Attachment_07,_TE6-FieldReport_w-CSO.pdf

PDF 2 MB Posted

Attached to
INTEGRATED COMMERCIAL INTRUSION DETECTION SYSTEM II AND IV (ICIDS II and ICIDS IV)
Solicitation number
W911S8-19-R-0002
Issued by

About this file

Attachment 07, TE6 - Field Report w-CSO

View the file

Other files

File Type Posted
Attachment_28,_Amendment_02,_W911S8-19-R-0002_Solicitation_A.pdf PDF
Questions_and_Response_14_Nov_18.pdf PDF
Attachment_24,_W91S8-19-R-0002_BlankPricingWorksheet_(CLIN_schedule).xlsx XLSX spreadsheet
Questions_and_Response_9_Nov_18.pdf PDF
Attachment_27,_Amendment_01,_W911S8-19-R-0002_Solicitation_A.pdf PDF
Attachment_26,_W91S8-19-R-0002_Historical_ICIDS_M&R.xlsx XLSX spreadsheet
Attachment_25,_W91S8-19-R-0002_LoadedLaborRateTable.xls XLS spreadsheet
Attachment_23,_W911S8-19-R-0002_Solicitatioin_A.pdf PDF
Attachment_02,_TE1-ICIDSCCTV_SOP.pdf PDF
Attachment_19,_TE18_-ICIDS_Account_Map.pdf PDF
Attachment_22,_TE21_-_AIE_LONG_TERM_BADGE_APPLICATION_FORM.PDF PDF
Attachment_13,_TE12-IDS_PerformanceVerificationTest_(PVT).pdf PDF
Attachment_15,_TE14-QUALITY_CONTROL_CHECK_SHEET.pdf PDF
Attachment_20,_TE19_-_New_Account_Activation_Request.pdf PDF
Attachment_01,_ICIDS-MMR-PWS_12SEP18.pdf PDF
Attachment_18,_TE17_-Deactivation.pdf PDF
Attachment_05,_TE4_-_ARMS_ROOM_TEST_LOG_-_MAR_-_2018.pdf PDF
Attachment_12,_TE11_MCA-ICIDS_IV-MaterialOrder.pdf PDF
Attachment_08,_TE7-ICIDSCatastrophicFailureReport.pdf PDF
Attachment_03,_TE2_-_ICIDS-DailyAlarmEventLog_example.pdf PDF
Attachment_04,_TE3_-_Open_Accounts_Report_(example).pdf PDF
Attachment_06,_TE5-_Contract_Service_Order.pdf PDF
Attachment_09,_TE8_-_MFR-ICIDS-PINUserPolicy-Oct17.pdf PDF
Attachment_21,_TE20_-_JBLM_Master_Worksheet.xlsx XLSX spreadsheet
Attachment_11,_TE10-MCA-ICIDS_II_MaterialOrder.pdf PDF
Attachment_14,_TE13-CCTV_Acceptance(PVT)Mstr.pdf PDF
Attachment_17,_TE16_-Activation_Checklist.pdf PDF
Attachment_10,_TE9_-_LMT_example.pdf PDF
W911S8-19-R-0002_Solicitatioin.pdf PDF
Attachment_16,_TE15-ICIDS&CCTV_Addition-Removal_Request.pdf PDF
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Date: 20 OCT 10 Job Title: YTC ASP IDS Troubleshooting

CS0: 2017-008

Technician: EFS

Arrived at YTC 0830 and checked in with Jason Kesselring at the MP station Arrived at the ASP at 0845 and started work at Yak1060 – Sporadic S-fault on the BMS. The loop metered fine however the II zim was extremely out of whack so I replaced it. Able to arm and disarm with no more sfaults on this account while I was on site today.

Yak1080 – Grid tamper. I metered the loop and it was around 1055 ohms. It was in alarm when I got there so I checked on the wiring connections in the panel as well as the J boxes at the two lower grids and tightened all the connections. I was able to get it down to 1025 ohms which cleared the alarm. We might have to put in a potentiometer at a later date.

No more sfaults on this account while I was on site today.

Yak1054 – Grid tamper. I couldn’t replicate this issue. However Gene Bell (ASP supervisor) informed me that as per John Sly, Yak1054 and Yak1064 are no longer licensable so they can’t store ammo in them anymore. I recommend that they deactivate those two accounts to minimize the false alarms.

Yak1095- Users unable to arm/disarm, having to call and get it force closed/opened daily. Multiple issues on this one.

The Kud8 was no longer working so I replaced it with a new Kud8. The KP ribbon cable was damaged so I replaced it. I realized that the front end was receiving any alarm activity from this account. Jonathan worked with me and I installed a new PB2000. We were able to get comms up but the first RIM card wasn’t forwarding alarm info. I replaced that RIM. I also checked all wiring inside the RADC and discovered that the 2 Wire copper for comms coming into the TELCO had a broken lead on the transmit side. I fixed that and we were able to get alarms to the front end in a timely manner. I also found that PIM2 was stuck in alarm. I couldn’t clear that alarm. It will take a 10’ or 12’ ladder and a return trip to work on that. Criss okayed me to 1k that point for now. He wants us to get a price for replacing that PIM, it’s an intrinsically safe one, Sentrol if I remember correctly. This account could really use a couple people to go through it thoroughly. I ran out of time today plus I wasn’t as prepared as I wanted to be (no tall ladder), but I noticed that with all the hands that have been in that account that a valid point on RIM1 had a point on the front end spared out. It has a valid device wired to it and to my knowledge shouldn’t be spared out. The 2nd RIM card has one device wired to it, which I believe was a PIM at once point, but the front end shows it as a spare.

I filled out all the CSOs and left copies at the MP station. Jason Kesselring wasn’t there so I checked out with the desk.