This document package includes drawings and specifications for a federal construction project. The solicitation is for a consolidated Helo/TRF Ops/AMU and Alert Facility to be constructed at FE Warren Air Force Base in Wyoming. The project involves construction of a new facility as well as associated site work and utilities. The drawings provide details for partition layouts, mechanical systems, electrical systems and site plans. Specifications cover requirements for partition types, mechanical equipment, electrical panels and feeders. The solicitation is issued by the Department of the Army Corps of Engineers Omaha District. Responses are due based on the specified solicitation number and issuing agency.

View the file

Other files

Show all 31

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECOND DIGIT IS THE

'SIZE INDICATOR'

THIRD DIGIT IS THE

PARTITION 'RATING'

"LINE OF STRUCTURE" INDICATED FOR EACH

PARTITION IS DIAGRAMMATIC ONLY AND DOES NOT

INDICATE EXACT CONSTRUCTION CONDITIONS OR

GEOMETRY. REFER TO FOR DETAILS ON THIS SHEET

FOR TYPICAL CONNECTION DETAILS.

DO NOT ATTACH METAL STUD TO THE TOP SLIP TRACK.

GYPSUM BOARD:

1. FIRE RESISTANT RATED PARTITIONS SHALL

USE TYPE "X" FIRE RATED GYPSUM BOARD.

2. PARTITIONS IN HIGH MOISTURE AREAS SHALL

USE MOISTURE RESISTANT GYPSUM BOARD

WHICH INCLUDE TOILET ROOM(S), LOCKER

ROOM(S),JANITOR CLOSET(S) AND WITHIN 4'-0"

OF WATER FOUNTAIN.

3. PARTITIONS BEHIND TOILETS, FIXTURES AND

WITHIN SHOWER AREAS SHALL USE CEMENT

BOARD WITH A MOISTURE BARRIER.

4. DO NOT ATTACH GYPSUM BOARD TO THE TOP

SLIP TRACK.

5. ALL GYPSUM BOARD LOCATED IN CORRIDORS,

CONFERENCE ROOMS, TRAINING ROOMS,

BREAK ROOMS, STORAGE ROOMS, SUPPLY

ROOMS, VENDING ROOMS, AND RECYCLE

ROOMS SHALL BE ABUSE RESISTANT TO 8'-0"

A.F.F. ALL GYPSUM BOARD LOCATED IN SHOPS

AND IN TRF AREAS SHALL BE IMPACT

RESISTANT TO 10'-0" A.F.F.

6. ALL CEILINGS LOCATED IN RESTROOMS SHALL

USE MOISTURE RESISTANT GYPSUM BOARD.

SEALANT:

1. FIRE RESISTANT RATED PARTITIONS SHALL USE

FIRE STOP SEALANT SYSTEM.

2. NON - RATED PARTITIONS AND SMOKE RATED

PARTITIONS SHALL USE ACOUSTICAL

SEALANT.FIRE RESISTANT RATED PARTITIONS

SHALL NOT USE ACOUSTICAL SEALANT.

INSULATION - HEAD CONDITION AT STRUCTURE

ABOVE:

1. FIRE RATED RESISTANT PARTITIONS SHALL USE

FIRE SAFING INSULATION.

2. NON - RATED PARTITIONS SHALL USE SOUND

ATTENUATION BLANKET.

FIRE AND / OR SMOKE RESISTANT ARE TO

SURROUND ALL OPENINGS IN RATED PARTITIONS.

FIRE AND / OR SMOKE RESISTANT PARTITIONS

SHALL EXTEND TO INSIDE FACE OF EXTERIOR

SHEATHING,INCLUDING EXTENSIONS THROUGH

SOFFITS.

EACH PARTITION INDICATED TO BE FIRE

AND/OR SMOKE RESISTANT SHALL BE

IDENTIFIED AS SUCH WITH A LABEL ABOVE

THE CEILING ON EACH SEGMENT OF WALL AT

8'-0" ON CENTER. INCLUDE LETTERING NOT

LESS THAN 3 INCHES IN HEIGHT AWITH A

MINIMUM 3/8 INCH STROKE IN A CONTRASTING

COLOR INCORPORATING THE SUGGESTED

WORDING, "FIRE AND/OR SMOKE BARRIER -

PROTECT ALL OPENINGS"

INSTALL HORIZONTAL STUD FRAMING BRACING AT 4'-

0" ON CENTER AT FURRING AND NON-RATED CHASE

WALLS

FIRST DIGIT IS THE

PARTITION 'TYPE'

A

B

C.

A3-2

GENERAL SHEET NOTES

PARTITION TYPES

D.

E.

F.

G.

H.

I. STC RATING IS BASED ON A MIN METAL STUD SIZE

OF 3 5/8".

J.

K.

L.

M.

ALL STUDS ARE 16" ON CENTER UNLESS OTHERWISE

NOTED.

ALL STUDS ARE MINIMUM 22 GAUGE.

REFER TO FLOOR PLANS FOR LOCATION OF

PARTITION TYPE TAGS.

CEILING AS SCHED

METAL STUD FRAMING

SOUND ATTENUATION

INSULATION - RATING 'A'

LINE OF STRUCTURE

ABOVE

D

A

3 5/8"

4"

6"

8"

NO RATING-NO INSULATION

ACOUSTICAL

4 7/8"

5 1/4"

7 1/4"

9 1/4"

SOUND ATTENTUATION

INSULATION TO 4'-0"

EACH SIDE - RATING 'A'

(1) LAYER OF GYP BD

ON EACH SIDE, TO 4 "

ABOVE CEILING

METAL TRACK

BETWEEN BRACING

F

2 1/2"

3 5/8"

4"

6"

8"

NO RATING-NO INSULATION

3 1/8"

4 1/4"

4 5/8"

6 5/8"

8 5/8"

CONT EVERY OTHER

MTL STUD TO STRUCT

2 2 1/2" 3 3/4"

CEILING AS SCHED

METAL STUD FRAMING

SOUND ATTENUATION

INSULATION - RATING 'A'

LINE OF STRUCTURE

ABOVE

WIDTH

SOUND ATTENTUATION

INSULATION TO 4'-0" ON

ONE SIDE - RATING 'A'

(1) LAYER OF GYP BD

ON ONE SIDE, TO

4 " ABOVE CEILING

METAL TRACK

BETWEEN BRACING

CONT EVERY OTHER

MTL STUD TO STRUCT

A ACOUSTICAL

H

A

S

3 5/8"

