W9128F20R0079-Drawings-Am-2.pdf
PDF 9 MB Posted
- Attached to
- General Billy Mitchell ANGB, WI Hydrant Fuel System Replacement Federal contract opportunity
- Solicitation number
- W9128F-20-R-0079
About this file
This document provides drawings and specifications for a federal contract opportunity to construct a new consolidated fueling facility at General Billy Mitchell ANGB in Wisconsin. Key project elements include aboveground fuel storage tanks, a pump house with control room, a product recovery tank, a POL operations building with laboratory, refueling vehicle parking, truck loading and unloading points, a motor gas storage tank, a diesel storage tank, and supporting facilities. The solicitation number is W9128F-20-R-0079 and was issued by the Department of the Army Corps of Engineers Engineering District Omaha. Interested parties should contact the points of contact listed to request electronic copies of the drawings. The response due date and anticipated award date are not provided.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Question and Answer related to Projnet question 8737383.pdf | ||
| 02 41 00-Am4.pdf | ||
| W9128F20R0079-Drawings-Am-4.pdf | ||
| Amendment 0004 Modification Copy W9128F-20-R-0079.pdf | ||
| Amendment 0004 Conformed Copy.pdf | ||
| Amendment 0003 W9128F-20-R-0079.pdf | ||
| W9128F20R0079-Vol-2-Specs-Am2.pdf | ||
| Amendment 0002 W9128F-20-R-0079.pdf | ||
| Bid Walk sign in list.pdf | ||
| Amendment 0001 W9128F-20-R-0079.pdf | ||
| W9128F-20-R-0079am_0001 SPECS Chng.pdf | ||
| ARW Form 11 Visitor Access.pdf | ||
| Site Walk and Visitor Access Instructions W9128F20R0079.pdf | ||
| W9128F-20-R-0079-Vol-2-Specs.pdf | ||
| Solicitation Gen. Billy Mitchell W9128F-20-R-0079.pdf |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
U
S
A
R M
Y
C
O R
P S
O
F
E
N G
I N
E E
R S
O M
A H
A
D
I S
T R
I C
T
W
A R
D
R
K W
A Y
K A
N S
C
I T
Y
M
D E
S C
L
C
I L
I T
I E
S
R
E P
L A
C E
M E
N T
G E
N E
R A
L
M
I T
C H
E L
L
I A
P
W
I
US Army Corps of Engineers Omaha District
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
T
N
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
SHEET ID
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
W F
R
X
R
E S
I G
N
S
U B
M I T
T A
L
R T
A
D
E S
I G
N
S
U B
M I T
T A
L
J U
P
I T
V E
O
M A
H A
N
E
D
R
O D
D Y
F I
A F
ADVERTISEMENT - NOT FOR CONSTRUCTION
\\BMCD\DFS\CLIENTS\ANF\USCOE\NWO\107341_GENMITCHMILCON\DESIGN\CIVIL\SHEETS\MT18-G-001.DWG 6/9/2020 9:04 AM JCEICHENBERGER
G-002
S H
E E
T
I N
D E
X
DRAWING INDEX
NOTE: ALL POL SITE REFERENCE DRAWINGS FOLLOWING FA603 ARE FOR REFERENCE ONLY.
A
M E
N D
M E
AutoCAD SHX Text
M. LITWIN
AutoCAD SHX Text
J. EICHENBERGER
AutoCAD SHX Text
S. MCLAUGHLIN
AutoCAD SHX Text MT18-G-001.dwg
/2
T /2
2"
CL SLEEVE
GALVANIZED STD WEIGHT
STEEL PIPE OR APPROVED
PREFABRICATED SLEEVE 1
TO 2 PIPE SIZES LARGER
THAN CARRIER PIPE SIZE TO
SUIT PIPE SEAL SYSTEM.
COORD WITH MECH
CONCRETE
SLAB OR WALL
STEEL RING 1/4" x 2" ALL
AROUND. GALVANIZE
AFTER ASSEMBLY
OMIT PROJECTION
UNDER SLABS (UNO)
3/16
U N
O
T
/2
3"
T /2
3"
1/2"
SMOOTH DOWEL SHOP EPOXY-
COATED. GREASE ONE END.
PLACE 12" MIN FROM ANY
JOINT INTERSECTION
BACKER ROD AND
SEALANT UNO
CONSTRUCTION JOINT (CJ)
TYP SLAB RST
(SINGLE OR DOUBLE
LAYER AS INDICATED)
CORNER BAR
CORNER BAR
DOWEL BAR
NOTE:
NOTE:
S P
L
IC
E
STD HOOK STD HOOK
S P
L
IC
E
SPLICE
S P
L
IC
E
STD HOOK
SPLICE
S P
L
IC
E CONSTRUCTION JOINT
AS REQUIRED WITH
1 1/2" x 3 1/2" KEYWAY
CORNER BAR SIZE AND
SPACING TO MATCH SIZE AND
SPACING OF LARGER DIAMETER
HORIZONTAL WALL REBAR (UNO).
DOWEL BAR
ALTERNATE HOOK
DIRECTION @
EVERY OTHER BAR
DOWEL BAR SIZE AND SPACING TO MATCH SIZE AND SPACING OF LARGER DIAMETER HORIZONTAL WALL REBAR.
AT CORNERS AT CORNERS AT INTERSECTIONS AT INTERSECTIONS
VERTICAL SURFACE
EXPANSION JOINT FILLER
1/2" TYP UNO
SEALANT AND
BACKER ROD, UNO
FLOOR SLAB
ISOLATION JOINT (IJ)
W16X26
STEEL BEAM SIZE
STANDARD BEAM CONNECTION,
SEE NOTES BELOW
NOTES:
1. UNLESS NOTED OTHERWISE ALL BEAMS ON COLUMN ROW SHALL
BE IN ACCORDANCE WITH TABLE 10-12 CASE 1 OF AISC STEEL
CONSTRUCTION MANUAL 14TH EDITION WITH SHOP WELDS.
2. END CONNECTIONS SHALL BE STANDARD "FRAMED BEAM" SNUG
TIGHTENED WITH THREADS INCLUDED CONNECTIONS PER TABLE 10-1
OF AISC STEEL CONSTRUCTION MANUAL 14TH EDITION.
UNLESS OTHERWISE INDICATED THE FOLLOWING MINIMUMS
APPLY TO TABLE 10-1 CONNECTIONS.
2"
2"
G ¹
GG
G & G¹ = 2" MIN FOR STD HOLES (G¹ = 1 1/4" MIN FOR BEAMS LESS
THAN A W12).
G & G¹ = 2 1/4" MIN FOR OVERSIZED AND SHORT SLOTTED HOLES
(G¹ = 1 3/8" MIN FOR BEAMS LESS THAN A W12).
MINIMUM CLIP ANGLE THICKNESS SHALL BE 3/8", UNO.
TABLE 10-12 CASE 1 WELDS TO BE 3/16".
3. BEAM END CONNECTIONS SHALL BE IN ACCORDANCE
WITH THESE NOTES AND WITH THE FOLLOWING MINIMUM
NUMBER OF HIGH STRENGTH BOLTS:
C6, W6, OR LESS = 2 ROWS W21 = 4 ROWS
C8 OR W8 = 2 ROWS W24 = 5 ROWS
C10 OR W10 = 2 ROWS W27 = 6 ROWS
C12 OR W12 = 2 ROWS W30 = 7 ROWS
W14 = 3 ROWS W33 = 8 ROWS
C15 OR W16 = 3 ROWS W36 = 8 ROWS
W 18 = 4 ROWS
4. THE NUMBER OF BOLTS AND NUMBER OF ROWS OF BOLTS INDICATED
OR STATED IS THE MINIMUM NUMBER OF BOLTS OR ROWS. PROVIDE
ADDITIONAL BOLTS OR CONNECTION DEVICES, IF NECESSARY, TO
COMPLY WITH OSHA REGULATION 29CFR1926 SUBPART R-STEEL
ERECTION.
5. ROWS OF BOLTS: THE NUMBER OF FASTENERS IN A VERTICAL ROW.
6. BEAM CONNECTIONS ARE BASED ON THE USE OF STANDARD,
OVERSIZED OR SHORT-SLOTTED HOLES AS DEFINED BY AISC STEEL
CONSTRUCTION MANUAL 14TH EDITION. LONG-SLOTTED HOLES ARE
NOT PERMITTED, UNLESS INDICATED OTHERWISE.
7. BEAM CONNECTIONS GAGE SHALL BE 5 1/2" MAX GAGE MAY BE
REDUCED AT FABRICATORS OPTION.
G ¹
L4X3 (LLO), UNO L4X3 (LLO), UNO
D
T /2
T
3" MAX
LESSER
OF T/4
OR 3"SMOOTH DOWEL SHOP
EPOXY - COATED. GREASE
ONE END. PLACE 12" MIN
FROM ANY JOINT INTERSECTION
1/8" TO 3/16"
(SAWED OR FORMED)
BACKER ROD
AND SEALANT,
UNO
CONTROL JOINT (CLJ)
TYP SLAB RST
(SINGLE OR DOUBLE
LAYER AS INDICATED)
BUILDING SLAB
TRAFFIC SLAB 1"
3/4"
1'-6"
1'-4"
1'-0"
1'-4"
LOCATION DIAMETER LENGTH SPACING
SMOOTH DOWEL SCHEDULE
NOTES:
1. PROVIDE FUEL RESISTANT JOINT SEALANT, UNO.
2. SLAB CONSTRUCTION JOINTS INDICATED IN THE DRAWINGS MAY
BE REPLACED WITH CONTROL JOINTS, OR VICE-VERSA UPON
CONTRACTING OFFICER'S APPROVAL.
3. OMIT DOWELS IN SLABS 5" AND THINNER.
4. PROVIDE SMOOTH DOWELS IN JOINTS OF THICKENED SLAB EDGES
SIMILARLY AS SHOWN ABOVE.
5. INSTALL DOWELS IN CONTROL JOINTS USING PREFABRICATED
DOWEL BASKET ASSEMBLIES.
NOTES:
ANCHOR COLLAR
FUEL PIPELINE
CL PIPE
L/2
3"T3"
PIPELINE CASING
INSULATOR
1/4" THICK CONT
STEEL ANCHOR
COLLAR (WELD TO
PIPE SLEEVE BOTH
SIDES OF COLLAR)
1. FUEL PIPE, PIPE SLEEVE, CASING PIPE
INSULATORS, SLEEVE AND CASING SEALS - AS
REQUIRED BY THE CONTRACT
SPECIFICATIONS.
2. NON-SHRINK GROUT SHALL BE INSTALLED
AFTER PIPE AND SLEEVE ASSEMBLY HAS BEEN
INSTALLED.
3. DIMENSION "T" TO BE FIELD VERIFIED.
4. DIMENSION "L" TO BE DETERMINED BY
DIMENSION "T".
5. GROUT FILL NOT REQUIRED IF PIPE SLEEVE
IS CAST INTEGRAL/MONOLITHIC WITH WALL.
6. PROVIDE 1" DEEP (MIN) CLEAN SAWCUT ALL
AROUND PRIOR TO ENLARGING THE OPENING.
PRESERVE ALL EXISTING WALL REINFORCING
EXCEPT THOSE INTERFERING WITH THE NEW
SLEEVE. REPLACE REINFORCING CUT OR
DAMAGED BY PLACING NEW REINFORCING OF
SAME SIZE AND QUANTITY ON EACH SIDE OF
THE NEW SLEEVE. DRILL AND EMBED NEW
REINFORCING INTO EXISTING CONCRETE
WALL USING ADHESIVE ANCHORING
COMPOUND. L
SEGMENTED PIPE SEAL (2 TOTAL)
PIPE SLEEVE. COORDINATE SIZE
WITH SEGMENTED PIPE SEAL
REQUIREMENTS.
SEE MF512 FOR SLEEVE DETAIL
RECTANGULAR
OPENING IN WALL
FOR PIPE
PENETRATION WITH
ROUGHENED
INTERFACE
SEE NOTE 6
CL
EXISTING CONCRETE WALL
NON-SHRINK
GROUT FILL
SEE NOTE 6
3/16
CONT FUEL-RESISTANT
SELF-EXPANDING STRIP
WATERSTOP
7.
