This document is a Test, Adjust and Balance (TAB) report for pneumatic control system replacements aboard the dredge Yaquina. The report details TAB work performed by MacDonald Miller Facility Solutions under job number 7322-3965. TAB procedures were conducted in accordance with NEBB standards on various dual duct box air distribution units serving over 30 zones. Test data is provided for both cooling and heating modes, including supply air flow measurements and temperatures. Measured data is noted as a percentage of design air flows. Most units measured between 30-80% of design air flow values, with some higher. The report includes instrumentation calibration records and generic schematics but no system design drawings.

The related federal contract opportunity is a solicitation from the US Army Corps of Engineers Portland District for the FY24 overhaul of the dredge Yaquina. The solicitation number is W9127N23B0014 but no further details are provided in the document.

View the file

Other files

File Type Posted
C.04_FormalAbstractOfOffers7N23B0014.pdf PDF
C.04_BidRoster7N23B0014.pdf PDF
B.08 W9127N23B0014 Yaquina Overhaul Amendment 0003.pdf PDF
B.08 Price List Amendment 0003.xlsx XLSX spreadsheet
Port Sewage Flat Tank Top fR 94 95.pdf PDF
Furuno 2827 Radars.pdf PDF
VD-TM-91721User Op.Manual.pdf PDF
Y-2232-18 Arrgt Details of Bow Thruster Instl.pdf PDF
Bottom plating within 4th strake from keel.pdf PDF
Furuno GP-170.pdf PDF
Furuno GP-170 AIS.pdf PDF
Ned-deck Marine O M Davit SCH rev E 14-12-2010.pdf PDF
Tank Top in way of Trunnion Room.pdf PDF
DT50-55 Tech Manual 80-677.pdf PDF
B.08 W9127N23B0014 Yaquina Overhaul Amendment 0002.pdf PDF
Furuno FE-700 Echo Sounder.pdf PDF
GX5500S.pdf PDF
LIPS-A004654.pdf PDF
Furuno RD-30 Repeater.pdf PDF
Y-2470-4_Installation_of_New_Hopper_Distribution_System.pdf PDF
Bottom plating in Steering Flat at port side aft of frame 88 .pdf PDF
Y-2496-3 Hyd Cylinders Ovfl Trough Hopper Doors.pdf PDF
95340 Swell Compensator Cylinder.pdf PDF
Y-2496-2 Arrgt Details Hopper Doors Operating Gear.pdf PDF
P7555 - Dredge Yaquina Launch Final.pdf PDF
19731_Longitudinal Stiffeners.pdf PDF
19731 REV 06 Sent to cust. 4.12.21.pdf PDF
Y-1032-16 Sheets 1 to 6.pdf PDF
Hundested 1-022-021126-2 MP700-CPG120 Installation Unit 6331-G1178.pdf PDF
Red Hawk FA-101 Fire Alarm System FAS Layout.pdf PDF
5241127.pdf PDF
Y-2636-1 Shaft Struts.pdf PDF
Y-2232-44 Seachests.pdf PDF
Y-2274-1 Detail 15-A Rudder Seal Ring.pdf PDF
D-1441-1.PDF PDF
Hundested 0-002-020932-2 MP700 Propeller Hoved Samling.pdf PDF
5241115 Trunnion.pdf PDF
Red Hawk FA-000 Fire Alarm System General Notes.pdf PDF
Y-3874-3 DIAGRAM Bilge and Ballast System.pdf PDF
Y-3872-4 Arrangement Firemain System.pdf PDF
Y-3874-4 Arrangement Bilge and Ballast System.pdf PDF
1788 0878 Stuffing Box female recess.pdf PDF
12V2000_P82_operating instructions.pdf PDF
Y-2636-2 Shafting Arrangement.pdf PDF
X-1441-2 Rev G.pdf PDF
Y-3872-3 DIAGRAM Firemain System.pdf PDF
Y-3872-5 DIAGRAM Sea Water Circ System.pdf PDF
Hundested 2-140-021135-1 MP700-CPG120 Flange Coupling Assembly.pdf PDF
Y-2274-1 Rudders.pdf PDF
Y-3872-6 Sea Water Argmt.pdf PDF
Show 40 more