4"

6"

NO RATING-NO INSULATION

ACOUSTICAL

SMOKE

2'-0"

2'-0"

2'-0"

LINE OF STRUCTURE

ABOVE

CEILING AS SCHED

METAL STUD FRAMING

SOUND ATTENUATION

INSULATION-RATING 'A'

FINISH FLOOR

(1) LAYER OF GYP BD

ON EACH SIDE REFER

TO GENERAL NOTES

WIDTH

1'-0" HIGH WATER

RESISTANT GYP BD

BRACE AT 4'-0" OC

VERT, FASTEN 3

PLACES TO EA STUD

2'-0" WIDE

R A

T

IN

G S

IZ

E

IN

D

IC

A T

O R

T Y

P E

IND STUD SIZE TOTAL WIDTH

A

A

S

2 1/2"

3 5/8"

4"

6"

8"

NO RATING-NO INSULATION

1 HR FIRE RATED UL# U419

ACOUSTICAL - STC 45

SMOKE

3 3/4"

4 7/8"

5 1/4"

7 1/4"

9 1/4"

LINE OF STRUCTURE

ABOVE

CEILING AS SCHED

METAL STUD FRAMING

SOUND ATTENUATION

INSULATION - RATING 'A'

FINISH FLOOR

(1) LAYER OF GYP BD

ON EACH SIDE

WIDTH

R A

T

IN

G S

IC

A T

O R

T Y

P E

IND STUD SIZE TOTAL WIDTH

WIDTH

R A

T

IN

G S

IC

A T

O R

T Y

P E

IND STUD SIZE TOTAL WIDTH

R A

T

IN

G S

IC

A T

O R

T Y

P E

IND STUD SIZE TOTAL WIDTH

P

1 HR FIRE RATED BASED

UPON U905

1 16 1/4"

R A

T

IN

G S

IC

A T

O R

T Y

P E

IND CMU SIZE TOTAL WIDTH

R

8 8"

NO RATING-NO INSULATION

11 1/8"

R A

T

IN

G S

IC

A T

O R

T Y

P E

IND CONCRETE

WALL SIZE

TOTAL WIDTH

NO RATING-NO INSULATION

1* 3 5/8" 4 1/4"

R A

T

IN

G S

IC

A T

O R

T Y

P E

IND WALL SIZE TOTAL WIDTH

LINE OF STRUCTURE

ABOVE

CEILING AS SCHED

ROOM SIDE

2 1/2" METAL STUD

FRAMING

FINISH FLOOR

(1) LAYER OF GYP BD

ABUSE RESISTANT

CAST-IN-PLACE

CONCRETE CEILING

REFER STRUCTURAL

CAST-IN-PLACE

CONCRETE WALL

REFER STRUCTURAL

WIDTH

VAULT

SIDE

LINE OF STRUCTURE

ABOVE

CEILING AS SCHED

FINISH FLOOR

8" GIRTS AT MASONRY

WAINSCOT

3 5/8" METAL STUD

INFILL BETWEEN

GIRTS

5/8" TYPE "X" GYP BD

TO 6" ABOVE CEILING

8" GIRT; REFER

STRUCTURAL

LINE OF STRUCTURE

ABOVE

CMU BOND BEAM;

REFER STRUCTURAL

2" RIGID INSULATION

CMU BACKUP

2" Z FURRING WITH

5/8" TYPE "X" GYPSUM

BOARD

FINISH FLOOR

11 5/8"

S

3 5/8" METAL STUD INFILL

WITHIN GIRT SPACE

N. PROVIDE PAINTED FINISH TO 1'-0" ABOVE CEILING AT

GYPSUM BOARD SIDE OF WALL TYPE P1-1; TAPING,

FLOATING AND FINISHING OF GYPSUM BOARD NOT

REQUIRED FROM 1'-0" ABOVE CEILING TO DECK ABOVE

ASSEMBLY

MINIMUM R VALUE

T

1 HR FIRE U415 SYSTEM A

2 3 1/8"

R A

T

IN

G S

IC

A T

O R

T Y

P E

IND STUD SIZE TOTAL WIDTH

1" GYP BD LINER

PANEL

GYP BD ON ONE SIDE

C-H METAL STUD

FRAMING

FINISH FLOOR

2 1/2"

LINE OF STRUCTURE

ABOVE

U

1 7 5/8" 7 5/8"

R A

T

IN

G S

IC

A T

O R

T Y

P E

IND CMU SIZE TOTAL WIDTH

LINE OF

STRUCTURE

ABOVE

CMU BOND

BEAM; REFER

STRUCTURAL

CMU

FINISH FLOOR

1 HR FIRE RATED BASED

UPON U905

R A

T

IN

G S

IC

A T

O R

T Y

P E

IND STUD SIZE TOTAL WIDTH

M

A

S

2 1/2"

3 5/8"

4"

6"

8"

NO RATING-NO INSULATION

1 HR FIRE RATED UL# U419

ACOUSTICAL - STC 50

SMOKE

4 3/8"

5 1/2"

5 7/8"

7 7/8"

9 7/8"

LINE OF STRUCTURE

ABOVE

CEILING AS SCHED

METAL STUD FRAMING

SOUND ATTENUATION

INSULATION - RATING 'A'

FINISH FLOOR

(2) LAYER OF GYP BD

WIDTH

(1) LAYER OF GYP BD

2 11 5/8" 11 5/8"

R O

O M

S

ID

E

1 HR FIRE U415 SYSTEM B2

ACOUSTICAL - STC 47A

S H

A F

T S

ID

E WIDTH

6 6 5/8"6"

1 7/8" 1 1/2"

N

2 1/2"

3 5/8"

6"

NO RATING-NO INSULATION

3 3/4"

4 7/8"

7 1/4"

CEILING AS SCHED

METAL STUD FRAMING

SOUND ATTENUATION

INSULATION - RATING 'A'

LINE OF STRUCTURE

ABOVE

WIDTH

(2) LAYERS OF GYP BD

ON ONE SIDE

A ACOUSTICAL

R A

T

IN

G S

IC

A T

O R

T Y

P E

IND STUD SIZE TOTAL WIDTH

1 7/8" 2 1/8"