BACKER ROD AND
JOINT SEALANT
PVC PIPE
SLEEVE
PIPE OR
CONDUIT
FDN WALL OR
GRADE BEAM
Omaha District
US Army Corps of Engineers ®
M A
K
S
C R
IP
T
IO
N
D A
T E
1 2 3 4 5
A
FILE:
DATE:
W
A R
D P
A R
K W
A Y
K A
N S
A S
C
IT
Y
M O
D E
S
IG
N E
D B
Y
D R
A W
N B
Y
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
S O
L
IC
IT
A
T
IO
N N
O
W F
-2 -R
-0
C O
N T
R A
C T
N O
U S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
O M
A H
A D
IS
T
R
IC
T C
A P
IT
O
L A
V E
O
M A
H A
N
E
S
IZ
E
X
SHEET ID
IS
S
U E
D D
A T
E
D E
S C
P
O L F
A C
IL
IT
IE
S
R E
P L A
C E
M E
N T
G E
N E
R A
L M
IT
C
H E
L L I A
P
W I
6 7 8 9 10
B
C
D
E
F
G
F
IL
E N
O
A F
-1
-0
ADVERTISEMENT - NOT FOR CONSTRUCTION
7/24/2020 9:14:12 AM
H S
A H
U D
IN
M P
A T
E L
J H
E
IM
107341S-502MT18
D R
O D
D Y
S-502
J U
N E
S T
A N
D A
R D
S T
R U
C T
U R
A L D
E T
A
IL
S S
H E
E T
NTSSCALE:
F1
TYPICAL PIPE SLEEVE DETAIL
NTSSCALE:
A3
TYP WALL & GRADE BEAM REINFORCEMENT DETAILS
NTSSCALE:
A1
STD BEAM CONNECTIONS
NTSSCALE:
E3
TYP SLAB-ON-GRADE JOINT DETAILS
NTSSCALE:
C3
PIPE SLEEVE THROUGH EXISTING WALL
NTSSCALE:
C8
TYPICAL UTILITY PENETRATION
THROUGH FOUNDATION WALL/GRADE BEAM
R
T A
D E
S
IG
N S
U B
M
IT
T A
L
/2
/2
A
M E
N D
M E
N T
/2 /2
1 1
3/4" CHAMFER, TYP
CONC SLAB
EL PER PLAN
T/RINGWALL
(5) #6 T&B
6-#6 EF FACE BARS
#4 TIES @ 9" OC, PROVIDE
TWO SETS OF TIES ON EACH
SIDE OF ANCHOR BOLTS
(WHERE PRESENT)
TANK BOTTOM
SET HIGH POINT OF RINGWALL AT EDGE
OF TANK CHIME. SET SHELL CENTERED
ON RINGWALL
SLOPE DOWN 5% TO MATCH
TANK BOTTOM SLOPE
SAND BEDDING
GEOTEXTILE FABRIC
FML
2'-0"
PROVIDE 3" OF
SLACK IN FML
ALONG RINGWALL
FML
GEOTEXTILE
FABRIC
" 3" COVER
2" COVER, TYP UNO
FUEL RESISTANT JOINT SEALANT
1/2" MIN ASPHALT IMPREGNATED FIBER BOARD
1'-0"
(8) #6 HORIZ
#4 VERT @ 12"
OC
LEAK DETECTION WELL
4"Ø SCH 40 SS PIPE
AND FITTINGS
TYP RINGWALL RST
PER SECTION
TANK RINGWALL
D5
S-512
1'-0"
1'-0"
2' -0
'-0
D1 / S-512
TANK BOTTOM
TANK SHELL
8" HINGED, LOCKABLE ALUMINUM
GAGE HATCH COVER W/ WATER
TIGHT SEAL
8" SS CASING PIPE. EMBED
16" MIN INTO FOUNDATION
AND FILL VOID W/ GROUT
CONC SLAB
LEAK DETECTION WELL
4" SCH 40 304 SS PIPE
AND FITTINGS
RINGWALL
FOUNDATION
GEOTEXTILE FABRIC
FML
4" THREADED SS
COUPLING (TYP)
4" FRP LEAK
DETECTION
TELL-TALE PIPE
2'-0"
1'-0" 1'-0"
CP/TRACER PIPE
GEOTEXTILE
FABRIC
FML
8" SS PIPE
JOINT SEALANT
AND BACKER ROD
TYP RINGWALL RST
PER SECTION
/8
D1 / S-512
LEAK DETECTION
WELL ADD RST PER
DETAIL A1 / S-512
1'-0"
3'-0"
8"
4'-8"
A6
S-512
TANK BOTTOM
TANK SHELL
RINGWALL
FOUNDATION
GEOTEXTILE FABRIC
CP/TRACER PIPE
1'-0"3'-8"2'-0"
/2
/2
1'-0"
#5 @ 12" OC
HORIZ
#5 @ 12" OC
VERT
#5 @ 12" OC
HORIZ PERIMETER
FML
TYP RINGWALL RST PER
SECTION D1 / S-512
TANK BOTTOM
TANK SHELL
2"
TANK EXTERIOR TANK INTERIOR
1/2" BUNA-N TANK BOTTOM
TO FOUNDATION GASKET1/2"
FUEL RESISTANT
JONT SEALANT.
DO NOT SEAL
END OF CHIME
TOP OF CONCRETE
RINGWALL FOUNDATION
Omaha District
US Army Corps of Engineers ®
M A
S
C R
IP
T
IO
N
D A
T E
1 2 3 4 5
A
FILE:
DATE:
W
A R
D P
A R
K W
A Y
K A
N S
A S
C
IT
Y
M O
D E
S
IG
N E
D B
Y
D R
A W
N B
Y
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
S O
L
IC
IT
A
T
IO
N N
O
W F
-2 -R
-0
C O
N T
R A
C T
N O
U S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
O M
A H
A D
IS
T
R
IC
T C
A P
IT
O
L A
V E
O
M A
H A
N
E
S
IZ
E
X
SHEET ID
IS
S
U E
D D
A T
E
D E
S C
P
O L F
A C
IL
IT
IE
S
R E
P L A
C E
M E
N T
G E
N E
R A
L M
IT
C
H E
L L I A
P
W I
6 7 8 9 10
B
C
D
E
F
G
F
IL
E N
O
A F
-1
-0
ADVERTISEMENT - NOT FOR CONSTRUCTION
7/24/2020 9:14:13 AM
H S
A H
U D
IN
M P
A T
E L
J H
E
IM
107341S-512MT18
D R
O D
D Y
S-512
J U
N E
T A
N K
F O
U N
D A
T
IO
N S
E C
T
IO
N S
A N
D D
E T
A
IL
S
SCALE: 1" = 1'-0"
D1
DETAIL
0 1/2' 1' 2'
SCALE: 1/2" = 1'-0"
A1
DETAIL
0 1' 2' 4'
SCALE: 1" = 1'-0"
D5
LEAK DETECTION WELL
0 1/2' 1' 2'
SCALE: 1/2" = 1'-0"
A4
TANK STAIR LANDING PAD DETAIL
0 1' 2' 4' SCALE: 1" = 1'-0"
A6
SECTION
0 1/2' 1' 2'
R
T A
D E
S
IG
N S
U B
M
IT
T A
L
/2
/2
A
M E
N D
M E
N T
/2 /2
SCALE: 1 1/2" = 1'-0"
E8
UNANCHORED TANK BOTTOM SEAL
. S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
O M
AH
A
D
IS
TR
IC
T
W
AR
D P
AR
KW
AY
KA
N
SA
S C
IT
Y, M O
D
ES
C
P
O L
FA
C
IL
IT
IE
S
R
EP
LA
C
EM
EN
T G
EN
ER
AL
M
IT
C
H
EL
L
IA
P, W
I
US Army Corps of Engineers Omaha District
SO
LI
C
IT
AT
IO
N N
O
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
M
AR
K
SI
ZE
SU
BM
IT
TE
D B
Y:
D
AT
E
C O
N
TR
AC
T
N O
C
H
EC
KE
D
B Y:
D R
AW
N
B Y:
IS
SU
E D
AT
E:
SHEET ID
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
W
F-
-R
-0
X2
R
TA
D
ES
IG
N S
U
BM
IT
TA
L
/2 9/
R
TA
D
ES
IG
N
S U
BM
IT
TA
L
/2
9/
JU
N
E
C
AP
IT
O
L
AV
E, O
M
AH
A, N
E
D . R
O D
D Y
FI
LE
N O
AF
4-
-0
ADVERTISEMENT - NOT FOR CONSTRUCTION
MF312
SE
C
TI
O
N S
- T
YP
E
III
P U
M
PH
O U
SE
A1 SCALE: 3/8" = 1'-0"
SECTION - PUMP HOUSE RECEIPT FILTRATION AND JOCKEY PUMP
1. REFER TO DRAWINGS MF001 AND MF002 FOR
LEGENDS, ABBREVIATIONS, AND GENERAL NOTES.
2. ALL LARGE BORE MANUAL VALVES LOCATED 72"
(OR GREATER) ABOVE THE FINISHED FLOOR,
SHALL BE PROVIDED WITH CHAIN OPERATORS.
E1 SCALE: 3/8" = 1'-0"
SECTION - PUMP HOUSE ISSUE PUMPS AND FILTRATION
6'
SCALE IN FEET
0 2' 4'
6'
SCALE IN FEET
0 2' 4'
FILTER SEPARATOR (REFER
TO DETAIL FOR SLOW FILL,
DRAIN AND TRV CONNECTION) MF513
A1FILTER
SEPARATOR
ELEMENT
CLEARANCE
REQUIREMENTS
FSI-5
600 GPM
FSCV-5
DR
TRENCH
DR PS
-1
2" SS F/S
SLOW FILL
2" SS TRV/DRAIN
FROM FILTER
SEPARATORS
PS
-9
MAV
PGPG
CV-56" BALL
VALVE
FP-5
600 GPM
PG
PG
DR
PS-4 PDP-1
10 GPM
6" CS
6" C
S
6" BALL
VALVE
TRV
TRV
FLOW
SWITCHMF514
A7
3" SS FLEX
CONNECTOR
3" CHECK
VALVE
6" X 3"
REDUCER
6" CS
4" SS FLEX
CONNECTOR
8" X 4" FOT
REDUCER
16" SUCTION
HEADER
2" SS TRV/DRAIN
TRV
(BEHIND)
DR
PS-1
2" BALL
VALVE
RECEIPT
FLOW
METER MF513
E1
JP-1
5 GPM
PG
2" CS F/S SLOW
FILL (TO TRENCH)
2" Y-STRAINER
1 1/4"
SS FLEX
2" X 1 1/4"
REDUCER
2" CHECK
VALVE
8' -6
MAV
MAV
MAV
MAV
PS-9PS-4A
PS-17PS-17
2" RETURN
FROM PRT PS-17 PS-17 PS-17
PS-4A PS-4
PS
-1
DR
FILTER SEPARATOR
(REFER TO DETAIL FOR
SLOW FILL, DRAIN AND
TRV CONNECTION)
FILTER SEPARATOR
ELEMENT CLEARANCE
REQUIREMENT
MF513
A1
FSR-1
1200 GPM
FSCV-6
PS-14
8" BALL VALVE
(BEHIND)
PG
8" BALL
VALVE
8" CS
8" CS
8" CS
8" CS
'-6
PS
-4
(O N
BY
PA
SS
TRV
8' -6
2" RETURN
FROM PRT
12" CS
12" CS
PS-6
ELECTRICAL/CONTROL
ROOM, ROOF ACCESS
'-6
MAV
NOTES:
TOP OF SLAB
TOP OF CURB
8" BASKET
STRAINER
8" DBB PLUG
VALVE
TOP OF SLAB
TOP OF CURB
PS-15
2" RETURN FROM PRT
℄ ELEVATION: 682'-9"
PS-15
D A
PS-1
AM
EN
D
M
EN
T
/2 7/
AutoCAD SHX Text
B. COOVER
AutoCAD SHX Text
H. HARMON
R. PERUE
. S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
O M
AH
A
D
IS
TR
IC
T
W
AR
D P
AR
KW
AY
KA
N
SA
S C
IT
Y, M O
D
ES
C
P
O L
FA
C
IL
IT
IE
S
R
EP
LA
C
EM
EN
T G
EN
ER
AL
M
IT
C
H
EL
L
IA
P, W
I
US Army Corps of Engineers Omaha District
SO
LI
C
IT
AT
IO
N N
O
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
M
AR
K
SI
ZE
SU
BM
IT
TE
D B
Y:
D
AT
E
C O
N
TR
AC
T
N O
C
H
EC
KE
D
B Y:
D R
AW
N
B Y:
IS
SU
E D
AT
E:
SHEET ID
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
W
F-
-R
-0
X2
R
TA
D
ES
IG
N S
U
BM
IT
TA
L
/2 9/
R
TA
D
ES
IG
N
S U
BM
IT
TA
L
/2
9/
JU
N
E
C
AP
IT
O
L
AV
E, O
M
AH
A, N
E
D . R
O D
D Y
FI
LE
N O
AF
4-
-0
ADVERTISEMENT - NOT FOR CONSTRUCTION
A1 ENLARGED PLAN - TYPE III HYDRANT SYSTEM PUMP HOUSE
SCALE: 1/4" = 1'-0"
N
MF411
EN
LA
R G
ED
P
LA
N
TY
PE
II
I H
YD
R
AN
T
SY
ST
EM
P
U M
PH
O
SE
AT
C H
LI
N
E
- S
EE
D
R
AW
IN
G
M F4
N
A/C
KEY PLANMF313
A1
MF312
A1
MF312
E1
MF311
A1
MF311
E1
NOTES:
1. REFER TO DRAWINGS MF001 AND MF002 FOR
LEGENDS, ABBREVIATIONS, AND GENERAL NOTES.
2. REFER TO SECTION CUTS FOR CLARITY OF
STACKED PIPING.
3. EXTEND UNDERGROUND FBE COATING A MINIMUM
OF 6 INCHES ABOVE CONCRETE PENETRATION
SLEEVE.
