REFERENCES
No. TITLE DRAWING No.
IFTP LBTS, BUILDING 77H 1.5MW 4160VAC-1000VDC
COMPACT PWR PHASE III INSTALLATION
EHQ10767
THIS IS A CAD MAINTAINED DRAWING DEVELOPED
IN AUTOCAD R2013 SOFTWARE. CHANGES SHALL BE
INCORPORATED BY THE DESIGN AUTHORITY
UNDER 12" ±1/8"
12" TO 6'-0" ±1/4"
OVER 6'-0" ±1/2"
DISTRIBUTION STATEMENT D
DISTRIBUTION AUTHORIZED TO THE DEPARTMENT
OF DEFENSE AND U.S. DoD CONTRACTORS ONLY;
CRITICAL TECHNOLOGY, 2/23/2011. OTHER U.S.
REQUESTS SHALL BE REFERRED TO COMMANDER,
NAVAL SEA SYSTEMS COMMAND.
PLAN VIEW 3A
BUILDING 77H KEY PLAN
SCALE: NONE
REVISION STATUS
REV SH DESCRIPTION
B 1 TITLE SHEET, BUILDING KEY PLAN, REFERENCES, NOTES
B 2 PLAN VIEW & ISOMETRIC, PHASE 3
B 3
IFTP FLT III EQPT REMOVAL ARRANGEMENT PAD LEVEL,
PHASE 3
B 4
IFTP FLT III EQPT REMOVAL ARRANGEMENT 13'-6" LEVEL,
PHASE 3
B 5
IFTP FLT III 1000VDC ONE LINE RECONFIGURATION,
PHASE 3
B 6
IFTP FLT III 800VDC & 450VAC
ONE LINE RECONFIGURATION, PHASE 3
B 7
IFTP FLT III PHASE 3 COMPACT POWER REMOVAL
BLOCK DIAGRAM
B 8
IFTP FLT III PHASE 3 COMPACT POWER REMOVAL
ARRANGEMENT
B 9
IFTP FLT III CABLE REWORK & REMOVAL ARRANGEMENT,
PHASE 3
B 10
IFTP FLT III PHASE 3 COMPACT POWER AREA
FOUNDATION REMOVAL
B 11
IFTP FLT III EQUIPMENT / TRAY ARRANGEMENT AFTER
PHASE 3
B 12
IFTP FLT III LIST OF MATERIALS, PP2 ONE LINE
RECONFIGURATION
IFTP LBTS, BUILDING 77H
IFTP RECONFIGURATION FOR
FLT III, PHASE 3
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 1 OF 12
89256D EHQ10886 B
CONTRACT No.
N00178-04-D-4089
OFFICAL SIGNATURE DATE
PREPARED R.S. Fox 1/5/16
CHECKED R. Chranowski 1/5/16
QA N/A -
PROJ MGR M. Lamberto 1/5/16
APPROVED NSWCPD
DIMENSIONAL TOLERANCES
UNLESS OTHERWISE SPECIFIED
DIMENSIONS IN FEET & INCHES
DECIMAL DIMENSIONS IN INCHES
TOLERANCE ON ANGLES ±.50°
1 PL ±.2, 2 PL ±.06, 3 PL ±.005
INTERPRET DIMENSIONS AND TOLERANCES
PER ASME Y14.5 - 2009
REVISION HISTORY
DESCRIPTIONREVZONE DATE APPROVED
D
C
B
A
D
C
B
A
12345678
12345678 A C A D F
IL
E N
A M E A C A D E
H P 1/ A C A D N
S W C C D S S E S
IF
T P L
B T S E H Q .D W G
NORTH
DDG 1000 IPS LBTS, BUILDING 77H
LOW VOLTAGE ELECTRICAL ONE LINE DIAGRAM
8328894
IFTP TEST SITE
SEE PLAN VIEW 14A
3 IFTP TEST SITE ONE LINE DIAGRAM 7261555
4 IFTP RECONFIGURATION FOR FLT III, PHASE 1 EHQ10764
NOTES:
1. DEVIATIONS FROM THIS DRAWING ARE NOT PERMITTED WITHOUT APPROVAL
FROM THE NSWCPD CONSTRUCTION MANAGER (CODE 212).
