SECTION 22 07 19.00 40 Page 1
SECTION 22 07 19.00 40
PLUMBING PIPING INSULATION
08/16
PART 1 GENERAL
Section 22 00 00 PLUMBING, GENERAL PURPOSE applies to work specified in this section.
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM A240/A240M (2017) Standard Specification for Chromium and Chromium-Nickel Stainless Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications
ASTM B209 (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B209M (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate (Metric)
ASTM C1136 (2017a) Standard Specification for
Flexible, Low Permeance Vapor Retarders for Thermal Insulation
ASTM C195 (2007; R 2013) Standard Specification for
Mineral Fiber Thermal Insulating Cement
ASTM C449 (2007; R 2013) Standard Specification for Mineral Fiber Hydraulic-Setting Thermal Insulating and Finishing Cement
ASTM C533 (2017) Standard Specification for Calcium
Silicate Block and Pipe Thermal Insulation
ASTM C534/C534M (2016) Standard Specification for Preformed Flexible Elastomeric Cellular Thermal Insulation in Sheet and Tubular Form
ASTM C547 (2017) Standard Specification for Mineral Fiber Pipe Insulation
ASTM C552 (2017; E 2018) Standard Specification for
Cellular Glass Thermal Insulation
ASTM C553 (2013) Standard Specification for Mineral Fiber Blanket Thermal Insulation for Commercial and Industrial Applications
SECTION 22 07 19.00 40 Page 2
ASTM C591 (2017) Standard Specification for Unfaced Preformed Rigid Cellular Polyisocyanurate Thermal Insulation
ASTM C592 (2016) Standard Specification for Mineral
Fiber Blanket Insulation and Blanket-Type Pipe Insulation (Metal-Mesh Covered) (Industrial Type)
ASTM C647 (2008; R 2013) Properties and Tests of
Mastics and Coating Finishes for Thermal Insulation
ASTM C795 (2008; R 2013) Standard Specification for
Thermal Insulation for Use in Contact with Austenitic Stainless Steel
ASTM C916 (2014) Standard Specification for
Adhesives for Duct Thermal Insulation
ASTM C920 (2018) Standard Specification for Elastomeric Joint Sealants
ASTM C921 (2010) Standard Practice for Determining the Properties of Jacketing Materials for Thermal Insulation
ASTM D226/D226M (2017) Standard Specification for
Asphalt-Saturated Organic Felt Used in Roofing and Waterproofing
ASTM D5590 (2000; R 2010; E 2012) Standard Test
Method for Determining the Resistance of Paint Films and Related Coatings to Fungal Defacement by Accelerated Four-Week Agar Plate Assay
ASTM D579/D579M (2015) Standard Specification for Greige
Woven Glass Fabrics
ASTM E84 (2018a) Standard Test Method for Surface Burning Characteristics of Building Materials
ASTM E96/E96M (2016) Standard Test Methods for Water
Vapor Transmission of Materials
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 220 (2018) Standard on Types of Building Construction
NFPA 255 (2006; Errata 2006) Standard Method of
Test of Surface Burning Characteristics of Building Materials
SECTION 22 07 19.00 40 Page 3
SOCIETY OF AUTOMOTIVE ENGINEERS INTERNATIONAL (SAE)
SAE AMS 3779 (2016; Rev B) Tape Adhesive, Pressure Sensitive Thermal Radiation Resistant, Aluminum Foil/Glass Cloth
U.S. DEPARTMENT OF DEFENSE (DOD)
MIL-A-3316 (1987; Rev C; Am 2 1990) Adhesives, Fire-Resistant, Thermal Insulation
MIL-PRF-19565 (1988; Rev C) Coating Compounds, Thermal Insulation, Fire- and Water-Resistant, Vapor-Barrier
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
FED-STD-595 (Rev C; Notice 1) Colors Used in
Government Procurement
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Installation Drawings; G
SD-03 Product Data
Adhesives; G
Coatings; G
Insulating Cement; G
Insulation Materials; G
Jacketing; G
Tape; G
SD-08 Manufacturer's Instructions
Installation Manual; G
SD-11 Closeout Submittals
Record Drawings
Adhesives; S
SECTION 22 07 19.00 40 Page 4
1.3 QUALITY CONTROL
1.3.1 Recycled Materials
Provide thermal insulation containing recycled materials to the extent practicable, provided that the material meets all other requirements of this section. The minimum recycled material content of the following insulation types are:
a. Rock Wool - 75 percent slag by weight
b. Fiberglass - 20-25 percent glass cullet by weight
c. Plastic Rigid Foam - 9 percent recovered material
d. Polyisocyanurate/Polyurethane - 9 percent recovered material
e. Rigid Foam - 9 percent recovered material
Submit recycled materials documentation indicating percentage of post-industrial and post-consumer recycled content per unit of product.