4. ALL LARGE BORE MANUAL VALVES LOCATED 72"
(OR GREATER) ABOVE THE FINISHED FLOOR,
SHALL BE PROVIDED WITH CHAIN OPERATORS.
5. SMALL BORE PIPING IS SHOWN SCHEMATICALLY.
REFER TO P&ID'S FOR SIZES. REFER TO
APPROPRIATE DETAILS ON MF512 TO MF515.
6. REFER TO STRUCTURAL DRAWINGS FOR PIPE
SUPPORT COORDINATION. PUMP HOUSE PIPE
SUPPORT SPACING AS INDICATED ON S-105.
REFER TO S-551 TO S-556 FOR PIPE SUPPORT
DETAILS. PIPES SHALL BE CENTERED ON THE PIPE
SUPPORT FOUNDATIONS.
7. FOR SMALL BORE PIPING ROUTED AROUND THE
PERIMETER OF THE PUMP ROOM, REFER TO PS-16
(ONE PIPE ONLY) AND SUPPORT AT INCREMENTS
NOT TO EXCEED 12 FEET.
8. MOUNT PRESSURE INDICATING TRANSMITTER
INSIDE PUMP ROOM NEAR 8" BALL VALVE MOV.
9. REFER TO MF512, DETAIL A4 FOR JET FUEL
PRODUCT LABELING REQUIREMENTS.
10. REFER TO A-503, DETAIL A3 FOR PIPE
PENETRATION REQUIREMENTS FOR PUMPHOUSE
EXTERIOR WALL PENETRATIONS.
SCALE IN FEET
0 2' 4' 8'
KEYED NOTES:
THE HINGE FOR FILTER SEPARATORS SHALL
OPEN AS INDICATED. MAINTAIN CLEAR SPACE
FOR FILTER PULL DISTANCE.
SUPPORT PIPING WITHIN PIPE TRENCH PER THE
STRUCTURAL TRENCH DETAIL AT INCREMENTS
NOT TO EXCEED 5 FT.
PROVIDE 1" BLIND FLANGE FOR FUTURE
CONNECTION FOR LEAK DETECTION SYSTEM.
12" DBB
PLUG VALVE
(MOTOR
OPERATED)
12" CS
HYDRANT
ISSUE
12" CS
HYDRANT
RETURN
8" DBB PLUG VALVE
8" CS TO TRUCK FILLSTAND
4" BALL VALVE W/BLIND (KICKER
FOR PIG LAUNCHER / RECEIVER)
PS-4
12" FULL BORE
DBB PLUG
VALVES
(TYP OF 2)
12" TEMPORARY
PIG LAUNCHER
EXTENSION (NIC)
12" TEMPORARY
PIG RECEIVER
EXTENSION (NIC)
PS-4
4" BALL VALVE W/
BLIND (KICKER FOR PIG
LAUNCHER / RECEIVER)
12" DBB PLUG VALVE
(MOTOR OPERATED)
PS-4A
PS-6
PS-7
PS-7
PS-4
PS-4C
PS-8
PS-4
PS-4A
PS-4
PS-14
PS-14
PS-10
PS-4A
PS-5
PS-4
PS-4
PS-4
PS-4
PS-4
PS-9
PS-4D PS-4
PS-6C
PS-6
PS-8
PS-4
PS-4C
PS-4
PS-15
PS-15
PG
PG
PC
V-
MAV
MAV
MAV
PS-4CSURGE
SUPPRESSOR
(TYP OF 2)MF513
D7
FSI-5
600 GPM
FSI-4
600 GPM
FSI-3
600 GPM
FSI-2
600 GPM
FSI-1
600 GPM
FSR-2
1200 GPM
FSR-1
1200 GPM 1
FSCV-5
FSCV-4
FSCV-3
FSCV-2
FSCV-1
FSCV-7
FSCV-6
8" BV
8" BALL VALVE
(SEE NOTE 4)
MAV
MAV
MAV
MAV
MAV
MAV
MAV
D /F
V-
B
PC
V-
(B
EL
O W
8" CS
8" CS
8" DBB PLUG VALVE
8" CS FROM HHT
CHECKOUT
8" DBB PLUG VALVE
8" CS FROM TRUCK
OFFLOADING
8" BLIND FLANGE
8" FUTURE RECEIPT
FROM COMMERCIAL
AIRPORT
8" BASKET
STRAINER
8" BALL
VALVE (IN THE
VERTICAL)
8" CS
8" C
S
8" CS
8" C
S
FLOOR
TRENCH
" C
S
" C
S
" C
S
" C
S
12" CS
10" CS
10" ISSUE
VENTURI
CV-5
CV-4
CV-3
CV-2
CV-1
FP-2
600 GPM
FP-3
600 GPM
FP-4
600 GPM
FP-5
600 GPM
PRESSURE
TRANSMITTER
(FP-1 ONLY)
6" BALL VALVE,
SEE NOTE 4
(TYP OF 5)
4" FLEX
CONNECTOR
(TYP OF 5)
8" X 4" FOT
REDUCER
PG
PG
FLOW
SWITCH
(TYP OF 5)MF514
A7
8" BASKET
STRAINER
(TYP OF 5)
8" DBB PLUG
VALVE (TYP OF 5)
16" ELBOW, ROLLED
MATCH PUMP
CENTERLINE ELEVATION
8" ELBOW
8" CS
PS-4C
SEE CONTINUATION ON MF412
MAV
8" BALL VALVE
(MOTOR OPERATED)
MAV
PS-7
TRV
TRV
PDP-1
10 GPM
2" BALL VALVE
2" WAFER
CHECK VALVE
2" CHECK VALVE
2" CS PRODUCT RETURN
℄ ELEVATION: 684'-0"
2" SS DRAIN/TRV TO PRT
℄ ELEVATION: 682'-9"
16" CS F-24 SUCTION
8" CS F-24 TANK 2 FILL
8" CS F-24 TANK 1 FILL
PG
TRV
S
JP-1
5 GPM
TRV
TRV
TRV TRV
2" RETURN
FROM PRT
8" BV
8" BV
8" BV
8" B
V
2" SS DRAIN/TRV
2" SS F/S SLOW FILL
FLOOR
TRENCH
2" SS DRAIN/TRV
2" SS F/S SLOW FILL
TRV
TRV
8" DBB PLUG
VALVES WITH
LIMIT SWITCHES
(TYP OF 4)
PG
8" BV
2" Y-
STRAINER
1 1/4" FLEX
CONNECTOR
PG
2" SS
DRAIN/TRV
8" CS
8" CS
2" BV
TRV
MAV
PG
2" SS DRAIN/TRV
℄ELEVATION: 681'-9"
2" BALL VALVE
2" BASKET
STRAINER
PS-4A
PG
2" BALL
VALVEMAV
MAV
TRV
TRV
TRV
FLOOR
TRENCH2
TRV TRV
TRV
TRV
2" BALL VALVE
(MOTOR OPERATED)
PRESSURE
INDICATING
TRANSMITTER
SEE NOTE 8
PS-15
PS-15
PS-15
PS-15
PS-15
PS-15
PS-15
2" SS F/S
SLOW FILL
PG
PG
PG
6" BV
6" BV
6" BV
6" BV
6" BVPG
SRV-2
PG
PS-17 PS-17 PS-17 PS-17 PS-17
S
2" BV
TRV
TRV
TRV
TRV
TRV
TRV
TRV8" BV
2" RETURN
FROM PRT
2" CS PRODUCT RETURN
℄ ELEVATION: 694'-0"
2" CS PRODUCT RETURN
℄ ELEVATION: 682'-9"
1/2" FUTURE
MONITORING POINT
2" SS DRAIN/TRV
℄ELEVATION: 681'-9"
MAV
CV-7PS-3A
IF
IFIF
IF
12" CS F-24
℄ ELEVATION: 683'-0"
12" CS F-24
℄ ELEVATION: 683'-0"
IF
IF
IF
IF
1" BLIND FOR
FUTURE TRV
10" CS
PS-18 (BELOW)
PS-18 (BELOW)
ISOLATED EQUIPMENT
PAD
CONCRETE PENETRATION
SLEEVE (TYP OF 3)
CONCRETE
PENETRATION
SLEEVE (TYP OF 2)
ISOLATED
EQUIPMENT PAD
MATCHLINE - SEE DRAWING MF101
MATCHLINE - SEE DRAWING MF101
M
AT
C H
LI
N
E
- S
EE
D
R
AW
IN
G
M F1
DR
16" TEE, ROLLED
2" DBB (TYP OF 2) FP-1
600 GPM FLOW
SWITCH
12" BARRED TEE
(TYP OF 2)
FLOW
SWITCH
AM
EN
D
M
EN
T
/2 7/
AutoCAD SHX Text
B. COOVER
AutoCAD SHX Text
H. HARMON
MECHANICAL
CONSTRUCTION PHASING
U . S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
O M
AH
A
D
IS
TR
IC
T
W
AR
D P
AR
KW
AY
KA
N
SA
S C
IT
Y, M O
D
ES
C
P
O L
FA
C
IL
IT
IE
S
R
EP
LA
C
EM
EN
T G
EN
ER
AL
M
IT
C
H
EL
L
IA
P, W
I
US Army Corps of Engineers Omaha District
SO
LI
C
IT
AT
IO
N N
O
D
ES
IG
N
ED
B
Y:
D
ES
C R
IP
TI
O N
M
AR
K
SI
ZE
SU
BM
IT
TE
D B
Y:
D
AT
E
C O
N
TR
AC
T
N O
C
H
EC
KE
D
B Y:
D R
AW
N
B Y:
IS
SU
E D
AT
E:
SHEET ID
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
W
F-
-R
-0
X2
R
TA
D
ES
IG
N S
U
BM
IT
TA
L
/2 9/
R
TA
D
ES
IG
N
S U
BM
IT
TA
L
/2
9/
JU
N
E
C
AP
IT
O
L
AV
E, O
M
AH
A, N
E
D . R
O D
D Y
FI
LE
N O
AF
4-
-0
ADVERTISEMENT - NOT FOR CONSTRUCTION
MF801
M
EC
H
AN
IC
AL
E Q
U
IP
M
EN
T
SC
H
ED
U
LE
S (1
O F
2)
AM
EN
D M
EN
T
/2
7/
AutoCAD SHX Text
B. COOVER
AutoCAD SHX Text
H. HARMON
X
X
X
U
P
U
P
U P
U P
U
P
U P
U P
U
P
U P
U P
U
P
U P
U
P
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
UP
U
P
U
P
U
P U
P
U
P
U
E
U
C
UE/UC UE/UC UE/UC UE/UC UE/UC UE/UC UE/UC UE/UC
U
C
U
C
U
E
U
C
U E
U
C U
E U
C U
E U
C U
E U
C U
E U
C
U
E
U
C
U
E
U
E
U
E
U
C
U
E
U
C
U
E
U
C
U
E
U
C
UE/UC
U E
U
C U
E U
C U
E U
C U
E U
C U
E U
C
UE/UCUE/UC
U
E
U
C
U
E
U
C
U
E
U
C
U
E
U
C
U
E
U
C
U
E
U
C
U
E
U
C
MM
U
S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O M
A H
A
D
I S
T R
I C
T
R
K W
A Y
K A
N S
T
Y
D E
S C
C
I L
I T
I E
S
R
E P
L A
C E
M E
N T
G E
N E
R A
L
M
I T
C H
E L
L
I A
P
W
I
US Army Corps of Engineers
Omaha District
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
SHEET ID
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
W F
R
X
R
S
I G
N
S
U B
M I T
T A
L
R T
A
D
E S
I G
N
S
U B
M I T
T A
L
J U
P
I T
E
O
M A
H A
N
E
D
R
O D
D Y
F I
A F
ADVERTISEMENT - NOT FOR CONSTRUCTION
\\BMCD\DFS\CLIENTS\ANF\USCOE\NWO\107341_GENMITCHMILCON\DESIGN\ELEC\SHEETS\MT18-E-091.DWG 7/23/2020 8:31 PM LHURST
E-091
H A
Z A
R D
O U
S
A
R E
A
C
L A
S S
I F
I C
A T
I O
N
P
L A
N
A1
HAZARDOUS AREA CLASSIFICATION PLAN
SCALE: 1"=30'
N
30' 60'0
UTILITY
TRANSFORMER
UTILITY
METERING
STAND-BY
GENERATOR
DISPENSERS (TYP)
PRODUCT SAVER
TANK (TYP)
PUMP HOUSE
REMOTE
CONTAINMENT BASIN
JET FUEL TANK 1
(5K BBL)
JET FUEL TANK 2
(5K BBL)
TRUCK OFFLOAD
POSITION #2
TRUCK OFFLOAD
POSITION #1
REFUELER LOAD
POSITION # 1 & HHTCS
REFUELER LOAD
POSITION #2
EXISTING SMALL
ARMS RANGE
DIESEL AND
MOGAS TANKS
POL OPS
BUILDING
(TYP)
E1
E-093
C1
E-093
E1
E-093
A1
E-092
A7
E-093
A1
E-092
C7
E-093
FITTINGS, FLANGES,
VALVES (TYP)
A1
E-093
PRODUCT
RECOVERY TANK
FUEL OFFLOADING
TRUCK
A5
E-092
TRANSITION SUMP
A7
E-093
STRAINER (TYP)
C1
E-093
STRAINER (TYP)
C1
E-093
OIL/WATER
SEPARATOR
(OWS-01)
D1
E-092
OIL/WATER
SEPARATOR
(OWS-02)
1. ALL EQUIPMENT INSTALLED WITHIN HAZARDOUS
AREAS SHALL BE LABELED AS SUITABLE FOR
USE IN THE HAZARDOUS AREA. ALL ELECTRICAL
EQUIPMENT SHALL BE INSTALLED IN
ACCORDANCE WITH NEC REQUIREMENTS FOR
SUCH AREAS.
