACED AT 18" INTERVALS UNLESS OTHERWISE

NOTED ON THIS DRAWING.

10. DO NOT EXCEED CABLE MANUFACTURERS LIMIT FOR CABLE PULLING TENSION,

SIDE WALL PRESSURE AND BEND RADIUS DURING CABLE INSTALLATION.

11. ALL CABLING INSTALLED SHALL HAVE PERMANENT CABLE IDENTIFICATION

TAGS INSTALLED AT EACH END OF CABLE ADJACENT TO EQUIPMENT

ENCLOSURES.

12. ALL CABLES ARE TO BE ROUTED BELOW EXISTING SITE STEEL OR ALONG

EXISTING EQUIPMENT FOUNDATIONS USING MILITARY TEE TYPE HANGERS AND

WELDING STUDS (ITEMS 65 & 37) AS SHOWN IN DETAIL 65B, UNLESS

OTHERWISE NOTED ON THIS DRAWING. FOR SINGLE AND DOUBLE CABLE RUNS,

USE MILITARY CRIMP-LOK TYPE HANGERS AND WELDING STUDS (ITEMS 38, 39,

40 & 41) AS SHOWN IN DETAIL 67B.

13. CABLES IN HORIZONTAL AND VERTICAL CABLEWAYS SHALL BE SECURED TO

HANGERS USING BLACK NYLON, UV RESISTANT, 120 POUND TENSILE STRENGTH

TIE WRAPS (ITEM 44) OR EQUAL.

14. AFTER WIRING 3 PHASE MOTOR LOADS, BUMP TEST EACH MOTOR TO VERIFY

PROPER ROTATION.

15. REMOVE PAINT AND DIRT FROM ANY STEEL GROUNDING CONNECTIONS AND

APPLY ANTIOXIDANT JOINT COMPOUND (PENATROX A-13) OR EQUAL PRIOR TO

BOLTING TIN PLATED COMPRESSION LUGS FOR GROUND CONNECTIONS.

16. PERFORM INSULATION RESISTANCE TESTING FOR ALL NEW POWER CIRCUITS IN

ACCORDANCE WITH INSTRUCTION PROVIDED BY NSWCPD PROGRAM OFFICE.

PERFORM INSULATION RESISTANCE TESTING ON CIRCUITS AFTER NEW WIRING

IS PULLED INTO EQUIPMENT ENCLOSURES BUT NOT CONNECTED TO POWER

SOURCE. SAFEGUARD ALL PERSONNEL DURING INSULATION RESISTANCE

TESTING.

17. SUPPORT ALL CONDUIT AS SPECIFIED IN NEC.

M. Lamberto

NOTES (CONTINUED):

18. INSTALLER TO REMOVE RED PORTIONS OF EXISTING HANDRAIL DURING

EQUIPMENT FOUNDATION INSTALLATION SHOWN IN PARTIAL ELEVATION 78A

AND WELD REMAINING PORTION OF HANDRAILS TO EQUIPMENT FOUNDATIONS

TO SAFEGUARD PERSONNEL ON 3'-8" PLATFORM.

19. ANY CABLES PASSING THRU GRATING UNDER NEW POWER PANELS SHALL

HAVE A CUT OUT AT EDGE OF GRATING AND UNDER PANELS TO PROVIDE A

CLEAN AREA FOR CABLE PASSAGE OF 10"W X 2"D. 1/4" THICK X 51

4" HIGH

STEEL FLATBAR KICK PLATE SHALL BE TACK WELDED TO THE (3) INTERIOR

EDGES OF THE GRATING CUT OUT. THE KICK PLATE SHALL HAVE AN

INSTALLED HEIGHT OF 4" ABOVE THE GRATING (51

4" FLATBAR - 1

4" GRATING =

4" INSTALLED HEIGHT). GRATING SHALL BE FULLY REMOVEABLE WITHOUT

DISCONNECTING CABLES UPON COMPLETION OF INSTALLATION.

20. ANY RECEPTACLE CABLES PASSING THRU GRATING REQUIRE A 1-1/4"Ø X 4"

LONG PIPE SLEEVE PENETRATION THRU GRATING. PIPE SLEEVE SHALL BE

WELDED TO ADJACENT STRUCTURE TO ALLOW FUTURE GRATING REMOVAL

WITHOUT DISCONNECTION OF RECEPTACLE WIRING.

21. ALL DESIGN MATERIAL, FABRICATION AND ERECTION SHALL CONFORM TO

ANSI/AISC 360-10 "SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS" (ASD).

22. DESIGN, DETAILING AND FABRICATION OF ALL WELDED AND BOLTED

CONNECTIONS SHALL CONFORM TO THE AISC STEEL CONSTRUCTION MANUAL,

LATEST EDITION.

23. FABRICATION, WELDING AND INSPECTION SPECIFIED ON THIS DRAWING SHALL

BE IN ACCORDANCE WITH AWS STRUCTURAL WELDING CODE D1.1. NSWCPD

PROGRAM OFFICE RESERVES THE RIGHT TO INSPECT SHOP FABRICATION PRIOR

TO SHIPMENT.

24. CONTRACTOR SHALL BE RESPONSIBLE FOR VISUAL INSPECTION OF ALL WELDS

BY AN AWS CERTIFIED INSPECTOR.

25. ALL STEEL SHALL BE CLEANED AND THEN PAINTED WITH AN ANTI-CORROSION

PRIMER UPON COMPLETION OF ALL WELDING AND WELD INSPECTION. FIELD

WELD ON STRUCTURAL MEMBERS SHALL BE CLEANED, WASHED WITH WATER

AND COATED WITH AN ANTI-CORROSION PRIMER. FINISH ALL STEEL WITH TWO

COATS OF LIGHT GRAY (ANSI 61) PAINT.

26. THE WORK ASSOCIATED WITH THIS DRAWING CAN NOT BE FULLY

IMPLEMENTED UNTIL AFTER GTG INSTALLATION AND INSTALLATION OF GTG

PLATFORMS.

27. LED LIGHTING FIXTURES SHALL BE MOUNTED FROM CHAIN KIT (ITEM 14) IN LIEU

OF BEING SURFACE MOUNTED TO ENSURE PROPER COOLING.

2-6-17

DDG 51 LBES, BLDG 77H

FLIGHT III EQPT PLATFORM ARR

EHQ10546

DDG 51 LBES, BLDG 77H

FLIGHT III GTG 23'-4" LEVEL PLATFORM ARR AND DETAILS

EHQ10946

DDG 51 LBES, BLDG 77H

FLIGHT III GTG1H AND GTG3H FDN INSTALLATION DETAILS

EHQ10936

2-13-17

NOTES (CONTINUED):

28. THE GTG1H AND GTG3H MOTOR CONTROLLERS SHOWN IN SINGLE LINE DIAGRAM

SHALL BE WIRED AS FOLLOWS: INPUT POWER SHALL CONNECT TO M-3, M-9,

M-5. OUTPUT POWER TO MOTOR SHALL CONNECT TO TB3-1, TB3-2, TB3-3.

SEE NOTE 14 FOR ROTATION CHECK.

29. VERIFY NEW STEEL LOCATIONS/DIMENSIONS SHOWN IN DETAILS 69D AND 78A

AGAINST EQUIPMENT PURCHASED PRIOR TO INSTALLATION.

30. ALL ITEMS REFERRED TO IN THE NOTES ABOVE CAN BE FOUND IN THE LIST OF

MATERIALS IN THIS DRAWING.

