FY 11 General Instruction Building (GIB) Presidio of Monterey 1624

07 81 23 -1 AM-05

SECTION TABLE OF CONTENTS

DIVISION 07 – THERMAL AND MOISTURE PROTECTION

SECTION 07 81 23

INTUMESCENT MASTIC FIREPROOFING

PART 1: GENERAL

1.1 WORK INCLUDED

1.2 RELATED WORK SPECIFIED ELSEWHERE

1.3 REFERENCES, Current Editions

1.4 QUALITY ASSURANCE

1.5 SUBMITTAL

1.6 SEQUENCING/SCHEDULING

1.7 PRODUCT DELIVERY, STORAGE AND HANDLING

1.8 PROJECT/SITE CONDITIONS

1.9 WARRANTY

PART 2: PRODUCTS

2.1 GENERAL:

2.2 ACCEPTABLE MATERIALS

PART 3: EXECUTION

3.1 PROTECTION

3.2 SURFACE PREPARATION

3.3 APPLICATION

3.4 REPAIRS AND CLEANING

3.5 INSPECTION

07 81 23 -2 AM-05

SECTION 07 81 23

INTUMESCENT MASTIC FIREPROOFING

PART 1: GENERAL

1.1 WORK INCLUDED:

A. This Construction Specification covers the materials, labor, equipment and application requirements for the intumescent spray-on fireproofing for interior unexposed structural wide flange columns, beams and related exposed structural steel as shown on the DRAWINGS or where specified herein, and in accordance with all applicable requirements of the Contract Documents for a one (1) hour fire rating.

B. CODES: The material and installation shall conform to the applicable building code requirements of all authorities having jurisdiction and insurance rating organizations.

C. QUESTIONS regarding this construction specification or discrepancies and conflicts between this Construction Specification, DRAWINGS and Reference Documents shall be referred to the CONTRACTING OFFICER for resolution.

D. EXCEPTIONS: No exceptions shall be taken from this specification without prior written approval of the CONTRACTING OFFICER.

E. SCOPE: Fireproofing includes purchasing, receiving and proper storage of the fireproofing and associated fireproofing materials, surface preparation, cleaning of previously primed surfaces to be fireproofed and checking those surfaces for primer compatibility, and if incompatible making the correction for an acceptable fireproofing surface, priming of steel surfaces to be fireproofed, touch-up where coatings are damaged, applying/installing fireproofing materials, applying an color topcoat to the fireproofing, repairs of the fireproofing, clean-up, inspection and testing of the fireproofing as indicated on the DRAWINGS and in accordance with this Specification.

G. FIREPROOFING LOCATION: The specific requirements for each surface to be fireproofed shall be as shown on the DRAWINGS and/or this Specification.

F. This Construction Specification covers a fire resistance rating of one

(1) hour based on test conducted by Underwriters Laboratories, Inc.

(ULI) UL 263 (ASTM-E-119 + ICBO ES specified Environmental Testing).

Ratings are based on fire test conducted in accordance with the current Uniform Building Code Standards, Section 7.

1.2 RELATED WORK SPECIFIED ELSEWHERE:

A. PRIMER COMPATIBILITY: Primer applied to the structural steel shall be compatible with the fireproofing material specified herein. Appropriate and complete product data for the primer shall be submitted by the Contracting Officer to the Fireproofing Manufacture to ascertain compatibility prior to application of any such primer.

B. Section 01 33 00 - Administrative Requirements.

07 81 23 -3 AM-05

C. Section 01 33 00 - Submittals.

D. Section 01 45 00.00 10 - Quality Control.

E. Section 01 33 00, paragraph 1.6 - Substitutions.

F. Section 05 12 00 - Structural Steel with reference to primer that receives fireproofing.

G. Section 09 90 00 – Paints and Coatings with reference to priming and finish painting.

1.3 REFERENCES, Current Editions:

A. ASTM Standards:

1. ASTM-E-119: Standard Methods of Fire Tests of Building Construction Materials.

2. ASTM-D-256-90b: Impact Resistance Test, min. 0-77 Ft-LB/in. of notch.

3. ASTM-E-84a: Standard Test Method for Surface Burning Characteristics of Building Materials, Flame Spread 02, Smoke Density 05.

4. ASTM-D-4541-85: Standard Test Method for Adhesion, 30 PSI.

5. ASTM-D-790-91: Standard Test Method for Flexural Strength, and

Standard Test Method for Modulus of Elasticity.

6. ASTM-D-1044-90: Standard Test Method for Taber Abrasion, 0 grams @

500 gram load, 100 cycles.

7. ASTM-D-952-90: Standard Test Method for Bond Strength.

8. ASTM-E-605: Thickness & Density of Sprayed fire-Resistive Material

Applied to Structural Members.

9. ASTM-E-84, Smoke Development and Flame Spread, Class “1” rating.

B. Other Material Standards, Current Edition:

1. Hardness: Shore “D”, 45 -50.

2. ASBESTOS CONTENT: NONE.

3. Dry Applied Density, 85 PCF.

4. Current Underwriters Laboratories, Inc. (UL) Fire Resistance

Directory, UL263 + ICBO ES specified Environmental Testing.

5. Steel Structures Painting Council (SSPC) Surface Preparation

Standards.

6. Current Uniform Building Code and Standard, Section 7.

7. MATERIAL Manufacturer’s published information, including bulletin entitled “Field Procedure for Density and Film Thickness” and “Fireproofing Application Manual & Field Guide”.

