W9128F20R0079-Drawings-Am-2.pdf

PDF 9 MB Posted

Attached to
General Billy Mitchell ANGB, WI Hydrant Fuel System Replacement Federal contract opportunity
Solicitation number
W9128F-20-R-0079
Issued by
Department of the Army Corps of Engineers Engineering District Omaha

About this file

This document provides drawings and specifications for a federal contract opportunity to construct a new consolidated fueling facility at General Billy Mitchell ANGB in Wisconsin. Key project elements include aboveground fuel storage tanks, a pump house with control room, a product recovery tank, a POL operations building with laboratory, refueling vehicle parking, truck loading and unloading points, a motor gas storage tank, a diesel storage tank, and supporting facilities. The solicitation number is W9128F-20-R-0079 and was issued by the Department of the Army Corps of Engineers Engineering District Omaha. Interested parties should contact the points of contact listed to request electronic copies of the drawings. The response due date and anticipated award date are not provided.

View the file

Other files for this federal contract opportunity

Other files attached to General Billy Mitchell ANGB, WI Hydrant Fuel System Replacement, newest first.
File Type Posted
Question and Answer related to Projnet question 8737383.pdf PDF
02 41 00-Am4.pdf PDF
W9128F20R0079-Drawings-Am-4.pdf PDF
Amendment 0004 Modification Copy W9128F-20-R-0079.pdf PDF
Amendment 0004 Conformed Copy.pdf PDF
Amendment 0003 W9128F-20-R-0079.pdf PDF
W9128F20R0079-Vol-2-Specs-Am2.pdf PDF
Amendment 0002 W9128F-20-R-0079.pdf PDF
Bid Walk sign in list.pdf PDF
Amendment 0001 W9128F-20-R-0079.pdf PDF
W9128F-20-R-0079am_0001 SPECS Chng.pdf PDF
ARW Form 11 Visitor Access.pdf PDF
Site Walk and Visitor Access Instructions W9128F20R0079.pdf PDF
W9128F-20-R-0079-Vol-2-Specs.pdf PDF
Solicitation Gen. Billy Mitchell W9128F-20-R-0079.pdf PDF
Show all 15

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

U

S

A

R M

Y

C

O R

P S

O

F

E

N G

I N

E E

R S

O M

A H

A

D

I S

T R

I C

T

W

A R

D

R

K W

A Y

K A

N S

C

I T

Y

M

D E

S C

L

C

I L

I T

I E

S

R

E P

L A

C E

M E

N T

G E

N E

R A

L

M

I T

C H

E L

L

I A

P

W

I

US Army Corps of Engineers Omaha District

S O

L I C

I T

A T

I O

N

N

O

D E

S I G

N E

D

B

Y

D E

S C

R I P

T I O

N

M A

R K

S I Z

E

S U

B M

I T

T E

D

B

Y

D A

T E

C O

N T

R A

T

N

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

I S

S U

E

D

A T

E

SHEET ID

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

W F

R

X

R

E S

I G

N

S

U B

M I T

T A

L

R T

A

D

E S

I G

N

S

U B

M I T

T A

L

J U

P

I T

V E

O

M A

H A

N

E

D

R

O D

D Y

F I

A F

ADVERTISEMENT - NOT FOR CONSTRUCTION

\\BMCD\DFS\CLIENTS\ANF\USCOE\NWO\107341_GENMITCHMILCON\DESIGN\CIVIL\SHEETS\MT18-G-001.DWG 6/9/2020 9:04 AM JCEICHENBERGER

G-002

S H

E E

T

I N

D E

X

DRAWING INDEX

NOTE: ALL POL SITE REFERENCE DRAWINGS FOLLOWING FA603 ARE FOR REFERENCE ONLY.

A

M E

N D

M E

AutoCAD SHX Text

M. LITWIN

AutoCAD SHX Text

J. EICHENBERGER

AutoCAD SHX Text

S. MCLAUGHLIN

AutoCAD SHX Text MT18-G-001.dwg

/2

T /2

2"

CL SLEEVE

GALVANIZED STD WEIGHT

STEEL PIPE OR APPROVED

PREFABRICATED SLEEVE 1

TO 2 PIPE SIZES LARGER

THAN CARRIER PIPE SIZE TO

SUIT PIPE SEAL SYSTEM.

COORD WITH MECH

CONCRETE

SLAB OR WALL

STEEL RING 1/4" x 2" ALL

AROUND. GALVANIZE

AFTER ASSEMBLY

OMIT PROJECTION

UNDER SLABS (UNO)

3/16

U N

O

T

/2

3"

T /2

3"

1/2"

SMOOTH DOWEL SHOP EPOXY-

COATED. GREASE ONE END.

PLACE 12" MIN FROM ANY

JOINT INTERSECTION

BACKER ROD AND

SEALANT UNO

CONSTRUCTION JOINT (CJ)

TYP SLAB RST

(SINGLE OR DOUBLE

LAYER AS INDICATED)

CORNER BAR

CORNER BAR

DOWEL BAR

NOTE:

NOTE:

S P

L

IC

E

STD HOOK STD HOOK

S P

L

IC

E

SPLICE

S P

L

IC

E

STD HOOK

SPLICE

S P

L

IC

E CONSTRUCTION JOINT

AS REQUIRED WITH

1 1/2" x 3 1/2" KEYWAY

CORNER BAR SIZE AND

SPACING TO MATCH SIZE AND

SPACING OF LARGER DIAMETER

HORIZONTAL WALL REBAR (UNO).

DOWEL BAR

ALTERNATE HOOK

DIRECTION @

EVERY OTHER BAR

DOWEL BAR SIZE AND SPACING TO MATCH SIZE AND SPACING OF LARGER DIAMETER HORIZONTAL WALL REBAR.

AT CORNERS AT CORNERS AT INTERSECTIONS AT INTERSECTIONS

VERTICAL SURFACE

EXPANSION JOINT FILLER

1/2" TYP UNO

SEALANT AND

BACKER ROD, UNO

FLOOR SLAB

ISOLATION JOINT (IJ)

W16X26

STEEL BEAM SIZE

STANDARD BEAM CONNECTION,

SEE NOTES BELOW

NOTES:

1. UNLESS NOTED OTHERWISE ALL BEAMS ON COLUMN ROW SHALL

BE IN ACCORDANCE WITH TABLE 10-12 CASE 1 OF AISC STEEL

CONSTRUCTION MANUAL 14TH EDITION WITH SHOP WELDS.

2. END CONNECTIONS SHALL BE STANDARD "FRAMED BEAM" SNUG

TIGHTENED WITH THREADS INCLUDED CONNECTIONS PER TABLE 10-1

OF AISC STEEL CONSTRUCTION MANUAL 14TH EDITION.

UNLESS OTHERWISE INDICATED THE FOLLOWING MINIMUMS

APPLY TO TABLE 10-1 CONNECTIONS.

2"

2"

G ¹

GG

G & G¹ = 2" MIN FOR STD HOLES (G¹ = 1 1/4" MIN FOR BEAMS LESS

THAN A W12).

G & G¹ = 2 1/4" MIN FOR OVERSIZED AND SHORT SLOTTED HOLES

(G¹ = 1 3/8" MIN FOR BEAMS LESS THAN A W12).

MINIMUM CLIP ANGLE THICKNESS SHALL BE 3/8", UNO.

TABLE 10-12 CASE 1 WELDS TO BE 3/16".

3. BEAM END CONNECTIONS SHALL BE IN ACCORDANCE

WITH THESE NOTES AND WITH THE FOLLOWING MINIMUM

NUMBER OF HIGH STRENGTH BOLTS:

C6, W6, OR LESS = 2 ROWS W21 = 4 ROWS

C8 OR W8 = 2 ROWS W24 = 5 ROWS

C10 OR W10 = 2 ROWS W27 = 6 ROWS

C12 OR W12 = 2 ROWS W30 = 7 ROWS

W14 = 3 ROWS W33 = 8 ROWS

C15 OR W16 = 3 ROWS W36 = 8 ROWS

W 18 = 4 ROWS

4. THE NUMBER OF BOLTS AND NUMBER OF ROWS OF BOLTS INDICATED

OR STATED IS THE MINIMUM NUMBER OF BOLTS OR ROWS. PROVIDE

ADDITIONAL BOLTS OR CONNECTION DEVICES, IF NECESSARY, TO

COMPLY WITH OSHA REGULATION 29CFR1926 SUBPART R-STEEL

ERECTION.

5. ROWS OF BOLTS: THE NUMBER OF FASTENERS IN A VERTICAL ROW.

6. BEAM CONNECTIONS ARE BASED ON THE USE OF STANDARD,

OVERSIZED OR SHORT-SLOTTED HOLES AS DEFINED BY AISC STEEL

CONSTRUCTION MANUAL 14TH EDITION. LONG-SLOTTED HOLES ARE

NOT PERMITTED, UNLESS INDICATED OTHERWISE.

7. BEAM CONNECTIONS GAGE SHALL BE 5 1/2" MAX GAGE MAY BE

REDUCED AT FABRICATORS OPTION.

G ¹

L4X3 (LLO), UNO L4X3 (LLO), UNO

D

T /2

T

3" MAX

LESSER

OF T/4

OR 3"SMOOTH DOWEL SHOP

EPOXY - COATED. GREASE

ONE END. PLACE 12" MIN

FROM ANY JOINT INTERSECTION

1/8" TO 3/16"

(SAWED OR FORMED)

BACKER ROD

AND SEALANT,

UNO

CONTROL JOINT (CLJ)

TYP SLAB RST

(SINGLE OR DOUBLE

LAYER AS INDICATED)

BUILDING SLAB

TRAFFIC SLAB 1"

3/4"

1'-6"

1'-4"

1'-0"

1'-4"

LOCATION DIAMETER LENGTH SPACING

SMOOTH DOWEL SCHEDULE

NOTES:

1. PROVIDE FUEL RESISTANT JOINT SEALANT, UNO.

2. SLAB CONSTRUCTION JOINTS INDICATED IN THE DRAWINGS MAY

BE REPLACED WITH CONTROL JOINTS, OR VICE-VERSA UPON

CONTRACTING OFFICER'S APPROVAL.

3. OMIT DOWELS IN SLABS 5" AND THINNER.

4. PROVIDE SMOOTH DOWELS IN JOINTS OF THICKENED SLAB EDGES

SIMILARLY AS SHOWN ABOVE.

5. INSTALL DOWELS IN CONTROL JOINTS USING PREFABRICATED

DOWEL BASKET ASSEMBLIES.

NOTES:

ANCHOR COLLAR

FUEL PIPELINE

CL PIPE

L/2

3"T3"

PIPELINE CASING

INSULATOR

1/4" THICK CONT

STEEL ANCHOR

COLLAR (WELD TO

PIPE SLEEVE BOTH

SIDES OF COLLAR)

1. FUEL PIPE, PIPE SLEEVE, CASING PIPE

INSULATORS, SLEEVE AND CASING SEALS - AS

REQUIRED BY THE CONTRACT

SPECIFICATIONS.

2. NON-SHRINK GROUT SHALL BE INSTALLED

AFTER PIPE AND SLEEVE ASSEMBLY HAS BEEN

INSTALLED.

3. DIMENSION "T" TO BE FIELD VERIFIED.

4. DIMENSION "L" TO BE DETERMINED BY

DIMENSION "T".

5. GROUT FILL NOT REQUIRED IF PIPE SLEEVE

IS CAST INTEGRAL/MONOLITHIC WITH WALL.

6. PROVIDE 1" DEEP (MIN) CLEAN SAWCUT ALL

AROUND PRIOR TO ENLARGING THE OPENING.

PRESERVE ALL EXISTING WALL REINFORCING

EXCEPT THOSE INTERFERING WITH THE NEW

SLEEVE. REPLACE REINFORCING CUT OR

DAMAGED BY PLACING NEW REINFORCING OF

SAME SIZE AND QUANTITY ON EACH SIDE OF

THE NEW SLEEVE. DRILL AND EMBED NEW

REINFORCING INTO EXISTING CONCRETE

WALL USING ADHESIVE ANCHORING

COMPOUND. L

SEGMENTED PIPE SEAL (2 TOTAL)

PIPE SLEEVE. COORDINATE SIZE

WITH SEGMENTED PIPE SEAL

REQUIREMENTS.

SEE MF512 FOR SLEEVE DETAIL

RECTANGULAR

OPENING IN WALL

FOR PIPE

PENETRATION WITH

ROUGHENED

INTERFACE

SEE NOTE 6

CL

EXISTING CONCRETE WALL

NON-SHRINK

GROUT FILL

SEE NOTE 6

3/16

CONT FUEL-RESISTANT

SELF-EXPANDING STRIP

WATERSTOP

7.