T. Checchio

A. Cairns

5-1-17

5-2-17

DWG NO.CAGE CODESIZE REV

SCALE : AS NOTED SHEET 2

89256D

D

C

B

A

D

C

B

A

910111213141516

910111213141516

PLAN VIEW 14A

FLT III GTG1H/3H FACILITY

POWER ARRANGEMENT & DETAILS - AREA PLAN

SCALE: NONE

NORTH

ISOMETRIC VIEW 11B

FLT III GTG1H/3H FACILITY

POWER ARRANGEMENT & DETAILS

LOOKING NORTHWEST

SCALE: NONE

SEE PLAN VIEW 20A, SHEET 3,

PLAN VIEW 28A, SHEET 4,

PLAN VIEW 52A, SHEET 7,

AND PLAN VIEW 60A, SHEET 8

FLT III GTG1H/3H PWR ARR

AREA PLAN & ISOMETRIC VIEWS

EHQ10998 -

16 17 18 19 20 211514 22 23

SEE PLAN VIEW 36A,

SHEET 5

SEE PLAN VIEW 44A,

SHEET 6

FLT III GTG1H/3H FAC PWR

EQUIPMENT POWER CIRCUIT ARR

DWG NO.CAGE CODESIZE REV

SCALE : AS NOTED SHEET 3

89256D EHQ10998 -

D

C

B

A

D

C

B

A

PLAN VIEW 20A

EQUIPMENT POWER ARRANGEMENT

FLT III PLATFORM - 3'-8"/6'-6" LEVELS

SCALE: 3/8" = 1'-0"

NORTH

181615 17

D

1718192021222324

1718192021222324

GRAPHIC SCALE 3/8"=1'-0"

0 6" 2' 3' 4' 5' 10'1'

A

A

CABLE LIST F

CABLE LIST E

CABLE LIST C

CABLE LIST D

CABLE LIST G

CABLE

LIST B

CABLE

LIST A

GTG1H CLG FAN CONTROLLER

GTG3H CLG FAN CONTROLLER

PP 5-188-3

DISC SW

5-188-1

XFMR

5-188-1

PP

5-188-1

GTG1HGTG3H

JB3

JB3

CABLE LIST A

(5-188-1)-4P-B

(5-188-3)-1P-B

(5-188-3)-1P-D

(5-188-3)-1P-F

(5-188-3)-1P-A

(5-188-3)-1P-C

CABLE LIST B

(5-188-3)-1P-B

(5-188-3)-1P-D

(5-188-3)-1P-F

(5-188-3)-1P-A

(5-188-3)-1P-C

CABLE LIST C

(5-188-1)-4P-D(1)

(5-188-1)-4P-H(1)

CABLE LIST D

(5-188-3)-1P-G

(5-188-3)-1P-Q

CABLE LIST E

(5-188-1)-4P-A

(5-188-1)-4P-E

(5-188-1)-4P-F

CABLE LIST F

(5-188-3)-1P-K

(5-188-3)-1P-M

(5-188-3)-1P-P

(5-188-3)-1P-L

(5-188-3)-1P-N

CABLE LIST G

(5-188-1)-4P-B

CABLE LIST H

(5-188-1)-4P-F

(5-188-3)-1P-K

(5-188-3)-1P-M

(5-188-3)-1P-P

(5-188-3)-1P-L

(5-188-3)-1P-N

CABLE LIST I

(5-188-1)-4P-D(2)

(5-188-1)-4P-H(2)

CABLE LIST J

(5-188-1)-4P-A

GTG1HNBPS-28DC-JB5

CABLE LIST K

(5-188-1)-4P-E

GTG3HNBPS-28DC-JB5

CABLE LIST D AND I TO

23'-4" LVL (PLAN VIEW 28A

& 60A) IN NEW VERTICAL

TEE HANGER CABLEWAY

CABLE LIST JCABLE LIST K

GTG1H NBPSGTG3H NBPS

NOTE:

ALL CABLES SHOWN ON THIS PAGE SHALL BE

INSTALLED IN NEW TEE-HANGER CABLEWAY BELOW

3'-8"/6'-6" LVL PLATFORM UNLESS OTHERWISE

INDICATED

1SA-4P-(5-188-1) TO 23'-4" LVL (PLAN VIEW 36A)

IN NEW VERTICAL TEE HANGER CABLEWAY

CABLE

LIST H

JB5JB5

GTG3HNBPS-28DC-JB5

GTG1HNBPS-28DC-JB5

(5-188-1)-4P-C(1)

(5-188-1)-1P-C(1)

(5-188-1)-1P-C(2)

EQUIPMENT POWER CIRCUIT ARR

DWG NO.CAGE CODESIZE REV

SCALE : AS NOTED SHEET 4

89256D EHQ10998 -

D

C

B

A

D

C

B

A

NORTH

181615 17

D

GRAPHIC SCALE 3/8"=1'-0"

0 6" 2' 3' 4' 5' 10'1'

PLAN VIEW 28A

EQUIPMENT POWER ARRANGEMENT

FLT III PLATFORM - 23'-4" LEVEL

SCALE: 3/8" = 1'-0"

2526272829303132

2526272829303132

CABLE LIST I TO 23'-4" LVL

(PLAN VIEW 20A)

GTG1HGTG3H

CABLE LIST I

(5-188-1)-4P-D(2)

(5-188-1)-4P-H(2)

EQUIPMENT REMOVAL RAILS

GTG3H COOLING FAN GTG1H COOLING FAN

1X TROLLEY TRACK

2X TROLLEY TRACK

2X TROLLEY TRACK

6X TROLLEY TRACK

NOTES:

1. ALL CABLES SHOWN ON THIS PAGE SHALL BE INSTALLED IN

NEW TEE-HANGER CABLEWAY BELOW 23'-4" LVL PLATFORM

UNLESS OTHERWISE INDICATED.

2. CABLES SHALL BE INSTALLED ABOVE TROLLEY TRACKS TO

PRECLUDE FUTURE INTERFERENCE DURING GTG MAINTENANCE

OPERATIONS.

SCALE : AS NOTED SHEET 5

89256D -

D

C

B

A

D

C

B

A

FLT III GTG1H/3H FAC PWR

EQUIPMENT POWER CIRCUIT ARR

EHQ10998

GRAPHIC SCALE 3/8"=1'-0"

0 6" 2' 3' 4' 5' 10'1'

3334353637383940

3334353637383940

D

19 20

CONTROL HOUSE

PLAN VIEW 36A

EQUIPMENT POWER ARRANGEMENT

DDG 51 23'-4" LEVEL

SCALE: 3/8" = 1'-0"

NORTH

EPSW 23'-4"

PLATFORM

DDG 51 23'-4"

PLATFORM

FLT III DDG 51

23'-4" PLATFORM

1SA-4P-(5-188-1) TO 3'-8" LVL (PLAN VIEW 20A)

IN NEW VERTICAL TEE HANGER CABLEWAY

1SA-4P-(5-188-1) TO 32'-6" LVL (PLAN VIEW 44A)

IN EXISTING VERTICAL CABLEWAY

NOTE:

ALL CABLES ON THIS PAGE SHALL BE INSTALLED IN

NEW TEE-HANGER CABLEWAY AS REQUIRED BELOW

23'-4" LEVEL UNLESS OTHERWISE INDICATED

22 23

SCALE : AS NOTED SHEET 6

89256D -

D

C

B

A

D

C

B

A

FLT III GTG1H/3H FAC PWR

EQUIPMENT POWER CIRCUIT ARR

EHQ10998

GRAPHIC SCALE 3/8"=1'-0"

0 6" 2' 3' 4' 5' 10'1'

D

20 21

CONTROL HOUSE

1SA-4P-(5-188-1) TO 23'-4" LVL (PLAN VIEW 36A)

IN EXISTING VERTICAL CABLEWAY

NOTE:

ALL CABLES ON THIS PAGE SHALL BE INSTALLED IN

EXISTING CABLEWAY ALONG THE SIDE OF THE 32'-6"

LEVEL UNLESS OTHERWISE INDICATED

PLAN VIEW 44A

EQUIPMENT POWER ARRANGEMENT

DDG 51 32'-6" LEVEL

SCALE: 3/8" = 1'-0"

NORTH

4142434445464748

4142434445464748

1SA SWBD3SA SWBD

NEW TEE HANGER

CABLEWAY ALONG SIDE

OF 32'-6" LVL I BEAM

LIGHTING AND RECPT CKT ARR

DWG NO.CAGE CODESIZE REV

SCALE : AS NOTED SHEET 7

89256D EHQ10998 -

D

C

B

A

D

C

B

A

PLAN VIEW 52A

LIGHTING AND RECEPTACLE ARRANGEMENT

FLT III PLATFORM - 3'-8"/6'-6" LEVELS

SCALE: 3/8" = 1'-0"

NORTH

181615 17

D

GRAPHIC SCALE 3/8"=1'-0"

0 6" 2' 3' 4' 5' 10'1'

E1

E2

E3

E4

E5

R3

R6

R4

R5

R2

R1

R1R2

R3

R6

LIGHTING AND RECEPTACLE NOTES SPECIFIC TO SHEET 7:

1. DUPLEX RECEPTACLES (ITEMS 30, 31, 64) SHOWN NEXT TO

COLUMNS SHALL BE MOUNTED TO PLATFORM COLUMNS AS

SHOWN IN DETAIL 67A, 18" ABOVE PAD.

2. DUPLEX RECEPTACLES (ITEMS 30, 31, 64) SHOWN NEXT TO

EDGE OF PLATFORM SHALL BE MOUNTED TO PLATFORM

KICKPLATE AS SHOWN IN DETAIL 65A.