FILL VOIDS BETWEEN MTL

DECK & PLATE WITH SPRAY

FOAM OR BATT INSULATION-

COVER COMPLETELY WITH

1" SEALANT

COMPRESSIBLE

INSULATION

STEEL ROOF OR

FLOOR DECK

SEAL BETWEEN

PLATE AND DECK AT

EACH SIDE

SEALANT WITH BOND

BREAKER TAPE

TOP RUNNER

CAPTURED WITHIN

DEEP LEG TRACK

CONT 18 GAGE X 3"

LEG TRACK,

ANCHOR TO DECK

WITH S-12 SCREWS

AT 12" OC

STAGGERED

PERPENDICULAR TO METAL

DECK FLUTES

PARALLEL TO METAL

DECK FLUTES

DO NOT ATTACH

GYP BD OR STUDS

TO TOP TRACK

PROVIDE

UL SYSTEMS

HW-D-0042

AT ALL 1 HR RATED

PARTITIONS

REFER TO

GENERAL NOTES

FOR SEALANT AND

INSULATION TYPES

GYP BD PARTITION

AS SCHED

GALV U-SHAPED

STEEL CASING

ACOUSTICAL SEALANT

AND BACKER ROD

METAL STUD

GYP BD PARTITION

AS SCHED

/8

FLR FIN AS

SCHED

GYP BD

PARTITION AS

SCHED

SEALANT AND

BACKER ROD, REF:

GENERAL NOTES

METAL STUD

BASE AS SCHED

ZINC CONTROL JOINT

AT BOTH SIDES

METAL STUD

GYP BD PARTITION

AS SCHED

/2

ZINC CONTROL JOINT

AT BOTH SIDES

2 LAYERS OF

5/8" GYP BD

METAL STUD

GYP BD PARTITION

AS SCHED

/8

/8

/8

BACKER ROD

AND SEALANT

CERAMIC FIBER

BLANKET

BOND BREAKER

SEALANT

P A

N E

L T

H

IC

K N

E S

S

JOINT WIDTH

FIRE SIDE

VERTICAL

NOTE: PROVIDE RATED JOINT ASSEMBLY IN

PRECAST UTILIZING FIBER FELT PER DEFERRED

DESIGN. COORDINATE JOINT DESIGN WITH

RATING REQUIREMENT.

R E

G

IS

T

ERED ARCH

IT

E

C T

S T

A T E

O F T EX

A S

C H

R I S

T

O

PHER M

S U

R L

E S

2 3 6 3 8

US Army Corps of Engineers Omaha District ®

SHEET

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D x

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

D R

A W

IN

G

C O

D E

A F

-1

-0

-W F

R

M

A R

C H

C H

O F

F F

IL

E

N A

M E

O M

A H

A D

IS

T

R

IC

T

O M

A H

A

N E

B R

A S

K A

F Y

H

E L

O /T

R F

/M A

IN

T

E N

A N

C E

F A

C

IL

IT

Y

P R

O J E

C T

N U

M B

E R

G

H L

N A

F E

W A

R R

E N

A F

B

W Y

J A

C O

B S

E N

G

IN

E E

R

IN

G G

R O

U P

I N

C

M a in

S tr e e t

F o rt

W o rt h

T X

READY-TO-ADVERTISE (RTA) DESIGN

A-601

P A

R T

IT

IO

N T

Y P

E S

C S

U R

L E

S

T R

IC

E

N V

IG

L

IO

T

T A

F E

-G

H L

N

A A

-6

3" = 1'-0"A1

TYP TOP OF GYP BD WALL CONX

3" = 1'-0"B3

TYP WALL-WALL CONX

3" = 1'-0"A3

TYP BOTTOM OF

WALL CONX

3" = 1'-0"B5

TYP CONTROL JOINT

3" = 1'-0"A5

TYP 1 HR RATED

CONTROL JOINT

N.T.S.A7

RATED

PRECAST JOINT

A

M

R E

V

IS

IO

N

S

-2

-2

09/21/2021

P

1'2' A4

M-302

GF-1

CU-4

CU-3

CU-8

UH-1

M

M

M

ACU-2

ACU-1

6" EQUIPMENT PAD

SHALL EXTEND A

MINIMUM OF 6" ON ALL

SIDES OF UNIT. REFER

TO STRUCTURAL FOR

DETAIL

6" EQUIPMENT PAD

SHALL EXTEND A

MINIMUM OF 6" ON ALL

SIDES OF UNIT. REFER

TO STRUCTURAL FOR

DETAIL

8"Ø BOILER COMBUSTION

AIR INLET. (TYP. 3)

6"Ø WATER HEATER VENT.

(TYP. 2)

8"Ø BOILER COMBUSTION

AIR INLET. (TYP. 2)

L.4

L

K.5

J

WELD (NOTE 6)

ANCHOR BOLTS, 2 AT

EACH PLATE. MIN.

SIZE 5/8"

STRUCTURAL

CHANNEL

OR ANGLES

2"x2"x1/4"

3/8" BASE PLATE

PIPE & INSULATION

3/8" PLATE CUT TO SUIT

PIPE DIA. AND

INSULATION THICKNESS

NOTE: INSULATE ANCHOR AS INDICATED FOR COLD PIPING.

1/2" U-BOLT

INSULATION

STRUCTURE

UNISTRUT CHANNEL

U-BOLT

PIPE (TYP.)

INSULATION (TYP.)

PROVIDE SLEEVE TO PROTECT INSULATION

PIPE GUIDE - 2-1/2" AND SMALLER

PIPE ANCHOR - 2-1/2" AND SMALLER

PROVIDE SWAY BRACING

PIPE

U-BOLT

PIPE GUIDE - 3" AND LARGER

PIPE

PIPE

PIPE ANCHOR - 3" AND LARGER

NOTE 4

(TYP.)

1/4"

1/4"

1/4"

1/4"

(TYP.)

(TYP.)

(TYP.)

NOTE 6

NOTE 6

NOTE 6

NOTE 6

SUPPORT

STEEL

SUPPORT STEEL

NOTES:

1. SEE PIPING DRAWINGS FOR SUPPORT LOCATIONS.

2. VERIFY ALL ELEVATIONS PRIOR TO FABRICATION.

3. FINAL PIPE SUPPORT, GUIDE, ANCHOR, AND SUPPORT STEEL

DESIGN AND SELECTION IS DELEGATED DESIGN. DETERMINE

LOADING ON GUIDES, ANCHORS AND SUPPORTS PRIOR TO

COMPONENT SELECTION AND INSTALLATION.

