Dredge Yaquina - TAB Report March 2023.pdf
PDF 7 MB Posted
- Attached to
- FY24 Yaquina Overhaul Solicitation
- Solicitation number
- W9127N23B0014
About this file
This document is a Test, Adjust and Balance (TAB) report for pneumatic control system replacements aboard the dredge Yaquina. The report details TAB work performed by MacDonald Miller Facility Solutions under job number 7322-3965. TAB procedures were conducted in accordance with NEBB standards on various dual duct box air distribution units serving over 30 zones. Test data is provided for both cooling and heating modes, including supply air flow measurements and temperatures. Measured data is noted as a percentage of design air flows. Most units measured between 30-80% of design air flow values, with some higher. The report includes instrumentation calibration records and generic schematics but no system design drawings.
The related federal contract opportunity is a solicitation from the US Army Corps of Engineers Portland District for the FY24 overhaul of the dredge Yaquina. The solicitation number is W9127N23B0014 but no further details are provided in the document.
View the file
Other files
Show 40 more
Latest 50 of 119 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MacDonald Miller Facility Solutions Test Adjust and Balance Report
Job #: 7322-3965
March 7, 2023
Prepared For
Everett Ship Repair 2730 Federal Ave Everett, WA 98201
Prepared By Joshua Buzzard
USS Yaquina
NEBB CERTIFIED
TEST, ADJUST & BALANCE REPORT
FOR
USS YAQUINA
JOB # 7322-3965
2730 FEDERAL AVE, EVERETT, WA 98201
HVAC CONTRACTOR: MACDONALD MILLER
THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL
ADJUSTMENTSTHAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE
NEBB PROCEDURAL STANDARDS FOR TESTING, ADJUSTING AND BALANCING OF ENVIRONMENTAL
SYSTEMS. THE MEASUREMENTS SHOW, AND THE INFORMATION GIVEN, IN THIS REPORT ARE
CERTIFIED TO BE ACCURATE AND COMPLETE, AT THE TIME AND DATE INFORMATION WAS GATHERED.
ANY VARIANCES FROM DESIGN QUANTITIES, WHICH EXCEED NEBB TOLERANCES, ARE NOTED IN THE
TEST-ADJUST- BALANCE REPORT PROJECT SUMMARY.
SUBMITTED & CERTIFIED BY:
MR NOAH WALKER, NEBB SUPERVISOR REPORT DATE:
Certification Expiration Date: December 31, 2023
FIELD FOREMAN: NOAH WALKER
FIELD TECHNICIAN: JOSHUA BUZZARD
ABBREVIATIONS
AC AIR CONDITIONING UNIT HP HORSEPOWER
BDD BACK DRAFT DAMPER HP HEAT PUMP AIR CONDITIONING UNIT
BHP BRAKE HORSEPOWER HWR HEATING WATER RETURN
B.S. BIRD SCREEN HWS HEATING WATER SUPPLY
CEG CEILING EXHAUST GRILLE INAC INACCESSIBLE
CRG CEILING RETURN GRILLE LAT (DB) LEAVING AIR TEMP. (DRY BULB)
CFM CUBIC FEET PER MINUTE LAT (WB) LEAVING AIR TEMP. (WET BULB)