Latest 50 of 119 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MacDonald Miller Facility Solutions Test Adjust and Balance Report

Job #: 7322-3965

March 7, 2023

Prepared For

Everett Ship Repair 2730 Federal Ave Everett, WA 98201

Prepared By Joshua Buzzard

USS Yaquina

NEBB CERTIFIED

TEST, ADJUST & BALANCE REPORT

FOR

USS YAQUINA

JOB # 7322-3965

2730 FEDERAL AVE, EVERETT, WA 98201

HVAC CONTRACTOR: MACDONALD MILLER

THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENTS AND FINAL

ADJUSTMENTSTHAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE

NEBB PROCEDURAL STANDARDS FOR TESTING, ADJUSTING AND BALANCING OF ENVIRONMENTAL

SYSTEMS. THE MEASUREMENTS SHOW, AND THE INFORMATION GIVEN, IN THIS REPORT ARE

CERTIFIED TO BE ACCURATE AND COMPLETE, AT THE TIME AND DATE INFORMATION WAS GATHERED.

ANY VARIANCES FROM DESIGN QUANTITIES, WHICH EXCEED NEBB TOLERANCES, ARE NOTED IN THE

TEST-ADJUST- BALANCE REPORT PROJECT SUMMARY.

SUBMITTED & CERTIFIED BY:

MR NOAH WALKER, NEBB SUPERVISOR REPORT DATE:

Certification Expiration Date: December 31, 2023

FIELD FOREMAN: NOAH WALKER

FIELD TECHNICIAN: JOSHUA BUZZARD

ABBREVIATIONS

AC AIR CONDITIONING UNIT HP HORSEPOWER

BDD BACK DRAFT DAMPER HP HEAT PUMP AIR CONDITIONING UNIT

BHP BRAKE HORSEPOWER HWR HEATING WATER RETURN

B.S. BIRD SCREEN HWS HEATING WATER SUPPLY

CEG CEILING EXHAUST GRILLE INAC INACCESSIBLE

CRG CEILING RETURN GRILLE LAT (DB) LEAVING AIR TEMP. (DRY BULB)

CFM CUBIC FEET PER MINUTE LAT (WB) LEAVING AIR TEMP. (WET BULB)

CHWR CHILLED WATER RETURN LD LINEAR DIFFUSER

CHWS CHILLED WATER SUPPLY LWT LEAVING WATER TEMPERATURE

CSD CEILING SUPPLY DIFFUSER MAX MAXIMUM

CWR CONDENSER WATER RETURN MIN MINIMUM

CWS CONDENSER WATER SUPPLY O WIDE OPEN DAMPER / AIR PATH

DD DIRECT DRIVE OBD OPPOSED BLADE DAMPER

DP DIFFERENTIAL PRESSURE OD OUTSIDE DIAMETER

DIFF DIFFUSER OSA OUTSIDE AIR

DMPR DAMPER RA RETURN AIR

DNA DATA NOT AVAILABLE REQ’D REQUIRED

DNL DATA NOT LISTED RH RELATIVE HUMIDITY

DNT DATA NOT TAKEN RTU ROOFTOP UNIT

DWDI DOUBLE WIDTH DOUBLE INLET SA SUPPLY AIR

EAT (DB) ENTERING AIR TEMP. (DRY BULB) SP STATIC PRESSURE

EAT (WB) ENTERING AIR TEMP. (WET BULB) SWG SIDE WALL GRILLE

EC EGGCRATE RETURN SWR SIDE WALL REGISTER

EF EXHAUST FAN SWSI SINGLE WIDTH SINGLE INLET

EG EXHAUST GRILLE T OUTLET NEAREST THERMOSTAT

ESP EXTERNAL STATIC PRESSURE TSP TOTAL STATIC PRESSURE

EWT ENTERING WATER TEMPERATURE T.P. THERMALLY PROTECTED

FPM FEET PER MINUTE T-STAT THERMOSTAT OR SENSOR

FH FUME HOOD TYP TYPICAL

GPM GALLONS PER MINUTE ∅ VOLTAGE PHASE / DUCT DIAMETER

HF HEPA FILTER V.D. VOLUME DAMPER

EXECUTIVE SUMMARY

I. GENERAL NOTES

A. TAB completion date: 02/28/2023

B. Design information was provided from original mechanical drawings, or they were field engineered.

C. TAB work was in accordance with the most current version of NEBB procedural standards for Testing

Adjusting and Balancing.