BACKER ROD AND

JOINT SEALANT

PVC PIPE

SLEEVE

PIPE OR

CONDUIT

FDN WALL OR

GRADE BEAM

Omaha District

US Army Corps of Engineers ®

M A

K

S

C R

IP

T

IO

N

D A

T E

1 2 3 4 5

A

FILE:

DATE:

W

A R

D P

A R

K W

A Y

K A

N S

A S

C

IT

Y

M O

D E

S

IG

N E

D B

Y

D R

A W

N B

Y

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

S O

L

IC

IT

A

T

IO

N N

O

W F

-2 -R

-0

C O

N T

R A

C T

N O

U S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

O M

A H

A D

IS

T

R

IC

T C

A P

IT

O

L A

V E

O

M A

H A

N

E

S

IZ

E

X

SHEET ID

IS

S

U E

D D

A T

E

D E

S C

P

O L F

A C

IL

IT

IE

S

R E

P L A

C E

M E

N T

G E

N E

R A

L M

IT

C

H E

L L I A

P

W I

6 7 8 9 10

B

C

D

E

F

G

F

IL

E N

O

A F

-1

-0

ADVERTISEMENT - NOT FOR CONSTRUCTION

7/24/2020 9:14:12 AM

H S

A H

U D

IN

M P

A T

E L

J H

E

IM

107341S-502MT18

D R

O D

D Y

S-502

J U

N E

S T

A N

D A

R D

S T

R U

C T

U R

A L D

E T

A

IL

S S

H E

E T

NTSSCALE:

F1

TYPICAL PIPE SLEEVE DETAIL

NTSSCALE:

A3

TYP WALL & GRADE BEAM REINFORCEMENT DETAILS

NTSSCALE:

A1

STD BEAM CONNECTIONS

NTSSCALE:

E3

TYP SLAB-ON-GRADE JOINT DETAILS

NTSSCALE:

C3

PIPE SLEEVE THROUGH EXISTING WALL

NTSSCALE:

C8

TYPICAL UTILITY PENETRATION

THROUGH FOUNDATION WALL/GRADE BEAM

R

T A

D E

S

IG

N S

U B

M

IT

T A

L

/2

/2

A

M E

N D

M E

N T

/2 /2

1 1

3/4" CHAMFER, TYP

CONC SLAB

EL PER PLAN

T/RINGWALL

(5) #6 T&B

6-#6 EF FACE BARS

#4 TIES @ 9" OC, PROVIDE

TWO SETS OF TIES ON EACH

SIDE OF ANCHOR BOLTS

(WHERE PRESENT)

TANK BOTTOM

SET HIGH POINT OF RINGWALL AT EDGE

OF TANK CHIME. SET SHELL CENTERED

ON RINGWALL

SLOPE DOWN 5% TO MATCH

TANK BOTTOM SLOPE

SAND BEDDING

GEOTEXTILE FABRIC

FML

2'-0"

PROVIDE 3" OF

SLACK IN FML

ALONG RINGWALL

FML

GEOTEXTILE

FABRIC

" 3" COVER

2" COVER, TYP UNO

FUEL RESISTANT JOINT SEALANT

1/2" MIN ASPHALT IMPREGNATED FIBER BOARD

1'-0"

(8) #6 HORIZ

#4 VERT @ 12"

OC

LEAK DETECTION WELL

4"Ø SCH 40 SS PIPE

AND FITTINGS

TYP RINGWALL RST

PER SECTION

TANK RINGWALL

D5

S-512

1'-0"

1'-0"

2' -0

'-0

D1 / S-512

TANK BOTTOM

TANK SHELL

8" HINGED, LOCKABLE ALUMINUM

GAGE HATCH COVER W/ WATER

TIGHT SEAL

8" SS CASING PIPE. EMBED

16" MIN INTO FOUNDATION

AND FILL VOID W/ GROUT

CONC SLAB

LEAK DETECTION WELL

4" SCH 40 304 SS PIPE

AND FITTINGS

RINGWALL

FOUNDATION

GEOTEXTILE FABRIC

FML

4" THREADED SS

COUPLING (TYP)

4" FRP LEAK

DETECTION

TELL-TALE PIPE

2'-0"

1'-0" 1'-0"

CP/TRACER PIPE

GEOTEXTILE

FABRIC

FML

8" SS PIPE

JOINT SEALANT

AND BACKER ROD

TYP RINGWALL RST

PER SECTION

/8

D1 / S-512

LEAK DETECTION

WELL ADD RST PER

DETAIL A1 / S-512

1'-0"

3'-0"

8"

4'-8"

A6

S-512

TANK BOTTOM

TANK SHELL

RINGWALL

FOUNDATION

GEOTEXTILE FABRIC

CP/TRACER PIPE

1'-0"3'-8"2'-0"

/2

/2

1'-0"

#5 @ 12" OC

HORIZ

#5 @ 12" OC

VERT

#5 @ 12" OC

HORIZ PERIMETER

FML

TYP RINGWALL RST PER

SECTION D1 / S-512

TANK BOTTOM

TANK SHELL

2"

TANK EXTERIOR TANK INTERIOR

1/2" BUNA-N TANK BOTTOM

TO FOUNDATION GASKET1/2"

FUEL RESISTANT

JONT SEALANT.

DO NOT SEAL

END OF CHIME

TOP OF CONCRETE

RINGWALL FOUNDATION

Omaha District

US Army Corps of Engineers ®

M A

S

C R

IP

T

IO

N

D A

T E

1 2 3 4 5

A

FILE:

DATE:

W

A R

D P

A R

K W

A Y

K A

N S

A S

C

IT

Y

M O

D E

S

IG

N E

D B

Y

D R

A W

N B

Y

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

S O

L

IC

IT

A

T

IO

N N

O

W F

-2 -R

-0

C O

N T

R A

C T

N O

U S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

O M

A H

A D

IS

T

R

IC

T C

A P

IT

O

L A

V E

O

M A

H A

N

E

S

IZ

E

X

SHEET ID

IS

S

U E

D D

A T

E

D E

S C

P

O L F

A C

IL

IT

IE

S

R E

P L A

C E

M E

N T

G E

N E

R A

L M

IT

C

H E

L L I A

P

W I

6 7 8 9 10

B

C

D

E

F

G

F

IL

E N

O

A F

-1

-0

ADVERTISEMENT - NOT FOR CONSTRUCTION

7/24/2020 9:14:13 AM

H S

A H

U D

IN

M P

A T

E L

J H

E

IM

107341S-512MT18

D R

O D

D Y

S-512

J U

N E

T A

N K

F O

U N

D A

T

IO

N S

E C

T

IO

N S

A N

D D

E T

A

IL

S

SCALE: 1" = 1'-0"

D1

DETAIL

0 1/2' 1' 2'

SCALE: 1/2" = 1'-0"

A1

DETAIL

0 1' 2' 4'

SCALE: 1" = 1'-0"

D5

LEAK DETECTION WELL

0 1/2' 1' 2'

SCALE: 1/2" = 1'-0"

A4

TANK STAIR LANDING PAD DETAIL

0 1' 2' 4' SCALE: 1" = 1'-0"

A6

SECTION

0 1/2' 1' 2'

R

T A

D E

S

IG

N S

U B

M

IT

T A

L

/2

/2

A

M E

N D

M E

N T

/2 /2

SCALE: 1 1/2" = 1'-0"

E8

UNANCHORED TANK BOTTOM SEAL

. S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

O M

AH

A

D

IS

TR

IC

T

W

AR

D P

AR

KW

AY

KA

N

SA

S C

IT

Y, M O

D

ES

C

P

O L

FA

C

IL

IT

IE

S

R

EP

LA

C

EM

EN

T G

EN

ER

AL

M

IT

C

H

EL

L

IA

P, W

I

US Army Corps of Engineers Omaha District

SO

LI

C

IT

AT

IO

N N

O

D

ES

IG

N

ED

B

Y:

D

ES

C R

IP

TI

O N

M

AR

K

SI

ZE

SU

BM

IT

TE

D B

Y:

D

AT

E

C O

N

TR

AC

T

N O

C

H

EC

KE

D

B Y:

D R

AW

N

B Y:

IS

SU

E D

AT

E:

SHEET ID

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

W

F-

-R

-0

X2

R

TA

D

ES

IG

N S

U

BM

IT

TA

L

/2 9/

R

TA

D

ES

IG

N

S U

BM

IT

TA

L

/2

9/

JU

N

E

C

AP

IT

O

L

AV

E, O

M

AH

A, N

E

D . R

O D

D Y

FI

LE

N O

AF

4-

-0

ADVERTISEMENT - NOT FOR CONSTRUCTION

MF312

SE

C

TI

O

N S

- T

YP

E

III

P U

M

PH

O U

SE

A1 SCALE: 3/8" = 1'-0"

SECTION - PUMP HOUSE RECEIPT FILTRATION AND JOCKEY PUMP

1. REFER TO DRAWINGS MF001 AND MF002 FOR

LEGENDS, ABBREVIATIONS, AND GENERAL NOTES.

2. ALL LARGE BORE MANUAL VALVES LOCATED 72"

(OR GREATER) ABOVE THE FINISHED FLOOR,

SHALL BE PROVIDED WITH CHAIN OPERATORS.

E1 SCALE: 3/8" = 1'-0"

SECTION - PUMP HOUSE ISSUE PUMPS AND FILTRATION

6'

SCALE IN FEET

0 2' 4'

6'

SCALE IN FEET

0 2' 4'

FILTER SEPARATOR (REFER

TO DETAIL FOR SLOW FILL,

DRAIN AND TRV CONNECTION) MF513

A1FILTER

SEPARATOR

ELEMENT

CLEARANCE

REQUIREMENTS

FSI-5

600 GPM

FSCV-5

DR

TRENCH

DR PS

-1

2" SS F/S

SLOW FILL

2" SS TRV/DRAIN

FROM FILTER

SEPARATORS

PS

-9

MAV

PGPG

CV-56" BALL

VALVE

FP-5

600 GPM

PG

PG

DR

PS-4 PDP-1

10 GPM

6" CS

6" C

S

6" BALL

VALVE

TRV

TRV

FLOW

SWITCHMF514

A7

3" SS FLEX

CONNECTOR

3" CHECK

VALVE

6" X 3"

REDUCER

6" CS

4" SS FLEX

CONNECTOR

8" X 4" FOT

REDUCER

16" SUCTION

HEADER

2" SS TRV/DRAIN

TRV

(BEHIND)

DR

PS-1

2" BALL

VALVE

RECEIPT

FLOW

METER MF513

E1

JP-1

5 GPM

PG

2" CS F/S SLOW

FILL (TO TRENCH)

2" Y-STRAINER

1 1/4"

SS FLEX

2" X 1 1/4"

REDUCER

2" CHECK

VALVE

8' -6

MAV

MAV

MAV

MAV

PS-9PS-4A

PS-17PS-17

2" RETURN

FROM PRT PS-17 PS-17 PS-17

PS-4A PS-4

PS

-1

DR

FILTER SEPARATOR

(REFER TO DETAIL FOR

SLOW FILL, DRAIN AND

TRV CONNECTION)

FILTER SEPARATOR

ELEMENT CLEARANCE

REQUIREMENT

MF513

A1

FSR-1

1200 GPM

FSCV-6

PS-14

8" BALL VALVE

(BEHIND)

PG

8" BALL

VALVE

8" CS

8" CS

8" CS

8" CS

'-6

PS

-4

(O N

BY

PA

SS

TRV

8' -6

2" RETURN

FROM PRT

12" CS

12" CS

PS-6

ELECTRICAL/CONTROL

ROOM, ROOF ACCESS

'-6

MAV

NOTES:

TOP OF SLAB

TOP OF CURB

8" BASKET

STRAINER

8" DBB PLUG

VALVE

TOP OF SLAB

TOP OF CURB

PS-15

2" RETURN FROM PRT

℄ ELEVATION: 682'-9"

PS-15

D A

PS-1

AM

EN

D

M

EN

T

/2 7/

AutoCAD SHX Text

B. COOVER

AutoCAD SHX Text

H. HARMON

R. PERUE

. S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

O M

AH

A

D

IS

TR

IC

T

W

AR

D P

AR

KW

AY

KA

N

SA

S C

IT

Y, M O

D

ES

C

P

O L

FA

C

IL

IT

IE

S

R

EP

LA

C

EM

EN

T G

EN

ER

AL

M

IT

C

H

EL

L

IA

P, W

I

US Army Corps of Engineers Omaha District

SO

LI

C

IT

AT

IO

N N

O

D

ES

IG

N

ED

B

Y:

D

ES

C R

IP

TI

O N

M

AR

K

SI

ZE

SU

BM

IT

TE

D B

Y:

D

AT

E

C O

N

TR

AC

T

N O

C

H

EC

KE

D

B Y:

D R

AW

N

B Y:

IS

SU

E D

AT

E:

SHEET ID

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

W

F-

-R

-0

X2

R

TA

D

ES

IG

N S

U

BM

IT

TA

L

/2 9/

R

TA

D

ES

IG

N

S U

BM

IT

TA

L

/2

9/

JU

N

E

C

AP

IT

O

L

AV

E, O

M

AH

A, N

E

D . R

O D

D Y

FI

LE

N O

AF

4-

-0

ADVERTISEMENT - NOT FOR CONSTRUCTION

A1 ENLARGED PLAN - TYPE III HYDRANT SYSTEM PUMP HOUSE

SCALE: 1/4" = 1'-0"

N

MF411

EN

LA

R G

ED

P

LA

N

TY

PE

II

I H

YD

R

AN

T

SY

ST

EM

P

U M

PH

O

SE

AT

C H

LI

N

E

- S

EE

D

R

AW

IN

G

M F4

N

A/C

KEY PLANMF313

A1

MF312

A1

MF312

E1

MF311

A1

MF311

E1

NOTES:

1. REFER TO DRAWINGS MF001 AND MF002 FOR

LEGENDS, ABBREVIATIONS, AND GENERAL NOTES.

2. REFER TO SECTION CUTS FOR CLARITY OF

STACKED PIPING.

3. EXTEND UNDERGROUND FBE COATING A MINIMUM

OF 6 INCHES ABOVE CONCRETE PENETRATION

SLEEVE.

4. ALL LARGE BORE MANUAL VALVES LOCATED 72"

(OR GREATER) ABOVE THE FINISHED FLOOR,

SHALL BE PROVIDED WITH CHAIN OPERATORS.

5. SMALL BORE PIPING IS SHOWN SCHEMATICALLY.

REFER TO P&ID'S FOR SIZES. REFER TO

APPROPRIATE DETAILS ON MF512 TO MF515.

6. REFER TO STRUCTURAL DRAWINGS FOR PIPE

SUPPORT COORDINATION. PUMP HOUSE PIPE

SUPPORT SPACING AS INDICATED ON S-105.