2. SEE REFERENCE 2 AND 3 FOR ANY ADDITIONAL IFTP EQUIPMENT INFORMATION
REQUIRED THAT IS NOT FOUND IN THIS DRAWING.
3. VERIFY ALL CIRCUITS ARE TAGGED OUT PRIOR TO EQUIPMENT AND CABLE
REMOVAL.
4. ANY EQUIPMENT WHICH HAS CABLE REMOVED AND EQUIPMENT REMAINS
INSTALLED SHALL HAVE CABLE OPENINGS CLOSED WITH PLUGS OR SHEET
METAL COVERS. IT IS PREFERABLE TO USE STUFFING TUBE PLUGS
(ITEMS 5-6) WHERE POSSIBLE.
5. FOLLOW THE LATEST VERSION OF THE NATIONAL ELECTRICAL CODE (NEC) FOR
ANY INSTALLATION DETAILS NOT COVERED WITHIN THIS DRAWING.
6. FOR DC CIRCUITS, 2 CONDUCTORS ARE TO BE CONNECTED IN PARALLEL FOR THE
POSITIVE CONNECTION AND 2 CONDUCTORS ARE TO BE CONNECTED IN PARALLEL
FOR THE NEGATIVE CONNECTION:
PHYSICALLY OPPOSING CONDUCTORS SHALL BE UTILIZED FOR POSITIVE AND
ALSO NEGATIVE CIRCUITS AS SHOWN IN SKETCH. WHITE AND GREEN
CONDUCTORS SHALL BE ENTIRELY SLEEVED TO BREAKOUT BOOT WITH WHITE
SHRINK TUBE (ITEM 4) IN DCJB1 FOR NOTE 15 ALTERED CIRCUITS. BLACK AND
RED CONDUCTORS SHALL BE ENTIRELY SLEEVED TO BREAKOUT BOOT WITH
BLACK SHRINK TUBE (ITEM 3) IN DCJB1 FOR NOTE 15 ALTERED CIRCUITS.
7. POWER CABLES SHALL BE INSTALLED IN A SINGLE LAYER IN TRAY AND SHALL
BE SECURED TO TRAY RUNGS EVERY 36" USING BLACK NYLON TIE WRAPS
HAVING A MINIMUM TENSILE STRENGTH OF 120 LBS.
8. MISCELLANEOUS HARDWARE SUCH AS TIE WRAPS ARE NOT INCLUDED IN THE
MATERIAL LIST BUT MUST BE PROVIDED BY THE INSTALLER.
9. CIRCUIT NUMBERING IS AS FOLLOWS: 1BB1S-10P-2BB1S
POWER SOURCE
10P = 1000V
LOAD
10. UTILIZE SILICON BRONZE BOLTING HARDWARE (BOLT, NUT, 2 FLAT WASHERS, 1
LOCK WASHER) FOR POWER CIRCUIT/BUS BAR CONNECTIONS IF ANY HARDWARE
REQUIRES REPLACING. ZINC PLATED, GRADE 5 CARBON STEEL HARDWARE CAN
BE USED FOR GROUNDING CONNECTIONS. REUTILIZE EXISTING BOLTING
HARDWARE UNLESS IT IS FOUND TO BE DAMAGED. UTILIZE TORQUE SEAL
MARKER (ITEM 8) TO MARK BOLTING HARDWARE AFTER TORQUING TO
SPECIFICATION. TORQUE 3/8" SILICONE BRONZE HARDWARE TO 2O FT LBS AND
1/2" SILICONE BRONZE TO 40 FT LBS. TORQUE 3/8" GRADE 5 STEEL HARDWARE
TO 20 FT LBS AND 1/2" GRADE 5 STEEL TO 48 FT LBS.
11. PCM'S BEING REMOVED HAVE INLET AND OUTLET 2" COOLING LINES WHICH ARE
ALL LESS THAN 5' IN LENGTH THAT REQUIRE DISCONNECTION AT FLANGE
ADJACENT TO LOCAL SHUTOFF VALVE. FABRICATE OR PURCHASE AND INSTALL
BLIND FLANGES WHERE INLET/OUTLET EQUIPMENT COOLING LINES ARE REMOVED.
