REFERENCES
No. TITLE DRAWING No.
1 US PIONEER SHORE TERMINAL BOX, P/N 3634-03 12474
THIS IS A CAD MAINTAINED DRAWING DEVELOPED
IN AUTOCAD R2013 SOFTWARE. CHANGES SHALL BE
INCORPORATED BY THE DESIGN AUTHORITY
UNDER 12" ±1/8"
12" TO 6'-0" ±1/4"
OVER 6'-0" ±1/2"
DISTRIBUTION STATEMENT D
DISTRIBUTION AUTHORIZED TO THE DEPARTMENT
OF DEFENSE AND U.S. DoD CONTRACTORS ONLY;
CRITICAL TECHNOLOGY, 2/23/2011. OTHER U.S.
REQUESTS SHALL BE REFERRED TO COMMANDER,
NAVAL SEA SYSTEMS COMMAND.
PLAN VIEW 3B
BUILDING 77H KEY PLAN
SCALE: NONE
REVISION STATUS
REV SH DESCRIPTION
D 1 TITLE SHEET, BUILDING KEY PLAN, REFERENCES, NOTES
D 2 PCM CABLE ROUTING AND ISOMETRIC VIEW
D 3
FLT III PCM 4160V/1000VDC ONE LINE DIAG & PCM
BONDING PLATE
D 4
FLT III PCM CABLE INSTALLATION MATERIAL LIST AND
DETAILS
D 5
FLT III PCM CABLE INSTALLATION MATERIAL LIST AND
DETAILS
D 6 FLT III PCM CABLE INSTALLATION MATERIAL LIST
DDG 51 LAND BASED ENGINEERING SITE (LBES), BUILDING 77H
FLT III PCM UTILITY POWER
CABLE INSTALLATION
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 1 OF 6
89256D EHQ10939
CONTRACT No.
N00178-04-D-4089
OFFICAL SIGNATURE DATE
PREPARED B. Everling 7/29/16
CHECKED R. Chranowski
QA N/A -
PROJ MGR M. Lamberto 8/1/16
APPROVED NSWCPD
DIMENSIONAL TOLERANCES
UNLESS OTHERWISE SPECIFIED
DIMENSIONS IN FEET & INCHES
DECIMAL DIMENSIONS IN INCHES
TOLERANCE ON ANGLES ±.50°
1 PL ±.2, 2 PL ±.06, 3 PL ±.005
INTERPRET DIMENSIONS AND TOLERANCES
PER ASME Y14.5 - 2009
REVISION HISTORY
DESCRIPTIONREVZONE DATE APPROVED
D
C
B
A
D
C
B
A
12345678
12345678 A C A D F
IL
E N
A M E A C A D E
H P 1/ A C A D N
S W C C D S S E S D D G
F L
IG
H T I
II/
E H Q F
L T I
II
P C M U
T
IL
IT
Y P
W R C
A B L E I N S T A L L A T
IO
N .D W G
NORTH
2 DRS TECHNOLOGIES PCM OUTLINE AND INSTALLATION RMC-037076
POWER CONVERSION
TEST SITE
SEE PLAN VIEW 14A
NOTES:
1. DEVIATIONS FROM THIS DRAWING ARE NOT PERMITTED WITHOUT APPROVAL
FROM THE NSWCPD CONSTRUCTION MANAGER (CODE 212).
2. VERIFY ALL CIRCUITS ARE TAGGED OUT PRIOR TO CONNECTION TO POWER
SOURCES.
3. FOLLOW THE LATEST VERSION OF THE ELECTRICAL CODE (NEC) INSTALLATION
DETAILS NOT COVERED WITHIN THIS DRAWING.
4. FOR DC CIRCUITS, 2 CONDUCTORS ARE TO BE CONNECTED IN PARALLEL FOR THE
POSITIVE CONNECTION AND 2 CONDUCTORS ARE TO BE CONNECTED IN PARALLEL
FOR THE NEGATIVE CONNECTION:
PHYSICALLY OPPOSING CONDUCTORS SHALL BE UTILIZED FOR POSITIVE AND
ALSO NEGATIVE CIRCUITS AS SHOWN IN SKETCH. WHITE AND GREEN
CONDUCTORS SHALL BE ENTIRELY SLEEVED TO BREAKOUT BOOT WITH WHITE
SHRINK TUBE (ITEM 4). BLACK AND RED CONDUCTORS SHALL BE ENTIRELY
SLEEVED TO BREAKOUT BOOT WITH BLACK SHRINK TUBE (ITEM 3).
5. POWER CABLES SHALL BE INSTALLED IN A SINGLE LAYER IN TRAY AND SHALL
BE SECURED TO TRAY RUNGS EVERY 36" USING BLACK NYLON TIE WRAPS
HAVING A MINIMUM TENSILE STRENGTH OF 120 LBS. CABLE CROSS OVERS ARE
ALLOWED BUT SHALL BE MINIMIZED.
6. MISCELLANEOUS HARDWARE SUCH AS TIE WRAPS ARE NOT INCLUDED IN THE
MATERIAL LIST BUT MUST BE PROVIDED BY THE INSTALLER.
7. CIRCUIT NUMBERING IS AS FOLLOWS: PCM1-10P-3BB1S
POWER SOURCE
10P = 1000V
40P = 4160V
LOAD
8. IN GENERAL, UTILIZE SILICON BRONZE BOLTING HARDWARE (BOLT, NUT, 2 FLAT
WASHERS, 1 LOCK WASHER) FOR POWER CIRCUIT/BUS BAR CONNECTIONS EXCEPT
PCM'S WHICH WILL GRADE 5 ZINC PLATED CARBON STEEL HARDWARE IDENTIFIED
IN THE EQUIPMENT CONNECTION HARDWARE TABLE (DET 39D) BASED ON
MANUFACTURER REQUIREMENTS. SEE THE EQUIPMENT CONNECTION HARDWARE
TABLE (DET 39D) FOR EXPECTED POWER CIRCUIT CONNECTION HARDWARE TO BE
UTILIZED FOR ALL EQUIPMENT. ZINC PLATED, GRADE 5 CARBON STEEL
HARDWARE CAN BE USED FOR GROUNDING CONNECTIONS. REUTILIZE EXISTING
BOLTING HARDWARE WHEN AVAILABLE UNLESS IT IS FOUND TO BE DAMAGED.
UTILIZE TORQUE SEAL MARKER (ITEM 7) TO MARK BOLTING HARDWARE AFTER
TORQUING TO SPECIFICATION. TORQUE 3/8" HARDWARE TO 2O FT LBS AND 1/2"
HARDWARE TO 40 FT LBS.
9. NSWCPD SHALL VERIFY 4160V SWBD 6S BREAKER CB6 AND CB8 BREAKERS
HAVE 200 AMP SENSORS INSTALLED AND HAVE LONG TIME TRIP SET AT 300A
WITH LTD BAND, SHORT TIME AT 1000A WITH DELAY BAND 4, AND
INSTANTANEOUS AT 4000A.