8. ICBO Evaluation Service, Inc. “Acceptance Criteria for Spray-Applied Fire-Protection Materials”, July 1993.

9. Coatings must comply with local regulatory requirements for “VOC Area Source” Rules, > 350 grams/liter.

1.4 QUALITY ASSURANCE:

A. REGULATORY REQUIREMENTS: Comply with applicable codes and regulations of governmental agencies having jurisdiction including those having jurisdiction over noise/energy conservation and fire control. Where requirements of applicable codes, regulations and standards conflict with the requirements of this Specification, user is to comply with the more stringent provisions.

07 81 23 -4 AM-05

B. NO ASBESTOS FIBERS ARE PERMITTED. Materials for which physical characteristics have been stipulated shall have such characteristics independently confirmed by laboratory tests employing industry recognized procedures, INCLUDING ASBESTOS CONTENT.

1.4 QUALITY ASSURANCE, CON’T:

C. To qualify for acceptance, an independent testing laboratory must demonstrate to the CONTRACTING OFFICER, based on evaluation of laboratory submitted criteria conforming to ASTM-E-699, that it has the experience and capability to conduct satisfactorily the testing indicated without delaying the progress of the work.

D. APPLICATION CONTRACTOR REQUIREMENTS:

1. SELLING MATERIAL: A MANUFACTURER’S willingness to sell its sprayed fire-resistive materials to a CONTRACTOR or an installer engaged by the CONTRACTOR does not in itself confer qualifications on the BUYER.

2. MANUFACTURER TRAINING: The FIREPROOFING MATERIAL MANUFACTURER shall qualify the APPLICATION CONTRACTOR and the APPLICATION CONTRACTOR shall submit to the CONTRACTING OFFICER written documentation that the APPLICATION CONTRACTOR has attended and successfully completed the required FIREPROOFING MATERIAL MANUFACTURER’S training program.

3. MANUFACTURER TESTIMONIAL: The APPLICATION CONTRACTOR shall provide a letter from the intumescent manufacturer approving the installer for this project size, scope, schedule and experience required.

4. PERSONNEL TESTIMONIAL: The APPLICATION CONTRACTOR shall demonstrate that the Contractor’s application personnel have a minimum of five

(5) years successful experience installing the products specified in this section, similar in design and extent to those indicated for this project.

5. PROJECT TESTIMONIAL: The APPLICATION CONTRACTOR shall submit to the CONTRACTING OFFICER written documentation the names of previous comparable type and size applications successfully completed on time, identified by project name, location, date, reference name and contact phone.

E. DISCREPANCIES: Fireproofing shall be installed in strict accordance with the Manufacturer’s latest written application instructions.

Discrepancies between the instructions and this specification, DRAWINGS, or site conditions are to be resolved in writing by the CONTRACTING

OFFICER.

1.5 SUBMITTAL

A. TYPE OF FIREPROOFING: The APPLICATION CONTRACTOR shall state in their bid which specific fireproofing material their quotation is based upon and shall submit Manufacturer’s specifications, technical data sheets and copy of dated valid “Certificate of Approval” to apply the intumescent fireproofing issued by the MATERIAL MANUFACTURER.

B. TABLE OF THICKNESS: The APPLICATION CONTRACTOR shall submit a table of dry film thickness measurements approved by the MATERIAL MANUFACTURER for all the projects structural steel which is to receiver intumescent fireproofing. Included in the table shall be W/D values used for wide flange, angle iron and channel members and A/P values used for pipe and tube steel members along with the collaborating Underwriters Laboratories, Inc. “listing” datum.

C. PRIMER COMPATIBILITY: The APPLICATION CONTRACTOR shall submit certification that the primers applied to the steel in the shop or field

07 81 23 -5 AM-05

are compatible with the sprayed-on intumescent fireproofing and will not impair the fireproofing performance under fire exposure for applications indicated as provided by UL 263.

1.5 SUBMITTAL, CON’T:

D. SAMPLES: Three (3) product samples, with achievable field finish must accompany the selected APPLICATION CONTRACTOR’S submittal. The sample shall be identified as to the name and product number. If approved, one

(1) sample will be returned to the APPLICATION CONTRACTOR marked “Approved”, the GENERAL CONTRACTOR as a datum will hold the second, and the CONTRACTING OFFICER will hold the third.

E. SAMPLE APPLICATION: Before proceeding with the application, the

APPLICATION CONTRACTOR shall prepare a sample installation at the site with one of the steel members which are representative of the average conditions and contours of the work. Finish, thickness, and System Engineering requirements shall be reviewed with the GENERAL CONTRACTOR and the CONTRACTING OFFICER before and after the sample preparation.

Written acknowledgment by the CONTRACTING OFFICER is needed before the APPLICATION CONTRACTOR can proceed. The APPLICATION CONTRACTOR shall adjust the method of application in whatever ways are necessary to achieve the desired visual effect, as per the submittal and within the inherent limitations of the specified materials and fire engineering systems.

F. TEST DATA: Independent laboratory test results shall be submitted for all performance criteria as specified.

G. RESUBMITTALS: Should additional re-submittals be required, APPLICATION

CONTRACTOR shall reimburse GOVERNMENT for time spent in processing additional re-submittals.

H. PRODUCT DATA

Local/Regional Materials

Submit documentation indicating distance between manufacturing facility and the project site. Indicate distance of raw material origin from the project site. Indicate relative dollar value of local/regional materials to total dollar value of products included in project.