2. ALL HEAT-PRODUCING EQUIPMENT SHALL BE
LABELED WITH AN NEC TEMPERATURE
IDENTIFICATION CODE OF T3 MINIMUM (E.G. T3A
IS ACCEPTABLE, T2D IS UNACCEPTABLE).
3. THIS DRAWING REPRESENTS GENERAL
IDENTIFICATION OF HAZARDOUS AREA
CLASSIFICATIONS. REFER TO THE DETAILS ON
E-092 AND E-093, SPECIFICATIONS, API 500, AND
NEC ARTICLES 500, 501, 514 AND 515 FOR
ADDITIONAL REQUIREMENTS.
4. THIS FACILITY RECEIVES/DISTRIBUTES THE
FOLLOWING PRODUCTS ASSOCIATED WITH THIS
PROJECT:
- F-24 - CLASS II LIQUID
- MOGAS - CLASS I LIQUID
- DIESEL - CLASS II LIQUID
CLASS II LIQUIDS SHALL BE CONSIDERED CLASS
I WHEN PRESSURIZED PER UFC 3-460-01.
AREA WITHIN LAB AND LESS THAN 48" AFF SHALL
BE CONSIDERED A CLASS I, DIVISION 2, GROUP D
HAZARDOUS LOCATION. AREA WITHIN 5' OF LAB
FUME HOOD SHALL BE CONSIDERED A CLASS I,
DIVISION 1, GROUP D HAZARDOUS LOCATION.
(REQUIREMENTS PER ANG ETL 15-01-05)
AREA WITHIN SPILL CONTAINMENT BASIN SHALL
BE CONSIDERED A CLASS I, DIVISION 1, GROUP D
HAZARDOUS LOCATION. AREA ABOVE BASIN TO
A HEIGHT OF 18" AND OUT TO 15' FROM EDGE OF
BASIN SHALL BE CONSIDERED A CLASS I,
DIVISION 2, GROUP D HAZARDOUS LOCATION.
DIVISION 2, 10' TRANSITION ZONES AROUND
DOORS AND EXHAUST.
HAZARDOUS AREAS PER UFC 3-460-01, CHAPTER
4.
REFER TO ES501 FOR SEAL-OFF REQUIREMENTS
WHEN TRANSITIONING BETWEEN HAZARDOUS
AREAS / BOUNDARIES. REFER TO ES502 FOR
SEAL-OFF INSTALLATION DETAIL INSIDE
MANHOLES.
CLASS I, DIVISION 1, GROUP D
(REQUIRES T3 RATED MOTORS/EQUIPMENT)
CLASS I, DIVISION 2, GROUP D
(REQUIRES T3 RATED MOTORS/EQUIPMENT)
NON-CLASSIFIED
NOTES:
KEYED NOTES:
LEGEND:
FUEL PIT
FUTURE PIPELINE
RECEIPT
D1
E-092
A5
E-092
TRUCK OFFLOAD
(TYP)
A
M E
N D
M E
S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O M
A H
A
D
I S
T R
I C
T
R
K W
A Y
K A
N S
T
Y
D E
S C
C
I L
I T
I E
S
R
E P
L A
C E
M E
N T
G E
N E
R A
L
M
I T
C H
E L
L
I A
P
W
I
US Army Corps of Engineers
Omaha District
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
SHEET ID
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
W F
R
X
R
S
I G
N
S
U B
M I T
T A
L
R T
A
D
E S
I G
N
S
U B
M I T
T A
L
J U
P
I T
E
O
M A
H A
N
E
D
R
O D
D Y
F I
A F
ADVERTISEMENT - NOT FOR CONSTRUCTION
E-092
H A
Z A
R D
O U
S
A
R E
A
C
L A
S S
I F
I C
A T
I O
N
D
E T
A I L
S
CLASS I, DIVISION 1, GROUP D
(REQUIRES T3 RATED MOTORS/
EQUIPMENT)
CLASS I, DIVISION 2, GROUP D
(REQUIRES T3 RATED MOTORS/
EQUIPMENT)
NON-CLASSIFIED
LEGEND:
10'
A1
TYPICAL ABOVEGROUND HORIZONTAL STORAGE TANK
SCALE: NTS
10'
D1
TYPICAL UNDERGROUND STORAGE TANK
SCALE: NTS
1. THIS DRAWING REPRESENTS GENERAL
IDENTIFICATION OF HAZARDOUS AREA
CLASSIFICATIONS. REFER TO THE SPECIFICATIONS,
API 500, AND ARTICLES 500, 501, 514, AND 515 FOR
ADDITIONAL REQUIREMENTS.
NOTES:
GRADE
SOURCE BENEATH
HAZARDOUS AREA
SOURCE BENEATH
NON-CLASSIFIED AREA
NON-CLASSIFIED
AREA
HAZARDOUS AREA WITH
ABOVE GRADE SOURCE
10'
A5
BELOW GRADE TRENCH CONTAINING PIPING WITH
VALVES, SCREWED FITTINGS, FLANGES OR SIMILAR -
OUTDOORS
SCALE: NTS
POSITION AND NUMBER OF VENTS, MANWAYS, ETC. DEPENDENT ON TANK FABRICATORS.
SPACE ABOVE FUEL AND WITHIN THE TANK SHELL IS A CLASS I, DIVISION 1 AREA.
KEYED NOTES:
PUMP NOZZLE
TANK NOZZLE
WITH FLANGE
GAUGE HATCH
5 RADIUS
10' RADIUS
SUMP NOZZLE
WITH FLANGE
MANWAY
3' RADIUS
VENT
5' RADIUS
10' RADIUS
TANK NOZZLE
WITH FLANGE
3' RADIUS
(TYP)
GRADE
SURFACE OF
CONTENTS
ABOVE GROUND
STORAGE TANK
5' RADIUS
(TYP)
MANUAL
GAUGING
HATCH
MANWAY(TYP)
VENT
10' RADIUS
5' RADIUS
12' ABOVE
GRADE
10' RADIUS
A
M E
N D
M E
S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O M
A H
A
D
I S
T R
I C
T
R
K W
A Y
K A
N S
T
Y
D E
S C
C
I L
I T
I E
S
R
E P
L A
C E
M E
N T
G E
N E
R A
L
M
I T
C H
E L
L
I A
P
W
I
US Army Corps of Engineers
Omaha District
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
SHEET ID
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
W F
R
X
R
S
I G
N
S
U B
M I T
T A
L
R T
A
D
E S
I G
N
S
U B
M I T
T A
L
J U
P
I T
E
O
M A
H A
N
E
D
R
O D
D Y
F I
A F
ADVERTISEMENT - NOT FOR CONSTRUCTION
ES102
D U
C T
B A
S
A
G R
A M
A1
RISER DIAGRAM
SCALE: NTS
JET A TANKS
PRT OWS-01
REFUELER
LOAD #1 AND
HHTCS
OFFLOAD #1 OFFLOAD #2
REFUELER
LOAD #2
EMH-04,
CMH-04
PUMPHOUSE
TMH-01,
EMH-01,
CMH-01
TMH-02,
EMH-02,
CMH-02
U
E
U
C
U
E
U
C
U
E
U
C
U
E
U
C
TMH-03,
EMH-03,
CMH-03
TMH-04,
EMH-05,
CMH-05
U
E
U
C
U
E
U
C
U
E
U
C
U
E
U
C
UE/UC UE/UC UE/UC UE/UC UE/UC
U
E
U
C
U
E
U
C
UE/UC UE/UC UE/UC UE/UC UE/UC UE/UC
U
E
U
C
U
E
U
C
U
E
U
C
U
E
U
C
U
E
U
C
U
E
U
C
U
E
U
C
U
E
U
C
U
E
U
C
U
E
U
C
U
E
U
C
U
E
U
C
U E
U
C U
E U
C U
E U
C U
E U
C U
E U
C U
E U
C U
E U
C U
E U
C
U
E
U
C
REFUELER
PARKING
POL
OPERATIONS
BUILDING
UE/UCUE/UC
REFER TO EP411 FOR
CONDUIT SCHEDULE
FOR THIS DUCTBANK
SECTION
U E
U
C
U E
U
C
U E
U
C
S55
GATE OPERATOR
(EAST)
TO MSS
(SEE EP451)
U
E
U
C
TO EPDS-8D &
GATE
OPERATOR
(NORTH)
U E
U
C
TO
MH27P7
U
E
U
C
TO
LIGHT
POLE
U
E
U
C
S39
TO
LIGHT
POLE
U
E
U
C
TO
LIGHT
POLE
U
E
U
C
U
E
U
C
TO SOUTH
ROAD
S54
DUCTBANK,
MANHOLES, AND
ASSOCIATED
SOUTH ROADWAY
CIRCUITS ARE
PART OF BID
OPTION 008.
U
E
U
C
TO
EPDS-8C
1. THIS SHEET IS DIAGRAMMATIC AND NOT TO
SCALE. REFER TO ES101, ES103, AND
SHEETS INDICATED FOR CONDUIT ROUTING
AND UNDERGROUND STRUCTURE DETAILS.
NOTES:
MAINTAIN ADEQUATE SEPARATION FOR
INTRINSICALLY SAFE CIRCUITS THROUGH
COMMUNICATION MANHOLES AS REQUIRED
BY NFPA 70, 504.30.
KEYED NOTES:
(TYP)
43 5
S
1615 S47
6 1817
1019 S20
87 11
P I/C T
S
47 S
10S27
8 15
P
I/C T
6 18
2221 23
2624 S
S32
127 14
PI/C
14 24
26 S
S29
PI/C
S
S
PI/C
7 21
23 S
S31
PI/C
S
56 S
36S39
P
I/C T
S51
S38
P I/C
S49 S
PI/C
S50S
P I/C
S45S
P I/C
44 S S
PI/C
56 S
PI/C
T
S
I/C
P
S
46 S
34S52
P
I/C T
S39
P
S53
P
P
P
P I/C
REFER TO DETAIL E1, SHEET
ES501 FOR DUCTBANK
SEPARATION REQUIREMENTS
(TYP)
E
C
T
E
C
T
E
C
T
E
C
T
E
C
A
M E
N D
M E
S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O M
A H
A
D
I S
T R
I C
T
R
K W
A Y
K A
N S
T
Y
D E
S C
C
I L
I T
I E
S
R
E P
L A
C E
M E
N T
G E
N E
R A
L
M
I T
C H
E L
L
I A
P
W
I
US Army Corps of Engineers Omaha District
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
SHEET ID
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
W F
R
X
R
S
I G
N
S
U B
M I T
T A
L
R T
A
D
E S
I G
N
S
U B
M I T
T A
L
J U
P
I T
E
O
M A
H A
N
E
D
R
O D
D Y
F I
A F
ADVERTISEMENT - NOT FOR CONSTRUCTION
ES504
E L E
C T
R I C
A L
S
I T
E
D
E T
A I
E
L E
V A
T I O
N S
1. REFER TO E-001 FOR LEGEND,
ABBREVIATIONS AND GENERAL NOTES.
2. REFER TO CONDUIT SCHEDULE ON SHEET
EP451 FOR CIRCUIT IDENTIFICATIONS.
NOTES:
HYDRANT FUELS
EMERGENCY
SHUTDOWN
EPDS SIGN
EPDS PUSHBUTTON
TOP OF
CONCRETE
GALVANIZED
C6x8.2 MEMBER
SEAL-OFF (TYP)
1. MOUNTING TO CONCRETE (SEE LEFT DETAIL)
2. PIER FOUNDATION IN NON-PAVED AREA (SEE RIGHT DETAIL).
CONSTRUCT EPDS STAND
USING VERTICAL,
GALVANIZED C6x8.2
MEMBERS AND PIER
FOUNDATION. PIER
FOUNDATION SHALL BE 18"
DIAMETER WITH 3'-0"
MINIMUM DEPTH.
GRADE
E1
EMERGENCY POWER DOWN SYSTEM (EPDS)
SCALE: NTS
MAINTAINED RED MUSHROOM PUSHBUTTON
WITH GUARD, HERMETICALLY SEALED
NORMALLY-CLOSED CONTACT AND LEGEND
PLATE WITH "PUSH TO STOP" ON RED
BACKGROUND. MOUNT PUSHBUTTON,
GUARD, AND LEGEND PLATE ON FACE OF
NEMA 4X BOX.