10. DUE TO BENDING RADIUS CONCERNS FOR CABLING INSIDE THE HVSP TERMINAL
BOX, UTILIZE THE UNSHIELDED 350MCM 5KV/15KV JUMPER WIRE (ITEM 12) INSIDE
THE HVSP TERMINAL BOX WITH (2) HOLE COMPRESSION LUGS (ITEM 15). BOLT
THE CABLING INSIDE THE HVSP TERMINAL BOX TO THE BUS BAR SECTION THAT
ACCOMMODATES THROUGH BOLTING. IF THE TAPPED BUS BAR SECTION IS
UTILIZED; ALTHOUGH NOT RECOMMENDED, REDUCE 3/8" BOLT TORQUE TO 15 FT
LBS IN LIEU OF 20 FT LBS SPECIFIED IN NOTE 8. UTILIZE (1) HOLE COMPRESSION
LUGS (ITEM 16) ON THE TRANSITION BOX END OF THE 5KV/15KV JUMPER
CABLES. SEE ONE LINE DIAGRAM IN THIS DRAWING.
11. INSTALL TERMINATION KIT (ITEM 8) AT EACH END OF LS5KVTSSGUSHR-250
CABLING. SEE ONE LINE DIAGRAM AND DETAIL 39D IN THIS DRAWING.
(+) = WHT AND GRN
(-) = BLK AND RED
NAVAL SURFACE WARFARE CENTER, PHILADELPHIA DIVISION
PHILADELPHIA, PA 19112-5083
TECH REVIEW
PROG MGR
NOTES (CONTINUED):
12. BOLT EACH PHASE OF 350MCM 5KV/15KV JUMPER CABLE TO EACH PHASE OF
LS5KVTSSGUSHR-250 CABLE AFTER PREPARING CABLE ENDS AS DESCRIBED IN
NOTE 10 AND 11. INSULATE EACH PHASE OF BOLTED CONNECTIONS USING MOTOR
CONNECTION KIT (ITEM 9) SEE ONE LINE DIAGRAM IN THIS DRAWING AND DETAIL
39D.
13. EACH JUMPER CABLE (3-1C-350MCM, 5KV/15KV) SHALL HAVE ITS 3 PHASES AND
GROUND CONDUCTOR INSTALLED IN (1) OF (4) CONDUIT NIPPLES BETWEEN THE
HVSP TERMINAL BOX AND HVSP TRANSITION BOX. THE CONDUIT NIPPLES WERE
PREVIOUSLY INSTALLED PER REFERENCE 3. SEE ONE LINE DIAGRAM IN THIS
DRAWING.
14. CKT 6SCB6-40P-HVSPTRANSB SHALL ENTER TOP OF 6S SWBD AND TOP OF
HVSP TRANSITION BOX VIA STUFFING TUBE AND PACKING ASSEMBLY (ITEMS 13,
14). SEE ONE LINE DIAGRAM, PCM CABLE ROUTING DETAIL AND DETAIL 39D IN
THIS DRAWING.
15. CKT HVSPTRANSB-40P-PCM2 SHALL ENTER TOP OF HVSP TRANSITION BOX VIA
STUFFING TUBE AND PACKING ASSEMBLY (ITEMS 13, 14) AND LEFT REAR OF
PCM1 USING MCT INSERT BLOCK ITEMS (19, 20, 21). 2ND 250MCM CABLE IS NOT
BEING USED SO FILL SPARE 120 MM BLOCK WITH ITEM 22. SEE ONE LINE
DIAGRAM, PCM CABLE ROUTING DETAIL AND DETAIL 39D IN THIS DRAWING.
16. NEW CKT PCM1-10P-3BB1S (CABLE TYPE LS4OW-200) AND NEW CKT
PCM2-10P-3BB1P (CABLE TYPE LS4OW-200) SHALL ENTER TOP OF BREAKOUT
BOXES 3BB1S &3BB1P VIA EXISTING STUFFING TUBES THAT ARE ALREADY
INSTALLED AT BREAKOUT BOXES AND NEW PACKING ASSEMBLIES (ITEM 31) .
THESE CABLES WILL ENTER RIGHT REAR OF PCM'S USING MCT INSERT BLOCK
(ITEM 23). SEE ONE LINE DIAGRAM, PCM CABLE ROUTING DETAIL AND DETAIL 39D
IN THIS DRAWING.
17. CKT 6SCB8-40P-PCM1 SHALL ENTER TOP OF 6S SWBD VIA STUFFING TUBE AND
PACKING ASSEMBLY (ITEMS 13, 14) AND LEFT REAR OF PCM1 USING MCT INSERT
BLOCK ITEMS (19, 20, 21). 2ND 250MCM CABLE IS NOT BEING USED SO FILL
SPARE 120 MM BLOCK WITH ITEM 22. SEE ONE LINE DIAGRAM, PCM CABLE
ROUTING DETAIL AND DETAIL 39D IN THIS DRAWING.
18. LS5KVTSSGUSHR-250R CABLE HAS A MINIMUM PULLING BEND RADIUS OF 26.5”
AND A MIMIMUM PERMANENT TRAINING REQUIREMENT OF 17.5”. THE EXISTING
TRAY BEING UTILIZED IN THIS AREA HAS 24” RADIUS FITTINGS SO CARE MUST
BE TAKEN WHEN INSTALLING CABLE.
19. SHIELDED 1000VDC FOUR CONDUCTOR 200MCM CABLE HAS A MINIMUM PULLING
BEND RADIUS OF 23” WHILE THE UNSHIELDED 200MCM TYPE CABLE HAS A
MINIMUM PULLING BEND RADIUS OF 11”.
20. PROVIDE FIELD SUPPORT OF CABLES IF NECESSARY IN VICINITY OF EQUIPMENT
CABINETS.
21. CUT TRAY RUNGS IF NECESSARY TO ACCOMMODATE CABLE PASSAGE TO
EQUIPMENT SO THAT CABLES DO NOT VIOLATE MINIMUM BEND RADIUS
REQUIREMENTS.
22. DO NOT ROUTE 4160V CIRCUITS IN SAME TRAY SECTIONS AS WHERE 1000VDC
AND OTHER LOWER VOLTAGE CIRCUITS ARE ROUTED.
23. VERIFY EXISTING TRAY SPLICE PLATES ARE WRENCH TIGHT TO PROVIDE
CONTINUOUS TRAY CONTINUITY FOR GROUNDING PURPOSES BETWEEN POWER
SOURCE AND LOADS. INSTALL 250MCM JUMPERS BETWEEN EQUIPMENT GND
TERMINAL AND TRAY RAIL TO PROVIDE COMPLETE GROUNDING CIRCUIT
CONTINUITY AS SHOWN IN THE PCM EQUIPMENT GROUNDING SCHEMATIC DETAIL
28A.
