OUST-AR RANGE PROJECTS FY19
SECTION 08 51 13.00 20
ALUMINUM WINDOWS
04/06
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ALUMINUM ASSOCIATION (AA)
AA 45 (2003) Designation System for Aluminum Finishes
AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)
AAMA 101 (2005) Voluntary Specifications for Aluminum, Vinyl (PVC) and Wood Windows and Glass Doors
AAMA 1302 (1976) Voluntary Specifications for Forced-Entry Resistant Aluminum Prime Windows
AAMA 1503 (1998) Voluntary Test Method for Thermal Transmittance and Condensation Resistance of Windows, Doors and Glazed Wall Sections
AAMA 2603 (2002) Voluntary Specification, Performance Requirements and Test Procedures for Pigmented Organic Coatings on Aluminum Extrusions and Panels
AAMA 2604 (2005) Voluntary Specification, Performance Requirements and Test Procedures for High Performance Organic Coatings on Aluminum Extrusions and Panels
AAMA 2605 (2005) Voluntary Specification, Performance Requirements and Test Procedures for Superior Performing Organic Coatings on Aluminum Extrusions and Panels
AAMA 611 (1998) Voluntary Specification for Anodized Architectural Aluminum
AAMA 902 (1999) Voluntary Specification for Sash Balances
1.2 CERTIFICATION
Each prime window unit shall bear the AAMA Label warranting that the product complies with AAMA 101. Certified test reports attesting that the prime window units meet the requirements of AAMA 101, including test size, will be acceptable in lieu of product labeling.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. The following shall be submitted in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Windows; G, RO
SD-03 Product Data
Windows; G, RO
Hardware; G, RO
Fasteners; G, RO
Screens; G, RO
Weatherstripping; G, RO
Accessories; G, RO
SD-04 Samples
Finish Sample, RO
Window Sample, RO
SD-05 Design Data
Structural calculations for deflection; G, RO
SD-06 Test Reports
Minimum condensation resistance factor
Resistance to forced entry
SD-10 Operation and Maintenance Data
Windows, Data Package 1; G, RO
Submit in accordance with Section 01 78 23 OPERATION AND
MAINTENANCE DATA.
1.4 QUALITY ASSURANCE
1.4.1 Shop Drawing Requirements
Drawings shall indicate elevations of windows, full-size sections, thickness and gages of metal, fastenings, proposed method of anchoring, size and spacing of anchors, details of construction, method of glazing, details of operating hardware, method and materials for weatherstripping, method of attaching screens, material and method of attaching subframes, stools, sills, trim, installation details, and other related items.
1.4.2 Sample Requirements
1.4.2.1 Finish Sample Requirements
Submit color chart of standard factory color coatings when factory-finish color coating is to be provided.
1.4.2.2 Window Sample Requirements
Submit one full-size corner of each window type proposed for use. Where screens or weatherstripping is required, fit sample with such items that are to be used.
1.4.3 Design Data Requirements
Submit calculations to substantiate compliance with deflection requirements. Calculations shall be provided by a Professional Engineer.
1.4.4 Test Report Requirements
Submit test reports for each type of window attesting that identical windows have been tested and meet the requirements specified herein for conformance to AAMA 101 including test size, minimum condensation resistance factor (CRF).
1.5 DELIVERY AND STORAGE
Deliver windows to project site in an undamaged condition. Use care in handling and hoisting windows during transportation and at the jobsite.
Store windows and components out of contact with the ground, under a weathertight covering, so as to prevent bending, warping, or otherwise damaging the windows. Damaged windows shall be repaired to an "as new" condition as approved. If windows can not be repaired, provide a new unit.
1.6 PROTECTION
Protect finished surfaces during shipping and handling using the manufacturer's standard method, except that no coatings or lacquers shall be applied to surfaces to which calking and glazing compounds must adhere.
PART 2 PRODUCTS
2.1 WINDOWS
Prime windows shall comply with AAMA 101 and the requirements specified herein. In addition to compliance with AAMA 101, window framing members for each individual lite of glass shall not deflect to the extent that deflection perpendicular to the glass lite exceeds L/175 of the glass edge length when subjected to uniform loads at specified design pressures.
Structural calculations for deflection shall be provided to substantiate compliance with deflection requirements. Provide windows of types, performance classes, performance grades, combinations, and sizes indicated or specified. Design windows to accommodate hardware, glass, weatherstripping, screens, and accessories to be furnished. Each window shall be a complete factory assembled unit with or without glass installed. Dimensions shown are minimum. Provide windows with insulating glass and thermal break necessary to achieve a minimum Condensation Resistance Factor (CRF) of 46 when tested in accordance with AAMA 1503.
Exterior frames, mullions, and window hardware shall be designed to resist equivalent static design loads of 1 pound per square inch applied to the surface of the glazing. Frame and mullion deformations shall not exceed 1/60 of the unsupported member lengths. A window that complies with the AAMA 101 Optional Performance Grade 60 is acceptable in lieu of tests or calculations showing compliance with load requirement specified above. The Contractor may use other products, but must demonstrate by calculations or tests that the window complies with the loading requirement. Equivalent static design loads for connections of window to the surrounding walls or hardware and associated connections, and glazing stop connections shall be
10.8 pounds per square inchfor glazing panels with a vision area less than or equal to 10.8 square feet and 4.4 pounds per square inch for glazing panels with a vision area greater than 10.8 square feetbut less than or equal to 32 square feet. Alternatively, use frames that provide an equivalent level of performance.