SEE DETAIL TO LEFT FOR
STATION SIGNAGE,
SEAL-OFF, AND GROUNDING
REQUIREMENTS
E5
ELEVATION - POL BUILDING WEST WALL VIEW
SCALE: NTS
RELAY
CONTROL
PANEL
TO MSS
NOTES:
STAINLESS STEEL
MOUNTING SCREW
QUANTITY AND LOCATION
AS REQUIRED (TYP)
84"
AG
(MINIMUM)
LETTERS 2"
HIGH
3/4" SPACE
(TYP)
1. PAINTED ALUMINUM SIGN OF THICKNESS SUITABLE FOR APPLICATION.
2. EUROSTILE BOLD EXTENDED STYLE LETTERS.
3. COLORS: LETTERS - RED
BACKGROUND - WHITE
4. PAINT SCREW HEADS TO MATCH SIGN COLOR.
5. PROVIDE SIGN WITH "MSS FUELS EMERGENCY SHUTDOWN" FOR MSS STATIONS.
HYDRANT FUELS
EMERGENCY
SHUTDOWN
18"
13"
A5
EPDS SIGN
SCALE: NTS
5" 2"
1/4
2"
9"
TOP OF
CONCRETE PAD
GALVANIZED C6x8.2
MEMBER
3/4" BASE PLATE
(4) 5/8" DIAMETER,
EXPANSION ANCHORS, 4"
MINIMUM EMBEDMENT
TO GROUND GRID OR
ROD AS INDICATED ON
DETAILS OR PLANS
#1/0 BOLTED GROUND CABLE.
DRILL HOLE PRIOR
TO GALVANIZING
A1
TYPICAL CONCRETE PAD & PIER FOUNDATIONS
SCALE: NTS
C1
EQUIPMENT RACK BASEPLATE
SCALE: NTS
ES504
C1
4'-0"
MAX
(TYP)
A1
ES504
(TYP)
GRADE
DIP-2
DIESEL
MS
TO ATG PANEL IN
POL BUILDING
CONTROL ROOM
3/4"C: T.TC.RCP
NOTES:
1. ELECTRICAL DEVICES SHALL BE FURNISHED AS
PACKAGED UNIT WITH EEW/S SYSTEM AND INSTALLED BY
ELECTRICAL CONTRACTOR.
2. ALL COMPONENTS AND WIRING SHALL MEET CLASS I, DIV 1
OR 2 REQUIREMENTS WHEN LOCATED WITHIN
HAZARDOUS AREAS, REFER TO SHEET E-091.
3. PROVIDE ADDITIONAL RELAY(S), AS NECESSARY, FOR POL
BUILDING EEW/S ALARM OUTPUTS TO BAS PANEL AND
FIRE ALARM PANEL.
4. REFER TO P501 FOR MECHANICAL EEW/S DETAILS.
VISUAL FLASHING LIGHT
AUDIBLE HORN
CONDUIT
SEAL (TYP)
JUNCTION
BOX (TYP)
SILENCE SWITCH
120V CIRCUIT AS
IDENTIFIED ON PLANS
NOTES:
GRADE
7'-0" A.G.
A7
EEW/S ALARM DETAIL
SCALE: NTS
FLOW SWITCH
(DPDT)
TO MCC
(POL BUILDING -
SEE NOTE 3)
HOT-DIPPED
GALVANIZED 1-5/8"
STRUT CHANNELS
AS NECESSARY (TYP
HORIZONTAL
MEMEBERS)
A5
ES504
1"C: C.RCP.PCP,
C.MSS.EPDS1
VERTICAL, GALVANIZED
C6x8.2 MEMBERS AND
PIER FOUNDATION. PIER
FOUNDATION SHALL BE
18" DIAMETER WITH 3'-0"
MINIMUM DEPTH.
GRADE
SEE DETAIL TO LEFT FOR
RACK CONSTRUCTION AND
GROUNDING
REQUIREMENTS
3/4"C: C.MSS.EPDS1
1"C: MSS-2, -4, & -6
1"C: PB-15;
1"C: PB-21
DIP-1
MOGAS
MS
OP-3
MOGAS
MS
OP-4
DIESEL
MS
3/4"C: C.RCP.MSMS
1"C: MSS-1;
1"C: MSS-5
3/4"C: C.RCP.DSMS
3/4"C: C.RCP.MOMS;
3/4"C: C.RCP.DOMS
1"C: C.RCP.EPDS.M6
3/4"C: C.RCP.ATG
S
A
M E
N D
M E
KB
W P
KB
KBKB
U
S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O M
A H
A
D
I S
T R
I C
T
R
K W
A Y
K A
N S
T
Y
D E
S C
C
I L
I T
I E
S
R
E P
L A
C E
M E
N T
G E
N E
R A
L
M
I T
C H
E L
L
I A
P
W
I
US Army Corps of Engineers
Omaha District
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
SHEET ID
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
W F
R
X
R
S
I G
N
S
U B
M I T
T A
L
R T
A
D
E S
I G
N
S
U B
M I T
T A
L
J U
P
I T
E
O
M A
H A
N
E
D
R
O D
D Y
F I
A F
ADVERTISEMENT - NOT FOR CONSTRUCTION
EP411
P U
M P
H O
U S
E
C
O N
T R
O
M
P
O W
A
N
4'0 2' 8'
1. ALL METALLIC CONDUITS THAT ARE NOT
ATTACHED TO A GROUNDED PANEL OR
ENCLOSURE SHALL BE GROUNDED USING
A GROUNDED BUSHING.
2. CIRCUITS IDENTIFIED IN PLAN A1 ARE
FROM CONTROL ROOM EQUIPMENT TO
CONTROL ROOM EQUIPMENT AND THOSE
IN PLAN A4 ARE FROM CONTROL ROOM
EQUIPMENT TO EXTERNAL EQUIPMENT.
NOTES:
MCC-PH
IPC-PH
COMMUNICATIONS
BACKBOARD
PCP
ATG
BACKBOARD
WALL- MOUNTED
GPD
FIRE
ALARM
PANELS
UPS-3
A1
PUMPHOUSE CONTROL ROOM INTERIOR CIRCUIT POWER PLAN
SCALE: 3/8" = 1'-0"
N
DESK FOR PC, MONITOR,
TELEPHONE, AND PRINTER
MDS-PH
PANEL FA
PROVIDE ANGLED WALL-MOUNT FOR GDP AND COORDINATE
MOUNTING HEIGHT WITH ANG PERSONNEL DURING CONSTRUCTION.
RECEPTACLES SHALL BE TIED TOGETHER ON CIRCUIT SPECIFIED ON
PANEL PC SCHEDULE ON DRAWING EP701.
PROVIDE GENERATOR SHUTDOWN KNOX BOX PER GENERAL
MITCHELL STANDARD AND ROUTE 1" CONDUIT TO GENERATOR
CONTROL PANEL.
REFER TO EP601 FOR REQUIRED ZONE SELECTIVE INTERLOCKING
BETWEEN MCC-PH AND MDS-PH BREAKERS.
KEYED NOTES:
UPS-3
UPS-3
1" C:
PC-19,21,23
EPDS-2
PC-25
PC-35
(3) 4"C:
P.MDS.MCC
1"C:
I.BAS.DM
P.MCC.FA
2"C:
C.MCC.PCP.1-9,
C.MCC.PCP,
C.MCC.EPDS2;
1"C:
C.MCC.EPDS4;
1"C:
C.MCC.FACP;
1"C:
C.MCC.CB;
1"C:
C.MCC.BAS
1"C:
C.MCC.EPDS3
3/4"C:
FA-1, FA-2
1"C: C.ATG.PCP;
1"C: SPARE
2-1/2"C:
P.MCC.PA
PC-9
UPS-3
(EPDS
SYSTEM)
4'0 2' 8'
A4
PUMPHOUSE CONTROL ROOM EXTERIOR CIRCUIT POWER PLAN
SCALE: 3/8" = 1'-0"
N
MCC-PH
IPC-PH
COMMUNICATIONS
BACKBOARD
PCP
ATG
BACKBOARD
WALL- MOUNTED
GPD
FIRE
ALARM
PANELS
GENERATOR
CONTROL PANEL
CABINET
DESK FOR PC, MONITOR,
TELEPHONE, AND PRINTER
MDS-PH
PANEL FA
EPDS-2
262524
34 35
4 6 9 12 16 20 23
30 31
32 33
29 38 39 40 4142
(3) 4"C:
P.MTR.MDS
(2) 4"C:
P.GEN.MDS;
1"C:
I.GEN.RGEN
2"C:
SPARE
2"C:
PC-10
TO GEN-PH &
UTILITY METER
TO MANHOLES
U
E
U
C
TO PUMPHOUSE
(SEE SHEET EP412
FOR CONTINUATION)
EPDS-4
EPDS-3
EPDS-4
EPDS-3
HOUSEKEEPING
PAD
TIGHTNESS
TEST PANEL
UPS-3
1"C:
C.TTP.PCP
TIGHTNESS
TEST PANEL
1"C:
C.BAS.PCP
BAS
CONTROL
PANEL
S
PC2-10
S
S
S
S
S
S
SPARE FOR FUTURE
PIPELINE
(SEE GRID B-6, EP412)
MOUNT GENERATOR
CONTROL PANEL TO
FACE OF CABINET.
CABINET SHALL BE FULL
HEIGHT OF MCC
2625 27
S
3736 S
38 4039
3141 S42
2928 32
P I/C T
PC-27
A
M E
N D
M E
J
J J
J
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
J
1 E G D
B
C
F
A
PD-39
GFI
AC
LAB-11
GFI
48" AFF
FUEL
ELEC
MECH
MULTI PURPOSE
101a
CONTROL
SUPERVISOR
VEST
JAN
WOMEN
LOCKER
MEN
106 OPEN OFFICE
PD-5
GFI
AC
PD-31
GFI
AC
PD2-14
GFI
AC
PD2-12
GFI
AC
PD-3
GFI
LAB-3
EXP
48" AFF
LAB-3
EXP
48" AFF
LAB-9
48" AFF
LAB-5
48" AFF
PD-1
PD-1
PD-3
PD-19 PD-19
PD-23PD-23
PD-17
AC
PD-15
AC
PD-15
PD-13
PD-13
PD-13 PD-13
PD-11
PD-11
PD-11
PD-9
PD-9
PD-5
PD-5
GFI
PD-39
PD-3
PD2-16
AC
PD2-18
AC
PD-1
PD2-10
GFI
AC
PD-7
PD-7
LAB-5
48" AFF
PD-39
GFI
PD-15
AC
LAB-7
EEWS-1
PD-17
PD-19
CIRCULATION
101b
PD-17
AC
PD-33
GFI
WPIU
PD-33
GFI
WPIU
PD-33
GFI
WPIU
PD-35
TMGB
MGB
F A
-1
F A
-3
FA-5
IPC-POL
MSS
D
IP
-1 ,2
O P
-3 ,4
RCP
E5
ES504
EF-101
LAB-17
FA
LAB
LAB-9
48" AFF
EXPLAB-11
GFI
48" AFF
EXP
LAB-13,15
NEMA 2-20R
48" AFF
GB
PD-29
AV
PD-21
TV
GB
EXP
ACCU-101
PD2-1,3
EUH-102
PB-8,10,12
EF-102
PD2-15
AHU-101
PB-14,16,18
EUH-101
PB-8,10,12
AC-101
PD2-1,3
CUH-103
PD2-11
CUH-104
PD2-13
CUH-102
PD2-9
WH-101
PD2-5
RP-101
PD2-17
CUH-101
PD2-7
VEST
EPDS-1
ATG-MSS
FH-101
LAB-1
VAV-105
PD2-35,37
VAV-102
PD2-23,25
VAV-106
PD2-39,41
VAV-101
PD2-19,21
VAV-104
PD2-31,33
PD2-8
GFI
EWC-1
VAV-103
PD2-27,29
PD-25
FB1PD-27
FB1
PD-22
FB1PD-24
FB1
PD-20
AV
PD2-20
AC
PD-41M
GRINDER PUMP
PD2-22,24
PD-38,40,42
UPS
Omaha District
US Army Corps of Engineers ®
M A
S
C R
IP
T
IO
N
D A
T E
1 2 3 4 5
A
FILE:
DATE:
W
A R
D P
A R
K W
A Y
K A
N S
A S
C
IT
Y
M O
D E
S
IG
N E
D B
Y
D R
A W
N B
Y
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
S O
L
IC
IT
A
T
IO
N N
O
W F
-2 -R
-0
C O
N T
R A
C T
N O
U S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
O M
A H
A D
IS
T
R
IC
T C
A P
IT
O
L A
V E
O
M A
H A
N
E
S
IZ
E
X
SHEET ID
IS
S
U E
D D
A T
E
D E
S C
P
O L F
A C
IL
IT
IE
S
R E
P L A
C E
M E
N T
G E
N E
R A
L M
IT
C
H E
L L I A
P
W I
P O
L O
P E
R A
T
IO
N S
B U
IL
D
IN
G
6 7 8 9 10
B
C
D
E
F
G
F
IL
E N
O
A F
-1
-0
ADVERTISEMENT - NOT FOR CONSTRUCTION
7/24/2020 9:50:24 AM
D R
ID
L E
Y
M B
A X
S L A
C Y
107341EP421MT18
D R
O D
D Y
EP421
J U
N E
P O
L O
P S
B U
IL
D
IN
G
F
C C
P
O W
E R
P L A
N
NOTES:
1.
2.