D. Methods of measurements: All measurements were taken with appropriate instruments based on the standards referenced above and comparable to the list of calibrated instruments listed in calibration report of this report.

E. Basic “not to scale” drawings with device and outlet numbering are included in Appendix of this report.

F. Motors of fans which did not list pF (power factor) or Eff (efficiency) ratings on their nameplate had it’s associated fan’s BHP (Brake Horsepower) approximated by using a nominal 0.9 pF and 0.8 Eff in the BHP calculation. Actual BHP's may vary slightly in this condition.

II. SCOPE OF WORK

A. Various pneumatic piston actuators were replaced, along with pneumatic thermostats, throughout the ship. All work was the test and balance each piece of equipment which was replaced.

III. DESCRIPTION OF THE SYSTEMS BALANCED

A. For each unit a pneumatic actuator moves a damper which modulates between cold deck ductwork and hot deck ductwork. This piston’s control signal comes from a thermostat located in each zone. There are no balancing dampers present on any of the pneumatic boxes.

IV. TAB PROCEDURES SUMMARIZED – AIR SYSTEM TESTING PROCEDURES

A. The zone was placed into full cooling by turning the thermostat to the lowest setting, which was 55 F.

B. The discharge air volume and temperature were read and recorded.

C. The unit was placed into full heating by turning the thermostat to the highest setting, which was 85 F.

D. The discharge air volume and temperature were read and recorded.

V. OTHER MISCELLANEOUS NOTES

A. Because the scope was limited to testing of the replaced elements of the system and there were components on the system which were not worked on, compounded by the issue of not dampers being found to further balance the system, the numbers recorded were marked as final. Any low readings were left as is because the balance of the entire system was out of scope and no action could be taken.

Instrument Calibration Record Calibration

DateFunction Range Accuracy

∆ Pressure

Measurement

0.4 to 75

PSI

±2% or Read

0.5 PSI

0.01

PSI

Model # Alnor HM675 11/1/2022

Serial # 7733099

±0.5% of

Reading or

2.0⁰F

Z406825

Extech - 461995Model #

Serial #

Temperature Measurement

Resolution Model & Serial Numbers

Instrument

Rotational Measurement

Tachometer 60-5000

RPM

±2% of Read

± 2 RPM

RPM

10/17/2022

6/22/2022

6/27/2022

6/27/2022

6/27/2022

Fluke 52II Series

50092988MV

Fluke 80PK-25

2098706

Fluke 80PK-25

2098706

Electrical Measurement

Volts

Amperes

1-600

VAC

0.1 -100

Amps

1 Volt

0.1 Ampers

Model #

OMEGA 794

NA

0.1⁰F

Model #

Serial #

Model #

Serial #

Model #

Serial #

Model #

Serial #

Thermometer

Air

Probe

Immersion

Probe

Contact

Probe

0⁰F to

200⁰F

6/24/2022

6/24/2022

±2% of

Reading or

±5 Digits

Air Pressure & Velocity

Pressure

Velocity

(Pitot Tube)

±2% of Read

±0.001" w.g.

±0.001 w.g.

≤1" w.g.

±5% of Read

±7 FPM

1.0 FPM

Serial #

Model #

Serial #

Fluke 378 FC

56550098

Fluke 378 FC

56550098

Serial #

Model #

Serial #

Velocity

(Hot Wire)

Digital Direct

Reading Hood

0 - 10.0 in W.G.

