Q33_Tankless_Water_Heater_for_EEW.pdf

PDF 391 KB Posted

Attached to
SYNOPSIS FOR CONSTRUCTION MATOC USPFO FL Federal contract opportunity
Solicitation number
W911YN-18-R-0001
Issued by
Department of the Army National Guard National Capital Region Integrated Air Defense System

About this file

This document provides details for an indefinite delivery, indefinite quantity multiple award task order contract solicitation for construction services. The solicitation will be issued by the United States Property and Fiscal Office for Florida and seeks maintenance, repair, construction, and possible design-build services at various military bases in Florida. Services include interior and exterior renovations, HVAC, plumbing, electrical work, site work, and other construction tasks. The primary NAICS codes are 236220 and 237990. The solicitation targets small businesses with average annual revenue under $36.5 million. A minimum of eight IDIQ contracts will be awarded. The base period is two years with three one-year options, not to exceed five total years. Task order values range from $2,000 to $5 million and total contracts cannot exceed $10 million. Proposals will be evaluated on past performance, technical, and price factors including two seed projects. The pre-proposal conference is January 18-19, 2018 and proposals are due February 8, 2018. The solicitation will be available on FedBizOpps on or around January 8, 2018.

Tankless Water Heater for MATOC Response to Question

View the file

Other files for this federal contract opportunity

Other files attached to SYNOPSIS FOR CONSTRUCTION MATOC USPFO FL, newest first.
File Type Posted
Posting_of_Received_Proposals_9_MAY_18.pdf PDF
W911YN-18-R-0001-0004.pdf PDF
QandA_for_MATOC_DTD_Response_APRIL_30_2018.docx DOCX document
EXHIBIT_D-1_SEED_PROJECT_LSGA132007-Mod.pdf PDF
Attachment__1_Plans_SK-1_27APR2018.pdf PDF
W911YN-18-R-0001-0003.pdf PDF
QandA_for_MATOC_DTD_APRIL_27_2018.docx DOCX document
Attachment_4_Spec_087100_Rev_27APR2018.pdf PDF
Site_Visit_attendance_11Apr18.pdf PDF
QandA_for_MATOC_DTD_APRIL_26_2018.docx DOCX document
W911YN-18-R-0001-0002.pdf PDF
QandA_for_MATOC_DTD_APRIL_20_2018.docx DOCX document
Q32_Compressed_air_detail.JPG JPG image
QandA_for_MATOC_DTD_APRIL_12_2018.docx DOCX document
Q30-FDZD3001_Combined_PDF_-_Rev_2_6.pdf PDF
EXHIBIT_D-1_SEED_PROJECT_LSGA132007_Rev1.pdf PDF
Attachment_7_ACM_Survey_LBP_Inspection.pdf PDF
EXHIBIT_D-2_SEED_PROJECT_LSGA132001_Rev1.pdf PDF
W911YN-18-R-0001-0001.pdf PDF
MATOC_Preproposal_Conference.pptx PPTX presentation
Pre-Proposal_Site_Visit_Minutes.doc DOC document
SIGN_IN_SHEETS.pdf PDF
EXHIBIT_C_Reference_Questionnaire_Package.docx DOCX document
Attachment_6_MATOC_DIVISION_01_Special_Contract_Requirements.docx DOCX document
EXHIBIT_D-1_SEED_PROJECT_LSGA132007.pdf PDF
EXHIBIT_E.docx DOCX document
EXHIBIT_D-2_SEED_PROJECT_LSGA132001.pdf PDF
W911YN-18-R-0001.pdf PDF
EXHIBIT_B.docx DOCX document
Show all 29

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Complies with

Standards for:

17451 Hurley St. :: City of Industry, CA 91744 Phone 800-447-4962 :: 626-937-4270

Fax 626-937-4279 :: www.chronomite.com

Since 1966

Chronomite Laboratories is a member of Acorn Engineering’s Family of Companies

APPLICATION: EYEWASH

IDEAL for

• Anywhere the eyes/face may be exposed to injurious corrosive material

• Heater to supply “tepid” warm water (at 70°-90°F) with inlet temperature range 50°-84°F according to ANSI Z358.1

• Industrial

• Schools, colleges & universities

• Swimming pool facilities (high chlorine levels)

Member of U.S. Green Building Council

Water Conserving Product

Made in the USA

APPL-EW 11/23/10

* 240 volt may be operated at 220V.

However, an approximate 15% decrease in temperature will be experienced.

** 84°F is an ideal temperature for eyewash application

INSTANT-TEMP® - (2.2 GPM)INSTANT-FLOW® MICRO (2.2 GPM)

MICROPROCESSOR MODELSMICROPROCESSOR MODELS

MODEL

BREAKER

SIZE

(AMPS) VOLTS WATTS

PRESET

TEMP.