REFER TO SHEETS E-001, E-002 AND E-003 FOR
GENERAL NOTES AND LEGEND.
REFER TO MECHANICAL DRAWINGS FOR HVAC
EQUIPMENT INFORMATION.
SCALE: 1/4" = 1'-0"A1
OVERALL ELECTRICAL POWER FLOOR PLAN
N
0 2' 4' 8'
KEYED NOTES:
AREA WITHIN LAB AND LESS THAN 48" AFF SHALL
BE CONSIDERED A CLASS I, DIVISION 2, GROUP D
HAZARDOUS LOCATION. ARE INSIDE THE FUME
HOOD AND WITHIN 5 FEET IN ALL DIRECTIONS
SHALL BE CLASSIFIED AS CLASS I DIVISION 1,
GROUP D HAZARDOUS LOCATION. ALL
EQUIPMENT LOCATED IN AND NEAR THE FUME
HOOD SHALL BE RATED FOR THE AREA
CLASSIFICATION INDICATED.
FUEL ROOM SHALL BE CLASSIFIED AS CLASS I,
DIVISION 2 BELOW 48" AFF.
PROVIDE JUNCTION BOX FOR CONNECTION TO
FUEL LAB FUME HOOD.
HALF OF RECEPTACLES IN ROOM INDICATED
SHALL BE CONTROLLED VIA TIME CLOCK WITH
HAND OFF AUTO SWITCH IN ACCORDANCE WITH
ASHRAE 90.1-2013. REFER TO E7/EP521.
PERSONNEL AND EQUIPMENT GROUNDING BUS
BAR.
PERSONNEL GROUNDING BUS BAR.
EPO PUSH BUTTON FOR ROOM FUEL 112.
PROVIDE SHUNT TRIP BREAKER IN PANEL LAB.
REFER TO SHEET EP721.
UPS FOR FCC COMPUTER.
PROVIDE 120VAC RECEPTACLES FLUSH WITH
SUSPENDED CEILING FOR GOVERNMENT
FURNISHED WIRELESS EQUIPMENT.
CONNECT EYEWASH TO FIRE ALARM CIRCUIT VIA
FIRE ALARM ADDRESSABLE MODULE (PROVIDED
BY DIVISION 28).
R
T A
D E
S
IG
N S
U B
M
IT
T A
L
/2
/2
A
M E
N D
M E
N T
D a te
ZSC
ZSO
UI
LSL
LSLL
ZSO
ZSC
ZSO
ZSC
LSH
LSHH
M
UT
TE
LE
UIT
J
J
\\BMCD\DFS\CLIENTS\ANF\USCOE\NWO\107341_GENMITCHMILCON\DESIGN\ELEC\SHEETS\MT18-EP431_432.DWG 7/24/2020 8:21 AM SLLACY
A1
ENLARGED PLAN - JET FUEL STORAGE TANK 1
SCALE: 3/16" = 1'-0"
U
S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O M
A H
A
D
I S
T R
I C
T
R
K W
A Y
K A
N S
T
Y
D E
S C
C
I L
I T
I E
S
R
E P
L A
C E
M E
N T
G E
N E
R A
L
M
I T
C H
E L
L
I A
P
W
I
US Army Corps of Engineers Omaha District
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
SHEET ID
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
W F
R
X
R
S
I G
N
S
U B
M I T
T A
L
R T
A
D
E S
I G
N
S
U B
M I T
T A
L
J U
P
I T
E
O
M A
H A
N
E
D
R
O D
D Y
F I
A F
ADVERTISEMENT - NOT FOR CONSTRUCTION
EP431
E N
L A
R G
A
N
J E
T
F
U E
L
S
T O
R A
G
N
K
N
8'0 4' 16'
M A
T C
H L I N
E
S
H E
F
N
T I N
U A
T I O
N
REFER TO SHEET EP433 FOR TANK CONDUIT AND
CIRCUIT ROUTING DETAILS. SEE CATHODIC PROTECTION
DRAWINGS FOR TANK CATHODIC PROTECTION
INFORMATION.
AUTOMATIC TANK GAUGING EQUIPMENT IS PART OF BID
OPTION 005. CONDUITS AND CONDUCTORS ARE PART OF
BASE BID.
PRODUCT SAVER TANK HEATERS SHALL OPERATE WHEN
PRP IS NOT IN OPERATION.
REFER TO EL431 AND EL432 FOR TANK PERIMETER LIGHT
POLE LOCATIONS AND INFORMATION. ROUTE CIRCUIT
PA-19 IN 1" CONDUIT ALONG CONTAINMENT WALL TO ALL
FIXTURES.
KEYED NOTES:
PRODUCT
SAVER TANK-1
TANK 1
JUNCTION BOX
(TYP OF 4)
PROVIDE JUNCTION BOXES
FOR EPDS AND TANK
PERIMETER LIGHTING
EPDS-9A
1"C: P.ATGB.T1.UIT, P.ATGB.T2.UIT,
I.ATG.T1.UIT, I.ATG.T2.UIT;
1"C: IS.PCP.T1.LSHH, IS.PCP.T1.LSLL,
IS.PCP.T2.LSHH, IS.PCP.T2.LSLL;
1"C: PA-20, PA-24;
1"C: PC-26, PC2-1, PC2-7;
1"C: C.PCP.T1.ZS1, C.PCP.T1.ZS2,
C.PCP.T1.ZS3, C.PCP.T2.ZS1,
C.PCP.T2.ZS2, C.PCP.T2.ZS3;
1"C: C.MCC.EPDS9
SEE SHEET ES101
FOR CONTINUATION
HEATER
(TYP OF 2)
SPARE QUANTITIES
AND SIZES PER EP702
PRP-1
A
M E
N D
M E
1 0
ZSC
ZSO
UI
LSL
LSLL
ZSC
ZSO
ZSC
ZSO
LSH
LSHH
M
UT
TE
LE
UIT
J
J
M
\\BMCD\DFS\CLIENTS\ANF\USCOE\NWO\107341_GENMITCHMILCON\DESIGN\ELEC\SHEETS\MT18-EP431_432.DWG 7/24/2020 8:21 AM SLLACY
A1
ENLARGED PLAN - JET FUEL STORAGE TANK 2
SCALE: 3/16" = 1'-0"
U
S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O M
A H
A
D
I S
T R
I C
T
R
K W
A Y
K A
N S
T
Y
D E
S C
C
I L
I T
I E
S
R
E P
L A
C E
M E
N T
G E
N E
R A
L
M
I T
C H
E L
L
I A
P
W
I
US Army Corps of Engineers Omaha District
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
SHEET ID
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
W F
R
X
R
S
I G
N
S
U B
M I T
T A
L
R T
A
D
E S
I G
N
S
U B
M I T
T A
L
J U
P
I T
E
O
M A
H A
N
E
D
R
O D
D Y
F I
A F
ADVERTISEMENT - NOT FOR CONSTRUCTION
EP432
E N
L A
R G
A
N
J E
T
F
U E
L
S
T O
R A
N
K
N
8'0 4' 16'
M A
T C
H L I N
E
S
E
N
T I N
U A
T I O
N
REFER TO SHEET EP433 FOR TANK CONDUIT AND
CIRCUIT ROUTING DETAILS. SEE CATHODIC PROTECTION
DRAWINGS FOR TANK CATHODIC PROTECTION
INFORMATION.
AUTOMATIC TANK GAUGING EQUIPMENT IS PART OF BID
OPTION 005. CONDUITS AND CONDUCTORS ARE PART OF
BASE BID.
PRODUCT SAVER TANK HEATERS SHALL OPERATE WHEN
PRP IS NOT IN OPERATION.
KEYED NOTES:
PRODUCT
SAVER TANK-2
TANK 2
JUNCTION BOX
(TYP OF 4)
PROVIDE JUNCTION BOXES
FOR EPDS AND TANK
PERIMETER LIGHTING ONLY
EPDS-9C
EPDS-9B
SEE SHEET ES101
FOR CONTINUATION
1"C: P.ATGB.T1.UIT, P.ATGB.T2.UIT,
I.ATG.T1.UIT, I.ATG.T2.UIT;
1"C: IS.PCP.T1.LSHH, IS.PCP.T1.LSLL,
IS.PCP.T2.LSHH, IS.PCP.T2.LSLL;
1"C: PA-20, PA-24;
1"C: PC-26, PC2-1, PC2-7;
1"C: C.PCP.T1.ZS1, C.PCP.T1.ZS2,
C.PCP.T1.ZS3, C.PCP.T2.ZS1,
C.PCP.T2.ZS2, C.PCP.T2.ZS3;
1"C: C.MCC.EPDS9
1"C: PA-20, PA-24
TO TANK 1 & 2
CP RECTIFIERS
(SEE SHEET CP101)
A1
EP433
HEATER
(TYP OF 2)
PRODUCT
RECOVERY TANK
PRP-2
A
M E
N D
M E
S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O M
A H
A
D
I S
T R
I C
T
R
K W
A Y
K A
N S
T
Y
D E
S C
C
I L
I T
I E
S
R
E P
L A
C E
M E
N T
G E
N E
R A
L
M
I T
C H
E L
L
I A
P
W
I
US Army Corps of Engineers
Omaha District
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
SHEET ID
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
W F
R
X
R
S
I G
N
S
U B
M I T
T A
L
R T
A
D
E S
I G
N
S
U B
M I T
T A
L
J U
P
I T
E
O
M A
H A
N
E
D
R
O D
D Y
F I
A F
ADVERTISEMENT - NOT FOR CONSTRUCTION
EP433
E N
L A
R G
A
N
P
O
R A
N
K
1. REFER TO E-001 FOR LEGEND,
ABBREVIATIONS AND GENERAL NOTES
NOTES:
A5
STORAGE TANK ELECTRICAL ELEVATION
SCALE: NTS
1. REFER TO CONTROL DIAGRAM D1, EP604 FOR MOTOR STARTER CONTROLS INFORMATION. MOTOR STARTER
SHALL BE IN NEMA 4X ENCLOSURE AND MOUNTED IN A SIMILAR MANNER AS SHOWN IN DETAIL E1, ES504.
2. PROVIDE JUNCTION BOXES FOR SAME SIGNAL TYPES AS NECESSARY ALONG TOP OF TANK.
A1
PRODUCT RECOVERY TANK ELECTRICAL PLAN VIEW
SCALE: NTS
FTP-1 WITH HEATER
AND MOTOR WINDING
TEMPERATURE SWITCH
OVERFILL
PREVENTION
VALVE
WATER LEVEL SWITCH
PRODUCT LEVEL
SWITCHES
WDP-1
LSH
LSH
LSM
LSL
LSHH
M
UT
ZSC
FS
M
1"C: P.MCC.FTP1,
C.MCC.FTP.TSH,
C.MCC.FTP.HTR
WDP/BP-1 MOTOR
STARTER
(SEE NOTE 1)
1. SEE TANK DRAWINGS ON MECHANICAL SHEETS FOR EXACT LOCATION OF TANK EQUIPMENT.
2. WELD CONDUIT SUPPORT STRUCTURES (UNISTRUT OR EQUAL) TO TANK MOUNTING PLATES, REFER TO MECHANICAL DRAWINGS
FOR MOUNTING PLATES PROVIDED BY TANK MANUFACTURER. DO NOT WELD UNISTRUT DIRECTLY TO TANK . USE THREADED ARC
STUDS OR EQUIVALENT TO INCLUDE THREADED COUPLERS OF THE SAME MATERIAL AS THE MATERIAL OF THE TANK.
