REFERENCES
No. TITLE DRAWING No.
THIS IS A CAD MAINTAINED DRAWING DEVELOPED
IN AUTOCAD R2013 SOFTWARE. CHANGES SHALL BE
INCORPORATED BY THE DESIGN AUTHORITY
UNDER 12" ±1/8"
12" TO 6'-0" ±1/4"
OVER 6'-0" ±1/2"
DISTRIBUTION STATEMENT D
DISTRIBUTION AUTHORIZED TO THE DEPARTMENT
OF DEFENSE AND U.S. DoD CONTRACTORS ONLY;
CRITICAL TECHNOLOGY, 2/23/2011. OTHER U.S.
REQUESTS SHALL BE REFERRED TO COMMANDER,
NAVAL SEA SYSTEMS COMMAND.
PLAN VIEW 5A
FLT III GTG1H/3H FACILITY
POWER ARRANGEMENT & DETAILS
BUILDING KEY PLAN
SCALE: NONE
REVISION STATUS
REV SH DESCRIPTION
- 1 TITLE SHEET, BUILDING KEY PLAN, REFERENCES, NOTES
- 2 AREA PLAN & ISOMETRIC VIEWS
- 3 EQUIPMENT POWER CIRCUIT ARRANGEMENT
- 4 EQUIPMENT POWER CIRCUIT ARRANGEMENT
- 5 EQUIPMENT POWER CIRCUIT ARRANGEMENT
- 6 EQUIPMENT POWER CIRCUIT ARRANGEMENT
- 7 LIGHTING AND RECEPTACLE CIRCUIT ARRANGMENT
- 8 LIGHTING AND RECEPTACLE CIRCUIT ARRANGMENT
- 9 FOUNDATION AND WELDING DETAILS
- 10 EQUIPMENT FOUNDATION DETAILS
- 11 MISCELLANEOUS DETAILS
- 12 SINGLE LINE DIAGRAM
- 13 ELECTRICAL CONNECTION TABLES
- 14 LIST OF MATERIALS
- 15 LIST OF MATERIALS
NAVAL SURFACE WARFARE CENTER, PHILADELPHIA DIVISION
PHILADELPHIA, PA 19112-5083
DDG 51 LAND BASED ENGINEERING SITE (LBES), BUILDING 77H
FLT III GTG1H/3H FACILITY
POWER ARR & DETAILS
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 1 OF 15
89256D EHQ10998 -
CONTRACT No.
N00178-04-D-4089
OFFICAL SIGNATURE DATE
PREPARED B. Everling 1-13-17
CHECKED D. Purves 2-3-17
QA R. Chranowski
PROJ MGR
APPROVED NSWCPD
TECH REVIEW
PROG MGR
DIMENSIONAL TOLERANCES
UNLESS OTHERWISE SPECIFIED
DIMENSIONS IN FEET & INCHES
DECIMAL DIMENSIONS IN INCHES
TOLERANCE ON ANGLES ±.50°
1 PL ±.2, 2 PL ±.06, 3 PL ±.005
INTERPRET DIMENSIONS AND TOLERANCES
PER ASME Y14.5 - 1994
REVISION HISTORY
DESCRIPTIONREVZONE DATE APPROVED
D
C
B
A
D
C
B
A
12345678
12345678 A C A D F
IL
E N
A M E A C A D E
H P 1/ A C A D N
S W C P D D D G M O D
IF
IC
A T
IO
N S E H Q .D W G
NORTH
SEE SHEET 2 PLAN VIEW 14A
NOTES:
1. DEVIATIONS FROM THIS DRAWING ARE NOT PERMITTED WITHOUT APPROVAL
FROM THE NSWCPD CONSTRUCTION MANAGER (CODE 212).
2. FOLLOW THE LATEST VERSION NEC FOR ANY ELECTRICAL INSTALLATION
DETAIL NOT COVERED WITHIN THIS DRAWING.
3. ELEVATIONS GIVEN ON THIS DRAWING ARE REFERENCED FROM THE FINISHED
FLOOR OF BUILDING 77H (EL 0'-0") AND ARE TO BE VERIFIED AT THE TIME OF
INSTALLATION.
4. PHANTOM LINES INDICATE EXISTING EQUIPMENT NOT SHOWN.
5. DIMENSIONS SHALL BE FIELD VERIFIED PRIOR TO BEGINNING ANY WORK. MINOR
DEVIATIONS MAY BE PERMITTED WITH THE APPROVAL OF THE NSWCCD-SSES
CONSTRUCTION MANAGER (CODE 212).
6. VERIFY ALL CIRCUITS ARE TAGGED OUT PRIOR TO CONNECTION TO POWER
SOURCES.
7. ALL POWER CIRCUITS REQUIRE AN EQUIPMENT GROUND CONDUCTOR TO BE
ROUTED WITH THE POWER CABLE. IN MOST CASES AN EXTRA CONDUCTOR IS
CONTAINED WITHIN EACH POWER CABLE THAT SHALL BE CONNECTED AS AN
EQUIPMENT GROUND CONDUCTOR.
8. MISCELLANEOUS HARDWARE NOT INCLUDED IN THE MATERIAL LIST MUST BE
PROVIDED BY THE INSTALLER.
9. ALL CABLE HANGERS ARE SPACED AT 18" INTERVALS UNLESS OTHERWISE
NOTED ON THIS DRAWING.
10. DO NOT EXCEED CABLE MANUFACTURERS LIMIT FOR CABLE PULLING TENSION,
SIDE WALL PRESSURE AND BEND RADIUS DURING CABLE INSTALLATION.
11. ALL CABLING INSTALLED SHALL HAVE PERMANENT CABLE IDENTIFICATION
TAGS INSTALLED AT EACH END OF CABLE ADJACENT TO EQUIPMENT
ENCLOSURES.
12. ALL CABLES ARE TO BE ROUTED BELOW EXISTING SITE STEEL OR ALONG
EXISTING EQUIPMENT FOUNDATIONS USING MILITARY TEE TYPE HANGERS AND
WELDING STUDS (ITEMS 65 & 37) AS SHOWN IN DETAIL 65B, UNLESS
OTHERWISE NOTED ON THIS DRAWING. FOR SINGLE AND DOUBLE CABLE RUNS,
USE MILITARY CRIMP-LOK TYPE HANGERS AND WELDING STUDS (ITEMS 38, 39,
40 & 41) AS SHOWN IN DETAIL 67B.
13. CABLES IN HORIZONTAL AND VERTICAL CABLEWAYS SHALL BE SECURED TO
HANGERS USING BLACK NYLON, UV RESISTANT, 120 POUND TENSILE STRENGTH
TIE WRAPS (ITEM 44) OR EQUAL.
14. AFTER WIRING 3 PHASE MOTOR LOADS, BUMP TEST EACH MOTOR TO VERIFY
PROPER ROTATION.
15. REMOVE PAINT AND DIRT FROM ANY STEEL GROUNDING CONNECTIONS AND
APPLY ANTIOXIDANT JOINT COMPOUND (PENATROX A-13) OR EQUAL PRIOR TO
BOLTING TIN PLATED COMPRESSION LUGS FOR GROUND CONNECTIONS.
16. PERFORM INSULATION RESISTANCE TESTING FOR ALL NEW POWER CIRCUITS IN
ACCORDANCE WITH INSTRUCTION PROVIDED BY NSWCPD PROGRAM OFFICE.
PERFORM INSULATION RESISTANCE TESTING ON CIRCUITS AFTER NEW WIRING
IS PULLED INTO EQUIPMENT ENCLOSURES BUT NOT CONNECTED TO POWER
SOURCE. SAFEGUARD ALL PERSONNEL DURING INSULATION RESISTANCE
TESTING.
17. SUPPORT ALL CONDUIT AS SPECIFIED IN NEC.
M. Lamberto
NOTES (CONTINUED):
18. INSTALLER TO REMOVE RED PORTIONS OF EXISTING HANDRAIL DURING
EQUIPMENT FOUNDATION INSTALLATION SHOWN IN PARTIAL ELEVATION 78A
AND WELD REMAINING PORTION OF HANDRAILS TO EQUIPMENT FOUNDATIONS
TO SAFEGUARD PERSONNEL ON 3'-8" PLATFORM.
19. ANY CABLES PASSING THRU GRATING UNDER NEW POWER PANELS SHALL
HAVE A CUT OUT AT EDGE OF GRATING AND UNDER PANELS TO PROVIDE A
CLEAN AREA FOR CABLE PASSAGE OF 10"W X 2"D. 1/4" THICK X 51
4" HIGH
STEEL FLATBAR KICK PLATE SHALL BE TACK WELDED TO THE (3) INTERIOR
EDGES OF THE GRATING CUT OUT. THE KICK PLATE SHALL HAVE AN
INSTALLED HEIGHT OF 4" ABOVE THE GRATING (51
4" FLATBAR - 1
4" GRATING =
4" INSTALLED HEIGHT). GRATING SHALL BE FULLY REMOVEABLE WITHOUT
DISCONNECTING CABLES UPON COMPLETION OF INSTALLATION.