CHWR CHILLED WATER RETURN LD LINEAR DIFFUSER
CHWS CHILLED WATER SUPPLY LWT LEAVING WATER TEMPERATURE
CSD CEILING SUPPLY DIFFUSER MAX MAXIMUM
CWR CONDENSER WATER RETURN MIN MINIMUM
CWS CONDENSER WATER SUPPLY O WIDE OPEN DAMPER / AIR PATH
DD DIRECT DRIVE OBD OPPOSED BLADE DAMPER
DP DIFFERENTIAL PRESSURE OD OUTSIDE DIAMETER
DIFF DIFFUSER OSA OUTSIDE AIR
DMPR DAMPER RA RETURN AIR
DNA DATA NOT AVAILABLE REQ’D REQUIRED
DNL DATA NOT LISTED RH RELATIVE HUMIDITY
DNT DATA NOT TAKEN RTU ROOFTOP UNIT
DWDI DOUBLE WIDTH DOUBLE INLET SA SUPPLY AIR
EAT (DB) ENTERING AIR TEMP. (DRY BULB) SP STATIC PRESSURE
EAT (WB) ENTERING AIR TEMP. (WET BULB) SWG SIDE WALL GRILLE
EC EGGCRATE RETURN SWR SIDE WALL REGISTER
EF EXHAUST FAN SWSI SINGLE WIDTH SINGLE INLET
EG EXHAUST GRILLE T OUTLET NEAREST THERMOSTAT
ESP EXTERNAL STATIC PRESSURE TSP TOTAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE T.P. THERMALLY PROTECTED
FPM FEET PER MINUTE T-STAT THERMOSTAT OR SENSOR
FH FUME HOOD TYP TYPICAL
GPM GALLONS PER MINUTE ∅ VOLTAGE PHASE / DUCT DIAMETER
HF HEPA FILTER V.D. VOLUME DAMPER
EXECUTIVE SUMMARY
I. GENERAL NOTES
A. TAB completion date: 02/28/2023
B. Design information was provided from original mechanical drawings, or they were field engineered.
C. TAB work was in accordance with the most current version of NEBB procedural standards for Testing
Adjusting and Balancing.
D. Methods of measurements: All measurements were taken with appropriate instruments based on the standards referenced above and comparable to the list of calibrated instruments listed in calibration report of this report.
E. Basic “not to scale” drawings with device and outlet numbering are included in Appendix of this report.
F. Motors of fans which did not list pF (power factor) or Eff (efficiency) ratings on their nameplate had it’s associated fan’s BHP (Brake Horsepower) approximated by using a nominal 0.9 pF and 0.8 Eff in the BHP calculation. Actual BHP's may vary slightly in this condition.
II. SCOPE OF WORK
A. Various pneumatic piston actuators were replaced, along with pneumatic thermostats, throughout the ship. All work was the test and balance each piece of equipment which was replaced.
III. DESCRIPTION OF THE SYSTEMS BALANCED
A. For each unit a pneumatic actuator moves a damper which modulates between cold deck ductwork and hot deck ductwork. This piston’s control signal comes from a thermostat located in each zone. There are no balancing dampers present on any of the pneumatic boxes.
IV. TAB PROCEDURES SUMMARIZED – AIR SYSTEM TESTING PROCEDURES
A. The zone was placed into full cooling by turning the thermostat to the lowest setting, which was 55 F.
B. The discharge air volume and temperature were read and recorded.
C. The unit was placed into full heating by turning the thermostat to the highest setting, which was 85 F.
D. The discharge air volume and temperature were read and recorded.
V. OTHER MISCELLANEOUS NOTES
A. Because the scope was limited to testing of the replaced elements of the system and there were components on the system which were not worked on, compounded by the issue of not dampers being found to further balance the system, the numbers recorded were marked as final. Any low readings were left as is because the balance of the entire system was out of scope and no action could be taken.
Instrument Calibration Record Calibration
DateFunction Range Accuracy
∆ Pressure
Measurement
0.4 to 75
PSI
±2% or Read
0.5 PSI
0.01
PSI
Model # Alnor HM675 11/1/2022
Serial # 7733099
±0.5% of
Reading or
2.0⁰F
Z406825
Extech - 461995Model #
Serial #
Temperature Measurement
Resolution Model & Serial Numbers
Instrument
Rotational Measurement
Tachometer 60-5000
RPM
±2% of Read
± 2 RPM
RPM
10/17/2022
6/22/2022
6/27/2022
6/27/2022
6/27/2022
Fluke 52II Series
50092988MV
Fluke 80PK-25
2098706
Fluke 80PK-25
2098706
Electrical Measurement
Volts
Amperes
1-600
VAC
0.1 -100
Amps
1 Volt
0.1 Ampers
Model #
OMEGA 794
NA
0.1⁰F
Model #
Serial #
Model #
Serial #
Model #
Serial #
Model #
Serial #
Thermometer
Air
Probe
Immersion
Probe
Contact
Probe
0⁰F to
200⁰F
6/24/2022
6/24/2022
±2% of
Reading or
±5 Digits
Air Pressure & Velocity
Pressure
Velocity
(Pitot Tube)
±2% of Read
±0.001" w.g.
±0.001 w.g.
≤1" w.g.
±5% of Read
±7 FPM
1.0 FPM
Serial #
Model #
Serial #
Fluke 378 FC
56550098
Fluke 378 FC
56550098
Serial #
Model #
Serial #
Velocity
(Hot Wire)
Digital Direct
Reading Hood
0 - 10.0 in W.G.