24. INSTALL GROUND BUS (ITEM 28) TO REAR OF HVSP TRANSITION BOX USING
GROUND BAR MOUNTING BRACKET (ITEM 29) USING 3/8 INCH DIAMETER GRADE 5
CARBON STEEL BOLTING HARDWARE INCLUDING 2 FLAT WASHERS AND
LOCKWASHER AT EACH BOLTING LOCATION. REMOVE PAINT AND DIRT FROM ANY
SURFACES IN CONTACT WITH THE GROUND BAR BRACKET OR BUS BAR. APPLY
ANTIOXIDANT JOINT COMPOUND ITEM (30) AT EACH BRACKET TO CABINET OR
BUS BAR TO BRACKET CONTACT LOCATION PRIOR TO BOLTING COMPONENTS
TOGETHER AND WIPING ANY EXCESS JOINT COMPOUND AWAY AFTER TIGHTENING
BOLTS. DRILL BUS BAR AS REQUIRED FOR POWER CIRCUIT GROUNDING
CONDUCTOR (ITEM 24) TERMINATION WITH BOLTED LUG (ITEM 25). ALSO
TERMINATE NAVY CABLE SHIELD TO GROUND BUS.
25. ALL POWER CABLE SHIELDS MUST BE TERMINATED TO EQUIPMENT'S GROUNDING
SYSTEM AT EACH END USING EMCT'S OR GROUND CLAMPS AND BRAID.
26. ALL ITEMS REFERRED TO IN THESE NOTES CAN BE FOUND IN THE LIST OF
MATERIALS IN THIS DRAWING.
3 FLT III HV SHORE POWER FDN ARRANGEMENT AND DETAILS EHQ10891
4 FLT III PCM 1, 2, AND MPU FDN ARRANGEMENT AND DET EHQ10874
5 FLT III PCM 1, 2 INSTALLATION EHQ10940
8/1/16
6 LS5KVTSSGUSHR CABLE TERMINATION PROCEDURE NOTE 28
NOTES (CONTINUED):
27. GROUND CONNECTIONS FOR PCM'S ARE APPROXIMATELY 24" FROM TOP OF TEE
BLOCK. GROUNDING SYSTEM FOR TEST SITE AS WELL AS POWER CABLES FOR
TEST SITE ARE SUPPLIED FROM ABOVE TRAY. THE GROUND CABLE TO PCM'S
REQUIRES PROPER SUPPORT TO ITS GND TERMINALS. RECOMMEND TO REMOVE
SHOCK MOUNTS PER ELEVATION VIEW 28A. INSTALL 3" X 3" X 1/4" THICK
ANGLE (ITEM 1) IN ITS PLACE USING 3/4" BOLTING HARDWARE THAT CAME WITH
SHOCK MOUNTS. BOLT GROUND CONNECTOR (ITEM 48) TO 3" ANGLE TO PROVIDE
REQUIRED SUPPORT FOR GROUND CABLE DOWN TO GROUND CONNECTION ON PCM.
ALSO BOND PCM TO TEE BLOCK AS SHOWN IN ELEVATION 28A. BONDING TO
THE BLOCK SHALL UTILIZE A BOLTED CONNECTION PER PCM BONDING PLATE
DETAIL 23C.
28. NSWCPD TO PROVIDE NAVY APPROVED LS5KVTSSGUSHR CABLE TERMINATION
PROCEDURE TO INSTALLER FOR USE WITH ITEM 8.
29. NSWCPD TO VERIFY LATEST PROGRAM REQUIREMENTS FOR PCM ELECTRICAL
CONNECTION HARDWARE PRIOR TO PURCHASE AND INSTALLATION.
30. MATERIAL ITEMS 19, 20, 21, 22, 23, AND 49 SHALL BE UTILIZED AS REQUIRED TO
SUPPLEMENT MCT MATERIAL PROVIDED BY MANUFACTURER. SEE DETAILS 36A
AND 34A IN THIS DRAWING.
D N. Silva 12/13/16
L. Skarbek for A. Cairns 12/19/16
1. INCREASED MATERIAL QUANTITY FOR ITEMS
10 & 11 FROM 500 FT TO 3000 FT EACH DUE
TO MANUFACTURER MINIMUM PURCHASE
REQUIREMENTS.
SH 4 A 1/10/17 TECH REVIEW
T. Checchio
1/10/17 PROG MGR
A. Cairns
1. ADDED CABLE TESTING REQUIREMENT
(NOTE 32 & 33) PER NSWCPD INSTRUCTION.
2. UPDATED MATERIAL LIST INCLUDING
IDENTIFICATION OF ANY ITEMS THAT ARE
NOW GOVERNMENT FURNISHED (GFM).
3. UPDATED 6SCB6 AND 6SCB8 BREAKER
SETTINGS.
SH 1,
SH 2,
SH 4,
SH 5
B 3/24/17 TECH REVIEW
N. Silva
3/26/17 PROG MGR
A. Cairns
1. INCORPORATED USACE COMMENTS OF
4/14/17 AND 4/18/17.
PREPARED: D MERLINO 4/28/17
CHECKED: R CHRANOWSKI 5/1/17
PROJ MGR: M LAMBERTO 5/1/17
ALL C
NOTES (CONTINUED):
31. CLEAN ALL ELECTRICAL CONTACT SURFACES OF THE TEE BLOCK AND PCM
BONDING PLATE PRIOR TO APPLYING ANTIOXIDANT JOINT COMPOUND (ITEM 30)
AND BOLTING TOGETHER PER DETAIL 23C. REMOVE EXCESS ANTIOXIDANT JOINT
COMPOUND AFTER TIGHTENING.
NOTES (CONTINUED ON SHT 2):
5/1/17 TECH REVIEW
T. Checchio
5/2/17 PROG MGR
A. Cairns
1. INCORPORATED NSWCPD MATERIAL LIST
COMMENTS OF 5/22/17.