20. ANY RECEPTACLE CABLES PASSING THRU GRATING REQUIRE A 1-1/4"Ø X 4"
LONG PIPE SLEEVE PENETRATION THRU GRATING. PIPE SLEEVE SHALL BE
WELDED TO ADJACENT STRUCTURE TO ALLOW FUTURE GRATING REMOVAL
WITHOUT DISCONNECTION OF RECEPTACLE WIRING.
21. ALL DESIGN MATERIAL, FABRICATION AND ERECTION SHALL CONFORM TO
ANSI/AISC 360-10 "SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS" (ASD).
22. DESIGN, DETAILING AND FABRICATION OF ALL WELDED AND BOLTED
CONNECTIONS SHALL CONFORM TO THE AISC STEEL CONSTRUCTION MANUAL,
LATEST EDITION.
23. FABRICATION, WELDING AND INSPECTION SPECIFIED ON THIS DRAWING SHALL
BE IN ACCORDANCE WITH AWS STRUCTURAL WELDING CODE D1.1. NSWCPD
PROGRAM OFFICE RESERVES THE RIGHT TO INSPECT SHOP FABRICATION PRIOR
TO SHIPMENT.
24. CONTRACTOR SHALL BE RESPONSIBLE FOR VISUAL INSPECTION OF ALL WELDS
BY AN AWS CERTIFIED INSPECTOR.
25. ALL STEEL SHALL BE CLEANED AND THEN PAINTED WITH AN ANTI-CORROSION
PRIMER UPON COMPLETION OF ALL WELDING AND WELD INSPECTION. FIELD
WELD ON STRUCTURAL MEMBERS SHALL BE CLEANED, WASHED WITH WATER
AND COATED WITH AN ANTI-CORROSION PRIMER. FINISH ALL STEEL WITH TWO
COATS OF LIGHT GRAY (ANSI 61) PAINT.
26. THE WORK ASSOCIATED WITH THIS DRAWING CAN NOT BE FULLY
IMPLEMENTED UNTIL AFTER GTG INSTALLATION AND INSTALLATION OF GTG
PLATFORMS.
27. LED LIGHTING FIXTURES SHALL BE MOUNTED FROM CHAIN KIT (ITEM 14) IN LIEU
OF BEING SURFACE MOUNTED TO ENSURE PROPER COOLING.
2-6-17
DDG 51 LBES, BLDG 77H
FLIGHT III EQPT PLATFORM ARR
EHQ10546
DDG 51 LBES, BLDG 77H
FLIGHT III GTG 23'-4" LEVEL PLATFORM ARR AND DETAILS
EHQ10946
DDG 51 LBES, BLDG 77H
FLIGHT III GTG1H AND GTG3H FDN INSTALLATION DETAILS
EHQ10936
2-13-17
NOTES (CONTINUED):
28. THE GTG1H AND GTG3H MOTOR CONTROLLERS SHOWN IN SINGLE LINE DIAGRAM
SHALL BE WIRED AS FOLLOWS: INPUT POWER SHALL CONNECT TO M-3, M-9,
M-5. OUTPUT POWER TO MOTOR SHALL CONNECT TO TB3-1, TB3-2, TB3-3.
SEE NOTE 14 FOR ROTATION CHECK.
29. VERIFY NEW STEEL LOCATIONS/DIMENSIONS SHOWN IN DETAILS 69D AND 78A
AGAINST EQUIPMENT PURCHASED PRIOR TO INSTALLATION.
30. ALL ITEMS REFERRED TO IN THE NOTES ABOVE CAN BE FOUND IN THE LIST OF
MATERIALS IN THIS DRAWING.
T. Checchio
A. Cairns
5-1-17
5-2-17
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 2
89256D
D
C
B
A
D
C
B
A
910111213141516
910111213141516
PLAN VIEW 14A
FLT III GTG1H/3H FACILITY
POWER ARRANGEMENT & DETAILS - AREA PLAN
SCALE: NONE
NORTH
ISOMETRIC VIEW 11B
FLT III GTG1H/3H FACILITY
POWER ARRANGEMENT & DETAILS
LOOKING NORTHWEST
SCALE: NONE
SEE PLAN VIEW 20A, SHEET 3,
PLAN VIEW 28A, SHEET 4,
PLAN VIEW 52A, SHEET 7,
AND PLAN VIEW 60A, SHEET 8
FLT III GTG1H/3H PWR ARR
AREA PLAN & ISOMETRIC VIEWS
EHQ10998 -
16 17 18 19 20 211514 22 23
SEE PLAN VIEW 36A,
SHEET 5
SEE PLAN VIEW 44A,
SHEET 6
FLT III GTG1H/3H FAC PWR
EQUIPMENT POWER CIRCUIT ARR
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 3
89256D EHQ10998 -
D
C
B
A
D
C
B
A
PLAN VIEW 20A
EQUIPMENT POWER ARRANGEMENT
FLT III PLATFORM - 3'-8"/6'-6" LEVELS
SCALE: 3/8" = 1'-0"
NORTH
181615 17
D
1718192021222324
1718192021222324
GRAPHIC SCALE 3/8"=1'-0"
0 6" 2' 3' 4' 5' 10'1'
A
A
CABLE LIST F
CABLE LIST E
CABLE LIST C
CABLE LIST D
CABLE LIST G
CABLE
LIST B
CABLE
LIST A
GTG1H CLG FAN CONTROLLER
GTG3H CLG FAN CONTROLLER
PP 5-188-3
DISC SW
5-188-1
XFMR
5-188-1
PP
5-188-1
GTG1HGTG3H
JB3
JB3
CABLE LIST A
(5-188-1)-4P-B
(5-188-3)-1P-B
(5-188-3)-1P-D
(5-188-3)-1P-F
(5-188-3)-1P-A
(5-188-3)-1P-C
CABLE LIST B
(5-188-3)-1P-B
(5-188-3)-1P-D
(5-188-3)-1P-F
(5-188-3)-1P-A
(5-188-3)-1P-C
CABLE LIST C
(5-188-1)-4P-D(1)
(5-188-1)-4P-H(1)
CABLE LIST D
(5-188-3)-1P-G
(5-188-3)-1P-Q
CABLE LIST E
(5-188-1)-4P-A
(5-188-1)-4P-E
(5-188-1)-4P-F
CABLE LIST F
(5-188-3)-1P-K
(5-188-3)-1P-M
(5-188-3)-1P-P
(5-188-3)-1P-L
(5-188-3)-1P-N
CABLE LIST G
(5-188-1)-4P-B
CABLE LIST H
(5-188-1)-4P-F
(5-188-3)-1P-K
(5-188-3)-1P-M
(5-188-3)-1P-P
(5-188-3)-1P-L
(5-188-3)-1P-N
CABLE LIST I
(5-188-1)-4P-D(2)
(5-188-1)-4P-H(2)
CABLE LIST J
(5-188-1)-4P-A
GTG1HNBPS-28DC-JB5
CABLE LIST K
(5-188-1)-4P-E
GTG3HNBPS-28DC-JB5
CABLE LIST D AND I TO
23'-4" LVL (PLAN VIEW 28A
& 60A) IN NEW VERTICAL
TEE HANGER CABLEWAY
CABLE LIST JCABLE LIST K
GTG1H NBPSGTG3H NBPS
NOTE:
ALL CABLES SHOWN ON THIS PAGE SHALL BE
INSTALLED IN NEW TEE-HANGER CABLEWAY BELOW
3'-8"/6'-6" LVL PLATFORM UNLESS OTHERWISE
INDICATED
1SA-4P-(5-188-1) TO 23'-4" LVL (PLAN VIEW 36A)
IN NEW VERTICAL TEE HANGER CABLEWAY
CABLE
LIST H
JB5JB5
GTG3HNBPS-28DC-JB5
GTG1HNBPS-28DC-JB5
(5-188-1)-4P-C(1)
(5-188-1)-1P-C(1)
(5-188-1)-1P-C(2)
EQUIPMENT POWER CIRCUIT ARR
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 4
89256D EHQ10998 -
D
C
B
A
D
C
B
A
NORTH
181615 17
D
GRAPHIC SCALE 3/8"=1'-0"
0 6" 2' 3' 4' 5' 10'1'
PLAN VIEW 28A
EQUIPMENT POWER ARRANGEMENT
FLT III PLATFORM - 23'-4" LEVEL
SCALE: 3/8" = 1'-0"
2526272829303132
2526272829303132
CABLE LIST I TO 23'-4" LVL
(PLAN VIEW 20A)
GTG1HGTG3H
CABLE LIST I
(5-188-1)-4P-D(2)
(5-188-1)-4P-H(2)
EQUIPMENT REMOVAL RAILS
GTG3H COOLING FAN GTG1H COOLING FAN
1X TROLLEY TRACK
2X TROLLEY TRACK
2X TROLLEY TRACK
6X TROLLEY TRACK
NOTES:
1. ALL CABLES SHOWN ON THIS PAGE SHALL BE INSTALLED IN
NEW TEE-HANGER CABLEWAY BELOW 23'-4" LVL PLATFORM
UNLESS OTHERWISE INDICATED.