3. EMERGENCY LIGHTS E-1 THRU E-5 SHALL BE MOUNTED TO

PLATFORM COLUMNS WITH TOP OF FIXTURE BETWEEN

7-1/2' TO 10' ABOVE PLATFORM LEVEL TO SUIT SITE

CONDITIONS, SEE DETAIL 82B. ADJUST LIGHT HEADS AS

REQUIRED TO SUPPORT EGRESS. INSTALL WIRING PER

EMERGENCY LIGHTING ONE-LINE RISER DIAGRAM (DETAIL

86A) AND PP 5-188-3 ONE LINE DETAILS.

- DENOTES RECEPTACLE CIRCUIT

(5-188-3)-1P-J

(5-188-3)-1P-H

POWER PANEL 5-188-3

TO 23'-4" LVL

TO 23'-4" LVL

TO 23'-4" LVL

4950515253545556

4950515253545556

LIGHTING AND RECEPT CKT ARR

DWG NO.CAGE CODESIZE REV

SCALE : AS NOTED SHEET 8

89256D EHQ10998 -

D

C

B

A

D

C

B

A

NORTH

181615 17

D

GRAPHIC SCALE 3/8"=1'-0"

0 6" 2' 3' 4' 5' 10'1'

E6

E7

E8

E9

R5

R4

R7

(5-188-3)-1P-G

PLAN VIEW 60A

LIGHTING AND RECEPTACLE ARRANGEMENT

FLT III PLATFORM - 23'-4" LEVEL

SCALE: 3/8" = 1'-0"

LIGHTING AND RECEPTACLE NOTES SPECIFIC TO SHEET 8:

1. LIGHT FIXTURES (ITEM 29) AND ASSOCIATED JUNCTION BOXES

(ITEMS 30, 32) ARE TO BE SUPPORTED FROM 23'-4" LEVEL

STEEL PER TYPICAL DETAILS 87D, 84D & 84C OR EQUAL.

FIXTURE LOCATIONS MAY BE MODIFIED AS NEEDED TO SUIT

PLATFORM EQUIPMENT LOCATIONS.

2. DUPLEX RECEPTACLES (ITEMS 30, 31, 64) SHALL BE FIELD

MOUNTED IN LOCATION SHOWN PER DETAIL 82A ABOVE 23'-4"

LVL, MOUNT RECEPTACLES CLOSE TO GTG1H/GTG3H EXHAUST

STACK SUCH THAT THEY DO NOT PROVIDE A TRIP HAZARD.

3. EMERGENCY LIGHTS E-6 THRU E-9 SHALL BE MOUNTED TO NEW

8' TALL W4-13 COLUMNS WITH TOP OF FIXTURE BETWEEN 7' TO

8' ABOVE 23'-4" LVL TO SUIT SITE CONDITIONS, SEE DETAILS

84B AND 82B. ADJUST LIGHT HEADS AS REQUIRED TO SUPPORT

EGRESS. INSTALL WIRING PER EMERGENCY LIGHTING ONE-LINE

RISER DIAGRAM (DETAIL 86A) AND PP 5-188-3 ONE LINE DETAILS.

4. ADJACENT TO 23'-4" LVL EMERGENCY LIGHTS, INSTALL

CONTINUOUS ON FIXTURES VT1-VT4 (ITEM 48). THESE

SUPPLEMENT THE NORMAL HIGH BAY LIGHT FIXTURES THAT ARE

ON A DIFFERENT POWER SOURCE. THESE FIXTURES ARE REQUIRED

IN CASE HIGH BAY LIGHTING IS LOST BUT POWER REMAINS ON

AT THE GTG PLATFORM AND EMERGENCY LIGHTING DOES NOT

TURN ON.

5. CABLES SHALL BE INSTALLED ABOVE TROLLEY TRACKS TO

PRECLUDE FUTURE INTERFERENCE DURING GTG MAINTENANCE

OPERATIONS.

- DENOTES RECEPTACLE CIRCUIT

TO 6'-6" LVL

TO 6'-6" LVL

TO 6'-6" LVL

(5-188-3)-1P-G TO 3'-8" LVL (PLAN VIEW 20A)

EQUIPMENT REMOVAL RAILS

5758596061626364

5758596061626364

1X TROLLEY TRACK

2X TROLLEY TRACK

2X TROLLEY TRACK

6X TROLLEY TRACK

L

L

L

L

L

L

L

L

L

L5L6L11

L4L7L12

(5-188-3)-1P-Q TO 3'-8" LVL (PLAN VIEW 20A)

VT4

VT3

VT1

VT2

(5-188-3)-1P-Q

SCALE : AS NOTED SHEET 9

89256D -

D

C

B

A

D

C

B

A

EHQ10998

GRAPHIC SCALE 3/8"=1'-0"

0 6" 2' 3' 4' 5' 10'1'

FLT III GTG1H/3H FAC PWR

FOUNDATION & WELDING DETAILS

DETAIL 68C

BEAM CONNECTION DETAIL

SCALE: NONE

EXST BEAMW4x13 (ITEM 45)

T.O. PLATF

2X 3/4" SNIPE

COPE TO FIT

DETAIL 65D

23'-4" BEAM TO FOUNDATION

COLUMN CONNECTION DETAIL

SCALE: NONE

W6x25 (ITEM 51)

EXST FLT III

23'-4" BEAM

W6x25 (ITEM 51)

DETAIL 67C

FOUNDATION BEAM CONNECTION DETAIL

SCALE: NONE

W4x13 (ITEM 45)

W4x13 (ITEM 45)

3/16 3/16

2X 1/2" SNIPE

COPE TO FIT

DETAIL 65C

CHANNEL TO FOUNDATION

CONNECTION DETAIL

SCALE: NONE

1/8

DETAIL 68D

FLTIII BEAMS TO FOUNDATION

COLUMN CONNECTION DETAIL

SCALE: NONE

W4x13 (ITEM 45)

EXST FLT III

3'-8" BEAM

W4x13 (ITEM 45)

W4x13 (ITEM 45)

1-5/8" x 1-5/8"

CHANNEL (ITEM 36)

CRIMP TYPE HANGER

(ITEMS 38, 39, 40)

DETAIL 67B

CRIMP TYPE HANGER CONNECTION

SINGLE OR DOUBLE CABLES

SCALE: NONE

EXST SITE STEEL

TUBULAR TEE HANGER

(ITEM 37)

DETAIL 65B

TUBULAR TEE HANGER CONNECTION

MULTIPLE CABLES

SCALE: NONE

THREADED ARC WELDING

STUD (ITEM 65)

EXST SITE STEEL

PARTIAL PLAN VIEW 69D

TRANSFORMER 5-188-1 FOUNDATION

FLT III 3'-8" PLATFORM

SCALE: 3/8" = 1'-0"

DETAIL 67A

DUPLEX RCPT TO COLUMN CONNECTION

SCALE: NONE

2X BEAM CLAMP

(ITEM 34)

EXST SITE STEEL

4" SQ J-BOX

(ITEM 30)

RCPT BOX COVER

(ITEM 31)

DUPLEX RCPT

(ITEM 64) DETAIL 65A

DUPLEX RCPT TO KICK PLATE

CONNECTION

SCALE: NONE

2X BEAM CLAMP

(ITEM 34)

EXST SITE STEEL

EXST KICK PLATE

3/16

3/16

3/16

1/8

3/8

3/16 3/16

THREADED ARC WELDING

STUD (ITEM 41)

3/8

4'-2"

5'-11

2X DET 68C W4x13 (ITEM 45)

A

A

GTG1H CLG FAN

CONTROLLER

GTG3H CLG FAN

CONTROLLER

PP 5-188-3

DISC SW

5-188-1

XFMR

5-188-1

PP

5-188-1

1'-5

8"

1'-8

3"

PARTIAL PLAN VIEW 71C

EQUIPMENT FOUNDATIONS DETAIL

FLT III 3'-8"/6'-6" PLATFORM

SCALE: 3/8" = 1'-0"

DETAIL 70A

FOUNDATION BASE PLATE AND CONCRETE ANCHOR

SCALE: NONE

3/4" PLATE

(ITEM 49)

W6x25

(ITEM 51)

3/16

1/2" ANCHOR

BOLT, WASHER,

NUT (ITEM 53)

NOM

IMBEDMENT

ITEM 51

3/4" PLATE

(ITEM 49)

3/4" NOM GROUT

DETAIL 68A

FOUNDATION KICKPLATE

CONNECTION DETAIL

SCALE: NONE

W4x13 (ITEM 45)

