This document package includes drawings and specifications for a federal construction project. The solicitation is for a consolidated Helo/TRF Ops/AMU and Alert Facility to be constructed at FE Warren Air Force Base in Wyoming. The project involves construction of a new facility as well as associated site work and utilities. The drawings provide details for partition layouts, mechanical systems, electrical systems and site plans. Specifications cover requirements for partition types, mechanical equipment, electrical panels and feeders. The solicitation is issued by the Department of the Army Corps of Engineers Omaha District. Responses are due based on the specified solicitation number and issuing agency.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECOND DIGIT IS THE
'SIZE INDICATOR'
THIRD DIGIT IS THE
PARTITION 'RATING'
"LINE OF STRUCTURE" INDICATED FOR EACH
PARTITION IS DIAGRAMMATIC ONLY AND DOES NOT
INDICATE EXACT CONSTRUCTION CONDITIONS OR
GEOMETRY. REFER TO FOR DETAILS ON THIS SHEET
FOR TYPICAL CONNECTION DETAILS.
DO NOT ATTACH METAL STUD TO THE TOP SLIP TRACK.
GYPSUM BOARD:
1. FIRE RESISTANT RATED PARTITIONS SHALL
USE TYPE "X" FIRE RATED GYPSUM BOARD.
2. PARTITIONS IN HIGH MOISTURE AREAS SHALL
USE MOISTURE RESISTANT GYPSUM BOARD
WHICH INCLUDE TOILET ROOM(S), LOCKER
ROOM(S),JANITOR CLOSET(S) AND WITHIN 4'-0"
OF WATER FOUNTAIN.
3. PARTITIONS BEHIND TOILETS, FIXTURES AND
WITHIN SHOWER AREAS SHALL USE CEMENT
BOARD WITH A MOISTURE BARRIER.
4. DO NOT ATTACH GYPSUM BOARD TO THE TOP
SLIP TRACK.
5. ALL GYPSUM BOARD LOCATED IN CORRIDORS,
CONFERENCE ROOMS, TRAINING ROOMS,
BREAK ROOMS, STORAGE ROOMS, SUPPLY
ROOMS, VENDING ROOMS, AND RECYCLE
ROOMS SHALL BE ABUSE RESISTANT TO 8'-0"
A.F.F. ALL GYPSUM BOARD LOCATED IN SHOPS
AND IN TRF AREAS SHALL BE IMPACT
RESISTANT TO 10'-0" A.F.F.
6. ALL CEILINGS LOCATED IN RESTROOMS SHALL
USE MOISTURE RESISTANT GYPSUM BOARD.
SEALANT:
1. FIRE RESISTANT RATED PARTITIONS SHALL USE
FIRE STOP SEALANT SYSTEM.
2. NON - RATED PARTITIONS AND SMOKE RATED
PARTITIONS SHALL USE ACOUSTICAL
SEALANT.FIRE RESISTANT RATED PARTITIONS
SHALL NOT USE ACOUSTICAL SEALANT.
INSULATION - HEAD CONDITION AT STRUCTURE
ABOVE:
1. FIRE RATED RESISTANT PARTITIONS SHALL USE
FIRE SAFING INSULATION.
2. NON - RATED PARTITIONS SHALL USE SOUND
ATTENUATION BLANKET.
FIRE AND / OR SMOKE RESISTANT ARE TO
SURROUND ALL OPENINGS IN RATED PARTITIONS.
FIRE AND / OR SMOKE RESISTANT PARTITIONS
SHALL EXTEND TO INSIDE FACE OF EXTERIOR
SHEATHING,INCLUDING EXTENSIONS THROUGH
SOFFITS.
EACH PARTITION INDICATED TO BE FIRE
AND/OR SMOKE RESISTANT SHALL BE
IDENTIFIED AS SUCH WITH A LABEL ABOVE
THE CEILING ON EACH SEGMENT OF WALL AT
8'-0" ON CENTER. INCLUDE LETTERING NOT
LESS THAN 3 INCHES IN HEIGHT AWITH A
MINIMUM 3/8 INCH STROKE IN A CONTRASTING
COLOR INCORPORATING THE SUGGESTED
WORDING, "FIRE AND/OR SMOKE BARRIER -
PROTECT ALL OPENINGS"
INSTALL HORIZONTAL STUD FRAMING BRACING AT 4'-
0" ON CENTER AT FURRING AND NON-RATED CHASE
WALLS
FIRST DIGIT IS THE
PARTITION 'TYPE'
A
B
C.
A3-2
GENERAL SHEET NOTES
PARTITION TYPES
D.
E.
F.
G.
H.
I. STC RATING IS BASED ON A MIN METAL STUD SIZE
OF 3 5/8".
J.
K.
L.
M.
ALL STUDS ARE 16" ON CENTER UNLESS OTHERWISE
NOTED.
ALL STUDS ARE MINIMUM 22 GAUGE.
REFER TO FLOOR PLANS FOR LOCATION OF
PARTITION TYPE TAGS.