1. 6 SEQUENCING/SCHEDULING:

A. SCHEDULING: The APPLICATION CONTRACTOR shall cooperate in the coordination and scheduling of fireproofing work to avoid delays in job progress.

B. INSPECTION: The GENERAL CONTRACTOR shall provide time for inspection, testing and subsequent correction of defective fireproofing.

1.7 PRODUCT DELIVERY, STORAGE AND HANDLING:

A. Intumescent Fireproofing materials shall be delivered in original unopened containers with the Manufacturer’s labels identifying product, batch numbers and ULI label. Fireproofing material storage conditions

07 81 23 -6 AM-05

shall be in accordance with the Fireproofing Manufacturer’s recommendations that include storing products to protect the material from extremes of heat, sunlight, moisture and freezing. Damaged containers found unsuitable for use will be rejected and removed from the job site. Use materials with limited shelf life within the period indicated. Remove from the project site and discard any materials whose shelf life has expired.

1.8 PROJECT/SITE CONDITIONS:

A. APPLICATION TEMPERATURE: Fireproofing shall not be applied when ambient or surface temperature is lower than thirty two (32) degrees Fahrenheit or when surface temperature is less than five (5) degrees Fahrenheit above the dew point.

B. VENTILATION: The APPLICATION CONTRACTOR shall provide ventilation to allow for proper drying of the fireproofing during and subsequent to its application and to ensure a non-toxic, unpolluted and safe working area.

In poorly ventilated areas lacking natural ventilation, use forced air ventilation to cause the material to properly dry within thirty (30) days after application.

1.8 PROJECT/SITE CONDITIONS:

C. PREINSTALLATION CONFERENCE: Attendees should include but not limited to, Project Superintendent (presides over meeting and is responsible for minutes); APPLICATION CONTRACTOR; Manufacturers technical representative, Testing/Inspection agency; GOVERNMENT representative and others directly affecting or affected by the work. Agenda should include but not limited to, Access to work and conditions of proper installation; conditions of installations, such as substrates, existing and surrounding conditions, and environmental conditions; conditions detrimental to installation; preparation procedures, including protection of adjacent work; verify installer’s receipt and understanding of installation instructions; review submittals, installation procedures and sequence; review coordination with other work (i.e. attachments to structural members); evaluate delivery schedule and Construction Progress Schedule; observe sample installation and required protection procedures.

1.9 WARRANTY:

A. The APPLICATION CONTRACTOR shall submit a written guarantee stating that all work shall be guaranteed against any defects in materials and/or workmanship for a period of one (1) year from the date of “Notice of Completion”. The fireproofing shall remain free from cracking, checking, dusting, flaking, spalling, separation and blistering.

Defective work that develops during guarantee period shall be repaired and/or replaced at no additional cost to the OWNER. Not covered under the Warranty are failures due to damage by occupants and OWNER’S maintenance personnel, other construction trades and other causes not reasonably foreseeable under construction or normal use.

B. APPLICATION CONTRACTOR must submit their intumescent fireproofing QA/QC plan for approved with their bid.

PART 2: PRODUCTS

2.1 GENERAL:

07 81 23 -7 AM-05

A. MATERIALS: Materials shall be the products of one (1) MANUFACTURER and shall be the ones upon which the design is based.

B. SUBSTITUTIONS: A request for “Substitution” shall include documentation which supports the physical properties as outlined in “References”, section 1.03, of this Specification and the APPLICATION CONTRACTOR shall have written acknowledgment by both the GENERAL CONTRACTOR and the

CONTRACTING OFFICER.

C. TESTING: The fireproofing materials shall have been tested and reported by UL in accordance with the provisions of UL 263 and the “current” Uniform Building Code Standard 7-1.

D. ASBESTOS: Sprayed fireproofing materials shall be free of all forms of asbestos and asbestos contamination, including actinolite, amosite, anthdophylite, chyrsotile, crocidolite and tremolite. MATERIAL MANUFACTURER shall provide certification of such properties upon request by CONTRACTING OFFICER.

2.2 ACCEPTABLE MATERIALS:

A. PRIMER: As per manufacturer’s recommendation.

C. FIREPROOFING: As per manufacturer’s recommendation The intumescent fireproofing shall be applied to conform to the DRAWINGS, this Specification and the following table:

D.

Member W/D UL Listing Dry Film Thickness

W12x40 0.737 X-625 62 mils W12x53 0.849 X-625 54 mils W14x28 0.560 X-625 82 mils W14x68 1.025 X-625 45 mils W14x74 1.109 X-625 41 mils W14x90 1.068 X-625 43 mils W14x120 1.404 X-625 33 mils W14x145 1.626 X-625 28 mils W14x159 1.717 X-625 26 mils W14x176 1.984 X-625 23 mils W27x368 3.149 X-625 14 mils

C12x20.7 Welded to W16x26

0.637 X-625 72 mils

PART 3: EXECUTION:

3.1 PROTECTION:

A. APPLICATION PROTECTION: APPLICATION CONTRACTOR shall provide protection, by masking or covering, all structures, equipment, decks and areas not to receive fireproofing that are in the vicinity of the application area.

B. VENTILATION: Close off and seal duct work in areas where fireproofing is being applied.

C. FINISH PROTECTION: The APPLICATION CONTRACTOR shall advise the GENERAL

CONTRACTOR of protection requirements which will ensure that the

07 81 23 -8 AM-05

fireproofing will be without damage or deterioration until just before occupancy of the building.

