M
AY
1. ALL MATERIALS AND WORKMANSHIP, DESIGN AND CONSTRUCTION SHALL
CONFORM TO THE DRAWING SPECIFICATIONS, AND THE INTERNATIONAL
BUILDING CODE 2015 EDITION.
2. THE STRUCTURAL DRAWINGS REPRESENT THE FINISHED STRUCTURE AND DO
NOT INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR AND PROVIDE ALL MEASURES NECESSARY TO PROTECT THE
STRUCTURE DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE BUT
NOT BE LIMITED TO BRACING, SHORING FOR LOADS DUE TO CONSTRUCTION
EQUIPMENT, WIND AND SEISMIC LOADING. ALL SHORING AND BRACING
SYSTEMS SHALL BE DESIGNED BY A LICENSED STRUCTURAL ENGINEER HIRED
AND PAID FOR BY THE CONTRACTOR. OBSERVATIONS VISITS TO THE SITE BY
THE CONTRACTING OFFICER AND GOVERNMENT A/E SHALL NOT INCLUDE
INSPECTION OF THE ABOVE ITEMS NOR RELIEVE THE CONTRACTOR OF HIS/HER
OBLIGATIONS, DUTIES AND RESPONSIBILITIES.
3. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR COORDINATING THE
WORK OF ALL TRADES AND SHALL CHECK ALL DIMENSIONS INCLUDING EXISTING
STRUCTURES. ALL DISCREPANCIES SHALL BE CALLED TO ATTENTION OF THE
CONTRACTING OFFICER AND BE RESOLVED BEFORE PROCEEDING WITH THE
WORK.
4. PRIOR TO FABRICATION, SHOP DRAWINGS REQUIRED BY THE
SPECIFICATIONS SHALL BE REVIEWED AND APPROVED BY THE CONTRACTOR
PRIOR TO SUBMITTAL TO THE CONTRACTING OFFICER.
5. OPENING SIZES AND LOCATIONS WHEN INDICATED ON DRAWINGS ARE FOR
INFORMATION ONLY AND SHALL BE VERIFIED WITH THE APPROPRIATE DRAWING
AND/OR SUPPLIER BEFORE CONSTRUCTION.
A. SEE ARCHITECTURAL DRAWINGS FOR SIZE AND LOCATION OF ALL
FLOOR AND WALL OPENINGS.
B. SEE MECHANICAL, PLUMBING AND ELECTRICAL, DRAWINGS FOR SIZE
AND LOCATION OF ALL OPENINGS REQUIRED FOR DUCTS, PIPES AND
PIPE SLEEVES.
C. OPENINGS OR POCKETS LARGER THAN 6 INCHES NOT INDICATED IN
STRUCTURAL DRAWINGS SHALL NOT BE PLACED WITHOUT WRITTEN
NOTIFICATION OF THE CONTRACTING OFFICER.
D. CONDUITS AND PIPES TO BE EMBEDDED IN CONCRETE SHALL SATISFY
THE REQUIREMENTS OF ACI 318-14 SECTION 6.3.
6. WHERE DISCREPANCIES, OMISSIONS AND/OR CONFLICTS ARISE BETWEEN
DRAWINGS, SPECIFICATIONS, BUILDING CODES, OR STANDARDS, CONTRACTOR
SHALL PROVIDE WRITTEN NOTIFICATION TO THE CONTRACTING OFFICER PRIOR
TO PROCEEDING WITH ANY WORK INVOLVED.
7. DIMENSIONS SHALL NOT BE SCALED FROM THE PLANS, SECTIONS AND/OR
DETAILS OF THE STRUCTURAL DRAWINGS.
8. EXISTING CONDITIONS ARE FOR GENERAL INFORMATION ONLY AND SHALL BE
FIELD VERIFIED BY THE CONTRACTOR BEFORE WORK IS BEGUN. PROVIDE
WRITTEN NOTIFICATION OF ANY DISCREPANCIES TO THE ARCHITECT BEFORE
PROCEEDING WITH THE WORK.
9. ARCHITECTURAL, MECHANICAL, AND ELECTRICAL COMPONENTS, SUPPORTS
AND ATTACHMENTS SHALL CONFORM WITH ASCE 7, CHAPTER 13. SEE DESIGN
CRITERIA FOR SEISMIC DESIGN CATEGORY. ISOLATORS, FASTENERS AND
OTHER ELEMENTS PROVIDING STABILITY FOR COMPONENTS SHALL BE
APPROVED BY ICC OR EQUIVALENT TESTING PROCEDURES. PROVIDE
SUSPENDED EQUIPMENT WITH APPROVED LATERAL OR SWAY BRACING. SEE
SPECIFICATIONS FOR RESPONSIBILITY OF BRACING DESIGN.
GENERAL NOTES:
DESIGN CRITERIA
1. THE STRUCTURAL DESIGN AND CONSTRUCTION SHALL COMPLY WITH THE
INTERNATIONAL BUILDING CODE (IBC) 2015
2. THE STRUCTURAL DESIGN AND CONSTRUCTION SHALL COMPLY WITH THE
FOLLOWING GOVERNMENT STANDARDS:
UFC 1-200-01,"GENERAL BUILDING REQUIREMENTS"
UFC 3-301-01, "STRUCTURAL ENGINEERING"
UFC 3-310-04, "SEISMIC DESIGN FOR BUILDINGS"
UFC 4-010-01, "DOD MINIMUM ANTI-TERRORISM STANDARDS FOR BUILDINGS"
3. LIVE LOAD
A. CORRIDORS, STAIRS AND EXITS:-------------------------------- 100 PSF
B. ROOF LIVE LOAD:------------------------------------------------------- 20 PSF
C. MECHANICAL EQUIPMENT ROOM, GENERAL-------------- 125 PSF
D. OFFICE---------------------------------------------------------------------- 50 PSF E. LATRINES------------------------------------------------------------------ 75 PSF F. PARTITIONS--------------------------------------------------------------- 15 PSF
G. LIGHT STORAGE-------------------------------------------------------- 125 PSF
H. HEAVY STORAGE------------------------------------------------------ 250 PSF
4. WIND DATA PER UFC 3-301-01:
A. RISK CATEGORY:-------------------------------------------------------- II
B. BASIC WIND SPEED:---------------------------------------------------- 130 MPH
C. WIND EXPOSURE:------------------------------------------------------- C
5. SEISMIC DATA PER UFC 3-301-01:
A. SHORT PERIOD------------------------0.550g
B. 1-SEC PERIOD -------------------------0.150g
C. SITE CLASS: C
D. IMPORTANCE FACTOR: 1.0
6. EQUIPMENT LOADS:
A. WHERE APPLICABLE, EQUIPMENT LOADS HAVE BEEN INCREASED FOR
IMPACT PER IBC 1607.9.
B. STRUCTURAL COMPONENTS ARE NOT DESIGNED FOR VIBRATORY
EQUIPMENT. PLACE VIBRATORY EQUIPMENT ON VIBRATION ISOLATORS.
C. LOADING OF MECHANICAL ROOMS ARE BASED ON WEIGHTS OF
ASSUMED EQUIPMENT AS INDICATED ON MECHANICAL DRAWINGS,
INCLUDING WEIGHTS ON CONCRETE PADS, WHERE INDICATED. REPORT
ANY PLANNED CHANGE IN TYPE, SIZE, LOCATION OR NUMBER OF
EQUIPMENT TO THE CONTRACTING OFFICER PRIOR TO ANY ACTION.
1. FOUNDATION DESIGN IS IN ACCORDANCE WITH THE GEOTECHNICAL
ENGINEERING EXPLORATION REPORT PREPARED BY GEOLABS DATED NOVEMBER
27, 2017. MATERIALS, EXCAVATION, BACKFILL, AND COMPACTION SHALL COMPLY
WITH SPECIFICATION SECTION 31 00 00 EARTHWORK.
2. GEOTECHNICAL DESIGN PARAMETERS:
ALLOWABLE BEARING PRESSURE 4,000 PSF
NEW FOUNDATIONS (1/3 TRANSIENT INCREASE)
COEFFICIENT OF FRICTION 0.4
PASSIVE PRESSURE 350 PCF
ACTIVE PRESSURE, UNRESTRAINED 34 PCF
ACTIVE PRESSURE, RESTRAINED 54 PCF
SITE CLASS C
3. FOUNDATIONS SHALL BEAR ON ON-SITE SOILS RECOMPACTED TO 90 PERCENT
RELATIVE COMPACTION. IF SOFT AND/OR LOOSE MATERIAL IS ENCOUNTERED AT THE
BOTTOM OF EXCAVATIONS, AREA SHOULD BE OVER-EXCAVATED TO EXPOSE FIRM
MATERIAL. OVER-EXCAVATION SHALL BE FILLED WITH SELECT GRANULAR MATERIAL
COMPACTED TO A MINIMUM OF 90 PERCENT RELATIVE COMPACTION.
4. SLAB SUBGRADE SOILS SHOULD BE SCARIFIED TO A DEPTH OF 8 INCHES,
MOISTURE-CONDITIONED TO AT LEAST 2 PERCENT ABOVE THE OPTIMUM MOISTURE
CONTENT, AND COMPACTED TO A MINIMUM 90 PERCENT RELATIVE COMPACTION
PRIOR TO PLACING THE NON-EXPANSIVE SELECT GRANULAR FILL. THE UNDERLYING
SUBGRADE SOIL AND SELECT GRANULAR FILL SHOULD BE WETTED AND KEPT MOIST
UNTIL THE FINAL PLACEMENT OF CUSHION FILLS AND SLAB CONCRETE.
FOUNDATIONDEMOLITION, REMOVAL AND
RELOCATION WORK:
1. THE CONSTRUCTION DRAWINGS INDICATE THE GENERAL EXTENT OF REQUIRED
DEMOLITION AND REMOVAL WORK. SEE ARCHITECTURAL, PLUMBING AND
ELECTRICAL DRAWINGS FOR DEMOLITION DRAWINGS.
2. THE CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS (PRIOR TO BID)
TO DETERMINE THE EXTENT OF ALL REQUIRED DEMOLITION WORK. THE REMOVAL
OR DEMOLITION OF MATERIALS, ACCESSORIES, FIXTURES, ETC. SHALL BE
COMPLETE AND INCLUDE ALL RELATED ITEMS TO THE EXTENT THAT
CONSTRUCTION CAN BE PERFORMED AND COMPLETED WITHOUT ADDITIONAL
COST TO THE GOVERNMENT.
3. ALL NECESSARY PRECAUTIONS SHALL BE TAKEN TO INSURE AGAINST DAMAGE
TO EXISTING ITEMS AND FEATURES REMAINING IN PLACE.
4. THE CONTRACTOR SHALL REMOVE EXISTING ITEMS AS DEEMED NECESSARY
SO THAT FUTURE WORK CAN BE PERFORMED AND ALSO, SO THAT ANY EXISTING
ITEM IS NOT DAMAGED WHEN FUTURE WORK IS PERFORMED. THE CONTRACTOR
SHALL ALSO INSTALL ANY OR ALL OF THE ITEMS, PATCH AND RESTORE
SURROUNDING SURFACES AS REQUIRED AS PART OF THE WORK ACCEPTABLE
TO THE CONTRACTING OFFICER.
5. ANY PORTION OF THE EXISTING UTILITIES THAT MUST BE REMOVED OR
OTHERWISE DISTURBED TO ACCOMPLISH THIS WORK CALLED FOR ON THE PLANS
SHALL BE RECONSTRUCTED, REPLACED OR RESTORED TO THE ORIGINAL
CONDITION AT THE CONTRACTORS OWN EXPENSE.