2. CABLES SHALL BE INSTALLED ABOVE TROLLEY TRACKS TO
PRECLUDE FUTURE INTERFERENCE DURING GTG MAINTENANCE
OPERATIONS.
SCALE : AS NOTED SHEET 5
89256D -
D
C
B
A
D
C
B
A
FLT III GTG1H/3H FAC PWR
EQUIPMENT POWER CIRCUIT ARR
EHQ10998
GRAPHIC SCALE 3/8"=1'-0"
0 6" 2' 3' 4' 5' 10'1'
3334353637383940
3334353637383940
D
19 20
CONTROL HOUSE
PLAN VIEW 36A
EQUIPMENT POWER ARRANGEMENT
DDG 51 23'-4" LEVEL
SCALE: 3/8" = 1'-0"
NORTH
EPSW 23'-4"
PLATFORM
DDG 51 23'-4"
PLATFORM
FLT III DDG 51
23'-4" PLATFORM
1SA-4P-(5-188-1) TO 3'-8" LVL (PLAN VIEW 20A)
IN NEW VERTICAL TEE HANGER CABLEWAY
1SA-4P-(5-188-1) TO 32'-6" LVL (PLAN VIEW 44A)
IN EXISTING VERTICAL CABLEWAY
NOTE:
ALL CABLES ON THIS PAGE SHALL BE INSTALLED IN
NEW TEE-HANGER CABLEWAY AS REQUIRED BELOW
23'-4" LEVEL UNLESS OTHERWISE INDICATED
22 23
SCALE : AS NOTED SHEET 6
89256D -
D
C
B
A
D
C
B
A
FLT III GTG1H/3H FAC PWR
EQUIPMENT POWER CIRCUIT ARR
EHQ10998
GRAPHIC SCALE 3/8"=1'-0"
0 6" 2' 3' 4' 5' 10'1'
D
20 21
CONTROL HOUSE
1SA-4P-(5-188-1) TO 23'-4" LVL (PLAN VIEW 36A)
IN EXISTING VERTICAL CABLEWAY
NOTE:
ALL CABLES ON THIS PAGE SHALL BE INSTALLED IN
EXISTING CABLEWAY ALONG THE SIDE OF THE 32'-6"
LEVEL UNLESS OTHERWISE INDICATED
PLAN VIEW 44A
EQUIPMENT POWER ARRANGEMENT
DDG 51 32'-6" LEVEL
SCALE: 3/8" = 1'-0"
NORTH
4142434445464748
4142434445464748
1SA SWBD3SA SWBD
NEW TEE HANGER
CABLEWAY ALONG SIDE
OF 32'-6" LVL I BEAM
LIGHTING AND RECPT CKT ARR
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 7
89256D EHQ10998 -
D
C
B
A
D
C
B
A
PLAN VIEW 52A
LIGHTING AND RECEPTACLE ARRANGEMENT
FLT III PLATFORM - 3'-8"/6'-6" LEVELS
SCALE: 3/8" = 1'-0"
NORTH
181615 17
D
GRAPHIC SCALE 3/8"=1'-0"
0 6" 2' 3' 4' 5' 10'1'
E1
E2
E3
E4
E5
R3
R6
R4
R5
R2
R1
R1R2
R3
R6
LIGHTING AND RECEPTACLE NOTES SPECIFIC TO SHEET 7:
1. DUPLEX RECEPTACLES (ITEMS 30, 31, 64) SHOWN NEXT TO
COLUMNS SHALL BE MOUNTED TO PLATFORM COLUMNS AS
SHOWN IN DETAIL 67A, 18" ABOVE PAD.
2. DUPLEX RECEPTACLES (ITEMS 30, 31, 64) SHOWN NEXT TO
EDGE OF PLATFORM SHALL BE MOUNTED TO PLATFORM
KICKPLATE AS SHOWN IN DETAIL 65A.
3. EMERGENCY LIGHTS E-1 THRU E-5 SHALL BE MOUNTED TO
PLATFORM COLUMNS WITH TOP OF FIXTURE BETWEEN
7-1/2' TO 10' ABOVE PLATFORM LEVEL TO SUIT SITE
CONDITIONS, SEE DETAIL 82B. ADJUST LIGHT HEADS AS
REQUIRED TO SUPPORT EGRESS. INSTALL WIRING PER
EMERGENCY LIGHTING ONE-LINE RISER DIAGRAM (DETAIL
86A) AND PP 5-188-3 ONE LINE DETAILS.
- DENOTES RECEPTACLE CIRCUIT
(5-188-3)-1P-J
(5-188-3)-1P-H
POWER PANEL 5-188-3
TO 23'-4" LVL
TO 23'-4" LVL
TO 23'-4" LVL
4950515253545556
4950515253545556
LIGHTING AND RECEPT CKT ARR
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 8
89256D EHQ10998 -
D
C
B
A
D
C
B
A
NORTH
181615 17
D
GRAPHIC SCALE 3/8"=1'-0"
0 6" 2' 3' 4' 5' 10'1'
E6
E7
E8
E9
R5
R4
R7
(5-188-3)-1P-G
PLAN VIEW 60A
LIGHTING AND RECEPTACLE ARRANGEMENT
FLT III PLATFORM - 23'-4" LEVEL
SCALE: 3/8" = 1'-0"
LIGHTING AND RECEPTACLE NOTES SPECIFIC TO SHEET 8:
1. LIGHT FIXTURES (ITEM 29) AND ASSOCIATED JUNCTION BOXES
(ITEMS 30, 32) ARE TO BE SUPPORTED FROM 23'-4" LEVEL
STEEL PER TYPICAL DETAILS 87D, 84D & 84C OR EQUAL.
FIXTURE LOCATIONS MAY BE MODIFIED AS NEEDED TO SUIT
PLATFORM EQUIPMENT LOCATIONS.
2. DUPLEX RECEPTACLES (ITEMS 30, 31, 64) SHALL BE FIELD
MOUNTED IN LOCATION SHOWN PER DETAIL 82A ABOVE 23'-4"
LVL, MOUNT RECEPTACLES CLOSE TO GTG1H/GTG3H EXHAUST
STACK SUCH THAT THEY DO NOT PROVIDE A TRIP HAZARD.
3. EMERGENCY LIGHTS E-6 THRU E-9 SHALL BE MOUNTED TO NEW
8' TALL W4-13 COLUMNS WITH TOP OF FIXTURE BETWEEN 7' TO
8' ABOVE 23'-4" LVL TO SUIT SITE CONDITIONS, SEE DETAILS
84B AND 82B. ADJUST LIGHT HEADS AS REQUIRED TO SUPPORT
EGRESS. INSTALL WIRING PER EMERGENCY LIGHTING ONE-LINE
RISER DIAGRAM (DETAIL 86A) AND PP 5-188-3 ONE LINE DETAILS.
4. ADJACENT TO 23'-4" LVL EMERGENCY LIGHTS, INSTALL
CONTINUOUS ON FIXTURES VT1-VT4 (ITEM 48). THESE
SUPPLEMENT THE NORMAL HIGH BAY LIGHT FIXTURES THAT ARE
ON A DIFFERENT POWER SOURCE. THESE FIXTURES ARE REQUIRED
IN CASE HIGH BAY LIGHTING IS LOST BUT POWER REMAINS ON
AT THE GTG PLATFORM AND EMERGENCY LIGHTING DOES NOT
TURN ON.
5. CABLES SHALL BE INSTALLED ABOVE TROLLEY TRACKS TO
PRECLUDE FUTURE INTERFERENCE DURING GTG MAINTENANCE
OPERATIONS.