4. CONTRACTOR TO SELECT OR DESIGN PIPE SUPPORTS FOR

DESIGN LOADS.

5. SUBMIT FINAL PIPE LAYOUT WITH MECHANICAL STRESS ANALYSIS

AND STATE COMPLIANCE WITH ASME B31.1.

6. CONTRACTOR TO DETERMINE WELD TYPE, THICKNESS AND

WELDING SPECIFICATION PER DESIGN LOADS FROM STRUCTURAL

DRAWINGS.

7. FORCES TRANSFERRED TO THE STRUCTURE MUST BE SUBMITTED

FOR APPROVAL TO THE STRUCTURAL DOR.

(TYP.)

1/8"

02 4 8134

SCALE: 1/4"=1'-0"

BRODIE B. B. HEFLIN

OF TEXASS

TATE

ALNOI

SS

E

F O

R P

ENG

IN

E E

R

NSEDECI

L 106046

TRUE NORTH

US Army Corps of Engineers Omaha District ®

SHEET

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D x

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

D R

A W

IN

G

C O

D E

A F

-1

-0

-W F

R

M

A R

C H

C H

O F

F F

IL

E

N A

M E

O M

A H

A D

IS

T

R

A H

A

N E

B R

A S

K A

F Y

H

E L

O /T

R F

/M A

IN

T

E N

A N

C E

F A

C

IL

IT

Y

P R

O J E

C T

N U

M B

E R

G

H L

N A

F E

W A

R R

E N

A F

B

W Y

J A

C O

B S

E N

G

IN

E E

R

IN

G G

R O

U P

I N

C

M a in

S tr e e t

F o rt

W o rt h

T X

READY-TO-ADVERTISE (RTA) DESIGN

TEXAS REGISTERED

ENGINEERING FIRM F-2966

M-403

H V

A C

E N

L A

R G

E D

P L A

N S

B B

S /R

C

B B

S /R

C

B H

F E

-G

H L N

A M

-4

1/4" = 1'-0"A6

MECHANICAL YARD - ENLARGED PLAN

GENERAL NOTES - HVAC PLANS

A MAINTAIN MANUFACTURER'S RECOMMENDED

CLEARANCES ON ALL EQUIPMENT.

B PROVIDE CLEARANCES FOR ALL ELECTRICAL AND

CONTROL PANELS PER NEC.

C PROVIDE BRACING FOR EQUIPMENT WEIGHING MORE

THAN 31 LBS PER UFC 4-010-01.

D COORDINATE THERMOSTATS WITH FURNISHINGS.

LOCATE THERMOSTATS 6" ON CENTER FROM LIGHT

SWITCH. MOUNT TOP OF THERMOSTAT AS SHOWN AT

ADA APPROVED MOUNTING HEIGHT.

E PROVIDE U.L. RATED THROUGH-PENETRATION FIRE

STOP SYSTEMS AT ALL PENETRATIONS BETWEEN

THE HANGAR/SHOP DEMISING WALL.

F PROVIDE REMOTE DAMPER ACTUATORS OR ACCESS

PANEL FOR ALL DAMPERS LOCATED ABOVE HARD

CEILINGS.