6. ANY WORK THAT INVOLVES STRENGTHENING OF EXISTING CONCRETE WALLS,
BEAMS OR SLABS, THE CONTRACTOR SHALL REMOVE ANY EXISTING PLASTER OR
ARCHITECTURAL COVERING PRIOR TO INSTALLING CONCRETE STRENGTHENING
MATERIAL (i.e. NEW SHOTCRETE, NEW ADDITIONAL LAYER OF CONCRETE, NEW STEEL BEAMS, etc.) AS INDICATED ON THE PLANS.
1. CONCRETE CONSTRUCTION SHALL CONFORM TO AMERICAN CONCRETE
INSTITUTE ACI 318
2. ALL CONCRETE UNLESS OTHERWISE NOTED SHALL BE NORMAL WEIGHT HARD
ROCK TYPE (150#/CU, FT) PORTLAND CEMENT SHALL CONFORM TO ASTM C-150
TYPE I OR II. CONCRETE MIXES SHALL BE DESIGNED BY A QUALIFIED TESTING
LABORATORY AND SHALL BE SUBMITTED TO THE CONTRACTING OFFICER FOR
REVIEW.
3. CONCRETE SHALL BE REGULAR WEIGHT HARD ROCK CONCRETE AND SHALL HAVE
THE FOLLOWING MINIMUM 28 DAY COMPRESSIVE STRENGTHS:
A. SLAB ON GRADE 4,000 PSI
B. COLUMNS 4,000 PSI
C. SUSPENDED SLABS AND BEAMS 4,000 PSI
D. FOUNDATIONS 3,000 PSI
E. ALL OTHER CONCRETE 4,000 PSI
F. SHOTCRETE 4,000 PSI
4. CONCRETE MIX DESIGN SUBMITTAL SHALL STATE LOCATION OF STRUCTURE
WHERE MIX IS USED. MIX DESIGN SHALL BE SUBMITTED TO CONTRACTING
OFFICER FOR REVIEW PRIOR TO CONSTRUCTION.
5. WATER USED IN MIXING CONCRETE SHALL BE POTABLE, CLEAN AND FREE FROM
INJURIOUS AMOUNTS OF OILS, ACIDS, ALKALIS, SALTS, ORGANIC MATERIALS OR
OTHER SUBTANCES THAT ARE DELETERIOUS TO CONCRETE OR STEEL
REINFORCEMENT.
6. MAXIMUM AGGREGATE SIZE IN CONCRETE TOPPING AND RAMPS SHALL NOT
EXCEED 3/8".
7. ALL REINFORCING BARS, ANCHOR BOLTS AND OTHER CONCRETE INSERTS SHALL
BE WELL SECURED IN POSITION PRIOR TO PLACING CONCRETE.
8. PROVIDE SLEEVES FOR PLUMBING AND ELECTRICAL OPENINGS IN CONCRETE
BEFORE PLACING. DO NOT CUT ANY REINFORCING WHICH MAY CONFLICT. CORING
IN CONCRETE IS NOT PERMITTED EXCEPT AS SHOWN. NOTIFY THE CONTRACTING
OFFICER IN ADVANCE OF CONDITIONS NOT SHOWN ON THE DRAWINGS.
9. CURING COMPOUNDS USED ON CONCRETE THAT IS TO RECEIVE AN
ARCHITECTURAL FINISH SHALL BE APPROVED BY THE FINISH SUPPLIER BEFORE
USE.
10. CONTRACTOR SHALL PROVIDE THE CONTRACTING OFFICER A SCHEDULE
SPECIFYING CONCRETE POURS IN UPCOMING THREE WEEKS.
11. CONCRETE ADMIXTURES CONTAINING CHLORIDE OR CHLORIDE SALTS SHALL
NOT BE USED.
12. ALL ROUGHENED SURFACES IN CONCRETE SHALL BE MADE WITH A MINIMUM
AMPLITUDE OF 1/4".
13. SEE ARCHITECTURAL DRAWINGS FOR CHAMFERS, EDGE RADII, DRIPS, REGLETS,
FINISHES AND OTHER NON-STRUCTURAL ITEMS NOT SHOWN OR SPECIFIED ON THE
STRUCTURAL DRAWINGS.
14. NON-SHRINK GROUT SHALL BE A PREMIXED NON-METALLIC FORMULA, CAPABLE
OF DEVELOPING A MINIMUM COMPRESSIVE STRENGTH OF 3,000 PSI IN 1 DAY AND
5,000 PSI IN 28 DAYS.
15. LEAVE FORMWORK FOR BEAM SOFFITS, JOISTS, SLABS, AND OTHER
STRUCTURAL ELEMENTS THAT SUPPORT WEIGHT OF CONCRETE IN PLACE UNTIL
CONCRETE HAS ACHIVED ITS 28 DAY DESIGN COMPRESSIVE STRENGTH.
16. EPOXY ADHESIVE SHALL BE SIMPSON SET-XP, HILTI HIT-RE 500 V3, OR
APPROVED EQUAL ADHESIVE SHALL MEET ASTM C881 AND HAVE AN
ULTIMATE TENSILE STRENGTH OF 48 KIPS (#5 2,000 PSI, 9" EMBEDMENT).
CONCRETE
A.B.
ALT
APPROX
ARCH
BAL
BOT
BRG
CIP
CJ
CLR
COL.
CONC
CONN
CONT
COORD
CSJ
CTRD
CWB
DCJ
DIA
DO
DWG
E.F.
E.W.
EA
EJ
EL
EQ
FTG
GA
GALV
GR.
GSN
HORIZ
I.A.W.
KSI
LLH
LLV
LONG.
MAX
MECH
MFR
MIN
M.S.L.
NTS
OC
OPP
OH
Pa
PL
PSI
PJF
REINF
SIM
SPA
STD
STL
THK
T.O.
TOC
TRANS
TYP
U.O.N.
VERT
W.W.M.
W.P.
ANCHOR BOLT
ALTERNATE
APPROXIMATELY
ARCHITECTURAL
BALANCE
BOTTOM
BEARING
CENTERLINE
CAST-IN-PLACE
CONTROL JOINT
CLEARANCE
COLUMN
CONCRETE
CONNECTION
CONTINUOUS
COORDINATE
CONSTRUCTION JOINT
CENTERED
CAPILLARY WATERBARRIER
DOWELED CONSTRUCTION JOINT
DIAMETER
DITTO (REPEAT)
DRAWING
EACH FACE
EACH WAY
EACH
EXPANSION JOINT
ELEVATION
EQUAL
FOOTING
GAGE
GALVANIZED
GRADE
GENERAL STRUCTURAL NOTE
HORIZONTAL
IN ACCORDANCE WITH
KIPS PER SQUARE INCH
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LONGITUDINAL
MAXIMUM
MECHANICAL
MANUFACTURER
MINIMUM
MEAN SEA LEVEL
NOT TO SCALE
ON CENTER
OPPOSITE
OPPOSITE HAND
PASCAL
PLATE
POUNDS PER SQUARE INCH
PREMOLDED JOINT FILLER
REINFORCING
SIMILAR
SPACES
STANDARD
STEEL
THICK
TOP OF
TOP OF CONCRETE
TRANSVERSE
TYPICAL
UNLESS OTHERWISE NOTED
VERTICAL
WELDED WIRE MESH
WORK POINT
ABBREVIATIONS
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
D
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
S-001
G
EN
ER
AL
S T R
U C
T U R
AL
N
O
TE
S
F Y
R E P
AI
R
B L D
G
H O
N O
L U
LU
D
IS
TR
IC
T
FT
. S H
AF
TE
R , H
AW
A I
I 9
-5
R
EG
IO
N
AL
E
N G
IN
EE
R
IN
G C
EN
TE
R H
O N
O
LU
LU
E
N G
IN
EE
R D
IS
TR
IC
T
H O
N O
LU
LU
, H I
C Y
BH
M
AY
RTA SUBMITTAL
SC
H
O
FI
EL
D
B
AR
R
AC
KS
, O
AH
U
, H
AW
AI
I
1. REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO
ASTM A615, GRADE 60.
2. WELDED REINFORCING STEEL SHALL BE LOW-ALLOY DEFORMED BARS
CONFORMING TO ASTM A706.
3. WELDED WIRE MESH REINFORCEMENT SHALL BE GALVANIZED
CONFORMING TO ASTM A1064.
4. CLEAR CONCRETE COVER FOR REINFORCING BARS SHALL BE AS
FOLLOWS, UNLESS OTHERWISE NOTED:
A. CONCRETE CAST AGAINST
AND PERMANENTLY EXPOSED TO EARTH---------------------------------3"
B. CONCRETE FORMED AND EXPOSED TO EARTH OR WEATHER
a. NO. 5 BAR, W31 WIRE, AND SMALLER------------------------------1.5"
C. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH
GROUND:
a. SLABS, WALL, JOIST:
i. NO. 11 BAR AND SMALLER----------------------------------0.75"
b. BEAMS, COLUMNS:
i. PRIMARY REINFORCEMENT, TIES, STIRRUPS,---------1.5"
SPIRALS
5. REINFORCING STEEL SHALL BE SPLICED WHERE INDICATED ON PLANS.
PROVIDE LAP SPLICE LENGTH PER TYPICAL DETAILS AND SCHEDULE,
UNLESS OTHERWISE NOTED.
6. MECHANICAL SPLICE CONNECTORS SHALL DEVELOP IN TENSON 125 PERCENT
OF THE SPECIFIED MINIMUM YIELD STRENGTH OF REINFORCING BARS.
7. STANDARD HOOKS ON REINFORCING BARS USED SHALL COMPLY
WITH ACI 318, SECTION 25.3.
8. MINIMUM REINFORCING BEND DIAMETERS SHALL COMPLY
WITH ACI 318, SECTION 25.3.
9. ANCHOR BOLTS, DOWELS AND OTHER EMBEDDED ITEMS ARE TO BE
SECURELY TIED IN PLACE BEFORE CONCRETE IS POURED.
10. REINFORCING BAR BENDS SHALL BE MADE COLD.
11. REINFORCING STEEL SHALL BE DETAILED AND PLACED IN CONFORMANCE
WITH THE "ACI DETAILING MANUAL - 2004" (SP-66) AS MODIFIED BY THE
PROJECT DRAWINGS AND SPECIFICATIONS.
12. CONTRACTOR SHALL SUBMIT REINFORCING BAR LAYOUTS AND DETAILS
FOR CONTRACTING OFFICER'S REVIEW PRIOR TO FABRICATION.
FABRICATE FROM REVIEWED DRAWINGS ONLY.
13. WELDING OF REINFORCING STEEL IS NOT PERMITTED UNLESS OTHERWISE
SHOWN ON THE DRAWINGS. WELDING OF REINFORCING STEEL SHALL
CONFORM TO AWS D1.4 "AWA STRUCTURAL WELDING CODE - REINFORCING
STEEL" OF THE AMERICAN WELDING SOCIETY.
REINFORCING STEEL
1.STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED AND ERECTED IN
ACCORDANCE WITH THE "AISC SPECIFICATION FOR THE DESIGN, FABRICATION AND
ERECTION OF STRUCTURAL STEEL FOR BUILDINGS."