100 to 3500
FPM
50 to 6000
FPM
100 to 2000
CFM
Model #
Serial #
4/28/2022
4/28/2022
11/30/2022
12/19/2022 50611991 / 1022
Humidity Measurement
Model #
Serial #
Shortridge 860C
M13055
Shortridge 860C
M13055
TSI 966
P22490016
Testo 420
±3% of Read
±3 FPM
1.0 FPM
±5% of Read
±7 CFM
1.0 CFM
Model #
Serial #
Model #
11/1/2022 Serial # 7733099
Date Updated 1/18/2023
TSI 966
P22490016 11/30/2022
Hydronic Measurement Pressure
Measurement
0.4 to 200
PSI
±2% or Read
1 PSI
0.1
PSI
Model # Alnor HM675
Humidity 10 to 90%
RH
±3% RH 1.00%
Calibration
Date
Instrument Calibration
Rotational Measurement Extech - 461895
Tachometer 60-5000
RPM
±2% of Read
±2 RPM
RPM
6/23/2022
Z341111
Instrument
Function
Minimum
Range
Minimum
Accuracy
Minimum
Resolution Instrument Information
Temperature Measurement
Thermometer
Air Probe
Immersion Probe
0⁰F to
200⁰F
±5% of
Reading or
2.0⁰F
0.1⁰F
Fluke 52 Series II
50092988MV
Fluke 80PK-25
NA
Fluke 80PK-25
NA
OMEGA 792
Contact Probe
NA
6/22/2022
6/27/2022
6/27/2022
6/27/2022
±2% of
Reading or
±5 Digits
Electrical Measurement
Volts
Amperes
6/24/2022
6/24/2022
1 - 600
VAC
0.1 - 100
Amps
1 Volt
0.1 Ampes
Fluke 378 FC
56550098
Fluke 378 FC
56550098
Air Pressure & Velocity
Air
Pressure
Air Velocity
Pitot Tube
Air
Velocity
0 to 10.0 in w.g.
±2% or read
±0.001" wg
50 to 3500
FPM
±5% of read
±7FPM
50 t0 6000
FPM
±3% of read
±3 FPM
4/28/2022
4/28/2022
9/22/2021
50 to 6000
FPM
±1% of read
±4 FPM
±0.01" wg
≤1 " wg
1.0 FPM
1.0 FPM
1.0 FPM
1.0%
TSI 9545-A
9545A1904010
9/22/2021
Shortridge 860C
M13055
Shortridge 860C
M13055
TSI 9545-A
9545A1904010
TSI 5725
T57251942002
Air Velocity
RVA
9/22/2021
Hydronic Measurement
Hydronic
Differential
0.4 to 200
PSI
±2% or read
1 PSI
0.1
PSI
4/6/2022
ALNOR HM685
72203018
Humidity Measurement
Humidity 10 to 90%
RH
±3% RH
Manufacturer:
ID / Asset Number:
Function / Range Nominal
Value As Found Result As Left Result Min Max Units Uncertainty
0.5 to 1,000 rpm 600.0 599.9 Pass Same Pass 599.6 600.4 rpm 0.060 rpm
1,000 to 99,999 rpm 18000 17998 Pass Same Pass 17990 18010 rpm 0.58 rpm
42000 41998 Pass Same Pass 41978 42022 rpm 0.59 rpm
60000 59995 Pass Same Pass 59969 60031 rpm 0.60 rpm
90000 89996 Pass Same Pass 89954 90046 rpm 0.63 rpm
Decision Rule 1 - Accredited Calibration Datasheets may contain measurements that are not covered by the Scope of Accreditation. These measurements are indicated by a pound sign(#).
Measurement Uncertainty IS NOT taken into account for determining PASS or FAIL.