100 to 3500

FPM

50 to 6000

FPM

100 to 2000

CFM

Model #

Serial #

4/28/2022

4/28/2022

11/30/2022

12/19/2022 50611991 / 1022

Humidity Measurement

Model #

Serial #

Shortridge 860C

M13055

Shortridge 860C

M13055

TSI 966

P22490016

Testo 420

±3% of Read

±3 FPM

1.0 FPM

±5% of Read

±7 CFM

1.0 CFM

Model #

Serial #

Model #

11/1/2022 Serial # 7733099

Date Updated 1/18/2023

TSI 966

P22490016 11/30/2022

Hydronic Measurement Pressure

Measurement

0.4 to 200

PSI

±2% or Read

1 PSI

0.1

PSI

Model # Alnor HM675

Humidity 10 to 90%

RH

±3% RH 1.00%

Calibration

Date

Instrument Calibration

Rotational Measurement Extech - 461895

Tachometer 60-5000

RPM

±2% of Read

±2 RPM

RPM

6/23/2022

Z341111

Instrument

Function

Minimum

Range

Minimum

Accuracy

Minimum

Resolution Instrument Information

Temperature Measurement

Thermometer

Air Probe

Immersion Probe

0⁰F to

200⁰F

±5% of

Reading or

2.0⁰F

0.1⁰F

Fluke 52 Series II

50092988MV

Fluke 80PK-25

NA

Fluke 80PK-25

NA

OMEGA 792

Contact Probe

NA

6/22/2022

6/27/2022

6/27/2022

6/27/2022

±2% of

Reading or

±5 Digits

Electrical Measurement

Volts

Amperes

6/24/2022

6/24/2022

1 - 600

VAC

0.1 - 100

Amps

1 Volt

0.1 Ampes

Fluke 378 FC

56550098

Fluke 378 FC

56550098

Air Pressure & Velocity

Air

Pressure

Air Velocity

Pitot Tube

Air

Velocity

0 to 10.0 in w.g.

±2% or read

±0.001" wg

50 to 3500

FPM

±5% of read

±7FPM

50 t0 6000

FPM

±3% of read

±3 FPM

4/28/2022

4/28/2022

9/22/2021

50 to 6000

FPM

±1% of read

±4 FPM

±0.01" wg

≤1 " wg

1.0 FPM

1.0 FPM

1.0 FPM

1.0%

TSI 9545-A

9545A1904010

9/22/2021

Shortridge 860C

M13055

Shortridge 860C

M13055

TSI 9545-A

9545A1904010

TSI 5725

T57251942002

Air Velocity

RVA

9/22/2021

Hydronic Measurement

Hydronic

Differential

0.4 to 200

PSI

±2% or read

1 PSI

0.1

PSI

4/6/2022

ALNOR HM685

72203018

Humidity Measurement

Humidity 10 to 90%

RH

±3% RH

Manufacturer:

ID / Asset Number:

Function / Range Nominal

Value As Found Result As Left Result Min Max Units Uncertainty

0.5 to 1,000 rpm 600.0 599.9 Pass Same Pass 599.6 600.4 rpm 0.060 rpm

1,000 to 99,999 rpm 18000 17998 Pass Same Pass 17990 18010 rpm 0.58 rpm

42000 41998 Pass Same Pass 41978 42022 rpm 0.59 rpm

60000 59995 Pass Same Pass 59969 60031 rpm 0.60 rpm

90000 89996 Pass Same Pass 89954 90046 rpm 0.63 rpm

Decision Rule 1 - Accredited Calibration Datasheets may contain measurements that are not covered by the Scope of Accreditation. These measurements are indicated by a pound sign(#).

Measurement Uncertainty IS NOT taken into account for determining PASS or FAIL.

********END OF MEASUREMENT REPORT********

Non-Contact RPM Contact RPM

1047875 Calibration Date: 6/22/2022

EXTECH Model Number: 461995

Certificate Number: 17381589

Data Page 1 of 1

Project

Job Number

No. Type Size Ak

(3) Asst. Master S.R. 1 CD 10"Ø Hood 28%

Totals 28%

(3) Asst. Master S.R. 1 CD 10"Ø Hood 72%

72%

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

145 33 105

145 33 105

145 313 40

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

145 313 40

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

Area Served Outlet Design Preliminary

No. Type Size Ak

(4) Master S.R. 1 CD 10"Ø Hood 24%

Totals 24%

(4) Master S.R. 1 CD 10"Ø Hood 69%

69%

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

166 33 115

166 33 115

166 313 40

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

166 313 40

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(5) Master Off. 1 CD 10"Ø Hood 56%

Totals 56%

(5) Master Off. 1 CD 10"Ø Hood 75%

75%

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

153 33 115

153 33 115

153 105 85

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

153 105 85

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(6) Ch. ENGR S.R. 1 CD 10"Ø Hood 45%