2.STRUCTURAL STEEL MATERIALS SHALL CONFORM TO ONE OF THE FOLLOWING
STANDARD SPECIFICATIONS, LATEST EDITION:
A. STRUCTURAL STEEL WIDE FLANGE ASTM A992
B. STRUCTURAL STEEL CHANNELS, ANGLES, ASTM A36
& PLATES
C. HOLLOW STRUCTURAL SECTIONS (HSS) ASTM A500, GRADE B
D. ANCHOR RODS (GALVANIZED) ASTM F1554,GRADE 36
E. HIGH STENGTH BOLTS ASTM A325
F. HEADED STUDS ASTM A108, TYPE B
3. CONNECTIONS OF STRUCTURAL STEEL SHALL CONFORM TO THE LATEST
EDITION OF THE AISC MANUAL OF STEEL CONSTRUCTION AND THE FOLLOWING:
A. BOLTED CONNECTIONS- ASTM A325-N WITH SNUG-TIGHT JOINT, UNLESS
NOTED OTHERWISE. (WHERE CONNECTIONS ARE NOTED AS SLIP
CRITICAL (SC) USE A325-SC BOLTS WITH LOAD-INDICATION WASHERS OR
TENSION CONTROL BOLTS) ALL BOLT HOLES IN STEEL SHALL BE
STANDARD HOLES (1/16" LARGER THAN NOMINAL BOLT DIAMETER),
UNLESS NOTED OTHERWISE, CONNECTIONS SHALL CONFORM WITH
RCSC SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR
A490 BOLTS.
B. WELDED CONNECTION-PERFORMED BY AWS CERTIFIED WELDERS IN
CONFORMANCE WITH AWS D1.1, U.N.O. ALL WELDS SHALL BE E70XX
ELECTRODES, WELDING SHALL BE DONE USING MATCHING FILLER
MATERIAL PER TABLE 3.1 AWS D1.1 USE ONLY LOW-HYDROGEN
ELECTRODES ON ASTM A572 AND A992 STEEL.
C. WHERE NOT INDICATED ON DRAWINGS, ALL WELDS SHALL BE
CONTINUOUS 3/16" FILLET WELDS, BUT NOT GREATER THAN THE AISC
MAXIMUM OR LESS THAN THE AISC MINIMUM BASED ON THE THICKNESS
OF THE PARTS JOINED.
D. TOUCH UP FIELD WELDS AND CONNECTIONS AS WELL AS ABRADED
AND RUSTED SHOP PAINT WITH SAME PAINT USED IN SHOP.
E. AUTOMATICALLY END WELD HEADED STUDS AND DEFORMED
BARS - IN ACCORDANCE WITH AWS D1.1.
4. THE CONTRACTOR SHALL REMOVE EXISTING PLASTER AND ARCHITECTURAL
COVERINGS PRIOR TO INSTALLATION OF RETROFIT WORK.
5. CAMBER: ALL MEMBERS SHALL BE ERECTED WITH NATURAL OR INDUCED
CAMBER UPWARDS, UNLESS NOTED OTHERWISE. CAMBER INDICATED ON
DRAWINGS SHALL BE AS DELIVERED TO THE JOB SITE. CONTRACTOR
SHALL CONSIDER CAMBER LOSS DUE TO SHIPPING AND HANDLING.
6. THE SPLICING OF STRUCTURAL STEEL WHERE NOT INDICATED SHALL NOT
BE ALLOWED UNLESS APPROVED BY CONTRACTING OFFICER.
7. FIELD MODIFICATIONS OF STRUCTURAL STEEL SUCH AS THE BURNING OF
HOLES, CUTTING OF STEEL AND HEATING AND BENDING OF STEEL OR
ANCHOR RODS SHALL NOT BE ALLOWED.
8. STRUCTURAL STEEL AND MISCELLANEOUS METAL EXPOSED TO WEATHER
SHALL BE HOT-DIPPED GALVANIZED PER ASTM A123 AFTER FABRICATION.
ALL FIELD WELDS EXPOSED TO WEATHER SHALL BE COATED WITH BRUSH
APPLIED PAINT CONTAINING ZINC DUST COMPLYING WITH ASTM A780. ALL
BOLTS AND ANCHOR RODS EXPOSED TO WEATHER SHALL BE HOT-DIPPED
GALVANIZED PER ASTM A153.
9. ALL GROUT (OR DRYPACK) BELOW BASE PLATES, BEAMS BEARING ON
CONCRETE WALLS, ETC, SHALL BE NON-SHRINK, NON-STAINING,
WITH fc= 5,000 PSI. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
STRUCTURAL STEEL STATEMENT OF SPECIAL INSPECTIONS:
1. CONTRACTOR SHALL HIRE A QUALIFIED INSPECTION AND TESTING AGENCY TO PERFORM SPECIAL INSPECTIONS AND TESTING IN ACCORDANCE WITH CHAPTER 17 OF THE IBC WITH REPORTS PER IBC SECTION 1704.1.2 SUBMITTED TO THE CONTRACTING OFFICER AND cc CONTRACTOR FOR EACH DAY SPECIAL INSPECTIONS OR TESTING IS PERFORMED. THESE INSPECTIONS ARE IN ADDITION TO THE INSPECTIONS SPECIFIED IN IBC SECTION 110. SEE TABLES BELOW FOR ADDITIONAL INFORMATION.
STRUCTURAL ITEMS
STRUCTURAL STEEL FABRICATION
AND ERECTION
FABRICATION PROCEDURES
SHOP AND FIELD WELDING
(INCL. METAL DECKING)
REINFORCING PLACEMENT
ANCHOR BOLT PLACEMENT
ANCHORS INSTALLED IN
HARDENED CONCRETE
CONCRETE AND
SHOTCRETE PLACEMENT
EXPANSION BOLTS & INSERTS
EPOXY GROUTED INSTALLATIONS
ARCH, MECH, & ELEC ITEMS
SUSPENDED CEILINGS
LIFE SAFETY COMPONENTS
INCLUDING SMOKE
EVACUATION FANS
(Ip=1.5 PER ASCE 7-10 SECTION 13.1.3)
INSTALLATION AND ANCHORAGE
OF SPRINKLER SYSTEMS,
(Ip=1.5 PER ASCE 7-10 SECTION 13.1.3)
ALL OTHER MECHANICAL AND
ELECTRICAL COMPONENTS
IBC REFERENCE
1704.2.5.1 TABLE 1705.2.2 ITEM 1
& AISC 360-10
1705.2.2.1, TABLE 1705.2.2 ITEM 2a, 1705.12.2, AISC 260-10 & AISC 341-10
TABLE 1705.3 ITEM 1
TABLE 1705.3 ITEM 3
TABLE 1705.3 ITEM 4
TABLE 1705.3 ITEM 5,6 & 7
PERIODIC SPECIAL INSPECTION
AS SPECIFIED PER IBC CHAPTER 17
INSPECTIONS PER IBC SECTION 110 AND
ASCE 7 13.5.6.2.2 AS REQUIRED
REQUIRED FOR VERIFICATION OF
CERTIFICATE OF COMPLIANCE LABEL
ON COMPONENT (IBC 1705.11.4)
REQUIRED (IBC 1705.11.4 & 1705.11.6)
NOT REQUIRED
SPECIAL INSPECTION FREQUENCY
PERIODIC
CONTINUOUS (PERIODIC FOR ITEMS
EXCEPTED PER IBC 1704.3 ITEM 2)
PERIODIC AND PRIOR TO ALL
CONCRETE POURS
PERIODIC AND PRIOR TO ALL
CONCRETE POURS
PERIODIC
CONTINUOUS
CONTINUOUS INCLUDING TORQUE
TESTS IN ACCORDANCE
WITH APPROVED ICC-ES REPORTS
CONTINUOUS INCLUDING
INSPECTION OF EMBEDMENT
DEPTH AND HOLE CLEANLINESS
PRIOR TO ALL INSTALLATIONS
SEISMIC DESIGN REQUIREMENTS
ASCE 7-10 CHAPTER 13
ASCE 7-10 SECTION 13.5.6
ASCE 7-10 SECTION 13.6 AND IBC
1705.12.3
ASCE 7-10 SECTION 13.6 AND IBC
1708.12.3
ASCE 7-10 SECTION 13.6
1. THE MANUFACTURE, DETAILING, AND ERECTION OF STEEL ROOF DECK SHALL BE
IN ACCORDANCE WITH THE LATEST EDITION OF THE STEEL DECK INSTITUTE
SPECIFICATIONS.
2. METAL DECK SHALL HAVE THE MINIMUM SECTION PROPERTIES (PER 3'-0" WIDE
PANEL)
GAUGE 20
MIN DEPTH 2 IN
MIN MOMENT OF INERTIA (I) 0.406 IN /FT
MIN SECTION MODULUS (+S) 0.341 IN /FT
MIN SECTION MODULUS (- S) 0.346 IN /FT
3. DECKING AND ALL ACCESSORIES SHALL BE FORMED FROM STEEL SHEETS
HAVING A MINIMUM YIELD POINT OF 33 KSI AND CONFORMING TO ASTM A653-SS GR33.
4. MINIMUM REQUIRED FINISH IS GALVANIZED COATING CONFORMING TO ASTM A653
G90.
5. MINIMUM BEARING OF DECKING ON SUPPORTS SHALL BE 2". SHEETS SHALL BE
ATTACHED TO ALL SUPPORTING STEEL MEMBERS BY WELDING AS INDICATED ON
THE DRAWINGS AND IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS,
UPON COMPLETION OF ERECTION, ALL WELDS SHALL HAVE TOUCH-UP.
6. DECK FASTENING SHALL BE A MINIMUM 36/4 WELD PATTERN AT SUPPORTS
UNLESS NOTED OTHERWISE
7. SIDELAP CONNECTIONS SHALL BE MADE USING TOP SEAM WELDS AT 24" O.C.,
MAX.
STEEL DECK
2. CONTRACTOR SHALL PROVIDE TWO WEEK SCHEDULE OF ANTICIPATED WORK REQUIRING SPECIAL INSPECTION. IT SHALL BE THE DUTY OF THE PERSON DOING THE WORK TO NOTIFY THE CONTRACTING OFFICER THAT SUCH WORK IS READY FOR INSPECTION. INSPECTION REQUESTS SHALL BE IN WRITING AND FILED AT LEAST
THREE WORKING DAYS BEFORE SUCH INSPECTION IS DESIRED.
3. IT SHALL BE THE DUTY OF THE CONTRACTOR TO KEEP THE WORK TO REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION PURPOSES. NEITHER THE SPECIAL INSPECTOR NOR THE OWNER SHALL BE LIABLE FOR EXPENSES ENTAILED IN THE REMOVAL OR REPLACEMENT OF ANY MATERIAL REQUIRED TO ALLOW INSPECTION.
4. THE SPECIAL INSPECTOR SHALL NOT BE RESPONSIBLE FOR THE MEANS, METHODS, TECHNIQUES, SEQUENCES, OR PRECEDURE OF CONSTRUCTION SELECTED BY THE CONTRACTOR OR SAFETY PRECAUTIONS AND PROGRAMS
INCIDENT TO THE WORK OF THE CONTRACTOR.
5. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE FINAL QUALITY CONTROL REVIEW OF WORK TO ENSURE THAT ITEMS OBSERVED BY THE SPECIAL INSPECTOR HAVE NOT BEEN MOVED, REMOVED, DISPLACED, OR DISLODGED BY THE NUMEROUS SUBCONTRACTORS WORKING ON THE SITE BETWEEN INSPECTION AND
COMPLETION OF WORK.
7. ACCEPTANCE AS A RESULT OF AN INSPECTION SHALL NOT BE CONSTRUED TO BE AN ACCEPTANCE OF A VIOLATION OF THE BUILDING CODE PROVISIONS OR OF OTHER ORDINANCES OF THE JURISDICTION. INSPECTION PRESUMING TO GIVE AUTHORITY TO VIOLATE OR CANCEL THE PROVISIONS OF THE BUILDING CODE OR OF OTHER
ORDINANCES OF THE JURISDICTION SHALL NOT BE VALID.
8. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE QUALITY OF WORK AND COMPLIANCE WITH CONSTRUCTION DOCUMENTS. THE SPECIAL INSPECTIONS DO NOT CONSTITUTE REPLACEMENT OF THEIR REQUIRED QUALITY CONTROL OR APPROVAL OF THEIR WORK. THE OWNER, SPECIAL INSPECTOR, AND S.E.R.
SHALL NOT BE LIABLE FOR ANY EXPENSES ENTAILED IN NON-CONFORMING WORK THAT MAY OR MAY NOT BE
IDENTIFIED IN THE SPECIAL INSPECTION PROCESS.
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
D
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
S-002
G
EN
ER
AL
S T R
U C
T U R
AL
N
O
TE
S
F Y
R E P
AI
R
B L D
G
H O
N O
L U
LU
D
IS
TR
IC
T
FT
. S H
AF
TE
R , H
AW
A I
I 9
-5
R
EG
IO
N
AL
E
N G
IN
EE
R
IN
G C
EN
TE
R H
O N
O
LU
LU
E
N G
IN
EE
R D
IS
TR
IC
T
H O
N O
LU
LU
, H I
C Y
BH
M
AY
RTA SUBMITTAL
SC
H
O
FI
EL
D
B
AR
R
AC
KS
, O
AH
U
, H
AW
TYP. EXPANSION JOINT (E.J.)
CUT REBAR AT JOINT REINF IN UPPER
1/3 OF SLAB
CUT REBAR AT JOINT
#4 x 24" LONG SMOOTH
DOWEL AT 24" O.C.
(GREASE ONE END ONLY)
CONT. KEYWAY OR
PREFORMED METAL
KEY OR 1 1/2" DEEP SAW-CUT
TYP. CONSTRUCTION JOINT (C.S.J.)
1/2" PREMOULDED JOINT
FILLER WITH ELASTOMERIC
SEALANT AT SURFACE
SEE JOINT SEALANT DETAIL
GEOTEXTILE
FABRIC
COMPACTED
SUBGRADE
15 MILS THK
VAPOR BARRIER
BASALTIC TERMITE
BARRIER (BTB) OPTION
SHOWN, SEE SPECS
3B FINE (ASTM C33, #67)
CAPILLARY WATER
BARRIER (CWB)
GEOTEXTILE
FABRIC
COMPACTED
SUBGRADE
15 MILS THK.
VAPOR BARRIER
BASALTIC TERMITE
BARRIER (BTB) OPTION
SHOWN, SEE SPECS
3B FINE (ASTM C33, #67)
CAPILLARY WATER
BARRIER (CWB)
TH
K.
SL
AB TH
K.
SL
AB
6" SELECT
GRANULAR FILL
6" SELECT
GRANULAR FILL
CONTRACTOR OPTION: SAW
CUT MAXIMUM OF 12 HOURS
AFTER POUR OR USE 1"
DEEP PLASTIC RIBBON
SLAB REINFORCING
CONCRETE
SLAB ON GRADE
3B FINE (ASTM C33, #67)
CAPILLARY WATER
BARRIER (CWB)
BASALTIC TERMITE
BARRIER (BTB) OPTION
SHOWN, SEE SPECS
GEOTEXTILE
FABRIC
COMPACTED
SUBGRADE
15 MILS THK
VAPOR BARRIER
NOTE:
CONSTRUCTION JOINTS
MUST BE USED AT THE
END OF DAYS WORK,
SEE CONSTRUCTION
JOINT (CJ) DETAILS
1/
2" C
LR
. 3/ 4"
TH
K.
SL
AB
4" 4"
6" SELECT
GRANULAR FILL
EJ
EJ
COL.COL.
EJ
EJ
EJ
SJ
SJ
#5 AT
MID-DEPTH
#5 AT
MID-DEPTH
EDGE OF SLAB
OR CONC WALL
SJ OR CSJ SJ OR CSJ SJ OR CSJ
EXPANSION JOINT
(EJ) SEE
#4 AT
MID-DEPTH
#4 AT
MID-DEPTH
8" TYP.
2'-0" TYP. 2'-0" TYP.
8" TYP.
/F2 S-003
#4
SPACING TO MATCH
SLAB REINF.
TYP. SLAB ON GRADE
REINFORCEMENT
TYP. SLAB ON GRADE
REINFORCEMENT
#4
SPACING TO MATCH
SLAB REINF.
#4
SPACING TO MATCH
SLAB REINF.
(2) #4 CONT
FIN GRADE OR
PAVING - SEE PLANS
TYP. SLAB ON GRADE
REINFORCEMENT
TYP. SLAB ON GRADE
REINFORCEMENT
TYP. SLAB ON GRADE
REINFORCEMENT
24" 24"
DEPRESSED SLAB
SEE ARCH DWGS
FOR EDGE
CONDITIONS
24" 24"
EXPANSION JOINT AT WALL FACE
24"
SLAB EDGE
DEPRESSED SLAB
#4 CONT
FACE OF WALL
1/2" PREMOULDED JOINT
FILLER WITH ELASTOMERIC
SEALANT AT SURFACE
SEE JOINT SEALANT DETAIL
#4 CONT
SEE ARCH FOR BTB
AND CAPPING DETAILS
AT SLAB EDGE
8" MIN.
8" M
IN
1' -0
" M
IN
"t" (4
" T O
2"
D
EP
R
ES
SI
O N
#4
SPACING TO MATCH
SLAB REINF.
24" 24"
6t OR
1'-6" MIN.
"t" (4
" M
AX
D
EP
R
ES
SI
O N
30° MAX, TYP.
BASALTIC TERMITE
BARRIER (BTB) OPTION
SHOWN, SEE SPECS
3B FINE (ASTM C33, #67)
CAPILLARY WATER
BARRIER (CWB)
6" SELECT
GRANULAR FILL
BASALTIC TERMITE
BARRIER (BTB) OPTION
SHOWN, SEE SPECS
3B FINE (ASTM C33, #67)
CAPILLARY WATER
BARRIER (CWB)
6" SELECT
GRANULAR FILL
4" 4"
4" 4"
8"
MIN.
A
A
A
OPENING
SJ*
SJ
SJ
SJ*
SJ
* #4 x 4'-0"
#4 E.W.
CONCRETE
WALL
1-#4 x 2'-0" @
MID-DEPTH
NOTES:
* ALSO FOR EJ
2-#4 x 4'-0"
2'-0" TYP.
TYP.
1'-6" MAX.
A
A
AT EXPANSION JOINT AT SAWCUT JOINT
1/2" PREMOLDED
JOINT FILLER
PAVEMENT OR
SLAB SURFACE
BACKER
MATERIAL
POURED JOINT
SEALER
LEGEND:
W = WIDTH OF SEALANT RESERVOIR = 1/2" MIN AND 5/8" MAX
D = DEPTH OF SEALANT = 1/2" MIN TO 3/4" MAX
PAVEMENT OR
SLAB SURFACE
BACKER
MATERIAL
POURED JOINT
SEALER
CRACK
NOTE:
TOP OF SEALANT WILL BE 1/8" TO 1/4"
BELOW TOP OF PAVEMENT OR SLAB.
ASTM NO. 67
GRAVEL FILL
EXISTING
CONCRETE
SLAB-ON-GRADE
MECH. PIPE
OR CONDUIT
#4x 1'-4" LONG
DOWELS AT 2'-0"
O.C. STAGGER.
EPOXY GROUT
INTO 5/8" DIA. x 4"
DEEP HOLES -
CENTER
DOWELS IN
SLABPROVIDE 4" MIN.
CONCRETE SLAB-ON-
GRADE REINFORCED
w/6x6-W7.4/W2.9W.W.M.
NOTE:
IF EXIST SLAB BECOMES UNDERMINED
BACKFILL W/ CONCRETE
SAWCUT AND REMOVE EXISTING
CONCRETE SLAB-ON-GRADE AS
REQUIRED TO INSTALL MECH. PIPES
OR CONDUIT
15 MIL VAPOR
BARRIER
MIN.
1' - 0"
2' -0
" M
AX
VA
R
IE
S
D MIN.
D
D MIN.
NTSF2 TYPICAL SLAB JOINT DETAIL
NTSF6 TYPICAL SAW CUT JOINT (SJ)
NTSC1
TYPICAL ISOLATION (EXPANSION)
JOINT AT COLUMN
NTSA1 DEPRESSED SLAB AND SLAB EDGE
NTSC3 TYPICAL ADDED SOG REINF.
NTSF8 TYPICAL JOINT SEALANT DETAILS
NTSC6 SLAB ON GRADE REPAIR DETAIL
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
D
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
S-003
TY
PI
C
AL
S
LA
B- O
N -G
R
AD
E D
ET
A I
LS
F Y
R E P
AI
R
B L D
G
H O
N O
L U
LU
D
IS
TR
IC
T
FT
. S H
AF
TE
R , H
AW
A I
I 9
-5
R
EG
IO
N
AL
E
N G
IN
EE
R
IN
G C
EN
TE
R H
O N
O
LU
LU
E
N G
IN
EE
R D
IS
TR
IC
T
H O
N O
LU
LU
, H I
C Y
BH
M
AY
RTA SUBMITTAL
SC
H
O
FI
EL
D
B
AR
R
AC
KS
, O
AH
U
, H
AW
180° HOOKS 90° HOOKS
135° HOOKS135° HOOKS90° HOOKSBAR
SIZE
D
A OR G J A OR G
90° HOOKS180° HOOKS
#3
#4
#5
#6
#7
#8
2 1/4
3 3/4
4 1/2
D
A OR G H
APPROX
90°
HOOKS 135° HOOKS
A OR G
#3
#4
#5
4 1/2
4 1/2
5 1/2
APPROXA OR G
135° HOOKS
#3
#4
#5
#6
#7
BAR
SIZE
D
(mm) H
1 1/2
2 1/2
BAR
SIZE
5 3
5 1/4
15#9 9 1/2 11 3/4 19
2 1/2
3 3/4
1 1/2
2 1/2
4 1/2
5 1/4 9
5 1/2
4 1/2
4 1/4 3
3 3/4
4 1/2
5 1/4
OFFSET BEND
A OR G
HOOK
d
JD
4d OR 60" MIN.
DETAILING
DIMENSION
D d d
A O
R G
H O
O K
DETAILING
DIMENSION
D
IM
EN
SI
O N
D
ET
AI
LI
N G
D d
A OR G
HOOK
6d
BEAM BEAM
D
IM
EN
SI
O N
D
ET
AI
LI
N G d
D
A O
R G
H O
O K
D
6d
H
A O
R G
H O
O K
H
(3" MIN.)
6d
D
D
ET
AI
LI
N G
D
IM
EN
SI
O N d
3" M
AX
MAIN BARS STANDARD STIRRUPS OR TIES SEISMIC STIRRUPS OR TIES
OTHER
BARS
SLAB & WALL SPLICE LENGTHS GRADE
60 (INCHES)
BAR
SIZE
SLAB TOP
BARS
OTHER
BARS
SLAB TOP
BARS
OTHER
BARS
SLAB TOP
BARS
fc' 3000 PSI 4000 PSI 5000 PSI
#3 13 17 12 16 12 16
#4 21 28 18 24 17 22
#5 31 41 27 35 24 32
#6 43 56 37 48 33 43
#7 69 90 60 78 53 69
#8 85 111 74 96 66 86
#9 103 134 90 116 80 104
BAR
SIZE
EPOXY GROUTED BARS
NOTES:
1. SEE STRUCTURAL SPECIFICATIONS FOR EPOXY PRODUCTS TO BE USED.
2. FOR #3, #4 & #5 BARS SPACED 6" CC OR WIDER, HOLE DEPTH MAY BE
REDUCED 20%.