FOR COMPACT POWER WATER LINE REMOVAL BE SURE TO REMOVE THE INLET
WATER FILTER ASSEMBLY AND STORE WITH COMPACT POWER.
12. CABLES BEING REMOVED ARE ALL GENERALLY BEING REMOVED FROM EXISTING
OVERHEAD TRAY. ALL TRAY SHALL BE LEFT IN PLACE FOR FUTURE USE.
13. ALL REMOVED EQUIPMENT SHALL BE PLACED IN A LAYDOWN AREA AS
INSTRUCTED BY THE NSWCPD CONSTRUCTION MANAGER.
(+) = WHT AND GRN
(-) = BLK AND RED
NOTES:
14. DISCONNECT EXISTING CIRCUIT 2BB1S-10P-3BB1S AT 2BB1S END ONLY. INSULATE
ENDS OF THIS CABLE AND LAY IN OVERHEAD TRAY FOR FUTURE CONNECTION TO
MPDU.
15. DISCONNECT EXISTING CIRCUIT 2BB1S-10P-DCJB1 AT DCJB1 END ONLY. REROUTE
CIRCUIT AS INDICATED IN DASHED LINES ON SHEET 9 AND RECONNECT IN DCJB1. CUT
CABLE TO LENGTH. UTILIZE NEW LUGS, BREAKOUT BOOTS, AND SLEEVING (ITEMS 1
THRU 4). SEE NOTE 6 FOR ADDITIONAL INSTRUCTIONS. REFERENCE 5 SHOWS
SHIPBOARD CABLE PREPARATION PROCEDURE. CABLE IS REROUTED TO KEEP THIS
CIRCUIT OUT OF CABLEWAY TO BE USED FOR 4KV CIRCUITS IN THE FUTURE.
16. TEMPORARILY MOVE ANY FENCE, PIPES, STAIRS, ETC THAT INTERFERES WITH
EQUIPMENT REMOVAL.
17. NSWCPD SHALL PERFORM INSULATION RESISTANCE TEST OF MODIFIED CIRCUITS AT
JOB'S END TO VERIFY ACCEPTABLE COMPLETION OF WORK. ISOLATE REQ'D
COMPONENTS PRIOR TO INSULATION RESISTANCE TESTING.
18. ALL COMPACT POWER AND COMPACT POWER PRECHARGE CABINET CABLES BEING
REMOVED SHALL BE REMOVED BACK TO THEIR TERMINATION POINTS INSIDE
ENCLOSURES. REMOVED CABLES FOR THIS EQUIPMENT CAN NOT BE JUST CUT OFF
AND LEFT CONNECTED INSIDE EQUIPMENT.
19. FOR EQUIPMENT BEING REMOVED, PLEASE MAKE SURE ALL CABLES INCLUDING
CONTROL CABLING AND SEALTITE ARE REMOVED IN THEIR ENTIRETY.
20. ALL ITEMS REFERRED TO IN THE NOTES ABOVE CAN BE FOUND IN THE LIST OF
MATERIALS IN THIS DRAWING.
ELECTRIC PLANT INSTALLATION METHODS FOR SURFACE
SHIPS
5 MIL-STD-2008
NAVAL SURFACE WARFARE CENTER, PHILADELPHIA DIVISION
PHILADELPHIA, PA 19112-5083
IFTP RECONFIGURATION FOR FLT III, PHASE 26 EHQ10771
N. Silva
A. Cairns
3/16/16
3/23/16
TECH REVIEW
PROG MGR
ALL
A
MINOR VERBIAGE CHANGES MADE THROUGHOUT
DRAWING FOR CLARITY.
PREPARED: B. EVERLING 11/15/16
CHECKED: R. CHRANOWSKI 11/16/16
PROJ. MGR: M. LAMBERTO 11/17/16
TECH REVIEW
PROG MGR
A. Cairns
11/23/16
N. Silva
11/28/16
B
B
INCORPORATED USACE COMMENTS OF 4/14/17
AND 4/18/17.