- DENOTES RECEPTACLE CIRCUIT
TO 6'-6" LVL
TO 6'-6" LVL
TO 6'-6" LVL
(5-188-3)-1P-G TO 3'-8" LVL (PLAN VIEW 20A)
EQUIPMENT REMOVAL RAILS
5758596061626364
5758596061626364
1X TROLLEY TRACK
2X TROLLEY TRACK
2X TROLLEY TRACK
6X TROLLEY TRACK
L
L
L
L
L
L
L
L
L
L5L6L11
L4L7L12
(5-188-3)-1P-Q TO 3'-8" LVL (PLAN VIEW 20A)
VT4
VT3
VT1
VT2
(5-188-3)-1P-Q
SCALE : AS NOTED SHEET 9
89256D -
D
C
B
A
D
C
B
A
EHQ10998
GRAPHIC SCALE 3/8"=1'-0"
0 6" 2' 3' 4' 5' 10'1'
FLT III GTG1H/3H FAC PWR
FOUNDATION & WELDING DETAILS
DETAIL 68C
BEAM CONNECTION DETAIL
SCALE: NONE
EXST BEAMW4x13 (ITEM 45)
T.O. PLATF
2X 3/4" SNIPE
COPE TO FIT
DETAIL 65D
23'-4" BEAM TO FOUNDATION
COLUMN CONNECTION DETAIL
SCALE: NONE
W6x25 (ITEM 51)
EXST FLT III
23'-4" BEAM
W6x25 (ITEM 51)
DETAIL 67C
FOUNDATION BEAM CONNECTION DETAIL
SCALE: NONE
W4x13 (ITEM 45)
W4x13 (ITEM 45)
3/16 3/16
2X 1/2" SNIPE
COPE TO FIT
DETAIL 65C
CHANNEL TO FOUNDATION
CONNECTION DETAIL
SCALE: NONE
1/8
DETAIL 68D
FLTIII BEAMS TO FOUNDATION
COLUMN CONNECTION DETAIL
SCALE: NONE
W4x13 (ITEM 45)
EXST FLT III
3'-8" BEAM
W4x13 (ITEM 45)
W4x13 (ITEM 45)
1-5/8" x 1-5/8"
CHANNEL (ITEM 36)
CRIMP TYPE HANGER
(ITEMS 38, 39, 40)
DETAIL 67B
CRIMP TYPE HANGER CONNECTION
SINGLE OR DOUBLE CABLES
SCALE: NONE
EXST SITE STEEL
TUBULAR TEE HANGER
(ITEM 37)
DETAIL 65B
TUBULAR TEE HANGER CONNECTION
MULTIPLE CABLES
SCALE: NONE
THREADED ARC WELDING
STUD (ITEM 65)
EXST SITE STEEL
PARTIAL PLAN VIEW 69D
TRANSFORMER 5-188-1 FOUNDATION
FLT III 3'-8" PLATFORM
SCALE: 3/8" = 1'-0"
DETAIL 67A
DUPLEX RCPT TO COLUMN CONNECTION
SCALE: NONE
2X BEAM CLAMP
(ITEM 34)
EXST SITE STEEL
4" SQ J-BOX
(ITEM 30)
RCPT BOX COVER
(ITEM 31)
DUPLEX RCPT
(ITEM 64) DETAIL 65A
DUPLEX RCPT TO KICK PLATE
CONNECTION
SCALE: NONE
2X BEAM CLAMP
(ITEM 34)
EXST SITE STEEL
EXST KICK PLATE
3/16
3/16
3/16
1/8
3/8
3/16 3/16
THREADED ARC WELDING
STUD (ITEM 41)
3/8
4'-2"
5'-11
2X DET 68C W4x13 (ITEM 45)
A
A
GTG1H CLG FAN
CONTROLLER
GTG3H CLG FAN
CONTROLLER
PP 5-188-3
DISC SW
5-188-1
XFMR
5-188-1
PP
5-188-1
1'-5
8"
1'-8
3"
PARTIAL PLAN VIEW 71C
EQUIPMENT FOUNDATIONS DETAIL
FLT III 3'-8"/6'-6" PLATFORM
SCALE: 3/8" = 1'-0"
DETAIL 70A
FOUNDATION BASE PLATE AND CONCRETE ANCHOR
SCALE: NONE
3/4" PLATE
(ITEM 49)
W6x25
(ITEM 51)
3/16
1/2" ANCHOR
BOLT, WASHER,
NUT (ITEM 53)
NOM
IMBEDMENT
ITEM 51
3/4" PLATE
(ITEM 49)
3/4" NOM GROUT
DETAIL 68A
FOUNDATION KICKPLATE
CONNECTION DETAIL
SCALE: NONE
W4x13 (ITEM 45)
EXST FLT III
3'-8" BEAM
1 1/2"
1X 1/4"X4"
FLATBAR
KICKPLATE
(ITEM 50)
R1 R2 R5 R3 R4
R6 R7
R1 R2 R3 R6 R4 R5
PP 5-188-3
2P
20A
LSTSGU-9 (TYP)
11X CABLE
CONNECTOR (ITEM 33)
LSTSGU-9 (TYP)
13X CABLE CONNECTOR
(ITEM 33)
2P
20A (5-188-3)-1P-H
LSTSGU-9
(5-188-3)-1P-J
LSTSGU-9
DETAIL 69B
CONVENIENCE RECEPTACLE CONNECTION DIAGRAM
SCALE: NONE
7X SQR BOX,
RECEPTACLE, COVER
PLATE (ITEMS 30, 31, 64)
6X SQR BOX,
RECEPTACLE, COVER
PLATE (ITEMS 30, 31, 64)
6566676869707172
6566676869707172
1/4"
3/16"
" 6"
" 1
1'
6"
1'
1/2" ANCHOR
BOLT, WASHER,
NUT (ITEM 53)
2X
3/16
2X
SCALE : AS NOTED SHEET 10
89256D -
D
C
B
A
D
C
B
A
FLT III GTG1H/3H FAC PWR
EQPT FOUNDATION DETAILS
EHQ10998
PARTIAL ELEVATION 78A
POWER PANEL & TRANSFORMER ARRANGEMENT
FLTIII 3'-8" PLATFORM
SCALE: 3/4" = 1'-0"
NORTH
PAD LVL 0'-0"
FLT III 3'-8" PLTF
PARTIAL ELEVATION 75A
COOLING FAN MOTOR CONTROLLER ARRANGEMENT
FLTIII 6'-6" PLATFORM
SCALE: 3/4" = 1'-0"
NORTH
PAD LVL 0'-0"
FLT III 6'-6" PLTF
AS REQ'D
AS REQ'D
7'-9"
8'
1'-0
2'-0
3'-10
4'-11
6'-6
8'
3X W4X13
(ITEM 45)
3X 1-5/8" x 1-5/8"
CHANNEL (ITEM 36)
2'-2"
16X DET 65C
5X 1-5/8" x 1-5/8"
CHANNEL (ITEM 36)
3X W4X13
(ITEM 45)
4'-2"
4X DET 67C
4X DET 68D
FLT III 23'-4" PLTF
PP 5-188-1
(ITEM 1)
DISC SW
5-188-1
(ITEM 3)
PP
5-188-3
(ITEM 2)
XFMR 5-188-1
(ITEM 5)
1'-7
3'-1
4'-8
6'-4
6'-5
7'-11
10X DET 65C
2X DET 65D
2X DET 70A
2X W6X25
(ITEM 51)
5X 1-5/8"x1-5/8"
CHANNEL (ITEM 36)
22'-1
3'-3
1X 1/4"X4"
FLATBAR
KICKPLATE
(ITEM 50)
1X 1/4"X4"
FLATBAR
KICKPLATE
(ITEM 50)
4X DET 68A
REMOVE INDICATED
HANDRAILS AND
WELD REMAINING
HANDRAILS TO
FND PER NOTE 18
GRAPHIC SCALE 3/4"=1'-0"
0 6" 2' 3' 4' 5'1'
7374757677787980
7374757677787980
SEE DET 69D
GTGH1 CLG
FAN MOTOR
CONTROLLER
(ITEM 4)
GTGH3 CLG
FAN MOTOR
CONTROLLER
(ITEM 4)
SCALE : AS NOTED SHEET 11
89256D -
D
C
B
A
D
C
B
A
EHQ10998
FLT III GTG1H/3H FAC PWR
MISCELLANEOUS DETAILS
23'-4" LVL
EXST SITE STEEL
24"
(MAX)
LED LIGHT
FIXTURE (ITEM 29)
DETAIL 84D
LIGHT FIXTURE MOUNTING DETAIL
SCALE: NONE
2X BEAM CLAMP
(ITEM 47)
2X 1-5/8" x 1-5/8" CHANNEL
(ITEM 36) (LENGTH AS REQ'D)
23'-4" LVL
EXST PLATFORM STEEL
LED LTG FIXTURE
(ITEM 29)
2X BEAM CLAMP
(ITEM 47)
2X 1-5/8" x 1-5/8" CHANNEL
(ITEM 36) (LENGTH AS REQ'D)
23'-4" LVL
EXST SITE STEEL
LED LIGHT
FIXTURE (ITEM 29)
DETAIL 84C
LIGHT FIXTURE MOUNTING DETAIL
SCALE: NONE
4X BEAM CLAMP
(ITEM 47)
1-5/8" x 1-5/8" CHANNEL
(ITEM 36) (LENGTH AS REQ'D)
23'-4" LVL
EXST PLATFORM STEEL
4X BEAM CLAMP
(ITEM 47)
1-5/8" x 1-5/8" CHANNEL
(ITEM 36) (LENGTH AS REQ'D)
LED LTG FIXTURE
(ITEM 29)
E1 PWR PNL
5-188-3
BRKR "T"
E2
3'-8"/6'-6" LEVELS
23'-4" LEVEL
E6 E7
CABLE CONNECTOR
(ITEM 33) (TYP)
CABLE CONNECTOR
(ITEM 33) (TYP)
(1) LSTSGU-4
(TYP)
(11X) 4" SQ BOX & COVER
(ITEMS 30 & 32)
(9X) EMERGENCY LIGHT
FIXTURE (ITEM 16)
NOTE:
1. SEE SHEETS 7 AND 8 FOR EMERGENCY LIGHT
FIXTURE LOCATIONS ON PLATFORM.