REFER TO S-551 TO S-556 FOR PIPE SUPPORT

DETAILS. PIPES SHALL BE CENTERED ON THE PIPE

SUPPORT FOUNDATIONS.

7. FOR SMALL BORE PIPING ROUTED AROUND THE

PERIMETER OF THE PUMP ROOM, REFER TO PS-16

(ONE PIPE ONLY) AND SUPPORT AT INCREMENTS

NOT TO EXCEED 12 FEET.

8. MOUNT PRESSURE INDICATING TRANSMITTER

INSIDE PUMP ROOM NEAR 8" BALL VALVE MOV.

9. REFER TO MF512, DETAIL A4 FOR JET FUEL

PRODUCT LABELING REQUIREMENTS.

10. REFER TO A-503, DETAIL A3 FOR PIPE

PENETRATION REQUIREMENTS FOR PUMPHOUSE

EXTERIOR WALL PENETRATIONS.

SCALE IN FEET

0 2' 4' 8'

KEYED NOTES:

THE HINGE FOR FILTER SEPARATORS SHALL

OPEN AS INDICATED. MAINTAIN CLEAR SPACE

FOR FILTER PULL DISTANCE.

SUPPORT PIPING WITHIN PIPE TRENCH PER THE

STRUCTURAL TRENCH DETAIL AT INCREMENTS

NOT TO EXCEED 5 FT.

PROVIDE 1" BLIND FLANGE FOR FUTURE

CONNECTION FOR LEAK DETECTION SYSTEM.

12" DBB

PLUG VALVE

(MOTOR

OPERATED)

12" CS

HYDRANT

ISSUE

12" CS

HYDRANT

RETURN

8" DBB PLUG VALVE

8" CS TO TRUCK FILLSTAND

4" BALL VALVE W/BLIND (KICKER

FOR PIG LAUNCHER / RECEIVER)

PS-4

12" FULL BORE

DBB PLUG

VALVES

(TYP OF 2)

12" TEMPORARY

PIG LAUNCHER

EXTENSION (NIC)

12" TEMPORARY

PIG RECEIVER

EXTENSION (NIC)

PS-4

4" BALL VALVE W/

BLIND (KICKER FOR PIG

LAUNCHER / RECEIVER)

12" DBB PLUG VALVE

(MOTOR OPERATED)

PS-4A

PS-6

PS-7

PS-7

PS-4

PS-4C

PS-8

PS-4

PS-4A

PS-4

PS-14

PS-14

PS-10

PS-4A

PS-5

PS-4

PS-4

PS-4

PS-4

PS-4

PS-9

PS-4D PS-4

PS-6C

PS-6

PS-8

PS-4

PS-4C

PS-4

PS-15

PS-15

PG

PG

PC

V-

MAV

MAV

MAV

PS-4CSURGE

SUPPRESSOR

(TYP OF 2)MF513

D7

FSI-5

600 GPM

FSI-4

600 GPM

FSI-3

600 GPM

FSI-2

600 GPM

FSI-1

600 GPM

FSR-2

1200 GPM

FSR-1

1200 GPM 1

FSCV-5

FSCV-4

FSCV-3

FSCV-2

FSCV-1

FSCV-7

FSCV-6

8" BV

8" BALL VALVE

(SEE NOTE 4)

MAV

MAV

MAV

MAV

MAV

MAV

MAV

D /F

V-

B

PC

V-

(B

EL

O W

8" CS

8" CS

8" DBB PLUG VALVE

8" CS FROM HHT

CHECKOUT

8" DBB PLUG VALVE

8" CS FROM TRUCK

OFFLOADING

8" BLIND FLANGE

8" FUTURE RECEIPT

FROM COMMERCIAL

AIRPORT

8" BASKET

STRAINER

8" BALL

VALVE (IN THE

VERTICAL)

8" CS

8" C

S

8" CS

8" C

S

FLOOR

TRENCH

" C

S

" C

S

" C

S

" C

S

12" CS

10" CS

10" ISSUE

VENTURI

CV-5

CV-4

CV-3

CV-2

CV-1

FP-2

600 GPM

FP-3

600 GPM

FP-4

600 GPM

FP-5

600 GPM

PRESSURE

TRANSMITTER

(FP-1 ONLY)

6" BALL VALVE,

SEE NOTE 4

(TYP OF 5)

4" FLEX

CONNECTOR

(TYP OF 5)

8" X 4" FOT

REDUCER

PG

PG

FLOW

SWITCH

(TYP OF 5)MF514

A7

8" BASKET

STRAINER

(TYP OF 5)

8" DBB PLUG

VALVE (TYP OF 5)

16" ELBOW, ROLLED

MATCH PUMP

CENTERLINE ELEVATION

8" ELBOW

8" CS

PS-4C

SEE CONTINUATION ON MF412

MAV

8" BALL VALVE

(MOTOR OPERATED)

MAV

PS-7

TRV

TRV

PDP-1

10 GPM

2" BALL VALVE

2" WAFER

CHECK VALVE

2" CHECK VALVE

2" CS PRODUCT RETURN

℄ ELEVATION: 684'-0"

2" SS DRAIN/TRV TO PRT

℄ ELEVATION: 682'-9"

16" CS F-24 SUCTION

8" CS F-24 TANK 2 FILL

8" CS F-24 TANK 1 FILL

PG

TRV

S

JP-1

5 GPM

TRV

TRV

TRV TRV

2" RETURN

FROM PRT

8" BV

8" BV

8" BV

8" B

V

2" SS DRAIN/TRV

2" SS F/S SLOW FILL

FLOOR

TRENCH

2" SS DRAIN/TRV

2" SS F/S SLOW FILL

TRV

TRV

8" DBB PLUG

VALVES WITH

LIMIT SWITCHES

(TYP OF 4)

PG

8" BV

2" Y-

STRAINER

1 1/4" FLEX

CONNECTOR

PG

2" SS

DRAIN/TRV

8" CS

8" CS

2" BV

TRV

MAV

PG

2" SS DRAIN/TRV

℄ELEVATION: 681'-9"

2" BALL VALVE

2" BASKET

STRAINER

PS-4A

PG

2" BALL

VALVEMAV

MAV

TRV

TRV

TRV

FLOOR

TRENCH2

TRV TRV

TRV

TRV

2" BALL VALVE

(MOTOR OPERATED)

PRESSURE

INDICATING

TRANSMITTER

SEE NOTE 8

PS-15

PS-15

PS-15

PS-15

PS-15

PS-15

PS-15

2" SS F/S

SLOW FILL

PG

PG

PG

6" BV

6" BV

6" BV

6" BV

6" BVPG

SRV-2

PG

PS-17 PS-17 PS-17 PS-17 PS-17

S

2" BV

TRV

TRV

TRV

TRV

TRV

TRV

TRV8" BV

2" RETURN

FROM PRT

2" CS PRODUCT RETURN

℄ ELEVATION: 694'-0"

2" CS PRODUCT RETURN

℄ ELEVATION: 682'-9"

1/2" FUTURE

MONITORING POINT

2" SS DRAIN/TRV

℄ELEVATION: 681'-9"

MAV

CV-7PS-3A

IF

IFIF

IF

12" CS F-24

℄ ELEVATION: 683'-0"

12" CS F-24

℄ ELEVATION: 683'-0"

IF

IF

IF

IF

1" BLIND FOR

FUTURE TRV

10" CS

PS-18 (BELOW)

PS-18 (BELOW)

ISOLATED EQUIPMENT

PAD

CONCRETE PENETRATION

SLEEVE (TYP OF 3)

CONCRETE

PENETRATION

SLEEVE (TYP OF 2)

ISOLATED

EQUIPMENT PAD

MATCHLINE - SEE DRAWING MF101

MATCHLINE - SEE DRAWING MF101

M

AT

C H

LI

N

E

- S

EE

D

R

AW

IN

G

M F1

DR

16" TEE, ROLLED

2" DBB (TYP OF 2) FP-1

600 GPM FLOW

SWITCH

12" BARRED TEE

(TYP OF 2)

FLOW

SWITCH

AM

EN

D

M

EN

T

/2 7/

AutoCAD SHX Text

B. COOVER

AutoCAD SHX Text

H. HARMON

MECHANICAL

CONSTRUCTION PHASING

U . S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

O M

AH

A

D

IS

TR

IC

T

W

AR

D P

AR

KW

AY

KA

N

SA

S C

IT

Y, M O

D

ES

C

P

O L

FA

C

IL

IT

IE

S

R

EP

LA

C

EM

EN

T G

EN

ER

AL

M

IT

C

H

EL

L

IA

P, W

I

US Army Corps of Engineers Omaha District

SO

LI

C

IT

AT

IO

N N

O

D

ES

IG

N

ED

B

Y:

D

ES

C R

IP

TI

O N

M

AR

K

SI

ZE

SU

BM

IT

TE

D B

Y:

D

AT

E

C O

N

TR

AC

T

N O

C

H

EC

KE

D

B Y:

D R

AW

N

B Y:

IS

SU

E D

AT

E:

SHEET ID

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

W

F-

-R

-0

X2

R

TA

D

ES

IG

N S

U

BM

IT

TA

L

/2 9/

R

TA

D

ES

IG

N

S U

BM

IT

TA

L

/2

9/

JU

N

E

C

AP

IT

O

L

AV

E, O

M

AH

A, N

E

D . R

O D

D Y

FI

LE

N O

AF

4-

-0

ADVERTISEMENT - NOT FOR CONSTRUCTION

MF801

M

EC

H

AN

IC

AL

E Q

U

IP

M

EN

T

SC

H

ED

U

LE

S (1

O F

2)

AM

EN

D M

EN

T

/2

7/

AutoCAD SHX Text

B. COOVER

AutoCAD SHX Text

H. HARMON

X

X

X

U

P

U

P

U P

U P

U

P

U P

U P

U

P

U P

U P

U

P

U P

U

P

UP

UP

UP

UP

UP

UP

UP

UP

UP

UP

UP

UP

UP

UP

UP

UP

UP

U

P

U

P

U

P U

P

U

P

U

E

U

C

UE/UC UE/UC UE/UC UE/UC UE/UC UE/UC UE/UC UE/UC

U

C

U

C

U

E

U

C

U E

U

C U

E U

C U

E U

C U

E U

C U

E U

C

U

E

U

C

U

E

U

E

U

E

U

C

U

E

U

C

U

E

U

C

U

E

U

C

UE/UC

U E

U

C U

E U

C U

E U

C U

E U

C U

E U

C

UE/UCUE/UC

U

E

U

C

U

E

U

C

U

E

U

C

U

E

U

C

U

E

U

C

U

E

U

C

U

E

U

C

MM

U

S

A

R M

Y

C

O R

E

N G

I N

E E

R S

O M

A H

A

D

I S

T R

I C

T

R

K W

A Y

K A

N S

T

Y

D E

S C

C

I L

I T

I E

S

R

E P

L A

C E

M E

N T

G E

N E

R A

L

M

I T

C H

E L

L

I A

P

W

I

US Army Corps of Engineers

Omaha District

S O

L I C

I T

A T

I O

N

N

O

D E

S I G

N E

D

B

Y

D E

S C

R I P

T I O

N

M A

R K

S I Z

E

S U

B M

I T

T E

D

B

Y

D A

T E

C O

N T

R A

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

I S

S U

E

D

A T

E

SHEET ID

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

W F

R

X

R

S

I G

N

S

U B

M I T

T A

L

R T

A

D

E S

I G

N

S

U B

M I T

T A

L

J U

P

I T

E

O

M A

H A

N

E

D

R

O D

D Y

F I

A F

ADVERTISEMENT - NOT FOR CONSTRUCTION

\\BMCD\DFS\CLIENTS\ANF\USCOE\NWO\107341_GENMITCHMILCON\DESIGN\ELEC\SHEETS\MT18-E-091.DWG 7/23/2020 8:31 PM LHURST

E-091

H A

Z A

R D

O U

S

A

R E

A

C

L A

S S

I F

I C

A T

I O

N

P

L A

N

A1

HAZARDOUS AREA CLASSIFICATION PLAN

SCALE: 1"=30'

N

30' 60'0

UTILITY

TRANSFORMER

UTILITY

METERING

STAND-BY

GENERATOR

DISPENSERS (TYP)

PRODUCT SAVER

TANK (TYP)

PUMP HOUSE

REMOTE

CONTAINMENT BASIN

JET FUEL TANK 1

(5K BBL)

JET FUEL TANK 2

(5K BBL)

TRUCK OFFLOAD

POSITION #2

TRUCK OFFLOAD

POSITION #1

REFUELER LOAD

POSITION # 1 & HHTCS

REFUELER LOAD

POSITION #2

EXISTING SMALL

ARMS RANGE

DIESEL AND

MOGAS TANKS

POL OPS

BUILDING

(TYP)

E1

E-093

C1

E-093

E1

E-093

A1

E-092

A7

E-093

A1

E-092

C7

E-093

FITTINGS, FLANGES,

VALVES (TYP)

A1

E-093

PRODUCT

RECOVERY TANK

FUEL OFFLOADING

TRUCK

A5

E-092

TRANSITION SUMP

A7

E-093

STRAINER (TYP)

C1

E-093

STRAINER (TYP)

C1

E-093

OIL/WATER

SEPARATOR

(OWS-01)

D1

E-092

OIL/WATER

SEPARATOR

(OWS-02)

1. ALL EQUIPMENT INSTALLED WITHIN HAZARDOUS

AREAS SHALL BE LABELED AS SUITABLE FOR

USE IN THE HAZARDOUS AREA. ALL ELECTRICAL

EQUIPMENT SHALL BE INSTALLED IN

ACCORDANCE WITH NEC REQUIREMENTS FOR

SUCH AREAS.

2. ALL HEAT-PRODUCING EQUIPMENT SHALL BE

LABELED WITH AN NEC TEMPERATURE

IDENTIFICATION CODE OF T3 MINIMUM (E.G. T3A

IS ACCEPTABLE, T2D IS UNACCEPTABLE).