********END OF MEASUREMENT REPORT********
Non-Contact RPM Contact RPM
1047875 Calibration Date: 6/22/2022
EXTECH Model Number: 461995
Certificate Number: 17381589
Data Page 1 of 1
Project
Job Number
No. Type Size Ak
(3) Asst. Master S.R. 1 CD 10"Ø Hood 28%
Totals 28%
(3) Asst. Master S.R. 1 CD 10"Ø Hood 72%
72%
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
145 33 105
145 33 105
145 313 40
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
145 313 40
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
Area Served Outlet Design Preliminary
No. Type Size Ak
(4) Master S.R. 1 CD 10"Ø Hood 24%
Totals 24%
(4) Master S.R. 1 CD 10"Ø Hood 69%
69%
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
166 33 115
166 33 115
166 313 40
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
166 313 40
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(5) Master Off. 1 CD 10"Ø Hood 56%
Totals 56%
(5) Master Off. 1 CD 10"Ø Hood 75%
75%
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
153 33 115
153 33 115
153 105 85
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
153 105 85
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(6) Ch. ENGR S.R. 1 CD 10"Ø Hood 45%
Totals 45%
71.6
(6) Ch. ENGR S.R. 1 CD 10"Ø Hood 66%
66%
71.6
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
212 140 140
212 140 140
212 95 95
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
212 95 95
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(7) Ch. ENGR. Off. 1 CD 10"Ø Hood 39%
Totals 39%
71.6
(7) Ch. ENGR. Off. 1 CD 10"Ø Hood 39%
39%
71.6
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
194 75 75
194 75 75
194 75 75
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
194 75 75
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(8) Asst. Ch. ENGR Sr. 1 CD 10"Ø Hood 57%
Totals 57%
(8) Asst. Ch. ENGR Sr. 1 CD 10"Ø Hood 88%
88%
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
131 115 115
131 115 115
131 75 75
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
131 75 75
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(9) Chief Mate Sr. 1 CD 10"Ø Hood 40%
Totals 40%
(9) Chief Mate Sr. 1 CD 10"Ø Hood 78%
78%
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
173 135 135
173 135 135
173 70 70
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
173 70 70
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(10) 3rd Asst. Engr. 1 CD 10"Ø Hood 30%
Totals 30%
86.4
68.1
(10) 3rd Asst. Engr. 1 CD 10"Ø Hood 44%
44%
56.4
68.1
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
135 60 60
135 60 60
135 40 40
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
135 40 40
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(11) 3rd Asst. Engr. 1 CD 10"Ø Hood 41%
Totals 41%
68.4
(11) 3rd Asst. Engr. 1 CD 10"Ø Hood 44%
44%
56.8
68.4
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
135 60 60
Room DB Temperature
Percent of
DesignCFM CFM CFM
135 55 55
Area Served Outlet Design Preliminary Final
ESR Dredge Yaquina
7322-3965 System Dual Duct Boxes
Inlet Size 5 inch
Full Heating Measured CFM
135 55 55
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Cooling Discharge DB Temperature
135 60
No. Type Size Ak
(12) 2nd Asst. Engr. 1 CD 10"Ø Hood 30%
Totals 30%
83.1
68.7
(12) 2nd Asst. Engr. 1 CD 10"Ø Hood 44%
44%
90.3
68.7
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
135 60 60
135 60 60
135 40 40
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
135 40 40
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(13) 1st Asst. Engr. 1 CD 10"Ø Hood 33%
Totals 33%
82.1
(13) 1st Asst. Engr. 1 CD 10"Ø Hood 52%
52%
58.3
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
135 70 70
135 70 70
135 45 45
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
135 45 45
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(14) Radio Equip. Off. 1 CD 10"Ø Hood 37%
Totals 37%
69.2
(14) Radio Equip. Off. 1 CD 10"Ø Hood 70%
70%
58.3
69.2
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
135 95 95
135 95 95
135 50 50
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
135 50 50
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(15) 3rd Mate 1 CD 10"Ø Hood 33%
Totals 33%
79.3
69.1
(15) 3rd Mate 1 CD 10"Ø Hood 81%
81%
57.2
69.1
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
135 110 110
135 110 110
135 45 45
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
135 45 45
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(16) 3rd Mate 1 CD 10"Ø Hood 63%
Totals 63%
88.9
66.5
(16) 3rd Mate 1 CD 10"Ø Hood 67%
67%
57.5
66.5
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
135 90 90
135 90 90
135 85 85
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
135 85 85
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(17) 2nd Mate 1 CD 10"Ø Hood 33%
Totals 33%
81.1
68.7
(17) 2nd Mate 1 CD 10"Ø Hood 74%
74%
56.4
68.7
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
135 100 100
135 100 100
135 45 45
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
135 45 45