3. THIS DETAIL SHALL BE USED ONLY WITH THE SPECIFIC APPROVAL OF
THE CONTRACTING OFFICER.
4. PROBE FOR EXISTING REINFORCEMENT BEFORE DRILLING HOLE. DO NOT
CUT EXISTING REINFORCEMENT.
5. CLEAN HOLES OF ALL DUST WITH MOTOR DRIVEN COMPRESSED AIR
AND WIRE BRUSH PRIOR TO GROUTING.
6. ALL DOWELS SHALL HAVE SPECIAL INSPECTION.
7. USE NON-SHRINK GROUT WHERE DIRECTED BY THE CONTRACTING
OFFICER.
DRILL BIT
(MIN) DIA
HOLE DEPTH - CONCRETE f"c
3000 PSI 4000 PSI 5000 PSI
#3
#4
#5
#6
#7
#8
#9
1/2"
5/8"
3/4"
7/8"
1"
1-1/8"
1-1/4"
8" 8" 8"
10"
12"
15"
20"
28"
36"
10"
12"
15"
18"
24"
32"
10"
12"
15"
16"
22"
28"
3" CLR.
MAIN OR
TEMPERATURE BAR
(TYP.)
STIRRUP OR TIE
EARTH/CONC.
CONCRETE CAST
AGAINST EARTH
NOTES:
1. PROTECTION COVER SHOWN IS MINIMUM PERMITTED.
2. THICKER PROTECTIVE COVER INDICATED IN SPECIFIC DETAILS SHALL GOVERN.
3. COMPLY WITH A CASE OF CONC. EXPOSED TO EARTH OR WEATHER FOR
STRL. SLAB-ON-GRADE.
4. PROTECTIVE COVER SHOWN IS FOR CAST-IN-PLACE CONCRETE ONLY.
3" C
LR
1 1/2" CLR
MAIN OR
TEMPERATUR
E BAR (TYP.)
FORMED CONC.
SURFACE
EXTERIOR FACE
EARTH
STIRRUP OR TIE
CONCRETE EXPOSED TO
EARTH OR WEATHER
1 1/2" CLR
NTSD1 STANDARD HOOK FOR BARS, STIRRUPS, & TIES
NTSA1 TYPICAL SLAB & WALL BAR SPLICE TABLE
NTSA4 DRILL AND EPOXY DOWEL SCHEDULE
NTSA7 CONCRETE PROTECTION OF REINFORCING
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
D
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
S-004
TY
PI
C A L
R
EI
N
FO
R C
IN
G
D
ET
AI
L S
F Y
R E P
AI
R
B L D
G
H O
N O
L U
LU
D
IS
TR
IC
T
FT
. S H
AF
TE
R , H
AW
A I
I 9
-5
R
EG
IO
N
AL
E
N G
IN
EE
R
IN
G C
EN
TE
R H
O N
O
LU
LU
E
N G
IN
EE
R D
IS
TR
IC
T
H O
N O
LU
LU
, H I
C Y
BH
M
AY
RTA SUBMITTAL
SC
H
O
FI
EL
D
B
AR
R
AC
KS
, O
AH
U
, H
AW
#3 TIES AND CROSS -
TIES @ 6" OC (WHEN
PIER WIDTH EXCEEDS
2'-0" USE NORMAL
HORIZ. REINFORCING)
(2)#4 x 4'-0"
DIAGONAL EA
CORNER, EA FACE SILL REINF. PER DETAILS SILL REINF.
PER DETAILS
(2)#4 x 4'-0"
DIAGONAL EA
CORNER, EA FACE
REINF. EA. SIDE
OF OPENING
(SEE NOTE 1)
HEADER
REINFORCING
SEE NOTE 2
VERTS
AT JAMBS (FULL
HEIGHT U.O.N.)
(1) #4 EA. FACE AT OF
PIER (OMIT AT PIERS 1'-0"
OR LESS IN WIDTH) - EXTEND
VERTS. FULL HEIGHT WHEN
PIER IS ADJACENT TO DOOR
OPENINGS
MATCH FOOTING
OR WALL DOWELS
BELOW PER DETAILS
(SEE NOTE 3)
"A"
"B"
HEADER
REINFORCING
SEE NOTE 2
VERTS AT JAMBS PER DETAIL(SEE NOTE 4)
MECH'L WALL OPENING DOOR OPENING COMBINED WINDOW-DOOR OPENING WINDOW OPENING
PIER SECTION
OPENOPENOPENOPEN
NOTE:
SEE ARCH/MECH DRAWINGS FOR ROUGH OPENING
SIZES AND ELEVATIONS
TOP OF SLAB
RECTANGULAR OPENINGS WITH L or H > 12"x12"
CIRCULAR WITH D>12"
(2)#4 x (D+32") DIAGONAL
(4) SIDES, EA FACE
PIER WIDTH
L
(SEE NOTE 3)
2'-0" TYP.
2' -0
TY
P.
H
H
D
WIDTH OF
OPENING
WIDTH OF
OPENING
WIDTH OF
OPENING
WIDTH OF
OPENING
WIDTH OF
OPENING"A"
"B"
"B" "B"
"A"
"A"
"B" "B"
"A"
"A"
SECTION "A"-"A" SECTION "B"-"B"
SINGLE LAYER
LINTEL AND TOP OF WALL
DOUBLE LAYER
PLAN-JAMB OR END OF WALL
DOUBLE LAYERSINGLE LAYER
U BARS
TO MATCH
WALL REINF.,
TYP.
TOP OF WALL
STD. HOOK
TYP WALL
REINF.
LINTEL REINF
180° HOOK
TYP WALL
REINF.
(2) #5 MIN
TYP. WALL
REINF.
180° HOOK
STD HOOK
(2) #5 MIN
SAME SIZE &
SPACING AS
HORIZ. BARS
(2) #5 MIN
NOTES:
1. VERTICAL AND HORIZONTAL BARS INTERRUPTED BY
OPENINGS SHALL BE REPLACED BY ADDITIONAL
REINFORCING EQUAL TO THAT INTERRUPTED. PLACE
HALF OF ADDITIONAL REINFORCING ON EACH SIDE OF
THE OPENING, (2) #5 MIN EACH SIDE (3" CC)
2. HEADER REINFORCING:
(2) #5 BARS, 4'-3" LONGER THAN OPENING 5'-0" OR LESS
(2) #6 BARS, 5'-0" LONGER THAN OPENING 5'-1" TO 7'-0"
(2) #7 BARS, 5'-9" LONGER THAN OPENING 7'-1" TO 9'-0"
3. WHERE EXTENSION IS NOT POSSIBLE, EXTEND AS FAR
AS POSSIBLE AND HOOK, TYP.
4. DOWELS NOT REQUIRED TO FOOTING OR WALL BELOW
WHEN H1 < 8'-0"
HORIZ. LAP
SPLICE
U-BARS MATCH
HORIZ. REINF.
SIZE AND SPACING
PLAN
CORNER
PLAN
INTERSECTION
PLAN
CORNER
SINGLE LAYER
DOUBLE LAYER
(2)#4 VERT TYP. U.O.N.
((2) #5 VERT AT INTERIOR
WALLS)
(4)#4 VERT TYP. U.O.N.
((4) #5 VERT AT INTERIOR
WALLS)
ADDED VERT. BAR TO
MATCH WALL VERT. REINF
2' -0
" T
YP
2'-0" TYP.
2' -0
" T
YP
2'-0" TYP.
WALL HORIZ. REINF.
WALL HORIZ. REINF.
SPECIAL NOTE:
CONTRACTOR MAY SUBSTITUTE 7'-0"
LONG 90 DEGREE BENT BAR
CENTERED AT CORNER IN LIEU OF
OUTER CORNER HOOKS (SAME SIZE
AND SPACING AS HORIZ. REINF.)
CHIP BACK CONC. AT ALL EXPOSED
EXIST. REINF. AND TRIM BAR AS
SHOWN, EPOXY GROUT TO FINISH
USING EPOXY BONDING AGENT
(SEE SPECS.)
SAW CUT
EDGE
CUT EXPOSED
EXIST. REINF.
3/4"
PORTION OF EXIST.
CONC. SLAB OR WALL
TO BE REMOVED
EXIST. CONC. WALL
DEMOLITION SEQUENCE:
PRIOR TO DEMOLITION OF PENETRATION OR OPENING, SHORE OR
PROVIDE SUPPORT AS SHOWN ON , , AND .
CORE DRILL HOLES AT SLAB OR WALL CORNERS
SAW CUT WALL BETWEEN DRILLED HOLES AND REMOVE.
DO NOT OVERCUT. ONLY SAW CUT EXTENT OF PANEL TO
BE REMOVED IMMEDIATELY AFTER CUTTING OPERATIONS.
CHIP OUT CONCRETE SLAB OR WALL BELOW GRADE AS SHOWN
SEE DETAIL
ELEVATION
/A8 S-005
/C6 S-006 /C6 S-007/E1 S-007
PLAN AT DOUBLE LAYER
VERT WALL REINF
TYP UNLESS
OTHERWISE NOTED
FIRST PLACEMENT
NOTES:
1. PROVIDE CONSTRUCTION JOINT AT 30'-0" OC MAX.
2. LOCATION AND DETAIL OF JOINT SHALL BE REVIEWED BY
ARCHITECT WHEN NOT LOCATED AT INTERSECTIONS OF WALLS
PRIOR TO CONSTRUCTING FORMS OR PLACING CONCRETE.
PLAN AT SINGLE LAYER
CONTINUE
HORIZ WALL
REINF THRU
JOINT, TYP.
VERT WALL REINF
TYP UNLESS
OTHERWISE NOTED
CSJ
3" 3"
FIRST PLACEMENT
TY
P.1"
TY
P.1"
CONTINUE
HORIZ WALL
REINF THRU
JOINT, TYP.
3" 3"
CONTINUE
REINF ACROSS
JOINT
1S
T
PO
U R
2N D
P O
U R
SECTION
NOTES:
1. JOINT LOCATION SHALL BE SUBMITTED TO
THE CONTRACTING OFFICER FOR REVIEW.
2. CONDITION FOR DOUBLE LAYER SHOWN,
SINGLE LAYER DETAIL SIMILAR
3" 3"
ADDED BARS
TO MATCH WALL
HORIZ. BARS
BUTT JOINT
NTSC1
TYPICAL CONCRETE OR SHOTCRETE WALL OPENING
REINFORCING
NTSA1
TYPICAL REINFORCING AT CORNERS
AND INTERSECTIONS
NTSA8 TYPICAL REBAR TERMINATION DETAIL
NTSA4
CONCRETE WALL OR SLAB
PENETRATION DETAIL
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
D
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
S-005
TY
PI
C
AL
C O
N C
R
ET
E W
AL
L
D
ET
A I
LS
F Y
R E P
AI
R
B L D
G
H O
N O
L U
LU
D
IS
TR
IC
T
FT
. S H
AF
TE
R , H
AW
A I
I 9
-5
R
EG
IO
N
AL
E
N G
IN
EE
R
IN
G C
EN
TE
R H
O N
O
LU
LU
E
N G
IN
EE
R D
IS
TR
IC
T
H O
N O
LU
LU
, H I
C Y
BH
M
AY
RTA SUBMITTAL
SC
H
O
FI
EL
D
B
AR
R
AC
KS
, O
AH
U
, H
AW
AI
I
NTSC7 SHOTCRETE VERTICAL WALL CONSTRUCTION JOINTS
NTSA6
SHOTCRETE HORIZONTAL WALL
CONSTRUCTION JOINTS
DRILL AND EPOXY
GROUT #4x36" MIN.