DETAIL 86A
EMERGENCY LIGHTING
ONE-LINE RISER DIAGRAM
SCALE: NONE
NEW OR EXST
PLATFORM
COLUMN
2X 1-5/8" x 1-5/8" CHANNEL
(ITEM 36) (LENGTH AS REQ'D)
EMERGENCY LIGHT
FIXTURE (ITEM 16)
DETAIL 83B
EMERGENCY LIGHT FIXTURE
MOUNTING DETAIL
SCALE: NONE
DETAIL 84B
FLTIII BEAMS TO FOUNDATION
COLUMN CONNECTION DETAIL
SCALE: NONE
W4x13 (ITEM 45)
EXST FLT III
23'-4" BEAM
W4x13 (ITEM 45)
3/16
3/16
8'
E4
E9
E3
E8
E5
8182838485868788
8182838485868788
PP 5-188-3
2P
20A (5-188-3)-1P-G
LSTSGU-9
9X SQR BOX, COVER PLATE
(ITEMS 30 AND 32)
L1
L4 L5
L8 L10
L12
L13 L15
DETAIL 86B
LIGHTING CONNECTION DIAGRAM
SCALE: NONE
LSTSGU-9 (TYP)
31X CABLE
CONNECTOR (ITEM 33)
15X STUFFING
TUBE/PACKING
ASSEMBLY
(ITEMS 60
AND 55)L7
DETAIL 82A
DUPLEX RCPT TO 4X4 ANGLE
CONNECTION
SCALE: NONE
2X BEAM CLAMP
(ITEM 34)
EXST SITE STEEL
4" X 4" X 1/4" ANGLE
(18" HIGH) (ITEM 66)
4" SQ J-BOX
(ITEM 30)
DUPLEX RCPT
(ITEM 64)
RCPT BOX COVER
(ITEM 31)
1/8
(5-188-3)-1P-T
.5"
CHAIN HANGING KIT (ITEM 14) (SEE NOTE 27)
(UTILIZE S HOOK TO ADJUST LAMP HEIGHT AND SECURE AROUND CHANNEL)
SECURE CHAIN TO CHANNEL WITH SCREW/BOLT TO
PREVENT FALLING OFF END OF CHANNEL
CHAIN HANGING KIT (ITEM 14)
(SEE NOTE 27)
CHAIN HANGING KIT (ITEM 14)
(SEE NOTE 27) (UTILIZE S HOOK TO
ADJUST LAMP HEIGHT AND SECURE
AROUND CHANNEL)
CHAIN HANGING KIT (ITEM 14)
3'
3'
L3
2P
20A (5-188-3)-1P-Q
LSTSGU-9
L2
L6 L9
L11 L14
VT3
CABLE CONNECTOR
(ITEM 33) (TYP)4X VAPORTIGHT
LIGHT (ITEM 48)
VT4 VT1 VT2
1/8 2X
2X 1-5/8" x 1-5/8" CHANNEL
(ITEM 36) (LENGTH AS REQ'D)
NEW OR EXST
PLATFORM
COLUMN
6" X 6" X 3/16" MOUNTING PLATE
(ITEM 52)
VAPORTIGHT LIGHT FIXTURE (ITEM 48)
6" X 6" X 3/16" MOUNTING PLATE
(ITEM 52)
VAPORTIGHT LIGHT FIXTURE (ITEM 48)
1/8 2X
SCALE : AS NOTED SHEET 12
89256D -
D
C
B
A
D
C
B
A
FROM EXISTING 1SA SWITCHBOARD
EXISTING 400AF/400AT CIRCUIT BREAKER*
PP 5-188-1
480VAC, 3∅, 3W, 400A
FLT III PLTF, 3'-8" LVL
1SA-4P-(5-188-1)
(2) LSFSGU-150
400AΔ
MAIN
3P
60A
3P
15A
3P
70A
3P
80A
3P SPACE
XFMR 5-188-1 (ITEM 5)
480V-120V
45KVA
2P
15A (5-188-3)-1P-B
LSTSGU-4 2P
20A (5-188-3)-1P-A
LSTSGU-9
2P
15A (5-188-3)-1P-C
LSTSGU-42P
15A
2P
15A
2P
20A
2P
15A
2P
15A
2P
15A
(5-188-1)-1P-C(1)
3-1C-250MCM, THHN/THWN
1-1C-#2 AWG, THHN/THWN GND
IN 2-1/2" LFMC
(CONNECT GND CONDUCTOR TO
GND BUSHINGS + SOURCE/LOAD
GND BUS OR TERMINAL)
2P
15A (5-188-3)-1P-E
LSTSGU-4
2P
20A
2P
20A
2P
20A
2P
15A
2P
20A
GTG1H JB3 RIMMS BAT CHGR GTG1H JB3 GEN HTRS
(5-188-3)-1P-D
LSTSGU-4
GTG1H JB3 SKID RECEPTACLES
(5-188-3)-1P-F
LSTSGU-4
GTG1H JB3 MODULE LTG
2P
15A
GTG1H JB3 FADC PWR AND UV DETECTION
GTG1H HFP SYSTEM (FUTURE)
2P
15A
2P
15A
.6 KVA
1 KVA
1.4 KVA
1.8 KVA
1.4 KVA
1.2 KVA
FLT III GTG1H/3H FAC PWR
SINGLE LINE DIAGRAM
EHQ10998
2X STUFFING
TUBE/PACKING
ASSEMBLY
FOR LSFSGU-50
(ITEMS 56, 62)
2X LIQUIDTIGHT STRAIGHT
CONNECTOR/GND BUSHING
FOR 2-1/2" LFMC (ITEMS 26, 27)
3P
60A
3P
15A
3P
70A
(5-188-1)-4P-A
LSFSGU-4
GTG1H NBPS3.9 KVA
(5-188-1)-4P-E
LSFSGU-4
GTG3H NBPS3.9 KVA
(5-188-1)-4P-B
LSFSGU-23
GTG1H JB3 AUX LUBO
OIL PUMP
23 KVA
(5-188-1)-4P-D(1)
LSFSGU-23
LVR MC
(5-188-1)-4P-F
LSFSGU-23
GTG3H JB3 AUX LUBO
OIL PUMP
23 KVA
(5-188-1)-4P-H(1)
LSFSGU-23
LVR MC
(5-188-3)-1P-G
LSTSGU-9
(5-188-3)-1P-H
LSTSGU-9
GTG1H/3H PLATFORM RECEPTACLES
(DETAIL 69B)
GTG1H/3H PLATFORM LIGHTING
(DETAIL 86B)
0.6 KVA
(5-188-3)-1P-J
LSTSGU-9
(5-188-3)-1P-K
LSTSGU-4
GTG3H JB3 RIMMS BAT CHGR
GTG1H/3 PLATFORM RECEPTACLES
(DETAIL 69B)
.6 KVA
(5-188-3)-1P-L
LSTSGU-9
(5-188-3)-1P-M
LSTSGU-4
GTG3H JB3 SKID RECEPTACLES GTG3H JB3 GEN HTRS1 KVA 1.8 KVA
(5-188-3)-1P-N
LSTSGU-4
(5-188-3)-1P-P
LSTSGU-4
GTG3H JB3 MODULE LIGHTING GTG3H JB3 FADC PWR AND UV DETECTION1.4 KVA 1.4 KVA
(5-188-3)-1P-R
LSTSGU-4
GTG3H HFP SYSTEM (FUTURE) 1.2 KVA
(5-188-1)-4P-C(1)
LSFSGU-50
(1.1 KVA)
(1.1 KVA)
250A
DISC SW 5-188-1
400 AMP
(ITEM 3)
2X LIQUIDTIGHT STRAIGHT CONNECTOR/GND BUSHING
FOR 2-1/2" LFMC (ITEMS 26, 27)
(5-188-1)-4P-D(2)
LSFSGU-23
GTG1H COOLING FAN 28 KVA
(5-188-1)-4P-H(2)
LSFSGU-23
GTG3H COOLING FAN 28 KVA
(5-188-3)-1P-T
LSTSGU-4
GTG1H/3H PLATFORM
EMERGENCY LIGHTING
(DETAIL 86A)
0.4 KVA
(5-188-1)-1P-C(2)
3-1C-250MCM, THHN/THWN
1-1C-#2 AWG, THHN/THWN GND
IN 2-1/2" LFMC
(CONNECT GND CONDUCTOR TO GND BUSHINGS + SOURCE/LOAD GND BUS OR TERMINAL)
SPARE
FUTURE GTG2H PWR AVAILABLE
ITEM 2
ITEM 1
8990919293949596
8990919293949596
FLT III
PLATFORM
STEEL
GROUND POWER
PANEL TO FLT III
PLATFORM STEEL
USING ITEM 24
FLT III PLATFORM STEEL
GROUND POWER
PANEL TO FLT III
PLATFORM STEEL
USING ITEM 23
* = SET LONG TIME (LT) PICKUP AT 1XP(400A) = 400A
SET LT DELAY TO 6 SECONDS AT 6XP
SET INSTANTANEOUS TRIP TO 6X400A = 2400A
PP 5-188-3
120VAC, 3∅, 3W, MLO (ALB-1)
FLT III PLTF, 3'-8" LVL
3P3P
SPACESPACE
GTG1H NBPS
TB1-3
TB1-8
GTG1H JB5
GTG1HNBPS-28DC-JB5
LSTSGU-23
GTG3H NBPS
TB1-3
TB1-8
GTG3H JB5
GTG3HNBPS-28DC-JB5
LSTSGU-23
DETAIL 90C
28VDC CONNECTION DIAGRAM
SCALE: NONE
2X STUFFING TUBE/PACKING ASSEMBLY
(ITEMS 56, 71)
2X STUFFING TUBE/PACKING ASSEMBLY
(ITEMS 56, 71)
GND
GND
(SEE NOTE 29)
(SEE NOTE 28)
(SEE NOTE 29)
(SEE NOTE 28)
GND DET
(5-188-3)-1P-Q
LSTSGU-9