PREPARED: D. MERLINO 4/25/17
CHECKED: R. CHRANOWSKI 4/25/17
PROJ MGR: M. LAMBERTO 4/28/17
ALL
TECH REVIEW
T.CHECCHIO
PROG MGR
A. CAIRNS
4/28/2017
4/29/2017
IFTP FLT III RECONFIGURATION
PLAN VIEW & ISO, PHASE 3
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 2
89256D EHQ10886 B
D
C
B
A
D
C
B
A
910111213141516
910111213141516
PLAN VIEW 14A
IFTP FLT III LBTS RECONFIGURATION, PHASE 3
BUILDING KEY PLAN
SCALE: NONE
NORTH
ISOMETRIC VIEW 10B
LOOKING NORTHWEST
IFTP FLT III LBTS RECONFIGURATION, PHASE 3
SCALE: NONESEE PLAN VIEW 21A
IFTP FLT III EQPT REMOVAL
ARRGMNT PAD LEVEL, PHASE 3
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 3
89256D EHQ10886 B
D
C
B
A
D
C
B
A
1718192021222324
1718192021222324
REMOVE 2-PCM4 AUX SWITCH
WITH FDN STEEL
REMOVE COMPACT PWR PHASE III PCM
(SEE FULL DETAILS ON SH 8, 10)
B
24232221
PLAN VIEW 21A
IFTP FLT III LBTS RECONFIGURATION,
PHASE 3, PAD LEVEL EQUIPMENT
SCALE: 1/4"=1'-0"
NORTH
REMOVE 1BB1P
REMOVE 1PCM4 WITH FDN STEEL
REMOVE 2PCM4
WITH FDN STEEL
REMOVE 1BB1S
RP1
A
3BB1P
GRAPHIC SCALE 1/4"=1'-0"
0 2'1' 3' 4' 5' 10' 15'
REMOVE 2BB1P REMOVE 2BB1S
3BB1S
JB2
IFTP CONTROL ROOM
7S SWBD
PP4BTSPP2
DCJB1
2X ABT
3PP2
3PP1
2PP2
2PP1
1PP3
1PP2
1PP1 1MBT1
2MBT1
3MBT1
PNCC IB
REMOVE 3BB2
JB3
JB1
REMOVE 2BB2
REMOVE 1BB2
XFMR2
XFMR3
ONLY REMOVE PIPING THAT
IS PART OF PCM EQUIPMENT
(SEE NOTE 11)
REMOVE BUT SAVE FOR
FLT III SHORE POWER
IFTP FLT III EQPT REMOVAL
ARRGMNT 13'-6" LEVEL, PHASE 3
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 4
89256D EHQ10886 B
D
C
B
A
D
C
B
A
B
24232221
PLAN VIEW 29A
IFTP FLT III LBTS RECONFIGURATION,
PHASE 3, 13'-6" LEVEL EQUIPMENT
SCALE: 1/4"=1'-0"
NORTH
A
GRAPHIC SCALE 1/4"=1'-0"
0 2'1' 3' 4' 5' 10' 15'
IFTP CONTROL ROOM
PAD LEVEL EQUIPMENT
NOT SHOWN
OVHD TRAY,
ELEVATION 11'-5"
13'-6" LEVEL EQUIPMENT PREVIOUSLY
REMOVED USING NSWCPD
2526272829303132
2526272829303132
IFTP FLT III 1000VDC ONE LINE
RECONFIGURATION, PHASE 3
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 5
89256D EHQ10886 B
D
C
B
A
D
C
B
A
(3) LSFSGU-200
INSTALLED PER REF 1