CEILING AS SCHED
METAL STUD FRAMING
SOUND ATTENUATION
INSULATION - RATING 'A'
LINE OF STRUCTURE
ABOVE
D
A
3 5/8"
4"
6"
8"
NO RATING-NO INSULATION
ACOUSTICAL
4 7/8"
5 1/4"
7 1/4"
9 1/4"
SOUND ATTENTUATION
INSULATION TO 4'-0"
EACH SIDE - RATING 'A'
(1) LAYER OF GYP BD
ON EACH SIDE, TO 4 "
ABOVE CEILING
METAL TRACK
BETWEEN BRACING
F
2 1/2"
3 5/8"
4"
6"
8"
NO RATING-NO INSULATION
3 1/8"
4 1/4"
4 5/8"
6 5/8"
8 5/8"
CONT EVERY OTHER
MTL STUD TO STRUCT
2 2 1/2" 3 3/4"
CEILING AS SCHED
METAL STUD FRAMING
SOUND ATTENUATION
INSULATION - RATING 'A'
LINE OF STRUCTURE
ABOVE
WIDTH
SOUND ATTENTUATION
INSULATION TO 4'-0" ON
ONE SIDE - RATING 'A'
(1) LAYER OF GYP BD
ON ONE SIDE, TO
4 " ABOVE CEILING
METAL TRACK
BETWEEN BRACING
CONT EVERY OTHER
MTL STUD TO STRUCT
A ACOUSTICAL
H
A
S
3 5/8"
4"
6"
NO RATING-NO INSULATION
ACOUSTICAL
SMOKE
2'-0"
2'-0"
2'-0"
LINE OF STRUCTURE
ABOVE
CEILING AS SCHED
METAL STUD FRAMING
SOUND ATTENUATION
INSULATION-RATING 'A'
FINISH FLOOR
(1) LAYER OF GYP BD
ON EACH SIDE REFER
TO GENERAL NOTES
WIDTH
1'-0" HIGH WATER
RESISTANT GYP BD
BRACE AT 4'-0" OC
VERT, FASTEN 3
PLACES TO EA STUD
2'-0" WIDE
R A
T
IN
G S
IZ
E
IN
D
IC
A T
O R
T Y
P E
IND STUD SIZE TOTAL WIDTH
A
A
S
2 1/2"
3 5/8"
4"
6"
8"
NO RATING-NO INSULATION
1 HR FIRE RATED UL# U419
ACOUSTICAL - STC 45
SMOKE
3 3/4"
4 7/8"
5 1/4"
7 1/4"
9 1/4"
LINE OF STRUCTURE
ABOVE
CEILING AS SCHED
METAL STUD FRAMING
SOUND ATTENUATION
INSULATION - RATING 'A'
FINISH FLOOR
(1) LAYER OF GYP BD
ON EACH SIDE
WIDTH
R A
T
IN
G S
IC
A T
O R
T Y
P E
IND STUD SIZE TOTAL WIDTH
WIDTH
R A
T
IN
G S
IC
A T
O R
T Y
P E
IND STUD SIZE TOTAL WIDTH
R A
T
IN
G S
IC
A T
O R
T Y
P E
IND STUD SIZE TOTAL WIDTH
P
1 HR FIRE RATED BASED
UPON U905
1 16 1/4"
R A
T
IN
G S
IC
A T
O R
T Y
P E
IND CMU SIZE TOTAL WIDTH
R
8 8"
NO RATING-NO INSULATION
11 1/8"
R A
T
IN
G S
IC
A T
O R
T Y
P E
IND CONCRETE
WALL SIZE
TOTAL WIDTH
NO RATING-NO INSULATION
1* 3 5/8" 4 1/4"
R A
T
IN
G S
IC
A T
O R
T Y
P E
IND WALL SIZE TOTAL WIDTH
LINE OF STRUCTURE
ABOVE
CEILING AS SCHED
ROOM SIDE
2 1/2" METAL STUD
FRAMING
FINISH FLOOR
(1) LAYER OF GYP BD
ABUSE RESISTANT
CAST-IN-PLACE
CONCRETE CEILING
REFER STRUCTURAL
CAST-IN-PLACE
CONCRETE WALL
REFER STRUCTURAL
WIDTH
VAULT
SIDE
LINE OF STRUCTURE
ABOVE
CEILING AS SCHED
FINISH FLOOR
8" GIRTS AT MASONRY
WAINSCOT
3 5/8" METAL STUD
INFILL BETWEEN
GIRTS
5/8" TYPE "X" GYP BD
TO 6" ABOVE CEILING
8" GIRT; REFER
STRUCTURAL
LINE OF STRUCTURE
ABOVE
CMU BOND BEAM;
REFER STRUCTURAL
2" RIGID INSULATION
CMU BACKUP
2" Z FURRING WITH
5/8" TYPE "X" GYPSUM
BOARD
FINISH FLOOR
11 5/8"
S
3 5/8" METAL STUD INFILL
WITHIN GIRT SPACE
N. PROVIDE PAINTED FINISH TO 1'-0" ABOVE CEILING AT
GYPSUM BOARD SIDE OF WALL TYPE P1-1; TAPING,
FLOATING AND FINISHING OF GYPSUM BOARD NOT
REQUIRED FROM 1'-0" ABOVE CEILING TO DECK ABOVE
ASSEMBLY
MINIMUM R VALUE
T
1 HR FIRE U415 SYSTEM A
2 3 1/8"
R A
T
IN
G S
IC
A T
O R
T Y
P E
IND STUD SIZE TOTAL WIDTH
1" GYP BD LINER
PANEL
GYP BD ON ONE SIDE
C-H METAL STUD
FRAMING
FINISH FLOOR
2 1/2"
LINE OF STRUCTURE
ABOVE
U
1 7 5/8" 7 5/8"
R A
T
IN
G S
IC
A T
O R
T Y
P E
IND CMU SIZE TOTAL WIDTH
LINE OF
STRUCTURE
ABOVE
CMU BOND
BEAM; REFER
STRUCTURAL
CMU
FINISH FLOOR
1 HR FIRE RATED BASED
UPON U905
R A
T
IN
G S
IC
A T
O R
T Y
P E
IND STUD SIZE TOTAL WIDTH
M
A
S
2 1/2"
3 5/8"
4"
6"
8"
NO RATING-NO INSULATION
1 HR FIRE RATED UL# U419
ACOUSTICAL - STC 50
SMOKE
4 3/8"
5 1/2"
5 7/8"
7 7/8"
9 7/8"
LINE OF STRUCTURE
ABOVE
CEILING AS SCHED
METAL STUD FRAMING
SOUND ATTENUATION
INSULATION - RATING 'A'
FINISH FLOOR
(2) LAYER OF GYP BD
WIDTH
(1) LAYER OF GYP BD
2 11 5/8" 11 5/8"
R O
O M
S
ID
E
1 HR FIRE U415 SYSTEM B2
ACOUSTICAL - STC 47A
S H
A F
T S
ID
E WIDTH
6 6 5/8"6"
1 7/8" 1 1/2"
N
2 1/2"
3 5/8"
6"
NO RATING-NO INSULATION
3 3/4"
4 7/8"
7 1/4"
CEILING AS SCHED