AT 24", TYP SIDES
AND BOTTOM
TOP OF (E) SLAB,
WHERE OCCURS
#4x36" MIN AT 24" EW
(N) CONC SURFACE TO
MATCH TEXTURE OF
ADJACENT (E) CONC.
WALL SURFACE
MIN. LENGTH
5/8" DIA X 6"
(E) CMU/CONC WALL
(N) CONC INFILL
FIELD VERIFY
NOTE:
IF (E) CMU WALL IS
UNGROUTED, FILL
FIRST CELL ADJACENT
TO JAMB WITH GROUT
TYP WALL
REINF.
ALTERNATE SPLICES
4'-0" MIN. SPACING FOR
TYP. LAP (24" MIN.)
HORIZ. REINF.
"T
D
MAX D=T
3D OR 4" MIN
SLEEVE, TYP.
SLAB
OR WALL
CONDUIT IN CENTER THIRD OF SLAB OR WALL
WHERE WALL REINF HAS 1 MAT IN CENTER
LOCATE CONDUIT IN SAME LAYER WITH WALL
VERT REINF OF VERT CONDUIT
D
3D OR 4" MIN
MAX D = T/3 OR 2"
WHICHEVER IS SMALLER
NOTE:
WHERE CLEAR DISTANCE BETWEEN SLEEVES IS IMPOSSIBLE OR MAX D IS
EXCEEDED, THIS AREA SHALL BE TREATED AS AN OPENING PER TYPICAL
DETAIL FOR OPENINGS ON SLAB OR WALL. CONTRACTOR SHALL LOCATE (E)
SLAB/WALL REINFORCING BY NON-DESTRUCTIVE MEANS TO AVOID DAMAGE
PRIOR TO DRILLING AND CORING FOR (N) PIPES AND CONDUITS
CONC INFILL
LINE OF (E) ROUND OR
RECTANGULAR SLAB
OPENING, ROUGHEN
TO 1/4" AMPLITUDE
#3 EPOXY EMBEDDED
DOWEL AT SLAB MID-
DEPTH, TYP
12" MAX.
3" EPOXY EMBED
4" TYP
4" EPOXY EMBED
13" - 24"
CONC INFILL
#3 EPOXY EMBEDDED
DOWEL AT SLAB MID-
DEPTH, TYP
LINE OF (E) ROUND OR
RECTANGULAR SLAB
OPENING, ROUGHEN
TO 1/4" AMPLITUDE
5" MAX TYP
PIPE, SEE MECH,
ELEC, PLUMBING
DWGS
#5 EA FACE
NOTE:
THIS DETAIL APPLIES TO INDIVIDUAL PIPE SLEEVE LOCATIONS ONLY.
WHEN SLEEVES ARE LESS THAN 3 SLEEVE DIAMETERS APART AND/OR
2 OR MORE SLEEVES ARE LINED UP, SPECIAL REINFORCING MAY BE
NEEDED. SEE OTHER DETAILS OR NOTIFY CONTRACTING OFFICER.
3" AT FLOORS,
FLUSH AT WALLS
PIPE SLEEVES TO
BE HELD RIGIDLY
IN PLACE
PIPE
CAULK IN EXTERIOR WALLS OR
AS NOTED ON ARCH, MECH,
ELEC OR PLUMB DWGS
BEND REINF BARS
TO CLEAR SLEEVE
AS DIRECTED
PLASTIC OR SCHED
40 STEEL PIPE
SLEEVE. INSIDE
DIA AS SHOWN ON
MECH, ELEC OR
PLUMB DWGS
2'-0"TYP.
3/8" THK. SHEAR
PLATE
TYP.
1/2" GAP
3/4" DIA. BOLTS AT 3"
O.C., SEE SCHEDULE
FOR QUANTITY
STL. BM. STL. BM.
1/4
1/4 1/2" GAP
1 1/2" 1 1/2"
3 1/2"
STL. BEAM
WHERE OCCURS
5/8" DIA. EXPANSION
ANCHORS AT 16", TYP.
TEMPORARY C6x8.2 HEADER
INSTALLED BEFORE DEMOLITION
WORK. REMOVE AFTER NEW
HEADER IS INSTALLED PER
BURN BACK ANCHORS AND
PATCH PER
TOP OF FLOOR TOP OF FLOOR
5/8" DIA. EXPANSION
ANCHORS AT 16", TYP
EXISTING
CONC WALL EXISTING
CONC WALL
AT DOOR OPENING AT WINDOW OPENING
1'-4"
TYP.4" TYP.
SA
W
C U
T O
PE
N
IN
G
N
EW
D O
O R
SAWCUT OPENING
NEW DOOR
1'-4"
TYP. 4" TYP.
MECH SAWCUT OPENING
NEW WINDOW OR
M
EC
H S
AW
C
U T
O
PE
N
IN
G N
EW
W
IN
D
O W
O R
2'-0"
MIN.
A6/S-006
A8/S-005
#4x DOWELS AT
24" DRILL AND EPOXY
TOP OF FLOOR
(2) #5 EACH JAMB
EXISTING
CONC. WALL
#5 DOWELS
EACH END, TYP
OPENING
NEW DOOR
N
EW
D O
O R
O
PE
N
IN
G
TY
P
2'
0"
AT DOOR OPENING AT WINDOW OPENING
#4x DOWELS AT
24" DRILL AND EPOXY
TOP OF FLOOR
(2) #5 EACH JAMB
EXISTING
CONC. WALL
#5 DOWELS
EACH END, TYP
8"
OPENING
NEW WINDOW8"
8" TYP
2'
0"
TYP.
8" MIN.
#5 DOWELS
EACH END, TYP
2"
EQ EQ EQ
12" LONG KEY AT 24"
CONTINUE
REINF ACROSS
JOINT
1S
T
PO
U R
2N D
P O
U R
SECTION
NOTE:
JOINT LOCATION SHALL BE SUBMITTED TO THE
CONTRACTING OFFICER FOR REVIEW.
PLAN
3"
1 1/2"
3"
EQ
EQ
EQ
HORIZ
12" LONG KEY AT 24"
CLEAN SURFACE
PRIOR TO PLACING
CONCRETE
HORIZ WALL
REINF TYP
VERT WALL REINF
TYP UNLESS
OTHERWISE NOTED
FIRST PLACEMENT
NOTES:
1. PROVIDE CONSTRUCTION JOINT AT 30'-0" OC MAX.
2. LOCATION AND DETAIL OF JOINT SHALL BE REVIEWED BY
ARCHITECT WHEN NOT LOCATED AT INTERSECTIONS OF WALLS
PRIOR TO CONSTRUCTING FORMS OR PLACING CONCRETE.
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
D
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
S-006
TY
PI
C
AL
C O
N C
R
ET
E W
AL
L
AN
D
S
TE
E L B
EA
M
C O
N N
EC
TI
O N
D
ET
AI
LS
F Y
R E P
AI
R
B L D
G
H O
N O
L U
LU
D
IS
TR
IC
T
FT
. S H
AF
TE
R , H
AW
A I
I 9
-5
R
EG
IO
N
AL
E
N G
IN
EE
R
IN
G C
EN
TE
R H
O N
O
LU
LU
E
N G
IN
EE
R D
IS
TR
IC
T
H O
N O
LU
LU
, H I
C Y
BH
M
AY
RTA SUBMITTAL
SC
H
O
FI
EL
D
B
AR
R
AC
KS
, O
AH
U
, H
AW
AI
I
NTSE1
INFILL EXISTING OPENING W/
CONCRETE
NTSE3 TYPICAL WALL REINFORCING
NTSC1
TYPICAL PIPING AND CONDUIT IN OR
THRU SLAB OR WALL
NTSA1 INFILL EXISTING SLAB
NTSC3
TYPICAL REINF. AT WALL AND SLAB
PIPE SLEEVES
NTSA3
TYPICAL STEEL BEAM TO BEAM
CONNECTION
NTSC6
TYPICAL TEMPORARY STEEL HEADER AT NEW DOOR/WINDOW
OPENING IN EXISTING CONCRETE WALL
NTSA6
TYPICAL NEW DOOR/WINDOW OPENING IN EXISTING CONCRETE
WALL
NTSE8
CONCRETE HORIZONTAL WALL
CONSTRUCTION JOINTS
NTSE6
CONCRETE VERTICAL WALL
CONSTRUCTION JOINTS
LAP 24"
ADD BARS TO MATCH
FOOTING REINF.
FOOTING REINF.
UNDER FOOTINGTHROUGH FOOTING
6" DIA. MAX.
6" DIA. MAX.
ADD 2-#4x4'
BEND 12"
ADD BARS TO MATCH
FOOTING REINF.
9"
"T
"T
9"
1"
1/ 2"
"T
"T
1/
2" M
IN
FOOTING
EXCAVATION SHALL NOT
EXTEND BELOW THIS LINE
NOTE:
CONTRACTOR SHALL BE RESPONSIBLE
FOR MAINTAINING ALL TRENCH SLOPES
BY SHORING AS REQUIRED
2' - 1"
PROVIDE 90°
BEND AT END OF
INTERRUPTED
BARS (TYP.)
2-DIAG. BARS EQUAL IN SIZE
TO MAIN DIRECTION
BARS x 96 BAR DIA. LONG, AT EACH CORNER, T&B (TYP.)
MAIN DIRECTION BARS:
ADD 1/2 THE NUMBER OF
BARS INTERRUPTED PLUS
ONE TO EACH SIDE OF
OPENING AT 3" O.C., TYP.
BARS SHALL CONTINUE
BETWEEN BEARING SUPPORTS
TRANSV. DIRECTION BARS:
ADD 1/2 THE NUMBER OF BARS
INTERRUPTED PLUS ONE TO EACH
SIDE OF OPENING AT 3" O.C.,TYP.
BARS SHALL CONTINUE BETWEEN
BEARING SUPPORTSUSE SIMILAR DETAILS
FOR ROUND OPENINGS
TOP OF FOOTING
FOR INTERSECTING
INTERIOR AND
PERIMETER WALLS
SLAB AT
ENTRY
TOP OF FOUNDATION
WALL AT DOOR OPENINGS
SOG OR TS
EJEJ
VAPOR BARRIER, TYP.
BTB OPTION SHOWN,
SEE SPECS, TYP.
GEOTEXTILE FABRIC, TYP.
3B FINE CWB, TYP.
COMPACTED
SUBGRADE, TYP.
VERTICAL CONTAINMENT
BARRIER-CORRUGATED
FIBERGLASS ROOFING
SHEETS, TYP.
NOTE:
BTB REQUIRED ON DIRECT CONTACT ALONG
VERTICAL FACES OF ALL INTERIOR AND
EXTERIOR FOUNDATION WALLS, GRADE
BEAMS, AND TOP OF FOOTING AS SHOWN
GTB, TYP.
4" MIN.
6" SELECT
GRANULAR FILL
(N) L4x4x1/4 BELOW (E)
CONC SLAB W/ (5) 5/8" DIA
EXP ANCHORS
(MIN TENSILE CAP = 1,600LB
MIN SHEAR CAP = 1,700 LB)
(E) CONC
GIRDER BELOW
(N) 4"x4"x1/4" PL, TYP
(N) 3/4" DIA
EPOXY EMBEDDED
THREADED RODS
CONC WALL
4' -4
" M
AX
2'-6" MAX.