3. THIS DRAWING REPRESENTS GENERAL

IDENTIFICATION OF HAZARDOUS AREA

CLASSIFICATIONS. REFER TO THE DETAILS ON

E-092 AND E-093, SPECIFICATIONS, API 500, AND

NEC ARTICLES 500, 501, 514 AND 515 FOR

ADDITIONAL REQUIREMENTS.

4. THIS FACILITY RECEIVES/DISTRIBUTES THE

FOLLOWING PRODUCTS ASSOCIATED WITH THIS

PROJECT:

- F-24 - CLASS II LIQUID

- MOGAS - CLASS I LIQUID

- DIESEL - CLASS II LIQUID

CLASS II LIQUIDS SHALL BE CONSIDERED CLASS

I WHEN PRESSURIZED PER UFC 3-460-01.

AREA WITHIN LAB AND LESS THAN 48" AFF SHALL

BE CONSIDERED A CLASS I, DIVISION 2, GROUP D

HAZARDOUS LOCATION. AREA WITHIN 5' OF LAB

FUME HOOD SHALL BE CONSIDERED A CLASS I,

DIVISION 1, GROUP D HAZARDOUS LOCATION.

(REQUIREMENTS PER ANG ETL 15-01-05)

AREA WITHIN SPILL CONTAINMENT BASIN SHALL

BE CONSIDERED A CLASS I, DIVISION 1, GROUP D

HAZARDOUS LOCATION. AREA ABOVE BASIN TO

A HEIGHT OF 18" AND OUT TO 15' FROM EDGE OF

BASIN SHALL BE CONSIDERED A CLASS I,

DIVISION 2, GROUP D HAZARDOUS LOCATION.

DIVISION 2, 10' TRANSITION ZONES AROUND

DOORS AND EXHAUST.

HAZARDOUS AREAS PER UFC 3-460-01, CHAPTER

4.

REFER TO ES501 FOR SEAL-OFF REQUIREMENTS

WHEN TRANSITIONING BETWEEN HAZARDOUS

AREAS / BOUNDARIES. REFER TO ES502 FOR

SEAL-OFF INSTALLATION DETAIL INSIDE

MANHOLES.

CLASS I, DIVISION 1, GROUP D

(REQUIRES T3 RATED MOTORS/EQUIPMENT)

CLASS I, DIVISION 2, GROUP D

(REQUIRES T3 RATED MOTORS/EQUIPMENT)

NON-CLASSIFIED

NOTES:

KEYED NOTES:

LEGEND:

FUEL PIT

FUTURE PIPELINE

RECEIPT

D1

E-092

A5

E-092

TRUCK OFFLOAD

(TYP)

A

M E

N D

M E

S

A

R M

Y

C

O R

E

N G

I N

E E

R S

O M

A H

A

D

I S

T R

I C

T

R

K W

A Y

K A

N S

T

Y

D E

S C

C

I L

I T

I E

S

R

E P

L A

C E

M E

N T

G E

N E

R A

L

M

I T

C H

E L

L

I A

P

W

I

US Army Corps of Engineers

Omaha District

S O

L I C

I T

A T

I O

N

N

O

D E

S I G

N E

D

B

Y

D E

S C

R I P

T I O

N

M A

R K

S I Z

E

S U

B M

I T

T E

D

B

Y

D A

T E

C O

N T

R A

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

I S

S U

E

D

A T

E

SHEET ID

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

W F

R

X

R

S

I G

N

S

U B

M I T

T A

L

R T

A

D

E S

I G

N

S

U B

M I T

T A

L

J U

P

I T

E

O

M A

H A

N

E

D

R

O D

D Y

F I

A F

ADVERTISEMENT - NOT FOR CONSTRUCTION

E-092

H A

Z A

R D

O U

S

A

R E

A

C

L A

S S

I F

I C

A T

I O

N

D

E T

A I L

S

CLASS I, DIVISION 1, GROUP D

(REQUIRES T3 RATED MOTORS/

EQUIPMENT)

CLASS I, DIVISION 2, GROUP D

(REQUIRES T3 RATED MOTORS/

EQUIPMENT)

NON-CLASSIFIED

LEGEND:

10'

A1

TYPICAL ABOVEGROUND HORIZONTAL STORAGE TANK

SCALE: NTS

10'

D1

TYPICAL UNDERGROUND STORAGE TANK

SCALE: NTS

1. THIS DRAWING REPRESENTS GENERAL

IDENTIFICATION OF HAZARDOUS AREA

CLASSIFICATIONS. REFER TO THE SPECIFICATIONS,

API 500, AND ARTICLES 500, 501, 514, AND 515 FOR

ADDITIONAL REQUIREMENTS.

NOTES:

GRADE

SOURCE BENEATH

HAZARDOUS AREA

SOURCE BENEATH

NON-CLASSIFIED AREA

NON-CLASSIFIED

AREA

HAZARDOUS AREA WITH

ABOVE GRADE SOURCE

10'

A5

BELOW GRADE TRENCH CONTAINING PIPING WITH

VALVES, SCREWED FITTINGS, FLANGES OR SIMILAR -

OUTDOORS

SCALE: NTS

POSITION AND NUMBER OF VENTS, MANWAYS, ETC. DEPENDENT ON TANK FABRICATORS.

SPACE ABOVE FUEL AND WITHIN THE TANK SHELL IS A CLASS I, DIVISION 1 AREA.

KEYED NOTES:

PUMP NOZZLE

TANK NOZZLE

WITH FLANGE

GAUGE HATCH

5 RADIUS

10' RADIUS

SUMP NOZZLE

WITH FLANGE

MANWAY

3' RADIUS

VENT

5' RADIUS

10' RADIUS

TANK NOZZLE

WITH FLANGE

3' RADIUS

(TYP)

GRADE

SURFACE OF

CONTENTS

ABOVE GROUND

STORAGE TANK

5' RADIUS

(TYP)

MANUAL

GAUGING

HATCH

MANWAY(TYP)

VENT

10' RADIUS

5' RADIUS

12' ABOVE

GRADE

10' RADIUS

A

M E

N D

M E

S

A

R M

Y

C

O R

E

N G

I N

E E

R S

O M

A H

A

D

I S

T R

I C

T

R

K W

A Y

K A

N S

T

Y

D E

S C

C

I L

I T

I E

S

R

E P

L A

C E

M E

N T

G E

N E

R A

L

M

I T

C H

E L

L

I A

P

W

I

US Army Corps of Engineers

Omaha District

S O

L I C

I T

A T

I O

N

N

O

D E

S I G

N E

D

B

Y

D E

S C

R I P

T I O

N

M A

R K

S I Z

E

S U

B M

I T

T E

D

B

Y

D A

T E

C O

N T

R A

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

I S

S U

E

D

A T

E

SHEET ID

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

W F

R

X

R

S

I G

N

S

U B

M I T

T A

L

R T

A

D

E S

I G

N

S

U B

M I T

T A

L

J U

P

I T

E

O

M A

H A

N

E

D

R

O D

D Y

F I

A F

ADVERTISEMENT - NOT FOR CONSTRUCTION

ES102

D U

C T

B A

S

A

G R

A M

A1

RISER DIAGRAM

SCALE: NTS

JET A TANKS

PRT OWS-01

REFUELER

LOAD #1 AND

HHTCS

OFFLOAD #1 OFFLOAD #2

REFUELER

LOAD #2

EMH-04,

CMH-04

PUMPHOUSE

TMH-01,

EMH-01,

CMH-01

TMH-02,

EMH-02,

CMH-02

U

E

U

C

U

E

U

C

U

E

U

C

U

E

U

C

TMH-03,

EMH-03,

CMH-03

TMH-04,

EMH-05,

CMH-05

U

E

U

C

U

E

U

C

U

E

U

C

U

E

U

C

UE/UC UE/UC UE/UC UE/UC UE/UC

U

E

U

C

U

E

U

C

UE/UC UE/UC UE/UC UE/UC UE/UC UE/UC

U

E

U

C

U

E

U

C

U

E

U

C

U

E

U

C

U

E

U

C

U

E

U

C

U

E

U

C

U

E

U

C

U

E

U

C

U

E

U

C

U

E

U

C

U

E

U

C

U E

U

C U

E U

C U

E U

C U

E U

C U

E U

C U

E U

C U

E U

C U

E U

C

U

E

U

C

REFUELER

PARKING

POL

OPERATIONS

BUILDING

UE/UCUE/UC

REFER TO EP411 FOR

CONDUIT SCHEDULE

FOR THIS DUCTBANK

SECTION

U E

U

C

U E

U

C

U E

U

C

S55

GATE OPERATOR

(EAST)

TO MSS

(SEE EP451)

U

E

U

C

TO EPDS-8D &

GATE

OPERATOR

(NORTH)

U E

U

C

TO

MH27P7

U

E

U

C

TO

LIGHT

POLE

U

E

U

C

S39

TO

LIGHT

POLE

U

E

U

C

TO

LIGHT

POLE

U

E

U

C

U

E

U

C

TO SOUTH

ROAD

S54

DUCTBANK,

MANHOLES, AND

ASSOCIATED

SOUTH ROADWAY

CIRCUITS ARE

PART OF BID

OPTION 008.

U

E

U

C

TO

EPDS-8C

1. THIS SHEET IS DIAGRAMMATIC AND NOT TO

SCALE. REFER TO ES101, ES103, AND

SHEETS INDICATED FOR CONDUIT ROUTING

AND UNDERGROUND STRUCTURE DETAILS.

NOTES:

MAINTAIN ADEQUATE SEPARATION FOR

INTRINSICALLY SAFE CIRCUITS THROUGH

COMMUNICATION MANHOLES AS REQUIRED

BY NFPA 70, 504.30.

KEYED NOTES:

(TYP)

43 5

S

1615 S47

6 1817

1019 S20

87 11

P I/C T

S

47 S

10S27

8 15

P

I/C T

6 18

2221 23

2624 S

S32

127 14

PI/C

14 24

26 S

S29

PI/C

S

S

PI/C

7 21

23 S

S31

PI/C

S

56 S

36S39

P

I/C T

S51

S38

P I/C

S49 S

PI/C

S50S

P I/C

S45S

P I/C

44 S S

PI/C

56 S

PI/C

T

S

I/C

P

S

46 S

34S52

P

I/C T

S39

P

S53

P

P

P

P I/C

REFER TO DETAIL E1, SHEET

ES501 FOR DUCTBANK

SEPARATION REQUIREMENTS

(TYP)

E

C

T

E

C

T

E

C

T

E

C

T

E

C

A

M E

N D

M E

S

A

R M

Y

C

O R

E

N G

I N

E E

R S

O M

A H

A

D

I S

T R

I C

T

R

K W

A Y

K A

N S

T

Y

D E

S C

C

I L

I T

I E

S

R

E P

L A

C E

M E

N T

G E

N E

R A

L

M

I T

C H

E L

L

I A

P

W

I

US Army Corps of Engineers Omaha District

S O

L I C

I T

A T

I O

N

N

O

D E

S I G

N E

D

B

Y

D E

S C

R I P

T I O

N

M A

R K

S I Z

E

S U

B M

I T

T E

D

B

Y

D A

T E

C O

N T

R A

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

I S

S U

E

D

A T

E

SHEET ID

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

W F

R

X

R

S

I G

N

S

U B

M I T

T A

L

R T

A

D

E S

I G

N

S

U B

M I T

T A

L

J U

P

I T

E

O

M A

H A

N

E

D

R

O D

D Y

F I

A F

ADVERTISEMENT - NOT FOR CONSTRUCTION

ES504

E L E

C T

R I C

A L

S

I T

E

D

E T

A I

E

L E

V A

T I O

N S

1. REFER TO E-001 FOR LEGEND,

ABBREVIATIONS AND GENERAL NOTES.

2. REFER TO CONDUIT SCHEDULE ON SHEET

EP451 FOR CIRCUIT IDENTIFICATIONS.

NOTES:

HYDRANT FUELS

EMERGENCY

SHUTDOWN

EPDS SIGN

EPDS PUSHBUTTON

TOP OF

CONCRETE

GALVANIZED

C6x8.2 MEMBER

SEAL-OFF (TYP)

1. MOUNTING TO CONCRETE (SEE LEFT DETAIL)

2. PIER FOUNDATION IN NON-PAVED AREA (SEE RIGHT DETAIL).

CONSTRUCT EPDS STAND

USING VERTICAL,

GALVANIZED C6x8.2

MEMBERS AND PIER

FOUNDATION. PIER

FOUNDATION SHALL BE 18"

DIAMETER WITH 3'-0"

MINIMUM DEPTH.

GRADE

E1

EMERGENCY POWER DOWN SYSTEM (EPDS)

SCALE: NTS

MAINTAINED RED MUSHROOM PUSHBUTTON

WITH GUARD, HERMETICALLY SEALED

NORMALLY-CLOSED CONTACT AND LEGEND

PLATE WITH "PUSH TO STOP" ON RED

BACKGROUND. MOUNT PUSHBUTTON,

GUARD, AND LEGEND PLATE ON FACE OF

NEMA 4X BOX.