PREPARED: R.S. FOX 5/23/17
CHECKED: R. CHRANOWSKI 5/23/17
PROJ MGR: M. LAMBERTO 5/23/17
ALL D
5/23/17 TECH REVIEW
T. Checchio
5/23/17 PROG MGR
L. Skarbek for A. Cairns
FLT III PCM CABLE ROUTING
AND ISOMETRIC VIEW
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 2
89256D EHQ10939
D
C
B
A
D
C
B
A
910111213141516
910111213141516
ISOMETRIC VIEW 10B
LOOKING NORTHWEST
DDG 51 FLIGHT III PCM AREA
SCALE: NONE
PLAN VIEW 14A
DDG 51 FLIGHT III PCM CABLE ROUTING
SCALE: 3/16"=1'-0"
PCM 1
(SEE REF 2 AND 3)
PCM 2
(SEE REF 2 AND 3)
20'20'20'
POWER CONVERSION
CONTROL ROOM
POWER CABLE TRAY
10'-1" ABV TEE BLOCK
FLOOR PAD
POWER CONVERSION SITE
TEE BLOCK SLOTTED FLOOR PAD
8-1/2" ABV CONCRETE PAD
POWER CONVERSION
UPPER LEVEL
10'-4" ABV CONCRETE PAD
NORTH
FUTURE
MPDU 1
24 252322
B
HV SHORE POWER
TERMINAL BOX
(SEE REF 1)
HV SHORE POWER
TRANSITION BOX
(SEE REF 1)
HV SHORE POWER
TERMINAL BOX
HV SHORE POWER
TRANSITION BOX
POWER CONVERSION
UPPER LEVEL
10'-4" ABV CONCRETE PAD
POWER CONVERSION
CONTROL ROOM
CABLE TRAY
SUPPORT STRUCTURE
10'-1" ABV TEE BLOCK
SLOTTED FLOOR PADPCM 1
PCM 2
FUTURE
MPDU 1
(FRONT)
(FRONT)(FRONT)
(SEE NOTE 22)
(SEE NOTE 22)
3BB1P
3BB1S
EXISTING 4160V CABLE TRAY
6S SWBD, CB6 & CB8
WITH 200 AMP
SENSOR
6SCB6-40P-HVSPTRANSB
(1) LS5KVTSSGUSHR-250
(SEE NOTE 14)
6SCB8-40P-PCM1
(1) LS5KVTSSGUSHR-250
(SEE NOTE 17)
PCM2-10P-3BB1P
(4) LS4OW-200
(SEE NOTE 16)
HVTRANSB-40P-PCM2
(1) LS5KVTSSGUSHR-250
(SEE NOTE 15)
PCM1-10P-3BB1S
(4) LS4OW-200
3BB1S-10P-DCJB1 CABLES SHALL BE LEFT IN PLACE DURING INSTALLATION OF PCM1-10P-3BB1S. CABLES OTHER
THAN 3BB1S-10P-DCJB1 SHALL BE REMOVED FROM 3BB1S & TRAY PRIOR TO INSTALLATION OF
PCM1-10P-3BB1S.
(NOTE 16)
GRAPHIC SCALE 3/16"=1'-0"
0 1' 2' 3' 4' 5' 10' 15' 20'
EXTRA CABLE LENGTH IS PROVIDED TO PCM'S
TO FACILITATE FUTURE HOOK-UP TO LCPCM'S
VERIFY ONLY 4160V CABLES ARE INSTALLED IN
4160V TRAY AREAS OR INSTALL METAL TRAY
BARRIER. APPLIES TO ALL AREAS.
1' SEPARATION OR ADD TRAY BARRIER
CAP UNUSED CONDUITS
WITH A PIPE CAP TO
PREVENT DEBRIS ENTRY.
D
NOTES (CONTINUED FROM LEFT):
33. TEST 1000VDC POWER CABLES AFTER PULLING AND TERMINATING, BUT PRIOR
TO CONNECTION TO EQUIPMENT AS FOLLOWS:
A. PERFORM VISUAL AND MECHANICAL INSPECTION OF CABLES IN SIMILAR
FASHION AS MEDIUM VOLTAGE CABLES IN NOTE 32 ON SHEET 1.
B. PERFORM 1000VDC INSULATION RESISTANCE TEST AND VERIFICATION OF
SHIELD AND CONDUCTOR CONDUCTIVITY IN ACCORDANCE WITH
INSTRUCTION PROVIDED BY NSWCPD.
C. INSTALLER SHALL PROVIDE TEST REPORT AND NOTIFY NSWCPD PRIOR
TO MAKING ANY REQUIRED REPAIRS FREE OF CHARGE AS STATED IN
NOTE 32 ON SHEET 1 FOR MEDIUM VOLTAGE CABLES.
NOTES (CONTINUED FROM SHEET 1):
32. UPON COMPLETION OF THE INSTALLATION, THE CONTRACTOR/INSTALLER SHALL
NOT CONNECT/TORQUE CABLE TERMINATIONS TO THE BUS BAR UNTIL
ELECTRICAL TESTING IS COMPLETE. CONTRACTOR/INSTALLER SHALL SECURE THE
SERVICES OF A QUALIFIED, INDEPENDENT TESTING FIRM TO CONDUCT TESTING OF
ALL MEDIUM-VOLTAGE CABLE, INCLUDING TERMINATIONS, AS PART OF THE
ELECTRICAL ACCEPTANCE TEST PHASE. THE TESTING SHALL BE IN ACCORDANCE
WITH ANSI/NETA ATS 2013-ACCEPTANCE TESTING SPECIFICATIONS FOR
ELECTRICAL POWER EQUIPMENT AND SYSTEMS PARAGRAPHS:
-SECTION 7.3.3 CABLES MEDIUM AND HIGH VOLTAGE. SECTION 7.3.3.1. VISUAL
AND MECHANICAL INSPECTION PERFORM ALL TESTS IN PARAGRAPH 7.3.3.1
EXCEPT FOR PARAGRAPHS 7.3.3.1.3.3 THERMOGRAPHIC SURVEY AND 7.3.3.1.7
FIREPROOFING.
-SECTION 7.3.3.2 ELECTRICAL TESTS, PERFORM ALL TESTS IN PARAGRAPHS 1
THROUGH 3. PERFORM PARAGRAPH 7.3.3.2.4.1.2 (VLF DIELECTRIC) AND
7.3.3.2.4.2.2 (DC INSULATION RESISTANCE).
-UTILIZE TEST VALUES IAW SECTION 7.3.3.3.1 AND 7.3.3.3.2 AS APPLICABLE
OR NSWCPD PROVIDED INFORMATION.
-FOR TESTS IN SECTION 7.3.3.2. ALL CABLES SHALL BE TESTED IN PLACE
WITH ALL TERMINATIONS MADE UP BUT NOT CONNECTED TO EQUIPMENT. IN
CASE OF FAILURE DURING ANY OF THE ELECTRICAL TESTS, THE INSTALLER
SHALL LOCATE THE FAILED COMPONENT, FAULTY TERMINATION, OR CABLE
SECTION AND NOTIFY NSWCPD BEFORE MAKING ANY REPAIRS. THE TESTING
FIRM SHALL SUBMIT TO NSWCPD COPIES OF ALL TEST REPORTS FOR
REVIEW. SHOULD THE TEST REPORTS INDICATE THAT THE CONDITION OF THE
NEW CABLE IS UNSATISFACTORY, THE INSTALLER SHALL MAKE ALL
REPAIRS AND/OR REPLACEMENTS TO THE SATISFACTION OF AND NO
ADDITIONAL COST TO NSWCPD.