LB2 2000KW
DCJB2
DCJB1
LB1 2000KW
(4) LSFSGU-200
(DCJB2-S)-10DC-LB1
(4) LSFSGU-200
DCJB1-10DC-(DCJB2-S)
(4) LSFSGU-200
(DCJB2-P)-10DC-LB2 (4) LSFSGU-200
DCJB1-10DC-(DCJB2-P)
PORT
STBD
4SG
4160VAC
P
S
(2PCM4)
P
S
CAPS CR2
(1PCM4)
2000 KW
(1BB1P)
COMPACT PWR
PH III PCM SYSTEM, 1.5MW
4160VAC - 1000VDC
INSTALLED PER REF 1
6S SWBD - 4160V
6S-CB4
1000 KW
(3BB1P) (2BB1P)
(3BB1S) (2BB1S) (1BB1S)
AFT CC
MAIN BUS
PREVIOUSLY REMOVED CABLE (REF 1)
EXISTING CABLES
NEW JUMPER CABLES
LEGEND
REMOVE CABLE & EQPT
(5) LSFSGS-200
(5) LSFSGU-200
(5) LSFSGU-200
INTERNAL CABINET
JUMPERS (TYP)
2P1P-10P-FWD
1BB1S-10P-2BB1S
2BB1P-10P-3BB1P
INTERNAL CABINET
JUMPERS (TYPICAL) 2BB1S-10P-3BB1S
(5) LSFSGS-200
3BB1P-10P-LB1
(5) LSFSGS-200
3BB1S-10P-DCJB1
(5) LSFSGS-200
(2) LSFSGS-200
2P4-1OP-2BB1S
(5) LSFSGS-200
1PCM4-10P-S
2P4-10P-AUXSWIN
(2) LSFSGS-200
(5) LSFSGS-200
1PCM4-1OP-P
(2) LSFSGS-200
2P4-10P-2BB1P
SEE NOTE 14
3334353637383940
3334353637383940
REMOVE PREVIOUSLY
DISCONNECTED CABLE
IFTP FLT III 800VDC & 450VAC
ONE LINE RECONFIG, PHASE 3
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 6
89256D EHQ10886 B
D
C
B
A
D
C
B
A
PREVIOUSLY REMOVED CABLE (REF 1)
EXISTING CABLES
NEW JUMPER CABLES
LEGEND
REMOVE CABLE & EQPT
MTG CLG FAN CAB (DDG1000 18'-0" LVL)
TO PNCC
IB
MTG2
F2
MTG2
F1
MTG MOD
CLG FAN VSD
80 HP80 HP
CLG FANCLG FAN
DISC, CONTROLLER &
COOLING WATER
7S
(SEE REF 2)
S P
2PP2
2PP1
A
C
L
C
21PP3
1PP2
1PP1
3PP3
3PP2
3PP1
A
C
L
C
7S
(SEE REF2)
3BB2
PP4
2MBT1
PUMP 2 DISC, CONTROLLER &
COOLING WATER
PP4
1MBT1
PUMP MOTOR 1DISC, PUMP DISC,
COOLING WATER
PP4
CONTROLLER,
& PUMP 33MBT1
3PCM REMAINING RELATED EQUIPMENT
SEE REF 4, 5 & 6 FOR CONNECTIONS PREVIOUSLY REMOVED
2PCM REMAINING RELATED EQUIPMENT
SEE REF 4, 5, & 6 FOR CONNECTIONS
PREVIOUSLY REMOVED
1PCM REMAINING RELATED EQUIPMENT
SEE REF 4, 5 & 6 FOR CONNECTIONS
PREVIOUSLY REMOVED
2BB2
PP2
IFTP ROUTER/SW
PP2
IFTP ROUTER/SW
PP2
IFTP ROUTER/SW
1BB2
1P 1P
T O D
D X
(1 L S F S G U
1P C M 1S
D C A
(1 L S F S G U
NOTE:
FOR PP2 ONE LINE DIAGRAM
RECONFIGURATION SEE SHEET 12.
