W9127P-13-R-003 – RAM Blast
Q&A V.6
6 SEP 2013
1. Could you please send technical specs of the RAM Blaster?
a. The weight or dimensions are not needed. The building and openings as specified will handle the RAM Blaster installation. Installation will be by a third party.
2. We are needing the weight, dimensions and how much heat it puts out for HVAC calculations.
a. Do not size the HVAC for the RAM Blaster. Size the AC to keep the building stable in a not in use configuration. When the RAM blast is in operation the overhead door will most likely be open.