3.2 SURFACE PREPARATION:

A. EXAMINATION OF SUBSTRATE: The application of the sprayed intumescent fireproofing shall not commence until certification in writing has been received by the GENERAL CONTRACTOR indicating that the surface to receive sprayed intumescent fireproofing has been inspected by the APPLICATION CONTRACTOR and are acceptable to receive the intumescent fireproofing. The APPLICATION CONTRACTOR shall further notify the GENERAL CONTRACTOR in writing, of all discrepancies and/or damage prior to the intumescent fireproofing application.

B. SURFACE PREPARATION FOR ALL UNPRIMED STEEL MEMBERS TO RECEIVE

INTUMESCENT FIREPROOFING:

1. SHOP: The surface reparation shall be a Commercial Blast Cleaning, SSPC-SP-6 (Steel Structures Painting Council) with average peak to valley profile of 1.0 mil.

2. FIELD: The surface preparation shall be and SSPC-SP-1 (Solvent Wipe) then either an SSPC-SP-2 (Hand Tool Cleaning) or SSPC-SP-3 (Power Tool Cleaning).

C. PRIMER FOR ALL UNPRIMED STEEL MEMBERS: The primer shall be corrosion resistant metal primer, applied at 2 - 3 mils dry film thickness.

BOLTED CONNECTIONS shall have the primer “cut back” to three (3”) inches minimum. WELDED CONNECTIONS shall have primer “cut back” to twelve (12”) inches minimum.

D. DAMAGED PRIMER: All areas of damaged primer shall be repaired by the

APPLICATION CONTRACTOR prior to applying fireproofing material as per the fireproofing Manufacturer’s recommendations and as approved by the

CONTRACTING OFFICER.

E. GALVANIZED & NON-FERROUS METAL SURFACES: Clean non-ferrous and galvanized surfaces in accordance with the Manufacturer’s instructions for the type of substrate and application required.

3.3 APPLICATION:

A. MANUFACTURER’S INSTRUCTIONS: Equipment, mixing and application shall be in accordance with the intumescent fireproofing Manufacturer’s written application instructions.

B. SURFACE DRYNESS: At the time of application all surfaces shall be completely dry and free of moisture and other contaminants.

C. ATTACHMENTS: Clips, hangers, supports, sleeves and other attachments to the substrate are to be placed by others, prior to the application of the sprayed intumescent fireproofing.

D. FINISH: The entire surface to be fireproofed shall be a monolithic blanket of uniform hardness, texture and density, applied to its full ULI thickness over the entire required substrate. Texture and finish shall be as approved by the CONTRACTING OFFICER during “sample application”. “Base Line Sample” held by CONTRACTING OFFICER showing representative finish to be bid to.

07 81 23 -9 AM-05

E. OPTIONAL COLOR TOPCOAT: For color other that the standard white or for additional chemical/UV protection an optional color topcoat can be applied. Topcoat must be compatible with intumescent fireproofing and meet ASTM-E-84, Class “1”. Color selected by CONTRACTING OFFICER.

3.4 REPAIRS AND CLEANING:

A. TOUCH-UP: At the completion of the fireproofing installation, the finish shall be touched-up and restored where damaged.

B. PATCHING: As other trades complete installations of their work, fireproofing which has been cut away to facilitate such installations shall be patched so as to maintain complete coverage of full thickness on appropriate substrate. Work requiring patching shall not be covered over before repairs have been completed.

C. PROTECTION: The APPLICATION CONTRACTOR shall advise the GENERAL

CONTRACTOR of protection requirements which will ensure that the fireproofing will be without damage or deterioration until just before occupancy of the building.

D. CLEAN-UP: After the completion of the work of this section in an area, equipment shall be removed from that area and all surfaces not to be sprayed with fireproofing shall be cleaned of all deposits of sprayed fireproofing material. The APPLICATION CONTRACTOR shall keep all floor areas clean by utilization of traps, vis-queen (4 mil minimum thickness) or other appropriate means during the fireproofing application.

E. WORKMANSHIP: Materials and workmanship not in accordance with the specification, DRAWINGS or the intumescent fireproofing manufacturer shall be replaced by the APPLICATION CONTRACTOR to the proper requirements.

3.5 INSPECTION:

A. INSPECTION: The GENERAL CONTRACTOR shall ensure that structure and surfaces to which sprayed fireproofing is applied is not enclosed and is open to view until inspected and accepted.

B. BUILDING CODES: Where the applicable building codes govern testing frequency, the applicable building code shall be consulted for exact requirements.

C. INSPECTION OF VOIDS: It shall be determined that the voids created by the intersection fluted deck and the structural members have been protected as required by the fire-resistance-rating design criteria.

Any observed deficiencies shall be immediately reported to the intumescent fireproofing APPLICATOR for correction. Application initially found to be deficient shall be corrected and inspected.

D. TIMING OF MEASUREMENTS: Thickness measurements shall be taken after the intumescent fireproofing has stabilized.

E. THICKNESS MAXIMUM: There are no thickness maximums.

F. THICKNESS MINIMUM: No individual thickness determination shall be less than 80 percent of the thickness specified in the fire-resistance-rating design criteria.

07 81 23 -10 AM-05

G. FAILURE: If an individual thickness determination or the average calculated thickness in the randomly selected area does not meet the design criteria for minimum individual thickness or thickness average, then only that specific member shall fail. The remaining structural members in other areas shall not be deemed to have failed solely because the tested component has failed. If the structural member fails to meet the design criteria for thickness average or minimum individual thickness, it shall be corrected and re-tested and another similar component in another randomly selected area on the same elevation shall also be tested.