Indicate relative dollar value of recycled content products to total dollar value of products included in project.
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
2.1.1 Performance Requirements
Provide noncombustible thermal-insulation system materials, as defined by NFPA 220. Provide adhesives, coatings, sealants, facings, jackets, and thermal-insulation materials, except cellular elastomers, with a flame-spread classification (FSC) of 25 or less, and a smoke-developed classification (SDC) of 50 or less. Determine these maximum values in accordance with NFPA 255. Provide coatings and sealants that are nonflammable in their wet state.
Provide adhesives, coatings, and sealants with published or certified temperature ratings suitable for the entire range of working temperatures normal for the surfaces to which they are to be applied.
2.2 COMPONENTS
2.2.1 Insulation
2.2.1.1 Omitted
2.2.1.2 Cellular Elastomer Insulation
Provide cellular elastomer insulation conforming to ASTM C534/C534M.
Ensure the water vapor permeability does not exceed 0.30 grain per foot per inch per hour per square foot mercury pressure difference for 25 millimeter 1-inch thickness of cellular elastomer.
2.2.1.3 Cellular Glass Insulation
Conform to ASTM C552, Type II, Grade 2, pipe covering for Cellular Glass.
Substitutions for this material are not permitted. Ensure minimum thickness is not less than 38 mm 1-1/2 inches.
SECTION 22 07 19.00 40 Page 5
2.2.1.4 Omitted
2.2.1.5 Omitted
2.2.1.6 Polyisocyanurate Pipe Insulation
Conform to ASTM C591 for polyisocyanurate, minimum density of 27.20 kilograms per cubic meter (kg/cu m) 1.7 pounds per cubic foot.
2.2.1.7 Pipe Barrel
For temperatures up to and including 650 degrees C 1200 degrees F, use pipe barrel insulation Type II, Molded, Grade A or Type III, Precision V-Groove, Grade A.
2.2.1.8 Pipe Fittings
Provide molded pipe fitting insulation covering for use at temperatures up to and including 650 degrees C 1200 degrees F.
2.2.1.9 Omitted
2.2.2 Adhesives
2.2.2.1 Lagging Adhesive
Lagging is the material used for thermal insulation, especially around a cylindrical object. This may include the insulation as well as the cloth/material covering the insulation. To resist mold/mildew, ensure lagging adhesive conforms to ASTM D5590 with 0 growth rating. Provide nonflammable and fire-resistant lagging adhesives with a maximum flame spread index of 25 and a maximum smoke developed index of 50 when tested in accordance with ASTM E84. Adhesive are MIL-A-3316, Class 1, pigmented white and suitable for bonding fibrous glass cloth to faced and unfaced fibrous glass insulation board; for bonding cotton brattice cloth to faced and unfaced fibrous glass insulation board; for sealing edges of and bonding glass tape to joints of fibrous glass board; for bonding lagging cloth to thermal insulation; or Class 2 for attaching fibrous glass insulation to metal surfaces. Apply lagging adhesives in strict accordance with the manufacturer's recommendations for pipe and duct insulation.
2.2.2.2 Vapor-Barrier Material Adhesives
Ensure adhesives conform to the requirements of ASTM C916, Type I, when attaching fibrous-glass insulation to metal surfaces or attaching insulation to itself, to metal, and to various other substrates.
2.2.2.3 Cellular Elastomer Insulation Adhesive
For cellular elastomer insulation adhesive, provide a solvent cutback chloroprene elastomer conforming to ASTM C916, Type I, and is approved by the manufacturer of the cellular elastomer for the intended use.
2.2.3 Insulating Cement
2.2.3.1 General Purpose Insulating Cement
Provide general purpose insulating cement, diatomaceous silica, conforming to ASTM C195. Ensure composite is rated for 982 degrees C 1800 degrees F service, with a thermal-conductivity maximum of
SECTION 22 07 19.00 40 Page 6
0.85 Btu per inch per hour per square foot for each degree F temperature differential at 93 degrees C 200 degrees F mean temperature for a 25 millimeter 1 inch thickness.