SEE DETAIL TO LEFT FOR

STATION SIGNAGE,

SEAL-OFF, AND GROUNDING

REQUIREMENTS

E5

ELEVATION - POL BUILDING WEST WALL VIEW

SCALE: NTS

RELAY

CONTROL

PANEL

TO MSS

NOTES:

STAINLESS STEEL

MOUNTING SCREW

QUANTITY AND LOCATION

AS REQUIRED (TYP)

84"

AG

(MINIMUM)

LETTERS 2"

HIGH

3/4" SPACE

(TYP)

1. PAINTED ALUMINUM SIGN OF THICKNESS SUITABLE FOR APPLICATION.

2. EUROSTILE BOLD EXTENDED STYLE LETTERS.

3. COLORS: LETTERS - RED

BACKGROUND - WHITE

4. PAINT SCREW HEADS TO MATCH SIGN COLOR.

5. PROVIDE SIGN WITH "MSS FUELS EMERGENCY SHUTDOWN" FOR MSS STATIONS.

HYDRANT FUELS

EMERGENCY

SHUTDOWN

18"

13"

A5

EPDS SIGN

SCALE: NTS

5" 2"

1/4

2"

9"

TOP OF

CONCRETE PAD

GALVANIZED C6x8.2

MEMBER

3/4" BASE PLATE

(4) 5/8" DIAMETER,

EXPANSION ANCHORS, 4"

MINIMUM EMBEDMENT

TO GROUND GRID OR

ROD AS INDICATED ON

DETAILS OR PLANS

#1/0 BOLTED GROUND CABLE.

DRILL HOLE PRIOR

TO GALVANIZING

A1

TYPICAL CONCRETE PAD & PIER FOUNDATIONS

SCALE: NTS

C1

EQUIPMENT RACK BASEPLATE

SCALE: NTS

ES504

C1

4'-0"

MAX

(TYP)

A1

ES504

(TYP)

GRADE

DIP-2

DIESEL

MS

TO ATG PANEL IN

POL BUILDING

CONTROL ROOM

3/4"C: T.TC.RCP

NOTES:

1. ELECTRICAL DEVICES SHALL BE FURNISHED AS

PACKAGED UNIT WITH EEW/S SYSTEM AND INSTALLED BY

ELECTRICAL CONTRACTOR.

2. ALL COMPONENTS AND WIRING SHALL MEET CLASS I, DIV 1

OR 2 REQUIREMENTS WHEN LOCATED WITHIN

HAZARDOUS AREAS, REFER TO SHEET E-091.

3. PROVIDE ADDITIONAL RELAY(S), AS NECESSARY, FOR POL

BUILDING EEW/S ALARM OUTPUTS TO BAS PANEL AND

FIRE ALARM PANEL.

4. REFER TO P501 FOR MECHANICAL EEW/S DETAILS.

VISUAL FLASHING LIGHT

AUDIBLE HORN

CONDUIT

SEAL (TYP)

JUNCTION

BOX (TYP)

SILENCE SWITCH

120V CIRCUIT AS

IDENTIFIED ON PLANS

NOTES:

GRADE

7'-0" A.G.

A7

EEW/S ALARM DETAIL

SCALE: NTS

FLOW SWITCH

(DPDT)

TO MCC

(POL BUILDING -

SEE NOTE 3)

HOT-DIPPED

GALVANIZED 1-5/8"

STRUT CHANNELS

AS NECESSARY (TYP

HORIZONTAL

MEMEBERS)

A5

ES504

1"C: C.RCP.PCP,

C.MSS.EPDS1

VERTICAL, GALVANIZED

C6x8.2 MEMBERS AND

PIER FOUNDATION. PIER

FOUNDATION SHALL BE

18" DIAMETER WITH 3'-0"

MINIMUM DEPTH.

GRADE

SEE DETAIL TO LEFT FOR

RACK CONSTRUCTION AND

GROUNDING

REQUIREMENTS

3/4"C: C.MSS.EPDS1

1"C: MSS-2, -4, & -6

1"C: PB-15;

1"C: PB-21

DIP-1

MOGAS

MS

OP-3

MOGAS

MS

OP-4

DIESEL

MS

3/4"C: C.RCP.MSMS

1"C: MSS-1;

1"C: MSS-5

3/4"C: C.RCP.DSMS

3/4"C: C.RCP.MOMS;

3/4"C: C.RCP.DOMS

1"C: C.RCP.EPDS.M6

3/4"C: C.RCP.ATG

S

A

M E

N D

M E

KB

W P

KB

KBKB

U

S

A

R M

Y

C

O R

E

N G

I N

E E

R S

O M

A H

A

D

I S

T R

I C

T

R

K W

A Y

K A

N S

T

Y

D E

S C

C

I L

I T

I E

S

R

E P

L A

C E

M E

N T

G E

N E

R A

L

M

I T

C H

E L

L

I A

P

W

I

US Army Corps of Engineers

Omaha District

S O

L I C

I T

A T

I O

N

N

O

D E

S I G

N E

D

B

Y

D E

S C

R I P

T I O

N

M A

R K

S I Z

E

S U

B M

I T

T E

D

B

Y

D A

T E

C O

N T

R A

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

I S

S U

E

D

A T

E

SHEET ID

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

W F

R

X

R

S

I G

N

S

U B

M I T

T A

L

R T

A

D

E S

I G

N

S

U B

M I T

T A

L

J U

P

I T

E

O

M A

H A

N

E

D

R

O D

D Y

F I

A F

ADVERTISEMENT - NOT FOR CONSTRUCTION

EP411

P U

M P

H O

U S

E

C

O N

T R

O

M

P

O W

A

N

4'0 2' 8'

1. ALL METALLIC CONDUITS THAT ARE NOT

ATTACHED TO A GROUNDED PANEL OR

ENCLOSURE SHALL BE GROUNDED USING

A GROUNDED BUSHING.

2. CIRCUITS IDENTIFIED IN PLAN A1 ARE

FROM CONTROL ROOM EQUIPMENT TO

CONTROL ROOM EQUIPMENT AND THOSE

IN PLAN A4 ARE FROM CONTROL ROOM

EQUIPMENT TO EXTERNAL EQUIPMENT.

NOTES:

MCC-PH

IPC-PH

COMMUNICATIONS

BACKBOARD

PCP

ATG

BACKBOARD

WALL- MOUNTED

GPD

FIRE

ALARM

PANELS

UPS-3

A1

PUMPHOUSE CONTROL ROOM INTERIOR CIRCUIT POWER PLAN

SCALE: 3/8" = 1'-0"

N

DESK FOR PC, MONITOR,

TELEPHONE, AND PRINTER

MDS-PH

PANEL FA

PROVIDE ANGLED WALL-MOUNT FOR GDP AND COORDINATE

MOUNTING HEIGHT WITH ANG PERSONNEL DURING CONSTRUCTION.

RECEPTACLES SHALL BE TIED TOGETHER ON CIRCUIT SPECIFIED ON

PANEL PC SCHEDULE ON DRAWING EP701.

PROVIDE GENERATOR SHUTDOWN KNOX BOX PER GENERAL

MITCHELL STANDARD AND ROUTE 1" CONDUIT TO GENERATOR

CONTROL PANEL.

REFER TO EP601 FOR REQUIRED ZONE SELECTIVE INTERLOCKING

BETWEEN MCC-PH AND MDS-PH BREAKERS.

KEYED NOTES:

UPS-3

UPS-3

1" C:

PC-19,21,23

EPDS-2

PC-25

PC-35

(3) 4"C:

P.MDS.MCC

1"C:

I.BAS.DM

P.MCC.FA

2"C:

C.MCC.PCP.1-9,

C.MCC.PCP,

C.MCC.EPDS2;

1"C:

C.MCC.EPDS4;

1"C:

C.MCC.FACP;

1"C:

C.MCC.CB;

1"C:

C.MCC.BAS

1"C:

C.MCC.EPDS3

3/4"C:

FA-1, FA-2

1"C: C.ATG.PCP;

1"C: SPARE

2-1/2"C:

P.MCC.PA

PC-9

UPS-3

(EPDS

SYSTEM)

4'0 2' 8'

A4

PUMPHOUSE CONTROL ROOM EXTERIOR CIRCUIT POWER PLAN

SCALE: 3/8" = 1'-0"

N

MCC-PH

IPC-PH

COMMUNICATIONS

BACKBOARD

PCP

ATG

BACKBOARD

WALL- MOUNTED

GPD

FIRE

ALARM

PANELS

GENERATOR

CONTROL PANEL

CABINET

DESK FOR PC, MONITOR,

TELEPHONE, AND PRINTER

MDS-PH

PANEL FA

EPDS-2

262524

34 35

4 6 9 12 16 20 23

30 31

32 33

29 38 39 40 4142

(3) 4"C:

P.MTR.MDS

(2) 4"C:

P.GEN.MDS;

1"C:

I.GEN.RGEN

2"C:

SPARE

2"C:

PC-10

TO GEN-PH &

UTILITY METER

TO MANHOLES

U

E

U

C

TO PUMPHOUSE

(SEE SHEET EP412

FOR CONTINUATION)

EPDS-4

EPDS-3

EPDS-4

EPDS-3

HOUSEKEEPING

PAD

TIGHTNESS

TEST PANEL

UPS-3

1"C:

C.TTP.PCP

TIGHTNESS

TEST PANEL

1"C:

C.BAS.PCP

BAS

CONTROL

PANEL

S

PC2-10

S

S

S

S

S

S

SPARE FOR FUTURE

PIPELINE

(SEE GRID B-6, EP412)

MOUNT GENERATOR

CONTROL PANEL TO

FACE OF CABINET.

CABINET SHALL BE FULL

HEIGHT OF MCC

2625 27

S

3736 S

38 4039

3141 S42

2928 32

P I/C T

PC-27

A

M E

N D

M E

J

J J

J

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

J

1 E G D

B

C

F

A

PD-39

GFI

AC

LAB-11

GFI

48" AFF

FUEL

ELEC

MECH

MULTI PURPOSE

101a

CONTROL

SUPERVISOR

VEST

JAN

WOMEN

LOCKER

MEN

106 OPEN OFFICE

PD-5

GFI

AC

PD-31

GFI

AC

PD2-14

GFI

AC

PD2-12

GFI

AC

PD-3

GFI

LAB-3

EXP

48" AFF

LAB-3

EXP

48" AFF

LAB-9

48" AFF

LAB-5

48" AFF

PD-1

PD-1

PD-3

PD-19 PD-19

PD-23PD-23

PD-17

AC

PD-15

AC

PD-15

PD-13

PD-13

PD-13 PD-13

PD-11

PD-11

PD-11

PD-9

PD-9

PD-5

PD-5

GFI

PD-39

PD-3

PD2-16

AC

PD2-18

AC

PD-1

PD2-10

GFI

AC

PD-7

PD-7

LAB-5

48" AFF

PD-39

GFI

PD-15

AC

LAB-7

EEWS-1

PD-17

PD-19

CIRCULATION

101b

PD-17

AC

PD-33

GFI

WPIU

PD-33

GFI

WPIU

PD-33

GFI

WPIU

PD-35

TMGB

MGB

F A

-1

F A

-3

FA-5

IPC-POL

MSS

D

IP

-1 ,2

O P

-3 ,4

RCP

E5

ES504

EF-101

LAB-17

FA

LAB

LAB-9

48" AFF

EXPLAB-11

GFI

48" AFF

EXP

LAB-13,15

NEMA 2-20R

48" AFF

GB

PD-29

AV

PD-21

TV

GB

EXP

ACCU-101

PD2-1,3

EUH-102

PB-8,10,12

EF-102

PD2-15

AHU-101

PB-14,16,18

EUH-101

PB-8,10,12

AC-101

PD2-1,3

CUH-103

PD2-11

CUH-104

PD2-13

CUH-102

PD2-9

WH-101

PD2-5

RP-101

PD2-17

CUH-101

PD2-7

VEST

EPDS-1

ATG-MSS

FH-101

LAB-1

VAV-105

PD2-35,37

VAV-102

PD2-23,25

VAV-106

PD2-39,41

VAV-101

PD2-19,21

VAV-104

PD2-31,33

PD2-8

GFI

EWC-1

VAV-103

PD2-27,29

PD-25

FB1PD-27

FB1

PD-22

FB1PD-24

FB1

PD-20

AV

PD2-20

AC

PD-41M

GRINDER PUMP

PD2-22,24

PD-38,40,42

UPS

Omaha District

US Army Corps of Engineers ®

M A

S

C R

IP

T

IO

N

D A

T E

1 2 3 4 5

A

FILE:

DATE:

W

A R

D P

A R

K W

A Y

K A

N S

A S

C

IT

Y

M O

D E

S

IG

N E

D B

Y

D R

A W

N B

Y

S U

B M

IT

T

E D

B Y

C H

E C

K E

D B

Y

S O

L

IC

IT

A

T

IO

N N

O

W F

-2 -R

-0

C O

N T

R A

C T

N O

U S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

O M

A H

A D

IS

T

R

IC

T C

A P

IT

O

L A

V E

O

M A

H A

N

E

S

IZ

E

X

SHEET ID

IS

S

U E

D D

A T

E

D E

S C

P

O L F

A C

IL

IT

IE

S

R E

P L A

C E

M E

N T

G E

N E

R A

L M

IT

C

H E

L L I A

P

W I

P O

L O

P E

R A

T

IO

N S

B U

IL

D

IN

G

6 7 8 9 10

B

C

D

E

F

G

F

IL

E N

O

A F

-1

-0

ADVERTISEMENT - NOT FOR CONSTRUCTION

7/24/2020 9:50:24 AM

D R

ID

L E

Y

M B

A X

S L A

C Y

107341EP421MT18

D R

O D

D Y

EP421

J U

N E

P O

L O

P S

B U

IL

D

IN

G

F

C C

P

O W

E R

P L A

N

NOTES:

1.

2.

REFER TO SHEETS E-001, E-002 AND E-003 FOR

GENERAL NOTES AND LEGEND.

REFER TO MECHANICAL DRAWINGS FOR HVAC

EQUIPMENT INFORMATION.