0.3 KVA
GTG1H/3H PLATFORM LIGHTING
(DETAIL 86B)
Δ = SET ADJUSTABLE INSTANTANEOUS TRIP TO 2400A
SCALE : AS NOTED SHEET 13
89256D -
D
C
B
A
D
C
B
A
FLT III GTG1H/3H FAC PWR
ELECTRICAL CONNECTION TABLES
EHQ10998
TABLE 104D: POWER PANEL 5-188-1 CABLE PENETRATIONS
CIRCUIT NAME CONNECTED DEVICE
STUFFING TUBE
AT POWER
PANEL
PACKING
ASSEMBLY AT
POWER PANEL
STUFFING TUBE
AT CONNECTED
DEVICE
PACKING
ASSEMBLY AT
CONNECTED
DEVICE
(5-188-1)-4P-A GTG1H NBPS ITEM 55 ITEM 59 ITEM 55 ITEM 59
(5-188-1)-4P-B
GTG1H JB3 AUX LUBO
OIL PUMP
ITEM 56 ITEM 61 ITEM 56 ITEM 61
(5-188-1)-4P-D(1)
GTG1H COOLING FAN
CONTROLLER
ITEM 56 ITEM 61 ITEM 56 ITEM 61
(5-188-1)-4P-D(2) GTG1H COOLING FAN ITEM 56 ITEM 61 ITEM 56 ITEM 61
(5-188-1)-4P-E GTG3H NBPS ITEM 55 ITEM 59 ITEM 55 ITEM 59
(5-188-1)-4P-F
GTG3H JB3 AUX LUBO
OIL PUMP
ITEM 56 ITEM 61 ITEM 56 ITEM 61
(5-188-1)-4P-H(1)
GTG3H COOLING FAN
CONTROLLER
ITEM 56 ITEM 61 ITEM 56 ITEM 61
(5-188-1)-4P-H(2) GTG3H COOLING FAN ITEM 56 ITEM 61 ITEM 56 ITEM 61
TABLE 104C: POWER PANEL 5-188-3 CABLE PENETRATIONS
CIRCUIT NAME CONNECTED DEVICE
STUFFING TUBE
AT POWER
PANEL
PACKING
ASSEMBLY AT
POWER PANEL
STUFFING TUBE
AT CONNECTED
DEVICE
PACKING
ASSEMBLY AT
CONNECTED
DEVICE
(5-188-3)-1P-A GTG1H JB3 GEN HTRS ITEM 55 ITEM 60 ITEM 55 ITEM 60
(5-188-3)-1P-B
GTG1H JB3 RIMMS
BAT CHGR
ITEM 54 ITEM 58 ITEM 54 ITEM 58
(5-188-3)-1P-C
GTG1H JB3 FADC PWR
AND UV DETECTION
ITEM 54 ITEM 58 ITEM 54 ITEM 58
(5-188-3)-1P-D
GTG1H JB3 SKID
RECEPTACLES
ITEM 54 ITEM 58 ITEM 54 ITEM 58
(5-188-3)-1P-F
GTG1H JB3 MODULE
LTG
ITEM 54 ITEM 58 ITEM 54 ITEM 58
(5-188-3)-1P-G
GTG1H/3H PLATFORM
LIGHTING
ITEM 55 ITEM 60 SEE DETAIL 86B
(5-188-3)-1P-H
GTG1H/3H PLATFORM
RECPTACLES
ITEM 55 ITEM 60 SEE DETAIL 69B
(5-188-3)-1P-J
GTG1H/3 PLATFORM
RECEPTACLES
ITEM 55 ITEM 60 SEE DETAIL 69B
(5-188-3)-1P-K
GTG3H JB3 RIMMS
BAT CHGR
ITEM 54 ITEM 58 ITEM 54 ITEM 58
(5-188-3)-1P-L GTG3H JB3 GEN HTRS ITEM 55 ITEM 60 ITEM 55 ITEM 60
(5-188-3)-1P-M
GTG3H JB3 SKID
RECEPTACLES
ITEM 54 ITEM 58 ITEM 54 ITEM 58
(5-188-3)-1P-N
GTG3H JB3 FADC PWR
AND UV DETECTION
ITEM 54 ITEM 58 ITEM 54 ITEM 58
(5-188-3)-1P-P
GTG3H JB3 MODULE
LIGHTING
ITEM 54 ITEM 58 ITEM 54 ITEM 58
(5-188-3)-1P-T
GTG1H/3H PLATFORM
EMERGENCY LIGHTING
ITEM 54 ITEM 58 SEE DETAIL 86A
(5-188-3)-1P-Q
GTG1H/3H PLATFORM
LTG
ITEM 55 ITEM 60 SEE DETAIL 86B
TABLE 99D: 120VAC CABLE TERMINATIONS IN GTG1H/GTG3H
JB3
CIRCUIT NAME CONNECTED DEVICE
HOT 1 TERMINAL
BLOCK AT CONNECTED
DEVICE
HOT 2 TERMINAL
BLOCK AT CONNECTED
DEVICE
GROUND CONDUCTOR
TERMINAL BLOCK AT
CONNECTED DEVICE
(5-188-3)-1P-A GTG1H JB3 GEN HTRS TB2-6 TB2-7 GND BUS/FRAME
(5-188-3)-1P-B
GTG1H JB3 RIMMS
BAT CHGR
TB1-9 TB1-10 GND BUS/FRAME
(5-188-3)-1P-C
GTG1H JB3 FADC PWR
AND UV DETECTION
TB1-11 TB1-12 GND BUS/FRAME
(5-188-3)-1P-D
GTG1H JB3 SKID
RECEPTACLES
TB1-1 TB1-2 GND BUS/FRAME
(5-188-3)-1P-F
GTG1H JB3 MODULE
LTG
TB1-6 TB1-7 GND BUS/FRAME
(5-188-3)-1P-K
GTG3H JB3 RIMMS
BAT CHGR
TB1-9 TB1-10 GND BUS/FRAME
(5-188-3)-1P-L GTG3H JB3 GEN HTRS TB2-6 TB2-7 GND BUS/FRAME
(5-188-3)-1P-M
GTG3H JB3 SKID
RECEPTACLES
TB1-1 TB1-2 GND BUS/FRAME
(5-188-3)-1P-N
GTG3H JB3 FADC PWR
AND UV DETECTION
TB1-11 TB1-12 GND BUS/FRAME
(5-188-3)-1P-P
GTG3H JB3 MODULE
LIGHTING
TB1-6 TB1-7 GND BUS/FRAME
TABLE 99C: 480VAC CABLE TERMINATIONS IN GTG1H/GTG3H JB3
CIRCUIT NAME CONNECTED DEVICE
PHASE A TERMINAL
BLOCK AT CONNECTED
DEVICE
PHASE B TERMINAL
BLOCK AT CONNECTED
DEVICE
PHASE C TERMINAL
BLOCK AT CONNECTED
DEVICE
GROUND CONDUCTOR
TERMINAL BLOCK AT
CONNECTED DEVICE
(5-188-1)-4P-B
GTG1H JB3 AUX LUBO
OIL PUMP
TB3-1 TB3-2 TB3-3 GND BUS/FRAME
(5-188-1)-4P-F
GTG3H JB3 AUX LUBO
OIL PUMP
TB3-1 TB3-3 TB3-3 GND BUS/FRAME
979899100101102103104
979899100101102103104
SCALE : AS NOTED SHEET 14
89256D -
D
C
B
A
D
C
B
A
FLT III GTG1H/3H FAC PWR
LIST OF MATERIALS
EHQ10998
105106107108109110111112
105106107108109110111112
LIST OF MATERIAL
ITEM QTY DESCRIPTION MATERIAL SPECIFICATION REMARKS
1 1
PANELBOARD, 400A W/BOTTOM FEED 400A MAIN
THERMAL MAGNETIC BRKR, 480VAC, 3PH, 3W, SPACE
FOR AT LEAST (8) 100AF(3) POLE BRANCH BREAKERS,
65KAIC AT 480V, NEMA 1 ENCL, MAX DIMENSIONS ARE
74"H x 28"W x 7"D, SURFACE MTD W/DOOR, INCLUDES
GND BUS, MUST BE RATED TO GND AT 480V MINIMUM
SINCE PANEL IS CONNECTED TO DELTA PWR SYSTEM,
UL LISTED
VARIOUS COMMERCIAL
2 1
PANELBOARD, 125VAC, 3PH, 400A, (14) 3PH OR (20)
1PH, CKTS, TYPE ALB-1, 37.5"H x 15.44"W x 6.5"D, WITH OPTIONAL GROUND DETECTOR (SYMBOL 1005.1
TYPE OR EQUAL)
VARIOUS MIL-DTL-23928/1D
MIL-DTL-23928/1-16DP WITH OPTIONAL GND
DETECTOR
3 1
FUSED DISCONNECT SWITCH, HEAVY DUTY, 240 VAC,
400 AMPS, 3 FUSED POLES, CLASS H FUSE CLIPS,
NEMA 1 ENCL, GROUND LUG, MAX DIMENSIONS WITH
HANDLE TRAVEL ARE 51"HX28"WX12.75"D, UL LISTED
VARIOUS COMMERCIAL
4 2
GTGH1/GTGH3 COOLING FAN MOTOR CONTROLLERS,
440V, 3PH, 50HP MOTOR, 115V CONTROL, INCLUDES CPT,
22"H X 20"W X 9.12"D
VARIOUS MILITARY
GOVERNMENT FURNISHED EQUIPMENT. REF
DRS DWG MC-04015. SOLE SOURCE
PROCUREMENT TO MATCH SHIP
5 1
TRANSFORMER, 45KVA, 480-120V, 3PH, DELTA-DELTA,