2.1.1 OMITTED
2.1.2 OMITTED
2.1.3 Single Hung Windows (SH)
Type SH-HC AW- 50.
2.1.4 Horizontal Sliding Windows (HS)
Type HS-HC AW- 50.
2.1.5 Projected Windows (AP)
Type AP-R15 HC AW- 50. Provide projected windows with concealed four bar friction hinges only.
2.1.6 OMITTED
2.1.7 OMITTED
2.1.8 OMITTED
2.1.9 OMITTED
2.1.10 Glass and Glazing
Materials are specified in Section 08 81 00 GLAZING.
2.1.11 Calking and Sealing
Are specified in Section 07 92 00 JOINT SEALANTS.
2.1.12 Weatherstripping
AAMA 101.
2.1.13 OMITTED
2.2 FABRICATION
Fabrication of window units shall comply with AAMA 101.
2.2.1 Provisions for Glazing
Design windows and rabbets suitable for glass thickness shown or specified. Design sash for inside double glazing and for securing glass with metal beads, glazing clips, glazing channels, or glazing compound.
2.2.2 Weatherstripping
Provide for ventilating sections of all windows to ensure a weather-tight seal meeting the infiltration requirements specified in AAMA 101. Provide easily replaceable factory-applied weatherstripping. Use molded vinyl, molded or molded-expanded neoprene or molded or expanded Ethylene Propylene Diene Terpolymer (EPDM) weatherstripping for compression contact surfaces.
Use treated woven pile or wool, or polypropylene or nylon pile bonded to nylon fabric and metal or plastic backing strip weatherstripping for sliding surfaces. Do no use neoprene or polyvinylchloride weatherstripping where they will be exposed to direct sunlight.
2.2.3 Fasteners
Use fasteners as standard with the window manufacturer for windows, trim, and accessories. Self-tapping sheet-metal screws are not acceptable for material more than 1/16 inch thick.
2.2.4 Drips and Weep Holes
Provide continuous drips over heads of top ventilators. Where fixed windows adjoin ventilators, drips shall be continuous across tops of fixed windows. Provide drips and weep holes as required to return water to the outside.
2.2.5 OMITTED
2.2.6 OMITTED
2.2.7 Accessories
Provide windows complete with necessary hardware, fastenings, clips, fins, anchors, glazing beads, and other appurtenances necessary for complete installation and proper operation. Furnish extruded aluminum subframe receptors and subsill with each window unit.
2.2.7.1 Hardware
AAMA 101. The item, type, and functional characteristics shall be the manufacturer's standard for the particular window type. Provide hardware of suitable design and of sufficient strength to perform the function for which it is used. Equip all operating ventilators with a lock or latching device which can be secured from the inside.
2.2.7.2 Fasteners
Provide concealed anchors of the type recommended by the window manufacturer for the specific type of construction. Anchors and fasteners shall be compatible with the window and the adjoining construction. Provide a minimum of three anchors for each jamb located approximately 6 inches from each end and at midpoint.
2.2.7.3 OMITTED
2.2.8 Finishes
Exposed aluminum surfaces shall be factory finished with an organic coating. Color shall be selected by government rep.
2.2.8.1 OMITTED
2.2.8.2 Organic Coating
Clean and prime exposed aluminum surfaces. Provide a high-performance finish in accordance with AAMA 2604 or AAMA 2605 with total dry film thickness of not less than 1.2 mils.
2.2.9 Screens
AAMA 101. Provide one insect screen for each operable exterior sash or ventilator. Design screens to be rewirable, easily removable from inside the building, and to permit easy access to operating hardware.
2.3 OMITTED
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Method of Installation
Install in accordance with the window manufacturer's printed instructions and details. Build in windows as the work progresses or install without forcing into prepared window openings. Set windows at proper elevation, location, and reveal; plumb, square, level, and in alignment; and brace, strut, and stay properly to prevent distortion and misalignment. Protect ventilators and operating parts against accumulation of dirt and building materials by keeping ventilators tightly closed and locked to frame. Bed screws or bolts in sill members, joints at mullions, contacts of windows with sills, built-in fins, and subframes in mastic sealant of a type recommended by the window manufacturer. Install windows in a manner that will prevent entrance of water and wind. Fasten insect screens securely in place.
3.1.2 Dissimilar Materials
Where aluminum surfaces are in contact with, or fastened to masonry, concrete, wood, or dissimilar metals, except stainless steel or zinc, the aluminum surface shall be protected from dissimilar materials as recommended in the Appendix to AAMA 101. Surfaces in contact with sealants after installation shall not be coated with any type of protective material.
3.1.3 Anchors and Fastenings
Make provision for securing units to each other, to masonry, and to other adjoining construction. Windows installed in masonry walls shall have head and jamb members designed to recess into masonry wall not less than 7/16 inch.
3.1.4 Adjustments After Installation
After installation of windows and completion of glazing and field painting, adjust all ventilators and hardware to operate smoothly and to provide weathertight sealing when ventilators are closed and locked. Lubricate hardware and operating parts as necessary. Adjust single hung windows to operate with maximum applied force of 25 pounds, not including breakaway friction force.
3.2 CLEANING
Clean interior and exterior surfaces of window units of mortar, plaster, paint spattering spots, and other foreign matter to present a neat appearance, to prevent fouling of weathering surfaces and weather-stripping, and to prevent interference with the operation of hardware. Replace all stained, discolored, or abraded windows that cannot be restored to their original condition with new windows.
-- End of Section --