METAL STUD FRAMING
SOUND ATTENUATION
INSULATION - RATING 'A'
LINE OF STRUCTURE
ABOVE
WIDTH
(2) LAYERS OF GYP BD
ON ONE SIDE
A ACOUSTICAL
R A
T
IN
G S
IC
A T
O R
T Y
P E
IND STUD SIZE TOTAL WIDTH
1 7/8" 2 1/8"
FILL VOIDS BETWEEN MTL
DECK & PLATE WITH SPRAY
FOAM OR BATT INSULATION-
COVER COMPLETELY WITH
1" SEALANT
COMPRESSIBLE
INSULATION
STEEL ROOF OR
FLOOR DECK
SEAL BETWEEN
PLATE AND DECK AT
EACH SIDE
SEALANT WITH BOND
BREAKER TAPE
TOP RUNNER
CAPTURED WITHIN
DEEP LEG TRACK
CONT 18 GAGE X 3"
LEG TRACK,
ANCHOR TO DECK
WITH S-12 SCREWS
AT 12" OC
STAGGERED
PERPENDICULAR TO METAL
DECK FLUTES
PARALLEL TO METAL
DECK FLUTES
DO NOT ATTACH
GYP BD OR STUDS
TO TOP TRACK
PROVIDE
UL SYSTEMS
HW-D-0042
AT ALL 1 HR RATED
PARTITIONS
REFER TO
GENERAL NOTES
FOR SEALANT AND
INSULATION TYPES
GYP BD PARTITION
AS SCHED
GALV U-SHAPED
STEEL CASING
ACOUSTICAL SEALANT
AND BACKER ROD
METAL STUD
GYP BD PARTITION
AS SCHED
/8
FLR FIN AS
SCHED
GYP BD
PARTITION AS
SCHED
SEALANT AND
BACKER ROD, REF:
GENERAL NOTES
METAL STUD
BASE AS SCHED
ZINC CONTROL JOINT
AT BOTH SIDES
METAL STUD
GYP BD PARTITION
AS SCHED
/2
ZINC CONTROL JOINT
AT BOTH SIDES
2 LAYERS OF
5/8" GYP BD
METAL STUD
GYP BD PARTITION
AS SCHED
/8
/8
/8
BACKER ROD
AND SEALANT
CERAMIC FIBER
BLANKET
BOND BREAKER
SEALANT
P A
N E
L T
H
IC
K N
E S
S
JOINT WIDTH
FIRE SIDE
VERTICAL
NOTE: PROVIDE RATED JOINT ASSEMBLY IN
PRECAST UTILIZING FIBER FELT PER DEFERRED
DESIGN. COORDINATE JOINT DESIGN WITH
RATING REQUIREMENT.
R E
G
IS
T
ERED ARCH
IT
E
C T
S T
A T E
O F T EX
A S
C H
R I S
T
O
PHER M
S U
R L
E S
2 3 6 3 8
US Army Corps of Engineers Omaha District ®
SHEET
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D x
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
D R
A W
IN
G
C O
D E
A F
-1
-0
-W F
R
M
A R
C H
C H
O F
F F
IL
E
N A
M E
O M
A H
A D
IS
T
R
IC
T
O M
A H
A
N E
B R
A S
K A
F Y
H
E L
O /T
R F
/M A
IN
T
E N
A N
C E
F A
C
IL
IT
Y
P R
O J E
C T
N U
M B
E R
G
H L
N A
F E
W A
R R
E N
A F
B
W Y
J A
C O
B S
E N
G
IN
E E
R
IN
G G
R O
U P
I N
C
M a in
S tr e e t
F o rt
W o rt h
T X
READY-TO-ADVERTISE (RTA) DESIGN
A-601
P A
R T
IT
IO
N T
Y P
E S
C S
U R
L E
S
T R
IC
E
N V
IG
L
IO
T
T A
F E
-G
H L
N
A A
-6
3" = 1'-0"A1
TYP TOP OF GYP BD WALL CONX
3" = 1'-0"B3
TYP WALL-WALL CONX
3" = 1'-0"A3
TYP BOTTOM OF
WALL CONX
3" = 1'-0"B5
TYP CONTROL JOINT
3" = 1'-0"A5
TYP 1 HR RATED
CONTROL JOINT
N.T.S.A7
RATED
PRECAST JOINT
A
M
R E
V
IS
IO
N
S
-2
-2
09/21/2021
P
1'2' A4
M-302
GF-1
CU-4
CU-3
CU-8
UH-1
M
M
M
ACU-2
ACU-1
6" EQUIPMENT PAD
SHALL EXTEND A
MINIMUM OF 6" ON ALL
SIDES OF UNIT. REFER
TO STRUCTURAL FOR
DETAIL
6" EQUIPMENT PAD
SHALL EXTEND A
MINIMUM OF 6" ON ALL
SIDES OF UNIT. REFER
TO STRUCTURAL FOR
DETAIL
8"Ø BOILER COMBUSTION
AIR INLET. (TYP. 3)
6"Ø WATER HEATER VENT.
(TYP. 2)
8"Ø BOILER COMBUSTION
AIR INLET. (TYP. 2)
L.4
L
K.5
J
WELD (NOTE 6)
ANCHOR BOLTS, 2 AT
EACH PLATE. MIN.
SIZE 5/8"
STRUCTURAL
CHANNEL
OR ANGLES
2"x2"x1/4"
3/8" BASE PLATE
PIPE & INSULATION
3/8" PLATE CUT TO SUIT
PIPE DIA. AND
INSULATION THICKNESS
NOTE: INSULATE ANCHOR AS INDICATED FOR COLD PIPING.
1/2" U-BOLT
INSULATION
STRUCTURE
UNISTRUT CHANNEL
U-BOLT
PIPE (TYP.)
INSULATION (TYP.)
PROVIDE SLEEVE TO PROTECT INSULATION
PIPE GUIDE - 2-1/2" AND SMALLER
PIPE ANCHOR - 2-1/2" AND SMALLER
PROVIDE SWAY BRACING
PIPE
U-BOLT
PIPE GUIDE - 3" AND LARGER
PIPE
PIPE
PIPE ANCHOR - 3" AND LARGER
NOTE 4
(TYP.)
1/4"
1/4"
1/4"
1/4"
(TYP.)
(TYP.)
(TYP.)
NOTE 6
NOTE 6
NOTE 6
NOTE 6
SUPPORT
STEEL
SUPPORT STEEL
NOTES:
1. SEE PIPING DRAWINGS FOR SUPPORT LOCATIONS.
2. VERIFY ALL ELEVATIONS PRIOR TO FABRICATION.
3. FINAL PIPE SUPPORT, GUIDE, ANCHOR, AND SUPPORT STEEL
DESIGN AND SELECTION IS DELEGATED DESIGN. DETERMINE
LOADING ON GUIDES, ANCHORS AND SUPPORTS PRIOR TO
COMPONENT SELECTION AND INSTALLATION.