SCALE: 1/4" = 1'-0"A1

OVERALL ELECTRICAL POWER FLOOR PLAN

N

0 2' 4' 8'

KEYED NOTES:

AREA WITHIN LAB AND LESS THAN 48" AFF SHALL

BE CONSIDERED A CLASS I, DIVISION 2, GROUP D

HAZARDOUS LOCATION. ARE INSIDE THE FUME

HOOD AND WITHIN 5 FEET IN ALL DIRECTIONS

SHALL BE CLASSIFIED AS CLASS I DIVISION 1,

GROUP D HAZARDOUS LOCATION. ALL

EQUIPMENT LOCATED IN AND NEAR THE FUME

HOOD SHALL BE RATED FOR THE AREA

CLASSIFICATION INDICATED.

FUEL ROOM SHALL BE CLASSIFIED AS CLASS I,

DIVISION 2 BELOW 48" AFF.

PROVIDE JUNCTION BOX FOR CONNECTION TO

FUEL LAB FUME HOOD.

HALF OF RECEPTACLES IN ROOM INDICATED

SHALL BE CONTROLLED VIA TIME CLOCK WITH

HAND OFF AUTO SWITCH IN ACCORDANCE WITH

ASHRAE 90.1-2013. REFER TO E7/EP521.

PERSONNEL AND EQUIPMENT GROUNDING BUS

BAR.

PERSONNEL GROUNDING BUS BAR.

EPO PUSH BUTTON FOR ROOM FUEL 112.

PROVIDE SHUNT TRIP BREAKER IN PANEL LAB.

REFER TO SHEET EP721.

UPS FOR FCC COMPUTER.

PROVIDE 120VAC RECEPTACLES FLUSH WITH

SUSPENDED CEILING FOR GOVERNMENT

FURNISHED WIRELESS EQUIPMENT.

CONNECT EYEWASH TO FIRE ALARM CIRCUIT VIA

FIRE ALARM ADDRESSABLE MODULE (PROVIDED

BY DIVISION 28).

R

T A

D E

S

IG

N S

U B

M

IT

T A

L

/2

/2

A

M E

N D

M E

N T

D a te

ZSC

ZSO

UI

LSL

LSLL

ZSO

ZSC

ZSO

ZSC

LSH

LSHH

M

UT

TE

LE

UIT

J

J

\\BMCD\DFS\CLIENTS\ANF\USCOE\NWO\107341_GENMITCHMILCON\DESIGN\ELEC\SHEETS\MT18-EP431_432.DWG 7/24/2020 8:21 AM SLLACY

A1

ENLARGED PLAN - JET FUEL STORAGE TANK 1

SCALE: 3/16" = 1'-0"

U

S

A

R M

Y

C

O R

E

N G

I N

E E

R S

O M

A H

A

D

I S

T R

I C

T

R

K W

A Y

K A

N S

T

Y

D E

S C

C

I L

I T

I E

S

R

E P

L A

C E

M E

N T

G E

N E

R A

L

M

I T

C H

E L

L

I A

P

W

I

US Army Corps of Engineers Omaha District

S O

L I C

I T

A T

I O

N

N

O

D E

S I G

N E

D

B

Y

D E

S C

R I P

T I O

N

M A

R K

S I Z

E

S U

B M

I T

T E

D

B

Y

D A

T E

C O

N T

R A

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

I S

S U

E

D

A T

E

SHEET ID

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

W F

R

X

R

S

I G

N

S

U B

M I T

T A

L

R T

A

D

E S

I G

N

S

U B

M I T

T A

L

J U

P

I T

E

O

M A

H A

N

E

D

R

O D

D Y

F I

A F

ADVERTISEMENT - NOT FOR CONSTRUCTION

EP431

E N

L A

R G

A

N

J E

T

F

U E

L

S

T O

R A

G

N

K

N

8'0 4' 16'

M A

T C

H L I N

E

S

H E

F

N

T I N

U A

T I O

N

REFER TO SHEET EP433 FOR TANK CONDUIT AND

CIRCUIT ROUTING DETAILS. SEE CATHODIC PROTECTION

DRAWINGS FOR TANK CATHODIC PROTECTION

INFORMATION.

AUTOMATIC TANK GAUGING EQUIPMENT IS PART OF BID

OPTION 005. CONDUITS AND CONDUCTORS ARE PART OF

BASE BID.

PRODUCT SAVER TANK HEATERS SHALL OPERATE WHEN

PRP IS NOT IN OPERATION.

REFER TO EL431 AND EL432 FOR TANK PERIMETER LIGHT

POLE LOCATIONS AND INFORMATION. ROUTE CIRCUIT

PA-19 IN 1" CONDUIT ALONG CONTAINMENT WALL TO ALL

FIXTURES.

KEYED NOTES:

PRODUCT

SAVER TANK-1

TANK 1

JUNCTION BOX

(TYP OF 4)

PROVIDE JUNCTION BOXES

FOR EPDS AND TANK

PERIMETER LIGHTING

EPDS-9A

1"C: P.ATGB.T1.UIT, P.ATGB.T2.UIT,

I.ATG.T1.UIT, I.ATG.T2.UIT;

1"C: IS.PCP.T1.LSHH, IS.PCP.T1.LSLL,

IS.PCP.T2.LSHH, IS.PCP.T2.LSLL;

1"C: PA-20, PA-24;

1"C: PC-26, PC2-1, PC2-7;

1"C: C.PCP.T1.ZS1, C.PCP.T1.ZS2,

C.PCP.T1.ZS3, C.PCP.T2.ZS1,

C.PCP.T2.ZS2, C.PCP.T2.ZS3;

1"C: C.MCC.EPDS9

SEE SHEET ES101

FOR CONTINUATION

HEATER

(TYP OF 2)

SPARE QUANTITIES

AND SIZES PER EP702

PRP-1

A

M E

N D

M E

1 0

ZSC

ZSO

UI

LSL

LSLL

ZSC

ZSO

ZSC

ZSO

LSH

LSHH

M

UT

TE

LE

UIT

J

J

M

\\BMCD\DFS\CLIENTS\ANF\USCOE\NWO\107341_GENMITCHMILCON\DESIGN\ELEC\SHEETS\MT18-EP431_432.DWG 7/24/2020 8:21 AM SLLACY

A1

ENLARGED PLAN - JET FUEL STORAGE TANK 2

SCALE: 3/16" = 1'-0"

U

S

A

R M

Y

C

O R

E

N G

I N

E E

R S

O M

A H

A

D

I S

T R

I C

T

R

K W

A Y

K A

N S

T

Y

D E

S C

C

I L

I T

I E

S

R

E P

L A

C E

M E

N T

G E

N E

R A

L

M

I T

C H

E L

L

I A

P

W

I

US Army Corps of Engineers Omaha District

S O

L I C

I T

A T

I O

N

N

O

D E

S I G

N E

D

B

Y

D E

S C

R I P

T I O

N

M A

R K

S I Z

E

S U

B M

I T

T E

D

B

Y

D A

T E

C O

N T

R A

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

I S

S U

E

D

A T

E

SHEET ID

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

W F

R

X

R

S

I G

N

S

U B

M I T

T A

L

R T

A

D

E S

I G

N

S

U B

M I T

T A

L

J U

P

I T

E

O

M A

H A

N

E

D

R

O D

D Y

F I

A F

ADVERTISEMENT - NOT FOR CONSTRUCTION

EP432

E N

L A

R G

A

N

J E

T

F

U E

L

S

T O

R A

N

K

N

8'0 4' 16'

M A

T C

H L I N

E

S

E

N

T I N

U A

T I O

N

REFER TO SHEET EP433 FOR TANK CONDUIT AND

CIRCUIT ROUTING DETAILS. SEE CATHODIC PROTECTION

DRAWINGS FOR TANK CATHODIC PROTECTION

INFORMATION.

AUTOMATIC TANK GAUGING EQUIPMENT IS PART OF BID

OPTION 005. CONDUITS AND CONDUCTORS ARE PART OF

BASE BID.

PRODUCT SAVER TANK HEATERS SHALL OPERATE WHEN

PRP IS NOT IN OPERATION.

KEYED NOTES:

PRODUCT

SAVER TANK-2

TANK 2

JUNCTION BOX

(TYP OF 4)

PROVIDE JUNCTION BOXES

FOR EPDS AND TANK

PERIMETER LIGHTING ONLY

EPDS-9C

EPDS-9B

SEE SHEET ES101

FOR CONTINUATION

1"C: P.ATGB.T1.UIT, P.ATGB.T2.UIT,

I.ATG.T1.UIT, I.ATG.T2.UIT;

1"C: IS.PCP.T1.LSHH, IS.PCP.T1.LSLL,

IS.PCP.T2.LSHH, IS.PCP.T2.LSLL;

1"C: PA-20, PA-24;

1"C: PC-26, PC2-1, PC2-7;

1"C: C.PCP.T1.ZS1, C.PCP.T1.ZS2,

C.PCP.T1.ZS3, C.PCP.T2.ZS1,

C.PCP.T2.ZS2, C.PCP.T2.ZS3;

1"C: C.MCC.EPDS9

1"C: PA-20, PA-24

TO TANK 1 & 2

CP RECTIFIERS

(SEE SHEET CP101)

A1

EP433

HEATER

(TYP OF 2)

PRODUCT

RECOVERY TANK

PRP-2

A

M E

N D

M E

S

A

R M

Y

C

O R

E

N G

I N

E E

R S

O M

A H

A

D

I S

T R

I C

T

R

K W

A Y

K A

N S

T

Y

D E

S C

C

I L

I T

I E

S

R

E P

L A

C E

M E

N T

G E

N E

R A

L

M

I T

C H

E L

L

I A

P

W

I

US Army Corps of Engineers

Omaha District

S O

L I C

I T

A T

I O

N

N

O

D E

S I G

N E

D

B

Y

D E

S C

R I P

T I O

N

M A

R K

S I Z

E

S U

B M

I T

T E

D

B

Y

D A

T E

C O

N T

R A

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

I S

S U

E

D

A T

E

SHEET ID

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

W F

R

X

R

S

I G

N

S

U B

M I T

T A

L

R T

A

D

E S

I G

N

S

U B

M I T

T A

L

J U

P

I T

E

O

M A

H A

N

E

D

R

O D

D Y

F I

A F

ADVERTISEMENT - NOT FOR CONSTRUCTION

EP433

E N

L A

R G

A

N

P

O

R A

N

K

1. REFER TO E-001 FOR LEGEND,

ABBREVIATIONS AND GENERAL NOTES

NOTES:

A5

STORAGE TANK ELECTRICAL ELEVATION

SCALE: NTS

1. REFER TO CONTROL DIAGRAM D1, EP604 FOR MOTOR STARTER CONTROLS INFORMATION. MOTOR STARTER

SHALL BE IN NEMA 4X ENCLOSURE AND MOUNTED IN A SIMILAR MANNER AS SHOWN IN DETAIL E1, ES504.

2. PROVIDE JUNCTION BOXES FOR SAME SIGNAL TYPES AS NECESSARY ALONG TOP OF TANK.

A1

PRODUCT RECOVERY TANK ELECTRICAL PLAN VIEW

SCALE: NTS

FTP-1 WITH HEATER

AND MOTOR WINDING

TEMPERATURE SWITCH

OVERFILL

PREVENTION

VALVE

WATER LEVEL SWITCH

PRODUCT LEVEL

SWITCHES

WDP-1

LSH

LSH

LSM

LSL

LSHH

M

UT

ZSC

FS

M

1"C: P.MCC.FTP1,

C.MCC.FTP.TSH,

C.MCC.FTP.HTR

WDP/BP-1 MOTOR

STARTER

(SEE NOTE 1)

1. SEE TANK DRAWINGS ON MECHANICAL SHEETS FOR EXACT LOCATION OF TANK EQUIPMENT.

2. WELD CONDUIT SUPPORT STRUCTURES (UNISTRUT OR EQUAL) TO TANK MOUNTING PLATES, REFER TO MECHANICAL DRAWINGS

FOR MOUNTING PLATES PROVIDED BY TANK MANUFACTURER. DO NOT WELD UNISTRUT DIRECTLY TO TANK . USE THREADED ARC

STUDS OR EQUIVALENT TO INCLUDE THREADED COUPLERS OF THE SAME MATERIAL AS THE MATERIAL OF THE TANK.