IFTP CONTROL
ROOM
4142434445464748
4142434445464748
IFTP FLT III PHASE 3 COMPACT
PWR REMOVAL BLK DIAGRAM
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 7
89256D EHQ10886 B
D
C
B
A
D
C
B
A
A1J3A1J3COMPACT PWR PH III
4160VAC SWGR TEST
(PRECHARGE CABINET)
REFERENCE 4
4160V
IN
4160V
OUT
3-1C-4/0, 7.5KV
TYPE AWM (EXISTING)
CPPH3PC-40P-CPPH3PCM
1-LS5KVTSSGSG-250
4SGA-40P-CPPH3PC
1-LS5KVTSSGSG-250
OPEN/CLOSE EMERG PWR REMOVAL (REAR)
4160V
IN (REAR)
PRECHARGE CABINET
CONNECTION BOX
1000VDC
OUT (REAR)
IFTP TEST SITE
JUNCTION BOX 3BB1P
CPPH3PCM-10DC-3BB1P
(3) LSFSGU-200
COMPACT POWER PH III
PCM - 1.5MW
A1J1
A1J2
IFTP 440VAC
PP2
CB6
440V IN (REAR)
EMERG PWR REMOVAL (REAR)
COMPACT PWR PH III
LOAD PERM TEST FIXTURE
(IFTP CONTROL ROOM)
A1J4A1J4
K-CPPH3-3
1-6C-#16AWG, 600V
TYPE S00W
LOAD PERM/E-STOP (REAR)
A1J5 REMOTE E-STOP (REAR)
IFTP CONTROL ROOM
LAPTOP
(IFTP CONTROL ROOM)
A1J6. K-CPPH3-5
ETHERNET CABLE
MAINTENANCE ETHERNET (FRONT)
A1J7 COMPUTER LOGIC USB PORT (FRONT)
A1J8
(N/A FOR TEST SITE)
MCS ETHERNET PORT (REAR)
(N/A FOR TEST SITE)
3-1C-4/0, 7.5KV
TYPE AWM (EXISTING)
FIXTURE
4160V 4SG SWBD, BRKR 1
4950515253545556
4950515253545556
VERIFY ALL CABLES CONNECTED TO COMPACT POWER
PH III HAVE BEEN REMOVED AT CONCLUSION OF WORK.
ANY CABLES STILL CONNECTED MUST BE REMOVED IN
THEIR ENTIRETY.
PWR REMOVAL ARRANGEMENT
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 8
89256D EHQ10886 B
D
C
B
A
D
C
B
A
5758596061626364
5758596061626364
IPS IFTP 6S
SWITCHBOARD
COMPACT PWR PH III PCM (CPPH3) 1.5MW (SEE NOTE 18)
B
CPPH3PC-40P-CPH3PCM & K-CPPH3-2
EXISTING 4160V
CABLE TRAY
3X CPPH3PCM OUTPUT CABLES
DOWN TO PCM CONNECTION
REMOVE CPPPH3PCM OUTPUT
CABLES DOWN TO 3BB1P
CONNECTION
REMOVE 1BB1P
4SGA-40P-CPPH3PC (1) LS5KVTSSGSG-250 & (1) SPARE
LS5KVTSSGSG-250 DISCONNECTED AT BOTH ENDS & INSULATED
1000VDC POWER CABLE TRAY.
REMOVE CPPH3PCM-10DC-3BB1P
(3) LSFSGU-200
PP2CB6-4P-CPPH3TF,
ATTACHED TO BOTTOM
FLANGE OF EXST TRAY
SUPPORT STEEL USING
BEAM CLAMPS & TIE-WRAPS
POWER PANEL PP2
A
3BB1P
PRECHARGE CABINET CONNECTION BOX
CPPH3 PRECHARGE CABINET (SEE NOTE 18)
REMOVE K-CPPH3-5, K-CPPH3-3
EXST 1000V CABLE TRAY
K-CPPH3-2 (EXISTING W/EXISTING A1J1)
K-CPPH3-3 (EXST A1J4)
K-CPPH3-5, EXISTING A1J6
CPPH3 LOAD PERMISSIVE TEST FIXTURE
EXISTING A1J4
LAPTOP
ROUTE ETHERNET CABLE
UNDER RAISED FLOOR
TO VICINITY OF 4SG SWBD - (2) 4KV CABLES
(ADDITIONAL 150 FT OF CABLE TO BE