EXST FLT III

3'-8" BEAM

1 1/2"

1X 1/4"X4"

FLATBAR

KICKPLATE

(ITEM 50)

R1 R2 R5 R3 R4

R6 R7

R1 R2 R3 R6 R4 R5

PP 5-188-3

2P

20A

LSTSGU-9 (TYP)

11X CABLE

CONNECTOR (ITEM 33)

LSTSGU-9 (TYP)

13X CABLE CONNECTOR

(ITEM 33)

2P

20A (5-188-3)-1P-H

LSTSGU-9

(5-188-3)-1P-J

LSTSGU-9

DETAIL 69B

CONVENIENCE RECEPTACLE CONNECTION DIAGRAM

SCALE: NONE

7X SQR BOX,

RECEPTACLE, COVER

PLATE (ITEMS 30, 31, 64)

6X SQR BOX,

RECEPTACLE, COVER

PLATE (ITEMS 30, 31, 64)

6566676869707172

6566676869707172

1/4"

3/16"

" 6"

" 1

1'

6"

1'

1/2" ANCHOR

BOLT, WASHER,

NUT (ITEM 53)

2X

3/16

2X

SCALE : AS NOTED SHEET 10

89256D -

D

C

B

A

D

C

B

A

FLT III GTG1H/3H FAC PWR

EQPT FOUNDATION DETAILS

EHQ10998

PARTIAL ELEVATION 78A

POWER PANEL & TRANSFORMER ARRANGEMENT

FLTIII 3'-8" PLATFORM

SCALE: 3/4" = 1'-0"

NORTH

PAD LVL 0'-0"

FLT III 3'-8" PLTF

PARTIAL ELEVATION 75A

COOLING FAN MOTOR CONTROLLER ARRANGEMENT

FLTIII 6'-6" PLATFORM

SCALE: 3/4" = 1'-0"

NORTH

PAD LVL 0'-0"

FLT III 6'-6" PLTF

AS REQ'D

AS REQ'D

7'-9"

8'

1'-0

2'-0

3'-10

4'-11

6'-6

8'

3X W4X13

(ITEM 45)

3X 1-5/8" x 1-5/8"

CHANNEL (ITEM 36)

2'-2"

16X DET 65C

5X 1-5/8" x 1-5/8"

CHANNEL (ITEM 36)

3X W4X13

(ITEM 45)

4'-2"

4X DET 67C

4X DET 68D

FLT III 23'-4" PLTF

PP 5-188-1

(ITEM 1)

DISC SW

5-188-1

(ITEM 3)

PP

5-188-3

(ITEM 2)

XFMR 5-188-1

(ITEM 5)

1'-7

3'-1

4'-8

6'-4

6'-5

7'-11

10X DET 65C

2X DET 65D

2X DET 70A

2X W6X25

(ITEM 51)

5X 1-5/8"x1-5/8"

CHANNEL (ITEM 36)

22'-1

3'-3

1X 1/4"X4"

FLATBAR

KICKPLATE

(ITEM 50)

1X 1/4"X4"

FLATBAR

KICKPLATE

(ITEM 50)

4X DET 68A

REMOVE INDICATED

HANDRAILS AND

WELD REMAINING

HANDRAILS TO

FND PER NOTE 18

GRAPHIC SCALE 3/4"=1'-0"

0 6" 2' 3' 4' 5'1'

7374757677787980

7374757677787980

SEE DET 69D

GTGH1 CLG

FAN MOTOR

CONTROLLER

(ITEM 4)

GTGH3 CLG

FAN MOTOR

CONTROLLER

(ITEM 4)

SCALE : AS NOTED SHEET 11

89256D -

D

C

B

A

D

C

B

A

EHQ10998

FLT III GTG1H/3H FAC PWR

MISCELLANEOUS DETAILS

23'-4" LVL

EXST SITE STEEL

24"

(MAX)

LED LIGHT

FIXTURE (ITEM 29)

DETAIL 84D

LIGHT FIXTURE MOUNTING DETAIL

SCALE: NONE

2X BEAM CLAMP

(ITEM 47)

2X 1-5/8" x 1-5/8" CHANNEL

(ITEM 36) (LENGTH AS REQ'D)

23'-4" LVL

EXST PLATFORM STEEL

LED LTG FIXTURE

(ITEM 29)

2X BEAM CLAMP

(ITEM 47)

2X 1-5/8" x 1-5/8" CHANNEL

(ITEM 36) (LENGTH AS REQ'D)

23'-4" LVL

EXST SITE STEEL

LED LIGHT

FIXTURE (ITEM 29)

DETAIL 84C

LIGHT FIXTURE MOUNTING DETAIL

SCALE: NONE

4X BEAM CLAMP

(ITEM 47)

1-5/8" x 1-5/8" CHANNEL

(ITEM 36) (LENGTH AS REQ'D)

23'-4" LVL

EXST PLATFORM STEEL

4X BEAM CLAMP

(ITEM 47)

1-5/8" x 1-5/8" CHANNEL

(ITEM 36) (LENGTH AS REQ'D)

LED LTG FIXTURE

(ITEM 29)

E1 PWR PNL

5-188-3

BRKR "T"

E2

3'-8"/6'-6" LEVELS

23'-4" LEVEL

E6 E7

CABLE CONNECTOR

(ITEM 33) (TYP)

CABLE CONNECTOR

(ITEM 33) (TYP)

(1) LSTSGU-4

(TYP)

(11X) 4" SQ BOX & COVER

(ITEMS 30 & 32)

(9X) EMERGENCY LIGHT

FIXTURE (ITEM 16)

NOTE:

1. SEE SHEETS 7 AND 8 FOR EMERGENCY LIGHT

FIXTURE LOCATIONS ON PLATFORM.

DETAIL 86A

EMERGENCY LIGHTING

ONE-LINE RISER DIAGRAM

SCALE: NONE

NEW OR EXST

PLATFORM

COLUMN

2X 1-5/8" x 1-5/8" CHANNEL

(ITEM 36) (LENGTH AS REQ'D)

EMERGENCY LIGHT

FIXTURE (ITEM 16)

DETAIL 83B

EMERGENCY LIGHT FIXTURE

MOUNTING DETAIL

SCALE: NONE

DETAIL 84B

FLTIII BEAMS TO FOUNDATION

COLUMN CONNECTION DETAIL

SCALE: NONE

W4x13 (ITEM 45)

EXST FLT III

23'-4" BEAM

W4x13 (ITEM 45)

3/16

3/16

8'

E4

E9

E3

E8

E5

8182838485868788

8182838485868788

PP 5-188-3

2P

20A (5-188-3)-1P-G

LSTSGU-9

9X SQR BOX, COVER PLATE

(ITEMS 30 AND 32)

L1

L4 L5

L8 L10

L12

L13 L15

DETAIL 86B

LIGHTING CONNECTION DIAGRAM

SCALE: NONE

LSTSGU-9 (TYP)

31X CABLE

CONNECTOR (ITEM 33)

15X STUFFING

TUBE/PACKING

ASSEMBLY

(ITEMS 60

AND 55)L7

DETAIL 82A

DUPLEX RCPT TO 4X4 ANGLE

CONNECTION

SCALE: NONE

2X BEAM CLAMP

(ITEM 34)

EXST SITE STEEL

4" X 4" X 1/4" ANGLE

(18" HIGH) (ITEM 66)

4" SQ J-BOX

(ITEM 30)

DUPLEX RCPT

(ITEM 64)

RCPT BOX COVER

(ITEM 31)

1/8

(5-188-3)-1P-T

.5"

CHAIN HANGING KIT (ITEM 14) (SEE NOTE 27)

(UTILIZE S HOOK TO ADJUST LAMP HEIGHT AND SECURE AROUND CHANNEL)

SECURE CHAIN TO CHANNEL WITH SCREW/BOLT TO

PREVENT FALLING OFF END OF CHANNEL

CHAIN HANGING KIT (ITEM 14)

(SEE NOTE 27)

CHAIN HANGING KIT (ITEM 14)

(SEE NOTE 27) (UTILIZE S HOOK TO

ADJUST LAMP HEIGHT AND SECURE

AROUND CHANNEL)

CHAIN HANGING KIT (ITEM 14)

3'

3'

L3

2P

20A (5-188-3)-1P-Q

LSTSGU-9

L2

L6 L9

L11 L14

VT3

CABLE CONNECTOR

(ITEM 33) (TYP)4X VAPORTIGHT

LIGHT (ITEM 48)