4. CONTRACTOR TO SELECT OR DESIGN PIPE SUPPORTS FOR
DESIGN LOADS.
5. SUBMIT FINAL PIPE LAYOUT WITH MECHANICAL STRESS ANALYSIS
AND STATE COMPLIANCE WITH ASME B31.1.
6. CONTRACTOR TO DETERMINE WELD TYPE, THICKNESS AND
WELDING SPECIFICATION PER DESIGN LOADS FROM STRUCTURAL
DRAWINGS.
7. FORCES TRANSFERRED TO THE STRUCTURE MUST BE SUBMITTED
FOR APPROVAL TO THE STRUCTURAL DOR.
(TYP.)
1/8"
02 4 8134
SCALE: 1/4"=1'-0"
BRODIE B. B. HEFLIN
OF TEXASS
TATE
ALNOI
SS
E
F O
R P
ENG
IN
E E
R
NSEDECI
L 106046
TRUE NORTH
US Army Corps of Engineers Omaha District ®
SHEET
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D x
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
D R
A W
IN
G
C O
D E
A F
-1
-0
-W F
R
M
A R
C H
C H
O F
F F
IL
E
N A
M E
O M
A H
A D
IS
T
R
A H
A
N E
B R
A S
K A
F Y
H
E L
O /T
R F
/M A
IN
T
E N
A N
C E
F A
C
IL
IT
Y
P R
O J E
C T
N U
M B
E R
G
H L
N A
F E
W A
R R
E N
A F
B
W Y
J A
C O
B S
E N
G
IN
E E
R
IN
G G
R O
U P
I N
C
M a in
S tr e e t
F o rt
W o rt h
T X
READY-TO-ADVERTISE (RTA) DESIGN
TEXAS REGISTERED
ENGINEERING FIRM F-2966
M-403
H V
A C
E N
L A
R G
E D
P L A
N S
B B
S /R
C
B B
S /R
C
B H
F E
-G
H L N
A M
-4
1/4" = 1'-0"A6
MECHANICAL YARD - ENLARGED PLAN
GENERAL NOTES - HVAC PLANS
A MAINTAIN MANUFACTURER'S RECOMMENDED
CLEARANCES ON ALL EQUIPMENT.
B PROVIDE CLEARANCES FOR ALL ELECTRICAL AND
CONTROL PANELS PER NEC.
C PROVIDE BRACING FOR EQUIPMENT WEIGHING MORE
THAN 31 LBS PER UFC 4-010-01.
D COORDINATE THERMOSTATS WITH FURNISHINGS.
LOCATE THERMOSTATS 6" ON CENTER FROM LIGHT
SWITCH. MOUNT TOP OF THERMOSTAT AS SHOWN AT
ADA APPROVED MOUNTING HEIGHT.
E PROVIDE U.L. RATED THROUGH-PENETRATION FIRE
STOP SYSTEMS AT ALL PENETRATIONS BETWEEN
THE HANGAR/SHOP DEMISING WALL.
F PROVIDE REMOTE DAMPER ACTUATORS OR ACCESS
PANEL FOR ALL DAMPERS LOCATED ABOVE HARD
CEILINGS.
G REFER TO PIPING PLAN FOR THERMOSTAT
ASSIGNMENT
H PROVIDE BALANCING DAMPER AT EACH TAKEOFF
I ALL MITERED ELBOWS HAVE TURNING VANES
J LOCATE TOP OF HVLS FAN CONTROL PANEL AT 4FT
AFF
A
M
R E
V
IS
IO
N
-2
-2
NTSA1
TYPICAL PIPE GUIDE AND ANCHOR
| � | � |
| � | � |
�0
2�
2�
#4
2�
"8�������9��
�1
�0
�8�� ���1������;���+� +��0� ����1���� 1����
�8�� ���1������;���+� +��0� �����"�1����
9/30/2021
2000 AF
2000 AT
3P
LSIG
NSB, 2000 A, 480/277 V
3 P, 4 W, 60 HZ, 65 KAIC
RM166
1200 AF
1200 AT
3P
LSIG
400 AF
3P
NHD1, 400 A, 480/277 V
3 P, 4 W, 60 HZ, 22 KAIC
RM 155
400 AF
400 AT
3P
LSI
400 4
N G
100 AF
50 AT
3P
100 AF
100 AT
3P
100 4
100 AF
50 AT
3P
NHL11
PANEL
RM 166
NLP11
PANEL
RM 166
480:208/120 V 30 kVA, Z~3.0%
T-NP11
RM 166
NLP12
PANEL
RM 137
480:208/120 V 30 kVA, Z~3.0%
T-NP12
RM 137
100 AF
50 AT
3P
100 AF
100 AT
3P
100 4
NHL13
PANEL
RM 155
NLP13
PANEL
RM 155
480:208/120 V 30 kVA, Z~3.0%
T-NP13
RM 155
100 AF
50 AT
3P
NHL21
PANEL
RM 228
480:208/120 V 75 kVA, Z~3.0%
T-NP21
RM 282
100 AF
100 AT
3P
100 4
NLP22A
PANEL
RM 228
480:208/120 V 75 kVA, Z~3.0%
T-NP22
RM 228
225 AF
125 AT
3P
480:208/120 V 30 kVA, Z~3.0%
T-NP14
RM 158
NLP14
PANEL
RM 158
NLP23
PANEL
RM 284
480:208/120 V 75 kVA, Z~3.0%
T-NP23
RM 284
RM 166
LCP11
RM 155
LCP13
RM 228
LCP21
225 AF
225 AT
3P
225 4
225 AF
225 AT
3P
225 4
NHH11
PANEL
RM 193
NHH12
PANEL
RM 193
NHH13
PANEL
RM 194
480:208/120 V 30 kVA, Z~3.0%
T-NH11
RM 193
NLH11
PANEL
RM 193
NLH12
PANEL
RM 193
NLH13
PANEL
RM 194
400 AF
400 AT
3P
400 4
480:208/120 V 30 kVA, Z~3.0%
T-NH12
RM 193
480:208/120 V 75 kVA, Z~3.0%
T-NH13
RM 194
400 AF
400 AT
3P
225 AF
125 AT
3P
225 AF
125 AT
3P
RM 166
RCP11
RM 284