REMOVED IN TRAY)
PARTIAL PLAN VIEW 57B
CPPH3 PCM CABLE ROUTING
SCALE: 1/2"=1'-0"
NORTH
COMPACT PWR PH III PCM
(CPPH3PCM) - 1.5MW
EXISTING A1J1 & A1J2
SEE PARTIAL PLAN
VIEW 57B FOR
ADDITIONAL CABLE
DETAILS
GRAPHIC SCALE 1/2"=1'-0"
0 6" 2' 3' 4' 5' 10'1'
SEE PARTIAL PLAN
VIEW 77B FOR FDN
REMOVAL AFTER
EQUIPMENT REMOVAL
PARTIAL PLAN VIEW 61A
CPPH3 PCM CABLE ROUTING
SCALE: 1/4"=1'-0"
NORTH
GRAPHIC SCALE 1/4"=1'-0"
0 2'1' 3' 4' 5' 10' 15'
REMOVE 2BB1P REMOVE 2BB2
REMOVE 1BB2 REMOVE 1BB1S
REMOVE 2BB1S
REMOVE 3BB2
EXISTING A1J5
IFTP FLT III CABLE REWORK &
REMOVAL ARRGMT, PHASE 3
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 9
89256D EHQ10886 B
D
C
B
A
D
C
B
A
B
24232221
PLAN VIEW 69A
IFTP FLT III LBTS RECONFIGURATION, PHASE 3,
CABLE REWORK & REMOVAL ARRANGEMENT PAD LEVEL
SCALE: 1/4"=1'-0"
NORTH
A
GRAPHIC SCALE 1/4"=1'-0"
0 2'1' 3' 4' 5' 10' 15'
3BB1S
IFTP CONTROL ROOM
2BB1P-10P-3BB1P
2BB1S-10P-3BB1S, DISCONNECT
CABLE AT 2BB1S END ONLY
SEE NOTE 14
EXISTING OVERHEAD CABLE
TRAY, ELEVATION 11'-5"
3BB1P
6566676869707172
6566676869707172
REMOVE 1BB1P REMOVE 2BB1P REMOVE 2BB2
REMOVE 1BB2 REMOVE 1BB1S
REMOVE 2BB1S
REMOVE 3BB2
JB1
JB2
LEGEND
REMOVE CABLE
CABLE TO REMAIN
CABLE REROUTED
3BB1P-10P-LB1
3BB1S-10P-DCJB1. SEE NOTE 15
3BB1S-10P-DCJB1
REROUTED AS
SHOWN. SEE
NOTE 15
2P1P-10P-FWD1PCM4-10P-P
3/4" SEALTITE TO JB1
2P4-10P-2BB1P
3/4" SEALTITE TO JB2
3/4" SEALTITE TO JB1
3/4" SEALTITE TO JB1
2P4-10P-2BB1S
1BB1S-10P-2BB1S
1PCM4-10P-S
2" SEALTITE W/CONT WIRING
2P4-10P-AUXSWIN
(1) 4KV CABLE
DCJB1PNCCIB
REMOVE COMPACT POWER
(SEE SH7 AND SH8 FOR COMPACT
POWER CABLE REMOVALS) REMOVE 2PCM-4 AUX SW
REMOVE 2PCM-4 REMOVE 1-PCM4
PWR AREA FDN REMOVAL
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 10
89256D EHQ10886 B
D
C
B
A
D
C
B
A
7374757677787980
7374757677787980
PARTIAL PLAN VIEW 77B
CPPH3 EQPT FOUNDATION & DIAMOND PLATE
REMOVAL
SCALE: 1 1/2"=1'-0"
20'-0"
2'-2 "4'-0
"6"
2'-3
6'-6"
4'-7"
GRAPHIC SCALE 1 1/2"=1'-0"
0 3" 6" 9" 2' 3' 4'1'
REMOVE EXISTING DIAMOMD PL
REMOVE EXISTING EQUIPMENT STRUCTURE
IFTP FLT III EQUIPMENT/TRAY
ARRANGEMENT AFTER PHASE 3
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 11
89256D EHQ10886 B
D
C
B
A
D
C
B
A
GRAPHIC SCALE 1/4"=1'-0"
0 2'1' 3' 4' 5' 10' 15'
B
24232221
PLAN VIEW 85A
IFTP FLT III LBTS RECONFIGURATION, PHASE 3,
CABLE INSTALLATION ARRGMT PAD LEVEL
SCALE: 1/4"=1'-0"
NORTH
A
IFTP CONTROL ROOM
EXISTING OVERHEAD CABLE