3. REFER TO ES501 FOR CONDUIT, DUCTBANK, NAMEPLATE, AND HAZARDOUS AND NON-HAZARDOUS INSTALLATION REQUIREMENTS.
LEAK DETECTION SENSOR
LD
NOTES:
NOTES:
J
J
J
ATG
TRANSITION TO CONCRETE-ENCASED
DUCTBANK AND ROUTE TO MANHOLES
SEE ES101
1"C: C.MCC.FTP.FS
1"C:
C.PCP.PRT.ZSC
1"C:
IS.ATG.PRT
1"C:
IS.MCC.PRT.L3
1"C:
IS.MCC.PRT.L1,
IS.MCC.PRT.L2
1"C:
IS.ATG.PRT.LD
1"C: PC2-2
SPARE QUANTITIES
AND SIZES PER EP702
1"C:
PC2-2,
C.WDP.HTR,
C.WDP.TSH
JY
1"C:
C.WDP.JY
SEE NOTE 2 (TYP)
LSHH
3x1
LSH
3x1
LSL
3x1
LSLL
3x1
UI
3x1
ZSC
3x1
ZSO
3x1
ZSC
3x2
ZSO
3x2
ZSC
3x3
ZSO
3x3
UIT
3x1
LE
3x1
TE
3x1
UT
3x1
M
J J
J
J
J
J
SEE PLANS FOR
CONTINUATION
SEE PLANS FOR
CONTINUATION
GRADE
TANK
FOUNDATION
NUMBER OF TANK
GROUNDING CONNECTIONS
AS INDICATED ON PLANS
TANK SIDE
INDICATOR
(COORDINATE FINAL
PLACEMENT WITH
CONTRACTING
OFFICER)
LIGHT SWITCH
INLET
VALVE
SUCTION
VALVE
LOW
SUCTION
VALVE
PRODUCT
SAVER TANK
PUMP AND
HEATERS
ALARMS AND
SENSORS TO BE
ACCESSIBLE
FROM STAIRS
GROUND
ROD (TYP)
#4/0 TW
CU GND
CABLE
M
I N
1"C
1"C
4 5 6
1"C
1"C
1"C
1"C
7 8
1"C
1"C
1"C
11"C
2 1"C
1"C
DSC
DSC
LIGHT
FIXTURE
(TYP)
D6
EL501
"x" INDICATES ABOVE
GROUND STORAGE
TANK NUMBER (TYP)
1"C
A
M E
N D
M E
LSH
LSM
LSL
TSH
FS
JY
JY
JY
HS
U
E
U
C
U
E
U
C
U
E
U
C
FT
J F
J F
J F
J F
J F
J F
J F
J F
LSH
LSM
LSL
TSH
FS
JY
JY
JY
HS
U
E
U
C
U
E
U
C
U
E
U
C
U
E
U
C
FT
U
S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O M
A H
A
D
I S
T R
I C
T
R
K W
A Y
K A
N S
T
Y
D E
S C
C
I L
I T
I E
S
R
E P
L A
C E
M E
N T
G E
N E
R A
L
M
I T
C H
E L
L
I A
P
W
I
US Army Corps of Engineers
Omaha District
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
SHEET ID
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
W F
R
X
R
S
I G
N
S
U B
M I T
T A
L
R T
A
D
E S
I G
N
S
U B
M I T
T A
L
J U
P
I T
E
O
M A
H A
N
E
D
R
O D
D Y
F I
A F
ADVERTISEMENT - NOT FOR CONSTRUCTION
0 2' 4' 6'
0 2' 4' 6'
EP441
T R
U C
K
O
F F
L O
S
I T
I O
W
A
N
1. REFER TO E-001 FOR LEGEND,
ABBREVIATIONS, AND GENERAL NOTES.
2. EQUIPMENT CONFIGURATION IDENTIFIED
HERE IS DIAGRAMMATIC ONLY. FINAL SKID
AND RACK CONFIGURATION TO BE
DETERMINED BY SKID MANUFACTURER.
CIRCUITS BETWEEN EQUIPMENT ON RACK TO
SKID-MOUNTED DEVICES/INSTRUMENTS ARE
NOT IDENTIFIED BUT SHALL BE PROVIDED BY
SKID MANUFACTURER AND WILL TERMINATE
AT RACK-MOUNTED MOTOR STARTER WITH
TERMINAL STRIPS.
NOTES:
OCP-2 ON OFFLOAD
ELECTRICAL RACK
EPDS-7B
OP-2
1"C: C.PCP.OCP2, C.MCC.EPDS7;
2"C: P.MCC.OP2;
1"C: I.PCP.FT421
TO MANHOLES CMH-04 &
EMH-04. SEE PAGE ES101
FOR CONTINUATION
TO MANHOLES CMH-04 &
EMH-04. SEE PAGE ES101
FOR CONTINUATION
1"C: C.PCP.OCP1, C.MCC.EPDS7;
2"C: P.MCC.OP1;
1"C: I.PCP.FT411
AIR ELIMINATOR-2
OCP-1 ON OFFLOAD
ELECTRICAL RACK
EPDS-7A
AIR ELIMINATOR-1
OP-1
ALL DEVICES ON
SKID SHALL BE
SUITABLE FOR A
CLASS I, DIVISION 1
AREA (TYP FOR
EACH SKID)
A1
ES503
A1
ES503
AB/CV-1
SCV-1
AB/CV-2
SCV-2
A1
ENLARGED PLAN - TRUCK OFFLOAD STATION 1
SCALE: 3/8" = 1'-0"
N
A6
ENLARGED PLAN - TRUCK OFFLOAD STATION 2
SCALE: 3/8" = 1'-0"
N
A
M E
N D
M E
U
C
U
E
U
C
U
E
U
C
U
E
U
C
U E
U
C
U
E
U
C
U E
U
C
U
E
U
C
U
E
U
C
U
E
U
C
U
E
U
C
LD
LD
U
E
U
E
U
E
U
E
U
E
U
E
U
E
U
E
U
E
\\BMCD\DFS\CLIENTS\ANF\USCOE\NWO\107341_GENMITCHMILCON\DESIGN\ELEC\SHEETS\MT18-EP453.DWG 7/23/2020 11:29 PM LHURST
A1
ENLARGED PLAN - MSS FUEL ISLAND
SCALE: 3/8" = 1'-0"
U
S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O M
A H
A
D
I S
T R
I C
T
R
K W
A Y
K A
N S
T
Y
D E
S C
C
I L
I T
I E
S
R
E P
L A
C E
M E
N T
G E
N E
R A
L
M
I T
C H
E L
L
I A
P
W
I
US Army Corps of Engineers
Omaha District
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
SHEET ID
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
W F
R
X
R
S
I G
N
S
U B
M I T
T A
L
R T
A
D
E S
I G
N
S
U B
M I T
T A
L
J U
P
I T
E
O
M A
H A
N
E
D
R
O D
D Y
F I
A F
ADVERTISEMENT - NOT FOR CONSTRUCTION
EP453
E N
L A
R G
A
N
M
E
L
I S
L A
N D
N
4'0 2' 8'
EPDS-M4
FMS
DIESEL DISPENSER
(DISP-2)
MOGAS DISPENSER
(DISP-1)
CANOPY
NOTES:
1. REFER TO CONDUIT SCHEDULE ON SHEET EP451 FOR
CIRCUIT IDENTIFICATIONS.
15 27
WEATHERPROOF
TELEPHONE ENCLOSURE
37 38 39 40
SEE SHEET EP452
FOR CONTINUATION
A6
ES502
F1
ET501
E1
ES504
E1
ES505
(TYP)
S
S33
5 8
9 S
I/C P
P
I/C P
S 9 S
I/C P
A
M E
N D
M E
S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O M
A H
A
D
I S
T R
I C
T
R
K W
A Y
K A
N S
T
Y
D E
S C
C
I L
I T
I E
S
R
E P
L A
C E
M E
N T
G E
N E
R A
L
M
I T
C H
E L
L
I A
P
W
I
US Army Corps of Engineers
Omaha District
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
SHEET ID
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
W F
R
X
R
S
I G
N
S
U B
M I T
T A
L
R T
A
D
E S
I G
N
S
U B
M I T
T A
L
J U
P
I T
E
O
M A
H A
N
E
D
R
O D
D Y
F I
A F
ADVERTISEMENT - NOT FOR CONSTRUCTION
EP601
P U
M P
H O
U S
E
O
N E
L
I N
E
D
I A
G R
A M
HOA
P M
C C
F
T P
P M
C C
F
P
P M
C C
F
P
P M
C C
F
P
MOTOR CONTROL CENTER (MCC-PH) 480V, 3 PHASE, 3 WIRE, 1200A MAIN BUS, 400A GROUND BUS, 42,000 AIC SYMMETRICAL
FVNR
NEMA 0
AUTO
XFMR
NEMA 5
FROM
MDS-PH
FUEL
TRANSFER
PUMP #1 (FTP-1)
5 HP
7.6 FLA
FUELING
PUMP #1
(FP-1)
125 HP
156 FLA
FUELING
PUMP #2
(FP-2)
125 HP
156 FLA
FUELING
PUMP #3
(FP-3)
125 HP
156 FLA
* KEYED HOA SWITCHES SHALL BE KEYED ALIKE WITH THE CORRESPONDING
KEYED HAND-AUTO SWITCHES LOCATED NEAR THE MOTORS. SEE DRAWING EP602
INCOMING
MAIN
BREAKER
MM M M
1. SEE DRAWING E-001 FOR ELECTRICAL LEGEND, ABBREVIATIONS, AND GENERAL
NOTES.
2. SEE DRAWING EP602 FOR THE TYPICAL PUMP MOTOR SCHEMATICS.
3. SEE DRAWING EP603 FOR EPDS WIRING DIAGRAM.
4. SEE PANEL AND POWER CIRCUIT SCHEDULES ON EP701 AND EP702 FOR ADDITIONAL
INFORMATION REGARDING LOW-VOLTAGE PANELBOARDS AND POWER CIRCUITS.
5. GROUNDING ABBREVIATIONS:
· EBJ - EQUIPMENT BONDING JUMPER
· GEC - GROUNDING ELECTRODE CONDUCTOR
· MBJ - MAIN BONDING JUMPER
· SSBJ - SUPPLY-SIDE BONDING JUMPER
· SBJ - SYSTEM BONDING JUMPER
3P
30A
(NOTE 4)
3P
225A
3P
MCP
30AF
9-325AT
D1
MOTOR CONTROL CENTER (MCC-PH) ELEVATION
SCALE: NTS
SIDE VIEW
D4
MAIN DISTRIBUTION SWITCHBOARD
(MDS-PH) ELEVATION
SCALE: NTS
SIDE VIEW
FRONT VIEW
A1
ONE-LINE DIAGRAM - PUMPHOUSE
SCALE: NTS
R
G
R
G
R
G
R
G
P M
D S
M
C C
P.MCC.PA
AUTO
XFMR
NEMA 5
AUTO
XFMR
NEMA 5
HOA HOA HOA
P M
C C
F
P
FUELING
PUMP #4
(FP-4)
125 HP
156 FLA
AUTO
XFMR
NEMA 5
HOA
TO GROUND
GRID
P M
C C
F
P
FUELING
PUMP #5
(FP-5)
125 HP
156 FLA
AUTO
XFMR
NEMA 5
HOA
OFFLOAD
PUMP
OP-1
50 HP
65 FLA
FVNR
NEMA 3
FVNR
NEMA 3
P M
C C
P
D P
PUMP HOUSE
DRAIN PUMP
PDP-1
1HP
2.1 FLA
FVNR
NEMA
HOA
P M
C C
J P
JOCKEY
PUMP
JP-1
2HP
3.4 FLA
FVNR
NEMA
HOA
GND
P M
C C
M
A
MAKE-UP
AIR UNIT
MAU-111
HEATER
82 FLA
T-2
208Y/120V
75 KVA
NOTES: GENERAL NOTES
3P
400AF
250AT
3P
400AF
250AT
3P
400AF
250AT
3P
400AF
250AT
3P
400AF
250AT
NEXUS 1500
GENERATOR
MAIN
BREAKER
MCC
FEEDER
BREAKER
UTILITY TRANSFORMER
1000kVA, 3 PHASE, 24.94KV:480Y/277V
(NOTE 8)
(3)
1200/5
UM
PAD-MOUNTED METERING,
NEMA 3R, STAINLESS STEEL, 1200A
(NOTE 8)
20"
7'-6"
35"
ADJ
WITH
GFP
ADJ
WITH
GFP
ADJ
WITH
GFP
ADJ
WITH
GFP
ADJ
WITH
GFP
SPACE SPACE
OFFLOAD
PUMP
OP-2
50 HP
65 FLA
MOTOR STARTER PROVIDED
AS PART OF SKID BY SKID
MANUFACTURER
INTEGRATED
POWER CABINET
(IPC-PH)
NEUT
PA
480V
400A MLO
PC
208Y/120V
225A
SPD
SPD
SPD
MCP
30AF
9-325AT
MCP
30AF
9-325AT
MAX RATING OF
125% FLA PER
NEC, 430.32(A)(1)
(TYP INCL. AUTO
XFMRS)
3P
100A
3P
100A
T-FA
MINI POWER
CABINET
(NOTE 7)
FA
240/
120V
40A
7.5KVA
240/120V
XFMR
20A
2P
P M
C C
O
P
P M
C C
O
P
WE ENERGIES UTILITY
(NOTE 8)
P M
T R
M
D S
P.UT.MTR
(3)
GEC -
#3/0
EBJ -
250 KCMIL
3P
90A
FP-5FP-4FP-3
FRONT VIEW
FP-1 FP-2
OP-1
OP-2
PANEL
PA
JP-1
17'-0"
FTP-1
MLO
FEEDER
SECTION
SPD
PC2
208Y/120V
225A
SPD
PDP-1
MAU
PF
CAP
PF
CAP
PF
CAP
PF
CAP
PF
CAP
SPACE
SPACE
2P
20A
NOTE 1 (TYP GFP BREAKERS)
SPACE
HOA HOA HOA HOA HOA
P M
C C
F
A
SPACE
POL OPS
BREAKER
FA
1. PROVIDE ZONE SELECTIVE INTERLOCKING FOR GROUND FAULTS BETWEEN GFP BREAKERS INDICATED AND MAIN BREAKER IN MDS-PH.
2. SET THE AUTOTRANSFORMER STARTER TAPS AT THE 80% TAP.
3. IC = INSULATED CASE TYPE OF CIRCUIT BREAKER.
4. SPD BREAKER SIZE DEPENDENT UPON MANUFACTURER.
5. CONTRACTOR SHALL SUPPLY CAPACITORS OF THE SIZE RECOMMENDED BY THE MANUFACTURES FOR MOTORS INDICATED TO HAVE
CAPACITORS.