RCP23
RM 158
RCP14
RM 155
RCP13
RM 137
RCP12
400 AF
400 AT
3P
400 4
100 AF
100 AT
3P
100 4
NHE15
PANEL
RM 189
NHL15
PANEL
RM 189
NLP15A
PANEL
RM 189
480:208/120 V
112.5 kVA, Z~3.0%
T-NP15
RM 189RM 189
LCP15
RM 189
RCP15B
400 AF
3P
400 AF
3P
NLP21A
PANEL
RM 282
NLP21B
PANEL
RM 282
NLP15B
PANEL
RM 189
225 4
100 4
DC11B
FC-12
250 AF
200 AT
3PREEL
CORD
REEL
CORD
REEL
CORD
RM 282
RCP21A
RM 282
RCP21B
NLP22B
PANEL
RM 228
100 4
RM 228
RCP22B
RM 228
RCP22A
OUTSIDE
ARMAG
100 3
DC11A DC12
FC-11
400 AF
300 AT
3P
300 4
NHSIM
PANEL
RM 162
NLSIM
PANEL
RM 162
480:208/120 V 30 kVA, Z~3.0%
T-NSIM
RM 162
SPD
60 AF
60 AT
3P
SPD
60 AF
60 AT
3P
TO FIRE PUMP TAP BOX
RE: SHEET A1/E-702
FEEDER BY HIGH
WEST ENERGY M
MSE
100% RATED
65 KAIC
TO HANGAR DOORS ECB 2O
VIA BY-PASS/ISOLATION ATS
RE: SHEET A1/E-702
T-HELO
13.8 KV:480/277 V
Z~5.75%
BY HIGH WEST ENERGY
T O
A T S -1
R E : A
1/E -702
S P A R
E
S P A R
E
S P A R
E
ECB 400HZ
400 HZ RATED
RM 189
400 HZ
RECEPTACLE
RM 189
234234234234234
240 240
#3/0
RE: D1/E-703
M
083 083
EPM EPM EPM EPM EPM EPM EPM EPM
US Army Corps of Engineers Omaha District ®
SHEET
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D x
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
D R
A W
IN
G
C O
D E
A F
-1
-0
-W F
R
M
A R
C H
C H
O F
F F
IL
E
N A
M E
O M
A H
A D
IS
T
R
A H
A
N E
B R
A S
K A
F Y
H
E L
O /T
R F
/M A
IN
T
E N
A N
C E
F A
C
IL
IT
Y
P R
O J E
C T
N U
M B
E R
G
H L
N A
F E
W A
R R
E N
A F
B
W Y
J A
C O
B S
E N
G
IN
E E
R
IN
G G
R O
U P
I N
C
M a in
S tr e e t
F o rt
W o rt h
T X
READY-TO-ADVERTISE (RTA) DESIGN
TEXAS REGISTERED
ENGINEERING FIRM F-2966
E-701
O N
E L
IN
E
D
IA
G R
A M
C T
R U
S S
E L L
C T
R U
S S
E L L
L .J
D
A V
IS
F E
-G
H L
N
A E
-7
GENERAL NOTES - ONE-LINE
E ONE-LINE DIAGRAMS DEPICT INTERCONNECTION OF
ELECTRICAL INFRASTRUCTURE. COORDINATE WITH
PANEL SCHEDULES FOR THE BALANCE OF ADDITIONAL
CONNECTIONS AND DEVICES.
F FOR DRY TYPE TRANSFORMERS WITH MULTIPLE FEEDS,
REFER TO PANEL SCHEDULES FOR PANEL MCB
BREAKER SIZING INFORMATION.
G PROVIDE EQUIPMENT WITH FULLY BUSSED SPACE FOR
FUTURE DEVICES.
H PROVIDE ALL OCPD RATED 1200 A AND GREATER WITH
ARC FLASH REDUCING MAINTENANCE BYPASS SWITCH.
GENERAL NOTES - ONE-LINE
A REFER TO SHEET E-001 FOR GENERAL NOTES, LEGEND,
AND ABBREVIATIONS.
B PROVIDE ARC FLASH WARNING SIGNS ON THE
SWITCHBOARDS, SWITCHGEAR, PANELBOARDS,
INDUSTRIAL CONTROL PANELS, METER SOCKET
ENCLOSURES, AND MOTOR CONTROL CENTERS AS
REQUIRED PER NFPA 70 (NEC) ARTICLE 110.16.
REFERENCE NFPA 70 ARTICLE 110.16; NFPA 70E
ARTICLE 130.3; AND UFC 3-560-01, ELECTRICAL SAFETY,
O & M.
C ALL BREAKERS 400A AND GREATER SHALL BE 100%
RATED.
D LCP AND SLCP REPRESENT SPACE ALLOCATED FOR
LIGHTING CONTROL PANELS. RCP REPRESENTS SPACE
ALLOCATED FOR RECEPTACLE CONTROL PANELS.
FEEDER SCHEDULE NOTES
A THIS SCHEDULE IS BASED ON INTERNAL AREA OF EMT,
RGS, OR SCHEDULE 40 PVC CONDUIT AND THE
AMPACITIES FOR EM OR CET INSULATION.
B FEEDER MARK " " INDICATES FEEDER RATING
AND NUMBER OF PHASE CONDUCTORS INCLUDING
NEUTRAL. PROVIDE GROUND AS INDICATED ON FEEDER
SCHEDULE.
C UNDERGROUND SERVICE ENTRANCE FEEDERS CONSIST
OF THREE PHASE WIRES AND NEUTRAL. NUMBER OF
CONDUCTORS PER PHASE ARE CALCULATED VALUES
BASED ON SPECIFIC DUCT BANK ARRANGEMENTS, LOAD
FACTORS, AND SOIL CONDITIONS.
D SECONDARY FEEDERS ARE AS SCHEDULED UON.
NTSA1
ONE-LINE DIAGRAM - NORMAL POWER
XXXXX
KEYNOTES
059 PROVIDE 8 SETS OF [4 - 500 KCMIL IN 6" C] + 2 SPARE 6"
C
083 200A DC RECTIFIER (BID OPTION 5).
