1. Start with the IDS system in the ARMED mode, testers inside the alarmed area and all doors and windows with BMS installed closed:
2. Open the RTU: receive TAMPER alarm Y/N NA
3. Move tamper switches to maintenance position: TAMPER return Y/N NA
4. Disconnect the communication line (RJ45 or copper): COMM FAIL alarm Y/N NA
5. Reconnect the communication line: COMM FAIL return Y/N NA
6. Turn off AC: AC FAIL alarm Y/N NA
7. Turn on AC: AC & COMMS return Y/N NA
8. Test S-fault & short (in sequence): remove and replace each active jumper Y/N NA
9. Open door(s) with BMS: INTRUSION alarm Y/N NA
10. Close door(s): INTRUSION return Y/N NA
11. Trigger motion sensor(s): INTRUSION alarm Y/N NA
12. Stand still: INTRUSION return Y/N NA
13. Place RTU into the UNARMED mode Y/N NA
14. Activate BMS tamper switch(all in sequence): TAMPER alarm Y/N NA
15. Return BMS tamper switch (all in sequence): TAMPER return Y/N NA
16. Activate PIMS tamper switch (all in sequence): TAMPER alarm Y/N NA
17. Return PIMS tamper switch (all in sequence): TAMPER return Y/N NA
18. Close RTU: TAMPER alarm & TAMPER return Y/N NA
19. Close facility and FORCE CLOSE the IDS: verify alarmed status Y/N NA
20. Reenter facility & input DURESS PIN: DURESS OPEN alarm Y/N NA
21. Reenter proper PIN: DURESS return Y/N NA
22. Activate duress switch(s) (all in sequence): DURESS alarm Y/N NA
23. Reset duress switch(s): DURESS return Y/N NA
24. Test Glass Break sensor(s) (all in sequence): INTRUSION alarm Y/N NA
25. Wait: INTRUSION return Y/N NA
26. Test fence sensor(s) (all in sequence): INTRUSION alarm Y/N NA
27. Wait: INTRUSION return Y/N NA
28. Test proximity sensor(s) (all in sequence): INTRUSION alarm Y/N NA
29. Wait: INTRUSION return Y/N NA
W911S8-19-R-0002 Attachment 13, TE12, ICIDS Performance Verification Test (PVT)
30. Test vibration sensor(s): INTRUSION alarm Y/N NA
31. Wait: INTRUSION return Y/N NA
32. Conducted IDS training for the building manager/POC Y/N NA
Name: Position: Date: .
Name: Position: Date: .
Name: Position: Date: .
33. Verify graphic map for each alarm point (provide accurate map) Y/N NA
34. Comments: _____________________________________________________________________________
By signing this form, you are attesting to the accuracy of the information contained in items 1 through 32 either by personal observation or by report of subordinate employee that personally observed the PVT.
Primary PSI:_________________________\___________________________Date:_____________
PRINT NAME SIGNATURE
USACE
PM/PE/QA:_________________________\___________________________Date:_____________
Prime Contractor
QA:_________________________\___________________________Date:_____________
Sub-contractor QA:_________________________\___________________________Date:_____________
W911S8-19-R-0002 Attachment 13, TE12, ICIDS Performance Verification Test (PVT)