(2) FCAN 2.5% TAPS, (4) FCBN 2.5% TAPS, 4.5%-5.6%
IMPEDANCE, NEMA 1 ENCLOSURE, MAX DIMENSIONS ARE
33"H X 28"W X 18"D, UL LISTED
VARIOUS COMMERCIAL
6 2
CIRCUIT BRKR, 480VAC, 15A, 3 POLE, THERMAL
MAGNETIC, FULL RATED 65KAIC AT 480VAC OR SERIES
RATED 65KAIC AT 480V W/UPSTREAM MAIN BRKR IN
ITEM 1, COMPATIBLE FOR USE AS BRANCH BREAKER IN
ITEM 1, MUST BE RATED FOR 480V PH TO GROUND
MINIMUM, UL LISTED
VARIOUS COMMERCIAL
7 2
CIRCUIT BRKR, 480V, 60A, 3 POLE, THERMAL MAGNETIC,
FULL RATED 65KAIC AT 480VAC OR SERIES RATED
65KAIC AT 480V W/UPSTREAM MAIN BRKR IN ITEM 1,
COMPATIBLE FOR USE AS BRANCH BREAKER IN ITEM 1,
MUST BE RATED FOR 480V PH TO GROUND MINIMUM, UL
LISTED
VARIOUS COMMERCIAL
8 2
CIRCUIT BRKR, 480V, 70A, 3 POLE, THERMAL MAGNETIC,
FULL RATED 65KAIC OR SERIES RATED 65KAIC AT 480V
W/UPSTREAM MAIN BRKR IN ITEM 1, COMPATIBLE FOR
USE AS BRANCH BREAKER IN ITEM 1, MUST BE RATED
FOR 480V PH TO GROUND MINIMUM, UL LISTED
VARIOUS COMMERCIAL
9 1
CIRCUIT BRKR, 480V, 80A, 3 POLE, THERMAL MAGNETIC,
FULL RATED 65KAIC AT 480VAC OR SERIES RATED
65KAIC AT 480V W/UPSTREAM MAIN BRKR IN ITEM 1,
COMPATIBLE FOR USE AS BRANCH BREAKER IN ITEM 1,
MUST BE RATED FOR 480V PH TO GROUND MINIMUM, UL
LISTED
VARIOUS COMMERCIAL
10 26
CIRCUIT BRKR, 1 POLE, 15A, 125VAC, TYPE ALB-1, 5KA
INTERRUPTING CAPACITY
VARIOUS MIL-C-17588 NSN 5925-00-244-1756
11 10
CIRCUIT BRKR, 1 POLE, 20A, 125VAC, TYPE ALB-1, 5KA
INTERRUPTING CAPACITY
VARIOUS MIL-C-17588 NSN 5925-00-501-5051
12 16 BREAKER HANDLE YOKE, 2 POLE, TYPE ALB-1 VARIOUS MIL-C-17588 NSN 5925-00-202-0938
13 1 BREAKER HANDLE YOKE, 3 POLE, TYPE ALB-1 VARIOUS MIL-C-17588 NSN 5925-00-862-5582
14 15
CHAIN HANGING KIT FOR LED LTG FIXTURE (ITEM 29),
PAIR, 36" LONG
VARIOUS COMMERCIAL
15 6
"FUSE, 250 VAC, 250A, DUAL ELEMENT, TIME DELAY,
CLASS RK5, 200 KAIC @ 250 VAC, UL LISTED"
VARIOUS COMMERCIAL INCLUDES 3 SPARES. USE WITH ITEM 3
16 9
EMERGENCY LIGHT (2) ADJUSTABLE 7.2W PAR 36
SEALED BEAM LAMPS, 120/277VAC INPUT, INCLUDES
TEST SWITCH, AC LOCKOUT SW WHICH PREVENTS
DISCHARGE, 20W MAX LOAD, METAL ENCLOSURE, MAX
DIMENSIONS INCLUDING HEADS ARE 12"H X 16"W X 6"D,
1-1/2 HOUR CAPACITY AT 16WATTS, INCLUDES
CHARGER, LOW VOLTAGE BATTERY DISCONNECT, 10-40
DEG C OPERATION, UL LISTED
VARIOUS COMMERCIAL
LF
CABLE, LSTSGU-4, 3C-#14AWG, STRANDED COPPER
CONDUCTOR, 1000V, O.D. = .449"
VARIOUS MIL-C-24643 NSN 6145-01-201-9498
LF
CABLE, LSTSGU-9, 3C-#10AWG, STRANDED COPPER
CONDUCTOR, 1000V, O.D. = .575"
VARIOUS MIL-C-24643 NSN 6145-01-201-9499
LF
CABLE, LSFSGU-4, 4C-#14AWG, STRANDED COPPER
CONDUCTOR, 1000V, O.D. = .513"
VARIOUS MIL-C-24643 NSN-6145-01-210-2344
LIST OF MATERIAL (CONTINUED)
ITEM QTY DESCRIPTION MATERIAL SPECIFICATION REMARKS
LF
CABLE, LSFSGU-23, 4C-#7AWG, STRANDED COPPER
CONDUCTOR, 1000V, O.D. = .890"
VARIOUS MIL-C-24643 NSN-6145-01-202-3479
LF
CABLE, LSFSGU-50, 4C-#3AWG, STRANDED COPPER
CONDUCTOR, 1000V, O.D. = 1.05"
VARIOUS MIL-C-24643 NSN 6145-01-205-3629
LF
CABLE, LSFSGU-150, 4C-3/0AWG, STRANDED COPPER
CONDUCTOR, 1000V, O.D. = 1.625"
VARIOUS MIL-C-24643 NSN-6145-01-202-6957
LF
BUILDING WIRE, 1C-#2AWG, STRANDED COPPER,
THHN/THWN 600V INSULATION, O.D. = .39", UL LISTED
VARIOUS COMMERCIAL USE FOR POWER PANEL GROUNDING.
LF
BUILDING WIRE, 1C-#250 MCM, STRANDED COPPER,
THHN/THWN 600V INSULATION, O.D. = .72", UL LISTED
VARIOUS COMMERCIAL
LF
LIQUID TIGHT CONDUIT, 2.5" DIAMETER, PVC UV
RESISTANT JACKET, FLEXIBLE STEEL CORE, 8" MIN
BEND RADIUS, 105C IN AIR, 60C WET, 70C OIL, UL
LISTED
VARIOUS COMMERCIAL
26 4 LIQUIDTIGHT STRAIGHT CONNECTOR, 2.5", UL LISTED
ZINC PLATED
MALLEABLE IRON
COMMERCIAL
27 4
GROUNDING BUSHING, 2.5"DIAMETER, THREADED,
INSULATED SLEEVE, #6 - 4/0 GROUND WIRE RANGE, UL
LISTED
ZINC PLATED
MALLEABLE IRON
COMMERCIAL
28 4
2.5" CONDUIT CLAMP, MIN LOAD RATINGS OF 800LB
VERTICAL, 125LB ALONG AXIS OF CHANNEL, 125LB
PERPENDICULAR TO CHANNEL
ZINC PLATED
CARBON STEEL
COMMERCIAL
29 15
LIGHT FIXTURE, HIGH BAY LED, 8000 LUMENS,
STANDARD EFFICIENCY, GENERAL DISTRIBUTION ACRYLIC
FROSTED LENS, 55 WATTS, 120V, 40K/70 CRI, HIGH
AMBIENT 55 DEGREES C, GLOSS WHITE METAL
ENCLOSURE, RECOMMENDED MTG HEIGHT 10 - 20 FEET,
MAX SPACING TO MTG HEIGHT = 1.25 TO 1.35, COEF OF
UTILIZATION APPROX .4 @0% REFLECTANCE ON CEILING
& WALL AND 20% ON CEILING WITH RCR = 5, SUITABLE
FOR CHAIN HANGING, DIMENSIONS APPROX 26"L X 12"W
X 3"H, UL LISTED
VARIOUS COMMERCIAL
30 33
4" SQUARE JUNCTION BOX, 2-1/8"D, (8)-1/2" KO ON
SIDES & (4)-1/2"&3/4"E KO ON SIDES, GROUND BUMP &
ADDITIONAL KO'S ON BACK, INDOOR USE, 30.3 CU IN
CAPACITY, UL LISTED
PRE-GALVANIZED
CARBON STEEL
COMMERCIAL
31 13
4" SQUARE BOX COVER, 1/2"D, FOR SINGLE DUPLEX
RECEPTACLE, 5 CU IN CAPACITY, FOR USE WITH ITEM
30, UL LISTED
PRE-GALVANIZED
CARBON STEEL
COMMERCIAL
32 20
4" SQUARE BOX COVER, FLAT, BLANK, FOR USE WITH
ITEM 30, UL LISTED
PRE-GALVANIZED
CARBON STEEL
COMMERCIAL
33 100
CABLE CONNECTOR, NYLON INSULATED, INCLUDES
LOCKNUT FOR 1/2" KO, CABLE RANGE .250" - .590", UL
LISTED
VARIOUS COMMERCIAL
USE AT LTG & RCPT JUNC BOXES, EMER
LTG FIXTURES.