VT4 VT1 VT2

1/8 2X

2X 1-5/8" x 1-5/8" CHANNEL

(ITEM 36) (LENGTH AS REQ'D)

NEW OR EXST

PLATFORM

COLUMN

6" X 6" X 3/16" MOUNTING PLATE

(ITEM 52)

VAPORTIGHT LIGHT FIXTURE (ITEM 48)

6" X 6" X 3/16" MOUNTING PLATE

(ITEM 52)

VAPORTIGHT LIGHT FIXTURE (ITEM 48)

1/8 2X

SCALE : AS NOTED SHEET 12

89256D -

D

C

B

A

D

C

B

A

FROM EXISTING 1SA SWITCHBOARD

EXISTING 400AF/400AT CIRCUIT BREAKER*

PP 5-188-1

480VAC, 3∅, 3W, 400A

FLT III PLTF, 3'-8" LVL

1SA-4P-(5-188-1)

(2) LSFSGU-150

400AΔ

MAIN

3P

60A

3P

15A

3P

70A

3P

80A

3P SPACE

XFMR 5-188-1 (ITEM 5)

480V-120V

45KVA

2P

15A (5-188-3)-1P-B

LSTSGU-4 2P

20A (5-188-3)-1P-A

LSTSGU-9

2P

15A (5-188-3)-1P-C

LSTSGU-42P

15A

2P

15A

2P

20A

2P

15A

2P

15A

2P

15A

(5-188-1)-1P-C(1)

3-1C-250MCM, THHN/THWN

1-1C-#2 AWG, THHN/THWN GND

IN 2-1/2" LFMC

(CONNECT GND CONDUCTOR TO

GND BUSHINGS + SOURCE/LOAD

GND BUS OR TERMINAL)

2P

15A (5-188-3)-1P-E

LSTSGU-4

2P

20A

2P

20A

2P

20A

2P

15A

2P

20A

GTG1H JB3 RIMMS BAT CHGR GTG1H JB3 GEN HTRS

(5-188-3)-1P-D

LSTSGU-4

GTG1H JB3 SKID RECEPTACLES

(5-188-3)-1P-F

LSTSGU-4

GTG1H JB3 MODULE LTG

2P

15A

GTG1H JB3 FADC PWR AND UV DETECTION

GTG1H HFP SYSTEM (FUTURE)

2P

15A

2P

15A

.6 KVA

1 KVA

1.4 KVA

1.8 KVA

1.4 KVA

1.2 KVA

FLT III GTG1H/3H FAC PWR

SINGLE LINE DIAGRAM

EHQ10998

2X STUFFING

TUBE/PACKING

ASSEMBLY

FOR LSFSGU-50

(ITEMS 56, 62)

2X LIQUIDTIGHT STRAIGHT

CONNECTOR/GND BUSHING

FOR 2-1/2" LFMC (ITEMS 26, 27)

3P

60A

3P

15A

3P

70A

(5-188-1)-4P-A

LSFSGU-4

GTG1H NBPS3.9 KVA

(5-188-1)-4P-E

LSFSGU-4

GTG3H NBPS3.9 KVA

(5-188-1)-4P-B

LSFSGU-23

GTG1H JB3 AUX LUBO

OIL PUMP

23 KVA

(5-188-1)-4P-D(1)

LSFSGU-23

LVR MC

(5-188-1)-4P-F

LSFSGU-23

GTG3H JB3 AUX LUBO

OIL PUMP

23 KVA

(5-188-1)-4P-H(1)

LSFSGU-23

LVR MC

(5-188-3)-1P-G

LSTSGU-9

(5-188-3)-1P-H

LSTSGU-9

GTG1H/3H PLATFORM RECEPTACLES

(DETAIL 69B)

GTG1H/3H PLATFORM LIGHTING

(DETAIL 86B)

0.6 KVA

(5-188-3)-1P-J

LSTSGU-9

(5-188-3)-1P-K

LSTSGU-4

GTG3H JB3 RIMMS BAT CHGR

GTG1H/3 PLATFORM RECEPTACLES

(DETAIL 69B)

.6 KVA

(5-188-3)-1P-L

LSTSGU-9

(5-188-3)-1P-M

LSTSGU-4

GTG3H JB3 SKID RECEPTACLES GTG3H JB3 GEN HTRS1 KVA 1.8 KVA

(5-188-3)-1P-N

LSTSGU-4

(5-188-3)-1P-P

LSTSGU-4

GTG3H JB3 MODULE LIGHTING GTG3H JB3 FADC PWR AND UV DETECTION1.4 KVA 1.4 KVA

(5-188-3)-1P-R

LSTSGU-4

GTG3H HFP SYSTEM (FUTURE) 1.2 KVA

(5-188-1)-4P-C(1)

LSFSGU-50

(1.1 KVA)

(1.1 KVA)

250A

DISC SW 5-188-1

400 AMP

(ITEM 3)

2X LIQUIDTIGHT STRAIGHT CONNECTOR/GND BUSHING

FOR 2-1/2" LFMC (ITEMS 26, 27)

(5-188-1)-4P-D(2)

LSFSGU-23

GTG1H COOLING FAN 28 KVA

(5-188-1)-4P-H(2)

LSFSGU-23

GTG3H COOLING FAN 28 KVA

(5-188-3)-1P-T

LSTSGU-4

GTG1H/3H PLATFORM

EMERGENCY LIGHTING

(DETAIL 86A)

0.4 KVA

(5-188-1)-1P-C(2)

3-1C-250MCM, THHN/THWN

1-1C-#2 AWG, THHN/THWN GND

IN 2-1/2" LFMC

(CONNECT GND CONDUCTOR TO GND BUSHINGS + SOURCE/LOAD GND BUS OR TERMINAL)

SPARE

FUTURE GTG2H PWR AVAILABLE

ITEM 2

ITEM 1

8990919293949596

8990919293949596

FLT III

PLATFORM

STEEL

GROUND POWER

PANEL TO FLT III

PLATFORM STEEL

USING ITEM 24

FLT III PLATFORM STEEL

GROUND POWER

PANEL TO FLT III

PLATFORM STEEL

USING ITEM 23

* = SET LONG TIME (LT) PICKUP AT 1XP(400A) = 400A

SET LT DELAY TO 6 SECONDS AT 6XP

SET INSTANTANEOUS TRIP TO 6X400A = 2400A

PP 5-188-3

120VAC, 3∅, 3W, MLO (ALB-1)

FLT III PLTF, 3'-8" LVL

3P3P

SPACESPACE

GTG1H NBPS

TB1-3

TB1-8

GTG1H JB5

GTG1HNBPS-28DC-JB5

LSTSGU-23

GTG3H NBPS

TB1-3

TB1-8

GTG3H JB5

GTG3HNBPS-28DC-JB5

LSTSGU-23

DETAIL 90C

28VDC CONNECTION DIAGRAM

SCALE: NONE

2X STUFFING TUBE/PACKING ASSEMBLY

(ITEMS 56, 71)

2X STUFFING TUBE/PACKING ASSEMBLY

(ITEMS 56, 71)

GND

GND

(SEE NOTE 29)

(SEE NOTE 28)

(SEE NOTE 29)

(SEE NOTE 28)

GND DET

(5-188-3)-1P-Q

LSTSGU-9

0.3 KVA

GTG1H/3H PLATFORM LIGHTING

(DETAIL 86B)

Δ = SET ADJUSTABLE INSTANTANEOUS TRIP TO 2400A

SCALE : AS NOTED SHEET 13

89256D -

D

C

B

A

D

C

B

A

FLT III GTG1H/3H FAC PWR

ELECTRICAL CONNECTION TABLES

EHQ10998

TABLE 104D: POWER PANEL 5-188-1 CABLE PENETRATIONS

CIRCUIT NAME CONNECTED DEVICE

STUFFING TUBE

AT POWER

PANEL

PACKING

ASSEMBLY AT

POWER PANEL

STUFFING TUBE

AT CONNECTED

DEVICE

PACKING

ASSEMBLY AT

CONNECTED

DEVICE

(5-188-1)-4P-A GTG1H NBPS ITEM 55 ITEM 59 ITEM 55 ITEM 59

(5-188-1)-4P-B

GTG1H JB3 AUX LUBO

OIL PUMP

ITEM 56 ITEM 61 ITEM 56 ITEM 61

(5-188-1)-4P-D(1)