Totals 45%

71.6

(6) Ch. ENGR S.R. 1 CD 10"Ø Hood 66%

66%

71.6

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

212 140 140

212 140 140

212 95 95

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

212 95 95

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(7) Ch. ENGR. Off. 1 CD 10"Ø Hood 39%

Totals 39%

71.6

(7) Ch. ENGR. Off. 1 CD 10"Ø Hood 39%

39%

71.6

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

194 75 75

194 75 75

194 75 75

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

194 75 75

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(8) Asst. Ch. ENGR Sr. 1 CD 10"Ø Hood 57%

Totals 57%

(8) Asst. Ch. ENGR Sr. 1 CD 10"Ø Hood 88%

88%

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

131 115 115

131 115 115

131 75 75

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

131 75 75

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(9) Chief Mate Sr. 1 CD 10"Ø Hood 40%

Totals 40%

(9) Chief Mate Sr. 1 CD 10"Ø Hood 78%

78%

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

173 135 135

173 135 135

173 70 70

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

173 70 70

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(10) 3rd Asst. Engr. 1 CD 10"Ø Hood 30%

Totals 30%

86.4

68.1

(10) 3rd Asst. Engr. 1 CD 10"Ø Hood 44%

44%

56.4

68.1

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

135 60 60

135 60 60

135 40 40

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

135 40 40

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(11) 3rd Asst. Engr. 1 CD 10"Ø Hood 41%

Totals 41%

68.4

(11) 3rd Asst. Engr. 1 CD 10"Ø Hood 44%

44%

56.8

68.4

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

135 60 60

Room DB Temperature

Percent of

DesignCFM CFM CFM

135 55 55

Area Served Outlet Design Preliminary Final

ESR Dredge Yaquina

7322-3965 System Dual Duct Boxes

Inlet Size 5 inch

Full Heating Measured CFM

135 55 55

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Cooling Discharge DB Temperature

135 60

No. Type Size Ak

(12) 2nd Asst. Engr. 1 CD 10"Ø Hood 30%

Totals 30%

83.1

68.7

(12) 2nd Asst. Engr. 1 CD 10"Ø Hood 44%

44%

90.3

68.7

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

135 60 60

135 60 60

135 40 40

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

135 40 40

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(13) 1st Asst. Engr. 1 CD 10"Ø Hood 33%

Totals 33%

82.1

(13) 1st Asst. Engr. 1 CD 10"Ø Hood 52%

52%

58.3

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

135 70 70

135 70 70

135 45 45

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

135 45 45

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(14) Radio Equip. Off. 1 CD 10"Ø Hood 37%

Totals 37%

69.2

(14) Radio Equip. Off. 1 CD 10"Ø Hood 70%

70%

58.3

69.2

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

135 95 95

135 95 95

135 50 50

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

135 50 50

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(15) 3rd Mate 1 CD 10"Ø Hood 33%

Totals 33%

79.3

69.1

(15) 3rd Mate 1 CD 10"Ø Hood 81%

81%

57.2

69.1

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

135 110 110

135 110 110

135 45 45

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

135 45 45

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(16) 3rd Mate 1 CD 10"Ø Hood 63%

Totals 63%

88.9

66.5

(16) 3rd Mate 1 CD 10"Ø Hood 67%

67%

57.5

66.5

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

135 90 90

135 90 90

135 85 85

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

135 85 85

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(17) 2nd Mate 1 CD 10"Ø Hood 33%

Totals 33%

81.1

68.7

(17) 2nd Mate 1 CD 10"Ø Hood 74%

74%

56.4

68.7

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

135 100 100

135 100 100

135 45 45

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

135 45 45

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(18) 3rd Mate & Spare 1 CD 10"Ø Hood 66%

Totals 66%

81.5

68.8

(18) 3rd Mate & Spare 1 CD 10"Ø Hood 94%

94%

59.8

68.8

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

159 150 150

159 150 150

159 105 105

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

159 105 105

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(19) 3rd Mate & Spare 1 CD 10"Ø Hood 70%

Totals 70%

82.3

67.9

(19) 3rd Mate & Spare 1 CD 10"Ø Hood 76%

76%

60.1

67.9

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

151 115 115

151 115 115

151 105 105

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

151 105 105

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(20) 3rd Mate & Spare 1 CD 10"Ø Hood 60%