3. REFER TO ES501 FOR CONDUIT, DUCTBANK, NAMEPLATE, AND HAZARDOUS AND NON-HAZARDOUS INSTALLATION REQUIREMENTS.

LEAK DETECTION SENSOR

LD

NOTES:

NOTES:

J

J

J

ATG

TRANSITION TO CONCRETE-ENCASED

DUCTBANK AND ROUTE TO MANHOLES

SEE ES101

1"C: C.MCC.FTP.FS

1"C:

C.PCP.PRT.ZSC

1"C:

IS.ATG.PRT

1"C:

IS.MCC.PRT.L3

1"C:

IS.MCC.PRT.L1,

IS.MCC.PRT.L2

1"C:

IS.ATG.PRT.LD

1"C: PC2-2

SPARE QUANTITIES

AND SIZES PER EP702

1"C:

PC2-2,

C.WDP.HTR,

C.WDP.TSH

JY

1"C:

C.WDP.JY

SEE NOTE 2 (TYP)

LSHH

3x1

LSH

3x1

LSL

3x1

LSLL

3x1

UI

3x1

ZSC

3x1

ZSO

3x1

ZSC

3x2

ZSO

3x2

ZSC

3x3

ZSO

3x3

UIT

3x1

LE

3x1

TE

3x1

UT

3x1

M

J J

J

J

J

J

SEE PLANS FOR

CONTINUATION

SEE PLANS FOR

CONTINUATION

GRADE

TANK

FOUNDATION

NUMBER OF TANK

GROUNDING CONNECTIONS

AS INDICATED ON PLANS

TANK SIDE

INDICATOR

(COORDINATE FINAL

PLACEMENT WITH

CONTRACTING

OFFICER)

LIGHT SWITCH

INLET

VALVE

SUCTION

VALVE

LOW

SUCTION

VALVE

PRODUCT

SAVER TANK

PUMP AND

HEATERS

ALARMS AND

SENSORS TO BE

ACCESSIBLE

FROM STAIRS

GROUND

ROD (TYP)

#4/0 TW

CU GND

CABLE

M

I N

1"C

1"C

4 5 6

1"C

1"C

1"C

1"C

7 8

1"C

1"C

1"C

11"C

2 1"C

1"C

DSC

DSC

LIGHT

FIXTURE

(TYP)

D6

EL501

"x" INDICATES ABOVE

GROUND STORAGE

TANK NUMBER (TYP)

1"C

A

M E

N D

M E

LSH

LSM

LSL

TSH

FS

JY

JY

JY

HS

U

E

U

C

U

E

U

C

U

E

U

C

FT

J F

J F

J F

J F

J F

J F

J F

J F

LSH

LSM

LSL

TSH

FS

JY

JY

JY

HS

U

E

U

C

U

E

U

C

U

E

U

C

U

E

U

C

FT

U

S

A

R M

Y

C

O R

E

N G

I N

E E

R S

O M

A H

A

D

I S

T R

I C

T

R

K W

A Y

K A

N S

T

Y

D E

S C

C

I L

I T

I E

S

R

E P

L A

C E

M E

N T

G E

N E

R A

L

M

I T

C H

E L

L

I A

P

W

I

US Army Corps of Engineers

Omaha District

S O

L I C

I T

A T

I O

N

N

O

D E

S I G

N E

D

B

Y

D E

S C

R I P

T I O

N

M A

R K

S I Z

E

S U

B M

I T

T E

D

B

Y

D A

T E

C O

N T

R A

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

I S

S U

E

D

A T

E

SHEET ID

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

W F

R

X

R

S

I G

N

S

U B

M I T

T A

L

R T

A

D

E S

I G

N

S

U B

M I T

T A

L

J U

P

I T

E

O

M A

H A

N

E

D

R

O D

D Y

F I

A F

ADVERTISEMENT - NOT FOR CONSTRUCTION

0 2' 4' 6'

0 2' 4' 6'

EP441

T R

U C

K

O

F F

L O

S

I T

I O

W

A

N

1. REFER TO E-001 FOR LEGEND,

ABBREVIATIONS, AND GENERAL NOTES.

2. EQUIPMENT CONFIGURATION IDENTIFIED

HERE IS DIAGRAMMATIC ONLY. FINAL SKID

AND RACK CONFIGURATION TO BE

DETERMINED BY SKID MANUFACTURER.

CIRCUITS BETWEEN EQUIPMENT ON RACK TO

SKID-MOUNTED DEVICES/INSTRUMENTS ARE

NOT IDENTIFIED BUT SHALL BE PROVIDED BY

SKID MANUFACTURER AND WILL TERMINATE

AT RACK-MOUNTED MOTOR STARTER WITH

TERMINAL STRIPS.

NOTES:

OCP-2 ON OFFLOAD

ELECTRICAL RACK

EPDS-7B

OP-2

1"C: C.PCP.OCP2, C.MCC.EPDS7;

2"C: P.MCC.OP2;

1"C: I.PCP.FT421

TO MANHOLES CMH-04 &

EMH-04. SEE PAGE ES101

FOR CONTINUATION

TO MANHOLES CMH-04 &

EMH-04. SEE PAGE ES101

FOR CONTINUATION

1"C: C.PCP.OCP1, C.MCC.EPDS7;

2"C: P.MCC.OP1;

1"C: I.PCP.FT411

AIR ELIMINATOR-2

OCP-1 ON OFFLOAD

ELECTRICAL RACK

EPDS-7A

AIR ELIMINATOR-1

OP-1

ALL DEVICES ON

SKID SHALL BE

SUITABLE FOR A

CLASS I, DIVISION 1

AREA (TYP FOR

EACH SKID)

A1

ES503

A1

ES503

AB/CV-1

SCV-1

AB/CV-2

SCV-2

A1

ENLARGED PLAN - TRUCK OFFLOAD STATION 1

SCALE: 3/8" = 1'-0"

N

A6

ENLARGED PLAN - TRUCK OFFLOAD STATION 2

SCALE: 3/8" = 1'-0"

N

A

M E

N D

M E

U

C

U

E

U

C

U

E

U

C

U

E

U

C

U E

U

C

U

E

U

C

U E

U

C

U

E

U

C

U

E

U

C

U

E

U

C

U

E

U

C

LD

LD

U

E

U

E

U

E

U

E

U

E

U

E

U

E

U

E

U

E

\\BMCD\DFS\CLIENTS\ANF\USCOE\NWO\107341_GENMITCHMILCON\DESIGN\ELEC\SHEETS\MT18-EP453.DWG 7/23/2020 11:29 PM LHURST

A1

ENLARGED PLAN - MSS FUEL ISLAND

SCALE: 3/8" = 1'-0"

U

S

A

R M

Y

C

O R

E

N G

I N

E E

R S

O M

A H

A

D

I S

T R

I C

T

R

K W

A Y

K A

N S

T

Y

D E

S C

C

I L

I T

I E

S

R

E P

L A

C E

M E

N T

G E

N E

R A

L

M

I T

C H

E L

L

I A

P

W

I

US Army Corps of Engineers

Omaha District

S O

L I C

I T

A T

I O

N

N

O

D E

S I G

N E

D

B

Y

D E

S C

R I P

T I O

N

M A

R K

S I Z

E

S U

B M

I T

T E

D

B

Y

D A

T E

C O

N T

R A

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

I S

S U

E

D

A T

E

SHEET ID

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

W F

R

X

R

S

I G

N

S

U B

M I T

T A

L

R T

A

D

E S

I G

N

S

U B

M I T

T A

L

J U

P

I T

E

O

M A

H A

N

E

D

R

O D

D Y

F I

A F

ADVERTISEMENT - NOT FOR CONSTRUCTION

EP453

E N

L A

R G

A

N

M

E

L

I S

L A

N D

N

4'0 2' 8'

EPDS-M4

FMS

DIESEL DISPENSER

(DISP-2)

MOGAS DISPENSER

(DISP-1)

CANOPY

NOTES:

1. REFER TO CONDUIT SCHEDULE ON SHEET EP451 FOR

CIRCUIT IDENTIFICATIONS.

15 27

WEATHERPROOF

TELEPHONE ENCLOSURE

37 38 39 40

SEE SHEET EP452

FOR CONTINUATION

A6

ES502

F1

ET501

E1

ES504

E1

ES505

(TYP)

S

S33

5 8

9 S

I/C P

P

I/C P

S 9 S

I/C P

A

M E

N D

M E

S

A

R M

Y

C

O R

E

N G

I N

E E

R S

O M

A H

A

D

I S

T R

I C

T

R

K W

A Y

K A

N S

T

Y

D E

S C

C

I L

I T

I E

S

R

E P

L A

C E

M E

N T

G E

N E

R A

L

M

I T

C H

E L

L

I A

P

W

I

US Army Corps of Engineers

Omaha District

S O

L I C

I T

A T

I O

N

N

O

D E

S I G

N E

D

B

Y

D E

S C

R I P

T I O

N

M A

R K

S I Z

E

S U

B M

I T

T E

D

B

Y

D A

T E

C O

N T

R A

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

I S

S U

E

D

A T

E

SHEET ID

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

W F

R

X

R

S

I G

N

S

U B

M I T

T A

L

R T

A

D

E S

I G

N

S

U B

M I T

T A

L

J U

P

I T

E

O

M A

H A

N

E

D

R

O D

D Y

F I

A F

ADVERTISEMENT - NOT FOR CONSTRUCTION

EP601

P U

M P

H O

U S

E

O

N E

L

I N

E

D

I A

G R

A M

HOA

P M

C C

F

T P

P M

C C

F

P

P M

C C

F

P

P M

C C

F

P

MOTOR CONTROL CENTER (MCC-PH) 480V, 3 PHASE, 3 WIRE, 1200A MAIN BUS, 400A GROUND BUS, 42,000 AIC SYMMETRICAL

FVNR

NEMA 0

AUTO

XFMR

NEMA 5

FROM

MDS-PH

FUEL

TRANSFER

PUMP #1 (FTP-1)

5 HP

7.6 FLA

FUELING

PUMP #1

(FP-1)

125 HP

156 FLA

FUELING

PUMP #2

(FP-2)

125 HP

156 FLA

FUELING

PUMP #3

(FP-3)

125 HP

156 FLA

* KEYED HOA SWITCHES SHALL BE KEYED ALIKE WITH THE CORRESPONDING

KEYED HAND-AUTO SWITCHES LOCATED NEAR THE MOTORS. SEE DRAWING EP602

INCOMING

MAIN

BREAKER

MM M M

1. SEE DRAWING E-001 FOR ELECTRICAL LEGEND, ABBREVIATIONS, AND GENERAL

NOTES.

2. SEE DRAWING EP602 FOR THE TYPICAL PUMP MOTOR SCHEMATICS.

3. SEE DRAWING EP603 FOR EPDS WIRING DIAGRAM.

4. SEE PANEL AND POWER CIRCUIT SCHEDULES ON EP701 AND EP702 FOR ADDITIONAL

INFORMATION REGARDING LOW-VOLTAGE PANELBOARDS AND POWER CIRCUITS.

5. GROUNDING ABBREVIATIONS:

· EBJ - EQUIPMENT BONDING JUMPER

· GEC - GROUNDING ELECTRODE CONDUCTOR

· MBJ - MAIN BONDING JUMPER

· SSBJ - SUPPLY-SIDE BONDING JUMPER

· SBJ - SYSTEM BONDING JUMPER

3P

30A

(NOTE 4)

3P

225A

3P

MCP

30AF

9-325AT

D1

MOTOR CONTROL CENTER (MCC-PH) ELEVATION

SCALE: NTS

SIDE VIEW

D4

MAIN DISTRIBUTION SWITCHBOARD

(MDS-PH) ELEVATION

SCALE: NTS

SIDE VIEW

FRONT VIEW

A1

ONE-LINE DIAGRAM - PUMPHOUSE

SCALE: NTS

R

G

R

G

R

G

R

G

P M

D S

M

C C

P.MCC.PA

AUTO

XFMR

NEMA 5

AUTO

XFMR

NEMA 5

HOA HOA HOA

P M

C C

F

P

FUELING

PUMP #4

(FP-4)

125 HP

156 FLA

AUTO

XFMR

NEMA 5

HOA

TO GROUND

GRID

P M

C C

F

P

FUELING

PUMP #5

(FP-5)

125 HP

156 FLA

AUTO

XFMR

NEMA 5

HOA

OFFLOAD

PUMP

OP-1

50 HP

65 FLA

FVNR

NEMA 3

FVNR

NEMA 3

P M

C C

P

D P

PUMP HOUSE

DRAIN PUMP

PDP-1

1HP

2.1 FLA

FVNR

NEMA

HOA

P M

C C

J P

JOCKEY

PUMP

JP-1

2HP

3.4 FLA

FVNR

NEMA

HOA

GND

P M

C C

M

A

MAKE-UP

AIR UNIT

MAU-111

HEATER

82 FLA

T-2

208Y/120V

75 KVA

NOTES: GENERAL NOTES

3P

400AF

250AT

3P

400AF

250AT

3P

400AF

250AT

3P

400AF

250AT

3P

400AF

250AT

NEXUS 1500

GENERATOR

MAIN

BREAKER

MCC

FEEDER

BREAKER

UTILITY TRANSFORMER

1000kVA, 3 PHASE, 24.94KV:480Y/277V

(NOTE 8)

(3)

1200/5

UM

PAD-MOUNTED METERING,

NEMA 3R, STAINLESS STEEL, 1200A

(NOTE 8)

20"

7'-6"

35"

ADJ

WITH

GFP

ADJ

WITH

GFP

ADJ

WITH

GFP

ADJ

WITH

GFP

ADJ

WITH

GFP

SPACE SPACE

OFFLOAD

PUMP

OP-2

50 HP

65 FLA

MOTOR STARTER PROVIDED

AS PART OF SKID BY SKID

MANUFACTURER

INTEGRATED

POWER CABINET

(IPC-PH)

NEUT

PA

480V

400A MLO

PC

208Y/120V

225A

SPD

SPD

SPD

MCP

30AF

9-325AT

MCP

30AF

9-325AT

MAX RATING OF

125% FLA PER

NEC, 430.32(A)(1)

(TYP INCL. AUTO

XFMRS)

3P

100A

3P

100A

T-FA

MINI POWER

CABINET

(NOTE 7)

FA

240/

120V

40A

7.5KVA

240/120V

XFMR

20A

2P

P M

C C

O

P

P M

C C

O

P

WE ENERGIES UTILITY

(NOTE 8)

P M

T R

M

D S

P.UT.MTR

(3)

GEC -

#3/0

EBJ -

250 KCMIL

3P

90A

FP-5FP-4FP-3

FRONT VIEW

FP-1 FP-2

OP-1

OP-2

PANEL

PA

JP-1

17'-0"

FTP-1

MLO

FEEDER

SECTION

SPD

PC2

208Y/120V

225A

SPD

PDP-1

MAU

PF

CAP

PF

CAP

PF

CAP

PF

CAP

PF

CAP

SPACE

SPACE

2P

20A

NOTE 1 (TYP GFP BREAKERS)

SPACE

HOA HOA HOA HOA HOA

P M

C C

F

A

SPACE

POL OPS

BREAKER

FA

1. PROVIDE ZONE SELECTIVE INTERLOCKING FOR GROUND FAULTS BETWEEN GFP BREAKERS INDICATED AND MAIN BREAKER IN MDS-PH.

2. SET THE AUTOTRANSFORMER STARTER TAPS AT THE 80% TAP.

3. IC = INSULATED CASE TYPE OF CIRCUIT BREAKER.

4. SPD BREAKER SIZE DEPENDENT UPON MANUFACTURER.

5. CONTRACTOR SHALL SUPPLY CAPACITORS OF THE SIZE RECOMMENDED BY THE MANUFACTURES FOR MOTORS INDICATED TO HAVE

CAPACITORS.