H. TESTS FOR BEAMS AND COLUMNS: A series of thickness determinations shall be conducted in a specific pattern as detailed herein. W-Shape Beams:

Thickness determinations shall be made at nine locations around the beam, at each end of a 12-inch length and at the mid-point. W-Shape Columns: Thickness determinations shall be made at 12 locations around the column, at each end of a 12-inch length and at the mid point.

I. THICKNESS MEASUREMENT AVERAGING: A single average thickness shall be calculated, as note in paragraph I. above, from each series of individual thickness determinations on the structural members tested.

The calculated average thickness shall be equal to or greater than the thickness specified in the fire-resistance design criteria. The single calculated average measurement shall be reported in mils.

J. THICKNESS CORRECTION: Thickness shall be corrected by applying additional intumescent fireproofing at any location where the calculated average thickness of the material is less than the minimum thickness required by the design or where an individual thickness determination is less than 80 percent of the thickness specified in the fire-resistance-rating design criteria.

K. VISUAL INSPECTION: The intumescent fireproofing applied to structural members shall not, upon complete drying/curing, exhibit deep or wide cracks, voids, spalling, delimitation or any exposure of the substrate.

Minor surface irregularities of applied intumescent fireproofing are inherent with application and shall be deemed acceptable.

L. PATCHING: When the intumescent fireproofing has been removed for any purpose, it shall be replaced.

M. PATCHING MATERIAL: All areas to be repaired shall be patched with the same intumescent fireproofing as used for the original application.

END OF SECTION

PART 2 PRODUCTS

2.1 DOORS AND FRAMES

Swing-type aluminum doors and frames of size, design, and location indicated. Provide doors complete with frames, framing members , subframes , transoms , adjoining sidelights , trim, and accessories.

2.2 MATERIALS

2.2.1 Anchors

Stainless steel .

2.2.2 Weatherstripping

Continuous wool pile, silicone treated, or type recommended by door manufacturer.

2.2.3 Aluminum Alloy for Doors and Frames

ASTM B 221, Alloy 6063-T5 for extrusions. ASTM B 209, alloy and temper best suited for aluminum sheets and strips.

2.2.4 Fasteners

Hard aluminum or stainless steel.

2.2.5 Structural Steel

ASTM A 36/A 36M.

2.2.6 Aluminum Paint

Aluminum door manufacturer's standard aluminum paint.

2.3 FABRICATION

2.3.1 Aluminum Frames

Extruded aluminum shapes with contours approximately as indicated. Provide removable glass stops and glazing beads for frames accommodating fixed glass. Use countersunk stainless steel Phillips screws for exposed fastenings, and space not more than 12 inches on center. Mill joints in frame members to a hairline fit, reinforce, and secure mechanically.

2.3.2 Aluminum Doors

Of type, size, and design indicated and not less than 1-3/4 inch thick.

Minimum wall thickness, 0.125 inch, except beads and trim, 0.050 inch. Door sizes shown are nominal and shall include standard clearances as follows:

0.093 inch at hinge and lock stiles, 0.125 inch between meeting stiles,

0.125 inch at top rails, 0.187 inch between bottom and threshold, and 0.687 inch between bottom and floor. Bevel single-acting doors 0.063 or 0.125 inch at lock, hinge, and meeting stile edges.

2.3.2.1 Full Glazed Stile and Rail Doors

Doors shall have wide, or at a minimum medium stiles and rails as indicated.

Fabricate from

08 11 16- 5 AM-05

MINIMUM

NOMINAL RABBET

MATERIAL THICKNESS MAXIMUM SIZE DEPTH

1 to 1-1/2 All sizes 3/4 inch inches

2.4.5 Finish

Exposed-to-View Aluminum Finish of surfaces shall be:

Polished frosted finish with integral-color anodic coating: Smooth specular buffed mechanical, followed by nonetching inhibitive alkaline cleaning, medium-matte chemical etch, and Architectural Class I ( 0.7-mil and greater thickness) anodic coating producing an integral-color finish. Color shall be:

as indicated on the Finish Schedule

Aluminum-finish color and appearance shall match that of the sample approved for use in the project within the aluminum producer's standard color range.

The anodic coating on aluminum shall be tested for thickness in accordance with ASTM B 244.

Anodically coated aluminum shall be tested for the weight of the coating in accordance with ASTM B 137.

The resistance of anodically coated aluminum to staining by dyes shall be tested in accordance with ASTM B 136.

2.5 CURTAIN-WALL FRAMING MEMBERS

2.5.1 General

Framing members shall be the section dimensions and arrangement indicated and shall be designed to accommodate windows, panels, and other materials to be incorporated into the curtain-wall system.

Curtain-wall framing shall be the grid type with both the vertical and horizontal mullions extending the indicated distance beyond the exterior face of the curtain wall.

2.5.2 Construction

Framing members shall be aluminum-alloy extrusions with a wall thickness not less than 0.125 .093inch. Glazing rabbet legs shall be an integral part of the frame with the leg depth not less than the minimum depth specified for the thickness and size of the glass material or panel to be installed in the curtain-wall frame. Frames shall be designed and constructed to receive window sash and louvers of the type specified when required.

Vertical mullions shall be prepared for anchorage to the building construction at the bottom, at each intermediate floor elevation, and at the top.