(NOTES CONTINUED ON RIGHT)
FLT III PCM 4160V/1000VDC ONE
LINE DIAG & PCM BONDING PL
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 3
89256D EHQ10939
D
C
B
A
D
C
B
A
LB2
2000KW
DCJB2
DCJB1
LB1
2000KW
(4) LSFSGU-200
(DCJB2-S)-10DC-LB1
(4) LSFSGU-200
DCJB1-10DC-(DCJB2-S)
(4) LSFSGU-200
(DCJB2-P)-10DC-LB2 (4) LSFSGU-200
DCJB1-10DC-(DCJB2-P)
PORT
STBD
(3BB1S)-1000 VDC
(3BB1P)-1000 VDC
AFT CC
(5) LSFSGS-200
INTERNAL CABINET
JUMPERS (TYPICAL)
3BB1S-10P-LB1
(5) LSFSGS-200
3BB1P-10P-DCJB1
6SCB6-40P-HVSPTRANSB
(1) LS5KVTSSGUSHR-250
(SEE NOTES 11, 14)
6SCB8-40P-PCM2
(1) LS5KVTSSGUSHR-250
(SEE NOTES 11, 17)
PCM1-10P-3BB1S
(4) LS4OW-200
(SEE NOTE 16)
HVTRANSB-40P-PCM2
(1) LS5KVTSSGUSHR-250
(SEE NOTES 11, 15)
PCM2-10P-3BB1P
(4) LS4OW-200
(NOTE 16)
3-1C-350MCM 5/15KV
UNSHIELDED JUMPER CABLE
(SEE NOTES 10, 13)
FLT III PCM 2
6S SWBD
4160VAC
6S SWBD
4160VAC
FLT III PCM 1
4160VAC, 3ɸ, 218A INPUT
1000VDC, 1415A OUTPUT
4160VAC, 3ɸ, 218A INPUT
1000VDC, 1415A OUTPUT
HVSP TERMINAL BOX
4160VAC, 3ɸ, 1000A
HVSP TRANSITION
BOX
BOLTED LUG CABLE
CONNECTIONS
(SEE NOTE 12)
MAIN BUS
CB8
(200AS, NOTE 9)
MAIN BUS
CB6
(200AS, NOTE 9)
1718192021222324
1718192021222324
BUS BAR
1000VDC
1000VDC
D
PLAN VIEW 23C
PCM BONDING PLATE
SCALE: NONE
(SEE NOTE 6 FOR ITEMS IN THIS DETAIL
NOT HAVING AN ITEM NUMBER)
∅1" STEEL TEE BLOCK BOLT WITH FLAT
WASHER, LOCK WASHER, AND NUT
(ITEMS 51, 52, 53) TO SECURE BONDING
PLATE TO TEE BLOCK.
(REMOVE EXCESS BOLT THREADS ABOVE
NUT TO PREVENT TRIP HAZARD)
TO PCM GND PAD/TERMS
(SEE ELEV VIEW 28A)
250 MCM COPPER (ITEM 24)
CABLE LUG (ITEM 25) WITH GRADE 5
STEEL BOLT, LOCKWASHER, FLAT
WASHER, AND NUT TO SECURE LUG
TO PLATE (ROTATE LUG IF DESIRED)
SEE NOTES 27 AND 31
ASTM A36 STEEL BONDING PLATE,
3"x 5"x1/4" THICK (ITEM 50)
TEE BLOCK SLOT
FLT III PCM CABLE INSTALLATION
MATERIAL LIST AND DETAILS
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 4
89256D EHQ10939
D
C
B
A
D
C
B
A
LIST OF MATERIAL
ITEM QTY DESCRIPTION MATERIAL SPECIFICATION REMARKS
LF
ANGLE, 3"x3"x1/4" THICK CARBON STEEL ASTM A36 CUT TO SUIT
2 9
BREAKOUT BOOT, 4 WAY, CABLE END MAX = 2.35"
WITH SHRINK TO 1.00" MIN, CONDUCTOR LEGS MAX =
1.00" WITH SHRINK TO .35" MIN
POLYOLEFIN DOD-STD-2003-1 (GFM)
ROLL
TUBING, SHRINKABLE FIT, 1.0" MAX TO .5" MIN WITH
SHRINK, -55°C TO 135°C, BLACK 50' ROLL
X LINK
POLYOLEFIN
MIL-DTL-23053/5 (GFM)
ROLL
TUBING, SHRINKABLE FIT, 1.0" MAX TO .5" MIN WITH
SHRINK, -55°C TO 135°C, WHITE 50' ROLL
X LINK
POLYOLEFIN
MIL-DTL-23053/5 (GFM)
5 4 STUFFING TUBE PLUG, SIZE 8 NEOPRENE MIL-S-19622
NSN 5975-00-296-3857.
USE IF REQUIRED TO SEAL ANY UNUSED
CABLE ENTRIES INTO ENCLOSURE (GFM)
6 4 STUFFING TUBE PLUG, SIZE 4 NEOPRENE MIL-S-19622
NSN 5975-00-296-3861.
USE IF REQUIRED TO SEAL ANY UNUSED
CABLE ENTRIES INTO ENCLOSURE. (GFM)
7 2
TORQUE SEAL, TAMPER PROOF MARKER, -20°F TO 450°,
.5 OZ TUBE, ORANGE, MADE FOR MARKING
ELECTRICAL BOLTED CONNECTIONS 120-4160V AND
COMPATABLE WITH VARIOUS METAL SURFACES
SUCH AS COPPER, TIN PLATED COPPER,
ZINC PLATED CARBON STEEL, AND SILICON BRONZE
VARIOUS COMMERCIAL
8 7
TERMINATION KIT, 8KV MARINE HIGH VOLTAGE, 3
PHASES, FOR USE WITH 250MCM 5KV CABLE ITEM 10
VARIOUS
MARINE HIGH
VOLTAGE
TYCO CAT# MHHT-8KV-2-3-0-G
VERIFY PART # WITH NSWCPD PRIOR TO
PURCHASE. INCLUDES 1 SPARE.
SOLE SOURCE PROCUREMENT REQUIRED
TO MIMIC / SUPPORT LEAD YARD
INSTALLATION PROCESS
9 3
MOTOR CONNECTION KIT, 5KV, 300-1000MCM CABLE
RANGE, 3 PHASES, 1.5" MAX BOLT LENGTH WITH USE
OF SINGLE HOLE LUG, MAX CONNECTION LENGTH 7.0"
VARIOUS COMMERCIAL
TYCO CAT# MICK-5-2L
INCLUDES 1 SPARE.