2.2.3.2 Finishing Insulating Cement
Provide finishing insulating cement of a mineral-fiber, hydraulic-setting type conforming to ASTM C449.
2.2.4 Caulk
Provide elastomeric joint sealant in accordance with ASTM C920, Type S, Grade NS, Class 25, Use A.
2.2.5 Corner Angles
Provide a nominal 0.41 millimeter 0.016 inch thick aluminum 25 by 25 millimeter 1 by 1 inch corner angle piping insulation with factory applied kraft backing. Ensure aluminum conforms to ASTM B209M ASTM B209, Alloy 3003.
2.2.6 Jacketing
2.2.6.1 Aluminum Jacket
Provide aluminum jackets conforming ASTM B209M ASTM B209, Temper H14, minimum thickness of 0.41 mm 0.016 inch, with factory-applied polyethylene and kraft paper moisture barrier on the inside surface. Provide smooth surface jackets for jacket outside diameters less than 200 mm 8 inches.
Provide corrugated surface jackets for jacket outside diameters 200 mm 8 inches and larger. Provide stainless steel bands, minimum width of 13 mm
0.5 inch. Provide factory prefabricated aluminum covers for insulation on fittings, valves, and flanges. Provide aboveground jackets and bands with factory-applied baked-on semi-gloss brown color conforming to Federal Standard FED-STD-595, "Colors," color chip number 20062.
2.2.6.2 Omitted
2.2.6.3 Stainless Steel Jacket
Provide stainless steel jackets conforming to ASTM A240/A240M; Type 304, minimum thickness of 0.25 mm 0.010 inch, smooth surface with factory-applied polyethylene and kraft paper moisture barrier on inside surface. Provide stainless steel bands, minimum width of 13 mm 0.5 inch.
Provide factory prefabricated stainless steel covers for insulation on fittings, valves, and flanges.
2.2.6.4 Omitted
2.2.6.5 Omitted
2.2.7 Coatings
2.2.7.1 Outdoor Vapor-Barrier Finishing
Provide a nonasphaltic, hydrocarbon polymer, mastic coating. Ensure the coating conforms to the requirements of ASTM C1136 and ASTM C921.
2.2.7.2 Omitted
SECTION 22 07 19.00 40 Page 7
2.2.7.3 Outdoor and Indoor Nonvapor-Barrier Finishing (NBF)
Provide a pigmented polymer-emulsion as recommended by the insulation material manufacturer for the surface to be coated.
2.2.7.4 Vapor Retarder
The vapor retarder coating shall be fire and water resistant and appropriately selected for either outdoor or indoor service. Color shall be white. The water vapor permeance of the compound shall be 0.013 perms or less at 1 mm 43 mils dry film thickness as determined according to procedure B of ASTM E96/E96M utilizing apparatus described in ASTM E96/E96M.
The coating shall be nonflammable, fire resistant type. [To resist mold/mildew, coating shall meet ASTM D5590 with 0 growth rating. ]Coating shall meet MIL-PRF-19565 Type II (if selected for indoor service) and be Qualified Products Database listed. All other application and service properties shall be in accordance with ASTM C647.
2.2.7.5 Cellular-Elastomer Finishing
Provide a polyvinylchloride lacquer coating recommended by the manufacturer of the cellular elastomer finish.
2.2.7.6 Coating Color
Provide white for the coating color.
2.2.8 Tape
Provide a knitted elastic cloth glass lagging specifically suitable for continuous spiral wrapping of insulated pipe bends and fittings that produces a smooth, tight, wrinkle-free surface. Conform to requirements of SAE AMS 3779, ASTM D579/D579M, and ASTM C921 for tape, weighing not less than 10 ounces per square yard.
2.3 MATERIALS
Submit manufacturer's catalog data for the following items:
a. Adhesives
b. Coatings
c. Insulating Cement
d. Insulation Materials
e. Jacketing
f. Tape
Provide compatible materials that do not contribute to corrosion, soften, or otherwise attack surfaces to which applied, in either the wet or dry state. Meet ASTM C795 requirements for materials to be used on stainless steel surfaces. Provide materials that are asbestos free.
PART 3 EXECUTION
Apply insulation only to the system or component surfaces that have previously been tested and approved by the Contracting Officer.
SECTION 22 07 19.00 40 Page 8
3.1 PREPARATION
Submit installation drawings for pipe insulation, conforming with the adhesive manufacturer's written instructions for installation. Submit installation manual clearly stating the manufacturer's instructions for insulation materials.