3" TYP. 12" TYP. 8" TYP. 5"
EMBED
1/4
TYP.
"C" "C"
"A"
"A"
1/4
TYP.
(N) OPN'G
SECTION "C"-"C"
DIRECTION
OF SLAB
SPAN
(N) L4x
(E) CONC.
TOPPING
(N) L4x
(E) CONC.
TOPPING
(E) STRUCTURAL
CONC. SLAB
(N) EXPANSION
ANCHOR
(N) EXPANSION
ANCHOR
(N) L4x4x1/4 BELOW (E)
CONC SLAB W/ (5) 5/8" DIA
EXP ANCHORS
(MIN TENSILE CAP = 1,600 LB
MIN SHEAR CAP = 1,700 LB)
3" TYP. 6" TYP.
2'-0" MIN. 2'-6" MAX.
4' -4
" M
AX
1/
2" M
IN
"B" "B"
"A"
"A"
(N) OPN'G
(N) OPN'G
SECTION "A"-"A"
SECTION "B"-"B"
EQ EQ
6"
EM
BE
D
4"
(E) STRUCTURAL
CONC. SLAB
#4 CONT HORIZ BARS AT
8" WITH 1'-6" BEND OR
1'-6"x1'-6" DOWELS AT
CORNERS, TYP
ROUGHEN
SURFACE
TOP OF SLAB
#3 AT 16" EW
ROUGHEN SURFACE #4 AT 12" DOWELS
EXIST. CONC.
TOPPING
EPOXY
SAWCUT EXIST.
CONC. TOPPING
3/4" CHAMFER
#3 AT 16" 90° BEND
EMBED 3" MIN INTO (E) SLAB
AROUND PERIMETER OF PAD
CURBPAD ON EXISTING CONCRETE SLAB
4 1/2"
1/
2"
MECH. EQUIPMENT
EXTEND 6" PAST
1" CLR.
7" U
.O .N
4"
5" MIN., 9" MAX.
CURB WIDTH AS REQ'D
" M
AX
"H
TH
K.
SL
AB
EM
BE
D
3"
ADD #4 IF H > 10"
NTSF6 TYPICAL PIPE SLEEVE AT FOOTING
NTSA6 TYPICAL TRENCH DETAIL
NTSA3 TYPICAL CONC. SLAB OPENING REINF.
NTSA1
BASALTIC TERMITE BARRIER (BTB)
AT FOUNDATION WALLS
NTSC6 CONDITION WHERE PENETRATION ABUTS CONC. WALL
NTSE1 NEW OPENING IN EXISTING SLAB GREATER THAN 18"
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
D
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
S-007
TY
PI
C A L
F O
U N
D
AT
IO
N
A N
D S
L A B
D E T
AI
LS
F Y
R E P
AI
R
B L D
G
H O
N O
L U
LU
D
IS
TR
IC
T
FT
. S H
AF
TE
R , H
AW
A I
I 9
-5
R
EG
IO
N
AL
E
N G
IN
EE
R
IN
G C
EN
TE
R H
O N
O
LU
LU
E
N G
IN
EE
R D
IS
TR
IC
T
H O
N O
LU
LU
, H I
C Y
BH
M
AY
RTA SUBMITTAL
SC
H
O
FI
EL
D
B
AR
R
AC
KS
, O
AH
U
, H
AW
AI
NTSC1 CONCRETE CURBS AND PADS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A
B
C
D
E
F
G
DEMOLISH PORTION
OF (E) CONC. WALL
SEE
DEMOLISH
PORTION OF
(E) CONC. WALL
SEE
DEMOLISH PORTION
OF (E) CONC. WALL
SEE
A4/S-005
A4/S-005
A4/S-005
DEMOLISH PORTION
OF (E) WALL FTG.
SHOWN , TYP.
DEMOLISH PORTION
OF (E) CONC. GRADE
BEAM
DEMOLISH (E) CONC. SLAB-
ON-GRADE THROUGHOUT
ENTIRE FACILITY
DEMOLISH PORTION OF
(E) CONC. FOUNDATION
(E) CONCRETE WALL TO BE
DEMOLISHED
(E) CONCRETE FOOTING OR TIE
BEAM TO BE DEMOLISHED
LEGEND
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
D
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
SD101
FO
U
N D
A T
IO
N D
EM
O
LI
TI
O N
P
LA
N
F Y
R E P
AI
R
B L D
G
H O
N O
L U
LU
D
IS
TR
IC
T
FT
. S H
AF
TE
R , H
AW
A I
I 9
-5
R
EG
IO
N
AL
E
N G
IN
EE
R
IN
G C
EN
TE
R H
O N
O
LU
LU
E
N G
IN
EE
R D
IS
TR
IC
T
H O
N O
LU
LU
, H I
D es ig ne r
Au th or
C he ck er
M
AY
RTA SUBMITTAL
SC
H
O
FI
EL
D
B
AR
R
AC
KS
, O
AH
U
, H
AW
AI
I
1/16" = 1'-0"D2 FOUNDATION AND FIRST FLOOR DEMOLITION PLAN
NOTE:
SEE SHEET SD102
FOR 2ND AND 3RD FLOOR DEMOLITION
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
DEMOLISH PORTION OF
CONC. SLAB AND BEAM
SHOWN TYP.
DEMOLISH PORTION OF
CONC. SLAB AND BEAM
SHOWN TYP.
DEMOLISH (E) STEEL BEAM
SHOWN TYP.
DEMOLISH
(E) CONC. SLAB
DEMOLISH (E) STEEL BEAM
SHOWN TYP.
DEMOLISH PORTION
OF CONC. SLAB FOR
MECH PIPING
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
A
B
C
D
E
F
G
DEMOLISH PORTION OF
CONC. SLAB AND BEAM
SHOWN TYP.
DEMOLISH PORTION OF
CONC. SLAB AND BEAM
SHOWN TYP.
DEMOLISH PORTION
OF CONC. SLAB FOR
MECH PIPING
(E) CONCRETE WALL TO BE
DEMOLISHED
(E) CONCRETE SLAB TO BE
DEMOLISHED
(E) STEEL BEAM TO BE
DEMOLISHED
LEGEND
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
D
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
SD102
SE
C
O N
D A
N D
T H
IR
D
F
LO
O R
D
EM
O
LI
TI
O
N P
L A N
F Y
R E P
AI
R
B L D
G
H O
N O
L U
LU
D
IS
TR
IC
T
FT
. S H
AF
TE
R , H
AW
A I
I 9
-5
R
EG
IO
N
AL
E
N G
IN
EE
R
IN
G C
EN
TE
R H
O N
O
LU
LU
E
N G
IN
EE
R D
IS
TR
IC
T
H O
N O
LU
LU
, H I
D es ig ne r
Au th or
C he ck er
M
AY
RTA SUBMITTAL
SC
H
O
FI
EL
D
B
AR
R
AC
KS
, O
AH
U
, H
AW
AI
I
1/16" = 1'-0"D2 THIRD FLOOR DEMOLITION PLAN
1/16" = 1'-0"A2 SECOND FLOOR DEMOLITION PLAN
1 2 3 4 5 6 7 8 9
B
C
D
E
F
G
E1
SB501
D8
SB502
SE
E
A1 /S
B1
M
AT
C H
LI
N
E
SE
E
A1 /S
B1
M
AT
C H
LI
N
E
E3
SB501
(E) 8" THK. CONC.
WALL, TYP.
8" THK. CONC. ARMS
VAULT WALLS, TYP.
EJ(E) CONC. COLUMN
AND FTG, TYP.(E) CONC. GRADE
BEAM AT (E) STAIR
CORE TO REMAIN, TYP.
CONC. SLAB-ON-
GRADE OVER FILL
SHOWN
MATCH BUILDING FINISH
FLOOR ELEVATION
W F-
W
F-
W F-
W F-
WF-1WF-1
WF-1
WF-1
W F-
W
F-
WF-2
WF-2
W F-
W F-
WF-2
TY
P.
2'
0"
8"X12" CONC. MULLION
SEE , TYP.
W F-
W F-
SLAB-ON-GRADE,
SEE NOTE 1
W F-
W
F-
6" THK. CONC. SLAB-
ON-GRADE, W/ #4 AT
12" O.C., E.W., AT
MID-DEPTH, TYP. AT
ARMS VAULTS
16" SQ. CONC. COL.
OVER (N) 6'-6" SQ. X 2'-0"
THK. FTG., TYP.
A1
SB501
E6
SA501
5" THK. CONC.
STOOP W/ #4
AT 12" O.C.,
E.W. MID-DEPTH
(E) CONC. GRADE
BEAM BELOW, TYP.
F7
SB501
TOF = -4.00'
TOF = -5.00'
TOF = -5.00' TOF = -4.00'
TOF = -4.00'
D1
SB502
A1
SF301
B1
SA501
WF-1
W F-
1 W F-
SUMP PIT, SEE
ARCH DWGS
TOF = -4.00'
A1
SB503
A1
SB502
TYP.
SB401
A1
CONC. EQUIP. PAD,
SEE C1/S-007, SIM.
SB502
A4
SB502
A6
WF-2
D6
SB503
8" THK. CONCRETE ARMS VAULT
WALL W/ #4 AT 9" O.C., STAGGERED
EA. FACE
(E) CONCRETE TO REMAIN
8" THK. CONCRETE WALL W/
#6 AT 16" O.C., E.W., CENTERED
2" DEEP DEPRESSED SLAB
CONC. SLAB-ON-GRADE OVER FILL
CONC. EQUIP. PAD
WF-1 WALL FOOTING
EXISTING FOOTING
NEW FOOTING
SLAB DEPRESSION
LEGEND
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
D
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
SB101
FO
U
N D
AT
IO
N P
LA
N
F Y
R E P
AI
R
B L D
G
H O
N O
L U
LU
D
IS
TR
IC
T
FT
. S H
AF
TE
R , H
AW
A I
I 9
-5
R
EG
IO
N
AL
E
N G
IN
EE
R
IN
G C
EN
TE
R H
O N
O
LU
LU
E
N G
IN
EE
R D
IS
TR
IC
T
H O
N O
LU
LU
, H I
C Y
JA
, B
H
M
AY
RTA SUBMITTAL
SC
H
O
FI
EL
D
B
AR
R
AC
KS
, O
AH
U
, H
AW
AI
I
1/8" = 1'-0"A3 PARTIAL FOUNDATION PLAN - PLAN WEST
KEY PLAN
NOT TO SCALE
1 8 9 16
C
G
A
04 8 16268
SCALE: 1/8"=1'-0"
TRUE NORTH
PLAN NORTH
NOTES:
1. 5" THK. SLAB-ON-GRADE W/ #4 AT 12" O.C.,
E.W. AT MID-DEPTH.
2. CONTRACTOR SHALL REMOVE ANY
EXISTING PLASTER OR ARCHITECTURAL
FINISH PRIOR TO INSTALLING ADDITIONAL
LAYER OF CONCRETE.
3. ALL ITEMS ARE NEW UNLESS NOTED AS
EXISTING, (E)
REFERENCE DRAWINGS:
S-001 GENERAL STRUCTURAL NOTES
S-002 GENERAL STRUCTURAL NOTES
S-003 TYPICAL SLAB-ON-GRADE DETAILS
S-004 TYPICAL REINFORCING DETAILS
S-005 TYPICAL CONCRETE WALL DETAILS
S-006 TYPICAL CONCRETE WALL DETAILS
S-007 TYPICAL FOUNDATION AND SLAB
DETAILS
8 9 10 11 12 13 14 15 16
B
C
D
E
F
G
M
AT
C H
LI
N
E
SE
E
A1 /S
B1
SE
E
A1 /S
B1
M
AT
C H
LI
N
E
EJ
(E) 8" THK. CONC.