G REFER TO PIPING PLAN FOR THERMOSTAT

ASSIGNMENT

H PROVIDE BALANCING DAMPER AT EACH TAKEOFF

I ALL MITERED ELBOWS HAVE TURNING VANES

J LOCATE TOP OF HVLS FAN CONTROL PANEL AT 4FT

AFF

A

M

R E

V

IS

IO

N

-2

-2

NTSA1

TYPICAL PIPE GUIDE AND ANCHOR

��
��

�0

2�

2�

#4

2�

"8�������9��

�1

�0

�8�� ���1������;���+� +��0� ����1���� 1����

�8�� ���1������;���+� +��0� �����"�1����

9/30/2021

2000 AF

2000 AT

3P

LSIG

NSB, 2000 A, 480/277 V

3 P, 4 W, 60 HZ, 65 KAIC

RM166

1200 AF

1200 AT

3P

LSIG

400 AF

3P

NHD1, 400 A, 480/277 V

3 P, 4 W, 60 HZ, 22 KAIC

RM 155

400 AF

400 AT

3P

LSI

400 4

N G

100 AF

50 AT

3P

100 AF

100 AT

3P

100 4

100 AF

50 AT

3P

NHL11

PANEL

RM 166

NLP11

PANEL

RM 166

480:208/120 V 30 kVA, Z~3.0%

T-NP11

RM 166

NLP12

PANEL

RM 137

480:208/120 V 30 kVA, Z~3.0%

T-NP12

RM 137

100 AF

50 AT

3P

100 AF

100 AT

3P

100 4

NHL13

PANEL

RM 155

NLP13

PANEL

RM 155

480:208/120 V 30 kVA, Z~3.0%

T-NP13

RM 155

100 AF

50 AT

3P

NHL21

PANEL

RM 228

480:208/120 V 75 kVA, Z~3.0%

T-NP21

RM 282

100 AF

100 AT

3P

100 4

NLP22A

PANEL

RM 228

480:208/120 V 75 kVA, Z~3.0%

T-NP22

RM 228

225 AF

125 AT

3P

480:208/120 V 30 kVA, Z~3.0%

T-NP14

RM 158

NLP14

PANEL

RM 158

NLP23

PANEL

RM 284

480:208/120 V 75 kVA, Z~3.0%

T-NP23

RM 284

RM 166

LCP11

RM 155

LCP13

RM 228

LCP21

225 AF

225 AT

3P

225 4

225 AF

225 AT

3P

225 4

NHH11

PANEL

RM 193

NHH12

PANEL

RM 193

NHH13

PANEL

RM 194

480:208/120 V 30 kVA, Z~3.0%

T-NH11

RM 193

NLH11

PANEL

RM 193

NLH12

PANEL

RM 193

NLH13

PANEL

RM 194

400 AF

400 AT

3P

400 4

480:208/120 V 30 kVA, Z~3.0%

T-NH12

RM 193

480:208/120 V 75 kVA, Z~3.0%

T-NH13

RM 194

400 AF

400 AT

3P

225 AF

125 AT

3P

225 AF

125 AT

3P

RM 166

RCP11

RM 284

RCP23

RM 158

RCP14

RM 155

RCP13

RM 137

RCP12

400 AF

400 AT

3P

400 4

100 AF

100 AT

3P

100 4

NHE15

PANEL

RM 189

NHL15

PANEL

RM 189

NLP15A

PANEL

RM 189

480:208/120 V

112.5 kVA, Z~3.0%

T-NP15

RM 189RM 189

LCP15

RM 189

RCP15B

400 AF

3P

400 AF

3P

NLP21A

PANEL

RM 282

NLP21B

PANEL

RM 282

NLP15B

PANEL

RM 189

225 4

100 4

DC11B

FC-12

250 AF

200 AT

3PREEL

CORD

REEL

CORD

REEL

CORD

RM 282

RCP21A

RM 282

RCP21B

NLP22B

PANEL

RM 228

100 4

RM 228

RCP22B

RM 228

RCP22A

OUTSIDE

ARMAG

100 3

DC11A DC12

FC-11

400 AF

300 AT

3P

300 4

NHSIM

PANEL

RM 162

NLSIM

PANEL

RM 162

480:208/120 V 30 kVA, Z~3.0%

T-NSIM

RM 162

SPD

60 AF

60 AT

3P

SPD

60 AF

60 AT

3P

TO FIRE PUMP TAP BOX

RE: SHEET A1/E-702

FEEDER BY HIGH

WEST ENERGY M

MSE

100% RATED

65 KAIC

TO HANGAR DOORS ECB 2O

VIA BY-PASS/ISOLATION ATS

RE: SHEET A1/E-702

T-HELO

13.8 KV:480/277 V

Z~5.75%

BY HIGH WEST ENERGY

T O

A T S -1

R E : A

1/E -702

S P A R

E

S P A R

E

S P A R

E

ECB 400HZ

400 HZ RATED

RM 189

400 HZ

RECEPTACLE

RM 189

234234234234234

240 240

#3/0

RE: D1/E-703

M

083 083

EPM EPM EPM EPM EPM EPM EPM EPM

US Army Corps of Engineers Omaha District ®

SHEET

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D x

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

D R

A W

IN

G

C O

D E

A F

-1

-0

-W F

R

M

A R

C H

C H

O F

F F

IL

E

N A

M E

O M

A H

A D

IS

T

R

A H

A

N E

B R

A S

K A

F Y

H

E L

O /T

R F

/M A

IN

T

E N

A N

C E

F A

C

IL

IT

Y

P R

O J E

C T

N U

M B

E R

G

H L

N A

F E

W A

R R

E N

A F

B

W Y

J A

C O

B S

E N

G

IN

E E

R

IN

G G

R O

U P

I N

C

M a in

S tr e e t

F o rt

W o rt h

T X

READY-TO-ADVERTISE (RTA) DESIGN

TEXAS REGISTERED

ENGINEERING FIRM F-2966

E-701

O N

E L

IN

E

D

IA

G R

A M

C T

R U

S S

E L L

C T

R U

S S

E L L

L .J

D

A V

IS

F E

-G

H L

N

A E

-7

GENERAL NOTES - ONE-LINE

E ONE-LINE DIAGRAMS DEPICT INTERCONNECTION OF

ELECTRICAL INFRASTRUCTURE. COORDINATE WITH

PANEL SCHEDULES FOR THE BALANCE OF ADDITIONAL

CONNECTIONS AND DEVICES.

F FOR DRY TYPE TRANSFORMERS WITH MULTIPLE FEEDS,

REFER TO PANEL SCHEDULES FOR PANEL MCB

BREAKER SIZING INFORMATION.

G PROVIDE EQUIPMENT WITH FULLY BUSSED SPACE FOR

FUTURE DEVICES.

H PROVIDE ALL OCPD RATED 1200 A AND GREATER WITH

ARC FLASH REDUCING MAINTENANCE BYPASS SWITCH.

GENERAL NOTES - ONE-LINE

A REFER TO SHEET E-001 FOR GENERAL NOTES, LEGEND,

AND ABBREVIATIONS.

B PROVIDE ARC FLASH WARNING SIGNS ON THE

SWITCHBOARDS, SWITCHGEAR, PANELBOARDS,

INDUSTRIAL CONTROL PANELS, METER SOCKET

ENCLOSURES, AND MOTOR CONTROL CENTERS AS

REQUIRED PER NFPA 70 (NEC) ARTICLE 110.16.

REFERENCE NFPA 70 ARTICLE 110.16; NFPA 70E

ARTICLE 130.3; AND UFC 3-560-01, ELECTRICAL SAFETY,

O & M.

C ALL BREAKERS 400A AND GREATER SHALL BE 100%

RATED.

D LCP AND SLCP REPRESENT SPACE ALLOCATED FOR

LIGHTING CONTROL PANELS. RCP REPRESENTS SPACE

ALLOCATED FOR RECEPTACLE CONTROL PANELS.

FEEDER SCHEDULE NOTES

A THIS SCHEDULE IS BASED ON INTERNAL AREA OF EMT,

RGS, OR SCHEDULE 40 PVC CONDUIT AND THE

AMPACITIES FOR EM OR CET INSULATION.

B FEEDER MARK " " INDICATES FEEDER RATING

AND NUMBER OF PHASE CONDUCTORS INCLUDING

NEUTRAL. PROVIDE GROUND AS INDICATED ON FEEDER

SCHEDULE.

C UNDERGROUND SERVICE ENTRANCE FEEDERS CONSIST

OF THREE PHASE WIRES AND NEUTRAL. NUMBER OF

CONDUCTORS PER PHASE ARE CALCULATED VALUES

BASED ON SPECIFIC DUCT BANK ARRANGEMENTS, LOAD

FACTORS, AND SOIL CONDITIONS.

D SECONDARY FEEDERS ARE AS SCHEDULED UON.

NTSA1

ONE-LINE DIAGRAM - NORMAL POWER

XXXXX

KEYNOTES

059 PROVIDE 8 SETS OF [4 - 500 KCMIL IN 6" C] + 2 SPARE 6"

C

083 200A DC RECTIFIER (BID OPTION 5).