Clean surfaces to remove oil and grease before insulation adhesives or mastics are applied. Provide solvent cleaning required to bring metal surfaces to such condition.
3.2 INSTALLATION OF INSULATION SYSTEMS
Apply materials in conformance with the recommendations of the manufacturer.
Install smooth and continuous contours on exposed work. Smoothly and securely paste down cemented laps, flaps, bands, and tapes. Apply adhesives on a full-coverage basis.
Install insulation lengths tightly butted against each other at joints.
Where lengths are cut, provide smooth and square and without breakage of end surfaces. Where insulation terminates, neatly taper and effectively seal ends, or finish as specified. Direct longitudinal seams of exposed insulation away from normal view.
Use insulation meeting maximum value conductance as tested at any point, do not use an average. Meet or exceed the specified maximum conductance by adding additional insulation thickness.
3.2.1 Cold-Water and Condensate-Drain Piping
Insulate aboveground pipes, valve bodies, fittings, unions, flanges, and miscellaneous surfaces.
Install a cellular-elastomer insulation conforming to ASTM C534/C534M, with a water-vapor permeability not 0.1 grain per square foot per hour per inch mercury pressure-differential for 1 inch thickness.
Provide flexible cellular-elastomeric thermal insulation for cold water piping, Type T-3, with a thickness of 1/2 inch. Use expanded, closed-cell pipe insulation only aboveground, not for underground piping.
3.3 APPLICATION
3.3.1 Type T-3, Cellular Elastomer
Cover piping-system surfaces with flexible cellular-elastomer sheet or preformed insulation. Maintain vapor seal. Cement insulation into continuous material using a solvent cutback chloroprene adhesive recommended by the manufacturer for the specific purpose. Apply adhesive to both of the contact surfaces on a 100-percent coverage basis to a minimum thickness of 0.254 millimeter 10-mils wet or approximately 4 square meter per liter 150 square feet per gallon of undiluted adhesive.
Set cold water piping insulation into an outdoor vapor-barrier coating applied intermittently over a minimum length of 6 inches at maximum intervals of 3500 millimeter 12 feet. At piping supports, ensure insulation is continuous by using outside-carrying type clevis hangers with insulation shield. Install Cork load-bearing inserts between the pipe and insulation shields to prevent insulation compression.
SECTION 22 07 19.00 40 Page 9
Insulate hot-water, cold-water, and condensate drain pipes to the extent shown with nominal 1/2-inch thick, fire retardant (FR), cellular elastomer, preformed pipe insulation. Seal joints with adhesive.
At pipe hangers or supports where the insulation rests on the pipe hanger strap, cut the insulation with a brass cork borer and insert a No. 3 superior grade cork. Seal seams with approved adhesive. Insulate sweat fitting with miter-cut pieces of cellular elastomer insulation of the same nominal pipe size and thickness as the insulation on the adjacent piping or tubing. Join miter-cut pieces with approved adhesive. Slit and snap covers over the fitting, and seal joints with approved adhesive.
Insulate screwed fittings with sleeve-type covers formed from miter-cut pieces of cellular elastomer thermal insulation having an inside diameter large enough to overlap adjacent pipe insulation. Lap pipe insulation against fittings, and overlap not less than 1 inch. Use adhesive to join cover pieces and cement the cover to the pipe insulation.
3.3.2 Type T-4, Cellular Glass with Vapor-Barrier Jacket
Apply factory and field attached vapor barrier jacket to piping insulated with cellular glass. Maintain vapor seal. Securely cement jackets, jacket laps, flaps, and bands in place with vapor-barrier adhesive. Provide jacket overlaps not less than 1-1/2 inches.
Provide jacket bands for butt joints of not less than 3 inches width. Provide insulation continuous through hangers. Bed insulation in an outdoor vapor-barrier coating applied to all piping surfaces.
Insulate flanges, unions, valves, anchors, and fittings with factory premolded or prefabricated or field fabricated segments of insulation of the same material and thickness as the adjoining pipe insulation. When segments of insulation are used, provide elbows with not less than three segments. For other fittings and valves, cut segments to the required curvature or nesting size.
3.4 CLOSEOUT ACTIVITIES
Final acceptance of the performed work is dependent upon providing Record Drawings details to the Contracting Officer. Include construction details, by building area, the insulation material type, amount, and installation method. An illustration or map of the pipe routing locations may serve this purpose.