SOLE SOURCE PROCUREMENT REQUIRED
TO MIMIC / SUPPORT LEAD YARD
INSTALLATION PROCESS
10 500 FT
CABLE, LS5KVTSSGUSHR-250, 3C-250MCM COPPER, 5KV
SILICONE RUBBER INSULATION, OVERALL SHIELD &
JACKET, OD= 2.30"
VARIOUS MIL-DTL-24643 (GFM)
11 500 FT
CABLE, LS40W-200, 4C-200MCM COPPER, 1000V
TERMOSET INSULATION, OVERALL JACKET, CABLE
RANGE OD = 1.885"-1.984"
VARIOUS
MIL-DTL
24643/68A
(GFM)
ELEVATION VIEW 28A
PCM RELATED EQUIPMENT GROUNDING SCHEMATIC
SCALE: NONE
3BB1S
1000 VDC
6S SWBD
4160VAC PCM 1
4160VAC, 3ɸ, 218A INPUT
1000VDC, 1415A OUTPUT
PCM2
4160VAC, 3ɸ, 218A INPUT
1000VDC, 1415A OUTPUT
HVSP TERMINAL BOX
4160VAC, 3ɸ, 1000A
HVSP TRANSITION
BOX
1-1C-250MCM (TYPICAL)
(ITEM 24)
(SEE NOTE 23
EXISTING GND BUS
STUFFING TUBE AND
PACKING ASSEMBLY
(ITEMS 26/27)
GND BUS
(ITEMS 28, 29)
(SEE NOTE 24)
GND
ONLY ROUTE GND CONDUCTOR
THROUGH NIPPLES ALSO USED
FOR POWER CIRCUITS
2X GND TERMS
ITEM 18
STUFFING TUBE AND
PACKING ASSEMBLY
(ITEMS 26/27)
EXISTING
GND BUS
EXISTING OVERHEAD 4160VAC TRAY ADJACENT TO 6S SWBD
GROUND PATH FOLLOWS POWER CABLES
(SEE NOTE 23)
EXISTING OVERHEAD TRAY FOR 4160VAC AND 1000VDC CABLING TO PCMS
GROUND PATH FOLLOWS POWER CABLES
(SEE NOTE 23)
TIN PLATED COMPRESSION LUG (TYPICAL)
(ITEM 25) EXCEPT WHEN IDENTIFIED DIFFERENTLY (SEE NOTE 23)
17 6
CABLE COMPRESSION LUG, 1 HOLE
w/INSPECTION WINDOW, NAVY 250KCMIL, 1/2" STUD, SHORT BARREL, TIN PLATED, 35kV 90° C, STD CHAMFERED BARREL, TIN PLATED COPPER, 2.67" LENGTH, UL LISTED, CSA CERTIFIED
TIN PLATED
COPPER
COMMERCIAL FOR USE AT HV SP TRANS BOX
18 20
CABLE COMPRESSION LUG, 2 HOLE
w/INSPECTION WINDOW, NAVY 250KCMIL, 3/8" STUD, SHORT BARREL, TIN PLATED, 35kV 90° C, STD CHAMFERED BARREL, TIN PLATED COPPER, 2.67" LENGTH, UL LISTED, CSA CERTIFIED
TIN PLATED
COPPER
COMMERCIAL
FOR USE AT PCM1&2 FOR INPUT &
GNDING CABLES ALSO USE AT 6S SWBD.
19 2
MCT EMC BLOCK, ADJUSTABLE BLOCK TYPE FOR 90MM
BLOCK & CABLE RANGE OF 49.5 TO 69.5MM.
LYCRON & COPPER COMMERCIAL
MCT BRATTBERG CAT# E90/49-69.
SOLE SOURCE PROCUREMENT REQUIRED FOR
MCT BRATTBERG COMPATIBILITY WITH GFE
PCM. FOR USE WITH PCM 250MCM CABLES.
2526272829303132
2526272829303132
GND
REMOVE SHOCK MOUNTS
AND INSTALL 3" ANGLE
AND GROUND CONNECTOR
TO SUPPORT VERTICAL
CABLES SEE NOTE 27 (TYP)
TEE BLOCK
DETAIL 23C
GND
TEE BLOCK
DETAIL 23C 3BB1P
1000 VDC
STUFFING TUBE AND
PACKING ASSEMBLY
(ITEMS 26/27)
EXISTING
GND BUS
2X GND TERMS
ITEM 18
D
LIST OF MATERIAL
ITEM QTY DESCRIPTION MATERIAL SPECIFICATION REMARKS
12 120 FT
JUMPER CABLE, HIGHLY FLEXIBLE, ROPE STRANDED,
ANNEALED UNCOATED COPPER. CONDUCTOR SHIELD
HAS A NYLON SEMI CONDUCTING TAPE. CABLE
IS INSULATED WITH HEAT, MOISTURE, AND
OZONE RESISTANT ETHYLENE PROPYLENE RUBBER,
MEETS ICEA S-96-659
VARIOUS COMMERCIAL
13 4 STUFFING TUBE, SIZE 9, 2.006" TO 2.700" CABLE RANGE NYLON MIL-S-19622
USE AT 6S SWBD & HVSP TRANS BOX
(GFM)
14 4
SIZE 9B2 PACKING ASSEMBLY, 2.295" - 2.364" CABLE
RANGE
VARIOUS MIL-S-19622
USE AT 6S SWBD & HVSP TRANS BOX
(GFM)
15 6
CABLE COMPRESSION LUG, 2 HOLE
w/INSPECTION WINDOW, 350MCM FLEX, 3/8" STUD, 1" STUD HOLE SPACING, SHORT BARREL, TIN - ELECTRO PLATED FOR 3/8" BOLT, 35kV 90° C, STD CHAMFERED BARREL, TIN PLATED COPPER, 3.88" LENGTH, UL LISTED, CSA CERTIFIED
TIN PLATED
COPPER
COMMERCIAL FOR USE AT HV SP TERM BOX
16 6
CABLE COMPRESSION LUG, 1 HOLE
w/INSPECTION WINDOW, 350MCM FLEX, 1/2" STUD, SHORT BARREL, TIN PLATED, 35kV 90° C, STD CHAMFERED BARREL, TIN PLATED COPPER, 3.12" LENGTH, UL LISTED, CSA CERTIFIED
TIN PLATED
COPPER
COMMERCIAL FOR USE AT HV SP TRANS BOX
LIST OF MATERIAL CONTINUED ON SHEET 5
FLT III PCM CABLE INSTALLATION
MATERIAL LIST AND DETAILS
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 5
89256D EHQ10939
D
C
B
A
D
C
B
A
LIST OF MATERIAL CONTINUED ON SHEET 6
DET 39D: EQUIPMENT CONNECTION HARDWARE TABLE
EQUIPMENT ITEM# DESCRIPTION
QTY PER
CONNECTION
QTY PER THREE
PHASE
QTY PER
EQUIPMENT