084 45 KVA 400HZ FREQUENCY CONVERTER. PROVIDE 1 SET
OF 3#3, 1#8G IN 1-1/4"C. (BID OPTION 5)
085 90 KVA 400HZ FREQUENCY CONVERTER. PROVIDE 1 SET
OF 3#3/0, 1#6G IN 2-1/2"C. (BID OPTION 5)
234 PROVIDE K-RATED TRANSFORMER.
240 PROVIDE A JACKETED, PLANETARY WRAPPED CABLE
(SIX PHASE WIRES AROUND ONE NEUTRAL) WITH #2
PHASE CONDUCTORS AND INTEGRAL CONTROL
CONDUCTORS (BID OPTION).
265 PROVIDE AMRS METER.
288 PROVIDE 8 SETS OF [4 - 500 KCMIL, 1 - 250 KCMIL G IN 6"
C] + 2 SPARE 6" C
322 PROVIDE PERMANENT ENGRAVED PLACARD THAT SAYS
"SERVICE DISCONNECT 1 OF 3. SERVICE DISCONNECT 2
OF 3 LOCATED AT ATS-2 IN ELECTRICAL ROOM 166.
SERVICE DISCONNECT 3 OF 3 LOCATED AT FIRE PUMP
TAP BOX IN FIRE SUPPRESSION EQUIP ROOM 191.
STANDBY GENERATOR IS LOCATED OUTSIDE ELECRICAL
ROOM 166 ON SITE."
325 PROVIDE ELECTRONIC POWER METER TO ALLOW FOR
SUBMETERING PER SECTION 8.4.3.1 OF ASHRAE 90.1.
TYPICAL FOR ALL ELECTRONIC POWER METERS SHOWN
ON SHEET.
TRANSFORMER SCHEDULE
KVA
RATING
PRIMARY (480V) SECONDARY (208/120V)
GROUNDBREAKER FEEDER BREAKER FEEDER
15 30/3 3#10, #10G, IN 3/4" C 50/3 4#6, #8G, IN 3/4" C #8
30 50/3 3#6, #10G, IN 3/4" C 100/3 4#1, #6G, IN 1-1/4" C #6
45 70/3 3#4, #8G, IN 1" C 150/3 4#1/0, #6G, IN 2" C #4
75 125/3 3#1/0, #6G, IN 1-1/2" C 225/3 4#4/0, #2G, IN 2-1/2" C #2
112.5 175/3 3#2/0, #6G, IN 1-1/2" C 400/3 2 SETS OF 4#3/0, #1/0G, IN 2" C #2
150 300/3 3-350kcmil, #4G, IN 2-1/2" C 500/3 2 SETS OF 4-250kcmil, #1/0G, IN 2-1/2" C #1/0
FEEDER SCHEDULE
FEEDER
MARK
PHASE
&NEUTRAL GROUND # OF SET
CONDUIT SIZE
3C+G 4C+G 5C+G
15 12 12 1 3/4" 3/4" 3/4"
20 12 12 1 3/4" 3/4" 3/4"
30 10 10 1 3/4" 3/4" 3/4"
40 8 10 1 3/4" 3/4" 1"
50 6 10 1 3/4" 1" 1"
60 4 10 1 1" 1 1/4" 1 1/4"
70 4 8 1 1" 1 1/4" 1 1/4"
80 3 8 1 1 1/4" 1 1/4" 1 1/4"
90 2 8 1 1 1/4" 1 1/2" 1 1/2"
100 1 8 1 1 1/2" 1 1/2" 2"
110 1 6 1 1 1/2" 1 1/2" 2"
125 1 6 1 1 1/2" 2" 2"
150 1/0 6 1 1 1/2" 2" 2"
175 2/0 6 1 2" 2" 2 1/2"
200 3/0 6 1 2" 2 1/2" 2 1/2"
225 4/0 4 1 2" 2 1/2" 3"
250 250 4 1 2 1/2" 3" 3"
300 350 4 1 3" 3" 3 1/2"
350 500 2 1 3" 4" 4"
400 3/0 2 2 2" 2" 2 1/2"
450 4/0 2 2 2" 2 1/2" 3"
500 250 2 2 2 1/2" 3" 3"
600 350 1/0 2 3" 3" 3 1/2"
700 500 1/0 2 3" 4" 4"
800 300 1/0 3 2 1/2" 3" 3"
1000 400 2/0 3 3" 3" 3 1/2"
1200 350 3/0 4 3" 3" 3 1/2"
1600 400 4/0 5 3" 3 1/2" 3 1/2"
2000 500 500 6 3 1/2" 4" 4"
A
M
R E
V
IS
IO
N
-3
-2
N G
G
1250 KW GEN, 480/277 V,
3 P, 4 W, 60 HZ, 22 KAIC
OUTSIDE
2000 AF
1200 AT
3P
LSIG
1200 4
M
480V, 60 HZ
800A, 4P
FPC-2
700 4
M
480V, 60 HZ
800A, 4P
FPC-1
700 4 700 4700 4 700 4
480V, 60 HZ
2000A, 4P
ATS-1, RM 166
35 KAIC
1200 4
1200 4
1200 AF
1200 AT
3P
LSIG
600 AF
600 AT
3P
LSI
600 4
SSB (STANDBY SWITCHBOARD)
1200 A, 480/277 V
3 P, 4 W, 60 HZ, 35 KAIC
RM 166
SPD
60 AF
60 AT
3P
225 AF
125 AT
3P
LSI
SHH11
PANEL
RM 195
480:208/120 V 75 kVA, Z~3.0%
T-SD1
RM 158
SLC12
PANEL
RM 156
SLC21
PANEL
RM 283
SLP13
PANEL
RM 155
600 AF
600 AT
3P SHD1, 600 A, 480/277 V
3 P, 4 W, 60 HZ, 25 KAIC
RM 158
225 AF
125 AT
3P
SPD
60 AF
60 AT
3P
225 AF
225 AT
3P
225 4
100 AF
100 AT
3P
100 4
225 AF
225 AT
3P SLD1, 225 A, 208/120 V
3 P, 4 W, 60 HZ, 10 KAIC
RM 158
100 AF
100 AT
3P
100 4
100 AF
100 AT
3P
100 4
SPD
60 AF
60 AT
3P
100 AF
100 AT
3P
100 4
225 AF
150 AT
3P
150 4
SLC11
PANEL
RM 136
SHE11
PANEL
RM 196
480:208/120 V 75 kVA, Z~3.0%
T-SD2
RM 166
SLC13
PANEL
RM 163
SLC14
PANEL
RM 184
FA
PANEL
RM 191
225 AF
225 AT
3P SLD2, 225 A, 208/120 V
3 P, 4 W, 60 HZ, 10 KAIC
RM 166
100 AF
100 AT
3P
100 4
SPD
60 AF