GTG1H COOLING FAN

CONTROLLER

ITEM 56 ITEM 61 ITEM 56 ITEM 61

(5-188-1)-4P-D(2) GTG1H COOLING FAN ITEM 56 ITEM 61 ITEM 56 ITEM 61

(5-188-1)-4P-E GTG3H NBPS ITEM 55 ITEM 59 ITEM 55 ITEM 59

(5-188-1)-4P-F

GTG3H JB3 AUX LUBO

OIL PUMP

ITEM 56 ITEM 61 ITEM 56 ITEM 61

(5-188-1)-4P-H(1)

GTG3H COOLING FAN

CONTROLLER

ITEM 56 ITEM 61 ITEM 56 ITEM 61

(5-188-1)-4P-H(2) GTG3H COOLING FAN ITEM 56 ITEM 61 ITEM 56 ITEM 61

TABLE 104C: POWER PANEL 5-188-3 CABLE PENETRATIONS

CIRCUIT NAME CONNECTED DEVICE

STUFFING TUBE

AT POWER

PANEL

PACKING

ASSEMBLY AT

POWER PANEL

STUFFING TUBE

AT CONNECTED

DEVICE

PACKING

ASSEMBLY AT

CONNECTED

DEVICE

(5-188-3)-1P-A GTG1H JB3 GEN HTRS ITEM 55 ITEM 60 ITEM 55 ITEM 60

(5-188-3)-1P-B

GTG1H JB3 RIMMS

BAT CHGR

ITEM 54 ITEM 58 ITEM 54 ITEM 58

(5-188-3)-1P-C

GTG1H JB3 FADC PWR

AND UV DETECTION

ITEM 54 ITEM 58 ITEM 54 ITEM 58

(5-188-3)-1P-D

GTG1H JB3 SKID

RECEPTACLES

ITEM 54 ITEM 58 ITEM 54 ITEM 58

(5-188-3)-1P-F

GTG1H JB3 MODULE

LTG

ITEM 54 ITEM 58 ITEM 54 ITEM 58

(5-188-3)-1P-G

GTG1H/3H PLATFORM

LIGHTING

ITEM 55 ITEM 60 SEE DETAIL 86B

(5-188-3)-1P-H

GTG1H/3H PLATFORM

RECPTACLES

ITEM 55 ITEM 60 SEE DETAIL 69B

(5-188-3)-1P-J

GTG1H/3 PLATFORM

RECEPTACLES

ITEM 55 ITEM 60 SEE DETAIL 69B

(5-188-3)-1P-K

GTG3H JB3 RIMMS

BAT CHGR

ITEM 54 ITEM 58 ITEM 54 ITEM 58

(5-188-3)-1P-L GTG3H JB3 GEN HTRS ITEM 55 ITEM 60 ITEM 55 ITEM 60

(5-188-3)-1P-M

GTG3H JB3 SKID

RECEPTACLES

ITEM 54 ITEM 58 ITEM 54 ITEM 58

(5-188-3)-1P-N

GTG3H JB3 FADC PWR

AND UV DETECTION

ITEM 54 ITEM 58 ITEM 54 ITEM 58

(5-188-3)-1P-P

GTG3H JB3 MODULE

LIGHTING

ITEM 54 ITEM 58 ITEM 54 ITEM 58

(5-188-3)-1P-T

GTG1H/3H PLATFORM

EMERGENCY LIGHTING

ITEM 54 ITEM 58 SEE DETAIL 86A

(5-188-3)-1P-Q

GTG1H/3H PLATFORM

LTG

ITEM 55 ITEM 60 SEE DETAIL 86B

TABLE 99D: 120VAC CABLE TERMINATIONS IN GTG1H/GTG3H

JB3

CIRCUIT NAME CONNECTED DEVICE

HOT 1 TERMINAL

BLOCK AT CONNECTED

DEVICE

HOT 2 TERMINAL

BLOCK AT CONNECTED

DEVICE

GROUND CONDUCTOR

TERMINAL BLOCK AT

CONNECTED DEVICE

(5-188-3)-1P-A GTG1H JB3 GEN HTRS TB2-6 TB2-7 GND BUS/FRAME

(5-188-3)-1P-B

GTG1H JB3 RIMMS

BAT CHGR

TB1-9 TB1-10 GND BUS/FRAME

(5-188-3)-1P-C

GTG1H JB3 FADC PWR

AND UV DETECTION

TB1-11 TB1-12 GND BUS/FRAME

(5-188-3)-1P-D

GTG1H JB3 SKID

RECEPTACLES

TB1-1 TB1-2 GND BUS/FRAME

(5-188-3)-1P-F

GTG1H JB3 MODULE

LTG

TB1-6 TB1-7 GND BUS/FRAME

(5-188-3)-1P-K

GTG3H JB3 RIMMS

BAT CHGR

TB1-9 TB1-10 GND BUS/FRAME

(5-188-3)-1P-L GTG3H JB3 GEN HTRS TB2-6 TB2-7 GND BUS/FRAME

(5-188-3)-1P-M

GTG3H JB3 SKID

RECEPTACLES

TB1-1 TB1-2 GND BUS/FRAME

(5-188-3)-1P-N

GTG3H JB3 FADC PWR

AND UV DETECTION

TB1-11 TB1-12 GND BUS/FRAME

(5-188-3)-1P-P

GTG3H JB3 MODULE

LIGHTING

TB1-6 TB1-7 GND BUS/FRAME

TABLE 99C: 480VAC CABLE TERMINATIONS IN GTG1H/GTG3H JB3

CIRCUIT NAME CONNECTED DEVICE

PHASE A TERMINAL

BLOCK AT CONNECTED

DEVICE

PHASE B TERMINAL

BLOCK AT CONNECTED

DEVICE

PHASE C TERMINAL

BLOCK AT CONNECTED

DEVICE

GROUND CONDUCTOR

TERMINAL BLOCK AT

CONNECTED DEVICE

(5-188-1)-4P-B

GTG1H JB3 AUX LUBO

OIL PUMP

TB3-1 TB3-2 TB3-3 GND BUS/FRAME

(5-188-1)-4P-F

GTG3H JB3 AUX LUBO

OIL PUMP

TB3-1 TB3-3 TB3-3 GND BUS/FRAME

979899100101102103104

979899100101102103104

SCALE : AS NOTED SHEET 14

89256D -

D

C

B

A

D

C

B

A

FLT III GTG1H/3H FAC PWR

LIST OF MATERIALS

EHQ10998

105106107108109110111112

105106107108109110111112

LIST OF MATERIAL

ITEM QTY DESCRIPTION MATERIAL SPECIFICATION REMARKS

1 1

PANELBOARD, 400A W/BOTTOM FEED 400A MAIN

THERMAL MAGNETIC BRKR, 480VAC, 3PH, 3W, SPACE

FOR AT LEAST (8) 100AF(3) POLE BRANCH BREAKERS,

65KAIC AT 480V, NEMA 1 ENCL, MAX DIMENSIONS ARE

74"H x 28"W x 7"D, SURFACE MTD W/DOOR, INCLUDES

GND BUS, MUST BE RATED TO GND AT 480V MINIMUM

SINCE PANEL IS CONNECTED TO DELTA PWR SYSTEM,

UL LISTED

VARIOUS COMMERCIAL

2 1

PANELBOARD, 125VAC, 3PH, 400A, (14) 3PH OR (20)

1PH, CKTS, TYPE ALB-1, 37.5"H x 15.44"W x 6.5"D, WITH OPTIONAL GROUND DETECTOR (SYMBOL 1005.1

TYPE OR EQUAL)