6. PROVIDE ARC FLASH LABELS FOR ELECTRICAL EQUIPMENT AND SERVICE ENTRANCE FAULT CURRENT LABEL FOR MDS. REFER TO EP501 FOR

LABEL REQUIREMENTS.

7. POWER FOR FIRE PROTECTION SYSTEM(S) SHALL BE PROVIDED USING A MINI-POWER CABINET PER SPECIFICATION 26 20 00. THE

TRANSFORMER/PANEL COMBINATION SHALL BE RED. PAINT THE LOCK-ON BREAKER IN THE MCC RED. IN ADDITION TO THE MCC MAIN

NAMEPLATE, PROVIDE A LABEL WITH THE FOLLOWING INSCRIPTION: "FIRE PROTECTION/LIFE SAFETY EQUIPMENT." LABEL SHALL BE IDENTICAL

TO THE MCC NAMEPLATE, EXCEPT THE LABEL MUST BE RED LAMINATED PLASTIC WITH WHITE CENTER CORE.

8. CONTRACTOR SHALL COORDINATE THE UTILITY WORK WITH WE ENERGIES. WE ENERGIES WILL PROVIDE THE TRANSFORMER, METER, AND

ALL CONDUCTORS AND CONNECTIONS TO THE PRIMARY SIDE OF THE TRANSFORMER. METER ENCLOSURE AND ALL SECONDARY POWER

DISTRIBUTION WORK ARE THE RESPONSIBILITIES OF THE CONTRACTOR.

SPACE

SPACE

SPACE

SPACE

TYPE 2

TYPE 2

TYPE 2

TYPE 2

G G G G G

HOA

G

HOA

G

SPACE

EPDS

A

M E

N D

M E

(3)

1200/5

(3)

AS

K

VS

A

V

K

G

1200AF

800AT

3P,IC

1200AF

1200AT

3P,IC

1200AF

225AT

KEYED INTERLOCK

MOTOR

CONTROL

CENTER

MCC-PH

TO POL

OPERATIONS

BUILDING PANEL

PB, SEE EP621

P M

D S

P

B

MAIN DISTRIBUTION SWITCHBOARD (MDS-PH)

480V, 3PH, 3W, 1200A BUS, 42,000 AIC SYMMETRICAL,

SERVICE ENTRANCE RATED (NOTE 4)

GEN-PH

400KW @ 0.8PF STARTING KVA

700sKVA MIN. @ 15%

V-DROP,STANDBY FLEX FUEL

(DIESEL/JET A) GENERATOR

UPSIZED ALTERNATOR

(SEPARATELY DERIVED)

GND

NEUT

TO GROUND

GRID

GEC - #3/0

SSBJ - 250 KCMIL

MBJ - 250 KCMIL

DM

ELECTRO

IND.

NEXUS

3P

NEUT

TO GROUND GRID

GEC - #3/0

SBJ - #3/0

P G

E N

M

D S

1200AF

1200AT

3P, IC

(NOTE 1)

SPD

TYPE 2

COMMUNICATIONS TO

BAS PANEL (I.BAS.DM)

S

A

R M

Y

C

O R

E

N G

I N

E E

R S

O M

A H

A

D

I S

T R

I C

T

R

K W

A Y

K A

N S

T

Y

D E

S C

C

I L

I T

I E

S

R

E P

L A

C E

M E

N T

G E

N E

R A

L

M

I T

C H

E L

L

I A

P

W

I

US Army Corps of Engineers

Omaha District

S O

L I C

I T

A T

I O

N

N

O

D E

S I G

N E

D

B

Y

D E

S C

R I P

T I O

N

M A

R K

S I Z

E

S U

B M

I T

T E

D

B

Y

D A

T E

C O

N T

R A

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

I S

S U

E

D

A T

E

SHEET ID

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

W F

R

X

R

S

I G

N

S

U B

M I T

T A

L

R T

A

D

E S

I G

N

S

U B

M I T

T A

L

J U

P

I T

E

O

M A

H A

N

E

D

R

O D

D Y

F I

A F

ADVERTISEMENT - NOT FOR CONSTRUCTION

EP602

C O

N T

R O

L

D

I A

G R

A M

S

F

P

F

T P

M

O V

M

OL

OL

OL

L1

L2

L3

G

1STRTR

CPT

480V-120V

CAPACITOR

R1

1S

2S

2S

2S

R1

1S

1S

R1

R1

2S

R1

AUTOTRANSFORMER STARTER

PCP

OUTPUT

OL'STS

oox xoo

OFF

HAND

AUTO

OTT

RUN

STOP

TR

SRx

SRx

HAND AUTO

K E

Y

ER2

SRx

FUELING PUMP STATUS

INST. NCTO

NOTC

MOTOR SPACE HEATER

MCP

L1

L2

L3

G

M

OL

OL

OL

oox xoo

OFF

HAND AUTO

OL'S

RUN

STOP

CPT

480V-120V

MC

TSER2 TR1

ON-DELAY

HIGH HIGH LEVEL (ALARM)

HIGH LEVEL (ALARM)

INTRINSICALLY SAFE RELAY

MC

MC

CR2

HIGH LEVEL ALARM

PUMP STATUS

MC

MC

MOTOR SPACE HEATER

CT

CT

CT

xo

START/DISABLE

PCP

INPUT

PCP

INPUT

PCP

INPUT

RUN

CR1

NCTO

FS-331

MCP

KEY CAPTIVE IN "HAND" POSITION.

SWITCH IS LOCATED NEAR MOTOR.

SEE NOTE 2.

KEY CAPTIVE IN "HAND" AND

"AUTO" POSITIONS. SEE NOTE 2.

LOCATED BY

"HAND-AUTO" SWITCH

2S

1S

R1

TR

SRx

CR4

CR1

TR1

MC

B1

TYPICAL FUELING PUMP (FP-x)

SCALE: NTS

A4

TYPICAL FUELING TRANSFER PUMP (FTP-1)

SCALE: NTS

CR CONTROL RELAY

DM DAMPER MOTOR

ER EMERGENCY/SAFTEY SYSTEM RELAY

TS MOTOR TEMPERATURE SWITCH

MC MOTOR CONTROLLER

OTT OVER TEMPERATURE THERMOSTAT

ON AUTOTRANSFORMER

SR STATUS RELAY

TR TIMER RELAY

EPDS EMERGENCY POWER DOWN STATION

PCP PUMP CONTROL PANEL

FCC FUELS CONTROL CENTER

ESO EMERGENCY SHUTOFF VALVE

LEGEND: THIS DRAWING ONLY

G

G

R

G

R

IN EPDS SECTION OF MCC

IN EPDS

SECTION

OF MCC

MID LEVEL (START)

LOW LEVEL (STOP)

CR2

CR3

PRODUCT RECOVERY TANK FLOAT SWITCH ASSEMBLY

WATER HIGH LEVEL (STOP, ALARM)

PRODUCT RECOVERY TANK WATER FLOAT SWITCH ASSEMBLY

INTRINSICALLY

SAFE RELAY

INTRINSICALLY

SAFE RELAY

INTRINSICALLY

SAFE RELAY

HIGH HIGH LEVEL ALARM

CR3

PCP

INPUT

WATER HIGH LEVEL ALARM

CR4

PCP

INPUT

x = 1 FOR FP-1 x = 2 FOR FP-2 x = 3 FOR FP-3 x = 4 FOR FP-4 x = 5 FOR FP-5

(TYP)

C.MCC.FPx.HTR

C.MCC.FPx.HS

C.MCC.FPx.TSH

C.MCC.PCP.x

C.MCC.FTP.TSH

C.MCC.FTP.FS

C.MCC.PRT.L2

C.MCC.PRT.L1

C.MCC.PRT.L3

C.MCC.FTP.HTR

C.MCC.PCP.8

C.MCC.PCP.9

C.MCC.FPx.HS

PCP

OUTPUT

PUMP DISABLED UPON

MANIFOLD/TANK

ERROR AND PRT HIGH

WATER DETECTION

C.MCC.PCP.8

1. REFERENCE E-001 FOR ELECTRICAL LEGEND, ABBREVIATIONS, AND GENERAL NOTES.

2. KEYED LOCKS FOR LOCAL HAND-AUTO SWITCHES AND CORRESPONDING MCC HAND-OFF-AUTO SWITCHES SHALL

BE KEYED ALIKE. KEYED LOCKS AMONG PUMP STARTERS SHALL BE UNIQUE SO THAT ANY GIVEN KEY WILL

CONTROL ONLY THE PUMP TO WHICH IT IS ASSIGNED.

3. THE ACTUAL CONFIGURATION OF POWER CORRECTING CAPACITORS SHALL BE DETERMINED BY THE EQUIPMENT

MANUFACTURER.

4. TIMING OF THE OPERATION SHALL BE SUCH THAT R1 CONTACTOR CONTACTS CLOSE BEFORE 1S CONTACTOR

CONTACTS OPEN.

NOTES:

NOTE 3

NOTE 4

NOTE 4

NOTE 4

120 VAC FROM ACTUATOR CONTROL POWER TRANSFORMER

L

O

R

XOO

OXO

OOX

STOP

CLOSE

OPEN

O

C

C

O

LIMIT SWITCH

(OPEN)

LIMIT SWITCH

(CLOSE)

MOV

O/L'S

H N

CLOSE

VALVE

OPEN

VALVE

OPEN

POSITION

CLOSED

POSITION

C.PCP.MOV231

C.PCP.MOV231

1. PROVIDE ISOLATION RELAYS AS NECESSARY FOR PCP INPUTS/OUTPUTS.

2. INTERNAL MOV WIRING DEPENDENT ON EQUIPMENT PROVIDED.

3. MOV-231 SHOWN, TYPICAL FOR OTHER MOV'S.

NOTES:

D7

MOTOR OPERATED VALVE

SCALE: NTS

N

L

SENSOR

INPUT

MODULE

INPUT POWER

TO RTU 8130

PROBE INPUT

MODULE

AUTOMATIC TANK

GAUGING PANEL

(VEEDER-ROOT TLS-450)

G

A7

CONTROL DIAGRAM - ATG-PH (VEEDER-ROOT TLS-450)

SCALE: NTS

ETHERNET

NETWORK CARD

G

CHASSIS GROUND

MODEM

NO

C

NC

TO PUMP

CONTROL PANEL

(C.ATG.PCP

I/O MODULE (PROVIDE

ADDITIONAL MODULES

AS NECESSARY)

UT

PRT TANK

LEVEL/TEMP//LEAK

DETECTION PROBE

IS.ATG.PRT

PRT TANK LEAK

DETECTION ALARM

OUTPUT

CONTACTS

LD

IS.ATG.PRT.LD

LT

OWS SEPARATION

CHAMBER LEVEL

PROBE

IS.ATG.OWS.LT341

LT

OWS OIL HOLDING

CHAMBER LEVEL

PROBE

IS.ATG.OWS.LT342

LD

IS.ATG.OWS.LD341

OWS INTERSTITIAL

LEAK DETECTION

PRT TANK

INTERSTITIAL LEAK

DETECTION

PCP

INPUT

PCP

INPUT

PCP

OUTPUT

PCP

OUTPUT

C.MCC.PCP.9

HIGH HIGH LEVEL ALARM

CR3

EPDS

SYSTEM

ATG

BACKBOARD

RECEPTACLE

A

M E

N D

M E

S

A

R M

Y

C

O R

E

N G

I N

E E

R S

O M

A H

A

D

I S

T R

I C

T

R

K W

A Y

K A

N S

T

Y

D E

S C

C

I L

I T

I E

S

R

E P

L A

C E

M E

N T

G E

N E

R A

L

M

I T

C H

E L

L

I A

P

W

I

US Army Corps of Engineers

Omaha District

S O

L I C

I T

A T

I O

N

N

O

D E

S I G

N E

D

B

Y

D E

S C

R I P

T I O

N

M A

R K

S I Z

E

S U

B M

I T

T E

D

B

Y

D A

T E

C O

N T

R A

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

I S

S U

E

D

A T

E

SHEET ID

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

W F

R

X

R

S

I G

N

S

U B

M I T

T A

L

R T

A

D

E S

I G

N

S

U B

M I T

T A

L

J U

P

I T

E

O

M A

H A

N

E

D

R

O D

D Y

F I

A F

ADVERTISEMENT - NOT FOR CONSTRUCTION

EP603

E P

R

I N

G

D

I A

G R

A M

LOW SENSITIVITY OR

TRANSISTOR SENSITIVE

ER1

PCP

INPUT

ER1

ER1

ER2

EMERGENCY SHUTOFF VALVE STATUS

ER3

EMERGENCY CIRCUIT POWER STATUS

EMERGENCY STOP STATUS

PCP

INPUT

PCP

INPUT

JY-111

ER3

ER2

ER1

E1

E1A

E1

LIGHT RESET

E1A

E2

E2A

E2

PCP

E2A

LIGHT RESET

E3

E3A

E3

EPDS-3

E3A

LIGHT RESET

E4

E4A

E4

EPDS-4

E4A

LIGHT RESET

E5

E5A

EPDS-5

E5

E5A

LIGHT RESET

E6

E6A

E6

EPDS-6

E6A

LIGHT RESET

E7A

E7

EPDS-7A

E7A

LIGHT RESET

E8

E8A

E8

EPDS-8A

E8A

LIGHT RESET

E7

CONTROL ROOM

CONTROL ROOM

PUMP HOUSE

PUMP HOUSE

E1

E2 E3 E4 E5 E6

E9

CONTINUED AT "A" CONTINUED AT "B"

"A" CONTINUED

"…