Totals 60%

81.4

68.2

(20) 3rd Mate & Spare 1 CD 10"Ø Hood 70%

70%

59.4

68.2

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

158 110 110

158 110 110

158 95 95

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

158 95 95

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(21) 3rd Mate & Spare 1 CD 10"Ø Hood 60%

Totals 60%

82.2

68.9

(21) 3rd Mate & Spare 1 CD 10"Ø Hood 94%

94%

59.4

68.9

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

159 150 150

159 150 150

159 95 95

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

159 95 95

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(22) Jr. ENGRs 1 CD 10"Ø Hood 81%

Totals 81%

79.9

70.2

(22) Jr. ENGRs 1 CD 10"Ø Hood 119%

119%

64.1

70.2

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

135 160 160

135 160 160

135 110 110

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

135 110 110

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(23) Cook Helper S.R. 1 CD 10"Ø Hood 44%

Totals 44%

77.7

70.3

(23) Cook Helper S.R. 1 CD 10"Ø Hood 89%

89%

70.3

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

135 120 120

135 120 120

135 60 60

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

135 60 60

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(24) Asst. Cook S.R. 1 CD 10"Ø Hood 44%

Totals 44%

76.6

65.1

(24) Asst. Cook S.R. 1 CD 10"Ø Hood 93%

93%

60.5

65.1

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

135 125 125

135 125 125

135 60 60

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

135 60 60

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(25) Steward Cook S.R. 1 CD 10"Ø Hood 67%

Totals 67%

92.6

65.7

(25) Steward Cook S.R. 1 CD 10"Ø Hood 85%

85%

57.4

65.7

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

135 115 115

135 115 115

135 90 90

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

135 90 90

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(27) Clerk S.R. 1 CD 10"Ø Hood 96%

Totals 96%

96.4

69.6

(27) Clerk S.R. 1 CD 10"Ø Hood 86%

86%

54.4

69.6

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F

Cooling Discharge DB Temperature

Room DB Temperature

125 108 108

125 108 108

125 120 120

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

125 120 120

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(28) Boatswain 1 CD 10"Ø Hood 74%

Totals 74%

88.9

68.4

(28) Boatswain 1 CD 10"Ø Hood 74%

74%

57.5

68.4

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

135 100 100

135 100 100

135 100 100

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

135 100 100

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(29) Dk. Hands S.R. 1 CD 10"Ø Hood 48%

Totals 48%

95.7

65.2

(29) Dk. Hands S.R. 1 CD 10"Ø Hood 55%

55%

65.2

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

135 74 74

135 74 74

135 65 65

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

135 65 65

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(31) Serving Line 1 CD 10"Ø Hood 97%

Totals 97%

(31) Serving Line 1 CD 10"Ø Hood 89%

89%

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

129 115 115

129 115 115

129 125 125

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

129 125 125

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 5 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(32) Officer Mess 1 CD 10"Ø Hood 131%

Totals 131%

(32) Officer Mess 1 CD 10"Ø Hood 25%

25%

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

130 33 33

130 33 33

130 170 170

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

Final

Full Heating Measured CFM

130 170 170

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 6 inch

7322-3965 System Dual Duct Boxes

No. Type Size Ak

(33) Crew Mess 1 CD 10"Ø Hood 40%

(33) Crew Mess 2 CD 10"Ø Hood 43%

Totals 41%

(33) Crew Mess 1 CD 10"Ø Hood 64%

(33) Crew Mess 2 CD 10"Ø Hood 63%

63%

Notes:

To test full cooling, the thermostat was set to 55 F.

To test full heating, the thermostat was set to 85 F.

Cooling Discharge DB Temperature

Room DB Temperature

250 160 160

497 315 315

247 155 155

Full Cooling Measured CFM

Heating Discharge DB Temperature

Room DB Temperature

497 205 205

247 105 105

Final

Full Heating Measured CFM

250 100 100

Percent of

DesignCFM CFM CFM

ESR Dredge Yaquina Inlet Size 6 inch

7322-3965 System Dual Duct Boxes

TABB-Summary
MM TAB Calibration Certificates 1.19.2023
Logs Draft 1