QTY PER (4) DC
CONNECTIONS (PER
EQUIPMENT)
REMARKS
HVSP TERMINAL
BOX
3/8-16 SILICON BRONZE BOLT (1-1/2"
LONG)
2 6 12
36 3/8" SILICON BRONZE FLAT WASHER 4 12 24
37 3/8" SILICON BRONZE LOCK WASHER 2 6 12
38 3/8" SILICON BRONZE NUT 2 6 12
2 HOLE 350MCM FLEX COND LUG WITH
3/8" HOLES
1 3 6
HVSP TRANSITION
BOX
1/2"-13 SILICON BRONZE BOLT (1-1/4")
LONG
1 3 6
40 1/2" SILICON BRONZE FLAT WASHER 2 6 12
41 3/8" SILICON BRONZE LOCK WASHER 1 3 6
42 1/2" SILICON BRONZE NUT 1 3 6
1 HOLE 250MCM NAVY COND LUG WITH
1/2" HOLE
1 3 3
1 HOLE 350MCM FLEX COND LUG WITH
1/2" HOLE
1 3 3
9 MOTOR CONNECTION KIT 1 3 3
8 (3) PHASE 250MCM TERMINATION KIT 1/3 1 2
6S SWBD (EACH
BKR)
3/8-16 SILICON BRONZE BOLT (2.0"
LONG)
2 6 6
36 3/8" SILICON BRONZE FLAT WASHER 4 12 12
37 3/8" SILICON BRONZE LOCK WASHER 2 6 6
38 3/8" SILICON BRONZE NUT 2 6 6
2 HOLE 250MCM NAVY COND LUG WITH
3/8" HOLES
1 3 3
8 (3) PHASE 250MCM TERMINATION KIT 1/3 1 1
PCM INPUT (EACH)
3/8-16 ZINC PLATED CARBON STEEL
BOLT (XX" LONG)
2 6 6 NOTE 29
3/8" ZINC PLATED CARBON STEEL
FLAT WASHER
4 12 12
45 3/8" ZINC PLATED LOCK NUT 2 6 6
2 HOLE 250MCM NAVY COND LUG WITH
3/8" HOLES
1 3 3
8 (3) PHASE 250MCM TERMINATION KIT 1/3 1 1
PCM OUTPUT
(EACH)
3/8-16 ZINC PLATED CARBON STEEL
BOLT (XX" LONG)
2 32 NOTE 29
3/8" ZINC PLATED CARBON STEEL
FLAT WASHER
4 64 NOTE 29
45 3/8" ZINC PLATED LOCK NUT 2 32 NOTE 29
2 HOLE NAVY 200MCM COND LUG WITH
3/8" HOLES
1 16 NOTE 29
2 BREAKOUT BOOT 4
3, 4 WHITE & BLACK SHRINK TUBE AS REQD AS REQD
BREAKOUT BOXES
3BB1P & 3BB1S
(EACH)
N/A
3/8-16 SILICON BRONZE BOLT (XX"
LONG)
1 16
REUTILIZE
EXISTING
N/A 3/8" SLICON BRONZE FLAT WASHER 2 32
REUTILIZE
EXISTING
N/A 3/8" SILICON BRONZE LOCK WASHER 1 16
REUTILIZE
EXISTING
N/A 3/8" SILICON BRONZE NUT 1 16
REUTILIZE
EXISTING
1 HOLE 4/0 NAVY COND LUG WITH
3/8" HOLE
1 16
2 BREAKOUT BOOT 4
46 SPRING CLAMP FOR GROUNDING 4
47 BRAID FOR GROUND CLAMP 4
3, 4 WHITE & BLACK SHRINK TUBE AS REQD AS REQD
3334353637383940
3334353637383940
DETAIL 36A
PCM MCT DETAILS (INPUT CABLES)
SCALE: NONE
STAYPLATE
PRESS WEDGE
E120/0
E90/49-69
STAYPLATE
STAYPLATE (PROVIDED
BY THIS DRAWING
120MM
280MM
NOTES:
1. MCT BLOCKS PROVIDED BY THIS DRAWING.
2. MCT FRAME, PRESS WEDGE, AND 2 OF 3 STAYPLATES
ARE PROVIDED BY PCM MANUFACTURER.
3. PRESS WEDGE UTILIZES 40MM IN HEIGHT OF MCT.
DETAIL 34A
PCM MCT DETAILS (OUTPUT CABLES)
SCALE: NONE
STAYPLATE
PRESS WEDGE
STAYPLATE
120MM
280MM
NOTES:
1. E60/* BLOCK REPRESENTS EITHER A E60/48 OR E60/50
BLOCK PROVIDED BY THIS DRAWING PENDING
INFORMATION ON CABLE DIAMETER.
2. MCT FRAME, PRESS WEDGE, E60/0 BLOCKS, AND
STAYPLATES ARE PROVIDED BY PCM MANUFACTURER.
3. PRESS WEDGE UTILIZES 40MM IN HEIGHT OF MCT.
STAYPLATE
STAYPLATE
E60/* E60/0
E60/* E60/0
E60/* E60/0
E60/* E60/0
D
23 16
MCT EMC BLOCK FOR 60MM BLOCK & CABLE RANGE OF
1.870"-1.949"
LYCRON & COPPER COMMERCIAL
MCT BRATTBERG CAT# E60/48. FOR USE
WITH PCM 200MCM 1000V CABLES IF CABLE
RANGE IS CORRECT. ALTERNATE PART IS
ITEM 49. SOLE SOURCE PROCUREMENT
REQUIRED FOR MCT BRATTBERG
COMPATABILITY WITH GFE PCM.
24 125 FT
CABLE, 250MCM, THHN/THWN, 600V BUILDING WIRE,
STRANDED COPPER CONDUCTOR, 0.69" OD
VARIOUS COMMERCIAL
25 24
CABLE LUG, (ONE HOLE CODE), I HOLE
w/INSPECTION WINDOW, NON INSULATED, 250 KCMIL
CODE, 250 NAVY, 600V-35kV, 1/2" STUD, LONG, YELLOW, COMPRESSION, 0.52" BCD, 90° C, SKIVED
BARREL, TIN PLATED COPPER, 3.23" LENGTH, UL
LISTED, CSA CERTIFIED
TIN PLATED
COPPER
COMMERCIAL FOR USE WITH GROUNDING CIRCUITS
20 2 MCT STAYPLATE STAINLESS STEEL COMMERCIAL
MCT BRATTBERG CAT# STAYPLATE SS.
USE BETWEEN NEW 90MM BLOCKS AND
ROW OF (4 ) 30MM BLOCKS WHICH
REPLACES ORIGINAL PLANNED 120MM
BLOCK. SOLE SOURCE PROCUREMENT
REQUIRED FOR MCT BRATTBERG
COMPATABILITY WITH GFE PCM.
LIST OF MATERIAL
ITEM QTY DESCRIPTION MATERIAL SPECIFICATION REMARKS
21 14 MCT EMC BLOCK, SPARE BLOCK TYPE E30/0 LYCRON & COPPER COMMERCIAL
MCT BRATTBERG CAT# E30/0.