084 45 KVA 400HZ FREQUENCY CONVERTER. PROVIDE 1 SET

OF 3#3, 1#8G IN 1-1/4"C. (BID OPTION 5)

085 90 KVA 400HZ FREQUENCY CONVERTER. PROVIDE 1 SET

OF 3#3/0, 1#6G IN 2-1/2"C. (BID OPTION 5)

234 PROVIDE K-RATED TRANSFORMER.

240 PROVIDE A JACKETED, PLANETARY WRAPPED CABLE

(SIX PHASE WIRES AROUND ONE NEUTRAL) WITH #2

PHASE CONDUCTORS AND INTEGRAL CONTROL

CONDUCTORS (BID OPTION).

265 PROVIDE AMRS METER.

288 PROVIDE 8 SETS OF [4 - 500 KCMIL, 1 - 250 KCMIL G IN 6"

C] + 2 SPARE 6" C

322 PROVIDE PERMANENT ENGRAVED PLACARD THAT SAYS

"SERVICE DISCONNECT 1 OF 3. SERVICE DISCONNECT 2

OF 3 LOCATED AT ATS-2 IN ELECTRICAL ROOM 166.

SERVICE DISCONNECT 3 OF 3 LOCATED AT FIRE PUMP

TAP BOX IN FIRE SUPPRESSION EQUIP ROOM 191.

STANDBY GENERATOR IS LOCATED OUTSIDE ELECRICAL

ROOM 166 ON SITE."

325 PROVIDE ELECTRONIC POWER METER TO ALLOW FOR

SUBMETERING PER SECTION 8.4.3.1 OF ASHRAE 90.1.

TYPICAL FOR ALL ELECTRONIC POWER METERS SHOWN

ON SHEET.

TRANSFORMER SCHEDULE

KVA

RATING

PRIMARY (480V) SECONDARY (208/120V)

GROUNDBREAKER FEEDER BREAKER FEEDER

15 30/3 3#10, #10G, IN 3/4" C 50/3 4#6, #8G, IN 3/4" C #8

30 50/3 3#6, #10G, IN 3/4" C 100/3 4#1, #6G, IN 1-1/4" C #6

45 70/3 3#4, #8G, IN 1" C 150/3 4#1/0, #6G, IN 2" C #4

75 125/3 3#1/0, #6G, IN 1-1/2" C 225/3 4#4/0, #2G, IN 2-1/2" C #2

112.5 175/3 3#2/0, #6G, IN 1-1/2" C 400/3 2 SETS OF 4#3/0, #1/0G, IN 2" C #2

150 300/3 3-350kcmil, #4G, IN 2-1/2" C 500/3 2 SETS OF 4-250kcmil, #1/0G, IN 2-1/2" C #1/0

FEEDER SCHEDULE

FEEDER

MARK

PHASE

&NEUTRAL GROUND # OF SET

CONDUIT SIZE

3C+G 4C+G 5C+G

15 12 12 1 3/4" 3/4" 3/4"

20 12 12 1 3/4" 3/4" 3/4"

30 10 10 1 3/4" 3/4" 3/4"

40 8 10 1 3/4" 3/4" 1"

50 6 10 1 3/4" 1" 1"

60 4 10 1 1" 1 1/4" 1 1/4"

70 4 8 1 1" 1 1/4" 1 1/4"

80 3 8 1 1 1/4" 1 1/4" 1 1/4"

90 2 8 1 1 1/4" 1 1/2" 1 1/2"

100 1 8 1 1 1/2" 1 1/2" 2"

110 1 6 1 1 1/2" 1 1/2" 2"

125 1 6 1 1 1/2" 2" 2"

150 1/0 6 1 1 1/2" 2" 2"

175 2/0 6 1 2" 2" 2 1/2"

200 3/0 6 1 2" 2 1/2" 2 1/2"

225 4/0 4 1 2" 2 1/2" 3"

250 250 4 1 2 1/2" 3" 3"

300 350 4 1 3" 3" 3 1/2"

350 500 2 1 3" 4" 4"

400 3/0 2 2 2" 2" 2 1/2"

450 4/0 2 2 2" 2 1/2" 3"

500 250 2 2 2 1/2" 3" 3"

600 350 1/0 2 3" 3" 3 1/2"

700 500 1/0 2 3" 4" 4"

800 300 1/0 3 2 1/2" 3" 3"

1000 400 2/0 3 3" 3" 3 1/2"

1200 350 3/0 4 3" 3" 3 1/2"

1600 400 4/0 5 3" 3 1/2" 3 1/2"

2000 500 500 6 3 1/2" 4" 4"

A

M

R E

V

IS

IO

N

-3

-2

N G

G

1250 KW GEN, 480/277 V,

3 P, 4 W, 60 HZ, 22 KAIC

OUTSIDE

2000 AF

1200 AT

3P

LSIG

1200 4

M

480V, 60 HZ

800A, 4P

FPC-2

700 4

M

480V, 60 HZ

800A, 4P

FPC-1

700 4 700 4700 4 700 4

480V, 60 HZ

2000A, 4P

ATS-1, RM 166

35 KAIC

1200 4

1200 4

1200 AF

1200 AT

3P

LSIG

600 AF

600 AT

3P

LSI

600 4

SSB (STANDBY SWITCHBOARD)