VARIOUS MIL-DTL-23928/1D

MIL-DTL-23928/1-16DP WITH OPTIONAL GND

DETECTOR

3 1

FUSED DISCONNECT SWITCH, HEAVY DUTY, 240 VAC,

400 AMPS, 3 FUSED POLES, CLASS H FUSE CLIPS,

NEMA 1 ENCL, GROUND LUG, MAX DIMENSIONS WITH

HANDLE TRAVEL ARE 51"HX28"WX12.75"D, UL LISTED

VARIOUS COMMERCIAL

4 2

GTGH1/GTGH3 COOLING FAN MOTOR CONTROLLERS,

440V, 3PH, 50HP MOTOR, 115V CONTROL, INCLUDES CPT,

22"H X 20"W X 9.12"D

VARIOUS MILITARY

GOVERNMENT FURNISHED EQUIPMENT. REF

DRS DWG MC-04015. SOLE SOURCE

PROCUREMENT TO MATCH SHIP

5 1

TRANSFORMER, 45KVA, 480-120V, 3PH, DELTA-DELTA,

(2) FCAN 2.5% TAPS, (4) FCBN 2.5% TAPS, 4.5%-5.6%

IMPEDANCE, NEMA 1 ENCLOSURE, MAX DIMENSIONS ARE

33"H X 28"W X 18"D, UL LISTED

VARIOUS COMMERCIAL

6 2

CIRCUIT BRKR, 480VAC, 15A, 3 POLE, THERMAL

MAGNETIC, FULL RATED 65KAIC AT 480VAC OR SERIES

RATED 65KAIC AT 480V W/UPSTREAM MAIN BRKR IN

ITEM 1, COMPATIBLE FOR USE AS BRANCH BREAKER IN

ITEM 1, MUST BE RATED FOR 480V PH TO GROUND

MINIMUM, UL LISTED

VARIOUS COMMERCIAL

7 2

CIRCUIT BRKR, 480V, 60A, 3 POLE, THERMAL MAGNETIC,

FULL RATED 65KAIC AT 480VAC OR SERIES RATED

65KAIC AT 480V W/UPSTREAM MAIN BRKR IN ITEM 1,

COMPATIBLE FOR USE AS BRANCH BREAKER IN ITEM 1,

MUST BE RATED FOR 480V PH TO GROUND MINIMUM, UL

LISTED

VARIOUS COMMERCIAL

8 2

CIRCUIT BRKR, 480V, 70A, 3 POLE, THERMAL MAGNETIC,

FULL RATED 65KAIC OR SERIES RATED 65KAIC AT 480V

W/UPSTREAM MAIN BRKR IN ITEM 1, COMPATIBLE FOR

USE AS BRANCH BREAKER IN ITEM 1, MUST BE RATED

FOR 480V PH TO GROUND MINIMUM, UL LISTED

VARIOUS COMMERCIAL

9 1

CIRCUIT BRKR, 480V, 80A, 3 POLE, THERMAL MAGNETIC,

FULL RATED 65KAIC AT 480VAC OR SERIES RATED

65KAIC AT 480V W/UPSTREAM MAIN BRKR IN ITEM 1,

COMPATIBLE FOR USE AS BRANCH BREAKER IN ITEM 1,

MUST BE RATED FOR 480V PH TO GROUND MINIMUM, UL

LISTED

VARIOUS COMMERCIAL

10 26

CIRCUIT BRKR, 1 POLE, 15A, 125VAC, TYPE ALB-1, 5KA

INTERRUPTING CAPACITY

VARIOUS MIL-C-17588 NSN 5925-00-244-1756

11 10

CIRCUIT BRKR, 1 POLE, 20A, 125VAC, TYPE ALB-1, 5KA

INTERRUPTING CAPACITY

VARIOUS MIL-C-17588 NSN 5925-00-501-5051

12 16 BREAKER HANDLE YOKE, 2 POLE, TYPE ALB-1 VARIOUS MIL-C-17588 NSN 5925-00-202-0938

13 1 BREAKER HANDLE YOKE, 3 POLE, TYPE ALB-1 VARIOUS MIL-C-17588 NSN 5925-00-862-5582

14 15

CHAIN HANGING KIT FOR LED LTG FIXTURE (ITEM 29),

PAIR, 36" LONG

VARIOUS COMMERCIAL

15 6

"FUSE, 250 VAC, 250A, DUAL ELEMENT, TIME DELAY,

CLASS RK5, 200 KAIC @ 250 VAC, UL LISTED"

VARIOUS COMMERCIAL INCLUDES 3 SPARES. USE WITH ITEM 3

16 9

EMERGENCY LIGHT (2) ADJUSTABLE 7.2W PAR 36

SEALED BEAM LAMPS, 120/277VAC INPUT, INCLUDES

TEST SWITCH, AC LOCKOUT SW WHICH PREVENTS

DISCHARGE, 20W MAX LOAD, METAL ENCLOSURE, MAX

DIMENSIONS INCLUDING HEADS ARE 12"H X 16"W X 6"D,

1-1/2 HOUR CAPACITY AT 16WATTS, INCLUDES

CHARGER, LOW VOLTAGE BATTERY DISCONNECT, 10-40

DEG C OPERATION, UL LISTED

VARIOUS COMMERCIAL

LF

CABLE, LSTSGU-4, 3C-#14AWG, STRANDED COPPER

CONDUCTOR, 1000V, O.D. = .449"

VARIOUS MIL-C-24643 NSN 6145-01-201-9498

LF

CABLE, LSTSGU-9, 3C-#10AWG, STRANDED COPPER

CONDUCTOR, 1000V, O.D. = .575"

VARIOUS MIL-C-24643 NSN 6145-01-201-9499

LF

CABLE, LSFSGU-4, 4C-#14AWG, STRANDED COPPER

CONDUCTOR, 1000V, O.D. = .513"

VARIOUS MIL-C-24643 NSN-6145-01-210-2344

LIST OF MATERIAL (CONTINUED)

ITEM QTY DESCRIPTION MATERIAL SPECIFICATION REMARKS

LF

CABLE, LSFSGU-23, 4C-#7AWG, STRANDED COPPER

CONDUCTOR, 1000V, O.D. = .890"

VARIOUS MIL-C-24643 NSN-6145-01-202-3479

LF

CABLE, LSFSGU-50, 4C-#3AWG, STRANDED COPPER

CONDUCTOR, 1000V, O.D. = 1.05"

VARIOUS MIL-C-24643 NSN 6145-01-205-3629

LF

CABLE, LSFSGU-150, 4C-3/0AWG, STRANDED COPPER

CONDUCTOR, 1000V, O.D. = 1.625"

VARIOUS MIL-C-24643 NSN-6145-01-202-6957

LF

BUILDING WIRE, 1C-#2AWG, STRANDED COPPER,

THHN/THWN 600V INSULATION, O.D. = .39", UL LISTED

VARIOUS COMMERCIAL USE FOR POWER PANEL GROUNDING.

LF

BUILDING WIRE, 1C-#250 MCM, STRANDED COPPER,

THHN/THWN 600V INSULATION, O.D. = .72", UL LISTED

VARIOUS COMMERCIAL

LF

LIQUID TIGHT CONDUIT, 2.5" DIAMETER, PVC UV

RESISTANT JACKET, FLEXIBLE STEEL CORE, 8" MIN

BEND RADIUS, 105C IN AIR, 60C WET, 70C OIL, UL

LISTED

VARIOUS COMMERCIAL

26 4 LIQUIDTIGHT STRAIGHT CONNECTOR, 2.5", UL LISTED

ZINC PLATED

MALLEABLE IRON

COMMERCIAL

27 4

GROUNDING BUSHING, 2.5"DIAMETER, THREADED,

INSULATED SLEEVE, #6 - 4/0 GROUND WIRE RANGE, UL

LISTED

ZINC PLATED

MALLEABLE IRON

COMMERCIAL

28 4

2.5" CONDUIT CLAMP, MIN LOAD RATINGS OF 800LB

VERTICAL, 125LB ALONG AXIS OF CHANNEL, 125LB

PERPENDICULAR TO CHANNEL

ZINC PLATED

CARBON STEEL

COMMERCIAL

29 15

LIGHT FIXTURE, HIGH BAY LED, 8000 LUMENS,

STANDARD EFFICIENCY, GENERAL DISTRIBUTION ACRYLIC

FROSTED LENS, 55 WATTS, 120V, 40K/70 CRI, HIGH

AMBIENT 55 DEGREES C, GLOSS WHITE METAL

ENCLOSURE, RECOMMENDED MTG HEIGHT 10 - 20 FEET,

MAX SPACING TO MTG HEIGHT = 1.25 TO 1.35, COEF OF

UTILIZATION APPROX .4 @0% REFLECTANCE ON CEILING

& WALL AND 20% ON CEILING WITH RCR = 5, SUITABLE

FOR CHAIN HANGING, DIMENSIONS APPROX 26"L X 12"W

X 3"H, UL LISTED

VARIOUS COMMERCIAL

30 33

4" SQUARE JUNCTION BOX, 2-1/8"D, (8)-1/2" KO ON

SIDES & (4)-1/2"&3/4"E KO ON SIDES, GROUND BUMP &

ADDITIONAL KO'S ON BACK, INDOOR USE, 30.3 CU IN

CAPACITY, UL LISTED

PRE-GALVANIZED

CARBON STEEL

COMMERCIAL

31 13

4" SQUARE BOX COVER, 1/2"D, FOR SINGLE DUPLEX

RECEPTACLE, 5 CU IN CAPACITY, FOR USE WITH ITEM

30, UL LISTED

PRE-GALVANIZED

CARBON STEEL

COMMERCIAL

32 20

4" SQUARE BOX COVER, FLAT, BLANK, FOR USE WITH

ITEM 30, UL LISTED

PRE-GALVANIZED

CARBON STEEL

COMMERCIAL

33 100

CABLE CONNECTOR, NYLON INSULATED, INCLUDES

LOCKNUT FOR 1/2" KO, CABLE RANGE .250" - .590", UL

LISTED

VARIOUS COMMERCIAL

USE AT LTG & RCPT JUNC BOXES, EMER

LTG FIXTURES.