SOLE SOURCE PROCUREMENT REQUIRED FOR
MCT BRATTBERG COMPATABILITY WITH GFE
PCM. FOR USE WITH PCM 250MCM CABLES.
22 2 MCT EMC BLOCK, SPARE BLOCK TYPE E120/0 LYCRON & COPPER COMMERCIAL
MCT BRATTBERG CAT# E120/0.
SOLE SOURCE PROCUREMENT REQUIRED FOR
MCT BRATTBERG COMPATABILITY WITH GFE
PCM. FOR USE WHERE 2ND PCM 250MCM
CABLE WAS ELIMINATED.
DWG NO.CAGE CODESIZE REV
SCALE : AS NOTED SHEET 6
89256D EHQ10939
D
C
B
A
D
C
B
A
D
FLT III PCM CABLE INSTALLATION
MATERIAL LIST
39 6 BOLT, 1-1/4" LONG, 1/2" DIAMETER-13 SILICON BRONZE ASTM B99
40 12 FLAT WASHER, 1/2" SILICON BRONZE ASTM B99
41 6 LOCKWASHER, 1/2" SILICON BRONZE ASTM B99
42 6 HEX NUT, 1/2" DIAMETER-13 SILICON BRONZE ASTM B99
43 76 BOLT, XX" LONG, 3/8" DIAMETER-16
GRADE 5 CARBON
STEEL
MIL-DTL-1222J (GFM)
44 152 FLAT WASHER, 3/8"
GRADE 5 CARBON
STEEL
MIL-DTL-1222J
45 76 LOCKNUT, 3/8"
GRADE 5 CARBON
STEEL
MIL-DTL-1222J
46 9
GROUND CLAMP, SPRING TYPE, 1.0-2.0" USE RANGE,
FOR SECURING BRAIDS WHEN SPLICING
OR TERMINATING POWER CABLES
STAINLESS STEEL COMMERCIAL INCLUDES (1) SPARE.
47 9 GROUND BRAID, #6AWG, 60" TINNED COPPER COMMERCIAL INCLUDES (1) SPARE.
48 4
GROUND CONNECTOR, 2/0-250MCM,
MECHANICAL GROUNDING CONNECTOR,
CABLE TO 1/4" THICK BAR, 2/0 AWG (SOL)-250 KCMIL,
1/2" STUD, 2" WIDTH
COPPER ALLOY COMMERCIAL (GFM)
49 16
MCT EMC BLOCK FOR 60MM BLOCK & CABLE RANGE OF
1.949"-2.028"
LYCRON &
COPPER
COMMERCIAL
MCT BRATBERG CAT No. E60/50.
USE WITH 200MCM 1000V CABLE AT PCM'S
IF CABLE RANGE IS CORRECT. ALTERNATE
PART IS ITEM 23.
SOLE SOURCE PROCUREMENT REQUIRED
FOR MCT BRATTBERG COMPATABILITY
WITH GFE PCM.
50 2 STEEL PLATE, 3"x5"x1/4" THICK STEEL ASTM A36
51 2 TEE SLOT BOLT, 1"-8 UNC-2A, 4" LONG HSS COMMERCIAL
52 2 FLAT WASHER, WIDE, ∅1" STEEL COMMERCIAL
53 2 NUT, 1"-8 UNC-2B STEEL COMMERCIAL
34 12 BOLT, 1-1/2" LONG, 3/8" DIAMETER-16 SILICON BRONZE ASTM B99
35 12 BOLT, 2" LONG, 3/8" DIAMETER-16 SILICON BRONZE ASTM B99
36 48 FLAT WASHER, 3/8" SILICON BRONZE ASTM B99
37 24 LOCKWASHER, 3/8" SILICON BRONZE ASTM B99
38 24 HEX NUT, 3/8" DIAMETER-16 SILICON BRONZE ASTM B99
30 2
ANTIOXIDANT JOINT COMPOUND, 4 OZ TUBE, USE FOR
GROUNDING CONNECTIONS (COPPER TO ALUMINUM,
COPPER TO STEEL, ALL CONNECTIONS TO UNPLATED
COPPER BAR)
VARIOUS COMMERCIAL
31 8
PACKING ASSEMBLY, SIZE 8B4, 1.94" - 2.00" CABLE
RANGE
VARIOUS MIL-S-19622
USE AT 3BB1S AND 3BB1P WITH
EXISTING STIUFFING TUBES. (GFM)
32 32
COPPER COMPRESSION LUG, BEVEL ENTRY, 2 HOLE
w/INSPECTION WINDOW, 4/0 AWG CODE, 200 NAVY, 600V-35kV, 3/8" STUD, 1.00" SPACING, LONG
SKIVED BARREL, PURPLE, FOR USE IN GROUNDING
CIRCUITS, 90° C, TIN PLATED COPPER, 3.99" LENGTH,
UL LISTED, CSA CERTIFIED
TIN PLATED
COPPER
COMMERCIAL FOR USE USE AT PCM1 AND 2 OUTPUT
33 32
COPPER COMPRESSION LUG, 1 HOLE
w/INSPECTION WINDOW, 4/0 AWG CODE, 200 NAVY, 3/8" STUD, LONG BARREL, TIN PLATED, SKIVED BARREL
ENTRY, PURPLE, FOR USE IN GROUNDING CIRCUITS,
600V-35kV, 90° C, TIN PLATED COPPER, 2.95" LENGTH, UL LISTED, CSA CERTIFIED
TIN PLATED
COPPER
COMMERCIAL FOR USE USE AT 3BB1S AND 3BB1P
LIST OF MATERIAL
ITEM QTY DESCRIPTION MATERIAL SPECIFICATION REMARKS
4142434445464748
4142434445464748
26 5 STUFFING TUBE, SIZE 4, .450" - .777" CABLE RANGE NYLON MIL-S-19622 (GFM)
27 5
PACKING ASSEMBLY, SIZE 4F, .669" - .719" CABLE
RANGE
VARIOUS MIL-S-19622 (GFM)
28 1
COPPER BUS, C110 ALLOY, 1/4" THICK, 2" WIDE X 24"
LONG
COPPER COMMERCIAL
29 2
BUS BAR MOUNTING BRACKET, (3) 7/16" HOLES
FOR USE WITH 3/8" HARDWARE. RAISED BRACKET
FOR SECURING GROUIND BUS APPROXIMATELY 1.5"
OFF CABINET WALL. SINGLE HOLE FOR BUS BAR
MOUNTING AND 2 HOLES FOR SECURING BRACKET TO
CABINET. MINIMUM .125" THICK CONDUCTIVE
STAINLESS STEEL HAVING WIDTH OF 1.5" TO 2".
STAINLESS STEEL COMMERCIAL
| EHQ10939-01 |
| EHQ10939-02 |
| EHQ10939-03 |
| EHQ10939-04 |
| EHQ10939-05 |
| EHQ10939-06 |