TRAY, ELEVATION 11'-5"
EXISTING OVERHEAD CABLE
TRAY, ELEVATION 11'-5"
PP4
BTS
PP2
2X ABT
3PP2
3PP1
2PP2
2PP1
1PP3
1PP2
1PP1 1MBT1
2MBT1
3MBT1
RP1
3BB1P
3BB1S
JB2
7S SWBD
DCJB1PNCC IB
JB3
JB1
XFMR2
XFMR3
8182838485868788
8182838485868788
IFTP FLT III LIST OF MATERIALS,
PP2 ONE LINE RECONFIGURATION
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 12
89256D EHQ10886 B
D
C
B
A
D
C
B
A
100A, 3P
20A, 3P
20A, 3P
20A, 3P
20A, 3P
20A, 3P
30A, 3P 30A, 3P
30A, 3P
20A, 3P
20A, 3P
20A, 3P
20A, 3P
PP2-4P-1
PP2-4P-3
(1) LSTSGU-9
PP2-4P-4
(1) LSTSGU-9
PNCC
2PCM4 1PCM4
SPARE
SPARE
SPARE
TO PP6A
DETAIL 91B
PP2 - 450VAC, 3Φ
ONE LINE DIAGRAM
SCALE: NONE
8990919293949596
8990919293949596
SPARE
SPARE
SPARE
LIST OF MATERIAL
ITEM QTY DESCRIPTION MATERIAL SPECIFICATION REMARKS
1 25
COPPER COMPRESSION LUG, 1 HOLE w/INSPECTION
WINDOW, 4/0 AWG, 200 NAVY, 3/8" STUD, LONG
BARREL, 35kV, 90° C, TIN PLATED COPPER, 2.95"
LENGTH, UL LISTED, CSA CERTIFIED
TIN PLATED
COPPER
COMMERCIAL
USE WITH LSFSGU-200 CABLE. INCLUDES 5
SPARE.
2 6
BREAKOUT BOOT, 4 WAY, CABLE END MAX = 2.35"
WITH SHRINK TO 1.00" MIN, CONDUCTOR LEGS MAX =
1.00" WITH SHRINK TO .35" MIN
POLYOLEFIN DOD-STD-2003-1
NSN 5970-01-554-6791
INCLUDES 1 SPARE.
ROLL
TUBING, SHRINKABLE FIT, 1.0" MAX TO .5" MIN WITH
SHRINK, -55°C TO 135°C, BLACK 50' ROLL,
INSULATION SLEEVING, ELECTRICAL, HEAT SHRINKABLE,
POLYOLEFIN, FLEXIBLE, CROSSLINKED
X LINK
POLYOLEFIN
MIL-DTL-23053/5
ROLL
TUBING, SHRINKABLE FIT, 1.0" MAX TO .5" MIN WITH
SHRINK, -55°C TO 135°C, WHITE 50' ROLL
INSULATION SLEEVING, ELECTRICAL, HEAT SHRINKABLE,
POLYOLEFIN, FLEXIBLE, CROSSLINKED
X LINK
POLYOLEFIN
MIL-DTL-23053/5
5 18 STUFFING TUBE PLUG, SIZE 8 NEOPRENE MIL-S-19622
NSN 5975-00-296-3857.
INCLUDES 5 SPARE.
6 5 STUFFING TUBE PLUG, SIZE 4 NEOPRENE MIL-S-19622
NSN 5975-00-296-3861.
INCLUDES 3 SPARE.
7 1 DIAMOND PLATE, 1/4" THICK 10' X 4'-7" CARBON STEEL ASTM A36 CUT TO SUIT
8 2
TORQUE SEAL, TAMPER PROOF MARKER, -20°F TO
450°F, .5 OZ TUBE, ORANGE, MADE FOR MARKING
ELECTRICAL BOLTED CONNECTIONS 120V-4160V AND
COMPATIBLE WITH VARIOUS METAL SURFACES
SUCH AS COPPER, TIN PLATED COPPER, ZINC PLATED
CARBON STEEL, AND SILICON BRONZE.
VARIOUS COMMERCIAL
SPARE
SPARE
SPARE
SPARE
B
B
B
B
B
| EHQ10886-01 |
| EHQ10886-02 |
| EHQ10886-03 |
| EHQ10886-04 |
| EHQ10886-05 |
| EHQ10886-06 |
| EHQ10886-07 |
| EHQ10886-08 |
| EHQ10886-09 |
| EHQ10886-10 |
| EHQ10886-11 |
| EHQ10886-12 |