1200 A, 480/277 V

3 P, 4 W, 60 HZ, 35 KAIC

RM 166

SPD

60 AF

60 AT

3P

225 AF

125 AT

3P

LSI

SHH11

PANEL

RM 195

480:208/120 V 75 kVA, Z~3.0%

T-SD1

RM 158

SLC12

PANEL

RM 156

SLC21

PANEL

RM 283

SLP13

PANEL

RM 155

600 AF

600 AT

3P SHD1, 600 A, 480/277 V

3 P, 4 W, 60 HZ, 25 KAIC

RM 158

225 AF

125 AT

3P

SPD

60 AF

60 AT

3P

225 AF

225 AT

3P

225 4

100 AF

100 AT

3P

100 4

225 AF

225 AT

3P SLD1, 225 A, 208/120 V

3 P, 4 W, 60 HZ, 10 KAIC

RM 158

100 AF

100 AT

3P

100 4

100 AF

100 AT

3P

100 4

SPD

60 AF

60 AT

3P

100 AF

100 AT

3P

100 4

225 AF

150 AT

3P

150 4

SLC11

PANEL

RM 136

SHE11

PANEL

RM 196

480:208/120 V 75 kVA, Z~3.0%

T-SD2

RM 166

SLC13

PANEL

RM 163

SLC14

PANEL

RM 184

FA

PANEL

RM 191

225 AF

225 AT

3P SLD2, 225 A, 208/120 V

3 P, 4 W, 60 HZ, 10 KAIC

RM 166

100 AF

100 AT

3P

100 4

SPD

60 AF

60 AT

3P

100 AF

100 AT

3P

100 4

100 AF

70 AT

3P

SLC15

PANEL

RM 181

100 AF

100 AT

3P

100 4

480:208/120 V 30 kVA, Z~3.0%

T-SP11

RM 196

SLP11

PANEL

RM 196

225 AF

225 AT

3P

225 4

480:208/120 V 30 kVA, Z~3.0%

T-SP21

RM 228

SLP21

PANEL

RM 228

SHE13

PANEL

RM 158

100 AF

25 AT

3P

SLP14

PANEL

RM 193

225 AF

3P

225 AF

3P

FC

SLP22

PANEL

RM 211

100 AF

100 AT

3P

100 4

CCR1

FC

REEL

CORD

REEL

CORD

REEL

CORD

SLP15

PANEL

RM 155

225 AF

150 AT

3P

150 4

480:208/120 V 45 kVA, Z~3.0%

TFA

RM 191

CCR2

RM 155

SRCP15

250 AF

250 AT

3P

LSIG

250 4

SHHD1

PANEL

RM 193

480V, 60 HZ

250A, 4P

ATS-2, RM 166

18 KAIC

250 4

250 AF

250 AT

3P

225 AF

200 AT

3P

LSIG

200 4

225 AF

200 AT

3P SHL1, 200 A, 480/277 V

3 P, 4 W, 60 HZ, 14 KAIC

RM 166

100 AF

100 AT

3P

100 4

100 AF

100 AT

3P

100 4

SHL11

PANEL

RM 137RM 166

SLCP12 SHL12

PANEL

RM 166 RM 137

SLCP11

RM 228

SLCP21SHL21

PANEL

RM 228

2000 AF

1600 AT

3P

LSIG

700 4

1200 AF

1200 AT

3P

1200 4

225 AF

175 AT

3P

LSI

PORTABLE GENERATOR

CONNECTION / LOAD

BANK CABINET

1200 AF

1200 AT

3P

LSIG

1200 4

SPD

60 AF

60 AT

3P

#3/0

J

J

J

FOR RECEPTACLE

AND LIGHTING

FOR BATTERY

CHARGER

FOR WATER JACKET

HEATERS

J

SLD2:6

SLD2:24

SLD2:14,16

2#10, 1#10G

SLD2:26,28

2#10, 1#10G

TO SERVICE

TRANSFORMER.

RE: A1/E-701

FIRE PUMP

CONTROLLER WITH

INTEGRAL ATS FIRE PUMP 2FIRE PUMP 1

800 A TAP BOX

TO NSB

RE: A1/E-701

S P A R

E

S P A R

E

084234

234 234

240 240

BY-PASS/ISOLATION

AUTOMATIC

TRANSFER SWITCH

TO SERVICE

TRANSFORMER.

RE: A1/E-701

ECB 2O

RM 166

M

ECB 1E

RM 166

ELEV 1

RE: E-602 FOR FEEDER

INFORMATION

LOAD BANK

CONNECTION

TEMPORARY

GENERATOR

EPM EPM

US Army Corps of Engineers Omaha District ®

SHEET

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D x

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

D R

A W

IN

G

C O

D E

A F

-1

-0

-W F

R

M

A R

C H

C H

O F

F F

IL

E

N A

M E

O M

A H

A D

IS

T

R

A H

A

N E

B R

A S

K A

F Y

H

E L

O /T

R F

/M A

IN

T

E N

A N

C E

F A

C

IL

IT

Y

P R

O J E

C T

N U

M B

E R

G

H L

N A

F E

W A

R R

E N

A F

B

W Y

J A

C O

B S

E N

G

IN

E E

R

IN

G G

R O

U P

I N

C

M a in

S tr e e t

F o rt

W o rt h

T X

READY-TO-ADVERTISE (RTA) DESIGN

TEXAS REGISTERED

ENGINEERING FIRM F-2966

E-702

O N

E L

IN

E

D

IA

G R

A M

S T

A N

D B

Y

C T

R U

S S

E L L

C T

R U

S S

E L L

L .J

D

A V

IS

F E

-G

H L

N

A E

-7

GENERAL NOTES - ONE-LINE

E ONE-LINE DIAGRAMS DEPICT INTERCONNECTION OF

ELECTRICAL INFRASTRUCTURE. COORDINATE WITH

PANEL SCHEDULES FOR THE BALANCE OF ADDITIONAL

CONNECTIONS AND DEVICES.

F FOR DRY TYPE TRANSFORMERS WITH MULTIPLE FEEDS,

REFER TO PANEL SCHEDULES FOR PANEL MCB

BREAKER SIZING INFORMATION.

G PROVIDE EQUIPMENT WITH FULLY BUSSED SPACE FOR

FUTURE DEVICES.

H PROVIDE ALL OCPD RATED 1200 A AND GREATER WITH

ARC FLASH REDUCING MAINTENANCE BYPASS SWITCH.

GENERAL NOTES - ONE-LINE

A REFER TO SHEET E-001 FOR GENERAL NOTES, LEGEND,

AND ABBREVIATIONS.

B PROVIDE ARC FLASH WARNING SIGNS ON THE

SWITCHBOARDS, SWITCHGEAR, PANELBOARDS,

INDUSTRIAL CONTROL PANELS, METER SOCKET

ENCLOSURES, AND MOTOR CONTROL CENTERS AS

REQUIRED PER NFPA 70 (NEC) ARTICLE 110.16.

REFERENCE NFPA 70 ARTICLE 110.16; NFPA 70E

ARTICLE 130.3; AND UFC 3-560-01, ELECTRICAL SAFETY,

O & M.

C ALL BREAKERS 400A AND GREATER SHALL BE 100%

RATED.

D LCP AND SLCP REPRESENT SPACE ALLOCATED FOR

LIGHTING CONTROL PANELS. RCP REPRESENTS SPACE

ALLOCATED FOR RECEPTACLE CONTROL PANELS.

FEEDER SCHEDULE NOTES

A THIS SCHEDULE IS BASED ON INTERNAL AREA OF EMT,

RGS, OR SCHEDULE 40 PVC CONDUIT AND THE

AMPACITIES FOR EM OR CET INSULATION.