E-80EW/208 40 208 8,000 84°F

E-90EW/240 50 240* 9,000 84°F

E-90EW/277 40 277 9,000 84°F

MODEL

BREAKER

SIZE

(AMPS) VOLTS WATTS

PRESET

TEMP.

M-40EW/208 40 208 8,320 84°F

M-40EW/240 40 240* 9,600 84°F

M-40EW/277 40 277 11,080 84°F

M-50EW/240 50 240* 11,520 84°F

StampeJJ Highlight

Standards for:

17451 Hurley St. :: City of Industry, CA 91744 Phone 800-447-4962 :: 626-937-4270

Fax 626-937-4279 :: www.chronomite.com

Since 1966

Chronomite Laboratories is a member of Acorn Engineering’s Family of Companies

APPLICATION: EYEWASH

Member of U.S. Green Building Council

Water Conserving Product

Made in the USA

APPL-EW 11/23/10

INSTANT-FLOW® MICRO

(2.2 GPM FLOW RATE)

Dimension:

6-1/4” (H) x 9-5/8” x 2-3/4” Weight: 5 lbs Material: Stainless steel housing;

Celcon plastic element assembly with nichrome coils.

Microprocessor Controlled: YES Min. Operating Flow: 2.2 GPM Operating Pressure: Minimum 45 PSI / Maximum 150 PSI Max. Operating Temperature: 84°F Accessory Package: Compression fittings are installed in factory Housing Options: High Polish Stainless Steel Fail safe to cold by pass: YES

INSTANT-TEMP®

(2.2 GPM FLOW RATE)

Dimension:

7-5/16” (H) x 10-3/4” x 2-3/4” Weight: 8 lbs Material: Stainless steel housing;

Celcon plastic element assembly with nichrome coils.

Microprocessor Controlled: YES Min. Operating Flow: 2.2 GPM Operating Pressure: Minimum 45 PSI / Maximum 150 PSI Max. Operating Temperature: 84°F Accessory Package: Compression fittings are installed in factory Housing Options: Satin Finish & High Polish Stainless Steel Fail safe to cold by pass: YES

T E M P E R A T U R E R I S E A T :

MODEL WATTS

2.2

GPM

(OPTI-

MUM)

2.4

GPM

2.5

GPM

2.6

GPM

2.8

GPM

3.0

GPM

M-40EW/208 8,320 25°F 23°F 22°F 21°F 20°F 19°F

M-40EW/240

9,600 29°F 27°F 26°F 25°F 23°F 21°F

M-40EW/277 11,080 34°F 31°F 30°F 29°F 27°F 25°F

M-50EW/240

11,520 35°F 32°F 31°F 30°F 28°F 26°F

T E M P E R A T U R E R I S E A T :

MODEL WATTS

2.2

GPM

(OPTI-

MUM)

2.4

GPM

2.5

GPM

2.6

GPM

2.8

GPM

3.0

GPM

E-80EW/208 8,000 25°F 23°F 22°F 21°F 20°F 18°F

E-90EW/240

9,000 28°F 26°F 25°F 24°F 22°F 21°F

E-90EW/277 9,000 28°F 26°F 25°F 24°F 22°F 21°F

* 240 volt may be operated at 220V.

However, an approximate 15% decrease in temperature will be experienced.

StampeJJ Highlight

Standards for:

17451 Hurley St. :: City of Industry, CA 91744 Phone 800-447-4962 :: 626-937-4270

Fax 626-937-4279 :: www.chronomite.com

Since 1966

Chronomite Laboratories is a member of Acorn Engineering’s Family of Companies

APPLICATION: EYEWASH

Member of U.S. Green Building Council

Water Conserving Product

Made in the USA

WARM

COLD

1-7/8" (48)

Instant-Flow Micro Heater

Mounting Flanges (4) with 7-32" Diam.Holes

J-Box 3/8" Cold Water Inlet

5/8" x 3/8" Angle Stop Valve

3/8" OD 84°F

(Tepid) Water Outlet Keep line as short as possible

2" (51)

3-5/16" (84)

Compression

Shown with Acorn Safety Model S0410 Eyewash

(not provided)

Fittings (2)

6-1/4" (159)

1/4" (6)

9-5/8" (244)

1/4" (6)

1/4" (6)

1/4" (6)

Conduit

WIRING CONNECTION

Hot or Neutral

Hot or Neutral

Refer to local code for wire size.

"GND"

is earth ground

ATTENTION:

Unit must be hard wired.

NOTE: Heater is single phase.

All tests are measured at the output of the heater.

APPL-EW 11/23/10

Note: Heater to be installed below the level of all hot water outlets serviced by the heater

Heater (shown Instant-Flow®

Micro) should be protected from water spray.

Mounting Flanges (4) with Ø 7/32” Holes