6. PROVIDE ARC FLASH LABELS FOR ELECTRICAL EQUIPMENT AND SERVICE ENTRANCE FAULT CURRENT LABEL FOR MDS. REFER TO EP501 FOR
LABEL REQUIREMENTS.
7. POWER FOR FIRE PROTECTION SYSTEM(S) SHALL BE PROVIDED USING A MINI-POWER CABINET PER SPECIFICATION 26 20 00. THE
TRANSFORMER/PANEL COMBINATION SHALL BE RED. PAINT THE LOCK-ON BREAKER IN THE MCC RED. IN ADDITION TO THE MCC MAIN
NAMEPLATE, PROVIDE A LABEL WITH THE FOLLOWING INSCRIPTION: "FIRE PROTECTION/LIFE SAFETY EQUIPMENT." LABEL SHALL BE IDENTICAL
TO THE MCC NAMEPLATE, EXCEPT THE LABEL MUST BE RED LAMINATED PLASTIC WITH WHITE CENTER CORE.
8. CONTRACTOR SHALL COORDINATE THE UTILITY WORK WITH WE ENERGIES. WE ENERGIES WILL PROVIDE THE TRANSFORMER, METER, AND
ALL CONDUCTORS AND CONNECTIONS TO THE PRIMARY SIDE OF THE TRANSFORMER. METER ENCLOSURE AND ALL SECONDARY POWER
DISTRIBUTION WORK ARE THE RESPONSIBILITIES OF THE CONTRACTOR.
SPACE
SPACE
SPACE
SPACE
TYPE 2
TYPE 2
TYPE 2
TYPE 2
G G G G G
HOA
G
HOA
G
SPACE
EPDS
A
M E
N D
M E
(3)
1200/5
(3)
AS
K
VS
A
V
K
G
1200AF
800AT
3P,IC
1200AF
1200AT
3P,IC
1200AF
225AT
KEYED INTERLOCK
MOTOR
CONTROL
CENTER
MCC-PH
TO POL
OPERATIONS
BUILDING PANEL
PB, SEE EP621
P M
D S
P
B
MAIN DISTRIBUTION SWITCHBOARD (MDS-PH)
480V, 3PH, 3W, 1200A BUS, 42,000 AIC SYMMETRICAL,
SERVICE ENTRANCE RATED (NOTE 4)
GEN-PH
400KW @ 0.8PF STARTING KVA
700sKVA MIN. @ 15%
V-DROP,STANDBY FLEX FUEL
(DIESEL/JET A) GENERATOR
UPSIZED ALTERNATOR
(SEPARATELY DERIVED)
GND
NEUT
TO GROUND
GRID
GEC - #3/0
SSBJ - 250 KCMIL
MBJ - 250 KCMIL
DM
ELECTRO
IND.
NEXUS
3P
NEUT
TO GROUND GRID
GEC - #3/0
SBJ - #3/0
P G
E N
M
D S
1200AF
1200AT
3P, IC
(NOTE 1)
SPD
TYPE 2
COMMUNICATIONS TO
BAS PANEL (I.BAS.DM)
S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O M
A H
A
D
I S
T R
I C
T
R
K W
A Y
K A
N S
T
Y
D E
S C
C
I L
I T
I E
S
R
E P
L A
C E
M E
N T
G E
N E
R A
L
M
I T
C H
E L
L
I A
P
W
I
US Army Corps of Engineers
Omaha District
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
SHEET ID
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
W F
R
X
R
S
I G
N
S
U B
M I T
T A
L
R T
A
D
E S
I G
N
S
U B
M I T
T A
L
J U
P
I T
E
O
M A
H A
N
E
D
R
O D
D Y
F I
A F
ADVERTISEMENT - NOT FOR CONSTRUCTION
EP602
C O
N T
R O
L
D
I A
G R
A M
S
F
P
F
T P
M
O V
M
OL
OL
OL
L1
L2
L3
G
1STRTR
CPT
480V-120V
CAPACITOR
R1
1S
2S
2S
2S
R1
1S
1S
R1
R1
2S
R1
AUTOTRANSFORMER STARTER
PCP
OUTPUT
OL'STS
oox xoo
OFF
HAND
AUTO
OTT
RUN
STOP
TR
SRx
SRx
HAND AUTO
K E
Y
ER2
SRx
FUELING PUMP STATUS
INST. NCTO
NOTC
MOTOR SPACE HEATER
MCP
L1
L2
L3
G
M
OL
OL
OL
oox xoo
OFF
HAND AUTO
OL'S
RUN
STOP
CPT
480V-120V
MC
TSER2 TR1
ON-DELAY
HIGH HIGH LEVEL (ALARM)
HIGH LEVEL (ALARM)
INTRINSICALLY SAFE RELAY
MC
MC
CR2
HIGH LEVEL ALARM
PUMP STATUS
MC
MC
MOTOR SPACE HEATER
CT
CT
CT
xo
START/DISABLE
PCP
INPUT
PCP
INPUT
PCP
INPUT
RUN
CR1
NCTO
FS-331
MCP
KEY CAPTIVE IN "HAND" POSITION.
SWITCH IS LOCATED NEAR MOTOR.
SEE NOTE 2.
KEY CAPTIVE IN "HAND" AND
"AUTO" POSITIONS. SEE NOTE 2.
LOCATED BY
"HAND-AUTO" SWITCH
2S
1S
R1
TR
SRx
CR4
CR1
TR1
MC
B1
TYPICAL FUELING PUMP (FP-x)
SCALE: NTS
A4
TYPICAL FUELING TRANSFER PUMP (FTP-1)
SCALE: NTS
CR CONTROL RELAY
DM DAMPER MOTOR
ER EMERGENCY/SAFTEY SYSTEM RELAY
TS MOTOR TEMPERATURE SWITCH
MC MOTOR CONTROLLER
OTT OVER TEMPERATURE THERMOSTAT
ON AUTOTRANSFORMER
SR STATUS RELAY
TR TIMER RELAY
EPDS EMERGENCY POWER DOWN STATION
PCP PUMP CONTROL PANEL
FCC FUELS CONTROL CENTER
ESO EMERGENCY SHUTOFF VALVE
LEGEND: THIS DRAWING ONLY
G
G
R
G
R
IN EPDS SECTION OF MCC
IN EPDS
SECTION
OF MCC
MID LEVEL (START)
LOW LEVEL (STOP)
CR2
CR3
PRODUCT RECOVERY TANK FLOAT SWITCH ASSEMBLY
WATER HIGH LEVEL (STOP, ALARM)
PRODUCT RECOVERY TANK WATER FLOAT SWITCH ASSEMBLY
INTRINSICALLY
SAFE RELAY
INTRINSICALLY
SAFE RELAY
INTRINSICALLY
SAFE RELAY
HIGH HIGH LEVEL ALARM
CR3
PCP
INPUT
WATER HIGH LEVEL ALARM
CR4
PCP
INPUT
x = 1 FOR FP-1 x = 2 FOR FP-2 x = 3 FOR FP-3 x = 4 FOR FP-4 x = 5 FOR FP-5
(TYP)
C.MCC.FPx.HTR
C.MCC.FPx.HS
C.MCC.FPx.TSH
C.MCC.PCP.x
C.MCC.FTP.TSH
C.MCC.FTP.FS
C.MCC.PRT.L2
C.MCC.PRT.L1
C.MCC.PRT.L3
C.MCC.FTP.HTR
C.MCC.PCP.8
C.MCC.PCP.9
C.MCC.FPx.HS
PCP
OUTPUT
PUMP DISABLED UPON
MANIFOLD/TANK
ERROR AND PRT HIGH
WATER DETECTION
C.MCC.PCP.8
1. REFERENCE E-001 FOR ELECTRICAL LEGEND, ABBREVIATIONS, AND GENERAL NOTES.
2. KEYED LOCKS FOR LOCAL HAND-AUTO SWITCHES AND CORRESPONDING MCC HAND-OFF-AUTO SWITCHES SHALL
BE KEYED ALIKE. KEYED LOCKS AMONG PUMP STARTERS SHALL BE UNIQUE SO THAT ANY GIVEN KEY WILL
CONTROL ONLY THE PUMP TO WHICH IT IS ASSIGNED.
3. THE ACTUAL CONFIGURATION OF POWER CORRECTING CAPACITORS SHALL BE DETERMINED BY THE EQUIPMENT
MANUFACTURER.
4. TIMING OF THE OPERATION SHALL BE SUCH THAT R1 CONTACTOR CONTACTS CLOSE BEFORE 1S CONTACTOR
CONTACTS OPEN.
NOTES:
NOTE 3
NOTE 4
NOTE 4
NOTE 4
120 VAC FROM ACTUATOR CONTROL POWER TRANSFORMER
L
O
R
XOO
OXO
OOX
STOP
CLOSE
OPEN
O
C
C
O
LIMIT SWITCH
(OPEN)
LIMIT SWITCH
(CLOSE)
MOV
O/L'S
H N
CLOSE
VALVE
OPEN
VALVE
OPEN
POSITION
CLOSED
POSITION
C.PCP.MOV231
C.PCP.MOV231
1. PROVIDE ISOLATION RELAYS AS NECESSARY FOR PCP INPUTS/OUTPUTS.
2. INTERNAL MOV WIRING DEPENDENT ON EQUIPMENT PROVIDED.
3. MOV-231 SHOWN, TYPICAL FOR OTHER MOV'S.
NOTES:
D7
MOTOR OPERATED VALVE
SCALE: NTS
N
L
SENSOR
INPUT
MODULE
INPUT POWER
TO RTU 8130
PROBE INPUT
MODULE
AUTOMATIC TANK
GAUGING PANEL
(VEEDER-ROOT TLS-450)
G
A7
CONTROL DIAGRAM - ATG-PH (VEEDER-ROOT TLS-450)
SCALE: NTS
ETHERNET
NETWORK CARD
G
CHASSIS GROUND
MODEM
NO
C
NC
TO PUMP
CONTROL PANEL
(C.ATG.PCP
I/O MODULE (PROVIDE
ADDITIONAL MODULES
AS NECESSARY)
UT
PRT TANK
LEVEL/TEMP//LEAK
DETECTION PROBE
IS.ATG.PRT
PRT TANK LEAK
DETECTION ALARM
OUTPUT
CONTACTS
LD
IS.ATG.PRT.LD
LT
OWS SEPARATION
CHAMBER LEVEL
PROBE
IS.ATG.OWS.LT341
LT
OWS OIL HOLDING
CHAMBER LEVEL
PROBE
IS.ATG.OWS.LT342
LD
IS.ATG.OWS.LD341
OWS INTERSTITIAL
LEAK DETECTION
PRT TANK
INTERSTITIAL LEAK
DETECTION
PCP
INPUT
PCP
INPUT
PCP
OUTPUT
PCP
OUTPUT
C.MCC.PCP.9
HIGH HIGH LEVEL ALARM
CR3
EPDS
SYSTEM
ATG
BACKBOARD
RECEPTACLE
A
M E
N D
M E
S
A
R M
Y
C
O R
E
N G
I N
E E
R S
O M
A H
A
D
I S
T R
I C
T
R
K W
A Y
K A
N S
T
Y
D E
S C
C
I L
I T
I E
S
R
E P
L A
C E
M E
N T
G E
N E
R A
L
M
I T
C H
E L
L
I A
P
W
I
US Army Corps of Engineers
Omaha District
S O
L I C
I T
A T
I O
N
N
O
D E
S I G
N E
D
B
Y
D E
S C
R I P
T I O
N
M A
R K
S I Z
E
S U
B M
I T
T E
D
B
Y
D A
T E
C O
N T
R A
C H
E C
K E
D
B
Y
D R
A W
N
B
Y
I S
S U
E
D
A T
E
SHEET ID
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
W F
R
X
R
S
I G
N
S
U B
M I T
T A
L
R T
A
D
E S
I G
N
S
U B
M I T
T A
L
J U
P
I T
E
O
M A
H A
N
E
D
R
O D
D Y
F I
A F
ADVERTISEMENT - NOT FOR CONSTRUCTION
EP603
E P
R
I N
G
D
I A
G R
A M
LOW SENSITIVITY OR
TRANSISTOR SENSITIVE
ER1
PCP
INPUT
ER1
ER1
ER2
EMERGENCY SHUTOFF VALVE STATUS
ER3
EMERGENCY CIRCUIT POWER STATUS
EMERGENCY STOP STATUS
PCP
INPUT
PCP
INPUT
JY-111
ER3
ER2
ER1
E1
E1A
E1
LIGHT RESET
E1A
E2
E2A
E2
PCP
E2A
LIGHT RESET
E3
E3A
E3
EPDS-3
E3A
LIGHT RESET
E4
E4A
E4
EPDS-4
E4A
LIGHT RESET
E5
E5A
EPDS-5
E5
E5A
LIGHT RESET
E6
E6A
E6
EPDS-6
E6A
LIGHT RESET
E7A
E7
EPDS-7A
E7A
LIGHT RESET
E8
E8A
E8
EPDS-8A
E8A
LIGHT RESET
E7
CONTROL ROOM
CONTROL ROOM
PUMP HOUSE
PUMP HOUSE
E1
E2 E3 E4 E5 E6
E9
CONTINUED AT "A" CONTINUED AT "B"
"A" CONTINUED
"…