B FEEDER MARK " " INDICATES FEEDER RATING

AND NUMBER OF PHASE CONDUCTORS INCLUDING

NEUTRAL. PROVIDE GROUND AS INDICATED ON FEEDER

SCHEDULE.

C UNDERGROUND SERVICE ENTRANCE FEEDERS CONSIST

OF THREE PHASE WIRES AND NEUTRAL. NUMBER OF

CONDUCTORS PER PHASE ARE CALCULATED VALUES

BASED ON SPECIFIC DUCT BANK ARRANGEMENTS, LOAD

FACTORS, AND SOIL CONDITIONS.

D SECONDARY FEEDERS ARE AS SCHEDULED UON.

XXXXX

TRANSFORMER SCHEDULE

KVA

RATING

PRIMARY (480V) SECONDARY (208/120V)

GROUNDBREAKER FEEDER BREAKER FEEDER

15 30/3 3#10, #10G, IN 3/4" C 50/3 4#6, #8G, IN 3/4" C #8

30 50/3 3#6, #10G, IN 3/4" C 100/3 4#1, #6G, IN 1-1/4" C #6

45 70/3 3#4, #8G, IN 1" C 150/3 4#1/0, #6G, IN 2" C #4

75 125/3 3#1/0, #6G, IN 1-1/2" C 225/3 4#4/0, #2G, IN 2-1/2" C #2

112.5 175/3 3#2/0, #6G, IN 1-1/2" C 400/3 2 SETS OF 4#3/0, #1/0G, IN 2" C #2

150 300/3 3-350kcmil, #4G, IN 2-1/2" C 500/3 2 SETS OF 4-250kcmil, #1/0G, IN 2-1/2" C #1/0

KEYNOTES

084 45 KVA 400HZ FREQUENCY CONVERTER. PROVIDE 1 SET

OF 3#3, 1#8G IN 1-1/4"C. (BID OPTION 5)

085 90 KVA 400HZ FREQUENCY CONVERTER. PROVIDE 1 SET

OF 3#3/0, 1#6G IN 2-1/2"C. (BID OPTION 5)

227 PROVIDE A 15 KVA 24 POLE INTEGRATED POWER

CENTER WITH A 480V DELTA CONNECTION AND 208/120

WYE OUTPUT.

234 PROVIDE K-RATED TRANSFORMER.

237 COORDINATE INSTALLATION WITH FIRE ALARM

INSTALLER. PAINT PANELBOARD, BREAKER OPERATING

AND PADLOCKING MECHANISMS RED.

240 PROVIDE A JACKETED, PLANETARY WRAPPED CABLE

(SIX PHASE WIRES AROUND ONE NEUTRAL) WITH #2

PHASE CONDUCTORS AND INTEGRAL CONTROL

CONDUCTORS (BID OPTION).

265 PROVIDE AMRS METER.

289 PROVIDE COMMUNICATIONS WIRING IN CONDUIT TO

GENERATOR CONTROL PANEL.

323 PROVIDE PERMANENT ENGRAVED PLACARD THAT SAYS

"SERVICE DISCONNECT 2 OF 3. SERVICE DISCONNECT 1

OF 3 LOCATED AT MSE IN ELECRICAL ROOM 166.

SERVICE DISCONNECT 3 OF 3 LOCATED AT FIRE PUMP

TAP BOX IN FIRE SUPPRESSION EQUIP ROOM 191.

STANDBY GENERATOR IS LOCATED OUTSIDE ELECRICAL

ROOM 166 ON SITE."

324 PROVIDE PERMANENT ENGRAVED PLACARD THAT SAYS

"SERVICE DISCONNECT 3 OF 3. SERVICE DISCONNECTS

1 AND 2 LOCATED IN ELECTRICAL ROOM 166. STANDBY

GENERATOR IS LOCATED OUTSIDE ELECRICAL ROOM

166 ON SITE."

325 PROVIDE ELECTRONIC POWER METER TO ALLOW FOR

SUBMETERING PER SECTION 8.4.3.1 OF ASHRAE 90.1.

TYPICAL FOR ALL ELECTRONIC POWER METERS SHOWN

ON SHEET.

FEEDER SCHEDULE

FEEDER

MARK

PHASE

&NEUTRAL GROUND # OF SET

CONDUIT SIZE

3C+G 4C+G 5C+G

15 12 12 1 3/4" 3/4" 3/4"

20 12 12 1 3/4" 3/4" 3/4"

30 10 10 1 3/4" 3/4" 3/4"

40 8 10 1 3/4" 3/4" 1"

50 6 10 1 3/4" 1" 1"

60 4 10 1 1" 1 1/4" 1 1/4"

70 4 8 1 1" 1 1/4" 1 1/4"

80 3 8 1 1 1/4" 1 1/4" 1 1/4"

90 2 8 1 1 1/4" 1 1/2" 1 1/2"

100 1 8 1 1 1/2" 1 1/2" 2"

110 1 6 1 1 1/2" 1 1/2" 2"

125 1 6 1 1 1/2" 2" 2"

150 1/0 6 1 1 1/2" 2" 2"

175 2/0 6 1 2" 2" 2 1/2"

200 3/0 6 1 2" 2 1/2" 2 1/2"

225 4/0 4 1 2" 2 1/2" 3"

250 250 4 1 2 1/2" 3" 3"

300 350 4 1 3" 3" 3 1/2"

350 500 2 1 3" 4" 4"

400 3/0 2 2 2" 2" 2 1/2"

450 4/0 2 2 2" 2 1/2" 3"

500 250 2 2 2 1/2" 3" 3"

600 350 1/0 2 3" 3" 3 1/2"

700 500 1/0 2 3" 4" 4"

800 300 1/0 3 2 1/2" 3" 3"

1000 400 2/0 3 3" 3" 3 1/2"

1200 350 3/0 4 3" 3" 3 1/2"

1600 400 4/0 5 3" 3 1/2" 3 1/2"

2000 500 500 6 3 1/2" 4" 4"

NTSA1

ONE-LINE DIAGRAM - STANDBY POWER

A

M

R E

V

IS

IO

N

-3

-2

A-601
M-403
IN101
E-701 - ONE LINE DIAGRAM
E-702 - ONE LINE DIAGRAM STANDBY