Corners of frames shall be mortise-and-tenon construction except that

08 44 00.00 40- 12 AM-05

L2EDMGH9

Cross-Out

L2EDMGH9

Cross-Out the corners of the vertical and horizontal mullions in grid frames shall be coped-and-welded construction. Welds shall be on the unexposed surfaces. Corner joints shall be accurately fitted and flush, with watertight hairline joints not exceeding 1/64 inch in width. Nonskinning sealing compound shall be applied to the unexposed surfaces of all mortise-and-tenon joints.

2.6 ALUMINUM DOORS AND FRAMES

Aluminum doors and frames are specified in Section 08 11 16 ALUMINUM DOORS

AND FRAMES.

2.7 METAL ACCESSORIES

2.7.1 Sills

Sills shall be the shapes and dimensions indicated and fabricated of aluminum-alloy extrusions having a wall thickness not less than 0.125 inch.

Sills shall run continuously under the curtain wall and permit the lower curtain wall frame member to interlock without fastenings.

2.8 PANELS

2.8.1 Spandrel Panel Type

Panels shall be made up of exterior glazing, with an inside facing of an applied high performance silicone elastomeric coating, insulating core, and interior metal backpan facing. Panel dimensions shall be as indicated.

2.8.2 Silicone Elastomeric Facing

Color shall be manufacturer's standard.

2.8.3 Core Insulation

Core shall be cellular glass conforming to ASTM C 552.

2.8.4 Interior Metal Facing

Facing shall bePorcelain-Enamel on steel, clor as indicated on finish schedule. Base metal shall be steel sheets for porcelain enameling, 0.010 to 0.015 inch thick, of the quality and type best suited for the work, stretcher level standard of flatness, conforming to ASTM A 424, and properly precleaned and treated for adherence of the porcelain enamel

Color of porcelain-enamel exposed-to-view surfaces shall be PEI CG-3 and shall match the color of the approved samples..

Gloss of exposed-to-view surfaces shall be medium reflectivity.

2.8.5 Panel Fabrication

Panel materials shall be securely bonded together to form a stable and durable composite unit. Panels shall conform to the following:

Structural requirements: Panels of the maximum size required by the work, when supported in the manner intended, shall withstand the windload and/or

08 44 00.00 40- 13 AM-05

L2EDMGH9

Cross-Out

UFC 4-010-01 specified. without permanent deformation or damage.

Thermal transmittance: U-factor of a panel, when a panel not less than 10 square feet in area and of identical construction is tested in accordance with ASTM C 1363, shall be as follows:

Not more than 0.10 Btu/hr-square foot-degree F.

2.9 THERMAL INSULATION MATERIALS

Thermal insulation materials are specified in UFGS Section 07 21 16 MINERAL

FIBER BLANKET INSULATION.

2.10 GLASS AND GLAZING

Glass and glazing, to include Glazing Materials, are specified in Section

08 80 00.00 40 GLAZING.

2.11 SEALANTS AND CALKINGS

Sealants and calkings are specified in Section 07 92 00 JOINT SEALANTS.

2.12 CURTAIN-WALL INSTALLATION MATERIALS

2.12.1 Threaded Concrete Inserts

Galvanized ferrous castings with enlarged bases with not less than two nailing lugs, length as indicated, internally threaded 3/4-inch diameter machine bolt shall conform to ASTM A 27/A 27M, Grade U-60-30, and shall be hot-dip galvanized in accordance with ASTM A 153/A 153M.

2.12.2 Wedge Concrete Inserts

Galvanized, box-type, ferrous castings with an integral loop at the back of the box and designed for 3/4-inch diameter bolts with wedge-shaped heads shall conform to ASTM A 47/A 47M, Grade 32510, and shall be hot-dip galvanized in accordance with ASTM A 153/A 153M.

Carbon steel bolts with wedge-shaped heads, nuts, washers, and shims shall be hot-dip galvanized in accordance with ASTM A 153/A 153M.

2.12.3 Slotted Concrete Inserts

Galvanized pressed-steel plate, welded construction, box type with a slot designed for 3/4-inch diameter square-head bolts to provide lateral adjustment shall be 1/8-inch minimum thickness, conforming to ASTM A 283/A 283M, Grade C, hot-dip galvanized in accordance with ASTM A 123/A 123M. Length of the insert body less anchorage lugs shall be 4-1/2 inches minimum and shall be provided with a knockout cover.

2.12.4 Masonry Anchorage Devices

2.12.5 Toggle Bolts

Toggle bolts shall be the tumble-wing type.

2.12.6 Steel Bolts, Nuts, and Washers

Bolts shall be regular hexagon head, low-carbon steel.

08 44 00.00 40- 14

Projected windows shall receive screens over ventilators where indicated.

Horizontal sliding or hinged wicket screens shall be provided where access to operating hardware is required. Wicket screens shall be framed with horizontal and vertical aluminum tubular or solid frame members and shall be equipped with friction catches.

2.5 WINDOW CLEANERS' BOLTS

Window cleaners' bolts shall be provided for all windows 7 feet or higher above finished grade, except windows located so they may be removed for cleaning or cleaned from the ground or from a lower roof level without the use of an extension ladder. Two bolts shall be provided for each single window unit and each fixed glass unit and shall be located 44 inches above the window sill.

Window cleaners' bolts shall be double-head type, AISI Series 300 corrosion-resistant steel, size and design complying with IWCA I-14.

Contact side of the bolts shall be ground to fit flat against window jambs. Bolts may be factory- or field-attached before windows are set.

Backs of frames to receive bolts shall be reinforced with 1/4- by 6-inch corrosion-resistant steel or aluminum plates bolted or welded to the frames at the factory. Special wall anchors shall be provided on frames at the point of bolt attachment.