60 AT
3P
100 AF
100 AT
3P
100 4
100 AF
70 AT
3P
SLC15
PANEL
RM 181
100 AF
100 AT
3P
100 4
480:208/120 V 30 kVA, Z~3.0%
T-SP11
RM 196
SLP11
PANEL
RM 196
225 AF
225 AT
3P
225 4
480:208/120 V 30 kVA, Z~3.0%
T-SP21
RM 228
SLP21
PANEL
RM 228
SHE13
PANEL
RM 158
100 AF
25 AT
3P
SLP14
PANEL
RM 193
225 AF
3P
225 AF
3P
FC
SLP22
PANEL
RM 211
100 AF
100 AT
3P
100 4
CCR1
FC
REEL
CORD
REEL
CORD
REEL
CORD
SLP15
PANEL
RM 155
225 AF
150 AT
3P
150 4
480:208/120 V 45 kVA, Z~3.0%
TFA
RM 191
CCR2
RM 155
SRCP15
250 AF
250 AT
3P
LSIG
250 4
SHHD1
PANEL
RM 193
480V, 60 HZ
250A, 4P
ATS-2, RM 166
18 KAIC
250 4
250 AF
250 AT
3P
225 AF
200 AT
3P
LSIG
200 4
225 AF
200 AT
3P SHL1, 200 A, 480/277 V
3 P, 4 W, 60 HZ, 14 KAIC
RM 166
100 AF
100 AT
3P
100 4
100 AF
100 AT
3P
100 4
SHL11
PANEL
RM 137RM 166
SLCP12 SHL12
PANEL
RM 166 RM 137
SLCP11
RM 228
SLCP21SHL21
PANEL
RM 228
2000 AF
1600 AT
3P
LSIG
700 4
1200 AF
1200 AT
3P
1200 4
225 AF
175 AT
3P
LSI
PORTABLE GENERATOR
CONNECTION / LOAD
BANK CABINET
1200 AF
1200 AT
3P
LSIG
1200 4
SPD
60 AF
60 AT
3P
#3/0
J
J
J
FOR RECEPTACLE
AND LIGHTING
FOR BATTERY
CHARGER
FOR WATER JACKET
HEATERS
J
SLD2:6
SLD2:24
SLD2:14,16
2#10, 1#10G
SLD2:26,28
2#10, 1#10G
TO SERVICE
TRANSFORMER.
RE: A1/E-701
FIRE PUMP
CONTROLLER WITH
INTEGRAL ATS FIRE PUMP 2FIRE PUMP 1
800 A TAP BOX
TO NSB
RE: A1/E-701
S P A R
E
S P A R
E
084234
234 234
240 240
BY-PASS/ISOLATION
AUTOMATIC
TRANSFER SWITCH
TO SERVICE
TRANSFORMER.
RE: A1/E-701
ECB 2O
RM 166
M
ECB 1E
RM 166
ELEV 1
RE: E-602 FOR FEEDER
INFORMATION
LOAD BANK
CONNECTION
TEMPORARY
GENERATOR
EPM EPM
US Army Corps of Engineers Omaha District ®
SHEET
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D x
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
D R
A W
IN
G
C O
D E
A F
-1
-0
-W F
R
M
A R
C H
C H
O F
F F
IL
E
N A
M E
O M
A H
A D
IS
T
R
A H
A
N E
B R
A S
K A
F Y
H
E L
O /T
R F
/M A
IN
T
E N
A N
C E
F A
C
IL
IT
Y
P R
O J E
C T
N U
M B
E R
G
H L
N A
F E
W A
R R
E N
A F
B
W Y
J A
C O
B S
E N
G
IN
E E
R
IN
G G
R O
U P
I N
C
M a in
S tr e e t
F o rt
W o rt h
T X
READY-TO-ADVERTISE (RTA) DESIGN
TEXAS REGISTERED
ENGINEERING FIRM F-2966
E-702
O N
E L
IN
E
D
IA
G R
A M
S T
A N
D B
Y
C T
R U
S S
E L L
C T
R U
S S
E L L
L .J
D
A V
IS
F E
-G
H L
N
A E
-7
GENERAL NOTES - ONE-LINE
E ONE-LINE DIAGRAMS DEPICT INTERCONNECTION OF
ELECTRICAL INFRASTRUCTURE. COORDINATE WITH
PANEL SCHEDULES FOR THE BALANCE OF ADDITIONAL
CONNECTIONS AND DEVICES.
F FOR DRY TYPE TRANSFORMERS WITH MULTIPLE FEEDS,
REFER TO PANEL SCHEDULES FOR PANEL MCB
BREAKER SIZING INFORMATION.
G PROVIDE EQUIPMENT WITH FULLY BUSSED SPACE FOR
FUTURE DEVICES.
H PROVIDE ALL OCPD RATED 1200 A AND GREATER WITH
ARC FLASH REDUCING MAINTENANCE BYPASS SWITCH.
GENERAL NOTES - ONE-LINE
A REFER TO SHEET E-001 FOR GENERAL NOTES, LEGEND,
AND ABBREVIATIONS.
B PROVIDE ARC FLASH WARNING SIGNS ON THE
SWITCHBOARDS, SWITCHGEAR, PANELBOARDS,
INDUSTRIAL CONTROL PANELS, METER SOCKET
ENCLOSURES, AND MOTOR CONTROL CENTERS AS
REQUIRED PER NFPA 70 (NEC) ARTICLE 110.16.
REFERENCE NFPA 70 ARTICLE 110.16; NFPA 70E
ARTICLE 130.3; AND UFC 3-560-01, ELECTRICAL SAFETY,
O & M.
C ALL BREAKERS 400A AND GREATER SHALL BE 100%
RATED.
D LCP AND SLCP REPRESENT SPACE ALLOCATED FOR
LIGHTING CONTROL PANELS. RCP REPRESENTS SPACE
ALLOCATED FOR RECEPTACLE CONTROL PANELS.
FEEDER SCHEDULE NOTES
A THIS SCHEDULE IS BASED ON INTERNAL AREA OF EMT,
RGS, OR SCHEDULE 40 PVC CONDUIT AND THE
AMPACITIES FOR EM OR CET INSULATION.