AS

REQD

BEAM CLAMP, 5/8" JAW OPENING, 10-24 TAPPED HOLE

SIZES ON BOTTOM & SIDE, 150LB MIN LOAD RATING,

CSA LISTED

ZINC PLATED

CARBON STEEL

COMMERCIAL

AS

REQD

BEAM CLAMP, 5/8" JAW OPENING, 1/4-20 TAPPED HOLE

SIZES ON BOTTOM & SIDE, 250LB MIN LOAD RATING,

CSA LISTED

ZINC PLATED

CARBON STEEL

COMMERCIAL

AS

REQD

CHANNEL, 1-5/8" x 1-5/8", 12 GAUGE, 10 FT LENGTH, MEETS ASTM A108, A1011, B633, MFMA-1

PRE-GALVANIZED

STEEL

COMMERCIAL

37 200

MILITARY CABLE HANGER, TUBULAR TEE TYPE, 6.5"

LONG, 3/8-16 FEMALE THREAD

ZINC PLATED

CARBON STEEL

US NAVY

APPROVED

38 200

MILITARY CABLE HANGER, SINGLE CRIMP-LOK TYPE,

3/8-16 FEMALE THREAD,

.375" - .531" CABLE RANGE

ZINC PLATED

CARBON STEEL

US NAVY

APPROVED

39 100

MILITARY CABLE HANGER, SINGLE CRIMP-LOK TYPE,

3/8-16 FEMALE THREAD,

.531" - .680" CABLE RANGE

ZINC PLATED

CARBON STEEL

US NAVY

APPROVED

40 100

MILITARY CABLE HANGER, DOUBLE CRIMP-LOK TYPE,

3/8 "-16 FEMALE THREAD, .531" - .680" CABLE RANGE

ZINC PLATED

CARBON STEEL

US NAVY

APPROVED

41 200

WELDING STUD, 3/8-16 THREAD SIZE, 3" LONG, FOR

USE WITH ITEMS 37-40, ASTM A-108

ZINC PLATED

CARBON STEEL

COMMERCIAL

42 1

ANTIOXIDANT JOINT COMPOUND, COMPATIBLE W/ALL

CABLE INSULATION TYPES & UL LISTED FOR ALL

VOLTAGES, SYNTHETIC BASE WITH ZINC PARTICLES

VARIOUS COMMERCIAL

LIST OF MATERIAL (CONTINUED ON SH 15)

SCALE : AS NOTED SHEET 15

89256D -

D

C

B

A

D

C

B

A

FLT III GTG1H/3H FAC PWR

LIST OF MATERIALS

EHQ10998

LIST OF MATERIAL (CONTINUED FROM SH 14)

43 1 ELECTRICAL TAPE, GREEN, ROLL VINYL COMMERCIAL USE FOR MARKING GROUND CONDUCTORS.

AS

REQD

CABLE TIE, BLACK, UV RESISTANT, 120LBS MINIMUM

TENSILE STRENGTH, 18" LONG, LOW PROFILE SELF

LOCKING HEAD, MEETS UL94V-2 REQMTS

NYLON COMMERCIAL

LF

BEAM, W4x13 CARBON STEEL ASTM A36 CUT TO SUIT

AS

REQD

THREADED ROD, 1/4"-20, 10' LENGTHS, 240LB LOAD

CAPACITY

ZINC PLATED

CARBON STEEL

COMMERCIAL

AS

REQD

BEAM CLAMP, FOR USE WITH 1-5/8" CHANNEL, 900LB

MIN CAPACITY WHEN USED IN PAIRS

ZINC PLATED

CARBON STEEL

COMMERCIAL SEE DET 84C FOR DESIGN TYPE

48 4

VAPOR TIGHT LIGHT, WALL MOUNT, COMPACT

FLUOURESCENT, 120V, 42 WATT, INCLUDES JX BOX,

MAX DIMENSIONS 15-1/2"H X 8-3/4"D

VARIOUS SEE DETAIL 83B FOR DESIGN TYPE

49 2 3/4" THK PLATE, 12" X 12" CARBON STEEL ASTM A36 UTILIZE FOR FOUNDATION BASE PLATE.

50 7 LF FLAT BAR 4"x 1/4" CARBON STEEL ASTM A36 UTILIZE FOR KICK PLATE, CUT TO SUIT

51 45 LF BEAM, W6x25 CARBON STEEL ASTM A36 CUT TO SUIT

52 4 MOUNTING PLATE, 6" X 6" X 3/16" CARBON STEEL ASTM A36

53 8

WEDGE EXPANSION ANCHOR FOR CONCRETE, HEX HD,

1/2-13UNC-2B,

7" LONG, W/ HEX NUT & WASHER, 4960 LB MIN

TENSILE STRENGTH & 12450 LB MIN SHEAR STRENGTH

WITH 3-1/2" EMBEDMENT IN 4000PSI CONCRETE

316 STAINLESS

STEEL

COMMERCIAL

54 17 STUFFING TUBE, SIZE 2, CABLE RANGE .275" - .472" NYLON MIL-S-19622 NSN 5975-00-296-4093

55 27 STUFFING TUBE, SIZE 4, CABLE RANGE .450" - .777" NYLON MIL-S-19622 NSN 5975-00-296-4095

56 16 STUFFING TUBE, SIZE 5, CABLE RANGE .737" - 1.113" NYLON MIL-S-19622 NSN 5975-00-296-4096

57 2 STUFFING TUBE, SIZE 8, CABLE RANGE 1.61" - 2.00" NYLON MIL-S-19622 NSN 5975-00-296-4099

58 17 PACKING ASSY, SIZE 2E, CABLE RANGE .422" - .472" VARIOUS MIL-S-19622 NSN 5330-00-202-2590

59 4 PACKING ASSY, SIZE 4B, CABLE RANGE .497" - .547" VARIOUS MIL-S-19622 NSN 5330-00-202-2592

60 23 PACKING ASSY, SIZE 4C, CABLE RANGE .534" - .584" VARIOUS MIL-S-19622 NSN 5330-00-202-2593

61 12 PACKING ASSY, SIZE 5D, CABLE RANGE .889" - .937" VARIOUS MIL-S-19622 NSN 5330-00-202-2603

62 2 PACKING ASSY, SIZE 5G, CABLE RANGE 1.033" - 1.073" VARIOUS MIL-S-19622 NSN 5330-00-202-2607

63 2 PACKING ASSY, SIZE 8A, CABLE RANGE 1.61" - 1.641" VARIOUS MIL-S-19622 NSN 5330-00-202-2620

64 13

RECEPTACLE, DUPLEX, 20A, 125VAC, SIDE WIRED, NYLON

FACE, COMMERCIAL GRADE, NEMA 5-20R, UL LISTED

VARIOUS COMMERCIAL

65 400

WELDING STUD, 3/8-16 THREAD SIZE, 1" LONG, FOR USE

WITH ITEMS 37-40, ASTM A-108

ZINC PLATED

CARBON STEEL

COMMERCIAL

66 5 LF 4" X 4" X 1/4" ANGLE STEEL ASTM A36

67 5 LF FLATBAR, 5-1/4" X 1/4" THICK STEEL ASTM A36 CUT TO SUIT

68 10 LF PIPE, 1-1/4" DIAMETER, SCHEDULE 40 GALVANIZED STEEL COMMERCIAL CUT TO SUIT

69 NOT USED

LF

CABLE, LSTSGU-23, 3C-#7 AWG, STRANDED COPPER

CONDUCTOR, 1000V, O.D. = .812"

VARIOUS MIL-C-24643 NSN 6145-01-201-9500

71 4 PACKING ASSY, SIZE 5A, CABLE RANGE .772" - .812" VARIOUS MIL-S-19622 NSN 5330-00-202-2600

EHQ10998-01
EHQ10998-02
EHQ10998-03
EHQ10998-04
EHQ10998-05
EHQ10998-06
EHQ10998-07
EHQ10998-08
EHQ10998-09
EHQ10998-10
EHQ10998-11
EHQ10998-12
EHQ10998-13
EHQ10998-14
EHQ10998-15