WALL, TYP.
8" THK. CONC.
WALL, TYP.
(E) CONC. GRADE
BEAM AT (E) STAIR
CORE TO REMAIN, TYP.
(E) CONC. COLUMN
AND FTG, TYP.
WF-1
WF-1
W F-
W F-
W F-
W F-
W F-
W F-
WF-1
WF-1
W F-
W F-
WF-1
W F-
8"X12" CONC. MULLION
SEE , TYP.
W F-
8" THK. CONC. ARMS
VAULT WALLS, TYP.
6" THK. CONC. SLAB-
ON-GRADE, W/ #4 AT
12" O.C., E.W., AT
MID-DEPTH, TYP. AT
ARMS VAULTS
16" SQ. CONC. COL.
OVER (N) 6'-6" SQ. X 2'-0"
THK. FTG., TYP.
E1
SB501
E1
SB501
E6
SA501
5" THK. CONC.
STOOP W/ #4
AT 12" O.C.,
E.W. MID-DEPTH
(E) CONC. GRADE
BEAM BELOW, TYP.
TOF = -3.25'
TOF = -3.25'
TOF = -3.25'
TOF = -3.25'
D5
SB502
D1
SB502
B1
SA501
TYP.
CONC. EQUIP PAD,
SEE C1/S-007, SIM.
SB502
A6
WF-2
WF-2
D1
SB502
SIM.
8" THK. CONCRETE ARMS VAULT
WALL W/ #4 AT 9" O.C., STAGGERED
EA. FACE
(E) CONCRETE TO REMAIN
8" THK. CONCRETE WALL W/
#6 AT 16" O.C., E.W., CENTERED
2" DEEP DEPRESSED SLAB
CONC. SLAB-ON-GRADE OVER FILL
CONC. EQUIP. PAD
WF-1 WALL FOOTING
EXISTING FOOTING
NEW FOOTING
SLAB DEPRESSION
LEGEND
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
D
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
SB102
FO
U
N D
AT
IO
N P
LA
N
F Y
R E P
AI
R
B L D
G
H O
N O
L U
LU
D
IS
TR
IC
T
FT
. S H
AF
TE
R , H
AW
A I
I 9
-5
R
EG
IO
N
AL
E
N G
IN
EE
R
IN
G C
EN
TE
R H
O N
O
LU
LU
E
N G
IN
EE
R D
IS
TR
IC
T
H O
N O
LU
LU
, H I
C Y
JA
, B
H
M
AY
RTA SUBMITTAL
SC
H
O
FI
EL
D
B
AR
R
AC
KS
, O
AH
U
, H
AW
AI
I
1/8" = 1'-0"A3 PARTIAL FOUNDATION PLAN - PLAN EAST
04 8 16268
SCALE: 1/8"=1'-0"
TRUE NORTH
PLAN NORTH
KEY PLAN
NOT TO SCALE
1 8 9 16
C
G
A
NOTES:
1. 5" THK. SLAB-ON-GRADE W/ #4 AT 12" O.C.,
E.W. AT MID-DEPTH.
2. CONTRACTOR SHALL REMOVE ANY
EXISTING PLASTER OR ARCHITECTURAL
FINISH PRIOR TO INSTALLING ADDITIONAL
LAYER OF CONCRETE.
3. ALL ITEMS ARE NEW UNLESS NOTED AS
EXISTING, (E)
REFERENCE DRAWINGS:
S-001 GENERAL STRUCTURAL NOTES
S-002 GENERAL STRUCTURAL NOTES
S-003 TYPICAL SLAB-ON-GRADE DETAILS
S-004 TYPICAL REINFORCING DETAILS
S-005 TYPICAL CONCRETE WALL DETAILS
S-006 TYPICAL CONCRETE WALL DETAILS
D
A1
SB503
D1
SB503
WF-1
W F-
SUMP PIT, SEE
ARCH DWGS
8" THK. CONC.
WALL
(E) CONC.
COLUMN TO
REMAIN
(E) CONC.
FOOTING TO
REMAIN
8" THK. CONC.
ELEV. PIT
WALL
12" THK. CONC.
ELEV. PIT
WALL
CONC. COLUMN
AND FOUNDATION,
SEE A3/SB101
(E) FOOTING TO
BE DEMOLISHED
SEE NOTE
D6
SB503
NOTE:
TEMPORARILY SHORE (E)
FTG. AS REQUIRED UNTIL
ELEVATOR MAT FOUNDATION
IS PLACED AS REACHES ITS
28-DAY STRENGTH.
D
TS
-1
2' - 0"
2'
0"
TS-1
FOOTING FOR
STAIR
P 3/8" X 12", MATCH
LENGTH OF CHANNEL
WEB
L
F1
SF503
TS
-1
TS-1
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
D
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
SB401
PA
R
TI
A L
E N
L A R
G E D
E
LE
VA
TO
R A
N D
S
TA
I R F O
U N
D
AT
IO
N
P
LA
N
F Y
R E P
AI
R
B L D
G
H O
N O
L U
LU
D
IS
TR
IC
T
FT
. S H
AF
TE
R , H
AW
A I
I 9
-5
R
EG
IO
N
AL
E
N G
IN
EE
R
IN
G C
EN
TE
R H
O N
O
LU
LU
E
N G
IN
EE
R D
IS
TR
IC
T
H O
N O
LU
LU
, H I
D es ig ne r
Au th or
C he ck er
M
AY
RTA SUBMITTAL
SC
H
O
FI
EL
D
B
AR
R
AC
KS
, O
AH
U
, H
AW
AI
I
1/2" = 1'-0"A1
PARTIAL ENLARGED ELEVATOR
FOUNDATION PLAN
1/2" = 1'-0"A6
PARTIAL ENLARGED STAIRS
FOUNDATION PLAN
TRUE NORTH
PLAN NORTH
TRUE NORTH
PLAN NORTH
01 2 42
SCALE: 1/2"=1'-0"
F.F.
0' - 0"
GROUND FLOOR
0' - 0"
3' - 0"
1'
0"
VE
R
IF
Y
IN
F
IE
LD
VA
R
IE
S, M
AT
C H
(E
BO
T.
O F
FT
G
. E
LE
VA
TI
O N
#6 AT 12" E.W.
TOP AND BOTT.
CONC. WALL
WALL REINF., SEE PLANS
DOWEL TO MATCH
SIZE, LOCATION, AND
SPACING OF WALL
VERT. REINF.
CONC. SLAB-ON-GRADE
3/4" DEEP X 1 1/2"
WIDE CONT. KEY
F.F.
0' - 0"
GROUND FLOOR
0' - 0"
#6 AT 12" E.W.
TOP AND BOTT.
CONC. ARMS
VAULT WALL
ARMS VAULT WALL
REINF., SEE PLANS
DOWEL TO MATCH
SIZE, LOCATION, AND
SPACING OF WALL
VERT. REINF.
CONC. SLAB-ON-GRADE
3/4" DEEP X 1 1/2"
WIDE CONT. KEY
2' - 0"
1'
0"
VE
R
IF
Y
IN
F
IE
LD
VA
R
IE
S, M
AT
C H
(E
BO
T.
O F
FT
G
. E
LE
VA
TI
O N
#4 AT 12" O.C., E.W.
EXTEND SLAB REINF.
INTO ARMS VAULT
WALL, TYP.
F.F.
0' - 0"
GROUND FLOOR
0' - 0"
ISOLATION JOINT,
SEE C1
S-003
CONC. SLAB-ON-GRADE
CONC. COLUMN,
SEE PLAN
VE
R
IF
Y
IN
F
IE
LD
VA
R
IE
S, M
AT
C H
(E
BO
T.
O F
FT
G
. E
LE
VA
TI
O N
2'
0"
6' - 6" SQ.
7-#6 E.W., TOP
AND BOTT.
COLUMN DOWELS, SIZE
AND LOCATION TO MATCH
COLUMN VERT. REINF., TYP.
LAP SPLICE,
SEE A1/S-004
WALL REINF.
SEE PLAN
6-#8 VERT. BARS
#4 TIES
8" 8"
1' - 4"
(E) CONC. GRADE BEAM
(E) CONC. FTG.
CONC. WALL FTG
CONC. WALL
DOWEL EPOXIED INTO
(E) COL. FTG., SIZE AND
SPACING TO MATCH
WALL FTG. CONT. BARS
SEE
A4/S-004
SEE A1/S-004
(E) CONC. PEDESTAL
BEYOND
WALL FTG. WHERE
OCCURS
CONC. COLUMN
FTG.
COLUMN FTG.
REINF.
WALL FTG.
REINF.
EXTEND WALL FTG.
REINF. THROUGH
COLUMN FTG.
CONC. WALL
3/4" = 1'-0"E1 WF-1 DETAIL
3/4" = 1'-0"E3 WF-2 DETAIL
3/4" = 1'-0"A1 COLUMN FOOTING DETAIL
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
D
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
SB501
ST
R
U C
TU
R
AL
F
O U
N D
AT
IO
N D
ET
AI
LS
F Y
R E P
AI
R
B L D
G
H O
N O
L U
LU
D
IS
TR
IC
T
FT
. S H
AF
TE
R , H
AW
A I
I 9
-5
R
EG
IO
N
AL
E
N G
IN
EE
R
IN
G C
EN
TE
R H
O N
O
LU
LU
E
N G
IN
EE
R D
IS
TR
IC
T
H O
N O
LU
LU
, H I
C Y
BH
M
AY
RTA SUBMITTAL
SC
H
O
FI
EL
D
B
AR
R
AC
KS
, O
AH
U
, H
AW
AI
I
SCALE: 3/4"=1'-0"
12 2
3/4" = 1'-0"D7 TYPICAL CONCRETE COLUMN DETAIL
3/4" = 1'-0"A6 WALL FOOTING TO (E) COLUMN FOOTING DETAIL
3/4" = 1'-0"F7 FOOTING INTERSECTION DETAIL
GROUND FLOOR
0' - 0"
#6 AT 12" E.W.
TOP AND BOTT.
DOWEL TO MATCH
SIZE, LOCATION, AND
SPACING OF WALL
VERT. REINF.
3/4" DEEP X 1 1/2"
WIDE CONT. KEY
CONC. SLAB-ON GRADE
8"
2' - 0"
1'
0"
VE
R
IF
Y
IN
F
IE
LD
B O
T.
O
F
FT
G E
LE
VA
TI
O
N
VA
R
IE
S M
AT
C
H (E
(E) WALL
CONC ARMS
VAULT WALL
ARMS VAULT WALL
REINF., SEE PLANS
#4 @ 12" OC
#4 AT 12" O.C., E.W.
EXTEND SLAB REINF.
INTO ARMS VAULT
WALL, TYP.
F.F.
0' - 0"
GROUND FLOOR
0' - 0"
1'
4"
5"
10"
(E) WALL BEYOND
1/2" PREMOLDED JOINT FILLER
#4 @ 12 OC
(E) GRADE BEAM
F.F.
0' - 0"
E
GROUND FLOOR
0' - 0"
(E) CONC. GRADE
BEAM TO REMAIN
PORTION OF (E)
MASONRY STEM
WALL TO REMAIN
M
IN
8"
CONC. SLAB-
ON GRADE
DEMOLISH PORTION
OF (E) MASONRY STEM
WALL…