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(18) 3rd Mate & Spare 1 CD 10"Ø Hood 66%
Totals 66%
81.5
68.8
(18) 3rd Mate & Spare 1 CD 10"Ø Hood 94%
94%
59.8
68.8
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
159 150 150
159 150 150
159 105 105
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
159 105 105
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(19) 3rd Mate & Spare 1 CD 10"Ø Hood 70%
Totals 70%
82.3
67.9
(19) 3rd Mate & Spare 1 CD 10"Ø Hood 76%
76%
60.1
67.9
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
151 115 115
151 115 115
151 105 105
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
151 105 105
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(20) 3rd Mate & Spare 1 CD 10"Ø Hood 60%
Totals 60%
81.4
68.2
(20) 3rd Mate & Spare 1 CD 10"Ø Hood 70%
70%
59.4
68.2
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
158 110 110
158 110 110
158 95 95
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
158 95 95
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(21) 3rd Mate & Spare 1 CD 10"Ø Hood 60%
Totals 60%
82.2
68.9
(21) 3rd Mate & Spare 1 CD 10"Ø Hood 94%
94%
59.4
68.9
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
159 150 150
159 150 150
159 95 95
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
159 95 95
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(22) Jr. ENGRs 1 CD 10"Ø Hood 81%
Totals 81%
79.9
70.2
(22) Jr. ENGRs 1 CD 10"Ø Hood 119%
119%
64.1
70.2
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
135 160 160
135 160 160
135 110 110
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
135 110 110
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(23) Cook Helper S.R. 1 CD 10"Ø Hood 44%
Totals 44%
77.7
70.3
(23) Cook Helper S.R. 1 CD 10"Ø Hood 89%
89%
70.3
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
135 120 120
135 120 120
135 60 60
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
135 60 60
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(24) Asst. Cook S.R. 1 CD 10"Ø Hood 44%
Totals 44%
76.6
65.1
(24) Asst. Cook S.R. 1 CD 10"Ø Hood 93%
93%
60.5
65.1
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
135 125 125
135 125 125
135 60 60
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
135 60 60
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(25) Steward Cook S.R. 1 CD 10"Ø Hood 67%
Totals 67%
92.6
65.7
(25) Steward Cook S.R. 1 CD 10"Ø Hood 85%
85%
57.4
65.7
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
135 115 115
135 115 115
135 90 90
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
135 90 90
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(27) Clerk S.R. 1 CD 10"Ø Hood 96%
Totals 96%
96.4
69.6
(27) Clerk S.R. 1 CD 10"Ø Hood 86%
86%
54.4
69.6
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F
Cooling Discharge DB Temperature
Room DB Temperature
125 108 108
125 108 108
125 120 120
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
125 120 120
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(28) Boatswain 1 CD 10"Ø Hood 74%
Totals 74%
88.9
68.4
(28) Boatswain 1 CD 10"Ø Hood 74%
74%
57.5
68.4
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
135 100 100
135 100 100
135 100 100
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
135 100 100
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(29) Dk. Hands S.R. 1 CD 10"Ø Hood 48%
Totals 48%
95.7
65.2
(29) Dk. Hands S.R. 1 CD 10"Ø Hood 55%
55%
65.2
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
135 74 74
135 74 74
135 65 65
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
135 65 65
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(31) Serving Line 1 CD 10"Ø Hood 97%
Totals 97%
(31) Serving Line 1 CD 10"Ø Hood 89%
89%
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
129 115 115
129 115 115
129 125 125
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
129 125 125
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 5 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(32) Officer Mess 1 CD 10"Ø Hood 131%
Totals 131%
(32) Officer Mess 1 CD 10"Ø Hood 25%
25%
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
130 33 33
130 33 33
130 170 170
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
Final
Full Heating Measured CFM
130 170 170
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 6 inch
7322-3965 System Dual Duct Boxes
No. Type Size Ak
(33) Crew Mess 1 CD 10"Ø Hood 40%
(33) Crew Mess 2 CD 10"Ø Hood 43%
Totals 41%
(33) Crew Mess 1 CD 10"Ø Hood 64%
(33) Crew Mess 2 CD 10"Ø Hood 63%
63%
Notes:
To test full cooling, the thermostat was set to 55 F.
To test full heating, the thermostat was set to 85 F.
Cooling Discharge DB Temperature
Room DB Temperature
250 160 160
497 315 315
247 155 155
Full Cooling Measured CFM
Heating Discharge DB Temperature
Room DB Temperature
497 205 205
247 105 105
Final
Full Heating Measured CFM
250 100 100
Percent of
DesignCFM CFM CFM
ESR Dredge Yaquina Inlet Size 6 inch
7322-3965 System Dual Duct Boxes
| TABB-Summary |
| MM TAB Calibration Certificates 1.19.2023 |
| Logs Draft 1 |
| Prints |