2.6 FINISH

Aluminum window, mullions, glazing beadings, trim, and accessory fittings shall be thoroughly cleaned and shall receive an Architectural Class I integral-color anodic coating in accordance with AA DAF-45. Anodic-coating thickness shall be not less than 0.7 mil.

Thickness of the anodic coating shall be tested in accordance with

ASTM B 244.

Anodic coating shall be continuous and, without being lacquered, shall be capable of withstanding 500 hours of salt-spray exposure for Class A anodic coatings and 250 hours of salt-spray exposure for Class B anodic coatings when tested in accordance with ASTM B 117.

PART 3 EXECUTION

3.1 INSTALLATION

Windows shall be set plumb, level to a tolerance of not more than 1/16 inch in 10 feet and in alignment without frame distortion and securely anchored in place as indicated, in accordance with the manufacturer's printed instructions and the approved drawings.

Fasteners shall be concealed except for specifically indicated mullion covers, window-operating hardware, screen attachment hardware, and similar surface-applied trim.

Ventilators and operating parts shall be protected against cement, lime, plaster, adhesives, and other building material after installation and until completion.

Steel work shall be drilled and tapped for the attaching window units, trim, and accessories. Where window units are set in prepared masonry

08 51 13.00 40- 9 AM-05

1.4 QUALIFICATIONS

The manufacturer shall be a company specializing in the manufacture of the specified products with a minimum of 5 years documented experience. The installer shall have documented experience of 5 years minimum performing the work specified.

1.5 DELIVERY STORAGE AND HANDLING

System modules shall be factory assembled to the greatest extent possible.

Panels shall be shipped to the jobsite in rugged shipping units and shall be ready for erection. All skylights shall have conspicuous decals affixed warning individuals against sitting or stepping on the units. Skylight panels shall be stored on the long edge, several inches above the ground, blocked and under cover to prevent warping. Unit skylights, and louver system shall be delivered in manufacturer's original containers, dry, undamaged, with seals and labels intact. All products shall be delivered, stored and protected in accordance with manufacturer's recommendations.

1.6 WARRANTY

The Contractor shall provide to the Government the manufacturer's complete warranty for materials, workmanship, and installation. The warranty shall be for 5 for skylights, and 2 years for the louver system from the time of project completion and shall not be prorated. The warranty shall guarantee, but shall not be limited to, the following:

a. Light transmission and color of the panels shall not change after exposure to heat of 300 degrees F for 25 minutes.

b. There is no delamination of the panel affecting appearance, performance, weatherability or structural integrity of the panels or the completed system.

c. There is no fiberbloom on the panel face.

d. Change in light transmission of no more than 6% per ASTM D 1003, and in color (yellowing index) no more than 10 points in comparison to the original specified value over a 10 year period.

1.7 QUALITY ASSURANCE

Sole source responsibilty: Complete sun control louver system including attachment hardware, operating mechanism, controls shall be provided by single firm to ensure compatibility and functional operation.

Make accurate mearsurements at the site before fabrication.

Design and install sun control louver system to comply with seismic requirements for Project location.

PART 2 PRODUCTS

2.1 SKYLIGHT SYSTEMS

The skylight systems shall meet the following requirements:

a. Integral perimeter framing system assembly shall be by the manufacturer.

08 62 00- 5 AM-05

Maximum allowable areas of glass subject to airblast and wind pressure shall conform to the glass manufacturer's recommendations.

Luminous transmittance value shall be not less than 50 percent.

2.1.7 Figured Glass

Glass shall be rolled flat conforming to ASTM C 1036, Type II, Class 1, Form 3, Finish f1, Quality q8. Pattern shall be frosted.

Maximum allowable areas of glass subject to airblast and wind pressure shall conform to the glass manufacturer's recommendations.

2.1.8 Fire-Rated Wired Glass

Glass shall be UL approved for fire windows and doors, shall be listed in the UL Bld Mat Dir, Guide Designation KCMZ, and shall bear the UL listing and marking.

Polished wire glass shall conform to ASTM C 1036, Type II, Class 1, Form 1, Mesh m1.

Figured fire-rated glass shall conform to ASTM C 1036, Type II, Class 1, Form 2, Mesh m1 or m2.

2.1.9 Laminated-Glazing Units

Units shall be factory fabricated, shall be two panels of flat glass laminat ed by PVB layer.

Units shall be a nominal overall thickness 0.75 1-3/16+/- inches; VLT minimum 50 percent, with Outside reflectance 8 percent, Inside reflectance 11 percent;

Total solar Transmittance 20 percent; Total Solar Reflectance (outside) 28 percent; Ultraviolet transmission 4 percent. Winter U value 0.29; Summer U value 0.27; Solar Heat Gain Coefficient 0.25; Shading Coeffiecient 0.29;

Relative Hest Gain 61; Light to Solar Gain 2.00.

Maximum allowable areas of glass subject airblast and to wind pressure shall conform to the glass manufacturer's recommendations.