B FEEDER MARK " " INDICATES FEEDER RATING
AND NUMBER OF PHASE CONDUCTORS INCLUDING
NEUTRAL. PROVIDE GROUND AS INDICATED ON FEEDER
SCHEDULE.
C UNDERGROUND SERVICE ENTRANCE FEEDERS CONSIST
OF THREE PHASE WIRES AND NEUTRAL. NUMBER OF
CONDUCTORS PER PHASE ARE CALCULATED VALUES
BASED ON SPECIFIC DUCT BANK ARRANGEMENTS, LOAD
FACTORS, AND SOIL CONDITIONS.
D SECONDARY FEEDERS ARE AS SCHEDULED UON.
XXXXX
TRANSFORMER SCHEDULE
KVA
RATING
PRIMARY (480V) SECONDARY (208/120V)
GROUNDBREAKER FEEDER BREAKER FEEDER
15 30/3 3#10, #10G, IN 3/4" C 50/3 4#6, #8G, IN 3/4" C #8
30 50/3 3#6, #10G, IN 3/4" C 100/3 4#1, #6G, IN 1-1/4" C #6
45 70/3 3#4, #8G, IN 1" C 150/3 4#1/0, #6G, IN 2" C #4
75 125/3 3#1/0, #6G, IN 1-1/2" C 225/3 4#4/0, #2G, IN 2-1/2" C #2
112.5 175/3 3#2/0, #6G, IN 1-1/2" C 400/3 2 SETS OF 4#3/0, #1/0G, IN 2" C #2
150 300/3 3-350kcmil, #4G, IN 2-1/2" C 500/3 2 SETS OF 4-250kcmil, #1/0G, IN 2-1/2" C #1/0
KEYNOTES
084 45 KVA 400HZ FREQUENCY CONVERTER. PROVIDE 1 SET
OF 3#3, 1#8G IN 1-1/4"C. (BID OPTION 5)
085 90 KVA 400HZ FREQUENCY CONVERTER. PROVIDE 1 SET
OF 3#3/0, 1#6G IN 2-1/2"C. (BID OPTION 5)
227 PROVIDE A 15 KVA 24 POLE INTEGRATED POWER
CENTER WITH A 480V DELTA CONNECTION AND 208/120
WYE OUTPUT.
234 PROVIDE K-RATED TRANSFORMER.
237 COORDINATE INSTALLATION WITH FIRE ALARM
INSTALLER. PAINT PANELBOARD, BREAKER OPERATING
AND PADLOCKING MECHANISMS RED.
240 PROVIDE A JACKETED, PLANETARY WRAPPED CABLE
(SIX PHASE WIRES AROUND ONE NEUTRAL) WITH #2
PHASE CONDUCTORS AND INTEGRAL CONTROL
CONDUCTORS (BID OPTION).
265 PROVIDE AMRS METER.
289 PROVIDE COMMUNICATIONS WIRING IN CONDUIT TO
GENERATOR CONTROL PANEL.
323 PROVIDE PERMANENT ENGRAVED PLACARD THAT SAYS
"SERVICE DISCONNECT 2 OF 3. SERVICE DISCONNECT 1
OF 3 LOCATED AT MSE IN ELECRICAL ROOM 166.
SERVICE DISCONNECT 3 OF 3 LOCATED AT FIRE PUMP
TAP BOX IN FIRE SUPPRESSION EQUIP ROOM 191.
STANDBY GENERATOR IS LOCATED OUTSIDE ELECRICAL
ROOM 166 ON SITE."
324 PROVIDE PERMANENT ENGRAVED PLACARD THAT SAYS
"SERVICE DISCONNECT 3 OF 3. SERVICE DISCONNECTS
1 AND 2 LOCATED IN ELECTRICAL ROOM 166. STANDBY
GENERATOR IS LOCATED OUTSIDE ELECRICAL ROOM
166 ON SITE."
325 PROVIDE ELECTRONIC POWER METER TO ALLOW FOR
SUBMETERING PER SECTION 8.4.3.1 OF ASHRAE 90.1.
TYPICAL FOR ALL ELECTRONIC POWER METERS SHOWN
ON SHEET.
FEEDER SCHEDULE
FEEDER
MARK
PHASE
&NEUTRAL GROUND # OF SET
CONDUIT SIZE
3C+G 4C+G 5C+G
15 12 12 1 3/4" 3/4" 3/4"
20 12 12 1 3/4" 3/4" 3/4"
30 10 10 1 3/4" 3/4" 3/4"
40 8 10 1 3/4" 3/4" 1"
50 6 10 1 3/4" 1" 1"
60 4 10 1 1" 1 1/4" 1 1/4"
70 4 8 1 1" 1 1/4" 1 1/4"
80 3 8 1 1 1/4" 1 1/4" 1 1/4"
90 2 8 1 1 1/4" 1 1/2" 1 1/2"
100 1 8 1 1 1/2" 1 1/2" 2"
110 1 6 1 1 1/2" 1 1/2" 2"
125 1 6 1 1 1/2" 2" 2"
150 1/0 6 1 1 1/2" 2" 2"
175 2/0 6 1 2" 2" 2 1/2"
200 3/0 6 1 2" 2 1/2" 2 1/2"
225 4/0 4 1 2" 2 1/2" 3"
250 250 4 1 2 1/2" 3" 3"
300 350 4 1 3" 3" 3 1/2"
350 500 2 1 3" 4" 4"
400 3/0 2 2 2" 2" 2 1/2"
450 4/0 2 2 2" 2 1/2" 3"
500 250 2 2 2 1/2" 3" 3"
600 350 1/0 2 3" 3" 3 1/2"
700 500 1/0 2 3" 4" 4"
800 300 1/0 3 2 1/2" 3" 3"
1000 400 2/0 3 3" 3" 3 1/2"
1200 350 3/0 4 3" 3" 3 1/2"
1600 400 4/0 5 3" 3 1/2" 3 1/2"
2000 500 500 6 3 1/2" 4" 4"
NTSA1
ONE-LINE DIAGRAM - STANDBY POWER
A
M
R E
V
IS
IO
N
-3
-2
| A-601 |
| M-403 |
| IN101 |
| E-701 - ONE LINE DIAGRAM |
| E-702 - ONE LINE DIAGRAM STANDBY |