AS
REQD
BEAM CLAMP, 5/8" JAW OPENING, 10-24 TAPPED HOLE
SIZES ON BOTTOM & SIDE, 150LB MIN LOAD RATING,
CSA LISTED
ZINC PLATED
CARBON STEEL
COMMERCIAL
AS
REQD
BEAM CLAMP, 5/8" JAW OPENING, 1/4-20 TAPPED HOLE
SIZES ON BOTTOM & SIDE, 250LB MIN LOAD RATING,
CSA LISTED
ZINC PLATED
CARBON STEEL
COMMERCIAL
AS
REQD
CHANNEL, 1-5/8" x 1-5/8", 12 GAUGE, 10 FT LENGTH, MEETS ASTM A108, A1011, B633, MFMA-1
PRE-GALVANIZED
STEEL
COMMERCIAL
37 200
MILITARY CABLE HANGER, TUBULAR TEE TYPE, 6.5"
LONG, 3/8-16 FEMALE THREAD
ZINC PLATED
CARBON STEEL
US NAVY
APPROVED
38 200
MILITARY CABLE HANGER, SINGLE CRIMP-LOK TYPE,
3/8-16 FEMALE THREAD,
.375" - .531" CABLE RANGE
ZINC PLATED
CARBON STEEL
US NAVY
APPROVED
39 100
MILITARY CABLE HANGER, SINGLE CRIMP-LOK TYPE,
3/8-16 FEMALE THREAD,
.531" - .680" CABLE RANGE
ZINC PLATED
CARBON STEEL
US NAVY
APPROVED
40 100
MILITARY CABLE HANGER, DOUBLE CRIMP-LOK TYPE,
3/8 "-16 FEMALE THREAD, .531" - .680" CABLE RANGE
ZINC PLATED
CARBON STEEL
US NAVY
APPROVED
41 200
WELDING STUD, 3/8-16 THREAD SIZE, 3" LONG, FOR
USE WITH ITEMS 37-40, ASTM A-108
ZINC PLATED
CARBON STEEL
COMMERCIAL
42 1
ANTIOXIDANT JOINT COMPOUND, COMPATIBLE W/ALL
CABLE INSULATION TYPES & UL LISTED FOR ALL
VOLTAGES, SYNTHETIC BASE WITH ZINC PARTICLES
VARIOUS COMMERCIAL
LIST OF MATERIAL (CONTINUED ON SH 15)
SCALE : AS NOTED SHEET 15
89256D -
D
C
B
A
D
C
B
A
FLT III GTG1H/3H FAC PWR
LIST OF MATERIALS
EHQ10998
LIST OF MATERIAL (CONTINUED FROM SH 14)
43 1 ELECTRICAL TAPE, GREEN, ROLL VINYL COMMERCIAL USE FOR MARKING GROUND CONDUCTORS.
AS
REQD
CABLE TIE, BLACK, UV RESISTANT, 120LBS MINIMUM
TENSILE STRENGTH, 18" LONG, LOW PROFILE SELF
LOCKING HEAD, MEETS UL94V-2 REQMTS
NYLON COMMERCIAL
LF
BEAM, W4x13 CARBON STEEL ASTM A36 CUT TO SUIT
AS
REQD
THREADED ROD, 1/4"-20, 10' LENGTHS, 240LB LOAD
CAPACITY
ZINC PLATED
CARBON STEEL
COMMERCIAL
AS
REQD
BEAM CLAMP, FOR USE WITH 1-5/8" CHANNEL, 900LB
MIN CAPACITY WHEN USED IN PAIRS
ZINC PLATED
CARBON STEEL
COMMERCIAL SEE DET 84C FOR DESIGN TYPE
48 4
VAPOR TIGHT LIGHT, WALL MOUNT, COMPACT
FLUOURESCENT, 120V, 42 WATT, INCLUDES JX BOX,
MAX DIMENSIONS 15-1/2"H X 8-3/4"D
VARIOUS SEE DETAIL 83B FOR DESIGN TYPE
49 2 3/4" THK PLATE, 12" X 12" CARBON STEEL ASTM A36 UTILIZE FOR FOUNDATION BASE PLATE.
50 7 LF FLAT BAR 4"x 1/4" CARBON STEEL ASTM A36 UTILIZE FOR KICK PLATE, CUT TO SUIT
51 45 LF BEAM, W6x25 CARBON STEEL ASTM A36 CUT TO SUIT
52 4 MOUNTING PLATE, 6" X 6" X 3/16" CARBON STEEL ASTM A36
53 8
WEDGE EXPANSION ANCHOR FOR CONCRETE, HEX HD,
1/2-13UNC-2B,
7" LONG, W/ HEX NUT & WASHER, 4960 LB MIN
TENSILE STRENGTH & 12450 LB MIN SHEAR STRENGTH
WITH 3-1/2" EMBEDMENT IN 4000PSI CONCRETE
316 STAINLESS
STEEL
COMMERCIAL
54 17 STUFFING TUBE, SIZE 2, CABLE RANGE .275" - .472" NYLON MIL-S-19622 NSN 5975-00-296-4093
55 27 STUFFING TUBE, SIZE 4, CABLE RANGE .450" - .777" NYLON MIL-S-19622 NSN 5975-00-296-4095
56 16 STUFFING TUBE, SIZE 5, CABLE RANGE .737" - 1.113" NYLON MIL-S-19622 NSN 5975-00-296-4096
57 2 STUFFING TUBE, SIZE 8, CABLE RANGE 1.61" - 2.00" NYLON MIL-S-19622 NSN 5975-00-296-4099
58 17 PACKING ASSY, SIZE 2E, CABLE RANGE .422" - .472" VARIOUS MIL-S-19622 NSN 5330-00-202-2590
59 4 PACKING ASSY, SIZE 4B, CABLE RANGE .497" - .547" VARIOUS MIL-S-19622 NSN 5330-00-202-2592
60 23 PACKING ASSY, SIZE 4C, CABLE RANGE .534" - .584" VARIOUS MIL-S-19622 NSN 5330-00-202-2593
61 12 PACKING ASSY, SIZE 5D, CABLE RANGE .889" - .937" VARIOUS MIL-S-19622 NSN 5330-00-202-2603
62 2 PACKING ASSY, SIZE 5G, CABLE RANGE 1.033" - 1.073" VARIOUS MIL-S-19622 NSN 5330-00-202-2607
63 2 PACKING ASSY, SIZE 8A, CABLE RANGE 1.61" - 1.641" VARIOUS MIL-S-19622 NSN 5330-00-202-2620
64 13
RECEPTACLE, DUPLEX, 20A, 125VAC, SIDE WIRED, NYLON
FACE, COMMERCIAL GRADE, NEMA 5-20R, UL LISTED
VARIOUS COMMERCIAL
65 400
WELDING STUD, 3/8-16 THREAD SIZE, 1" LONG, FOR USE
WITH ITEMS 37-40, ASTM A-108
ZINC PLATED
CARBON STEEL
COMMERCIAL
66 5 LF 4" X 4" X 1/4" ANGLE STEEL ASTM A36
67 5 LF FLATBAR, 5-1/4" X 1/4" THICK STEEL ASTM A36 CUT TO SUIT
68 10 LF PIPE, 1-1/4" DIAMETER, SCHEDULE 40 GALVANIZED STEEL COMMERCIAL CUT TO SUIT
69 NOT USED
LF
CABLE, LSTSGU-23, 3C-#7 AWG, STRANDED COPPER
CONDUCTOR, 1000V, O.D. = .812"
VARIOUS MIL-C-24643 NSN 6145-01-201-9500
71 4 PACKING ASSY, SIZE 5A, CABLE RANGE .772" - .812" VARIOUS MIL-S-19622 NSN 5330-00-202-2600
| EHQ10998-01 |
| EHQ10998-02 |
| EHQ10998-03 |
| EHQ10998-04 |
| EHQ10998-05 |
| EHQ10998-06 |
| EHQ10998-07 |
| EHQ10998-08 |
| EHQ10998-09 |
| EHQ10998-10 |
| EHQ10998-11 |
| EHQ10998-12 |
| EHQ10998-13 |
| EHQ10998-14 |
| EHQ10998-15 |