Tinted laminated-glazing units shall be as follows:

OUTER PANE INNER PANE AIR SPACE

GLASS, THICKNESS GLASS, THICKNESS

Tinted sheet, 1/4 3/8 inch thick clear 1/2 inch luminous trans-mittance value reflective, Low-E #2 1/4 inch thick

08 80 00.00 40- 5 AM-05

Cross-Out

b. Exterior panel faces shall meet the requirements of glazing as set forth in specification 08 80 00.00 40 GLAZING.

c. Air infiltration at 6.24 psf shall be less than 0.1 cfm/ft2 in accordance with ASTM E 283.

d. Water penetration at test pressure of 15 psf shall be zero in accordance with ASTM E 331.

e. Manufacturer shall be responsible for maximum system deflection, in accordance with the applicable building code, and without damage to system performance. Deflection shall be calculated in accordance with engineering principles.

f. Proper weepage elements shall be incorporated within the perimeter framework of the glazing system for drainage of any condensation or water penetration.

g. System shall accommodate movement within the system; movement between the system and perimeter framing components; dynamic loading and release of loads; and deflection of supporting members. This shall be achieved without damage to system or components, deterioration of weather seals and fenestration properties specified.

h. The exterior panel face shall repel an impact of 60 foot-pounds without fracture or tear when impacted by a 3.5 inch diameter,

6.37 pound free falling ball.

i. Exposed aluminum color shall be selected from the manufacturer's standard range. Corrosion resistant finish shall be anodized finish complying with AA STFA-601711, in accordance with AAMA 2605.

j. Design criteria shall be: Wind Load 41 psf.

k. Extruded aluminum shall be 6063-T6 and 6063-T5; all fasteners shall be stainless steel or cadmium plated steel.

2.1.1 Glass Glazed Skylights and Roof Windows

Roof window shall be of the following type:

a. Fixed skylight featuring an aluminum frame, mortise and tenon joints, gaskets to drain any condensation to the outside, a choice of tempered clear, laminated, insulated daylight area. The protective exterior cladding shall be aluminum for protection and low profile appearance. The skylight shall have a ventilation flap that opens to allow air circulation and contains a filter within the flap to keep dust and insects out

2.1.2 Framed Skylights

Framed skylights shall be designed to indicated size in a pyramid pitch configuration; rafter and purlin spacing shall be determined by loading requirements. Skylights manufactured in prefabricated sections easy to install are available in a wide range of standardized pitches. Framing members shall be tubular]; deflection of rafters shall not exceed L/175 of

08 62 00- 6 AM-05

INTERIOR STEEL / FERROUS SURFACES

MPI INT 5.1T-G5 (Semigloss) Primer: Intermediate: Topcoat:

MPI 23 MPI 47 MPI 47

System DFT: 5.25 mils

D. INTERIOR STEEL / FERROUS SURFACES / STRUCTURAL FRAMING

INTUMESCENT PAINT COATING

THIS BUILDING IS CLASSIFIED AS A TYPE II-A, WHICH REQUIRES A 1-HOUR

FIRE-RESISTANCE RATING OF THE FOLLOWING BUILDING ELEMENTS: STRUCTURAL

FRAME; FLOOR CONSTRUCTION INCLUDING BEAMS AND JOISTS; FLOOR CONSTRUCTION INCLUDING

BEAMS AND JOISTS SHALL RECEIVE A 1-HOUR FIRE RESISTANCE RATED SPRAY-APPLIED

FIREPROOFING PER SPEC. SEC. 07 81 23; ALL STRUCTURAL FRAME COLUMNS AND EXTERIOR

STAIRWELL FRAMING ELEMENTS SHALL RECEVE A 1-HOUR RATED INTUMESCENT PAINT COATING PER SPE. SEC. 078123 INTUSCENT MASTIC FIREPROOFING TO MEET THS REQUIREMENT, EXCEPT ROOF STRUCTURE WHICH IS SEPARATED FROM BUILDING BY A 1-HOUR COMPOSITE CONCRETE DECK; PER 2006 INTERNATIONAL BUILDING CODE. CONTRACTOR SHALL OBTAIN WRITTEN CERTIFICATION THAT THE INTUMESCENT PAINT COATING IS APPLIED, INSPECTED AND PROTECTED AS PER THE REQUIRED

MANUFACTURER'S SPECIFICATIONS.

DIVISION 6: INTERIOR WOOD PAINT TABLE

A. New Wood not otherwise specified:

1. High Performance Architectural Latex MPI INT 6.4S-G3 (Eggshell) Primer: Intermediate: Topcoat:

MPI 39 MPI 139 MPI 139

System DFT: 4.5 mils MPI INT 6.4S-G5 (Semigloss) Primer: Intermediate: Topcoat:

MPI 39 MPI 141 MP141

System DFT: 4.5 mils

2. Alkyd MPI INT 6.4B-G3 (Eggshell) Primer: Intermediate: Topcoat:

MPI 45 MPI 51 MP51

System DFT: 4.5 mils

MPI INT 6.4B-G5 (Semigloss) Primer: Intermediate: Topcoat:

MPI 45 MPI 47 MPI 47

System DFT: 4.5 mils

3. Institutional Low Odor / Low VOC Latex New; MPI INT 6.3V-G3 (Eggshell) Primer: Intermediate: Topcoat:

MPI 39 MPI 145 MPI 145

System DFT: 4 mils

New; MPI INT 6.3V-G5 (Semigloss) Primer: Intermediate: Topcoat:

MPI 39 MPI 147 MPI 147

B. New Wood , 09 90 00- 32 AM-05

Amendment No. 5 - Technical Specifications
Section 07 81 23 (New)
08 11 16 - 5
08 44 00 - 12
08 44 00 - 13
08 44 00 - 14
08 51 13.00 40 - 9
08 62 00 -5
08 62 00 - 6
08 80 00.00 40 - 5
09 90 00 - 32
Attachment No. 6 - Drawing List
Amendment No. 5 - Drawings